InteliMain
s 1010
Order code: IM31010XBBB
Mains supervision/Utility breaker controller
Datasheet
Double redundancy of the communication line with other
Product description controllers allows usage in complex applications like Data centres
True RMS measurement is used with Voltage, Current and Power and others
measurement. For easy handling for operators or troubleshooting purposes the
Comprehensive Mains/Utility breaker controller for any site InteliMains 1010 offers up to 31 characters in text fields which
Synchronize set of gen-sets to the Mains/Utility when needed makes Parameters, Values and Alarms self-explanatory and easy
to handle for anyone
Acts as Mains protection relay
Pre-programmed functions allow fast and easy system set-up Application overview
Large in-built PLC interpreter allows customization at no extra
costs
Key features
Hardware compliant to the latest switchgear market needs
Supports latest Grid codes requirements from Europe, USA or
Australia
Cooperates with other controllers forming a solution with up to 64
units without any extra repeaters or extensions
Concept of pre-programmed functions and internal PLC
interpreter allows to make the basic solution fast and easy. Shall
the project require any specific requirements this can be done
easily at no extra costs and with minimum effort or programming
skills
Cybernetic security by design, based on the ANSI/ISA-62443
standard
Handles large number of simultaneously connected clients like
HMIs, SCADA, BMS and others, allowing easy and convenient
monitoring from both local and remote areas
AirGate 2.0 allows faster, more reliable remote connection from all
around the world
Modbus client (master) functionality allows easy integration of
Modbus based devices into the InteliMains 1010 to benefit from
provided data – e.g. diagnostics
Load transfer from gen-sets back to Mains/Utility is adjustable,
with an option of short time parallel operation, even below 100ms
| InteliMains 1010 3.1.0 Datasheet | Related HW ver: 1.1.0.0 | Related SW ver: 3.1.0 | Date of issue: 4/30/2024
Terminals and dimensions
InteliMains 1010 3.1.0 Datasheet 2
Technical data Binary inputs
Number 12, non-isolated
Power supply Close/Open 0-2 V DC close contact
Power supply range 8-36 V DC indication 6-36 V DC open contact
Power consumption 16 W Configurable Pull-up / Pull-down
RTC battery Replaceable, type CR1632 3V Pulse input Bin 9 and 10 max. 50 Hz
Fusing power 8A Binary outputs
Consumption 2.5 A Controller + 10 x 0.5 A BOUTs @ 8 V
Number 12, non-isolated
Fusing E-STOP 1A
Max. current 0.5 A
Max. Heat Dissipation 16 W
Switching to Positive supply terminal
Operating conditions
Analog inputs
Operating temperature -40 °C to +70 °C
Number 4, switchable (R/U/I)
Storage temperature -40 ˚C to +80 ˚C
Range R = 0-10000 Ω; U = 0-10 V; I = 0-20 mA
25/55°C, 48hours,95 % non-
Operating humidity (norm R: 2 % from value for 0-250 Ω
condensing
60068-2-30) R: 4% from value for 250-2500 Ω
(EN 60068-2-30)
Accuracy R: 6 % from value for 5000-10000 Ω
Protection degree IP20 U: 1% from value ±100 mV
5-25 Hz, ± 1.6 mm I: 1% from value ±200 uA
Vibration
25-100 Hz, a = 4 g
Shocks a = 500 m/s
2 Voltage regulator outputAnalog output 1
Surrounding air temperature rating 70 °C. Protection Reinforced isolation
Suitable for pollution degree 2. Switchable: U ±10 V, I ±20 mA, PWM: 0 V/5
Type
V
AC Current measurement
U: 1 % from value ±100 mV
3ph Mains (Bus Left) current Accuracy
I: 1 % from value ±200 uA
Measurement inputs 1ph Bus (Bus Right) current (Auxiliary
current)
Analog output 2
Measurement range 1A/5A
Protection Basic isolation
Maximum continuous
2 A / 10 A Type Switchable: U ±10 V, I ±20 mA, PWM: 0 V/5 V
current
Allowed overload 18 A for 15 sec. U: 1 % from value ±100 mV
Accuracy
±3 mA / ±15 mA for 0.0 to 0.4 A / 0.0 to 2.0 I: 1 % from value ±200 uA
Accuracy A0.75 % of value for 0.4 to 1.0 A / 2.0 to
5.0 A
Communications
Frequency range 40-70 Hz (accuracy 0.002 %) USB Device Basic isolation, USB type B
Input impedance < 0.1 Ω RS 485 Basic isolation
ETH1
AC Voltage measurement ETH2 10/100 Mbit
3ph-n Mains (Bus Left) voltage ETH3
Measurement inputs
3ph-n Bus (Bus Right) voltage CAN 1A
115 V ph-N / 200 V ph-ph CAN 2A Basic isolation, 1000/250/50 kbps
CAN 1B , nominal impedance 120 Ω
suitable also for VTs output
Measurement range CAN 2B
231 V ph-N / 400 V ph-ph
UL, cUL: 346 V ph-N / 600 V ph-ph
Weight
Linear measurement Controller 750 g
and protection range 433 V ph-N / 750 V ph-ph Package 920 g
(maximal voltage)
Controller handles 300 million records into the History, which represents
Accuracy 0.25 % roughly 1 record per second during 9,5 years. Shall be the History recording
Frequency range 40-70 Hz (accuracy 0.002 %) faster, the controller lifetime will become smaller.
Input impedance 0.72 MΩ ph-ph , 0.36 MΩ ph-n
Upper-harmonics Active Low-Pass filter, Cutoff frequency
filtering 3100Hz (-3bB)
Measurement category CAT III, overvoltage category III
E-Stop
Physically disconnects BO 1 & BO 2 from power supply.
InteliMains 1010 3.1.0 Datasheet 3
Available plug-in modules
Product Description Order code
CM-4G-GPS An easy-to-use and highly efficient solution for connecting the controllers online via 4G network. CM24GGPSXBX
CM-RS232-485 Communication module enabling integration of the controller into the local monitoring system CM223248XBX
*EM-BIO8-EFCP Binary I/O plug-in module with 8 binary inputs or outputs. EM2BIO8EXBX
Note: Controller has 2 slots for plug-in modules.
Note: *EFCP is already included on the CU as aux current measurement, EFCP on BIO8 module is not available.
Available external displays
Product Description Order code
InteliVision 5.2 5" TFT external display with 800x480 px resolution RD2IV5BXBAA
InteliVision 10Touch 10.1" Touchscreen display uni with 1280 x 800 px resolution RD1IV10TBPF
InteliVision 13Touch 13.3" Marine certified display unit with 1920 × 1080 px resolution RD1IV13TBME
InteliVision 18 18.5" Touchscreen display unit with 1366 × 768 px resolution RD31840PBIE
Available CAN modules
Product Description Order code
Inteli AIN8 8 Analog Input Channels and 1 RPM/Impulse Input Module I-AIN8
Inteli AIN8TC 8 Analog Input Channels for termocouples measurement I-AIN8TC
4 Analog Inputs for differential voltage measurement, 4 Analog Input equipment
Inteli AIO9/1 I-AIO9/1
channels, 1 Analog Input for resistance measurement and 1 Analog Output
Inteli IO8/8 16 Configurable Binary Inputs/Outputs and Analog Outputs Module I-IO8/8
IGL-RA15 Remote Annunciator w/ 15 programmable LEDs EM2IGLRABAA
IGS-PTM 4 Analog Inputs, 1 Analog Output, 8 Binary Inputs and 8 Binary Outputs IGS-PTM
I-AOUT8 8 configurable analog outputs I-AOUT8
IS-AIN8 8 configurable analog inputs IS-AIN8
IS-BIN16/8 16 galvanically separated inputs, 8 binary outputs, 2 pulse inputs IS-BIN16/8
InteliFieldbus Gateway Modbus TCP/RTU Communication gateway CM1IFGATBBB
CAN Repeater Module, compatible when using 32C/8C CAN Intercontroller Comm
I-CR I-CR
Mode
Communication gateway with configurable interfaces between Modbus TCP/RTU,
InteliGateway 300 ComAp CAN, WebSupervisor and InteliScada protocols allowing user-defined CM2GW300BAB
interconnection of all attached devices
Functions and protections
Support of functions and protections as defined by ANSI (American National Standards Institute):
Description ANSI code Description ANSI code
Master unit 1 Temperature monitoring 49T
Multi-function device 11 Overcurrent 50/50TD
Speed and frequency matching device 15 Overcurrent IDMT 51
Data communications device 16ECFM+16SC AC circuit breaker 52
Synchronizing-check 25 Power factor 55
Thermal relay 26 Overvoltage 59
Undervoltage 27 Pressure switch 63
Annunciator 30 Liquid level switch 71
Overload 32 Alarm relay * 74
Load shedding 32P Vector shift 78
E-mail: [email protected]
Web: www.comap-control.com
© ComAp. Features and specification are subject to change without prior notice.
Master sequence device 34 Reclosing relay 79
Undercurrent 37 Overfrequency 81H
Unit sequence starting 44 Underfrequency 81U
Current unbalance 46 ROCOF 81R
Voltage unbalance 47 Auto selective control/transfer 83
Incomplete sequence relay 48 Regulating device 90
* extension module IGL-RA15 required
Certifications and standards
EN 61000-6-2 EN 60068-2-1 (-40 °C/16 h) UL6200 *
EN 61000-6-4 EN 60068-2-2 (70 °C/16 h) UKCA
EN 61010-1 EN 60068-2-6 (2÷25 Hz / ±1,6 mm; 25÷100 Hz / 4,0
EN 60255-1 g)
2
EN 60529 (IP20) EN 60068-2-27 (a=500 m/s ; T=6 ms)
EN 60068-2-30 (25/55 °C, RH 95%, 48 h)
* ULC 6200:2019 Certified (see the NFL File for the FW version with the Witness test if it is required by the certification of the end product)
Grid Codes
European Requirements for Generators, 2016/631
German VDE-AR-N 4110:2018 UK ENA EREC G99
American IEEE 1547 Austrian TOR
List of SW Key Features
SW Key Feature Order Code
CAN bus redundancy SKREDCAN201
Hot Swap Redundancy SKHOTSWAP01
Modbus Client SKMODBCLI01
PLC package SKPLCPCKG01
E-mail: [email protected]
Web: www.comap-control.com
© ComAp. Features and specification are subject to change without prior notice.