Marine Table - LSAM range

Low Voltage Alternators - 4 pole


General features and ratings
Table of contents

1 - CLASSIFICATION SOCIETIES SPECIFICATIONS OVERVIEW ......................................................... 3

2 - GENERAL FEATURES......................................................................................................................... 4
2.1 - Standards..................................................................................................................................................4
2.2 - Electrical features......................................................................................................................................4
2.3 - Mechanical features..................................................................................................................................4

3 - ACCESSORIES AND OPTIONS........................................................................................................... 4

4 - PRODUCT DESCRIPTION.................................................................................................................... 4

5 - RATING BY MARINE SPECIFICATION FAMILY.................................................................................. 6


380 ... 415V / 50 Hz – 440 ... 480V / 60 Hz
LR class H.........................................................................................................................................................6
LR class F..........................................................................................................................................................7
ClassNK - KRS class H......................................................................................................................................8
ClassNK - KRS class F......................................................................................................................................9
BV - DNV - RINA - ABS - CCS - TL - PRS - RS class H.....................................................................................10
BV - DNV - RINA - ABS - CCS - TL class F......................................................................................................11
PRS - RS class F.............................................................................................................................................12
690V - 50 Hz
BV - DNV - RINA - PRS - ClassNK - RS - LR - ABS - KRS - CCS - TL class H and F........................................14
690V - 60 Hz
BV - DNV - RINA - PRS - ClassNK - RS - LR - ABS - KRS - CCS - TL class H and F........................................15

2 Electric Power Generation


Technical definitions

1 - Classification societies specifications overview


Alternators for marine use have to comply with the specifications on the table below in order to meet customer’s request.
Temperature Temperature
rise rise Short- Transient % Shaft
Temperature Space Factory Spare
Ambient Ambient circuit voltage Overload Regulation conformity
detector heaters setting parts
temperature temperature current drop P.F. = 0.8 certificate
Class H Class F

LR
300% 15% at Pn 50% Electrical
Lloyd’s 110°/45° 95°/45° R* ± 2.5% P ≥ 100 kW P ≥ 100 kW NS*
2 sec. P.F. = 0.8 30 sec. propulsion
Register

ABS
P ≥ 500 kVA
American 300% 15% at 0.6 Pn 50% If weight Electrical
120°/45° 100°/45° Electrical ± 2.5% P ≥ 100 kW Bearings
Bureau 2 sec. P.F. = 0.4 30 sec. ≥ 455 kg propulsion
propulsion
of Shipping

ClassNK P ≥ 500 kVA 1 bearing


300% 15% at PN 50%
Nippon Kaiji 120°/45° 100°/45° Electrical P ≥ 500 kW ± 2.5% P ≥ 100 kW P > 0 kW for each
2 sec. P.F. = 0.8 2 mn
Kyokai propulsion 4 or less

R* Shaft driven
BV
300% 15% at 0.6 Pn 50% Electrical Electrical +
Bureau 120°/45° 100°/45° ± 2.5% P ≥ 100 kW NS*
2 sec. P.F. 0.4 30 sec. propulsion propulsion Propulsion
Veritas application

DNV Shaft driven


1/3 of the
300% 15% at 0.6 Pn 50% +
Det Norske 120°/45° 100°/45° P > 5000 kW S* ± 2.5% P ≥ 100 kW diodes
2 sec. P.F. 0.4 30 sec. Propulsion
Veritas + A.V.R.
application

PRS
P ≥ 500 kVA
Polish 300% 15% at 0.6 Pn 50% Electrical Bearings
120°/45° 95°/45° Electrical ± 2.5% NS* P ≥ 50 kVA
Register 2 sec. P.F. = 0.4 2 mn propulsion (R*)
propulsion
of Shipping

KRS
P ≥ 500 kVA
Korea 300% 15% at Pn 50%
120°/45° 100°/45° Electrical R* ± 2.5% P ≥ 100 kW P ≥ 100 kW Bearings
Register 2 sec. P.F. = 0.8 2 mn
propulsion
of Shipping

RINA Shaft driven


Registro 300% 15% at 0.6 Pn 50% Electrical Electrical +
120°/45° 100°/45° ± 2.5% P ≥ 100 kVA NS*
Italiano 2 sec. P.F. = 0.4 30 sec. propulsion propulsion Propulsion
Navale application

RS
Russian
300% 15% at 0.6 Pn 50% Electrical
Maritime 120°/45° 95°/45° R* ± 2.5% NS* P > 0 kW NS*
2 sec. P.F. = 0.4 2 mn propulsion
Register
of Shipping

CCS
China 300% 15% at 0.6 Pn 50%
120°/45° 100°/45° - - ± 2.5% - -
Classification 2 sec. P.F. = 0.4 2 mn. -
Society

Shaft driven
TL P ≥ 500 kVA
300% 15% at 0.6 Pn 50% +
Turkish 120°/45° 100°/45° Electrical P ≥ 500 kW ± 2.5% P ≥ 100 kW NS*
2 sec. P.F. = 0.4 2 mn Propulsion
Lloyd’s propulsion
application

*: NS: not specified - R: recommended - S: specified

Notes:
Alternators are proposed for secondary use. All demands for propulsion must be submitted for consultation. Generators intended
for propulsion are subjected to case by case approval and shaft certification type 3.2 by classification societies requested.
This list is not exhaustive and may be revised to include other classification societies. Whatever Class H or F, all the other
specifications remain the same.
Table is applicable to standard low voltage alternators up to 5000 kW electrical power.
Consult the societies rules for all other products (e.g. heat exchangers, medium voltage, electrical propulsion, ...).

Electric Power Generation 3


Technical definitions

2 - General features
2.1 - Standards
Nidec Leroy-Somer LSAM Marine alternators meet all key international standards and regulations, including IEC 60034, NEMA MG
1.32-33, ISO 8528-3, CSA C22.2 n°100-14 and UL 1446 (UL 1004 on request). Also compliant with IEC 61000-6-2, IEC 61000-6-3,
IEC 61000-6-4, VDE 0875G, VDE 0875N and EN 55011, group 1 class A for European zone.
Nidec Leroy-Somer LSAM Marine alternators can be integrated in EC marked generator sets, and they bear EC, UKCA and CMIM
markings. They are designed, manufactured and marketed in an ISO 9001 and ISO 14001 quality assurance environment.

2.2 - Electrical features


- Excitation systems: Nidec Leroy-Somer propose a large choice of excitation systems, depending on the customer needs:
AREP or PMG system, with a short-circuit capacity of 3 times the nominal current for 10 seconds
- Voltage regulators: The 4-pole LSAM alternators are fitted with reliable and performant digital AVRs, designed and
manufactured by Nidec Leroy-Somer. Available excitation systems depending on selected alternator and are indicated in nominal
rating tables.
- Frequency: LSAM alternators may operate either 50 or 60 Hz. The standard winding (code 6) is suitable both for 50 and 60 Hz.
For dedicated windings, see specific table or consult factory.
- Power factor P.F.: LSAM alternators are designed to operate between 0.8 and 1 power factor. A derating is necessary below 0.8
power factor (see derating chart). Consult us for other PF needs.
- Waveform: Total harmonic distorsion (THD), at no load or linear load is less than 5% according to IEC. TIF/Telephone influence
factor according to NEMA is less than 50.
- Transient features: Transient voltage dip for rated step load at 0.8 power factor is less than 18 %. Recovery time for a 20 %
transient voltage dip is less than 0.5 s.
- Parallel operation: All LSAM alternators can operate in parallel with other alternators (2/3 pitch winding) with AREP/PMG
(except LSAM 40 with AREP only), or with the mains, when they are equipped with the appropriate devices (AVR, current
transformer...).
- Overload acceptance: LSAM alternators can be overloaded according to NEMA.

2.3 - Mechanical features


- Mechanical arrangement: LSAM alternators can be provided in single bearing or two bearing configurations. A large range of
engine adaptors and coupling discs are available to fit the major engines.
- Enclosure: Standard enclosure is IP 23. Other enclosures such as IP 44, IP 55 can be offered on request (possible derating).
- Bearings: Sealed for life bearings up to LSAM 50.2 (regreasable bearing option from LSAM 46.3), regreasable bearings from
LSAM 52.3.
- Balancing: All rotors are dynamically balanced according to ISO 1940 and IEC 60034-14. Two bearing rotors are balanced with
a half key.
- Direction of rotation: LSAM alternators can operate in both directions (5% derating for anticlockwise running for LSAM 47.3,
LSAM 49.3 and LSAM 50.2). LSAM 52.3 alternators are designed to have only one direction of rotation, which has to be defined
upon ordering.
- Overspeed: The maximum overspeed is 2250 R.P.M. (1.25 times the 60 Hz rated speed).
- Insulation and protection: LSAM alternators are class H insulated. The standard winding protection can accept up to 95 %
relative humidity and is suitable for indoors marine applications. Specific added coatings can be proposed for harsh
environments. Refer to technical note TN12 (ref. 5338).
- Terminal box and connectors: LSAM alternators are fitted with a large terminal box which facilitates access to the AVR and
allows easy access to the connections. Current transformers and other optional modules can be fitted within the terminal box.
- Mechanical structure: Steel frame. Aluminum, cast iron or steel housings and flanges depending on models.
- Painting: LSAM generators are supplied painted. The color can be chosen by the customer. For more details on the paint
specification LSAM 52, refer to technical note TN18 (ref. 5727).

4 Electric Power Generation


Technical definitions

3 - Accessories and options


- Digital A.V.R. D550 (includes three phase sensing and paralleling with the grid)
- EMI suppression module R791 for other areas than EC
- PMG (from LSAM 42.3)
- Engine adaptors for two bearing alternators
- Air inlet filters (5% derating)
- Air inlet or outlet filters with IP44 (10% derating) (8% derating for LSAM 52.3)
- Specific stator protections for harsh environments
- Specific painting
- Greasable bearings for LSAM 46.3, LSAM 47.3, LSAM 49.3 and LSAM 50.2
- Thermal sensors for bearings
- Thermal sensors for stator windings
- Anti condensation heaters (retrofitable)
- Remote voltage potentiometers
- Current transformers for paralleling with other alternators
- First emergency kits (AVR + diodes)

4 - Product description
The machine name is defined according to various criteria (see below).
Example of description for:
LSAM 49.3 M6 C6S/4
• LSAM: Range
• 49.3: Frame size
• M6: Core length
• C: Excitation system (C: AREP / J: SHUNT or SHUNT + PMG)
• 6S/4: Winding number / number of poles

Electric Power Generation 5


LR
Class H
7 to 2350 kVA - 50 Hz / 8 to 2615 kVA - 60 Hz

5 - Rating by marine specification family


TEMPERATURE RISE: Class H - 110°/45°
AREP* 1500 R.P.M. - 50 Hz - P.F. = 0.8 1800 R.P.M. - 60 Hz - P.F. = 0.8
380V ... 415V 380 V 440V ... 480V 450 V
4 P - 3 Ph + Neutral kVA kWe Effic.** kWm** kVA kWe Effic.** kWm**
LSAM 40 VS1 C6/4 7 5.6 84.3 6.6 8 6.4 84.8 7.5
40 VS2 C6/4 10 8 85.6 9.3 11.5 9.2 86.2 10.7
40 S3 C6/4 13 10.4 85.8 12.1 15 12 86.6 13.9
40 S4 C6/4 17 13.6 86.1 15.8 19 15.2 87.2 17.4
40 M5 C6/4 20 16 87 18.4 23 18.4 87.9 20.9
LSAM 42.3 VS2 C6/4 22.4 17.9 88.5 20.2 25.7 20.6 89.4 23
42.3 VS3 C6/4 27 21.6 89 24.3 31 24.8 89.9 27.6
42.3 S4 C6/4 35 28 90 31.1 40.5 32.4 90.8 35.7
42.3 S5 C6/4 37 29.6 89.7 33 42 33.6 90.7 37
42.3 M7 C6/4 41 32.8 90.1 36.4 47 37.6 90.9 41.4
42.3 M8 C6/4 46 36.8 90.3 40.8 54 43.2 91 47.5
42.3 L9 C6/4 53 42.4 90.8 46.7 60 48 91.6 52
LSAM 44.3 S2 C6/4 70 56 92.2 61 88 70 92.4 76
44.3 S3 C6/4 80 64 91.9 70 100 80 92.3 87
44.3 S4 C6/4 90 72 92.6 78 113 90 92.9 97
44.3 S5 C6/4 100 80 92.3 87 125 100 92.7 108
44.3 M6 C6S/4 118 94 92.7 101 141 113 93.2 121
44.3 M8 C6/4 132 106 93 114 157 126 93.5 135
44.3 L10 C6S/4 147 118 93.3 126 177 142 93.8 151
44.3 VL13 C6/4 175 140 93.3 150 210 168 93.6 179
44.3 VL14 C6/4 186 149 93.1 160 223 178 93.5 190
LSAM 46.3 S4 C6/4 212 170 93 183 252 202 93.2 216
46.3 S5 C6/4 223 178 92.8 192 267 214 93.1 229
46.3 M7 C6S/4 250 200 93.5 214 300 240 93.6 256
46.3 M8 C6S/4 275 220 93.2 236 325 260 93.5 278
46.3 L10 C6/4 300 240 94.1 255 365 292 94.2 309
46.3 L11 C6/4 330 264 93.9 281 380 304 94.2 323
LSAM 47.3 VS3 C6/4 355 284 93.6 303 450 360 93.7 384
47.3 S4 C6S/4 400 320 94.2 340 490 392 94.3 416
47.3 S5 C6/4 425 340 94.7 359 530 424 94.8 447
47.3 M7 C6/4 476 381 94.8 402 602 482 94.8 508
47.3 M8 C6/4 500 400 94.6 423 620 496 94.7 524
47.3 L9 C6S/4 550 440 95.2 462 685 548 95.3 575
47.3 L10 C6S/4 610 488 95.2 513 723 578 95.4 606
LSAM 49.3 M6 C6S/4 705 564 94.6 596 840 672 94.7 710
49.3 M8 C6S/4 800 640 94.7 676 940 752 94.8 793
49.3 L9 C6S/4 910 728 95.3 764 1045 836 95.4 876
49.3 L10 C6S/4 935 748 95.4 784 1126 901 95.4 944
LSAM 50.2 M6 C6S/4 1140 912 95 960 1380 1104 95 1162
50.2 L7 C6S/4 1255 1004 95.2 1055 1480 1184 95.1 1245
50.2 L8 C6S/4 1355 1084 95.4 1136 1600 1280 95.4 1342
50.2 VL10 C6S/4 1495 1196 95.7 1250 1760 1408 95.5 1474
LSAM 52.3 S6 C6S/4 1650 1320 96.2 1372 - - - -
52.3 S7 C6S/4 1950 1560 96.2 1622 1950 1560 96.5 1617
52.3 L9 C6S/4 2165 1732 96.3 1799 2325 1860 96.5 1928
52.3 L12 C6S/4 2350 1880 96.3 1952 2615 2092 96.5 2168

kWe: electrical rating available from the alternator. kWm: necessary mechanical rating from the engine.
* Optional: SHUNT + PMG available.
** Efficiency and mechanical power (kWm) are calculated for 380V - 50Hz and 450V - 60Hz.

6 Electric Power Generation


LR
Class F
7 to 2087 kVA - 50 Hz / 8 to 2323 kVA - 60 Hz

TEMPERATURE RISE: Class F - 95°/45°


AREP* 1500 R.P.M. - 50 Hz - P.F. = 0.8 1800 R.P.M. - 60 Hz - P.F. = 0.8
380V ... 415V 380 V 440V ... 480V 450 V
4 P - 3 Ph + Neutral kVA kWe Effic.** kWm** kVA kWe Effic.** kWm**
LSAM 40 VS1 C6/4 7 5.6 84.3 6.6 8 6.4 84.8 7.5
40 VS2 C6/4 10 8 85.6 9.3 11.5 9.2 86.2 10.7
40 S3 C6/4 13 10.4 85.8 12.1 15 12 86.6 13.9
40 S4 C6/4 16 12.8 86.3 14.8 19 15.2 87.2 17.4
40 M5 C6/4 18.5 14.8 87.3 17 21.5 17.2 88.1 19.5
LSAM 42.3 VS1 C6/4 20 16 88.3 18.1 23 18.4 89.1 20.7
42.3 VS2 C6/4 22.5 18 88.5 20.3 26 20.8 89.3 23.3
42.3 VS3 C6/4 27 21.6 89 24.3 31 24.8 89.9 27.6
42.3 S4 C6/4 32 25.6 90.3 28.3 39 31.2 90.9 34.3
42.3 S5 C6/4 35 28 90 31.1 41.5 33.2 90.7 36.6
42.3 M7 C6/4 38 30.4 90.4 33.6 45 36 91.1 39.5
42.3 M8 C6/4 42 33.6 90.6 37.1 50 40 91.3 43.8
42.3 L9 C6/4 47.5 38 91.2 41.7 54.5 43.6 91.8 47.5
LSAM 44.3 S2 C6/4 64 51 92.3 55 80 64 92.5 69
44.3 S3 C6/4 73 58 92.1 63 91 73 92.4 79
44.3 S4 C6/4 82 66 92.7 71 102 82 93 88
44.3 S5 C6/4 91 73 92.5 79 114 91 92.9 98
44.3 M6 C6S/4 108 86 92.9 93 128 102 93.3 109
44.3 M8 C6/4 120 96 93.3 103 142 114 93.7 122
44.3 L10 C6S/4 135 108 93.5 116 161 129 93.9 137
44.3 VL13 C6/4 156 125 93.6 134 190 152 93.9 162
44.3 VL14 C6/4 170 136 93.4 146 200 160 93.8 171
LSAM 46.3 S4 C6/4 185 148 93.3 159 225 180 93.4 193
46.3 S5 C6/4 200 160 93.1 172 240 192 93.3 206
46.3 M7 C6S/4 225 180 93.7 192 275 220 93.8 235
46.3 M8 C6S/4 250 200 93.5 214 300 240 93.6 256
46.3 L10 C6/4 275 220 94.3 233 325 260 94.4 275
46.3 L11 C6/4 299 239 94.1 254 347 278 94.3 295
LSAM 47.3 VS3 C6/4 325 260 93.9 277 410 328 94 349
47.3 S4 C6S/4 375 300 94.4 318 455 364 94.5 385
47.3 S5 C6/4 415 332 94.7 351 480 384 94.9 405
47.3 M7 C6/4 455 364 94.9 384 545 436 95 459
47.3 M8 C6/4 480 384 94.7 405 560 448 95 472
47.3 L9 C6S/4 525 420 95.3 441 610 488 95.4 512
47.3 L10 C6S/4 565 452 95.4 474 681 545 95.5 571
LSAM 49.3 M6 C6S/4 635 508 94.8 536 760 608 94.8 641
49.3 M8 C6S/4 730 584 94.9 615 850 680 94.9 717
49.3 L9 C6S/4 820 656 95.5 687 940 752 95.5 787
49.3 L10 C6S/4 851 681 95.5 713 1020 816 95.5 854
LSAM 50.2 M6 C6S/4 1055 844 95.2 887 1200 960 95.1 1009
50.2 L7 C6S/4 1145 916 95.4 960 1285 1028 95.3 1079
50.2 L8 C6S/4 1230 984 95.6 1029 1400 1120 95.5 1173
50.2 VL10 C6S/4 1365 1092 95.8 1140 1545 1236 95.7 1292
LSAM 52.3 S6 C6S/4 1630 1304 96.2 1356 1650 1320 96.5 1368
52.3 S7 C6S/4 1860 1488 96.3 1550 2050 1640 96.5 1700
52.3 L9 C6S/4 1924 1539 96.4 1597 2116 1693 96.5 1754
52.3 L12 C6S/4 2087 1669 96.4 1732 2323 1858 96.6 1924

kWe: electrical rating available from the alternator. kWm: necessary mechanical rating from the engine.
* Optional: SHUNT + PMG available.
** Efficiency and mechanical power (kWm) are calculated for 380V - 50Hz and 450V - 60Hz.

Electric Power Generation 7


ClassNK – KRS
Class H
7 to 2350 kVA - 50 Hz / 8 to 2615 kVA - 60 Hz

TEMPERATURE RISE: Class H - 120°/45°


AREP* 1500 R.P.M. - 50 Hz - P.F. = 0.8 1800 R.P.M. - 60 Hz - P.F. = 0.8
380V ... 415V 380 V 440V ... 480V 450 V
4 P - 3 Ph + Neutral kVA kWe Effic.** kWm** kVA kWe Effic.** kWm**
LSAM 40 VS1 C6/4 7 5.6 84.3 6.6 8 6.4 84.8 7.5
40 VS2 C6/4 10 8 85.6 9.3 11.5 9.2 86.2 10.7
40 S3 C6/4 13 10.4 85.8 12.1 15 12 86.6 13.9
40 S4 C6/4 17 13.6 86.1 15.8 19 15.2 87.2 17.4
40 M5 C6/4 20 16 87 18.4 23 18.4 87.9 20.9
LSAM 42.3 VS2 C6/4 22.4 17.9 88.5 20.2 25 20 89.4 22.4
42.3 VS3 C6/4 27 21.6 89 24.3 31 24.8 89.9 27.6
42.3 S4 C6/4 35 28 90 31.1 40.5 32.4 90.8 35.7
42.3 S5 C6/4 37 29.6 89.7 33 42.5 34 90.6 37.5
42.3 M7 C6/4 41 32.8 90.1 36.4 47.5 38 90.9 41.8
42.3 M8 C6/4 48 38.4 90.1 42.6 55.5 44.4 90.9 48.8
42.3 L9 C6/4 55 44 90.6 48.6 60 48 91.6 52
LSAM 44.3 S2 C6/4 70 56 92.2 61 88 70 92.4 76
44.3 S3 C6/4 80 64 91.9 70 100 80 92.3 87
44.3 S4 C6/4 90 72 92.6 78 113 90 92.9 97
44.3 S5 C6/4 100 80 92.3 87 125 100 92.7 108
44.3 M6 C6S/4 123 98 92.5 106 147 118 93.1 127
44.3 M8 C6/4 135 108 92.9 116 164 131 93.4 140
44.3 L10 C6S/4 150 120 93.3 129 184 147 93.7 157
44.3 VL13 C6/4 180 144 93.2 155 210 168 93.6 179
44.3 VL14 C6/4 195 156 92.9 168 230 184 93.4 197
LSAM 46.3 S4 C6/4 220 176 92.9 189 261 209 93.1 224
46.3 S5 C6/4 231 185 92.7 200 275 220 93 237
46.3 M7 C6S/4 261 209 93.4 224 307 246 93.6 263
46.3 M8 C6S/4 275 220 93.2 236 324 259 93.5 277
46.3 L10 C6/4 300 240 94.1 255 345 276 94.3 293
46.3 L11 C6/4 332 266 93.9 283 388 310 94.1 329
LSAM 47.3 VS3 C6/4 365 292 93.5 312 450 360 93.7 384
47.3 S4 C6S/4 400 320 94.2 340 500 400 94.3 424
47.3 S5 C6/4 450 360 94.6 381 531 425 94.8 448
47.3 M7 C6/4 500 400 94.7 422 625 500 94.7 528
47.3 M8 C6/4 530 424 94.4 449 630 504 94.7 532
47.3 L9 C6S/4 590 472 95.1 496 675 540 95.3 567
47.3 L10 C6S/4 610 488 95.2 513 720 576 95.4 604
LSAM 49.3 M6 C6S/4 730 584 94.6 617 840 672 94.7 710
49.3 M8 C6S/4 810 648 94.6 685 940 752 94.8 793
49.3 L9 C6S/4 910 728 95.3 764 1045 836 95.4 876
49.3 L10 C6S/4 970 776 95.3 814 1146 917 95.4 961
LSAM 50.2 M6 C6S/4 1195 956 94.9 1007 1420 1136 94.9 1197
50.2 L7 C6S/4 1290 1032 95.2 1084 1550 1240 95.1 1304
50.2 L8 C6S/4 1400 1120 95.4 1174 1685 1348 95.3 1414
50.2 VL10 C6S/4 1540 1232 95.6 1289 1840 1472 95.5 1541
LSAM 52.3 S6 C6S/4 1650 1320 96.2 1372 - - - -
52.3 S7 C6S/4 1950 1560 96.2 1622 1950 1560 96.5 1617
52.3 L9 C6S/4 2165 1732 96.3 1799 2325 1860 96.5 1928
52.3 L12 C6S/4 2350 1880 96.3 1952 2615 2092 96.5 2168

kWe: electrical rating available from the alternator. kWm: necessary mechanical rating from the engine.
* Optional: SHUNT + PMG available.
** Efficiency and mechanical power (kWm) are calculated for 380V - 50Hz and 450V - 60Hz.

8 Electric Power Generation


ClassNK – KRS
Class F
7 to 2255 kVA - 50 Hz / 8 to 2510 kVA - 60 Hz

TEMPERATURE RISE: Class F - 100°/45°


AREP* 1500 R.P.M. - 50 Hz - P.F. = 0.8 1800 R.P.M. - 60 Hz - P.F. = 0.8
380V ... 415V 380 V 440V ... 480V 450 V
4 P - 3 Ph + Neutral kVA kWe Effic.** kWm** kVA kWe Effic.** kWm**
LSAM 40 VS1 C6/4 7 5.6 84.3 6.6 8 6.4 84.8 7.5
40 VS2 C6/4 10 8 85.6 9.3 11.5 9.2 86.2 10.7
40 S3 C6/4 13 10.4 85.8 12.1 15 12 86.6 13.9
40 S4 C6/4 16 12.8 86.3 14.8 19 15.2 87.2 17.4
40 M5 C6/4 18.5 14.8 87.3 17 21.5 17.2 88.1 19.5
LSAM 42.3 VS1 C6/4 20 16 88.3 18.1 24 19.2 89 21.6
42.3 VS2 C6/4 22.5 18 88.5 20.3 25.5 20.4 89.4 22.8
42.3 VS3 C6/4 27 21.6 89 24.3 31 24.8 89.9 27.6
42.3 S4 C6/4 32 25.6 90.3 28.3 39 31.2 90.9 34.3
42.3 S5 C6/4 36.5 29.2 89.8 32.5 42 33.6 90.7 37
42.3 M7 C6/4 40 32 90.2 35.5 47 37.6 90.9 41.4
42.3 M8 C6/4 44 35.2 90.5 38.9 52 41.6 91.1 45.7
42.3 L9 C6/4 50.5 40.4 91 44.4 54.5 43.6 91.8 47.5
LSAM 44.3 S2 C6/4 64 51 92.3 55 80 64 92.5 69
44.3 S3 C6/4 73 58 92.1 63 91 73 92.4 79
44.3 S4 C6/4 82 66 92.7 71 102 82 93 88
44.3 S5 C6/4 91 73 92.5 79 114 91 92.9 98
44.3 M6 C6S/4 113 90 92.8 97 135 108 93.3 116
44.3 M8 C6/4 123 98 93.2 105 150 120 93.6 128
44.3 L10 C6S/4 137 110 93.5 118 169 135 93.8 144
44.3 VL13 C6/4 164 131 93.5 140 191 153 93.9 163
44.3 VL14 C6/4 180 144 93.2 155 210 168 93.6 179
LSAM 46.3 S4 C6/4 202 162 93.1 174 237 190 93.3 204
46.3 S5 C6/4 215 172 92.9 185 250 200 93.2 215
46.3 M7 C6S/4 240 192 93.6 205 280 224 93.7 239
46.3 M8 C6S/4 253 202 93.5 216 295 236 93.7 252
46.3 L10 C6/4 276 221 94.2 235 314 251 94.4 266
46.3 L11 C6/4 303 242 94.1 257 353 282 94.3 299
LSAM 47.3 VS3 C6/4 330 264 93.9 281 410 328 94 349
47.3 S4 C6S/4 375 300 94.4 318 455 364 94.5 385
47.3 S5 C6/4 400 320 94.8 338 480 384 94.9 405
47.3 M7 C6/4 450 360 94.9 379 561 449 95 473
47.3 M8 C6/4 475 380 94.7 401 587 470 94.8 496
47.3 L9 C6S/4 525 420 95.3 441 600 480 95.4 503
47.3 L10 C6S/4 595 476 95.3 499 681 545 95.5 571
LSAM 49.3 M6 C6S/4 660 528 94.8 557 760 608 94.8 641
49.3 M8 C6S/4 760 608 94.8 641 850 680 94.9 717
49.3 L9 C6S/4 820 656 95.5 687 940 752 95.5 787
49.3 L10 C6S/4 895 716 95.4 751 1031 825 95.5 864
LSAM 50.2 M6 C6S/4 1070 856 95.2 899 1275 1020 95.1 1073
50.2 L7 C6S/4 1165 932 95.4 977 1360 1088 95.3 1142
50.2 L8 C6S/4 1255 1004 95.6 1050 1485 1188 95.4 1245
50.2 VL10 C6S/4 1380 1104 95.8 1152 1650 1320 95.7 1379
LSAM 52.3 S6 C6S/4 1650 1320 96.2 1372 - - - -
52.3 S7 C6S/4 1937 1550 96.2 1611 1950 1560 96.5 1617
52.3 L9 C6S/4 2085 1668 96.4 1730 2286 1828 96.5 1895
52.3 L12 C6S/4 2255 1804 96.4 1871 2510 2008 96.6 2079

kWe: electrical rating available from the alternator. kWm: necessary mechanical rating from the engine.
* Optional: SHUNT + PMG available.
** Efficiency and mechanical power (kWm) are calculated for 380V - 50Hz and 450V - 60Hz.

Electric Power Generation 9


BV – DNV – RINA – ABS – CCS – TL – PRS – RS
Class H
10 to 2350 kVA - 50 Hz / 11.5 to 2615 kVA - 60 Hz

TEMPERATURE RISE: Class H - 120°/45°


AREP* 1500 R.P.M. - 50 Hz - P.F. = 0.8 1800 R.P.M. - 60 Hz - P.F. = 0.8
380V ... 415V 380 V 440V ... 480V 450 V
4 P - 3 Ph + Neutral kVA kWe Effic.** kWm** kVA kWe Effic.** kWm**
LSAM 40 VS1 C6/4 10 8 83.4 9.6 11.5 9.2 84.5 10.9
40 VS2 C6/4 12.5 10 84.8 11.8 14.5 11.6 85.8 13.5
40 S3 C6/4 15 12 85.2 14.1 17.5 14 86.2 16.2
40 S4 C6/4 17.5 14 86 16.3 20 16 87 18.4
40 M5 C6/4 20 16 87 18.4 23 18.4 87.9 20.9
LSAM 42.3 VS1 C6/4 25 20 87.2 22.9 30 24 88.2 27.2
42.3 VS2 C6/4 27 21.6 87.5 24.7 32.5 26 88.5 29.4
42.3 VS3 C6/4 31 24.8 88.2 28.1 37 29.6 89.2 33.2
42.3 S4 C6/4 35 28 90 31.1 43 34.4 90.6 38
42.3 S5 C6/4 39.5 31.6 89.4 35.3 47 37.6 90.2 41.7
42.3 M7 C6/4 43 34.4 89.8 38.3 51.5 41.2 90.6 45.5
42.3 M8 C6/4 48 38.4 90.1 42.6 56.5 45.2 90.9 49.7
42.3 L9 C6/4 55 44 90.6 48.6 60 48 91.6 52
LSAM 44.3 S2 C6/4 70 56 92.2 61 88 70 92.4 76
44.3 S3 C6/4 80 64 91.9 70 100 80 92.3 87
44.3 S4 C6/4 90 72 92.6 78 113 90 92.9 97
44.3 S5 C6/4 100 80 92.3 87 125 100 92.7 108
44.3 M6 C6S/4 123 98 92.5 106 147 118 93.1 127
44.3 M8 C6/4 135 108 92.9 116 164 131 93.4 140
44.3 L10 C6S/4 150 120 93.3 129 184 147 93.7 157
44.3 VL13 C6/4 180 144 93.2 155 210 168 93.6 179
44.3 VL14 C6/4 195 156 92.9 168 230 184 93.4 197
LSAM 46.3 S4 C6/4 220 176 92.9 189 261 209 93.1 224
46.3 S5 C6/4 231 185 92.7 200 275 220 93 237
46.3 M7 C6S/4 261 209 93.4 224 307 246 93.6 263
46.3 M8 C6S/4 275 220 93.2 236 324 259 93.5 277
46.3 L10 C6/4 300 240 94.1 255 345 276 94.3 293
46.3 L11 C6/4 332 266 93.9 283 388 310 94.1 329
LSAM 47.3 VS3 C6/4 365 292 93.5 312 450 360 93.7 384
47.3 S4 C6S/4 400 320 94.2 340 500 400 94.3 424
47.3 S5 C6/4 450 360 94.6 381 530 424 94.8 447
47.3 M7 C6/4 500 400 94.7 422 625 500 94.7 528
47.3 M8 C6/4 530 424 94.4 449 630 504 94.7 532
47.3 L9 C6S/4 590 472 95.1 496 675 540 95.3 567
47.3 L10 C6S/4 610 488 95.2 513 755 604 95.3 634
LSAM 49.3 M6 C6S/4 730 584 94.6 617 840 672 94.7 710
49.3 M8 C6S/4 820 656 94.6 693 940 752 94.8 793
49.3 L9 C6S/4 910 728 95.3 764 1045 836 95.4 876
49.3 L10 C6S/4 971 777 95.3 815 1146 917 95.4 961
LSAM 50.2 M6 C6S/4 1195 956 94.9 1007 1420 1136 94.9 1197
50.2 L7 C6S/4 1290 1032 95.2 1084 1550 1240 95.1 1304
50.2 L8 C6S/4 1400 1120 95.4 1174 1685 1348 95.3 1414
50.2 VL10 C6S/4 1540 1232 95.6 1289 1840 1472 95.5 1541
LSAM 52.3 S6 C6S/4 1650 1320 96.2 1372 - - - -
52.3 S7 C6S/4 1950 1560 96.2 1622 1950 1560 96.5 1617
52.3 L9 C6S/4 2165 1732 96.3 1799 2325 1860 96.5 1928
52.3 L12 C6S/4 2350 1880 96.3 1952 2615 2092 96.5 2168

kWe: electrical rating available from the alternator. kWm: necessary mechanical rating from the engine.
* Optional: SHUNT + PMG available.
** Efficiency and mechanical power (kWm) are calculated for 380V - 50Hz and 450V - 60Hz.

10 Electric Power Generation


BV – DNV – RINA – ABS – CCS – TL
Class F
9 to 2255 kVA - 50 Hz / 10.5 to 2510 kVA - 60 Hz

TEMPERATURE RISE: Class F - 100°/45°


AREP* 1500 R.P.M. - 50 Hz - P.F. = 0.8 1800 R.P.M. - 60 Hz - P.F. = 0.8
380V ... 415V 380 V 440V ... 480V 450 V
4 P - 3 Ph + Neutral kVA kWe Effic.** kWm** kVA kWe Effic.** kWm**
LSAM 40 VS1 C6/4 9 7.2 83.9 8.6 10.5 8.4 84.8 9.9
40 VS2 C6/4 11.5 9.2 85.2 10.8 13.5 10.8 86 12.6
40 S3 C6/4 14 11.2 85.5 13.1 16.5 13.2 86.4 15.3
40 S4 C6/4 16 12.8 86.3 14.8 19 15.2 87.2 17.4
40 M5 C6/4 18.5 14.8 87.3 17 21.5 17.2 88.1 19.5
LSAM 42.3 VS1 C6/4 23 18.4 87.7 21 28.5 22.8 88.5 25.8
42.3 VS2 C6/4 25 20 88 22.8 30 24 88.8 27
42.3 VS3 C6/4 28.5 22.8 88.7 25.7 34 27.2 89.5 30.4
42.3 S4 C6/4 32 25.6 90.3 28.3 39 31.2 90.9 34.3
42.3 S5 C6/4 36.5 29.2 89.8 32.5 43.5 34.8 90.5 38.5
42.3 M7 C6/4 40 32 90.2 35.5 47.5 38 90.9 41.8
42.3 M8 C6/4 44 35.2 90.5 38.9 52 41.6 91.1 45.7
42.3 L9 C6/4 50.5 40.4 91 44.4 54.5 43.6 91.8 47.5
LSAM 44.3 S2 C6/4 64 51 92.3 55 80 64 92.5 69
44.3 S3 C6/4 73 58 92.1 63 91 73 92.4 79
44.3 S4 C6/4 82 66 92.7 71 102 82 93 88
44.3 S5 C6/4 91 73 92.5 79 114 91 92.9 98
44.3 M6 C6S/4 113 90 92.8 97 135 108 93.3 116
44.3 M8 C6/4 123 98 93.2 105 150 120 93.6 128
44.3 L10 C6S/4 137 110 93.5 118 169 135 93.8 144
44.3 VL13 C6/4 164 131 93.5 140 191 153 93.9 163
44.3 VL14 C6/4 180 144 93.2 155 210 168 93.6 179
LSAM 46.3 S4 C6/4 202 162 93.1 174 237 190 93.3 204
46.3 S5 C6/4 215 172 92.9 185 250 200 93.2 215
46.3 M7 C6S/4 240 192 93.6 205 280 224 93.7 239
46.3 M8 C6S/4 253 202 93.5 216 295 236 93.7 252
46.3 L10 C6/4 276 221 94.3 234 314 251 94.4 266
46.3 L11 C6/4 303 242 94.1 257 353 282 94.3 299
LSAM 47.3 VS3 C6/4 330 264 93.9 281 410 328 94 349
47.3 S4 C6S/4 375 300 94.4 318 455 364 94.5 385
47.3 S5 C6/4 400 320 94.8 338 480 384 94.9 405
47.3 M7 C6/4 450 360 94.9 379 561 449 95 473
47.3 M8 C6/4 475 380 94.7 401 575 460 94.9 485
47.3 L9 C6S/4 525 420 95.3 441 610 488 95.4 512
47.3 L10 C6S/4 590 472 95.3 495 681 545 95.5 571
LSAM 49.3 M6 C6S/4 660 528 94.8 557 760 608 94.8 641
49.3 M8 C6S/4 760 608 94.8 641 850 680 94.9 717
49.3 L9 C6S/4 820 656 95.5 687 940 752 95.5 787
49.3 L10 C6S/4 892 714 95.5 748 1031 825 95.5 864
LSAM 50.2 M6 C6S/4 1080 864 95.1 909 1300 1040 95 1095
50.2 L7 C6S/4 1175 940 95.4 985 1390 1112 95.3 1167
50.2 L8 C6S/4 1270 1016 95.5 1064 1520 1216 95.4 1275
50.2 VL10 C6S/4 1390 1112 95.8 1161 1670 1336 95.6 1397
LSAM 52.3 S6 C6S/4 1650 1320 96.2 1372 - - - -
52.3 S7 C6S/4 1937 1550 96.2 1611 1950 1560 96.5 1617
52.3 L9 C6S/4 2085 1668 96.4 1730 2286 1828 96.5 1895
52.3 L12 C6S/4 2255 1804 96.4 1871 2510 2008 96.6 2079

kWe: electrical rating available from the alternator. kWm: necessary mechanical rating from the engine.
* Optional: SHUNT + PMG available.
** Efficiency and mechanical power (kWm) are calculated for 380V - 50Hz and 450V - 60Hz.

Electric Power Generation 11


PRS – RS
Class F
9 to 2172 kVA - 50 Hz / 10.5 to 2418 kVA - 60 Hz

TEMPERATURE RISE: Class F - 95°/45°


AREP* 1500 R.P.M. - 50 Hz - P.F. = 0.8 1800 R.P.M. - 60 Hz - P.F. = 0.8
380V ... 415V 380 V 440V ... 480V 450 V
4 P - 3 Ph + Neutral kVA kWe Effic.** kWm** kVA kWe Effic.** kWm**
LSAM 40 VS1 C6/4 9 7.2 83.9 8.5 10.5 8.4 84.8 9.9
40 VS2 C6/4 11.5 9.2 85.2 10.8 13.5 10.8 86 12.6
40 S3 C6/4 14 11.2 85.5 13.1 16.5 13.2 86.4 15.3
40 S4 C6/4 16 12.8 86.3 14.8 19 15.2 87.2 17.4
40 M5 C6/4 18.5 14.8 87.3 17 21.5 17.2 88.1 19.5
LSAM 42.3 VS1 C6/4 20 16 88.3 18.1 25 20 88.9 22.5
42.3 VS2 C6/4 24 19.2 88.2 21.8 29 23.2 88.9 26.1
42.3 VS3 C6/4 28 22.4 88.8 25.2 33.5 26.8 89.6 29.9
42.3 S4 C6/4 32 25.6 90.3 28.3 39 31.2 90.9 34.3
42.3 S5 C6/4 35.5 28.4 89.9 31.6 42 33.6 90.7 37
42.3 M7 C6/4 39 31.2 90.3 34.6 46.5 37.2 91 40.9
42.3 M8 C6/4 43 34.4 90.6 38 50.5 40.4 91.2 44.3
42.3 L9 C6/4 49 39.2 91.1 43 54.5 43.6 91.8 47.5
LSAM 44.3 S2 C6/4 64 51 92.3 55 80 64 92.5 69
44.3 S3 C6/4 73 58 92.1 63 91 73 92.4 79
44.3 S4 C6/4 82 66 92.7 71 102 82 93 88
44.3 S5 C6/4 91 73 92.5 79 114 91 92.9 98
44.3 M6 C6S/4 111 89 92.8 96 131 105 93.3 113
44.3 M8 C6/4 123 98 93.2 105 146 117 93.6 125
44.3 L10 C6S/4 137 110 93.5 118 165 132 93.9 141
44.3 VL13 C6/4 160 128 93.6 137 190 152 93.9 162
44.3 VL14 C6/4 176 141 93.3 151 205 164 93.7 175
LSAM 46.3 S4 C6/4 197 158 93.2 170 230 184 93.3 197
46.3 S5 C6/4 215 172 92.9 185 243 194 93.2 208
46.3 M7 C6S/4 233 186 93.6 199 271 217 93.8 231
46.3 M8 C6S/4 246 197 93.5 211 286 229 93.7 244
46.3 L10 C6/4 265 212 94.3 225 304 243 94.4 257
46.3 L11 C6/4 300 240 94.1 255 341 273 94.3 290
LSAM 47.3 VS3 C6/4 330 264 93.9 281 410 328 94 349
47.3 S4 C6S/4 375 300 94.4 318 455 364 94.5 385
47.3 S5 C6/4 400 320 94.8 338 480 384 94.9 405
47.3 M7 C6/4 450 360 94.9 379 561 449 95 473
47.3 M8 C6/4 475 380 94.7 401 575 460 94.9 485
47.3 L9 C6S/4 525 420 95.3 441 610 488 95.4 512
47.3 L10 C6S/4 580 464 95.3 487 681 545 95.5 571
LSAM 49.3 M6 C6S/4 650 520 94.8 549 760 608 94.8 641
49.3 M8 C6S/4 745 596 94.8 629 850 680 94.9 717
49.3 L9 C6S/4 820 656 95.5 687 940 752 95.5 787
49.3 L10 C6S/4 870 696 95.5 729 1031 825 95.5 864
LSAM 50.2 M6 C6S/4 1070 856 95.2 899 1275 1020 95.1 1073
50.2 L7 C6S/4 1165 932 95.4 977 1360 1088 95.3 1142
50.2 L8 C6S/4 1255 1004 95.6 1050 1485 1188 95.4 1245
50.2 VL10 C6S/4 1380 1104 95.8 1152 1650 1320 95.7 1379
LSAM 52.3 S6 C6S/4 1650 1320 96.2 1372 - - - -
52.3 S7 C6S/4 1867 1496 96.3 1551 1950 1560 96.5 1617
52.3 L9 C6S/4 2002 1601 96.4 1661 2325 1860 96.6 1925
52.3 L12 C6S/4 2172 1737 96.5 1801 2418 1934 96.6 2003

kWe: electrical rating available from the alternator. kWm: necessary mechanical rating from the engine.
* Optional: SHUNT + PMG available.
** Efficiency and mechanical power (kWm) are calculated for 380V - 50Hz and 450V - 60Hz.

12 Electric Power Generation


Notes

Electric Power Generation 13


BV – DNV – RINA – PRS – ClassNK – RS – LR – ABS – KRS – CCS – TL
Class H – 21.5 to 2290 kVA - 50 Hz
Class F – 19.5 to 2055 kVA - 50 Hz

TEMPERATURE RISE: Class H - 120°/45° - 110°/45° Class F - 100°/45° - 95°/45°


AREP* 1500 R.P.M. - 50 Hz - P.F. = 0.8 1500 R.P.M. - 50 Hz - P.F. = 0.8
690V 690 V 690V 690 V
4 P - 3 Ph + Neutral kVA kWe Effic. kWm kVA kWe Effic. kWm
LSAM 42.3 VS1 C10/4 21.5 17.2 86.7 19.8 19.5 15.6 87 17.9
42.3 VS2 C10/4 23 18.4 86.9 21.2 21 16.8 87.3 19.2
42.3 VS3 C10/4 27 21.6 88.4 24.4 25 20 88.6 22.6
42.3 S4 C10/4 28 22.4 89.8 24.9 27 21.6 89.9 24
42.3 S5 C10/4 34 27.2 89.3 30.5 30.9 24.7 89.6 27.6
42.3 M7 C10/4 38.5 30.8 89.6 34.4 35 28 90 31.1
42.3 M8 C10/4 42.5 34 90 37.8 38.5 30.8 90.3 34.1
42.3 L9 C10/4 49 39.2 90 43.6 44 35.2 90.3 39
LSAM 44.3 S2 C10/4 76 61 90.3 68 65 52 90.6 57
44.3 S3 C10/4 80 64 90.2 71 70 56 90.5 62
44.3 S4 C52/4 85 68 92 74 75 60 92.2 65
44.3 S5 C52/4 90 72 91.8 78 80 64 92.1 69
44.3 M6 C52/4 95 76 92.4 82 90 72 92.6 78
44.3 M8 C52/4 111 89 92.7 96 101 81 92.8 87
44.3 L10 C52/4 128 102 92.8 110 117 94 92.9 101
44.3 VL13 C10/4 160 128 93.3 137 145 116 93.5 124
44.3 VL14 C10/4 170 136 93.1 146 160 128 93.3 137
LSAM 46.3 S4 C10/4 200 160 93.1 172 180 144 93.2 155
46.3 S5 C10/4 210 168 93 181 190 152 93.2 163
46.3 M7 C10/4 240 192 93.1 206 216 173 93.2 186
46.3 M8 C10/4 253 202 93 217 230 184 93.1 198
46.3 L10 C52S/4 270 216 94.1 230 240 192 94.3 204
46.3 L11 C52S/4 282 226 94 240 256 205 94.2 218
LSAM 47.3 S4 C52T/4 350 280 94.8 295 319 255 94.9 269
47.3 S5 C52S/4 400 320 94.5 339 364 291 94.7 307
47.3 M7 C52S/4 450 360 94.8 380 400 320 95 337
47.3 M8 C52S/4 465 372 94.7 393 425 340 94.9 358
47.3 L9 C10S/4 515 412 94.9 434 480 384 94.9 405
47.3 L10 C10S/4 565 452 95.2 475 520 416 95.3 437
LSAM 49.3 S4 C10S/4 615 492 94.4 521 550 440 94.6 465
49.3 M6 C10S/4 680 544 94.3 577 600 480 94.4 508
49.3 M8 C10S/4 700 560 94.7 591 650 520 94.8 549
49.3 L9 C10S/4 800 640 95.1 673 725 580 95.3 609
49.3 L10 C10S/4 850 680 95.1 715 775 620 95.3 651
LSAM 50.2 M6 C52S/4 1030 824 95.1 866 960 768 95.2 807
50.2 L7 C52S/4 1100 880 95.4 922 1030 824 95.5 863
50.2 L8 C52S/4 1215 972 95.6 1017 1125 900 95.7 940
50.2 VL10 C52S/4 1385 1108 95.8 1157 1290 1032 95.9 1076
LSAM 52.3 S6 C52S/4 1655 1324 95.9 1381 1485 1188 96 1238
52.3 S7 C52S/4 1870 1496 96 1559 1680 1344 96 1399
52.3 L9 C52S/4 1990 1592 96.1 1657 1785 1428 96.1 1486
52.3 L12 C52S/4 2290 1832 96.1 1907 2055 1644 96.1 1711

kWe: electrical rating available from the alternator. kWm: necessary mechanical rating from the engine.
* Optional: SHUNT + PMG available.

14 Electric Power Generation


BV – DNV – RINA – PRS – ClassNK – RS – LR – ABS – KRS – CCS – TL
Class H – 26 to 2365 kVA - 60 Hz
Class F – 24 to 2121 kVA - 60 Hz

TEMPERATURE RISE: Class H - 120°/45° - 110°/45° Class F - 100°/45° - 95°/45°


AREP* 1800 R.P.M. - 60 Hz - P.F. = 0.8 1800 R.P.M. - 60 Hz - P.F. = 0.8
690V 690 V 690V 690 V
4 P - 3 Ph + Neutral kVA kWe Effic. kWm kVA kWe Effic. kWm
LSAM 42.3 VS1 C22T/4 26 20.8 87.3 23.8 24 19.2 87.5 21.9
42.3 VS2 C22T/4 28 22.4 87.8 25.5 25 20 88.1 22.7
42.3 VS3 C22T/4 32.5 26 88.8 29.3 29 23.2 89 26.1
42.3 S4 C22T/4 35.5 28.4 90.2 31.5 34 27.2 90.3 30.1
42.3 S5 C22T/4 41.5 33.2 90 36.9 37.5 30 90.2 33.3
42.3 M7 C22T/4 45 36 90.6 39.7 40.5 32.4 90.9 35.6
42.3 M8 C22T/4 49 39.2 90.1 43.5 43.5 34.8 90.2 38.6
42.3 L9 C22T/4 57.5 46 90.8 51 51 40.8 91 44.8
LSAM 44.3S2 C22TS/4 85 68 91.1 75 75 60 91.1 66
44.3S3 C22TS/4 91 73 91.1 80 80 64 91.1 70
44.3S4 C22T/4 100 80 91.6 87 90 72 91.5 79
44.3S5 C22T/4 110 88 91.5 96 95 76 91.6 83
44.3M6 C22T/4 124 99 91.7 108 105 84 91.7 92
44.3M8 C22TS/4 129 103 92.6 111 115 92 92.6 99
44.3L10 C22T/4 155 124 93.1 133 140 112 93.2 120
44.3 VL13 C22T/4 185 148 93.4 158 165 132 93.4 141
44.3 VL14 C22T/4 206 165 93.3 177 185 148 93.4 158
LSAM 46.3 S4 C22T/4 240 192 93.1 206 213 170 93.1 183
46.3 S5 C22T/4 250 200 93 215 225 180 93.1 193
46.3 M7 C22TS/4 270 216 93.5 231 240 192 93.5 205
46.3 M8 C22TS/4 287 230 93.5 246 255 204 93.5 218
46.3 L10 C22T/4 300 240 94.2 255 270 216 94.2 229
46.3 L11 C22T/4 330 264 94.1 281 295 236 94.2 251
LSAM 47.3 S4 C22TS/4 456 365 94.6 386 415 332 94.8 350
47.3 S5 C23/4 480 384 94.7 405 437 350 94.8 369
47.3 M7 C23/4 530 424 94.9 447 500 400 95 421
47.3 M8 C23/4 550 440 94.8 464 515 412 94.9 434
47.3 L9 C22T/4 605 484 94.5 512 540 432 94.4 458
47.3 L10 C22T/4 650 520 95.2 546 580 464 95.2 487
LSAM 49.3 S4 C22TS/4 700 560 93.8 597 625 500 93.9 532
49.3 M6 C22TS/4 800 640 94.5 677 750 600 94.6 634
49.3 M8 C22TS/4 860 688 94.7 727 800 640 94.8 675
49.3 L9 C22TS/4 900 720 94.6 761 850 680 94.6 719
49.3 L10 C22TS/4 950 760 95 800 900 720 95 758
LSAM 50.2 S4 C23S/4 1080 864 94.6 913 970 776 94.6 820
50.2 M6 C22S/4 1220 976 95.1 1026 1090 872 95.1 917
50.2 L8 C23S/4 1440 1152 95.4 1208 1290 1032 95.5 1081
50.2 VL10 C22S/4 1625 1300 95.7 1358 1450 1160 95.7 1212
LSAM 52.3 S6 C22S/4 1800 1440 96 1500 1646 1316 96 1372
52.3 S7 C22S/4 2128 1702 95.9 1775 1909 1527 96 1591
52.3 L9 C22S/4 2175 1740 96.3 1807 1952 1561 96.2 1623
52.3 L12 C22S/4 2365 1892 96.6 1959 2121 1697 96.6 1757

kWe: electrical rating available from the alternator. kWm: necessary mechanical rating from the engine.
* Optional: SHUNT + PMG available.

Electric Power Generation 15


www.leroy-somer.com/epg

Connect with us at:

© 2024 Moteurs Leroy-Somer SAS. The information contained in this brochure is for guidance only and
does not form part of any contract. The accuracy cannot be guaranteed as Moteurs Leroy-Somer SAS
have an ongoing process of development and reserve the right to change the specification of their products
without notice.
Moteurs Leroy-Somer SAS. Headquarters: Bd Marcellin Leroy, CS 10015, 16915 Angoulême Cedex 9,
France. Share Capital: 32,239,235 €, RCS Angoulême 338 567 258.

4715 en - 2024.02 / p