Modeling
Modeling
FIRE PROTECTION
Fire
Modeling page 9
ALSO:
19 EVALUATING COMPUTER
FIRE MODELS
46 BRIEFING ON THE
WORLD TRADE CENTER
ATTACKS
No one in the life safety consulting profession offers more
diverse and exciting career challenges than The RJA Group.
With our reputation as a leader and project involvement all
over the world, we’ll challenge your abilities every day while
we give you the opportunity to grow and develop.
Open your Our disciplines range from fire engineering (Rolf Jensen &
Associates, Inc.) and security (Sako & Associates, Inc.) to
If you have an open mind about how far you’d like to take
www.sfpe.org 1
Naturally...
Nontoxic. Noncorrosive. Unregulated.
Unrestricted. Chemical-free.
Safe to breathe.
www.ansul.com
viewpoint
PERFORMANCE-
the ‘Life Safety Evaluation,’ there should
be a factor of safety, especially in view
of the incomplete technical grasp of
both egress and fire issues at the pre-
sent. For example, in a conservative
BASED DESIGNS
approach, the ‘time available’ should be
at least twice as long as the ‘time
required.’” Despite this well-documented
recommendation, one of the engineers
who participated in a design we
reviewed stated, “Jake Paul’s method
(SFPE Handbook) of doubling the occu-
By Joseph M. Fleming I have reviewed many “deterministic” pant egress time is not commonly
timed egress analyses. A key component accepted or used for fire engineering
of these analyses is the selection of ten- analysis. For almost any engineering
I n Response to “Lessons Learned When significant defects are identi- importance of simplicity over complex-
from a Carbon Dioxide System fied, many manufacturers issue recall ity and of mechanical over electronic
Accident,” Issue No. 12. notices to ensure that not only is the schemes where robustness is of top
consumer made aware of the defect,
priority. Designers of water-based
Having been at the INEEL for about but also that the defect is “correct-
extinguishment systems have known
two years, talked and worked with per- ed.” Standards dealing with fire sup-
the value of indicating valves for over
sonnel involved or familiar with the pression agent design concentra-
a century, and it is still the most
incident, and toured the area where the tions, which, if exceeded, could be
tragic event occurred, I have learned a hazardous to occupants, should robust way of shutting off a system
few “lessons” that were not focused on include provisions that address prod- and having its status be unambiguous-
in the article. Here they are: uct defects. These provisions should ly indicated. Designers, OSHA, and the
1. Carbon dioxide (CO2) at minimum require manufacturers to immediate- NFPA 12 committee should consider
design concentrations required to ly notify users of the defective prod- the wisdom that a heat-seeking missile
suppress fires is lethal to humans. uct and initiate recalls when it is may prove not to be more reliable
Given its inherent hazard, it should determined that the defect is suffi- than a fly swatter in swatting flies. Get
not be used in areas subject to occu- ciently hazardous to endanger mechanical indicating valves in there
pancy – EXCEPT when the risk of human life. now, and don’t accept non-robust
fire is documented to be greater than 4. Standards dealing with fire suppres- “modern” substitutions!
the risk to personnel AND there are sion agent design concentrations,
no viable suppression alternatives. which, if exceeded, could be haz- Vytenis Babrauskas, Ph.D.
When considering the recent ardous to occupants, should include President,
advances our industry has made in provisions that address system config- Fire Science and Technology, Inc.
fire suppression agents (notably urations. System configurations where
water mist and Halon alternatives),
no situations which meet the excep-
tion condition come to mind.
the failure of a single component
could result in hazardous concentra-
tions to occupants should be prohib-
I n the Fall 2001 issue (No. 12) of
Fire Protection Engineering, the arti-
cle “UL 2360, A New Test for Wet
2. When it is evident that adherence to ited (some “approved” gaseous agent Bench Plastics”1 by Jane Lataille con-
a national consensus standard is not reserve manifolds would not meet tains a number of inaccuracies and
sufficient to preclude a fatal accident, this provision). omissions that could misinform read-
that standard must be evaluated to A final thought. As fire protection ers about the state of flammability
determine its adequacy. Immediately engineers, we need to be continually testing for plastics used in semicon-
following the tragic event, NFPA 12, scrutinizing our engineering approach ductor clean rooms.
Standard on Carbon Dioxide to the fire problem. To quote one of my Ms. Lataille notes in the article that
Extinguishing Systems (2000 edition)1, engineers, just because “we can” do Factory Mutual Research introduced
was changed to require the addition something doesn’t mean “we should.” fire tests to determine the acceptability
of an isolation valve to enable the of plastics for use in the semiconduc-
system to be physically isolated. Stephen Thorne, P.E. tor industry. These tests, known as the
Additionally, the appendix guidance INEEL Fire Marshal Factory Mutual Research Test Standard
in NFPA 72 (1999 edition)2 was modi- The opinions expressed above are my 49102 (FM4910), were released in 1997
fied to suggest the use of devices own and do not necessarily reflect and included both small-scale tests
which detect the flow of agent and those of my employer. and an intermediate-scale (parallel
your spouse be able to afford your for yourself and your spouse, or High-Limit Accident Plan
family’s current lifestyle if something Comprehensive HealthCare coverage for Member Assistance Plan
happened to you? Will you be around to your whole family, the SFPE-sponsored
Program is your one-stop source for Catastrophe Major Medical Plan
put your kids through college? If not,
what then? custom-tailored protection for what Medicare Supplement Plans
matters most in your life. And each plan
Unfortunately, it’s not always is available to members like you at
Comprehensive HealthCare Plan
possible to—like Thomas Edison— SFPE group-negotiated rates that fit Dental Discount Plan
invent your own instant solutions to your budget.
what keeps you up at night. Cancer Expense Plan
Rest easy.... The SFPE-sponsored
SFPE can help. As an SFPE member, Insurance Program looks out for you.
you can choose from nine quality
SFPE-sponsored insurance plans to help
safeguard you and your family.
Sponsored by:
For FREE information about any of the SFPE-sponsored Plans, call toll free 1-800-424-9883.
The Term Life, High-Limit Accident and Comprehensive HealthCare Insurance Plans are underwritten by New York Life Insurance Company, 51 Madison Avenue, New York, NY 10010. The Catastrophe
Major Medical and Dental Discount Plans are underwritten by The United States Life Insurance Company in the City of New York, Member American General Financial Group. The Member Assistance
Plan is underwritten by Unum Life Insurance Company of America. The Medicare Supplement and Cancer Expense Insurance Plans are underwritten by Monumental Life Insurance Company.
677-01
From PHLOGISTON to
COMPUTATIONAL
FLUID
DYNAMICS
By Harold E. Nelson, P.E.
D
uring the last decade, fire
models have had a major
influence on applied fire pro-
tection engineering. Modern compart-
ment fire models solve fire dynamics
equations that have been only very
recently seriously investigated. The
information developed as a result of
these investigations has helped transfer
fire dynamics methods from the
research realm to field application. Fire
protection engineering applications
now range from straightforward alge-
braic equations, such as those for
describing fire plumes, to complex
computer models that solve complex
simultaneous fire dynamics equations
iteratively.
Over the past 50 years, fire dynamics
information was derived from scientific
principles abstracted from other disci-
plines. The basis for the fire dynamics
in compartment fire models lies in the
physics relationships inherent in com-
bustion, such as heat balance and con-
servation equations.
All of combustion science rests at
least in part on Lavoisier’s discovery in
the late 18th century that combustion
involves reaction with the element oxy-
gen. This article reviews the steps that
brought fire dynamics from there to the
models of today.
What’s more, the FireFinder offers a very-low life-cycle cost. Learn how this big-screen system can
bring you big savings and big peace-of-mind. Call Siemens Building Technologies, Fire Safety Division
at 973-593-2600 or visit cerbpyro.com
Bldg.
K-14 K-25 K-22
Height (Ft.) Pressure Flow Pressure Flow Pressure Flow
30' 50 psi 99 gpm 20 psi 113 gpm 25 psi 112 gpm
35' 75psi 121 gpm 30 psi 138 gpm 35 psi 133 gpm
40' 75 psi 121 gpm 40 psi 159 gpm 45 psi 150 gpm
45' w/ 35' stor. 90 psi* 133 gpm* 50 psi 178 gpm 50 psi 158 gpm
45' w/ 40' stor. 90 psi* 133 gpm* 50 psi 178 gpm 50 psi 158 gpm
* K.14 Must Include one row of in-rack sprinklers.
1.800.431.1588
www.reliablesprinkler.com
Corporate Offices United Kingdom Office China Office
Tel: 9.14.668.3470 Tel: 441.372.728899 Tel: 010.6489.3998
E V A L U AT I N G
E volutions in fire science and technology and computing What Is a Computer Fire Model?
have resulted in a growing number of powerful mathe- A fire model is a physical or mathematical representation
matical models that are used in support of fire safety engi- of burning or other processes associated with fires.1
neering design and analysis. Good engineering practice requires Mathematical models range from relatively simple formulae
that a statement of uncertainty accompany all computer fire that can be solved analytically to extensive hybrid sets of dif-
model calculations. This article summarizes a series of standard ferential and algebraic equations that must be solved numeri-
guides that help assess uncertainties in computer fire models. It cally on a computer. Software to accomplish the latter is
also discusses application of the guides by SFPE and others. referred to as a computer fire model.
Introducing
SPEC 1 FIRE
A Family of MultiCandela AppliancesSM
™
FEATURES
• Field Selectable Candela Settings of: 15, 30, 75 or 110cd • Satisfies Virtually ALL
Requirements for Indoor, Wall Mount Applications • Both Sync and Non Sync In ONE
Appliance • Approvals: UL 1971; New York City (MEA), California State Fire Marshall (CSFM),
Factory Mutual (FM), Chicago (BFP) and ULC • ADA / NFPA / ANSI Compliant • Synchronize
with Wheelock SM, DSM Sync Modules or Wheelock’s PS-12/24-8 Power Supply with Built-In
Sync Protocol • Backward Compatible With Other Wheelock Appliances
TM enabled
E D WAR D S S Y S T E M S T E C H N O L O G Y
w w w. A n a L A S E R . c o m
Active detection technology that’s thousands of times more sensitive than
traditional smoke detectors. Selectable sensitivity for installation flexibility.
Networking for up to 127 devices in one or multiple locations. Engineered
for reliability from Fenwal, mission-critical specialists for more than 30 years.
FENWAL PROTECTION SYSTEMS 400 Main Street • Ashland, MA 01721 • (508) 881-2000 Protection Systems
cations. The trouble with many types of
engineering software is that it is packed
with so many features that the learning
curve for even the simplest of problems
is too steep. Fire modeling, especially
field modeling, will advance only if
there is a large enough core of users to
justify the time and expense of develop-
ing and maintaining a very complex
computer code. Sustaining that core of
users means making the software acces-
sible to a wide audience.
Not only must the software be easy to
use, but the calculations must run as fast
as possible. Veteran CFD practitioners do
not find week-long calculations unusual,
but fire protection engineers who only
have experience with zone models find
it intolerable. Faster computers have
soothed some, but the demands for
more-detailed calculations often negate
gains made in computer speed. To keep
up with demand, the fire models will
need to exploit advances in computer
science and numerical methods that go
beyond just faster chips. Parallel process-
ing is becoming more of a reality in cer-
tain fields, but still is a few years away
for those using the current generation of
personal computers. However, in the
not-too-distant future, relatively inexpen-
sive desktop computers will come with
2, 4, or 8 processors, plus the necessary
hardware and software to make these
chips work together effectively. Also,
techniques to better distribute the grid
cells will allow for greater flexibility in
the design of simulations. One technique
that is used by many CFD packages (but
not yet FDS) is called multiblocking. An
example of how this would work is a
house in which every room has its own
numerical grid. Those rooms requiring
more spatial resolution could have finer
grids, those that don’t need it could
remain coarsely gridded. The numerical
algorithms presently used in single-block
codes will not change except there
needs to be extra logic built into the
algorithms so that information is proper-
ly communicated across block interfaces.
Such a technique is perfect for fire mod-
els because most simulations investigate
buildings with relatively simple, rectan-
gular geometries. Contrast this with the
aerospace industry where simulations are
performed on very complicated body
shapes. These models utilize numerical FIGURE 7. Several snapshots of a fire spreading through a townhouse. The fire
grids that are far more sophisticated and originates in the kitchen area (lower left), and eventually spreads throughout the house.
difficult to construct than those needed The front door (right) is assumed to be open, as are the windows on the second level.
for fire models.
SENSITIVITY
AMBIENT
ACCLIMATE™ reduces nuisance alarms. Faced with an increase in “noise,” NOISE
such as dust or fibers, ACCLIMATE will increase its alarm level. When the
disturbance subsides, the unit becomes more sensitive. TIME
INTRODUCTION
The
builder knows what tools are available
RIGHT TOOL
for different tasks, knows how to
properly use each tool, and under-
stands which tool is appropriate for
the task at hand. If not qualified for a
particular task, the master builder
either develops the skills to perform
the necessary tasks to complete the
for the
project, or, more likely, hires another
professional with the required skills
and expertise.
The practice of virtually any trade or
profession demands a similar
approach. We all have a limited set of
JOB
skills and expertise. Consequently, we
must all understand our limitations as
well as our capabilities. This demands
that we understand the appropriate
uses and limitations of the tools that
are available to us as well as our own
competencies in applying the available
tools. Where our competencies are
lacking, we need to either enhance
our skills or obtain the services of One of the first things the fire protec- • The calculation clearly demon-
people with the required skills. tion engineer must do before perform- strates achievement of the objec-
In the field of fire protection engi- ing a quantitative fire hazard analysis is tive performance criteria;
neering, the “toolbox” of models and decide what is the right tool for the job. • The calculation does not clearly
calculations available for quantitative demonstrate either achievement of
fire hazard analysis has expanded WHY FIRE MODELING? or failure to achieve the objective
greatly over the past two decades. We performance criteria;
have gone from “slide rule estimates of All of the tools discussed in this article • The calculation clearly demon-
fire growth”1 and other hand calcula- permit the calculation of one or more strates failure to achieve the objec-
tions and correlations embodied in aspects of enclosure fire dynamics. It is tive performance criteria.
many chapters of the SFPE Handbook important to keep sight of the objectives It is for this reason that calculation
of Fire Protection Engineering,2 through of such analyses. We perform calcula- methods ranging from “back-of-the-
computer-based single- and multiroom tions and other analyses to evaluate the envelope” hand calculations through
two-zone fire models,3, 4 to emerging adequacy of a proposed or existing the most sophisticated computer-based
highly detailed computational fluid component, system, or process to fulfill CFD models all have a place in the fire
dynamics (CFD) models.5, 6 its functions. In other words, we per- protection engineering toolbox. A rela-
Spurred by the ever-increasing form calculations to support design deci- tively simple hand calculation may
processor speeds and memory capaci- sions. As noted in the SFPE Guide to clearly demonstrate the achievement of,
ties of desktop computers, it is now Performance-Based Fire Protection or the failure to achieve, a specified
practical to perform detailed fire Analysis and Design of Buildings,7 the performance criterion, in which case
dynamics calculations and visualize first steps in the process involve the use of a more powerful tool would be
results in ways that were virtually establishment of fire safety goals, objec- unnecessary as well as uneconomical.
unimaginable only a few years ago. tives, and performance criteria. Ideally, we would like to think that the
While these ever-increasing computa- Once the performance criteria are more powerful the tool used for an
tional capabilities are valuable, they are established, different calculations can analysis, the smaller would be the
not needed for every job. Given the be performed to determine whether the uncertain middle area of the possible
enormous computational needs of specified performance criteria will be outcomes. The perfect analytical tool
these sophisticated calculations, it achieved by a proposed design. Some would be one that eliminates the
makes sense to make use of computa- evaluations may involve only a few uncertain middle area, such that the
tionally less-intensive tools where pos- simple calculations, while others, such results of a calculation would either
sible and save the more-detailed, com- as CFD analyses, may require millions demonstrate achievement of the objec-
putationally intensive calculations for or even billions of calculations. In gen- tive performance criteria or the failure
those tasks where the simpler tools are eral, there are three possible outcomes to achieve it. This concept is illustrated
inadequate. for a calculation within this context: in Figure 1. Unfortunately, the perfect
2 DiNenno, P., Editor-in-Chief, SFPE Handbook of Fire Protection 10 Cooper, L. Y., “Mathematical Model for Estimating Available Safe
Engineering, 2nd edition, National Fire Protection Association, Egress Time in Fires,” Fire and Materials, Vol. 6, No. 3-4, 135-144,
1995. September/December 1982.
3 Nelson, H. E., “FPETOOL: Fire Protection Engineering Tools for 11 Baum, H. “Large Eddy Simulations of Fires,” Fire Protection
Hazard Estimation,” NISTIR 4380, National Institute of Standards Engineering, Society of Fire Protection Engineers, No. 6, Spring 2000.
and Technology, Gaithersburg, MD, October 1990. 12 Ho, V., Siu, N., Apostolakis, G., “COMPBRN III—A Fire Hazard
4 Peacock, R. D., Forney, G. P., Reneke, P. A., Portier, R. W., Jones, Model for Risk Analysis,” Fire Safety Journal, Vol. 13, No. 2-3,
W. W., “CFAST, The Consolidated Model of Fire Growth and 137-154, 1988.
Smoke Transport,” NIST TN 1299, National Institute of Standards 13 Stroup, D. W., Evans, D. D., “Use of Computer Fire Models for
and Technology, Gaithersburg, MD, February 1993. Analyzing Thermal Detector Spacing,” Fire Safety Journal, Vol. 14,
5 McGrattan, K. B., Baum, H. R., Rehm, R. G., Hamins, A., Forney, 33-45, 1988.
G. P., “Fire Dynamics Simulator: Technical Reference Guide,” 14 Dungan, K. W., “Practical Applications of Risk-Based Technologies,”
NISTIR 6467, National Institute of Standards and Technology, Fire Protection Engineering, Society of Fire Protection Engineers,
Gaithersburg, MD, January 2000. No. 10, Spring 2001.
WORLD
Craig Gibbons – Structures, Hong Kong
Dick Custer – Fire and Forensics, Boston
Faith Wainwright – Structures, London
Jim Pinzari – Risk/Business Continuity, Boston
Jim Quiter – Fire, San Francisco
John MacArthur – Structures, New York
Leo Argiris – Structures, New York
Michael Willford – Structures, London
Richard Hough – Structures, Sydney
This brief was prepared for a broad audience
inside and outside of Arup. Thus, some material will
be familiar to readers of this magazine. However, the
brief described many of the factors that need to be
TRADE
considered when evaluating how a building responds
to such an extreme event. Accordingly, it forms one
part of a broader risk assessment designed to advise
clients on individual risk, whether in a new building
or an existing one. Prevention measures designed to
reduce the probability of a terrorist attack will be
CENTER
taken into account in such an assessment.
Attacks
Attacks
INTRODUCTION
Neighboring buildings
The twin towers were part of the combination of the impact loads from Preliminary analysis of what led to
World Trade Center complex of seven the collapse of One and Two WTC, the total collapse of One and Two
buildings. the tremendous fire that ensued, and WTC
In addition to these high-rise build- foundations being affected by the col- The initial impact destroyed many
ings, there was a 47-story high-rise lapsing towers. Specifics of the col- columns and more than one floor. How
building (Seven WTC), a 22-story high- lapse mechanism are being analyzed much was damaged may never be
rise building (Marriott hotel), two by many parties. known, but the impact itself did not
9-story buildings, and one 8-story build- Falling debris also damaged build- cause the towers to collapse. The build-
ing. Excluding the hotel, most of the ings beyond the World Trade Center ings remained standing long enough to
occupied space within the buildings complex. An assessment of these allow many people to escape.
was dedicated for office use. All the buildings was undertaken during the The initial impact probably removed
buildings, except for Seven WTC, were week of September 17, by SEAoNY some columns and significantly weak-
constructed over a plaza area that con- (Structural Engineers Association of ened many others. Deformed, and
tained a shopping mall, four under- NY) and is available on the SEAoNY probably unbraced over two or more
ground levels of public parking, and Web site at www.seaony.org. The floors, these columns would also have
two utility levels. assessment was based on an ATC-20 been subjected to additional load from
The entire center contained approxi- Post-Seismic Building Assessment. The damaged floors and debris. The spread-
mately 1.25 million square meters (13.5 affected perimeter buildings contain ing fire would have continued to weak-
million square feet) of rentable space approximately 1.5 million square en the structure, most likely leading to
including .18 million square meters (2 meters (16 million square feet) of a collapse under vertical load.
million square feet) in Seven WTC. space. In all, more than 30% of down- The aircraft were heavily laden with
The collapse of these neighboring town Manhattan office space has been jet fuel, having just taken off from
buildings was probably due to the affected. Boston en route to Los Angeles. The
Structure
The Towers were steel framed, 110
stories high, and square on plan. The
buildings were designed by Skilling,
Helle, Christianson, Robertson, which
was the structural engineering firm of
record for the World Trade Center com-
plex, and completed in phases starting
in 1970. One WTC was 417.0 meters THE WORLD TRADE CENTER
(1368') tall, and Two WTC was 415.1
meters (1362') tall. Each 110-story tower
had a floor plate 637 x 637 meters (209' (BOCA) when developing designs. The
by 209'). The central core in each steel frame had been clad in fire spray.
building was 26.2 x 42.3 meters (86' x Asbestos-based spray had been used ini-
139'), constructed with steel columns tially in the building, but later changed
and lightweight drywall for infill. to a nonasbestos material. Further specif-
Around the perimeter of the build- ics, including which structural members
ings, 356 mm (14") steel box columns were treated and to what level of fire
were spaced at 1 meter (3'-3") on cen- resistance, are still being determined.
ter, with 1.2 meters (48") deep plate
girder spandrels at each floor. At the Blast resistance
third level, the columns transitioned in One WTC had already survived an
an arch-like formation to a 3.05 meter explosion in February 1993 when a
(10'-0") spacing for the lower story. rental truck packed with explosives was TYPICAL FLOOR PLATE
Floors were supported by steel trusses detonated in basement level B2. That
spanning 18.3 meters (60'-0") from the bomb blew out one section of a north
core to the perimeter wall on each side tower cross-brace between two of the
of the building. perimeter columns. The blast ripped buildings, incorporating specific mea-
The building perimeter structure was out sections of three structural slabs in sures intended to address lessons
the key element in the performance of the basement levels, but did little dam- learned. Because building and fire
the building. In addition to taking verti- age to the columns. codes do not typically consider deliber-
cal gravity loads, it also resisted all hor- According to one of the original ate, willful attacks, such as arson or ter-
izontal loads by framing action designers, the towers were originally rorism, these events have not played a
between the close-centered columns designed to take the impact of a significant role in code development.
and the spandrel beams, such that the Boeing 707. A member of the original The current code-based design
perimeter structure acted as a pierced design team has clarified recently that approach on its own is inadequate for
tube in resisting loads. this addressed impact only and not the addressing the question “how would
Vertical structure inside the building consequences of a jet-fuel fire. buildings perform under such an
supported gravity loads only. attack?” However, it is possible to look
THE QUESTIONS at any building on a case-by-case basis.
Fire protection To inform future design, perhaps it
The World Trade Center was devel- How would our current buildings may be better to turn the question
oped and constructed by the Port fare under such an attack? around – “What are the implications for
Authority of New York and New Jersey, The answer is not simple. Structures design if the building were required to
a self-supporting agency of the two are designed to building and fire codes, remain standing for longer after such
states. Although the Port Authority has and these documents reflect our soci- an extreme event?” This is addressed
not adopted any specific fire safety ety’s tolerance of risk from fire, earth- below.
code, it considers the requirements quake, floods, and a host of other haz-
developed by the National Fire ards, and establish the minimum levels Is this a question just for tall
Protection Association (NFPA), New of safety. Historically, building and fire buildings?
York City, and the Building Officials and codes have evolved in response to fire The World Trade Center’s promi-
Code Administrators International and other events that have affected nence and symbolism must have been
&
SAMPLES Watts ACV Has It Now!
CALL Whether you need UL-Listed Pressure Reducing
Valves, Factory Mutual System approved and
800-873-0894 UL-Listed Fire Pump Relief Valves, Factory Mutual
System approved Fire Pump Suction Control Valves
OR VISIT OUR
or UL-Listed Pneumatic, Hydraulic, or Electronically
WEBSITE @ Actuated Deluge valves, Watts ACV has them in
www.decoshield.com We have been serving the fire sprin- sizes from 3” through 10”, in globe or angle pattern.
kler retrofit industry for more than ten For more detailed information, call us at:1-713-943-0688
years. Our system is clean, attractive, or visit our website at www.wattsacv.com.
paintable, durable, tamper-resistant,
economical and quick to install. That
is why we are the #1 choice for retro-
fitting all types of buildings.
Sprinklers • Secure
Fire protection by automatic sprin- • Attractive
klers assumes that there will be water
available at a sufficient pressure to
121 E. Burbank Ave. • Versatile
Janesville, WI 53546
deliver a spray of water to the fire area. 800/800-3213; Fax: 608/757-1452 • Economical
Sprinkler systems are not typically
designed to support water flow from
E-mail: [email protected] • Durable
www.soffisteel.com
all sprinklers simultaneously, as the
water demand could be enormous and
is typically not needed. The intent is
that the water supply system provides
only enough water for a specific
design area, with a certain number of
sprinklers at the most hydraulically
remote location. The density and
Fire Protection Reference Guide engineering and technical services to national and international clients.
Career growth opportunities are available for entry-level and senior-level
fire protection engineers, design professionals, and code consultants.
Viking has released a new color product Opportunities available in the Boston, Chicago, Charlotte, Dallas, Denver, Las
brochure entitled, “Your Fire Protection Vegas, Los Angeles, Miami, Phoenix, San Diego, San Francisco, and
Solutions Partner.” A reference guide for Washington, DC, areas. There is also a need for experienced loss control
fire protection specialists, it contains draw- engineers countrywide. We offer a competitive salary/benefits package. EOE
ings of sprinkler systems suitable for train-
ing. The sprinkler section contains a full Send résumé to:
G. Johnson
range of products, with photographs and Schirmer Engineering Corporation
technical reference tables. Other areas cov- 707 Lake Cook Road
ered include foam and foam equipment Deerfield, IL 60015-4997
and other related fire protection products. Fax: 847.272.2365
www.vikingcorp.com e-mail: [email protected]
—Viking Corp.
UPCOMING EVENTS
4th International Conference on Performance-Based
UPCOMING EVENTS
Codes and Fire Safety Design Methods
Melbourne, Australia
Info: www.sfpe.org
February 5-6, 2002
May 19-23, 2002
Flame Retardants 2002
NFPA World Fire Safety Congress and Exposition
London, England
Minneapolis, MN
Info: www.intercomm.dial.pipex.com/fr2002cfp.htm Info: www.nfpa.org
March 18-19, 2002 June 16-21, 2002
Structures in Fire The 75th International symposium on Fire Safety Science
University of Canterbury, Worcester Polytechnic Institute
Christchurch, New Zealand Worcester, Massachusetts, USA
Info: www.civil.canterbury.ac.nz Info: www.iafss.org
Society
of Fire Protection
Engineers
An Invitation to Join
What is The Society of Fire Protection Engineers (SFPE)?
SFPE, established in 1950, is a growing association of professionals involved in advancing the science
and practice of fire protection engineering and fostering fire protection engineering education.
What are the benefits of SFPE membership?
The Society will provide you with many new opportunities for professional advancement, education,
and networking. The specific benefits members receive are:
Free access to SFPE’s periodicals
This includes:
▲ Fire Protection Engineering magazine. ▲ The peer-reviewed Journal
▲ SFPE Today - Our bimonthly Society newsletter. of Fire Protection Engineering.
Substantial discounts on continuing education
This includes:
▲ Technical symposia on current fire protection issues.
▲ International conferences on state-of-the-art applications of fire protection engineering.
▲ Short courses and seminars offering hands-on instruction.
▲ Discounts on fire-related publications.
I’m interested in learning more about joining SFPE. Please send me additional information.
Name Title
Company/Organization
Country
BENEFACTORS
Rolf Jensen & Associates, Inc.
PATRONS
Code Consultants, Inc.
Solve the following equation for x: Edwards Systems Technology
Hughes Associates, Inc.
The Reliable Automatic Sprinkler Company
( x 2 − 9 x + 20 )
( )
Schirmer Engineering Corporation
x 2
− 5 x + 5 =1 MEMBERS
Arup Fire
Automatic Fire Alarm Association
Thanks to Jane Lataille, P.E., for providing this BFPE International
Factory Mutual Research Corporation
Fike Corporation
issue’s brainteaser. Grinnell Fire Protection Systems
Harrington Group, Inc.
HSB Professional Loss Control
Hubbell Industrial Controls
Joslyn Clark Controls, Inc.
James W. Nolan Company (Emeritus)
Industrial Risk Insurers
Koffel Associates, Inc.
Marsh Risk Consulting
National Electrical Manufacturers Association
Solution to last issue’s brainteaser National Fire Protection Association
National Fire Sprinkler Association
Nuclear Energy Institute
The difference between any two numbers in the set The Protectowire Co., Inc.
Reliable Fire Equipment Company
{2, 3, 4} is equal to their greatest common factor. The Risk Technologies, LLC
Siemens Cerberus Division
same is true of any two numbers in the sets {6, 8, 9, 12} SimplexGrinnell
TVA Fire and Lifesafety, Inc.
and {8, 9, 10, 12}. Find a set of five numbers for which Underwriters Laboratories, Inc.
Wheelock, Inc.
this is true. W.R. Grace Company
DONORS
Gage-Babcock & Associates, Inc.
Answer: Two sets of solutions are {900, 912, 915, 918,
SMALL BUSINESS MEMBERS
920} and {1664, 1665, 1666, 1668, 1680} and the multi- Bourgeois & Associates, Inc.
ples of both sets. Demers Associates, Inc.
Fire Consulting Associates, Inc.
MountainStar Enterprises
Performance Technology Consulting Ltd.
Poole Fire Protection Engineering, Inc.
S.S. Dannaway & Associates, Inc.
The Code Consortium, Inc.
Index of • Advanced Fire Technology, Inc..............Page 44 • Marsh Affinity Group Services ..................Page 7
Advertisers • Ansul, Inc. ..................................................Page 2 • NOTIFIER Fire Systems...........Inside Back Cover
• Central Sprinkler ......................................Page 59 • Potter Electric Signal Company ..............Page 28
• Commercial Products Group ..................Page 45 • The Protectowire Co., Inc. ......................Page 22
• DecoShield Systems, Inc. ........................Page 50 • The RJA Group .......................Inside Front Cover
• Edwards Systems Technology ...........Page 30-31 • Reliable Automatic Sprinkler ..................Page 18
• Essex Fluid Controls................................Page 44 • Siemens Fire Safety ............................Page 12-13
• Fenwal Protection Systems .....................Page 34 • SimplexGrinnell .......................................Page 27
• Fike Protection Systems ..........................Page 53 • System Sensor ..........................................Page 37
• Fire Control Instruments, Inc. ...................Page 8 • Tyco Fire Products .............................Back Cover
• Grice Engineering....................................Page 51 • Watts Regulator (ACV).............................Page 50
• Koffel Associates......................................Page 38 • Wheelock, Inc..........................................Page 23
Max. Storage Ht. Max. Ceiling Ht. K17 ESFR Min. Press. K14 ESFR Min. Press.
Ft. (m) Ft. (m) psi (bar) psi (bar)
40 (12.2)* 45 (13.7) 63 (4.3) 90 (5.2)
35 (10.7) 40 (12.2) 52 (3.6) 75 (5.2)
25 (7.6) 32 (9.8) 42 (2.9) 60 (4.1)
25 (7.6) 30 (9.1) 35 (2.4) 50 (3.4)
451 North Cannon Avenue • Lansdale, PA 19446
*Indicates One Level Of In-Rack Sprinklers Required. Phone: (800) 523-6512 • Fax: (215) 362-5385
See Tech Data Sheet 3-1.5 for other ESFR applications. www.tyco-central.com
from the technical director
Plug into the Onyx 640 panel — first in the new Onyx
series of products from NOTIFIER.