B2 Current and Voltage Transformers
B2 Current and Voltage Transformers
B2 Current and Voltage Transformers
B2 Transformers
Network Protection & Automation Guide
Network Protection & Automation Guide
Chapter
B2
Current and Voltage
Transformers
1. Introduction 107
B2 1. Introduction
Whenever the values of voltage or current in a power circuit are 1.1 Measuring transformers
too high to permit convenient direct connection of measuring
Voltage and current transformers for low primary voltage or
instruments or relays, coupling is made through transformers.
current ratings are not readily distinguishable; for higher ratings,
Such 'measuring' transformers are required to produce a scaled
dissimilarities of construction are usual. Nevertheless the
down replica of the input quantity to the accuracy expected for
differences between these devices lie principally in the way they
the particular measurement; this is made possible by the high
are connected into the power circuit. Voltage transformers are
efficiency of the transformer. The performance of measuring
much like small power transformers, differing only in details of
transformers during and following large instantaneous changes
design that control ratio accuracy over the specified range of
in the input quantity is important, in that this quantity may depart
output. Current transformers have their primary windings
from the sinusoidal waveform. The deviation may consist of a
connected in series with the power circuit, and so also in series
step change in magnitude, or a transient component that persists
with the system impedance. The response of the transformer is
for an appreciable period, or both. The resulting effect on
radically different in these two modes of operation.
instrument performance is usually negligible, although for
precision metering a persistent change in the accuracy of the
transformer may be significant.
However, many protection systems are required to operate during
the period of transient disturbance in the output of the measuring 1/1 Rp Lp Rs Ls
transformers that follows a system fault. The errors in transformer
output may abnormally delay the operation of the protection, or
cause unnecessary operations. The functioning of such
Ze Burden
transformers must, therefore, be examined analytically.
It can be shown that the transformer can be represented by the
equivalent circuit of Figure B2.1, where all quantities are referred
to the secondary side.
When the transformer is not 1/1 ratio, this condition can be
represented by energising the equivalent circuit with an ideal
Figure B2.1:
transformer of the given ratio but having no losses.
Equivalent circuit of transformer
In the shunt mode, the system voltage is applied across the 2.1 Errors
input terminals of the equivalent circuit of Figure B2.1. The
The ratio and phase errors of the transformer can be calculated
vector diagram for this circuit is shown in Figure B2.2.
using the vector diagram of Figure B2.2.
The secondary output voltage Vs is required to be an accurate The ratio error is defined as:
scaled replica of the input voltage Vp over a specified range
of output. To this end, the winding voltage drops are made ( K n Vs )
×100%
small, and the normal flux density in the core is designed to Vp
be well below the saturation density, in order that the exciting
current may be low and the exciting impedance substantially where:
constant with a variation of applied voltage over the desired Kn is the nominal ratio
operating range including some degree of overvoltage. These Vp is the primary voltage
limitations in design result in a VT for a given burden being Vs is the secondary voltage
much larger than a typical power transformer of similar rating.
If the error is positive, the secondary voltage exceeds the
The exciting current, in consequence, will not be as small,
nominal value. The turns ratio of the transformer need not be
relative to the rated burden, as it would be for a typical power
equal to the nominal ratio; a small turns compensation will
transformer.
usually be employed, so that the error will be positive for low
burdens and negative for high burdens.
Table B2.1:
Measuring voltage transformer error limits
Ie = exciting current
Im = magnetizing component
2.2 Voltage factors
Ic = iron loss component
The quantity Vf in Table B2.3 is an upper limit of operating
Ф = phase angle error voltage, expressed in per unit of rated voltage. This is important
for correct relay operation and operation under unbalanced
Ѳ = secondary burden angle
fault conditions on unearthed or impedance earthed systems,
Ip Rp = primary resistance voltage drop resulting in a rise in the voltage on the healthy phases.
Ip Xp = primary reactance voltage drop Voltage factors, with the permissible duration of the maximum
voltage, are given in Table B2.3.
Is Rs = secondary resistance voltage drop
Is Xs = secondary reactance voltage drop
Is = secondary current
I pL = load component of primary current
Ip = primary current
Table B2.3:
Voltage transformers: Permissible duration of maximum
voltage
2.4 Protection of voltage transformers The three voltages of a balanced system summate to zero,
but this is not so when the system is subject to a single-phase
Voltage Transformers can be protected by H.R.C. fuses on
earth fault. The residual voltage of a system is measured by
the primary side for voltages up to 66kV. Fuses do not usually
connecting the secondary windings of a VT in 'broken delta'
have a sufficient interrupting capacity for use with higher
as shown in Figure B2.4.
voltages. Practice varies, and in some cases protection on
the primary is omitted.
The secondary of a Voltage Transformer should always be A B C
protected by fuses or a miniature circuit breaker (MCB). The
device should be located as near to the transformer as
possible. A short circuit on the secondary circuit wiring will
produce a current of many times the rated output and cause
excessive heating. Even where primary fuses can be fitted,
these will usually not clear a secondary side short circuit
because of the low value of primary current and the minimum
practicable fuse rating.
Residual
2.5 Construction voltage
The output of the secondary windings connected in broken 2.8 Cascade voltage transformers
delta is zero when balanced sinusoidal voltages are applied,
The capacitor VT Section 3 was developed because of the
but under conditions of unbalance a residual voltage equal
high cost of conventional electromagnetic voltage transformers
to three times the zero sequence voltage of the system will
but, as shown in Section 3.2, the frequency and transient
be developed.
responses are less satisfactory than those of the orthodox
In order to measure this component, it is necessary for a zero voltage transformers. Another solution to the problem is the
sequence flux to be set up in the VT, and for this to be possible cascade VT (Figure B2.5).
there must be a return path for the resultant summated flux.
The conventional type of VT has a single primary winding,
The VT core must have one or more unwound limbs linking
the insulation of which presents a great problem for voltages
the yokes in addition to the limbs carrying windings. Usually
above about 132kV. The cascade VT avoids these difficulties
the core is made symmetrically, with five limbs, the two
by breaking down the primary voltage in several distinct and
outermost ones being unwound. Alternatively, three single-
separate stages.
phase units can be used. It is equally necessary for the primary
winding neutral to be earthed, for without an earth, zero The complete VT is made up of several individual transformers,
sequence exciting current cannot flow. the primary windings of which are connected in series, as
shown in Figure B2.5. Each magnetic core has primary
A VT should be rated to have an appropriate voltage factor
windings (P) on two opposite sides. The secondary winding
as described in Section 2.2 and Table B2.3, to cater for the
(S) consists of a single winding on the last stage only. Coupling
voltage rise on healthy phases during earth faults.
windings (C) connected in pairs between stages, provide low
Voltage transformers are often provided with a normal star- impedance circuits for the transfer of load ampere-turns
connected secondary winding and a broken-delta connected between stages and ensure that the power frequency voltage
‘tertiary’ winding. Alternatively the residual voltage can be is equally distributed over the several primary windings.
extracted by using a star/broken-delta connected group of
The potentials of the cores and coupling windings are fixed
auxiliary voltage transformers energised from the secondary
at definite values by connecting them to selected points on
winding of the main unit, providing the main voltage transformer
the primary windings. The insulation of each winding is
fulfils all the requirements for handling a zero sequence voltage
sufficient for the voltage developed in that winding, which is
as previously described. The auxiliary VT must also be suitable
a fraction of the total according to the number of stages. The
for the appropriate voltage factor. It should be noted that third
individual transformers are mounted on a structure built of
harmonics in the primary voltage wave, which are of zero
insulating material, which provides the interstage insulation,
sequence, summate in the broken-delta winding.
accumulating to a value able to withstand the full system
2.7 Transient performance voltage across the complete height of the stack.
Transient errors cause few difficulties in the use of conventional
voltage transformers, although some do occur. Errors are
A
generally limited to short time periods following the sudden
application or removal of voltage from the VT primary.
If a voltage is suddenly applied, an inrush transient will occur, C
as with power transformers. The effect will, however, be less P
Figure B2.5:
Schematic diagram of typical cascade voltage transformer
The entire assembly is contained in a hollow cylindrical Capacitors C1 and C2 cannot conveniently be made to close
porcelain housing with external weather-sheds; the housing tolerances, so tappings are provided for ratio adjustment,
is filled with oil and sealed, an expansion bellows being either on the transformer T, or on a separate auto-transformer
included to maintain hermetic sealing and to permit expansion in the secondary circuit. Adjustment of the tuning inductance
with temperature change. L is also needed; this can be done with tappings, a separate
tapped inductor in the secondary circuit, by adjustment of
The size of electromagnetic voltage transformers for the higher
gaps in the iron cores, or by shunting with variable capacitance.
voltages is largely proportional to the rated voltage; the cost
A simplified equivalent circuit is shown in Figure B2.7.
tends to increase at a disproportionate rate. The capacitor
voltage transformer (CVT) is often more economic.
This device is basically a capacitance potential divider. As
with resistance-type potential dividers, the output voltage is
seriously affected by load at the tapping point. The capacitance
divider differs in that its equivalent source impedance is
capacitive and can therefore be compensated by a reactor
connected in series with the tapping point. With an ideal
reactor, such an arrangement would have no regulation and
could supply any value of output.
A reactor possesses some resistance, which limits the output
that can be obtained. For a secondary output voltage of 110V,
the capacitors would have to be very large to provide a useful
output while keeping errors within the usual limits. The solution
Figure B2.7:
is to use a high secondary voltage and further transform the
Simplified equivalent circuit of capacitor voltage transformer
output to the normal value using a relatively inexpensive
electromagnetic transformer. The successive stages of this
reasoning are indicated in Figure B2.6. It will be seen that the basic difference between Figure B2.7
and Figure B2.1 is the presence of C and L. At normal
frequency when C and L are in resonance and therefore
cancel, the circuit behaves in a similar manner to a conventional
VT. At other frequencies, however, a reactive component exists
C1 which modifies the errors.
Standards generally require a CVT used for protection to
conform to accuracy requirements of Table B2.2 within a
C2 C2
frequency range of 97-103% of nominal. The corresponding
frequency range of measurement CVT’s is much less, 99%-
101%, as reductions in accuracy for frequency deviations
(a) Basic capacitive (b) Capacitive divider with
voltage divider inductive compensation outside this range are less important than for protection
applications.
L = tuning inductance
Rp = primary winding resistance (plus losses)
Ze = exciting impedance of transformer T
Rs = secondary circuit resistance
auxiliary capacitor. The voltage on the auxiliary capacitor is components, oscillations at fundamental frequency or at other
higher at full rated output than at no load, and the capacitor sub-harmonics or multiples of the supply frequency are
is rated for continuous service at this raised value. The spark possible but the third sub-harmonic is the one most likely to
gap will be set to flash over at about twice the full load voltage. be encountered.
The effect of the spark gap is to limit the short-circuit current The principal manifestation of such an oscillation is a rise in
which the VT will deliver and fuse protection of the secondary output voltage, the r.m.s. value being perhaps 25%-50% above
circuit has to be carefully designed with this point in mind. the normal value; the output waveform would generally be of
Facilities are usually provided to earth the tapping point, either the form shown in Figure B2.8.
manually or automatically, before making any adjustments to
tappings or connections.
3.2 Transient behaviour of capacitor voltage
transformers
A CVT is a series resonant circuit. The introduction of the
Amplitude
electromagnetic transformer between the intermediate voltage
and the output makes possible further resonance involving
Time
the exciting impedance of this unit and the capacitance of
the divider stack. When a sudden voltage step is applied,
oscillations in line with these different modes take place, and
will persist for a period governed by the total resistive damping
that is present. Any increase in resistive burden reduces the
time constant of a transient oscillation, although the chance
of a large initial amplitude is increased.
Figure B2.8:
For very high-speed protection, transient oscillations should Typical secondary voltage waveform with third sub-harmonic
be minimised. Modern capacitor voltage transformers are oscillation.
much better in this respect than their earlier counterparts, but
high performance protection schemes may still be adversely
affected. Such oscillations are less likely to occur when the circuit losses
are high, as is the case with a resistive burden, and can be
3.3 Ferro-resonance
prevented by increasing the resistive burden. Special anti-
The exciting impedance Ze of the auxiliary transformer T and ferro-resonance devices that use a parallel-tuned circuit are
the capacitance of the potential divider together form a sometimes built into the VT. Although such arrangements help
resonant circuit that will usually oscillate at a sub-normal to suppress ferro-resonance, they tend to impair the transient
frequency. If this circuit is subjected to a voltage impulse, the response, so that the design is a matter of compromise.
resulting oscillation may pass through a range of frequencies.
Correct design will prevent a CVT that supplies a resistive
If the basic frequency of this circuit is slightly less than one-
burden from exhibiting this effect, but it is possible for non-
third of the system frequency, it is possible for energy to be
linear inductive burdens, such as auxiliary voltage transformers,
absorbed from the system and cause the oscillation to build
to induce ferro- resonance. Auxiliary voltage transformers for
up. The increasing flux density in the transformer core reduces
use with capacitor voltage transformers should be designed
the inductance, bringing the resonant frequency nearer to
with a low value of flux density that prevents transient voltages
the one-third value of the system frequency.
from causing core saturation, which in turn would bring high
The result is a progressive build-up until the oscillation exciting currents.
stabilises as a third sub-harmonic of the system, which can
be maintained indefinitely. Depending on the values of
B2 4. Current transformers
=21.2Ω
4. Current transformers B2
A reduction of the secondary winding by one or two turns is 4.3 Accuracy limit current of protection current
often used to compensate for this. For example, in the CT transformers
corresponding to Figure B2.9, the worst error due to the use
Protection equipment is intended to respond to fault conditions,
of an inductive burden of rated value would be about 1.2%.
and is for this reason required to function at current values
If the nominal turns ratio is 2:120, removal of one secondary
above the normal rating. Protection class current transformers
turn would raise the output by 0.83% leaving the overall current
must retain a reasonable accuracy up to the largest relevant
error as -0.37%.
current. This value is known as the ‘accuracy limit current’
For lower value burden or a different burden power factor, the and may be expressed in primary or equivalent secondary
error would change in the positive direction to a maximum of terms. The ratio of the accuracy limit current to the rated
+0.7% at zero burden; the leakage reactance of the secondary current is known as the 'accuracy limit factor'.
winding is assumed to be negligible. No corresponding
The accuracy class of protection current transformers is
correction can be made for phase error, but it should be noted
shown in Table B2.5.
that the phase error is small for moderately reactive burdens.
4.2 Composite error
Phase Composite
This is defined in IEC 60044-1 as the r.m.s. value of the Current error
displacement error at rated
at rated
difference between the ideal secondary current and the actual Class at rated accuracy
primary
secondary current. It includes current and phase errors and current limit primary
current (%)
(minutes) current (%)
the effects of harmonics in the exciting current. The accuracy
class of measuring current transformers is shown in Table 5P +/-1 +/-60 5
B2.4. 10P +/-3 10
Standard accuracy limit factors are 5, 10, 15, 20, and 30
B2 4. Current transformers
4. Current transformers B2
B2 4. Current transformers
4.8 Secondary current rating most important, and were first observed in connection with
balanced forms of protection, which were liable to operate
The choice of secondary current rating is determined largely
unnecessarily when short-circuit currents were suddenly
by the secondary winding burden and the standard practice
established.
of the user. Standard CT secondary current ratings are 5A
and 1A. The burden at rated current imposed by digital or 4.10.1 Primary current transient
numerical relays or instruments is largely independent of the
The power system, neglecting load circuits, is mostly inductive,
rated value of current. This is because the winding of the
so that when a short circuit occurs, the fault current that flows
device has to develop a given number of ampere-turns at
is given by:
rated current, so that the actual number of turns is inversely
Ep
proportional to the current, and the impedance of the winding
varies inversely with the square of the current rating. However,
ip =
2
R + ω L 2 2
[ sin (ω t + β − α ) + sin ( α − β ) e − ( R L) t
]
electromechanical or static earth-fault relays may have a
...Equation B2.1
burden that varies with the current tapping used.
where:
Interconnection leads do not share this property, however,
being commonly of standard cross-section regardless of Ep = peak system e.m.f.
rating. Where the leads are long, their resistance may be R = system resistance
appreciable, and the resultant burden will vary with the square
of the current rating. For example a CT lead run of the order L = system inductance
of 200 metres, a typical distance for outdoor EHV switchgear, β = initial phase angle governed by instant of fault
could have a loop resistance of approximately 3 Ω. occurrence
The CT lead VA burden if a 5A CT is used would be 75VA, to α = system power factor angle
which must be added the relay burden (up to perhaps 10VA
for an electromechanical relay, but less than 1VA for a numerical = tan-1ωL/R
relay), making a total of 85VA. Such a burden would require The first term of Equation B2.1 represents the steady state
the CT to be very large and expensive, particularly if a high alternating current, while the second is a transient quantity
accuracy limit factor were also applicable. responsible for displacing the waveform asymmetrically.
With a 1A CT secondary rating, the lead burden is reduced Ep is the steady state peak current Ip.
to 3VA, so that with the same relay burden the total becomes 2 2 2
R +ω L
a maximum of 13VA. This can be provided by a CT of normal
dimensions, resulting in a saving in size, weight and cost. The maximum transient occurs when sin = ( α - β ) = 1; no
Hence modern CT’s tend to have secondary windings of 1A other condition need be examined.
rating. However, where the primary rating is high, say above
2000A, a CT of higher secondary rating may be used, to limit So:
the number of secondary turns. In such a situation secondary π
i p = I p sin ω t − + e − (
R L) t
ratings of 5A may be used. In extreme cases a 20A secondary 2 ...Equation B2.2
CT may be used, followed by a 20/1 interposing CT.
When the current is passed through the primary winding of a
4.9 Rated short-time current
current transformer, the response can be examined by replacing
A current transformer is overloaded while system short-circuit the CT with an equivalent circuit as shown in Figure B2.9(b).
currents are flowing and will be short-time rated. Standard
As the 'ideal' CT has no losses, it will transfer the entire function,
times for which the CT must be able to carry rated short-time
and all further analysis can be carried out in terms of equivalent
currents (STC) are 0.25, 0.5, 1.0, 2.0 or 3.0 seconds.
secondary quantities ( is and Is ). A simplified solution is
A CT with a particular short-time current/ time rating will carry obtainable by neglecting the exciting current of the CT.
a lower current for a longer time in inverse proportion to the
The flux developed in an inductance is obtained by integrating
square of the ratio of current values. The converse, however,
the applied e.m.f. through a time interval:
cannot be assumed, and larger current values than the S.T.C.
rating are not permissible for any duration unless justified by φ = K ∫t vdt
t2
...Equation B2.3
a new rating test to prove the dynamic capability. 1
4. Current transformers B2
0.7
Again, fT is the time constant expressed in cycles of the a.c.
quantity T', so that: 0.6
0.1
For example, a system time constant of three cycles results
in a transient factor of (1+6 π ), or 19.85; that is, the CT would 0
Time
be required to handle almost twenty times the maximum flux
-0.1
produced under steady state conditions.
= Transient exciting current
The above theory is sufficient to give a general view of the = Secondary output current to burden
problem. In this simplified treatment, no reverse voltage is = 0.06s
= 0.12s
applied to demagnetise the CT, so that the flux would build
up as shown in Figure B2.13.
Figure B2.14:
Response of a current transformer to a transient asymmetric
current
B2 4. Current transformers
d. the effect of hysteresis, apart from loss as discussed under Secondary current
(b) above, is not included. Hysteresis makes the inductance Residual flux = 0
Resistive burden
different for flux build up and decay, so that the secondary Power system T.C. = 0.05s
time constant is variable. Moreover, the ability of the core
to retain a 'remanent' flux means that the value of B
developed in Equation B2.5 has to be regarded as an Figure B2.16:
Distortion in secondary current due to saturation
4. Current transformers B2
The presence of residual flux varies the starting point of the 4.11 Harmonics during the transient period
transient flux excursion on the excitation characteristic.
When a CT is required to develop a high secondary e.m.f.
Remanence of like polarity to the transient will reduce the
under steady state conditions, the non-linearity of the excitation
value of symmetric current of given time constant which the
impedance causes some distortion of the output waveform;
CT can transform without severe saturation; conversely, reverse
such a waveform will contain, in addition to the fundamental
remanence will greatly increase the ability of a CT to transform
current, odd harmonics only.
transient current.
When, however, the CT is saturated uni-directionally while
If the CT were the linear non-saturable device considered in
being simultaneously subjected to a small a.c. quantity, as in
the analysis, the sine current would be transformed without
the transient condition discussed above, the output will contain
loss of accuracy. In practice the variation in excitation
both odd and even harmonics. Usually the lower numbered
inductance caused by transferring the centre of the flux swing
harmonics are of greatest amplitude and the second and
to other points on the excitation curve causes an error that
third harmonic components may be of considerable value.
may be very large. The effect on measurement is of little
This may affect relays that are sensitive to harmonics.
consequence, but for protection equipment that is required
to function during fault conditions, the effect is more serious. 4.12 Test windings
The output current is reduced during transient saturation,
On-site conjunctive testing of current transformers and the
which may prevent the relays from operating if the conditions
apparatus that they energise is often required. It may be
are near to the relay setting. This must not be confused with
difficult, however, to pass a suitable value of current through
the increased r.m.s. value of the primary current due to the
the primary windings, because of the scale of such current
asymmetric transient, a feature which sometimes offsets the
and in many cases because access to the primary conductors
increase ratio error. In the case of balanced protection, during
is difficult. Additional windings may be provided to make such
through faults the errors of the several current transformers
tests easier, these windings usually being rated at 10A. The
may differ and produce an out-of-balance quantity, causing
test winding will inevitably occupy appreciable space and
unwanted operation.
the CT will cost more. This fact should be weighed against
the convenience achieved; very often it will be found that the
tests in question can be replaced by alternative procedures.
The preceding types of instrument transformers have all been Optical converters and optical glass fibre channels implement
based on electromagnetic principles using a magnetic core. the link between the sensor and the low-voltage output. The
There are now available several new methods of transforming fundamental difference between an instrument transducer
the measured quantity using optical and mass state methods. and a conventional instrument transformer is the electronic
interface needed for its operation, providing a low power
5.1 Optical instrument transducers
signal (voltage or current or digital) for connection to protection
The key features of a freestanding optical instrument transducer devices. This type of interface is not practical for 1 or 5A
can be illustrated with the functional diagram of Figure B2.17. conventional inputs. This interface is required both for the
sensing function and for adapting the new sensor technology
to that of the secondary output in low current, low voltage or
digital communication format (IEC 61850-9-2).
HV
Bus Non-conventional optical transducers lend themselves to
smaller, lighter devices where the overall size and power rating
Insulating of the unit does not have any significant bearing on the size
function
Sensor
Sensing and the complexity of the sensor. Small, lightweight insulator
function Instrument structures may be tailor-made to fit optical sensing devices
E/O converter Transformer
+ as an integral part of the insulator. Additionally, the non-linear
Communication effects and electromagnetic interference problems in the
secondary wiring of conventional VTs and CTs are minimised.
Optical link
(fibre optics) Optical transducers can be separated into two families: firstly
Electronic the hybrid transducers, making use of conventional electrical
interface Communication circuit techniques to which are coupled various optical
+
O/E converter converter systems, and secondly the ‘all-optical’ transducers
that are based on fundamental, optical sensing principles.
Secondary
output 5.1.1 Optical sensor concepts
Certain optical sensing media (glass, crystals, plastics) show
a sensitivity to electric and magnetic fields and some properties
of a probing light beam can be altered when passing through
Figure B2.17: them. One simple optical transducer description is given in
Functional diagram of optical instrument transducer Figure. B2.18.
'Odd' polariser
input output
polariser polariser
optical optical
fibre fibre sensing
light
detector
in out
light source
45 ∞ 90 ∞
optical
zero field level
1.0 sensing 1.0
medium
+
0.5 0.5
0 0
t t
reference modulated
light input light input
intensity intensity
Figure. B2.18:
Schematic representation of the concepts behind the optical sensing of varying electric and magnetic fields
Consider the case of a beam of light passing through a pair of current measuring device the sensitive element is either located
polarising filters. If the input and output polarising filters have their free in the magnetic field (Figure B2.19(a)) or it can be immersed
axes rotated 45° from each other, only half the light will come in a field-shaping magnetic ‘gap’ (Figure B2.19(b)). In the case of
through. The reference light input intensity is maintained constant a voltage-sensing device (Figure B2.20) the same alternatives
over time. Now if these two polarising filters remain fixed and a exist, this time for elements that are sensitive to electric fields. The
third polarising filter is placed in between them, a random rotation possibility exists of combining both sensors within a single housing,
of this middle polariser either clockwise or counter-clockwise will thus providing both a CT and VT within a single compact housing
be monitored as a varying or modulated light output intensity at that gives rise to space savings within a substation.
the light detector.
When a block of optical sensing material (glass or crystal) is
immersed in a varying magnetic or electric field, it plays the role I AC line current
due to the presence of varying fields is converted back to time- (a) 'Free-field' type
measuring applications. This reflects the fact that the sensor is not
basically sensitive to a current but to the magnetic field generated
by this current. Although ‘all-fibre’ approaches are feasible, most Optical fibres
Magnetic field
commercially available optical current transducers rely on a bulk-
Gapped
glass sensor. Most optical voltage transducers, on the other hand, magnetic core
Magneto-optic sensor
rely on an electro-optic effect sensor. This reflects the fact that the (b) 'Field-shaping' type
running between the base of the unit and the sensor location
provides the communication link.
Figure B2.20:
The sensing element is made of an optical material that is positioned Optical voltage sensor based on the electrical properties of
in the electric or magnetic field to be sensed. In the case of a optical materials
In all cases there is an optical fibre that channels the probing Similar to conventional instrument transformers there are ‘live
reference light from a source into the medium and another tank’ and ‘dead tank’ optical transducers. Typically, current
fibre that channels the light back to analysing circuitry. In transducers take the shape of a closed loop of light-transparent
sharp contrast with a conventional free-standing instrument material, fitted around a straight conductor carrying the line
transformer, the optical instrument transformer needs an current (Figure B2.22). In this case a bulk-glass sensor unit
electronic interface module in order to function. Therefore its is depicted (Figure B2.22(a)), along with an ‘all-optical’ sensor
sensing principle (the optical material) is passive but its example, as shown in Figure B2.22(b).
operational integrity relies on the interface that is powered in
the control room (Figure B2.21).
High voltage
sensor assembly
Fibre optic cable
Optical
interface
unit
Junction
box
AC/DC source
Figure B2.21:
Novel instrument transducer concept requiring an electronic interface in the control room
Electro-optic sensor
(bulk-glass transducer) AC line current
Dome
I
Electro-optic sensor
('all-fibre' transducer)
AC Bulk-glass
H1 H2 sensing element
line I I
current
Light in
Optical fibres
Light out
Fibre optic Liquid /solid/ gaseous
cable conduit internal insulation (a) Glass sensor approach
AC line current
I
Insulator
column Light in
Figure B2.22:
Conceptual design of a double-sensor optical CT
Figure B2.23:
Optical voltage transducer concepts, using a ‘full-voltage’ sensor
Figure B2.24:
Field installation of a combined optical CT/VT
Sensing current
Sensing element
Air core
toroidal coil
Figure B2.25:
Conceptual design of a Hall-effect current sensing element Electrical to optical
fitted in a field-shaping gap converter
B2