Transmission Lines Protection Using SIPR
Transmission Lines Protection Using SIPR
SUMMARY
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
165 Special Issue,
p. 165–183 https://doi.org/10.37798/2017661-4103
1. INTRODUCTION
2. DISTANCE PROTECTION
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
166 Special Issue,
p. 165–183
Figure 1 Distance protection fundamentals
Cautious choice of the reach settings and tripping times for different zones
allow correct coordination between distance relays on a power system. Basic
distance protection will compromise instantaneous directional Zone 1 protection
and one or more time-delayed zones. Numerical distance relays may have more
than five zones, some of which can be set to measure in the reverse direction.
Typical settings for three forward-looking zones of basic distance protection are
given in the following sub-sections.
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
167 Special Issue,
p. 165–183
2.1.1 Zone 1 Setting
Remote backup protection for all faults on adjacent lines can be provided
by a third zone of protection which needs to be time delayed to discriminate with
Zone 2 protection increased with trip time of circuit breaker for the adjacent line.
Zone 3 reach should cover at least 120% of the impedance given to the
relay for a fault located at the remote end of the second line [1]. Zones 1 and 2
should never overreach the end of the remote line, and Zone 3 should never
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
168 Special Issue,
p. 165–183
underreach it. Equally, Zones 1 and 2 are set using the actual impedance of the
protected line, ignoring current infeed at the remote busbar, while Zone 3 must
be set for a fault at the end of the remote line with maximum infeed conditions at
the remote bus.
The Zone 3 distance element rarely needs to operate; however, it must not
work during extreme loading conditions, stressed power system conditions, or
slow power swings [3, 4]. All three zones are presented in Figure 2.
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
169 Special Issue,
p. 165–183
Figure 3 Quadrilateral characteristic
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
170 Special Issue,
p. 165–183
2.3.1 Distance Protection 7SA611 Relay
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
171 Special Issue,
p. 165–183
Figure 4 Relay parameterising
Several further physical quantities are adjustable in different Settings
Groups as shown in Figure 5.
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
172 Special Issue,
p. 165–183
As the calculation of the line impedance on a phase to ground loop is not
possible only with measured values, additional information regarding the
ratio, 𝑍𝑍𝐿𝐿 /𝑍𝑍𝐸𝐸 needs to be provided to the relay. Here, it is assumed that the ratio is
constant along the line. After individually setting the distance zones (Figure 6), a
graph of the characteristic can be plotted (Figure 7) in which the dotted lines
represent the tolerances of each zone. The type of the characteristic is
quadrilateral, and although the reach of every single zone can be edited, the form
of the characteristic cannot be changed once it is integrated into the relay.
Additionally, it is possible to export the relay characteristic in an RIO File which
then enables easy import into Omicron (test device used).
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
173 Special Issue,
p. 165–183
Figure 7 Relay characteristic
The relay was tested with Omicron CMC 56, a device created for testing all
generations and types of protection relays. Its software, Test Universe, is a
helpful tool for advanced secondary testing of protection and measuring devices.
It enables a range of approaches, from manual to entirely automated and
standardised tests, running on a PC or a laptop. For this testing process, the
adequate test module was Distance.
It is possible to test each adjusted distance zone separately, or more zones
at the same time. Different types of faults (one-pole, two-pole or three-pole short
circuit) need to be tested independently. According to the previously set up
parameters in DIGSI, the nominal values for tripping time for each zone are as
following:
- for Zone 1: 0 ms (instantaneous),
- for Zone 2: 350 ms,
- for Zone 3: 800 ms,
- for Zone 4: 700 ms,
- for Zone 5: 1,5 s.
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
174 Special Issue,
p. 165–183
Table 1 Zone settings (Test Universe)
Label Type Fault loop Trip time Tol.Trel Tol.T abs+ Tol.T abs- Tol.Z rel. Tol.Z abs
Z1 Tripping L-L 0,000 s 1,000 % 100,0 ms 100,0 ms 5,000 % 100,0 mΩ
Z1 Tripping L-E 0,000 s 1,000 % 100,0 ms 100,0 ms 5,000 % 100,0 mΩ
Z2 Tripping L-L 350,0 ms 1,000 % 100,0 ms 100,0 ms 5,000 % 100,0 mΩ
Z2 Tripping L-E 350,0 ms 1,000 % 100,0 ms 100,0 ms 5,000 % 100,0 mΩ
Z4 Tripping L-L 700,0 ms 1,000 % 100,0 ms 100,0 ms 5,000 % 100,0 mΩ
Z4 Tripping L-E 700,0 ms 1,000 % 100,0 ms 100,0 ms 5,000 % 100,0 mΩ
Z3 Tripping L-L 800,0 ms 1,000 % 100,0 ms 100,0 ms 5,000 % 100,0 mΩ
Z3 Tripping L-E 800,0 ms 1,000 % 100,0 ms 100,0 ms 5,000 % 100,0 mΩ
Z5 Tripping L-L 1,500 s 1,000 % 100,0 ms 100,0 ms 5,000 % 100,0 mΩ
Z5 Tripping L-E 1,500 s 1,000 % 100,0 ms 100,0 ms 5,000 % 100,0 mΩ
Ten different impedances were tested and successfully passed the test as
shown in the results from the Test Universe report.
As expected, the relay tripped for all impedances less than the Zone 1
impedance within the Zone 1 tripping time, whereas for the impedances bigger
than the Zone 1 impedance, it tripped within the Zone 2 tripping time. Nominal
tripping time for Zone 1 is instantaneous, and for Zone 2 equals 350 ms. In both
cases, for every selected impedance, there was an inevitable time delay within
the permitted tolerances which illustrates the real-life situations in power
systems.
Test results consist of the value and the angle of the impedance, nominal
and activating time of the relay, time deviation and the decision of the testing as
presented in the following figure.
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
175 Special Issue,
p. 165–183
Furthermore, if the test impedances successfully pass the test, they
become visually green in the graph (Figure 8).
X/Ω
25
20
15
10
-5
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
176 Special Issue,
p. 165–183
Fault Trip
Postfault
V/V
60
40
20
0
-20 -0,8 -0,6 -0,4 -0,2 0,0 0,2 0,4 0,6 0,8 t/s
-40
-60
-80
I/A
2,0
1,0
0,0
-0,8 -0,6 -0,4 -0,2 0,0 0,2 0,4 0,6 0,8 t/s
-1,0
-2,0
-3,0
IL1 IL2 IL3
Trip
Start
-0,8 -0,6 -0,4 -0,2 0,0 0,2 0,4 0,6 0,8 t/s
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
177 Special Issue,
p. 165–183
3.2 Testing Zone 3 for Single-Pole Short Circuits
As shown in the graph below, Zone 3 was set to have a reversed direction.
As a result, it provides distance protection against faults behind the relay
(busbar) of the protected transmission line. It is also the reason that the Zone 4
tripping time can be less than the Zone 3 tripping time; otherwise, the zones
would not discriminate.
Eight impedances selected are located within the Zone 3 setting, and one
within Zone 5 and its relay tripping time, thus, equals the Zone 5 nominal time
increased with time deviation.
X/Ω
25
20
15
10
-5
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
178 Special Issue,
p. 165–183
3.3 Testing Zone 4 for Three-Pole Short Circuits
Due to Omicron's restraints, tests for Zones 4 and 5 were only possible for
three-pole short circuits; otherwise, impedances selected would appear to be out
of range. In this experiment, six impedances were less than the Zone 4
impedance. Hence the tripping times corresponded to the tripping time of the
Zone 4 (nominal time 700 ms + time deviation). On the other hand, the remaining
four impedances selected were higher than the Zone 4 impedance and their
tripping times consequently corresponded to the tripping time of the Zone 5
(nominal time 1, 5 s + time deviation) as expected. For all the impedances
selected, the relay tripped within the correct times, depending on the zone.
X/Ω
25
20
15
10
-5
15
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
179 Special Issue,
p. 165–183
3.4 Testing the Complete Characteristic for Three-Pole Short Circuits
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
180 Special Issue,
p. 165–183
X/Ω
25
20
15
10
-5
4. CONCLUSION
This study set out to describe the principles of transmission lines distance
protection and to emphasize the importance of correct relay parameterizing as it
is crucial for the security and stability of any power system. The challenge today
is to implement cost-efficient solutions in modern, intelligent and smart grids
where communication and monitoring of the system would enable optimal
functioning of power systems across the globe. Hence, setting the adequate
protection systems, to provide selective tripping, will minimize the extent and
time of the outage. Their communication protocols and precise determination of
the fault location, therefore, contribute to the reduction of the on-site inspection
time.
In this investigation, the aim was to evaluate adequate zone reach settings
and corresponding tripping times of a numerical distance relay and to illustrate
the selectivity between different zones of the characteristic.
The results of this study indicate that correct reach settings and tripping
times of different zones result in the selective acting of a relay on the protected
transmission line and further adjacent line(s), whether in forward or reversed
direction. The analysis undertaken here has also confirmed our knowledge on the
basic protection principles and applied it to a specific relay type.
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
181 Special Issue,
p. 165–183
5. LITERATURE
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
182 Special Issue,
p. 165–183
[16] Tziouvaras, D., Mooney, J., Alexander, G.: Functional Integration in
Modern Distance Relays Improves the Reliability of Power Systems.
Schweitzer Engineering Laboratories, Inc., USA, 2004.
[17] Tziouvaras, D.E., Altura, H., Benmouyal, G., Roberts, JR.: Line
Differential Protection with an Enhanced Characteristic. Pullman,
Washington, USA, 2014.
A. Stošić, A. Marušić, J. Havelka, Transmission lines protection using SIPROTEC numerical relays, Journal of Energy, vol. 66 Number 1–4 (2017)
183 Special Issue,
p. 165–183