Flowm
Flowm
Page 3 of 30
Page 4 of 30
A.0 Recommended Tools
Page 5 of 30
1.0 Mechanical Installation
1.1 Sensor Installation
Sensor needs to be full at all times. Vertical Pipes
Page 6 of 30
1.2 Sensor Prom Installation.
1 2 3 4
1
Sensor shipped with Sensor-Prom installed in junction Box.
2
Remove SensorProm before potting terminal box’
3
Make sure Sensor-Prom details match details of Magflow Sensor, Cal Factor & Serial Number
4
Install Sensor-Prom into transmitter REMOTE junction box (as shown).
Page 7 of 30
2.0 Wire Connections
2.1 Wire Connections for Compact Sensor.
Page 8 of 30
2.3 Cable Specifications
Page 9 of 30
2.4 Examples of Good and Bad Installations.
Page 10 of 30
2.5 Overview of Transmitter Connections
Electrode connections – 82, 0, 83 standard configuration with No empty pipe detection (EPD).
Terminals 81 and 84 used for empty pipe detection, and can only be used with Siemens supplied double
screen cable. Screen cable at sensor end only. Keep unscreened lengths to a maximum of 50mm.
Coil connections - 85 – 86 standard screened cable can be used. Connect screen to earth and sensor
and transmitter. Keep unscreened lengths to a maximum of 50mm to prevent corruption of electrode
signal.
Page 11 of 30
3.0 Parameters
Page 12 of 30
Page 13 of 30
3.1 Basic Settings
Page 14 of 30
3.2 Output Parameters
Current Output
NOTE:
Current Output - “Time Constant” effects response time of unit, (Mag 6000/5000) not just the
mA output.
Time Constant can only be altered if mA is set to ON.
If the output terminals (31, 32) are not connected , Turn off mA output after adjusting “Time
Constant”, this will prevent P42 alarm. May require power re-cycle to clear alarm.
Page 15 of 30
3.3 Service Menu
Page 16 of 30
3.3 Service Menu Continued
Page 17 of 30
3.4 Sensor Characteristics
Page 18 of 30
4.0 Fault Finding.
2 menus are available in service and operator menus for registration of information and errors
1. Error pending
2. Status log
Page 19 of 30
4.1 Error Codes Continued..
Page 20 of 30
4.2 Sensor Fault Finding. (Sensor Full)
1 Check coil resistance with Remove remote cables and Faulty Coil Cable Replace
a multimeter: recheck coil resistance with and recheck
R85-86 Nominal value: multimeter:
see table R85-86 Nominal value:
see table
2
Remove cables and re-
Check coil insulation with Faulty Coil Cable Replace
Check coil insulation with
a megger (500 V) and recheck
a megger (500 V)
R85 or 86 – GND
R85 or 86 – GND
Nominal value: Infinite
Nominal value: Infinite
resistance
resistance
Check electrode circuit Remove cable and re- Faulty Electrodes Cable
with a moving-coil check electrode circuit Replace and recheck
instrument without
amplifier. Note: If Both Values are
R82-0 > 500 kohm,
Nominal value: Dirty Electrodes
5 – 500 kohm Empty Pipe
R83-0
Nominal value:
5 – 500 kohm
Faulty Sensor check
WARRENTY
Sensor Healthy,
Proceed with Verification
Page 21 of 30
4.3 Sensor Fault Finding. (Sensor Empty)
Check coil resistance with Remove remote cables and Faulty Coil Cable Replace
a multimeter: recheck coil resistance with and recheck
R85-86 Nominal value: multimeter:
see table R85-86 Nominal value:
see table
Page 22 of 30
4.4 Coil Resistance Table (Connections 85 & 86)
1 ) On MAG 1100 DN 15 produced as from May 1999 the coil resistance must be 86 ohm, +8/ 4 ohm.
All resistance values are at 20 °C.
The resistance changes proportionally 0.4% / °C.
Page 23 of 30
5.0 Sitrans FM Magflo Verificator Important Instructions
BEFORE VERIFICATION
Steps 1 to 5 below MUST be completed before verification is carried out
1. Make sure the Sitrans FM sensor is full of liquid and the flow meter is
operating.
2. Switch off the power to the flow meter to be verified.
3. Remove the transmitter (Mag5000 or Mag6000).
4. Ensure sensor and transmitter are correctly earthed.
5. Insulation Check – Coils.
Using an insulation tester (megger), with 500v insulation voltage, check for
correct insulation between the electromagnetic coils and ground.
Measure the resistance between terminal 85 and ground, then between
terminal 86 and ground.
The resistance should be infinite (greater than 500 Megohms).
If the insulation test fails, DO NOT connect the Verificator to the flow meter.
Warning: Connecting to a flow meter which has failed insulation will
damage the Verificator.
Typical repair cost: £2000.00 to £3000.00.
DURING VERIFICATION
Refer to the Verificator manual for detailed information about the verification
process and diagnostic messages.
Page 24 of 30
Important:
Do not press the keypad or change any settings on the transmitter during
the verification process.
Never switch off power to the Verificator during a test, unless the test has
been stopped (by pressing the “Esc” key).
AFTER VERIFICATION
15. When the verification is finished press “Go” to return to the main menu and
automatically store the data.
16. Turn off the Verificator power switch.
17. Switch off the power to the Sitrans FM flow meter.
18. Remove the adaptor and re-fit the transmitter.
19. Switch on the power to the Sitrans FM flow meter.
Warning
Disconnection of the transmitter or the Verificator adaptor during a test
may damage the Sensorprom module, the transmitter or the Verificator.
In normal use the Verificator power cable (maximum 2.5m) should be used
in a workshop environment when downloading data to a PC following site
verifications.
Page 25 of 30
5.1 Verificator – Check List
Coil circuit (connections 85 & 86) must be Megger tested with reference to earth
before using Verificator. Failure to comply too this procedure can result in damage to
Verifcator. If in doubt please contact Siemens.
There are a number of possible reasons why the Verificator may fail the Insulation test on a Magflo flowmeter.
The most common reasons are listed below.
If possible try a signal converter compact mounted in order to eliminate cable problems. From our experience
incorrect cable installation is the main cause of Insulation failure when using the Verificator.
Page 26 of 30
6.0 Appendix.
Action Passed
Check power connection for the Mag 6000, including earth connection
Check Earth connection to bottom plate
Ensure Sensor Prom is installed and serial number matches serial number on
junction box
Ensure Molded plug (2 pins) with indication 85 & 86 is connected to PCB with
corresponding number.
Ensure Molded plug (3 pins) with indication 82, 83 & 0 is connected to PCB with
corresponding number.
Insert Communication card into base of Mag 6000 transmitter if required.
Test coil insulation at 500 Volts, measure 85, to earth, and 86 to earth.
With Moving coil meter test electrode circuit (see page xx)
Fit Mag 6000 transmitter and tighten 2 fixing screws.
Turn on power and check for and errors.
Action Passed
Check power connection the Mag 6000, including earth connection
Remove Sensor Prom from sensor junction box
Ensure Sensor Prom is installed in remote transmitter and serial number matches
serial number on junction box of connected sensor
Fit white terminal block to metal plate in sensor using x2 fixing screws.
Fix Molded Plug into white terminal block in sensor ensuring all screw as tight
Using recommended cable make wire connections in accordance with page xx.
Ensure unscreened lengths in sensor and transmitter are less than 50mm.
Insert Communication card into base of Mag 6000 transmitter if required.
Test coil insulation at 500 Volts, measure 85, to earth, and 86 to earth.
With Moving coil meter test electrode circuit (see page xx)
Fit Mag 6000 transmitter and tighten 2 fixing screws.
Turn on power and check for and errors.
Page 27 of 30
6.3 Sensor Operating Range
Ideal flow velocities between 0.5 and 5 m/sec meter will operate up to 10m/sec.
Page 28 of 30
6.4 Cable Kit Part Numbers
Cabling:
Cable kit with standard coil cable, 3 x 1.5 mm2/18 gage with shield PVC and electrode cable
double shielded, 3 x 0.25mm2 (-30 to +70 deg C)
Page 29 of 30
Call us on +44 (0)1449 674 986
Or visit www.pisales.co.uk