SAQ6
SAQ6
SAQ6
1
Prime Review Center (Review Course) UST Correlation PIPE 03
1. A 4 m by 4 m by 4 m room has a relative A. 0.50 C. 0.70 than 15C dry bulb. The sensible heat gain is
humidity ratio of 80%. The pressure in the 7. If the sensible heat ratio is 0.80 and the B. 0.60 D. 0.40 110 kW and the latent gain is 37.5 kW. Take
room is 120 kPa and temperature is 35°C (Psat cooling load is 100 kW, what is the amount ventilating air as 25% by weight of the air
= 5.628 kPa). What is the mass of vapor in the of sensible heating? 13. A stream of outdoor air is mixed with a from the room, and is at 35C dry bulb and
room. Use Rvapor = 0.4615 kN-m/kg-K. A. 80 kW C. 125 kW stream of return air in an air conditioning 60% RH. Determine refrigerating capacity in
A. 2.03 kgv C. 3.03 kgv B. 60 kW D. 100 kW system that operates at 101 kPa pressure. tons.
B. 5.03 kgv D. 1.03 kgv 8. A pressure difference of 350 Pa is available to The flow rate of outdoor system air is 2 kg/s A. 43.45 C. 63.28
force 20°C air through a circular sheet-metal and its condition is 35C dry-bulb B. 54.23 D. 76.34
2. What is the specific volume of an air-vapor duct 450 mm in diameter and 25 m long. At temperature and 25C wet-bulb temperature
mixture at 30C and a relative humidity of 20°C, ρ = 1.204 kg/m3 and take friction factor, .The flow rate of return air is 3 kg/s and its 18. Determine the quantity of heat required to
45% at 101.325 kPa. f = 0.016. Determine the velocity. conditions is 24C and 50% relative humidity. raise 20 m3/min of air at 20C and 80 percent
A. 0.587 m3/kg C. 0.875 m3/kg A. 25.57 m/s C. 28.54 m/s Determine the enthalpy of the mixture. relative humidity to 35C.
3
B. 0.785 m /kg D. 0.758 m3/kg B. 27.55 m/s D. 24.85 m/s A. 91.56 kJ/kg C. 69.15 kJ/kg A. 5 kW C. 7 kW
B. 51.69 kJ/kg D. 59.16 kJ/kg B. 6 kW D. 8 kW
3. Compute the humidity ratio of air at 62 9. Determine the quantity of heat required to
percent relative humidity and 34°C when the raise 20 m3/min of air at 20°C and 80 percent 14. A mixture of dry air and water vapor is at 19. Determine the sensible heat of 5 lb of air
barometric pressure is 101.325 kPa. relative humidity to 35°C. temperature of 21C under a pressure of 101 having a dry bulb temperature of 70F and a
A. 0.021 C. 0.041 A. 5 kW C. 7 kW kPa. The dew point temperature is 15C. humidity ratio of 0.0092 lb/lb, the latter
B. 0.031 D. 0.051 B. 6 kW D. 8 kW Calculate the relative humidity? corresponding to a dew point temperature
A. 1.60 kg C. 2.60 kg of approximately 55F.
4. Determine the partial pressure of water 10. In an air conditioning system, if the re- B. 1.80 kg D. 2.80 kg A. 94 Btu C. 84 Btu
vapor if the barometric pressure is 101.325 circulated air is three times the outside air B. 48 Btu D. 49 Btu
kPa and the humidity ratio is 0.05. and the mass of supply air is 20 kg/s, what is 15. In an air conditioning unit, 3.5 m3/s of air at
A. 7.54 kPa C. 5.74 kPa the mass of the outside air. 27C dry-bulb temperature 50 percent 18. A 10 kg/s of air enters the theater at 16C. The
B. 4.75 kPa D. 5.47 kPa A. 5 kg/s C. 10 kg/s relative humidity and standard atmospheric theater is to be maintained at 27C dry-bulb
B. 7 kg/s D. 12 kg/s pressure enters the unit. The leaving temperature and 20C wet-bulb temperature.
5. An air-vapor mixture has a dry bulb condition of the air is 13C dry-bulb If the sensible heat ratio is 0.71, calculate the
temperature of 30°C and a humidity ratio of 11. A duct 0.40 m high and 0.80 wide suspended temperature and 90% relative humidity. latent heat load of the theater?
0.015. Calculate the enthalpy at 85 kPa from the ceiling in a corridor, makes a right Calculate the refrigerating capacity in kW. A. 45.21 kW C. 74.24 kW
barometric pressure. angle turn in the horizontal plane. The inner A. 87.57 kW C. 57.87 kW B. 110.682 kW D. 78.58 kW
A. 68.34 kJ/kg C. 72.45 kJ/kg radius is 0.2 m and the outer radius is 1.0 B. 77.57 kW D. 58.77 kW
B. 54.35 kJ/kg D. 67.45 kJ/kg measured from the same center. The velocity 20. Calculate the air flow in ft3/min of
of air in the duct is 10 m/s. Compute the 16. One hundred fifty cubic meters of air per mechanical ventilation required to exhaust
6. A room being air conditioned is being held at pressure drop in this elbow. Assuming, f = minute at 35C dry bulb and 25C wet bulb an accumulation of refrigerant due to leaks
25°C dry bulb and 50% relative humidity. A 0.3, ρ = 1.204 kg/m3 and L = 10 m. temperature are to be cooled to 21C. of the system capable of revolving air from
flow rate of 5 m3/s of supply air at 15°C dry A. 341 Pa C. 143 Pa Determine the refrigeration capacity. the machinery room for a mass of 4 kg
bulb and 80% RH is being delivered to the B. 441 Pa D. 144 Pa A. 10 TOR C. 12 TOR refrigerant.
room to maintain that steady condition at B. 11 TOR D. 13 TOR A. 200 C. 300
100 kPa. What is the sensible heat absorbed 12. If the total heat removed per pound of dry B. 350 D. 400
from the room air in kW air is 0.10 Btu and the sensible heat removed 17. An auditorium is to be maintained at a
A. 60.5 kW C. 60.5 hp per pound of dry air is 6 Btu. Compute the temperature of 26C dry bulb and 50% RH. Air …End…
B. 88 kW D. 214.2 kW sensible heat factor (SHR). is to be supplied at a temperature not lower