Solution Ex3 Rectifier
Solution Ex3 Rectifier
1-1 R is neglected. Give the relationship between Vc1 and Vc2 (average values of vc1(t) and vc2(t)
respectively)
𝑑𝐼
𝑣𝑐1(𝑡) − 𝑅. 𝐼(𝑡) − 𝐿 ∙ + 𝑣𝑐2(𝑡) = 0
𝑑𝑡
𝑑𝐼
R is neglected, and the average value of 𝐿 ∙ is zero. Thus:
𝑑𝑡
Vc1 = -Vc2
Then deduce a relationship between 1 and 2.
3.U . 2 3.U . 2
Since Vc1 cos 1 and Vc2 cos 2 with same phase to phase voltage on the French
and UK sides, this leads to
𝛼1 = 𝜋 − 𝛼2
1-2 Operating with 1 = 30°on the French side and with I = 1 850 A,
Calculate 2
𝛼2 = 150°
Compute the exchanged power. What is the direction of the power flow?
I is supposed constant, therefore, P = Vc1 . I = - Vc2 . I (both are in generator convention, so one must be
negative since power is transferred from converter 1 to converter 2 or vice versa)
P = 255MW
Show that the connexion is reversible despite the unidirectional current flow.
The connexion is reversible since Vc1 and Vc2 can change sign. P1 is positive (and P2 is negative) when 1
<90° (and 2 > 90°). P1 becomes negative (and P2 positive) when 1 > 90° (and 2 < 90°).
1-3 The frequencies f1 and f2 are equal to 50 Hz. Is it necessary to have the same frequencies in the
same way as it is the case for 2 alternators in parallel on the same network ? (synchronous
connection).
No since there is a DC link between the two rectifiers so the two rectifiers can see different frequencies on the
AC side
2 – R is no longer neglected and taken equal to R = 3.1 ,, but L is big enough to neglect I current ripple.
2-1 What is the relationship between Vc1, Vc2 and I?
𝑑𝐼
𝑣𝑐1(𝑡) − 𝑅. 𝐼(𝑡) − 𝐿 ∙ + 𝑣𝑐2(𝑡) = 0
𝑑𝑡
So
𝑉𝑐1 − 𝑅. 𝐼 + 𝑉𝑐2 = 0
cos(1) = -0.902, 1 = 25,6° (a bit less than 30° to generate a higher voltage on side 1 to anticipate the resistive
voltage drop)
P1 = Vc1.I = 265.9 MW
P2 = Vc2.I = -255.3 MW
Is the difference predictable and computable?
The value of vc1(t) is obtained by summing these two voltages. It is not displayed in this figure, it will be
displayed in the following one. The frequency is twice the frequency of vc1' and vc1'' thus 12 times the grid
frequency.
v
What is the period of vc1(t) ? What is its relative ripple: ?
Vc1
The frequency is twice the frequency of vc1' and vc1'' thus 12 times the grid frequency.
v v'
What is the relationship between and (question 3-2) ?
Vc1 V' c1
v' 166.9 83.4
0.6 (V'c1 = 138kV with 1 = 30°)
V'c1 138
To compute the ratio with two bridge delayed by 30°, the most simple is to measure it on the graph. This
ripple can also be computed mathematically (but this is not really useful):
We obtain Vc1(max) as follows:
𝑉𝑐1 ′ (max) = 𝑈. √2. sin(90°) = 166.9 kV. At this time, 𝑉𝑐1 ′′ = 𝑈. √2. sin(90° − 30°) = 144.5 kV (since
voltage of Vc2'' is lagging 30°). Thus Vc1(max) = 311.4 kV
We obtain Vc1(min) as follows:
𝑉𝑐1 ′ (min) = 𝑈. √2. sin(90° + 60°) = 83.4 kV. At this time, 𝑉𝑐1 ′′ = 𝑈. √2. sin(90° + 60° − 30°) = 144.5 kV
(since voltage of Vc2'' is lagging 30°). Thus Vc1(min) = 227.9 kV
Therefore
v 311.4 227.9
0.3 (Vc1 = 276kV with 1 = 30°) – This is half voltage ripple (what can be seen on the
Vc1 276
figure below comparing 2.v'c1 and vc1
4–
Compute the active power flow P as well as the reactive one Q.
With 1 = 30°, the French side is delivering Active power to UK. Reactive Power is ABSORBED
With 1 = 30°, the UK side is receiving Active power from France. Reactive Power is ABSORBED to UK
side