description monitoring and assessing equipment in electricity supply systems. It combines the monitoring functions of
high-resolution digital fault recorders, power quality analysers, phasor measurement units, continuous data
recorders and event recorders in one device.
Individual devices can be networked via an Interlink interface to monitor extensive installations.
Multi-processor Digital signal processor (DSP) for processing signals and processes in real time
system Communication processor
for mass data storage, simultaneous data communication using different interfaces and
protocols, web server functionality and stand-alone operation
User controls and 8 status LEDs for alarm, trigger and status display
displays 3.5" colour graphical display with touch screen and 4 function keys
Operating software SHERLOG operating software for Windows 7, Windows 8.1 (32 and 64 bit),
Windows 10 (32 and 64 bit), Windows Server 2012 R2
Function Recording functions Digital fault recorder, 2 sampling rates from 500 Hz…30 kHz
overview RMS fault recorder, sampling rate from 1 Hz...120 Hz
Continuous data recording
Event data recording
Power quality analyser, class A (optional)
Phasor measurement unit/PMU (optional)
Technical specifications subject to change without prior notice | ©03/2018 KoCoS Messtechnik AG
www.kocos.com Doc. 7618000 Rev. 1.50
Analog inputs General information Resolution 16 Bit, S/R:92 dB typical
Resolution 0.1 ms
Binary outputs Electronic relays Number 2, freely configurable for status and alarm signals
Mechanical relays Number 8, freely configurable for status and alarm signals
Technical specifications subject to change without prior notice | ©03/2018 KoCoS Messtechnik AG
www.kocos.com Doc. 7618000 Rev. 1.50
Time Standard equipment Internal real-time clock Accuracy 2.5 ppm without external time synchronisation
synchronisation
NTP/SNTP Synchronisation over Ethernet network
Synchronisation GPS receiver Internal GPS receiver with SMA antenna connection
module (optional) Accuracy of internal seconds pulse: <60 ns
Optical GPS input For connection to external GPS systems over optical fibre
(2 x ST II)
Time telegram: NMEA-0183-RMC, 4800 baud, non-inverted
Pulse input: seconds or minutes pulses, non-inverted
DCF 77 input DCF 77 pulse telegram input for connection to external clock
systems or to the KoCoS DCF 77 antenna module
IRIG-B signal input Coaxial connection for B001, B002 and B003 telegrams
Interface module Data communication 1 x 10/100 Mbit optical Ethernet (ST II)
(optional)
1 x 10/100 Mbit Ethernet (RJ 45)
Power supply Operating voltage Type 1: 90…365 VDC and 85…265 VAC; 47…63 Hz
Type 2: 9…18 VDC
Type 3: 18…36 VDC
Type 4: 36…72 VDC
Power consumption Max. 30 VA with maximum configuration (32 analog and 128 binary inputs)
Redundancy Power supply unit and power supply redundancy provided by accommodation of up to
two independent power supply modules of the same type or of different types
Technical specifications subject to change without prior notice | ©03/2018 KoCoS Messtechnik AG
www.kocos.com Doc. 7618000 Rev. 1.50
Complete system Mechanical Weight 2.9 kg
properties
Housing 19" housing for rack mounting, 84 HP/3 U
Other RoHS-compliant
EMC standards IEC 60255-1 Measuring relays and protection equipment - Part 1
Technical specifications subject to change without prior notice | ©03/2018 KoCoS Messtechnik AG
www.kocos.com Doc. 7618000 Rev. 1.50