870 43 12 Technical Documentation Sika AnchorFix 2+ 09 2016 1 - Compressed

Download as pdf or txt
Download as pdf or txt
You are on page 1of 30

Technical Documentation

Sika AnchorFix®-2+
Product Information
Sika Services AG
TABLE OF CONTENTS
Sika AnchorFix®-2+ 3
Installation Parameters of Threaded Bars 5
Installation Parameters of Reinforcing Bars Used as Anchors 5
Theoretical Number of Fixings Per Cartridge 6
Steel Failure Information - Threaded Bars 7
®
Using Sika AnchorFix -2+ with Threaded Bars 8
Tension load calculations for combined concrete cone & pullout failure at various embedment depths 8
Tension load calculations for combined concrete cone & pullout failure at 8d embedment depth 9
Tension load calculations for combined concrete cone & pullout failure at std embedment depth 11
Tension load calculations for combined concrete cone & pullout failure at 20d embedment depth 13
®
Using Sika AnchorFix -2+ with Threaded Bars 15
Tension load calculations for combined concrete cone & pullout failure at various embedment depths 15
Tension load calculations for combined concrete cone & pullout failure at std embedment depth 18
Tension load calculations for combined concrete cone & pullout failure at 20d embedment depth 20
®
Using Sika AnchorFix -2+ with Reinforcing Bars 21
Tension load calculations for combined concrete cone & pullout failure at various embedment depths 22
Tension load calculations for combined concrete cone & pullout failure at 8d embedment depth 23
Tension load calculations for combined concrete cone & pullout failure at std embedment depth 25
Tension load calculations for combined concrete cone & pullout failure at 20d embedment depth 27
Using Sika AnchorFix®-2+ With Post-installed Rebar Connections 29
Design bond strength values 29
Important Notes 30

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

2/30
SIKA ANCHORFIX®-2+

Chemical Resistance
The chemical mortar has undergone extensive chemical resistance testing. The results are summarised in the table below.
Chemical Environment Concentration Result
Aqueous Solution Acetic Acid 10% 
Acetone 100% 
Aqueous Solution Aluminium Chloride Saturated 
Aqueous Solution Aluminium Nitrate 10% 
Ammonia Solution 5% 
Jet Fuel 100% 
Benzene 100% 
Benzoic Acid Saturated 
Benzyl Alcohol 100% 
Sodium Hypochlorite Solution 5 - 15% C
Butyl Alcohol 100% C
Calcium Sulphate Aqueous Solution Saturated 
Carbon Monoxide Gas 
Carbon Tetrachloride 100% 
Chlorine Water Saturated 
Chloro Benzene 100% 
Citric Acid Aqueous Solution Saturated 
Cyclohexanol 100% 
Diesel Fuel 100% 
Diethylene Glycol 100% 
Ethanol 95% C
Ethanol Aqueous Solution 20% C
Heptane 100% 
Hexane 100% C
10% 
Hydrochloric Acid 15% 
25% C
Hydrogen Sulphide Gas 100% 
Isoproyl Alcohol 100% C
Linseed Oil 100% 
Lubricating Oil 100% 
Mineral Oil 100% 
Paraffin / Kerosene (Domestic) 100% 
Phenol Aqueous Solution 1% 
Phosphoric Acid 50% 
Potassium Hydroxide 10% / pH13 C
Sea Water 100% 
Styrene 100% 
Sulphur Dioxide Solution 10% 
Sulphur Dioxide (40°C) 5% 

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

3/30
10% 
Sulphuric Acid
50% 
Turpentine 100% C
White Spirit 100% 
Xylene 100% 
 = Resistant to 75°C with at least 80% of physical properties retained.
C = Contact only to a maximum of 25°C.
 = Not Resistant

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

4/30
INSTALLATION PARAMETERS OF THREADED BARS
Size M8 M10 M12 M16 M20 M24 M27 M30

Nominal drill hole diameter Ød0 [mm] 10 12 14 18 22 26 30 35

Diameter of cleaning brush db db [mm] 14 14 20 20 29 29 40 40

Torque moment Tinst Tinst [Nm] 10 20 40 80 150 200 240 275

hef,min = 8d

Depth of drill hole h0 h0 [mm] 64 80 96 128 160 192 216 240

Minimum edge distance cmin cmin [mm] 35 40 50 65 80 96 110 120

Minimum spacing smin smin [mm] 35 40 50 65 80 96 110 120

Minimum thickness of member hmin hmin [mm] hef + 30 mm ≥ 100 mm hef + 2d0

hef,max = 20d

Depth of drill hole h0 h0 [mm] 160 200 240 320 400 480 540 600

Minimum edge distance cmin cmin [mm] 80 100 120 160 200 240 270 300

Minimum spacing smin smin [mm] 80 100 120 160 200 240 270 300

Minimum thickness of member hmin hmin [mm] hef + 30 mm ≥ 100 mm hef + 2d0

INSTALLATION PARAMETERS OF REINFORCING BARS USED AS ANCHORS


Size Ø8 Ø10 Ø12 Ø16 Ø20 Ø25 Ø32

Nominal drill hole diameter Ød0 [mm] 12 14 16 20 25 32 40

Diameter of cleaning brush db db [mm] 14 14 19 22 29 40 42

hef,min = 8d

Depth of drill hole h0 h0 [mm] 64 80 96 128 160 200 256

Minimum edge distance cmin cmin [mm] 35 40 50 65 80 100 130

Minimum spacing smin smin [mm] 35 40 50 65 80 100 130

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

5/30
Minimum thickness of member hmin hmin [mm] hef + 30 mm ≥ 100 mm hef + 2d0

hef,max = 20d

Depth of drill hole h0 h0 [mm] 160 200 240 320 400 500 640

Minimum edge distance cmin cmin [mm] 80 100 120 160 200 250 320

Minimum spacing smin smin [mm] 80 100 120 160 200 250 320

Minimum thickness of member hmin hmin [mm] hef + 30 mm ≥ 100 mm hef + 2d0

THEORETICAL NUMBER OF FIXINGS PER CARTRIDGE


Applies to installations in solid substrates only

M8 M10 M12 M16 M20 M24


Cartridge
hef
Volume Drilling Ø Drilling Ø Drilling Ø Drilling Ø Drilling Ø Drilling Ø
10mm 12mm 14mm 18mm 22mm 26mm

8d 148 91 60 32 19 12

10d 118 72 48 26 15 9
410 ml

STD 118 81 52 32 17 11

12d 98 60 40 21 12 8

8d 106 65 43 23 13 8

10d 85 52 34 18 11 7
300 ml

STD 85 58 38 23 12 8

12d 71 43 29 15 9 5

Note: Jobsite/contractor installations usually result in more resin being injected than the theoretical requirement resulting in lower number of fixings per cartridge. The reduction to the number of
fixings per cartridge in practice is greater for smaller diameter holes and shallower embedment depths.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

6/30
STEEL FAILURE INFORMATION - THREADED BARS
Characteristic resistance values to tension load
Steel Failure - Characteristic resistance
Size M8 M10 M12 M16 M20 M24 M27 M30
Steel grade 4.6 NRk,s [kN] 15 23 34 63 98 141 184 224
Partial safet y factor Ms [-] 2
Steel grade 5.8 NRk,s [kN] 18 29 42 79 123 177 230 281
Partial safety factor Ms [-] 1.5
Steel grade 8.8 NRk,s [kN] 29 46 67 126 196 282 367 449
Partial safety factor Ms [-] 1.5
Steel grade 10.9 NRk,s [kN] 37 58 84 157 245 353 459 561
Partial safety factor Ms [-] 1.4
Stainless steel grade A4-70 NRk,s [kN] 26 41 59 110 172 247 321 393
Partial safety factor Ms [-] 1.9
Stainless steel grade A4-80 NRk,s [kN] 29 46 67 126 196 282 367 449
Partial safety factor Ms [-] 1.6
Stainless steel grade 1.4529 NRk,s [kN] 26 41 59 110 172 247 321 393

Characteristic resistance values to shear load


Steel Failure - without lever arm

Size M8 M10 M12 M16 M20 M24 M27 M30

Steel grade 4.8 VRk,s [kN] 7 12 17 31 49 71 92 112


Partial safety factor Ms [-] 1.67
Steel grade 5.8 VRk,s [kN] 9 15 21 39 61 88 115 140
Partial safety factor Ms [-] 1.25
Steel grade 8.8 VRk,s [kN] 15 23 34 63 98 141 184 224
Partial safety factor Ms [-] 1.25
Steel grade 10.9 VRk,s [kN] 18 29 42 79 123 177 230 281
Partial safety factor Ms [-] 1.5
Stainless steel grade A4-70 VRk,s [kN] 13 20 30 55 86 124 161 196
Partial safety factor Ms [-] 1.56
Stainless steel grade A4-80 VRk,s [kN] 15 23 34 63 98 141 184 224
Partial safety factor Ms [-] 1.33
Stainless steel grade 1.4529 VRk,s [kN] 13 20 30 55 86 124 161 196
Partial safety factor Ms [-] 1.25

Steel Failure - with lever arm

Size M8 M10 M12 M16 M20 M24 M27 M30

Steel grade 4.8 VRk,s [kN] 15 30 52 133 260 449 666 900
Partial safety factor Ms [-] 1.67
Steel grade 5.8 VRk,s [kN] 19 37 66 166 325 561 832 1125
Partial safety factor Ms [-] 1.25
Steel grade 8.8 VRk,s [kN] 30 60 105 266 519 898 1332 1799
Partial safety factor Ms [-] 1.25
Steel grade 10.9 VRk,s [kN] 37 75 131 333 649 1123 1664 2249
Partial safety factor Ms [-] 1.50
Stainless steel grade A4-70 VRk,s [kN] 26 52 92 233 454 786 1165 1574
Partial safety factor Ms [-] 1.56

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

7/30
Stainless steel grade A4-80 VRk,s [kN] 30 60 105 266 519 898 1332 1799
Partial safety factor Ms [-] 1.33
Stainless steel grade 1.4529 VRk,s [kN] 26 52 92 233 454 786 1165 1574
Partial safety factor Ms [-] 1.25
Concrete pryout failure
Factor k from TR 029 Design of bonded anchors pt 5.2.3.3 2
Partial safety factor Ms [-] 1.5

USING SIKA ANCHORFIX®-2+ WITH THREADED BARS


Combined pullout and concrete cone failure in non-cracked concrete C20/25

Size M8 M10 M12 M16 M20 M24 M27 M30

Characteristic bond resistance in non-cracked concrete

Characteristic bond resistance dry/wet concrete Rk [N/mm2] 11 10 9.5 9.0 8.5 8.0 6.5 5.5

Partial safety factor Mc [-] 1.8 2.1

TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT


FAILURE AT VARIOUS EMBEDMENT DEPTHS
using threaded rods in dry / wet, uncracked, C20/25 concrete. Temperature range -40°C to +80°C.
Anchor Size
Property Symbol Unit
M8 M10 M12 M16 M20 M24 M27 M30

Effective Embedment Depth = 8d hef mm 64 80 96 128 160 192 216 240

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 17.69 25.13 34.38 57.91 85.45 115.81 119.09 124.41
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 2.10 2.10

Effective Embedment Depth = 10d hef mm 80 100 120 160 200 240 270 300
Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 22.12 31.42 42.98 72.38 106.81 144.76 148.86 155.51
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 2.10 2.10

Effective Embedment Depth = STD hef mm 80 90 110 128 170 210 270 300

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 22.12 28.27 39.40 57.91 90.79 126.67 148.86 155.51

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 2.10 2.10

Effective Embedment Depth = 12d hef mm 96 120 144 192 240 288 324 360
Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 26.54 37.70 51.57 86.86 128.18 173.72 178.64 186.61

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 2.10 2.10

Effective Embedment Depth = 14d hef mm 112 140 168 224 280 336 378 420
Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 30.96 43.98 60.17 101.34 149.54 202.67 208.41 217.71

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 2.10 2.10

Effective Embedment Depth = 16d hef mm 128 160 192 256 320 384 432 480

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 35.39 50.27 68.76 115.81 170.90 231.62 238.18 248.81
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 2.10 2.10

Effective Embedment Depth = 18d hef mm 144 180 216 288 360 432 486 540

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

8/30
Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 39.81 56.55 77.36 130.29 192.27 260.58 267.96 279.92
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 2.10 2.10

Effective Embedment Depth = 20d hef mm 160 200 240 320 400 480 540 600

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 44.23 62.83 85.95 144.76 213.63 289.53 297.73 311.02

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 2.10 2.10
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well as including
combined effects of tension and shear, must be considered in accordance with TR029.
2.
Characteristic loads are valid for single anchors without close edge, anchor spacing or eccentric loading considerations.
3.
Tabulated values are valid for temperature range -40°C to +80°C (Max LTT = +50°C; Max STT = +80°C).
4.
Tabulated values are only valid for the installation conditions stated. Other conditions, such as different temperature ranges, may affect the performance of the product.
5.
Long term temperatures are those that remain roughly constant over prolonged periods. Short term temperatures occur over brief intervals, eg: diurnal cycling.
6.
The compressive strength of the concrete (fck,cube ) is assumed to be 25 N/mm2 for C20/25 concrete.
7.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient to avoid splitting failure.

TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT


FAILURE AT 8D EMBEDMENT DEPTH
using threaded rods in dry / wet, uncracked, C20/25 concrete. Temperature range -40°C to +80°C.

Anchor Size
Property Symbol Unit
M8 M10 M12 M16 M20 M24 M27 M30
Nominal Anchor Diameter d mm 8 10 12 16 20 24 27 30

Characteristic Bond Strength


Rk N/mm2 11.00 10.00 9.50 9.00 8.50 8.00 6.50 5.50

Effective Embedment Depth hef mm 64 80 96 128 160 192 216 240

Characteristic Load (Combined Concrete Cone and Pullout Failure) N0Rk,p kN 17.69 25.13 34.38 57.91 85.45 115.81 119.09 124.41

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 2.10 2.10

Characteristic Anchor Spacing (Splitting Failure) Scr,sp mm 192 240 288 384 480 576 648 720

Characteristic Edge Distance (Splitting Failure) Ccr,sp mm 96 120 144 192 240 288 324 360

Characteristic Anchor Spacing (Combined Concrete Cone and Pullout Failure) Scr,Np mm 192 231 270 351 426 496 503 514

Characteristic Edge Distance (Combined Concrete Cone and Pullout Failure) Ccr,Np mm 96 115 135 175 213 248 251 257
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well as including
combined effects of tension and shear, must be considered in accordance with TR029.
2.
Characteristic loads are valid for single anchors without close edge, anchor spacing or eccentric loading considerations.
3.
Tabulated values are valid for temperature range -40°C to +80°C (Max LTT = +50°C; Max STT = +80°C).
4.
Tabulated values are only valid for the installation conditions stated. Other conditions, such as different temperature ranges, may affect the performance of the product.
5.
Long term temperatures are those that remain roughly constant over prolonged periods. Short term temperatures occur over brief intervals, eg: diurnal cycling.
6.
The compressive strength of the concrete (fck,cube ) is assumed to be 25 N/mm2 for C20/25 concrete.
7.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient to avoid splitting failure.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

9/30
Reduction factors for close edge: Reduction factors for anchor spacing:
Combined concrete cone and pullout failure Combined concrete cone and pullout failure
Anchor Size Anchor Size

M8 M10 M12 M16 M20 M24 M27 M30 M8 M10 M12 M16 M20 M24 M27 M30
35 0.55 35 0.65
40 0.58 0.54 40 0.66 0.65
50 0.65 0.59 0.56 50 0.69 0.66 0.65
60 0.72 0.65 0.60 60 0.71 0.68 0.66
65 0.76 0.68 0.63 0.56 65 0.72 0.69 0.67 0.63
70 0.79 0.71 0.65 0.57 70 0.73 0.70 0.68 0.64
80 0.87 0.77 0.70 0.61 0.56

Anchor Spacing Distance, S (mm)


80 0.75 0.72 0.69 0.65 0.63
90 0.95 0.83 0.75 0.65 0.59 90 0.78 0.74 0.71 0.67 0.64
Close Edge Distance, C (mm)

96 N/R 0.87 0.78 0.67 0.61 0.57 96 0.79 0.75 0.72 0.67 0.64 0.62
100 0.90 0.80 0.68 0.62 0.58 100 0.80 0.76 0.73 0.68 0.65 0.63
110 0.96 0.86 0.72 0.65 0.60 0.60 110 0.82 0.78 0.74 0.69 0.66 0.64 0.66
115 N/R 0.88 0.74 0.66 0.61 0.61 120 0.84 0.80 0.76 0.70 0.67 0.65 0.67 0.68
120 0.91 0.76 0.68 0.63 0.62 0.62 150 0.91 0.85 0.81 0.74 0.70 0.67 0.69 0.70
130 0.97 0.80 0.71 0.65 0.65 0.64 192 N/R 0.93 0.88 0.80 0.75 0.71 0.73 0.74
135 N/R 0.82 0.73 0.67 0.66 0.65 200 0.94 0.89 0.81 0.76 0.72 0.74 0.74
140 0.85 0.74 0.68 0.68 0.67 231 N/R 0.94 0.85 0.79 0.75 0.76 0.77
150 0.89 0.78 0.71 0.70 0.69 250 0.97 0.87 0.81 0.77 0.78 0.79
160 0.93 0.81 0.74 0.73 0.72 270 N/R 0.90 0.83 0.79 0.80 0.80
170 0.98 0.84 0.76 0.76 0.75 300 0.94 0.87 0.82 0.83 0.83
175 N/R 0.86 0.78 0.77 0.76 351 N/R 0.92 0.86 0.87 0.87
180 0.88 0.79 0.78 0.77 400 0.97 0.91 0.91 0.91
190 0.92 0.82 0.81 0.80 426 N/R 0.94 0.93 0.93
200 0.95 0.85 0.84 0.83 450 0.96 0.96 0.95
213 N/R 0.89 0.88 0.87 496 N/R 0.99 0.99
220 0.91 0.90 0.89 503 N/R 0.99
240 0.97 0.96 0.95 514 N/R
248 N/R 0.99 0.97
251 N/R 0.98
257 N/R
1.
Tabulated values are only applicable for instances where combined 1.
Tabulated values are only applicable for instances where combined concrete cone and pullout
concrete cone and pullout failure is the controlling failure mode as described by TR029.
failure is the controlling failure mode as described by TR029. All other failure modes must be
All other failure modes must be considered and different reduction factors may apply.
2. considered and different reduction factors may apply.
Tabulated values are based on a single anchor with a single close edge. Tabulated 2.
Tabulated values are based on a group of 2 anchors with the geometry defined by “S” and
values must not be used if multiple close edges exist. “Scr,Np” but without close edge considerations.
3. 3.
Anchors with geometry different to that defined in the above table must be Anchors with geometry different to that defined in the above table must be considered
considered separately and the tabulated values must not be used. separately and the tabulated values must not be used.
4.
4.
Interpolation is allowed. Interpolation is allowed.
5.
5.
Tabulated values assume that the geometry of the anchor(s) and concrete Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient
to avoid splitting failure.
member is sufficient to avoid splitting failure. 6.
6. Anchor spacing distances must exceed or be equal to the minimum anchor spacing (S min ) as
Close edge distances must exceed or be equal to the minimum close edge defined in the ETA.
distance (Cmin) as defined in the ETA.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

10/30
TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT
FAILURE AT STD EMBEDMENT DEPTH
using threaded rods in dry / wet, uncracked, C20/25 concrete. Temperature range -40°C to +80°C.

Anchor Size
Property Symbol Unit
M8 M10 M12 M16 M20 M24 M27 M30
Nominal Anchor Diameter d mm 8 10 12 16 20 24 27 30

Characteristic Bond Strength Rk N/mm2 11.00 10.00 9.50 9.00 8.50 8.00 6.50 5.50

Effective Embedment Depth hef mm 80 90 110 128 170 210 270 300

Characteristic Load (Combined Concrete Cone and Pullout Failure) N0Rk,p kN 22.12 28.27 39.40 57.91 90.79 126.67 148.86 155.51

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 2.10 2.10

Characteristic Anchor Spacing (Splitting Failure) Scr,sp mm 240 270 330 384 510 630 810 900

Characteristic Edge Distance (Splitting Failure) Ccr,sp mm 120 135 165 192 255 315 405 450

Characteristic Anchor Spacing (Combined Concrete Cone and Pullout Failure) Scr,Np mm 194 231 270 351 426 496 503 514

Characteristic Edge Distance (Combined Concrete Cone and Pullout Failure) Ccr,Np mm 97 115 135 175 213 248 251 257
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well
02

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

11/30
Reduction factors for close edge: Reduction factors for anchor spacing:
Combined concrete cone and pullout failure Combined concrete cone and pullout failure
Anchor Size Anchor Size

M8 M10 M12 M16 M20 M24 M27 M30 M8 M10 M12 M16 M20 M24 M27 M30
40 0.58 40 0.67
45 0.61 0.57 45 0.68 0.66
50 0.65 0.59 0.56 50 0.70 0.67
55 0.68 0.62 0.58 55 0.71 0.68 0.66
60 0.72 0.65 0.60 0.54 60 0.72 0.69 0.67
65 0.75 0.68 0.63 0.56 65 0.73 0.70 0.68 0.63
Close Edge Distance, C (mm)

70 0.79 0.71 0.65 0.57 0.53 70 0.74 0.71 0.69 0.64


80 0.87 0.77 0.70 0.61 0.56 80 0.76 0.73 0.70 0.65

Anchor Spacing Distance, S (mm)


85 0.90 0.80 0.72 0.63 0.57 85 0.77 0.74 0.71 0.66 0.64
90 0.94 0.83 0.75 0.65 0.59 0.55 90 0.78 0.75 0.72 0.67 0.64
97 N/R 0.88 0.79 0.67 0.61 0.57 100 0.80 0.76 0.73 0.68 0.65
100 0.90 0.80 0.68 0.62 0.58 105 0.81 0.77 0.74 0.69 0.66 0.64
105 0.93 0.83 0.70 0.63 0.59 120 0.85 0.80 0.77 0.70 0.67 0.65
115 N/R 0.88 0.74 0.66 0.61 135 0.88 0.83 0.79 0.72 0.69 0.67 0.69
135 N/R 0.82 0.73 0.67 0.66 140 0.89 0.84 0.80 0.73 0.70 0.67 0.70
150 0.89 0.78 0.71 0.70 0.69 150 0.91 0.86 0.81 0.74 0.71 0.68 0.70 0.71
175 N/R 0.86 0.78 0.77 0.76 194 N/R 0.93 0.88 0.80 0.75 0.72 0.74 0.75
200 0.95 0.85 0.84 0.83 200 0.95 0.89 0.81 0.76 0.73 0.75 0.75
213 N/R 0.89 0.88 0.87 231 N/R 0.94 0.85 0.79 0.76 0.77 0.78
225 0.93 0.92 0.90 250 0.97 0.87 0.81 0.77 0.79 0.79
248 N/R 0.99 0.97 270 N/R 0.90 0.84 0.79 0.81 0.81
251 N/R 0.98 300 0.94 0.87 0.82 0.83 0.83
257 N/R 351 N/R 0.92 0.87 0.88 0.87
400 0.97 0.91 0.92 0.91
1. 426 N/R 0.94 0.94 0.93
Tabulated values are only applicable for instances where combined concrete cone and
pullout failure is the controlling failure mode as described by TR029. All other failure 450 0.96 0.96 0.95
modes must be considered and different reduction factors may apply. 496 N/R 0.99 0.99
2.
Tabulated values are based on a single anchor with a single close edge. Tabulated 503 N/R 0.99
values must not be used if multiple close edges exist. 514 N/R
3.
Anchors with geometry different to that defined in the above table must be considered
separately and the tabulated values must not be used.
4.
Interpolation is allowed. 1.
5. Tabulated values are only applicable for instances where combined concrete cone and
Tabulated values assume that the geometry of the anchor(s) and concrete member is
pullout failure is the controlling failure mode as described by TR029. All other failure
sufficient to avoid splitting failure.
6. modes must be considered and different reduction factors may apply.
Close edge distances must exceed or be equal to the minimum close edge distance 2.
Tabulated values are based on a group of 2 anchors with the geometry defined by “S”
(Cmin) as defined in the ETA.
and “Scr,Np” but without close edge considerations.
3.
Anchors with geometry different to that defined in the above table must be considered
separately and the tabulated values must not be used.
4.
Interpolation is allowed.
5.
Tabulated values assume that the geometry of the anchor(s) and concrete member is
sufficient to avoid splitting failure.
6.
Anchor spacing distances must exceed or be equal to the minimum anchor spacing
(Smin) as defined in the ETA.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

12/30
TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT
FAILURE AT 20D EMBEDMENT DEPTH
using threaded rods in dry / wet, uncracked, C20/25 concrete. Temperature range -40°C to +80°C.

Anchor Size
Property Symbol Unit
M8 M10 M12 M16 M20 M24 M27 M30
Nominal Anchor Diameter d mm 8 10 12 16 20 24 27 30

Rk
2
Characteristic Bond Strength N/mm 11.00 10.00 9.50 9.00 8.50 8.00 6.50 5.50

Effective Embedment Depth hef mm 160 200 240 320 400 480 540 600

Characteristic Load (Combined Concrete Cone and Pullout Failure) N0Rk,p kN 44.23 62.83 85.95 144.76 213.63 289.53 297.73 311.02

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 2.10 2.10

Characteristic Anchor Spacing (Splitting Failure) Scr,sp mm 480 600 720 960 1200 1440 1620 1800

Characteristic Edge Distance (Splitting Failure) Ccr,sp mm 240 300 360 480 600 720 810 900

Characteristic Anchor Spacing (Combined Concrete Cone and Pullout Failure) Scr,Np mm 194 231 270 351 426 496 503 514

Characteristic Edge Distance (Combined Concrete Cone and Pullout Failure) Ccr,Np mm 97 115 135 175 213 248 251 257
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well as including
combined effects of tension and shear, must be considered in accordance with TR029.
2.
Characteristic loads are valid for single anchors without close edge, anchor spacing or eccentric loading considerations.
3.
Tabulated values are valid for temperature range -40°C to +80°C (Max LTT = +50°C; Max STT = +80°C).
4.
Tabulated values are only valid for the installation conditions stated. Other conditions, such as different temperature ranges, may affect the performance of the product.
5.
Long term temperatures are those that remain roughly constant over prolonged periods. Short term temperatures occur over brief intervals, eg: diurnal cycling.
6.
The compressive strength of the concrete (fck,cube ) is assumed to be 25 N/mm2 for C20/25 concrete.
7.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient to avoid splitting failure.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

13/30
Reduction factors for close edge: Reduction factors for anchor spacing:
Combined concrete cone and pullout failure Combined concrete cone and pullout failure
Anchor Size Anchor Size
M8 M10 M12 M16 M20 M24 M27 M30 M8 M10 M12 M16 M20 M24 M27 M30
80 0.87 80 0.78
90 0.94 90 0.80
97 N/R 100 0.82 0.79
100 0.90 120 0.86 0.82 0.79
115 N/R 140 0.90 0.86 0.82

Anchor Spacing Distance, S (mm)


120 0.91 160 0.94 0.89 0.85 0.79
130 0.97 180 0.97 0.92 0.88 0.81
Close Edge Distance, C (mm)

135 N/R 194 N/R 0.94 0.90 0.83


140 200 0.95 0.90 0.84 0.79
150 220 0.98 0.93 0.86 0.81
160 0.93 231 N/R 0.95 0.87 0.82
170 0.98 240 0.96 0.88 0.83 0.80
175 N/R 260 0.99 0.90 0.85 0.81
180 270 N/R 0.91 0.86 0.82 0.83
190 280 0.92 0.87 0.83 0.83
200 0.95 300 0.95 0.89 0.85 0.85 0.85
213 N/R 351 N/R 0.93 0.89 0.89 0.89
220 400 0.98 0.93 0.92 0.92
240 0.97 426 N/R 0.95 0.94 0.94
248 N/R 450 0.96 0.96 0.96
251 496 N/R 0.99 0.99
257 503 N/R 0.99
260 514 N/R
270 N/R
280 1.
300 N/R Tabulated values are only applicable for instances where combined concrete cone and
pullout failure is the controlling failure mode as described by TR029. All other failure
modes must be considered and different reduction factors may apply.
2.
Tabulated values are based on a group of 2 anchors with the geometry defined by “S”
1.
Tabulated values are only applicable for instances where combined concrete cone and pullout and “Scr,Np” but without close edge considerations.
3.
failure is the controlling failure mode as described by TR029. All other failure modes must be Anchors with geometry different to that defined in the above table must be considered
considered and different reduction factors may apply. separately and the tabulated values must not be used.
2. 4.
Tabulated values are based on a single anchor with a single close edge. Tabulated values must Interpolation is allowed.
5.
not be used if multiple close edges exist. Tabulated values assume that the geometry of the anchor(s) and concrete member is
3.
Anchors with geometry different to that defined in the above table must be considered sufficient to avoid splitting failure.
6.
separately and the tabulated values must not be used. Anchor spacing distances must exceed or be equal to the minimum anchor spacing
4.
Interpolation is allowed. (Smin) as defined in the ETA.
5.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient
to avoid splitting failure.
6.
Close edge distances must exceed or be equal to the minimum close edge distance (C min) as
defined in the ETA.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

14/30
USING SIKA ANCHORFIX®-2+ WITH THREADED BARS
Combined pullout and concrete cone failure cracked concrete C20/25

Size M10 M12 M16 M20 M24

Characteristic bond resistance in non-cracked concrete

Characteristic bond resistance dry/wet concrete Rk [N/mm2] 5.0 5.0 5.0 4.5 4.5

Partial safety factor Mc [-] 1.8

TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT


FAILURE AT VARIOUS EMBEDMENT DEPTHS
using threaded rods in dry / wet, cracked, C20/25 concrete. Temperature range -40°C to +80°C.
Anchor Size
Property Symbol Unit
M10 M12 M16 M20 M24

Effective Embedment Depth = 8d hef mm 80 96 128 160 192

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 12.57 18.10 32.17 45.24 65.14
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 10d hef mm 100 120 160 200 240

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 15.71 22.62 40.21 56.55 81.43
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = STD hef mm 90 110 128 170 210

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 14.14 20.73 32.17 48.07 71.25
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 12d hef mm 120 144 192 240 288

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 18.85 27.14 48.25 67.86 97.72
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 14d hef mm 140 168 224 280 336

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 21.99 31.67 56.30 79.17 114.00
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 16d hef mm 160 192 256 320 384

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 25.13 36.19 64.34 90.48 130.29
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 18d hef mm 180 216 288 360 432

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 28.27 40.72 72.38 101.79 146.57
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 20d hef mm 200 240 320 400 480

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 31.42 45.24 80.42 113.10 162.86
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well as including
combined effects of tension and shear, must be considered in accordance with TR029.
2.
Characteristic loads are valid for single anchors without close edge, anchor spacing or eccentric loading considerations.
3.
Tabulated values are valid for temperature range -40°C to +80°C (Max LTT = +50°C; Max STT = +80°C).
4.
Tabulated values are only valid for the installation conditions stated. Other conditions, such as different temperature ranges, may affect the performance of the product.
5.
Long term temperatures are those that remain roughly constant over prolonged periods. Short term temperatures occur over brief intervals, eg: diurnal cycling.
6.
The compressive strength of the concrete (fck,cube ) is assumed to be 25 N/mm2 for C20/25 concrete.
7.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient to avoid splitting failure.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

15/30
TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT
FAILURE AT 8D EMBEDMENT DEPTH
using threaded rods in dry / wet, cracked, C20/25 concrete. Temperature range -40°C to +80°C.
Anchor Size
Property Symbol Unit
M10 M12 M16 M20 M24
Nominal Anchor Diameter d mm 10 12 16 20 24

Rk
2
Characteristic Bond Strength N/mm 5.00 5.00 5.00 4.50 4.50

Effective Embedment Depth hef mm 80 96 128 160 192

Characteristic Load (Combined Concrete Cone and Pullout Failure) N0Rk,p kN 12.57 18.10 32.17 45.24 65.14

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80

Characteristic Anchor Spacing (Splitting Failure) Scr,sp mm 240 288 384 480 576

Characteristic Edge Distance (Splitting Failure) Ccr,sp mm 120 144 192 240 288

Characteristic Anchor Spacing (Combined Concrete Cone and Pullout Failure) Scr,Np mm 163 196 261 310 372

Characteristic Edge Distance (Combined Concrete Cone and Pullout Failure) Ccr,Np mm 82 98 131 155 186
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well as including
combined effects of tension and shear, must be considered in accordance with TR029.
2.
Characteristic loads are valid for single anchors without close edge, anchor spacing or eccentric loading considerations.
3.
Tabulated values are valid for temperature range -40°C to +80°C (Max LTT = +50°C; Max STT = +80°C).
4.
Tabulated values are only valid for the installation conditions stated. Other conditions, such as different temperature ranges, may affect the performance of the product.
5.
Long term temperatures are those that remain roughly constant over prolonged periods. Short term temperatures occur over brief intervals, eg: diurnal cycling.
6.
The compressive strength of the concrete (fck,cube ) is assumed to be 25 N/mm2 for C20/25 concrete.
7.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient to avoid splitting failure.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

16/30
Reduction factors for close edge: Reduction factors for anchor spacing:
Combined concrete cone and pullout failure Combined concrete cone and pullout failure
Anchor Size Anchor Size
M10 M12 M16 M20 M24 M10 M12 M16 M20 M24
40 0.63 40 0.71
50 0.71 0.64 50 0.73 0.71
60 0.80 0.71 60 0.76 0.73
65 0.84 0.75 0.64 65 0.77 0.74 0.69
70 0.89 0.78 0.66 70 0.78 0.75 0.70
80 0.98 0.86 0.71 0.65 80 0.81 0.77 0.72 0.69
90 N/R 0.87 0.72 0.66

Anchor Spacing Distance, S (mm)


90 0.83 0.79 0.73 0.71
96 0.94 0.77 0.69 0.65 96 0.84 0.80 0.74 0.72 0.69
Close Edge Distance, C (mm)

100 0.98 0.80 0.72 0.66 100 0.85 0.81 0.75 0.72 0.69
110 N/R 0.81 0.73 0.66 120 0.90 0.85 0.78 0.75 0.71
115 0.82 0.74 0.70 140 0.95 0.89 0.81 0.78 0.74
120 0.88 0.78 0.74 160 0.99 0.93 0.84 0.80 0.76
130 0.94 0.83 0.78 163 N/R 0.94 0.85 0.81 0.76
135 N/R 0.88 0.81 180 0.97 0.88 0.83 0.78
140 0.92 0.85 196 N/R 0.90 0.85 0.80
150 0.97 0.87 200 0.91 0.86 0.81
160 N/R 0.89 220 0.94 0.88 0.83
170 0.93 240 0.97 0.91 0.85
175 0.97 261 N/R 0.94 0.88
180 N/R 280 0.96 0.90
190 300 0.99 0.92
200 310 N/R 0.93
213 320 0.94
220 340 0.96
240 360 0.99
248 372 N/R
251
257
1.
Tabulated values are only applicable for instances where combined concrete cone and pullout
failure is the controlling failure mode as described by TR029. All other failure modes must be
1.
Tabulated values are only applicable for instances where combined concrete cone and considered and different reduction factors may apply.
2.
pullout failure is the controlling failure mode as described by TR029. All other failure Tabulated values are based on a group of 2 anchors with the geometry defined by “S” and
modes must be considered and different reduction factors may apply. “Scr,Np” but without close edge considerations.
2. 3.
Tabulated values are based on a single anchor with a single close edge. Tabulated Anchors with geometry different to that defined in the above table must be considered
values must not be used if multiple close edges exist. separately and the tabulated values must not be used.
3. 4.
Anchors with geometry different to that defined in the above table must be considered Interpolation is allowed.
5
separately and the tabulated values must not be used. . Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient
4.
Interpolation is allowed. to avoid splitting failure.
5. 6.
Tabulated values assume that the geometry of the anchor(s) and concrete member is Anchor spacing distances must exceed or be equal to the minimum anchor spacing (Smin) as
sufficient to avoid splitting failure. defined in the ETA.
6.
Close edge distances must exceed or be equal to the minimum close edge distance
(Cmin) as defined in the ETA.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

17/30
TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT
FAILURE AT STD EMBEDMENT DEPTH
using threaded rods in dry / wet, cracked, C20/25 concrete. Temperature range -40°C to +80°C.
Anchor Size
Property Symbol Unit
M10 M12 M16 M20 M24
Nominal Anchor Diameter d mm 10 12 16 20 24

Rk
2
Characteristic Bond Strength N/mm 5.00 5.00 5.00 4.50 4.50

Effective Embedment Depth hef mm 90 110 128 170 210

Characteristic Load (Combined Concrete Cone and Pullout Failure) N0Rk,p kN 14.14 20.73 32.17 48.07 71.25

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80

Characteristic Anchor Spacing (Splitting Failure) Scr,sp mm 270 330 384 510 630

Characteristic Edge Distance (Splitting Failure) Ccr,sp mm 135 165 192 255 315

Characteristic Anchor Spacing (Combined Concrete Cone and Pullout Failure) Scr,Np mm 163 196 261 310 372

Characteristic Edge Distance (Combined Concrete Cone and Pullout Failure) Ccr,Np mm 82 98 131 155 186
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well as including
combined effects of tension and shear, must be considered in accordance with TR029.
2.
Characteristic loads are valid for single anchors without close edge, anchor spacing or eccentric loading considerations.
3.
Tabulated values are valid for temperature range -40°C to +80°C (Max LTT = +50°C; Max STT = +80°C).
4.
Tabulated values are only valid for the installation conditions stated. Other conditions, such as different temperature ranges, may affect the performance of the product.
5.
Long term temperatures are those that remain roughly constant over prolonged periods. Short term temperatures occur over brief intervals, eg: diurnal cycling.
6.
The compressive strength of the concrete (fck,cube ) is assumed to be 25 N/mm2 for C20/25 concrete.
7.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient to avoid splitting failure.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

18/30
Reduction factors for anchor spacing: Reduction factors for close edge:
Combined concrete cone and pullout failure Combined concrete cone and pullout failure
Anchor Size Anchor Size

M10 M12 M16 M20 M24 M10 M12 M16 M20 M24
45 0.72 45 0.67
50 0.74 50 0.71
55 0.75 0.72 55 0.75 0.68
60 0.76 0.73 60 0.80 0.71
65 0.77 0.74 0.69 65 0.84 0.75 0.64
70 0.78 0.75 0.70 70 0.89 0.78 0.66

Close Edge Distance, C (mm)


80 0.81 0.77 0.72 80 0.98 0.86 0.71
Anchor Spacing Distance, S (mm)

90 0.83 0.79 0.73 0.71 82 N/R 0.87 0.72


100 0.86 0.81 0.75 0.72 85 0.90 0.74 0.67
105 0.87 0.82 0.76 0.73 0.70 90 0.94 0.77 0.69
120 0.90 0.85 0.78 0.75 0.72 98 N/R 0.81 0.73
140 0.95 0.89 0.81 0.78 0.74 100 0.82 0.74
160 0.99 0.93 0.84 0.81 0.76 105 0.85 0.76 0.68
163 N/R 0.94 0.85 0.81 0.77 110 0.88 0.78 0.70
180 0.97 0.88 0.83 0.79 120 0.94 0.83 0.74
196 N/R 0.90 0.85 0.80 131 N/R 0.88 0.78
200 0.91 0.86 0.81 140 0.92 0.81
220 0.94 0.88 0.83 150 0.97 0.85
240 0.97 0.91 0.85 155 N/R 0.87
261 N/R 0.94 0.88 160 0.89
280 0.96 0.90 170 0.93
300 0.99 0.92 180 0.97
310 N/R 0.93 186 N/R
320 0.94
340 0.97 1.
Tabulated values are only applicable for instances where combined concrete
360 0.99 cone and pullout failure is the controlling failure mode as described by TR029. All other
372 N/R failure modes must be considered and different reduction factors may apply.
2.
Tabulated values are based on a group of 2 anchors with the geometry defined by “S”
1.
and “Scr,Np” but without close edge considerations.
Tabulated values are only applicable for instances where combined concrete cone and 3.
Anchors with geometry different to that defined in the above table must be considered
pullout failure is the controlling failure mode as described by TR029. All other failure separately and the tabulated values must not be used.
modes must be considered and different reduction factors may apply. 4.
Interpolation is allowed.
2.
Tabulated values are based on a single anchor with a single close edge. Tabulated 5.
Tabulated values assume that the geometry of the anchor(s) and concrete member is
values must not be used if multiple close edges exist.
3.
sufficient to avoid splitting failure.
Anchors with geometry different to that defined in the above table must be considered 6.
Anchor spacing distances must exceed or be equal to the minimum anchor spacing
separately and the tabulated values must not be used. (Smin) as defined in the ETA.
4.
Interpolation is allowed.
5.
Tabulated values assume that the geometry of the anchor(s) and concrete member is
sufficient to avoid splitting failure.
6.
Close edge distances must exceed or be equal to the minimum close edge distance (Cmin)
as defined in the ETA.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

19/30
TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT
FAILURE AT 20D EMBEDMENT DEPTH
using threaded rods in dry / wet, cracked, C20/25 concrete. Temperature range -40°C to +80°C.
Anchor Size
Property Symbol Unit
M10 M12 M16 M20 M24
Nominal Anchor Diameter d mm 10 12 16 20 24

Rk
2
Characteristic Bond Strength N/mm 5.00 5.00 5.00 4.50 4.50

Effective Embedment Depth hef mm 200 240 320 400 480

Characteristic Load (Combined Concrete Cone and Pullout Failure) N0Rk,p kN 31.42 45.24 80.42 113.10 162.86

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80

Characteristic Anchor Spacing (Splitting Failure) Scr,sp mm 600 720 960 1200 1440

Characteristic Edge Distance (Splitting Failure) Ccr,sp mm 300 360 480 600 720

Characteristic Anchor Spacing (Combined Concrete Cone and Pullout Failure) Scr,Np mm 163 196 261 310 372

Characteristic Edge Distance (Combined Concrete Cone and Pullout Failure) Ccr,Np mm 82 98 131 155 186
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well as including
combined effects of tension and shear, must be considered in accordance with TR029.
2.
Characteristic loads are valid for single anchors without close edge, anchor spacing or eccentric loading considerations.
3.
Tabulated values are valid for temperature range -40°C to +80°C (Max LTT = +50°C; Max STT = +80°C).
4.
Tabulated values are only valid for the installation conditions stated. Other conditions, such as different temperature ranges, may affect the performance of the product.
5.
Long term temperatures are those that remain roughly constant over prolonged periods. Short term temperatures occur over brief intervals, eg: diurnal cycling.
6.
The compressive strength of the concrete (fck,cube ) is assumed to be 25 N/mm2 for C20/25 concrete.
7.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient to avoid splitting failure.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

20/30
Reduction factors for anchor spacing: Reduction factors for close edge:
Combined concrete cone and pullout failure Combined concrete cone and pullout failure
Anchor Size Anchor Size
M10 M12 M16 M20 M24 M10 M12 M16 M20 M24
100 0.87 100 N/R

Distance, C (mm)
110 0.89 110

Close Edge
120 0.91 0.86 120 N/R
130 0.93 0.88 130
140 0.95 0.90 140
Anchor Spacing Distance, S (mm)

150 0.97 0.92 160 N/R


160 0.99 0.94 0.86 180
163 N/R 0.94 0.87 200 N/R
170 0.96 0.88 220
180 0.97 0.89 240 N/R
190 0.99 0.90
196 N/R 0.91 1.
Tabulated values are only applicable for instances where combined concrete cone and
200 0.92 0.87
pullout failure is the controlling failure mode as described by TR029. All other failure
220 0.94 0.90 modes must be considered and different reduction factors may apply.
240 0.97 0.92 0.87 2.
Tabulated values are based on a single anchor with a single close edge. Tabulated
261 N/R 0.94 0.89 values must not be used if multiple close edges exist.
3.
280 0.97 0.91 Anchors with geometry different to that defined in the above table must be considered
300 0.99 0.93 separately and the tabulated values must not be used.
4.
310 N/R 0.94 Interpolation is allowed.
5.
Tabulated values assume that the geometry of the anchor(s) and concrete member is
320 0.95
sufficient to avoid splitting failure.
340 0.97 6.
Close edge distances must exceed or be equal to the minimum close edge distance (Cmin)
360 0.99 as defined in the ETA.
372 N/R

1.
Tabulated values are only applicable for instances where combined concrete cone and
pullout failure is the controlling failure mode as described by TR029. All other failure
modes must be considered and different reduction factors may apply.
2.
Tabulated values are based on a group of 2 anchors with the geometry defined by “S”
and “Scr,Np” but without close edge considerations.
3.
Anchors with geometry different to that defined in the above table must be considered
separately and the tabulated values must not be used.
4.
Interpolation is allowed.
5.
Tabulated values assume that the geometry of the anchor(s) and concrete member is
sufficient to avoid splitting failure.
6.
Anchor spacing distances must exceed or be equal to the minimum anchor spacing
(Smin) as defined in the ETA.

USING SIKA ANCHORFIX®-2+ WITH REINFORCING BARS


Combined pullout and concrete cone failure in non-cracked concrete C20/25

Ø10m Ø12m Ø16m Ø20m Ø25m Ø32m


Size Ø8mm
m m m m m m

Characteristic bond resistance in non-cracked concrete

Characteristic bond resistance dry/wet concrete Rk [N/mm2] 12 10 10 9.0 9.0 9.0 5.5

Partial safety factor Mc [-] 1.8

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

21/30
TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT
FAILURE AT VARIOUS EMBEDMENT DEPTHS
using reinforcing bars in dry / wet, uncracked, C20/25 concrete. Temperature range -40°C to +80°C.
Anchor Size
Property Symbol Unit
Ø10m Ø12m Ø16m Ø20m Ø25m Ø32m
Ø8mm
m m m m m m

Effective Embedment Depth = 8d hef mm 64 80 96 128 160 200 256

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 19.30 25.13 36.19 57.91 90.48 141.37 141.55
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 10d hef mm 80 100 120 160 200 250 320

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 24.13 31.42 45.24 72.38 113.10 176.71 176.93
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = STD hef mm 80 90 110 128 170 210 300

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 24.13 28.27 41.47 57.91 96.13 148.44 165.88
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 12d hef mm 96 120 144 192 240 300 384

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 28.95 37.70 54.29 86.86 135.72 212.06 212.32
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 14d hef mm 112 140 168 224 280 350 448

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 33.78 43.98 63.33 101.34 158.34 247.40 247.71
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 16d hef mm 128 160 192 256 320 400 512

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 38.60 50.27 72.38 115.81 180.96 282.74 283.10
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 18d hef mm 144 180 216 288 360 450 576

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 43.43 56.55 81.43 130.29 203.58 318.09 318.48
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 1.80

Effective Embedment Depth = 20d hef mm 160 200 240 320 400 500 640

Characteristic Load (Combined Concrete Cone & Pullout Failure) N0Rk,p kN 48.25 62.83 90.48 144.76 226.19 353.43 353.87
Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 1.80
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well as including
combined effects of tension and shear, must be considered in accordance with TR029.
2.
Characteristic loads are valid for single anchors without close edge, anchor spacing or eccentric loading considerations.
3.
Tabulated values are valid for temperature range -40°C to +80°C (Max LTT = +50°C; Max STT = +80°C).
4.
Tabulated values are only valid for the installation conditions stated. Other conditions, such as different temperature ranges, may affect the performance of the product.
5.
Long term temperatures are those that remain roughly constant over prolonged periods. Short term temperatures occur over brief intervals, eg: diurnal cycling.
6.
The compressive strength of the concrete (fck,cube ) is assumed to be 25 N/mm2 for C20/25 concrete.
7.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient to avoid splitting failure.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

22/30
TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT
FAILURE AT 8D EMBEDMENT DEPTH
using reinforcing bars in dry / wet, uncracked, C20/25 concrete. Temperature range -40°C to +80°C.

Anchor Size
Property Symbol Unit
Ø8mm Ø10m Ø12m Ø16m Ø20m Ø25m Ø32m
Nominal Anchor Diameter d mm 8 m
10 m
12 m
16 m
20 m
25 m
32

Characteristic Bond Strength


Rk N/mm2 12.00 10.00 10.00 9.00 9.00 9.00 5.50

Effective Embedment Depth hef mm 64 80 96 128 160 200 256

Characteristic Load (Combined Concrete Cone and Pullout Failure) N0Rk,p kN 19.30 25.13 36.19 57.91 90.48 141.37 141.55

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 1.80

Characteristic Anchor Spacing (Splitting Failure) Scr,sp mm 192 240 288 384 480 600 768

Characteristic Edge Distance (Splitting Failure) Ccr,sp mm 96 120 144 192 240 300 384

Characteristic Anchor Spacing (Combined Concrete Cone and Pullout Failure) Scr,Np mm 192 231 277 351 438 548 548

Characteristic Edge Distance (Combined Concrete Cone and Pullout Failure) Ccr,Np mm 96 115 139 175 219 274 274
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well as including
combined effects of tension and shear, must be considered in accordance with TR029.
2.
Characteristic loads are valid for single anchors without close edge, anchor spacing or eccentric loading considerations.
3.
Tabulated values are valid for temperature range -40°C to +80°C (Max LTT = +50°C; Max STT = +80°C).
4.
Tabulated values are only valid for the installation conditions stated. Other conditions, such as different temperature ranges, may affect the performance of the product.
5.
Long term temperatures are those that remain roughly constant over prolonged periods. Short term temperatures occur over brief intervals, eg: diurnal cycling.
6.
The compressive strength of the concrete (fck,cube ) is assumed to be 25 N/mm2 for C20/25 concrete.
7.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient to avoid splitting failure.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

23/30
Reduction factors for close edge: Reduction factors for anchor spacing:
Combined concrete cone and pullout failure Combined concrete cone and pullout failure
Anchor Size Anchor Size

Ø8mm Ø10m Ø12m Ø16m Ø20m Ø25m Ø32m Ø8mm Ø10m Ø12m Ø16m Ø20m Ø25m Ø32m
35 0.55 m m m m m m 35 0.64 m m m m m m
40 0.58 0.54 40 0.65 0.65
50 0.65 0.59 0.55 50 0.67 0.66 0.64
60 0.72 0.65 0.59 60 0.70 0.68 0.65
65 0.76 0.68 0.62 0.56 65 0.71 0.69 0.66 0.63
70 0.79 0.71 0.64 0.57 70 0.72 0.70 0.67 0.64
80 0.87 0.77 0.69 0.61 0.55 80 0.74 0.72 0.69 0.65 0.61
90 0.95 0.83 0.74 0.65 0.58 90 0.77 0.74 0.70 0.67 0.62
Close Edge Distance, C (mm)

Anchor Spacing Distance, S (mm)


96 N/R 0.87 0.77 0.67 0.60 100 0.79 0.76 0.72 0.68 0.64 0.59
100 0.90 0.79 0.68 0.61 0.55 120 0.84 0.80 0.75 0.70 0.66 0.61
115 N/R 0.87 0.74 0.65 0.59 130 0.86 0.82 0.77 0.72 0.67 0.62 0.68
120 0.90 0.76 0.67 0.60 140 0.88 0.83 0.78 0.73 0.68 0.63 0.68
130 0.95 0.80 0.70 0.62 0.62 160 0.93 0.87 0.81 0.76 0.70 0.65 0.70
139 N/R 0.84 0.73 0.64 0.64 180 0.97 0.91 0.85 0.78 0.72 0.67 0.71
140 0.85 0.73 0.64 0.64 192 N/R 0.93 0.87 0.80 0.74 0.68 0.72
150 0.89 0.76 0.67 0.67 200 0.94 0.88 0.81 0.74 0.68 0.73
160 0.93 0.80 0.69 0.69 220 0.98 0.91 0.83 0.77 0.70 0.75
170 0.98 0.83 0.72 0.72 231 N/R 0.93 0.85 0.78 0.71 0.76
175 N/R 0.85 0.73 0.73 240 0.94 0.86 0.79 0.72 0.76
180 0.86 0.74 0.74 260 0.97 0.89 0.81 0.74 0.78
190 0.90 0.77 0.77 277 N/R 0.91 0.83 0.75 0.79
200 0.93 0.80 0.79 280 0.91 0.83 0.76 0.79
219 N/R 0.85 0.85 300 0.94 0.85 0.77 0.81
240 0.90 0.90 351 N/R 0.91 0.82 0.85
260 0.96 0.96 400 0.96 0.87 0.89
270 0.99 0.99 438 N/R 0.90 0.92
274 N/R N/R 450 0.91 0.93
500 0.96 0.96
1. 548 N/R N/R
Tabulated values are only applicable for instances where combined concrete cone and pullout
failure is the controlling failure mode as described by TR029. All other failure modes must be
considered and different reduction factors may apply. 1.
Tabulated values are only applicable for instances where combined concrete cone and
2.
Tabulated values are based on a single anchor with a single close edge. Tabulated values must pullout failure is the controlling failure mode as described by TR029. All other failure
not be used if multiple close edges exist. modes must be considered and different reduction factors may apply.
3.
Anchors with geometry different to that defined in the above table must be considered 2.
Tabulated values are based on a group of 2 anchors with the geometry defined by “S”
separately and the tabulated values must not be used. and “Scr,Np” but without close edge considerations.
4.
Interpolation is allowed. 3.
Anchors with geometry different to that defined in the above table must be considered
5.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient separately and the tabulated values must not be used.
to avoid splitting failure. 4.
Interpolation is allowed.
6.
Close edge distances must exceed or be equal to the minimum close edge distance (Cmin) as 5.
Tabulated values assume that the geometry of the anchor(s) and concrete member is
defined in the ETA. sufficient to avoid splitting failure.
6.
Anchor spacing distances must exceed or be equal to the minimum anchor spacing
(Smin) as defined in the ETA.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

24/30
TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT
FAILURE AT STD EMBEDMENT DEPTH
using reinforcing bars in dry / wet, uncracked, C20/25 concrete. Temperature range -40°C to +80°C.

Anchor Size
Property Symbol Unit
Ø8mm Ø10m Ø12m Ø16m Ø20m Ø25m Ø32m
Nominal Anchor Diameter d mm 8 m
10 m
12 m
16 m
20 m
25 m
32

Characteristic Bond Strength


Rk N/mm2 12.00 10.00 10.00 9.00 9.00 9.00 5.50

Effective Embedment Depth hef mm 80 90 110 128 170 210 300

Characteristic Load (Combined Concrete Cone and Pullout Failure) N0Rk,p kN 24.13 28.27 41.47 57.91 96.13 148.44 165.88

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 1.80

Characteristic Anchor Spacing (Splitting Failure) Scr,sp mm 240 270 330 384 510 630 900

Characteristic Edge Distance (Splitting Failure) Ccr,sp mm 120 135 165 192 255 315 450

Characteristic Anchor Spacing (Combined Concrete Cone and Pullout Failure) Scr,Np mm 202 231 277 351 438 548 548

Characteristic Edge Distance (Combined Concrete Cone and Pullout Failure) Ccr,Np mm 101 115 139 175 219 274 274
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well as including
combined effects of tension and shear, must be considered in accordance with TR029.
2.
Characteristic loads are valid for single anchors without close edge, anchor spacing or eccentric loading considerations.
3.
Tabulated values are valid for temperature range -40°C to +80°C (Max LTT = +50°C; Max STT = +80°C).
4.
Tabulated values are only valid for the installation conditions stated. Other conditions, such as different temperature ranges, may affect the performance of the product.
5.
Long term temperatures are those that remain roughly constant over prolonged periods. Short term temperatures occur over brief intervals, eg: diurnal cycling.
6.
The compressive strength of the concrete (fck,cube ) is assumed to be 25 N/mm2 for C20/25 concrete.
7.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient to avoid splitting failure.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

25/30
Reduction factors for close edge: Reduction factors for anchor spacing:
Combined concrete cone and pullout failure Combined concrete cone and pullout failure
Anchor Size Anchor Size

Ø8mm Ø10m Ø12m Ø16m Ø20m Ø25m Ø32m Ø8mm Ø10m Ø12m Ø16m Ø20m Ø25m Ø32m
40 0.57 m m m m m m 40 0.66 m m m m m m
45 0.60 0.57 45 0.67 0.66
50 0.63 0.59 50 0.68 0.67
55 0.67 0.62 0.57 55 0.69 0.68 0.65
60 0.70 0.65 0.59 60 0.70 0.69 0.66
65 0.73 0.68 0.62 0.56 65 0.71 0.70 0.67 0.63
70 0.77 0.71 0.64 0.57 70 0.72 0.71 0.68 0.64

Anchor Spacing Distance, S (mm)


80 0.84 0.77 0.69 0.61 80 0.75 0.73 0.69 0.65
85 0.88 0.80 0.71 0.63 0.57 85 0.76 0.74 0.70 0.66 0.62
Close Edge Distance, C (mm)

90 0.91 0.83 0.74 0.65 0.58 90 0.77 0.75 0.71 0.67 0.63
101 N/R 0.90 0.79 0.69 0.61 100 0.79 0.76 0.72 0.68 0.64
105 0.93 0.82 0.70 0.62 0.56 105 0.80 0.77 0.73 0.69 0.65 0.60
110 0.96 0.84 0.72 0.64 0.58 125 0.84 0.81 0.76 0.71 0.67 0.62
115 N/R 0.87 0.74 0.65 0.59 150 0.89 0.86 0.80 0.74 0.69 0.64 0.70
120 0.90 0.76 0.67 0.60 175 0.94 0.90 0.84 0.78 0.72 0.66 0.72
130 0.95 0.80 0.70 0.62 202 N/R 0.95 0.89 0.81 0.75 0.69 0.74
139 N/R 0.84 0.73 0.64 225 0.99 0.92 0.84 0.77 0.71 0.76
140 0.85 0.73 0.64 231 N/R 0.93 0.85 0.78 0.72 0.76
150 0.89 0.76 0.67 0.67 250 0.96 0.87 0.80 0.73 0.78
160 0.93 0.80 0.69 0.69 277 N/R 0.91 0.83 0.76 0.80
170 0.98 0.83 0.72 0.72 300 0.94 0.85 0.78 0.81
175 N/R 0.85 0.73 0.73 351 N/R 0.91 0.82 0.85
180 0.86 0.74 0.74 400 0.96 0.87 0.89
190 0.90 0.77 0.77 438 N/R 0.90 0.92
200 0.93 0.80 0.79 450 0.91 0.93
220 N/R 0.85 0.85 500 0.96 0.96
240 0.90 0.90 548 N/R N/R
260 0.96 0.96
274 N/R N/R
1.
Tabulated values are only applicable for instances where combined concrete cone and
pullout failure is the controlling failure mode as described by TR029. All other failure
1.
Tabulated values are only applicable for instances where combined concrete cone and modes must be considered and different reduction factors may apply.
pullout failure is the controlling failure mode as described by TR029. All other failure modes 2.
Tabulated values are based on a group of 2 anchors with the geometry defined by “S”
must be considered and different reduction factors may apply. and “Scr,Np” but without close edge considerations.
2. 3.
Tabulated values are based on a single anchor with a single close edge. Tabulated values Anchors with geometry different to that defined in the above table must be considered
must not be used if multiple close edges exist. separately and the tabulated values must not be used.
3. 4.
Anchors with geometry different to that defined in the above table must be considered Interpolation is allowed.
separately and the tabulated values must not be used. 5.
Tabulated values assume that the geometry of the anchor(s) and concrete member is
4.
Interpolation is allowed. sufficient to avoid splitting failure.
5. 6.
Tabulated values assume that the geometry of the anchor(s) and concrete member is Anchor spacing distances must exceed or be equal to the minimum anchor spacing
sufficient to avoid splitting failure. (Smin) as defined in the ETA.
6.
Close edge distances must exceed or be equal to the minimum close edge distance (C min) as
defined in the ETA.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

26/30
TENSION LOAD CALCULATIONS FOR COMBINED CONCRETE CONE & PULLOUT
FAILURE AT 20D EMBEDMENT DEPTH
using reinforcing bars in dry / wet, uncracked, C20/25 concrete. Temperature range -40°C to +80°C.
Anchor Size
Property Symbol Unit
Ø8mm Ø10m Ø12m Ø16m Ø20m Ø25m Ø32m
Nominal Anchor Diameter d mm 8 m
10 m
12 m
16 m
20 m
25 m
32

Characteristic Bond Strength


Rk N/mm2 12.00 10.00 10.00 9.00 9.00 9.00 5.50

Effective Embedment Depth hef mm 160 200 240 320 400 500 640

Characteristic Load (Combined Concrete Cone and Pullout Failure) N0Rk,p kN 48.25 62.83 90.48 144.76 226.19 353.43 353.87

Partial Safety Factor Mc - 1.80 1.80 1.80 1.80 1.80 1.80 1.80

Characteristic Anchor Spacing (Splitting Failure) Scr,sp mm 480 600 720 960 1200 1500 1920

Characteristic Edge Distance (Splitting Failure) Ccr,sp mm 240 300 360 480 600 750 960

Characteristic Anchor Spacing (Combined Concrete Cone and Pullout Failure) Scr,Np mm 202 231 277 351 438 548 548

Characteristic Edge Distance (Combined Concrete Cone and Pullout Failure) Ccr,Np mm 101 115 139 175 219 274 274
1.
Characteristic loads are valid for combined concrete cone and pullout failure as defined by TR029 only. All other failure modes, including steel failure, detailed in TR029 as well as including
combined effects of tension and shear, must be considered in accordance with TR029.
2.
Characteristic loads are valid for single anchors without close edge, anchor spacing or eccentric loading considerations.
3.
Tabulated values are valid for temperature range -40°C to +80°C (Max LTT = +50°C; Max STT = +80°C).
4.
Tabulated values are only valid for the installation conditions stated. Other conditions, such as different temperature ranges, may affect the performance of the product.
5.
Long term temperatures are those that remain roughly constant over prolonged periods. Short term temperatures occur over brief intervals, eg: diurnal cycling.
6.
The compressive strength of the concrete (fck,cube ) is assumed to be 25 N/mm2 for C20/25 concrete.
7.
Tabulated values assume that the geometry of the anchor(s) and concrete member is sufficient to avoid splitting failure.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

27/30
Reduction factors for anchor spacing:
Reduction factors for close edge:
Combined concrete cone and pullout failure
Combined concrete cone and pullout failure
Anchor Size Anchor Size

Ø8mm Ø10m Ø12m Ø16m Ø20m Ø25m Ø32m Ø8mm Ø10m Ø12m Ø16m Ø20m Ø25m Ø32m
80 0.84 80 0.77 m m m m m m
m m m m m m
90 0.91 90 0.79
100 0.99 0.90 100 0.81 0.79
101 1.00 0.90 120 0.85 0.82 0.78
110 0.96 140 0.89 0.86 0.81

Anchor Spacing Distance, S (mm)


115 N/R 160 0.92 0.89 0.84 0.79
120 0.90 180 0.96 0.92 0.87 0.81
Close Edge Distance, C (mm)

130 0.95 200 0.99 0.95 0.90 0.84 0.78


139 N/R 202 N/R 0.96 0.90 0.84 0.79
140 225 0.99 0.93 0.86 0.81
150 231 N/R 0.94 0.87 0.81
160 0.93 250 0.96 0.89 0.83 0.78
170 0.98 277 N/R 0.92 0.86 0.80
175 N/R 300 0.95 0.88 0.82
180 320 0.97 0.90 0.83 0.85
190 325 0.97 0.90 0.83 0.85
200 0.93 351 N/R 0.92 0.85 0.87
219 N/R 375 0.94 0.87 0.89
220 400 0.97 0.89 0.90
240 438 N/R 0.92 0.93
250 0.93 450 0.93 0.94
260 0.96 500 0.97 0.97
274 N/R 548 N/R N/R
280
300 1.
Tabulated values are only applicable for instances where combined concrete cone and
320 N/R pullout failure is the controlling failure mode as described by TR029. All other failure modes
must be considered and different reduction factors may apply.
2.
Tabulated values are based on a group of 2 anchors with the geometry defined by “S” and
1.
Tabulated values are only applicable for instances where combined concrete cone and “Scr,Np” but without close edge considerations.
3.
pullout failure is the controlling failure mode as described by TR029. All other failure modes Anchors with geometry different to that defined in the above table must be considered
must be considered and different reduction factors may apply. separately and the tabulated values must not be used.
2. 4.
Tabulated values are based on a single anchor with a single close edge. Tabulated values Interpolation is allowed.
5.
must not be used if multiple close edges exist. Tabulated values assume that the geometry of the anchor(s) and concrete member is
3.
Anchors with geometry different to that defined in the above table must be considered sufficient to avoid splitting failure.
6.
separately and the tabulated values must not be used. Anchor spacing distances must exceed or be equal to the minimum anchor spacing (S min) as
4.
Interpolation is allowed. defined in the ETA.
5.
Tabulated values assume that the geometry of the anchor(s) and concrete member is
sufficient to avoid splitting failure.
6.
Close edge distances must exceed or be equal to the minimum close edge distance (Cmin) as
defined in the ETA.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

28/30
USING SIKA ANCHORFIX®-2+ WITH POST-INSTALLED REBAR CONNECTIONS
Installation parameters

Rebar Min. Min. Max.


Cleaning
Drill Hole Anchorage Lap/Splice Embedment
Brush*
Diameter fy,k (mm) Length Length Depth
(mm)
(mm) (N/mm2) (mm) (mm) (mm)

8 500 12 (10) 14 114 200 400

10 500 14 (12) 14 142 200 500

12 500 16 19 171 200 600

14 500 18 22 199 210 700

16 500 20 22 227 240 800

20 500 25 29 284 300 1000

25 500 32 40 355 375 1000

28 500 35 40 595 630 1000

32 500 40 42 681 720 1000

* Values in parenthesis represent alternative drilling diameters.

DESIGN BOND STRENGTH VALUES


Design values of the ultimate bond resistance fbd in N/mm2 for rotary hammer drilling and compressed air drilling for
good bond conditions.

Concrete Class
Rebar Ø
(mm)
C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60

10

12 4.0 4.3
3.4 3.7
14 3.0
2.7
16 1.6 2.0 2.3

20 3.7

25 3.0

28 2.7

32 2.3

Tabulated values for fbd are valid for good bond conditions according to EN 1992-1-1. For all other bond conditions multiply the values for f bd by 0.7.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

29/30
IMPORTANT NOTES

Use in Porous Substrates


This bonded anchor is not intended for use as a cosmetic or decorative product. When anchoring into porous or reconstituted
stone it is recommended that technical assistance is sought. Due to the nature of the product, migration of the monomer in the
resin may cause staining in certain materials. If you are still uncertain, it is advisable to test the resin by applying it in a small,
discrete area and testing before using the resin on the project.

Important Note
Whilst all reasonable care is taken in compiling technical data on the Company’s products, all recommendations or suggestions
regarding the use of such products are made without guarantee, since the conditions of use are beyond the control of the
Company. It is the customer’s responsibility to satisfy himself that each product is fit for the purpose for which he intends to use
it, that the actual conditions of use are suitable and that, in the light of our continual research and development programme the
information relating to each product has not been superseded.

Technical Documentation English/Sika Services AG/Translation template


Sika AnchorFix-2+ template for local adaption
09 2016, 00
870 43 12

30/30

You might also like