SC 1000 RDM PB - Eng

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

SC-1000 INTEGRATED SYSTEM

SC-1000-RDM-PB
DOOR INTERFACE MODULE IN MEDIUM METAL BOX WITH 2A PSU

PRODUCT DESCREPTION
The SC-1000-RDM access control panel is a product in the SC-1000 integrated
access system. It has increased number of inputs and outputs for universal use and it
can replace moduls SC-1000-02/06/07. It provides RS-232 connection with and
external converter through the reader ports. Typical application as part of an acces
control system is controlling one bidirectional or two oneway entry points, but inputs
can also be equipped with security sensors with resistive termination. There are two
types of firmware: can be used as an SC-1000-02 module on older systems, or can
be integrated as an RDM module into the system from software version Incedo Pro
2.1.
This module is not able to make access decision and doesn’t storage datas. The input
signals are transmitted via CAN-bus in real time to the SC-1000 main controller,
which makes the access decision and releases the programmed controls.
The inputs, outputs, function of reader ports and the parameters of hardwares are not
specified in advance, those are flexibly programmable during the installation
according to the software configuration of logical gateways. The physical data points
of the modules on the same data lines are arbitrarily usable and those can be freely
combined in the main control panel logical units (e.g. gateways, alarm partitions,
controls, etc.)

TECHNICAL DATA
 Real time mode with the SC-1000-MX7 integrated access system
 Event driven, two-way communication in half-duplex mode via
CAN-bus
 Identification based on production serial number
 Flexible physical and logical parameterization
 Multi-state, resistance-locked or contact inputs
 Inputs and outputs can be inverted with the software
 One input can be used in more than one logical unit
 AbaTrack2, Wiegand and serial TTL reader interface native handling
 RS-232 interface witch external converter through the reader ports
 Detachable terminal blocks
 Security grade up to: Grade 3, Grade 4

MODUL DATA
 1 pc power supply input
 1 pc power supply output
 2 pc reader port
 6 pc multi-state input
 1 pc sabotage contact input
 2 pc power failure (230V and battery failure) contact input
 2 pc relay out
 2 pc open-collector output
 1 pc CAN-bus connector

EXAMPLES OF APPLICATION
 Access contol, integrated and time and attendance systems
 One or two way passages (doors, gates, turngates, speed gates, etc.)
 1 door in two-way or 2 doors in one-way with RFID authentication
 1 door in one-way with RFID and biometric authentication

ASSA ABLOY Opening Solutions Hungary Kft. reserves the


right to change product parameters without prior notice!
SC-1000 INTEGRATED SYSTEM

BOX TECHNICAL DATA


 Metal plate covering
 Three different sizes
 Modular device placement
 Prefabricated holes for SC-1000 and SW-500 system devices
 Front and rear tamper switches
 Rear spacers for cable entry and ventilation
 During installation the cover removable from the front; there is
no need for additional space for mounting
 Cover with metric screws
 Cable locking tabs inside the box
 Drill template for fixing
 Possibility to place additional devices on a horizontal
mounting plate (for large and medium sized mounting boxes)
 Unified, powder-coated surface finish and appearance
(RAL9001 colour)
 Indoor use, protection: IP30

POWER SUPPLY DESCRIPTION


 Linear PSU
 Safe toroidal transformer
 Stabilised output voltage
 Current limited output
 Overload and short circuit protection
 Thermal safety switch
 Reverse polarity protection, overload protection and deep
discharging protection
 LED feedback in case of power outage output DC outage
 Opto transistor output for fault check in case of AC outage or
battery deep discharge
 protection against electric shock grade 1: protective grounding is
mandatory, can be used only in box
 Certification: IP00; MEEI

Identification:en_SC_1000_RDM-PB
Type: Technical datasheet
Version: Rev.1
Date: 26.04.2022
SC-1000 INTEGRATED SYSTEM

ELECTRICAL SPECIFICATION
Input Power: 11…14 VDC
Power consumption (without peripherals): 50 mA / max. 100 mA @ 12VDC
Protection of Input Power: 1 pc; Protected against reverse polarity
Protection of Output Power: 1 pc; 12VDC
Reader Output Power (MAX): 2 pcs; max. 500 mA @ 12VDC / output
Reader OC Output Power (MAX): 500 mA / output (open collector - Darlington)
(LEDG, LEDR, BUZ, OUT3, OUT4)
Inputs (dedicated): Cannot be inverted or parameterized from software
- Sabotage input: 1 pc (SAB NC)
- 230V power failure: 1 pc 230V FAULT (NC)

- Battery failure: 1 pc BAT FAULT (NC)


Inputs (genaral): 6 pcs bipolar, analogue; INP1-6
- States: On-hold, alarm, anti-mask, sabotage
- Closures: Inputs can be selected from software:
Incedo settings: NC NO DEOL 5,1 kΩ 5,6 kΩ
On-hold: 0 ∞ 1 kΩ 5,1 kΩ 5,6 kΩ
Alarm: ∞ 0 +1 kΩ +5,1 kΩ +5,6 kΩ
Anti-mask: - - - +33 kΩ +33 kΩ
Sabotage: - - - 0, ∞ 0, ∞
Relay Outputs: 2 pcs morse relay (C, NC, NO); max. 8A / 24VDC
Open collector outputs: 2 pcs; max. 500 mA / output; Relay module can be
connected
Card reader port: 2 pcs AbaTrack2 or Wiegand or TTL native handling
asynchronous serial interface
Card reader cable (for SW-R-xxx readers): max. 15 m, 2 x 0,5 + 6 x 0,22 mm2, shielded
RS-232: With external converter on connectors of readers
TX/RX ports
CAN-BUS: 1 pc; CAN 2.0B; 62,5 kbps; length: max. 500 m
- Protokoll: SW-CAN
- Topology: Bus structure, line or loop design
- Cable: Twisted-pair: U/UTP cat5e AWG24
- Closure: 120 ohm, jumper-connected (JP1) max. 15 m;
recommended: 2x0,5+6x0,22 mm2, shielded
Module adressing, identification: Based on production serial number (S/N)
Module firmware: Flash EPROM; upgraded via CAN-bus
Status LEDs:
- LD1: CAN RX CAN bus communication (Receiver)
- LD2: CAN TX CAN bus communication (Transmitter)
- LD3: POWER Power
- LD4: DIAG Modul status
Hardware settings:
- EOL: CAN-BUS TERMINATOR CAN-bus line terminating resistor (120 ohm)
- RES: RESET Module restart
Fuses: F1, F2, F3 500 mA; aut-reset PTC fuse

MECHANICAL SPECIFICATION
Dimensions: 118 x 65 mm
Panel mounting holes: 108 x 55 mm; 4 mm
Weight (without mounting box): 90 g
Connectors: Terminal; max. 0,75 mm2, AWG 19

OPERATION CONDITIONS
Operating temperature: 0…+50 oC
Storage temperature: -20…+60 oC
Vibration during operation: Not allowed
Direct sunlight: Not allowed
Operating humidity: < 95% relative, non-condensing
Installation: Grounded, on plastic spacer in metal box
IP Protection: IP30 (installed in Seawing metal box)

COMPLIANCE
Electromagnetic Compatibility Directive: EN 50130-4:2011; EN 55032:2015
Restriction of the use of certain Hazardous EN 50581:2013
Substances (RoHS):
Product specific standards: EN 60839-11-1, EN 60839-11-2, MABISZ
Hardver compatibility: SC-1000 product family
Software compatibility: Incedo Pro
- below ver. 2.1 : as SC-1000-02 module
- above ver. 2.1 : as SC-1000-RDM module

Identification:en_SC_1000_RDM-PB
Type: Technical datasheet
Version: Rev.1
Date: 26.04.2022
SC-1000 INTEGRATED SYSTEM

ORDERING INFORMATION
Article nr. Type Product name
90EKVEZ0150 SC-1000-RDM Access Control Panel
Related products
90EKVEZ4000 SC-1000-MX7 Main controller panel
90EKVEZ1015 SC-1000-03 Intrusion module
90EKVEZ0178 SC-1000-04 Output module
93MF0100162 SC-1000-03-D Samll metal box
93MF0100157 SC-1000-02-D Medium metal box
93MF010152 SC-1000-D Large metal box
90EKVEZ0330 LINTAP2-12V/2A 12V/2A power supply card
01AVEZA0482 SW-IT-401-M Time/attendance system,
terminal without card reader
Accessories
02KIEMOD210 CAN-ISOL-1 CAN-bus galvanic isolator

Identification:en_SC_1000_RDM-PB
Type: Technical datasheet
Version: Rev.1
Date: 26.04.2022

You might also like