Coiled Vessel
Coiled Vessel
Equation No. 1 combines all the factors that determine the surface area of the heat transfer device.
A = Q/U T. A = area; Q = total heat input required; U = number describing the heat transfer
coefficient or degree of influence of materials, agitation, viscosity and other system details. The U-factor is
usually developed from past experience.
T is a difference in temperature. There are actually two variations of T that will be used in
calculations. The first ( T1) is the difference in temperature of the solution in the tank before and after
heating.
For example, a solution is at 70F before heating and must be elevated to 140F: T1 = 140 - 70 =70F.
The second variation of temperature ( T2) is between the heating medium (steam or hot water) and
Q/U T.
As you calculate the required surface area of the heat transfer device, you see where each T value
is used. To solve the basic equation (A = Q/U T), you must first determine the value of Q, or the total
relative amount of heat needed by different materials to be heated the same amount; T1 = the
Referring to Table I
Cp = 1.00 (specific heat of water)
T1 = 140 - 70 = 70F
Assuming a steam pressure of 10 psig, the temperature of the steam delivered to the finishing tank would
TABLE III—
be 239F. Since the solution will be heated to 140F, the Typical Heat Transfer Coefficients—"U"
T2 = 239-140 = 99F.
Type Heating U-Value U-Value
Medium (Agitated Tank) (Still Tank)
Steam 150 100
Hot Water 125 75
Completing the basic equation
Now that the basic values have been determined for all of the variables in equation A = Q/U T, we
can solve it. In order to heat the solution to 140F in four hours you need the following:
Q = 179,040 Btu/hr
U = 150
T2 = 99F.
TABLE IV—
Steam Pressure vs. Steam
Completing the equation Temp.
A = 179,040/150 × 99 = 170,040/14,850 = 12.06 sq ft.
Steam Steam Temp.
Pressure (F)
Surface area vs. heat transfer device configuration (Psig) 227
5 239
When the surface area of a heat transfer device has been calculated, 10 266
the next consideration is the configuration of the device. In many 25 297
finishing plants in-tank heating/cooling coils are used. When a coil is to 50
be immersed, there are several major considerations.
Coils must be sized and installed so they do not interfere with material moving into or out of the tank. The
most common form of damage to an in-tank coil is mechanical. In tanks with current-carrying racks,
accidental contact between a rack and coil may cause an electrical arc, resulting in a hole in the coil.
Coils should be installed to ensure the entire coil body is immersed. This assures that the rated heat
transfer surface is operating at maximum effectiveness.
TABLE V—Heat-Transfer Coil Sizes vs.
Surface Areas
Coil Dimensions
There are many coil styles available Surface Area Width Length Tubes
(sq ft) (Inches) (Inches)
A typical style is shown in Fig. 1. In a typical heat 4.6 12.5 24 8
transfer coil a one-inch outside diameter tubing is 5.6 12.5 30 8
used. Tubes are welded on 1.5 inch centers between 6.7 12.5 36 8
two manifolds, one of which includes an inlet and 6.8 18.5 24 12
outlet riser for the heating medium. 8.4 18.5 30 12
8.8 12.5 48 8
Before determining the length and width of the coil, 9.4 24.5 24 16
measure the length of the tank wall and the solution 10.0 18.5 36 12
depth. For this example, the tank walls are 3-ft wide 10.9 12.5 60 8
and 10-ft long, and the solution is 4-ft deep. 11.5 24.5 30 16
Considering each possibility, the coil would need to be 11.5 30.5 24 20
sized to fit within an area that is 3 × 4 ft or one that is 13.2 18.5 48 12
10 × 4 ft. 13.6 24.5 36 16
13.7 12.5 72 8
In sizing heat transfer coils it is important to select the 13.7 36.5 24 24
configuration with the smallest width and longest 14.2 30.5 30 20
length compatible with tank size to provide the best 15.1 12.5 84 8
heat distribution. Using data found in Table V, you can 15.8 42.5 24 28
determine that a coil width of 18.5 inches and a length 16.3 18.5 60 12
of 48 inches provides 13.2 sq ft of surface area. 16.8 30.5 36 20
Moving further down the chart you find a coil of 13.7 16.8 36.5 30 24
sq ft with a width of 12.5 inches and a length of 72 17.2 12.5 96 8
inches. It, too, has slightly more than the required 17.8 24.5 48 16
12.06 sq ft. 18.0 48.5 24 32
Although both coils will fit,we selected the 13.7-sq-ft 19.2 12.5 108 8
coil which offers the best combination of performance 19.5 18.5 72 12
and economy. The coil would be installed along the 19.5 42.5 30 28
10-ft wall of the tank. If the installation had to be along 20.0 36.5 36 24
the 3-ft wall, a coil with 13.7 sq ft of surface area and dimensions of 36.5 wide by 24 inches long (Table V)
could be used. Assuming that the solution depth would never go below 4 feet, this coil would function
properly.
Why is it important to calculate surface area when determining the size of heating coils? Heat transfer
devices, particularly ones fabricated from a costly material such as titanium or stainless steel, can be
expensive. Since most heat transfer devices are priced according to size, it simply does not pay to
purchase larger devices than are necessary to accomplish the task. Using the information in this article
will help determine how much area you will need after you establish how long heat up should take and
what temperature you must maintain.
A little pencil pushing can go a long way toward improving operating efficiency and lowering heat transfer
equipment costs.