The Racking Performance of Shear Walls With Variou
The Racking Performance of Shear Walls With Variou
The Racking Performance of Shear Walls With Variou
net/publication/238072956
The racking performance of shear walls with various aspect ratios. Part 1.
Monotonic tests of fully anchored walls
CITATIONS READS
12 1,289
2 authors:
All content following this page was uploaded by J. Daniel Dolan on 09 April 2015.
✳
Alexander J. Salenikovich
✳
J. Daniel Dolan
Abstract
Current design values for light-frame timber shear walls are based on results of standard monotonic tests of 2.4-m (8-ft.) square
walls restrained against overturning. The shear resistance of walls is calculated in terms of load per unit length, assuming that shear
forces are distributed uniformly throughout the wall of any size. In past earthquakes, structural failures occurred near large open-
ings where the lateral forces were transmitted through narrow wall segments. To improve our understanding of shear wall racking
performance and to facilitate further development of seismic design methodology, a comprehensive study has been conducted that
combines experimental and numerical analyses of shear walls of various configurations. This study included static monotonic and
cyclic tests of full-size shear walls with height-to-length ratios of 4:1, 2:1, 1:1, and 2:3. Discussed in this paper is the static
monotonic response of shear walls with overturning restraint representative of segmented wall construction practices. These walls
were attached to the foundation by means of hold-down anchors and shear bolts. Test results revealed that the performance of seg-
mented walls did not depend on the aspect ratio with the exception of narrow (4:1) walls, which exhibited 50 percent lower stiffness
per unit length relative to the other walls tested. Differences in failure patterns and reduction in deformation capacity were ob-
served when low-density studs were used at the wall ends. Traditional methods of analyzing segmented shear walls with hold-down
anchors were shown to be sufficiently conservative.
alls as components of the lateral bers are called struts. Struts collect the resist the overturning moment created by
force resisting system of a building are horizontal forces from the upper parts of the shear forces. Segmented wall design
defined as shear walls. When resisting the building through framing fasteners practice usually requires that the chords
wind or an earthquake, shear walls act as and transfer the load to the sheathing be attached to the lower structures (foun-
vertical cantilevers transferring the lat- through the sheathing fasteners. dation or story below) through hold-
eral forces from the upper parts of the Sheathing panels provide racking resis- down anchors and anchor bolts to re-
building to the foundation. In light-frame tance, and transfer the load to the chords strain shear walls from overturning.
buildings, shear walls typically consist of through the sheathing fasteners. Chords Bolts attaching the struts to the upper and
lumber framing and exterior and interior
panel sheathing attached with dowel- The authors are, respectively, Assistant Professor, Dept. of Wood and Forest Sciences, Fac-
type fasteners (nails, staples, or screws). ulty of Forestry and Geomatics, Laval Univ., Quebec, Canada (formerly Post Doctoral Asso-
Exterior walls often represent a combi- ciate, Forest Prod. Lab., Mississippi State Univ.); and Professor, Dept. of Civil and Environ-
nation of fully-sheathed segments of var- mental Engineering, Washington State Univ., Pullman, WA 99164-2910. The authors
respectfully acknowledge the financial support given to the research project by the
ious lengths interrupted by windows and USDA/CSREES NRI Competitive Grant Program through award number 95-37103-2102.
doors of various sizes. In shear wall anal- Approved as Journal Article No. FP-231 of the Forest & Wildlife Research Center, Missis-
ysis, the vertical framing members at the sippi State Univ. This paper was received for publication in June 2002. Article No. 9503.
✳Forest Products Society Member.
ends of the wall segment are called ©Forest Products Society 2003.
chords and the horizontal framing mem- Forest Prod. J. 53(10):65-73.
66 OCTOBER 2003
the vertical edges. As a means of over-
turning restraint, Simpson Strong-Tie®
HTT22 connectors were attached on the
inside of the chords by thirty-two 16d
(3.8- by 82.6-mm) sinker nails.
Test setup
The specimens were stored in the lab-
oratory ambient conditions for at least 2
weeks after fabrication to allow for
wood relaxation around the nails. Each
specimen was tested in a horizontal po-
sition (Fig. 2). No dead load was applied
in the plane of the wall, which conserva-
tively represented a wall parallel to floor
joists. The wall was supported by two
76- by 127-mm (3- by 5-in.) steel beams
attached to the wall top and bottom
Figure 2. — Test setup. plates with 15.9-mm (5/8-in.) bolts
spaced 0.6 m (24 in.) on centers. These
bolts were secured by nuts with the use
of 64- by 64-mm- (2.5- by 2.5-in.-) wide
and 6-mm- (0.25-in.-) thick steel plate
washers. In 0.6-m (2-ft.) walls, the dis-
tance between the shear bolts was re-
duced as shown in Figure 3.
To eliminate interference of the sup-
port with the sheathing displacements,
the narrow face of the support beams
was oriented toward the plates. To re-
duce the amount of the wall slip along
the support during the test, the oversize
of holes for the shear bolts was mini-
mized. Holes in the supporting beams
were only 0.8 mm (1/32 in.) larger than
the bolt diameter; holes in the top and
bottom plates were drilled without over-
size. At the ends, the wall was anchored
to the supporting beam by 15.9-mm
(5/8-in.) bolts through the hold-down
connectors. Anchor bolts were instru-
mented with strain gages to measure the
tension forces transferred to the chords
through the hold-down anchors. The
bolts were tightened to approximately
Figure 3. — Anchorage and effective length of 0.6-m (2-ft.) wall. 18 kN (4 kips) of initial tension. The
holes for the anchor bolts were oversized
Prior to wall assembly, modulus of common nails every 0.60 m (2 ft.). All by 13 mm (1/2 in.) to minimize the base
elasticity and density of each framing studs were attached to the single bottom shear effects on the tension force mea-
member were measured using a plate and the double top plate, with two surements in the instrumented bolts.
Metriguard® Model 340 transverse vi- 16d common nails at each end. A single The steel beam at the bottom plate
bration E-computer (Metriguard 1994); layer of OSB sheathing, 11 mm (7/16 was secured to the reinforced-concrete
moisture content was measured using a in.) thick, was attached to one wall side reaction wall. The steel beam at the top
Delmhorst® Model J-3 moisture meter. by power-driven 8d (3.3- by 63.5-mm) plate distributed the racking load from a
The wall frame was assembled of 38- by common SENCO® nails at 0.15 m (6 programmable hydraulic actuator. The
89-mm (2- by 4-in.-nominal) spruce- in.) on centers along the edges and 0.30 actuator, with a displacement range of ±
pine-fir (SPF) stud grade members m (12 in.) on centers along intermediate 152 mm (6 in.) and a capacity of 245 kN
spaced 0.41 m (16 in.) on centers, except studs. The long dimension of the sheath- (55 kips), was secured between the
for the walls with the aspect ratio of 4:1 ing was oriented parallel to the studs and support and the distribution beam by
with studs at the wall ends only (Fig. 1). fastened to the framing with a 19-mm means of the hinged connections shown
The chords consisted of two studs fas- (3/4-in.) edge distance along the top and in Figure 2. If these hinges were omit-
tened by two 16d ( 4.1- by 89-mm) bottom plates, and 10 mm (3/8 in.) along ted, the separation of the wall framing
68 OCTOBER 2003
The bilinear EEEP curves depict how
an ideal perfectly elastic-plastic wall
would perform, dissipating an equiva-
lent amount of energy, and allow com-
parison of the nonlinear performance of
different walls on the equivalent energy
basis. The elastic shear modulus, G, was
obtained as follows:
G = ke h [4]
General observations
All walls exhibited a significant
amount of racking. Figure 6 shows a
graph of sheathing displacements rela-
tive to the framing near the corners of
the first panel in the 12FAm1 wall. Sim-
ilar displacements were observed in
08FAm walls. At peak loads, the hori-
zontal displacements reached 5 mm (0.2
Figure 5. — Performance parameters of shear walls. in.) and vertical displacements reached
10 mm (0.4 in.). Bearing and friction
forces between adjacent edges of
Table 1. — Performance parameters of fully anchored shear walls under monotonic sheathing panels might have provided
load. a for a relatively uniform distribution of
Units 12FAm1 12FAm2 08FAm1 08FAm2 04FAm1 04FAm2 02FAm1 02FAm2
the sheathing displacements relative to
vpeak
the framing in these walls (There was
kN/m 10.33 9.33 10.82 10.40 9.76 10.11 10.17 9.51
less than a 50% difference between cor-
kip/ft. 0.708 0.639 0.741 0.713 0.669 0.693 0.697 0.652 responding displacements at the top and
'peak mm 79.9 53.5 81.2 65.6 49.0 65.2 150.8 112.5 the bottom). In walls with one sheathing
in. 3.15 2.11 3.20 2.58 1.93 2.57 5.94 4.43 panel (04FAm and 02FAm), displace-
vyield kN/m 9.15 8.36 9.47 9.28 8.48 9.06 8.56 8.29 ments at the top were less than a half of
kip/ft. 0.627 0.573 0.649 0.636 0.581 0.621 0.587 0.568 those at the bottom, and horizontal dis-
'yield mm 13.7 12.5 14.2 12.4 10.3 13.2 20.8 24.6 placements were less than a half of verti-
in. 0.54 0.49 0.56 0.49 0.41 0.52 0.82 0.97 cal displacements. The displacements
'e mm 6.2 5.6 6.5 5.6 4.8 5.9 9.5 11.1
might be more uniform if the chords
were anchored at the top as well as at the
in. 0.24 0.22 0.25 0.22 0.19 0.23 0.38 0.44
b b
bottom.
'failure mm 116.8 87.2 107.2 107.2 62.4 105.4 152.4 152.4
Major performance characteristics of
in. 4.60 3.43 4.22 4.22 2.46 4.15 6.0 6.0
fully-anchored shear walls under static
G kN/mm 1.63 1.63 1.63 1.83 2.00 1.68 1.04 0.83 monotonic loads are shown in Table 1.
kip/in. 9.32 9.31 9.30 10.43 11.42 9.58 5.94 4.76 Eight walls of different sizes developed
wfailure kNm/m 1.01 0.68 0.95 0.94 0.49 0.90 1.26
a
1.19
a
the average vpeak of 10.1 kN/m (0.69
kipft./ft. 0.226 0.152 0.213 0.211 0.109 0.201 0.283 0.268 kip/ft.) with a remarkably low coeffi-
aSeeFigure 1 for shear wall notation.
cient of variation (5%). These data indi-
bThe test was stopped before failure was observed. cate that narrow walls can develop the
same unit shears as long walls if calcula-
tions are based on a proper effective
limited by the failure point approxi- ness (ke = 0.4vpeak/'e, where 'e = de-
length. Note however, if the loads were
mated unit work to failure (wfailure) (i.e., flection at 0.4vpeak).1 To find the yield
normalized by the overall wall length
the energy dissipated by the wall of unit load (vyield), the following equation was
(width of shear panel), the shear forces
length). Using these data, the equivalent derived by equating the areas under the
in the narrow walls would be signifi-
energy elastic-plastic (EEEP) curve was observed and EEEP curves:
cantly underestimated.
derived as shown in Figure 5. The initial
slope of the EEEP curve, drawn through v yield Typical load-deflection curves of the
0.4 vpeak on the load-deflection curve, tested walls are presented in Figure 7.
2w failure
determined the unit secant elastic stiff- ( )2 k e [3] These graphs do not include walls
failure failure
ke 04FAm1 and 12FAm2, which are dis-
cussed in the next section. Graphs
1The value of 0.4v 02FAm and 08FAm represent the aver-
peak is a value that is used in several
national and international test standards for deter- where the expression in parentheses de- age curves from two matching tests. Es-
mining the initial stiffness of non-linear responses. termined the yield deflection ('yield) sentially, walls with aspect ratios d 2:1
70 OCTOBER 2003
Table 2. — Specific gravity and strength parameters of shear walls under monotonic bottom plate and caused the early
load. strength degradation of the entire shear
12FAm1 12FAm2 08FAm1 08FAm2 04FAm1 04FAm2 02FAm1 02FAm2
wall.
SG averagea 0.49 0.46 0.53 0.53 0.46 0.46 0.47 0.47 Design implications
SG right end studb 0.53 0.37 0.56 0.52 0.42 0.49 0.44 0.50 According to the International Build-
Fpeak (kips)c 8.14 7.35 5.56 5.34 2.34 2.43 1.04 0.98 ing Code (ICC 2000), the allowable
vpeak/vseismic 2.96 2.67 3.10 2.98 2.80 2.90 2.91 2.73 shear for walls of the tested configura-
Fpeak/Fseismic 2.84 2.56 2.90 2.79 2.45 2.53 2.18 2.04 tion (11-mm [7/16-in.] vertical sheath-
Tpeak (kips) 5.48 4.68 4.23 4.95 4.65 5.15 7.23 4.02 ing attached with 8d nails with 150-mm
aSpecific gravity of all framing members based on the ovendry volume. [6-in.] spacing at panel edges, and with
bSpecific gravity of the right end stud based on the ovendry volume. stud spacing 410 mm [16-in.] on cen-
c1 kip = 1000 lbf = 4.45 kN.
ters) with framing of Douglas-fir-larch
or southern pine equals 3.79 kN/m
(0.260 kip/ft.). Allowable shears are ad-
justed for specific gravity of the framing
lumber using the specific gravity adjust-
ment factor = [1 (0.5 SG)] d 1, where
SG is specific gravity for the species of
lumber in the National Design Specifi-
cation for Wood Construction (AF&PA
1997). For SPF species, SG = 0.42.
Therefore, in seismic design, the allow-
able shear for the tested walls equals
vseismic = 3.79 u 0.92 = 3.49 kN/m
(0.239 kip/ft.). In wind design, a 40 per-
cent increase of design capacities is per-
mitted (ICC 2000): vwind = 3.49 u 1.40 =
4.89 kN/m (0.335 kip/ft.). Corre-
sponding design load capacities
(Fseismic and Fwind) can be estimated by
multiplying the allowable shears and the
overall wall length (L).
To compare the design values with
test results, Table 2 shows the ultimate
Figure 8. — Vertical displacements of studs. load (Fpeak) resisted by each shear wall
tested and strength ratios: vpeak/vseismic
and Fpeak/Fseismic. The corresponding
strength ratios for wind design (not
shown in the table) are 40 percent lower.
The comparison shows that design val-
ues for shear walls with the aspect ratios
d 1:1 are sufficiently conservative.
Strength ratios exceeded 2.8 for seismic
design (2.0 for wind design) with the ex-
ception of wall 12FAm2, which had a
very low-density right end stud. Walls
with the aspect ratio 2:1 developed simi-
lar unit shears as the longer walls; how-
ever, their strength ratios based on Fpeak
were less conservative, because the de-
sign capacity included the overall
length. To equalize the safety levels of
narrow walls and long walls the load ca-
pacities should be calculated using the
effective length (L0). Alternatively, ap-
propriate adjustment factors should be
recommended for narrow (2:1) walls,
depending on the anchorage conditions.
Although shear walls with the aspect
ratio 4:1 are not permitted in engineered
Figure 9. — Typical view of the wall bottom after failure. design (ICC 2000), Table 2 shows that
72 OCTOBER 2003
Diekmann, E.F. 1997. Diaphragms and
shearwalls. In: Wood Engineering and Con-
struction. 3rd ed. K.F. Faherty and T.G. Wil-
liamson, eds. McGraw-Hill, New York. pp.
8.47-8.79
Federal Emergency Management Agency
(FEMA). 1997. NEHRP Guidelines for the
Seismic Rehabilitation of Buildings (FEMA
Publication 273). FEMA, Washington, DC.
International Code Council (ICC). 2000. Inter-
national Building Code 2000. ICC, Falls
Church, VA.
Metriguard. 1994. Precision testing equipment
for wood. Catalog 21-1. Metriguard, Inc.,
Pullman, WA. pp.13-16.
Patton-Mallory, M., R.M. Gutkowski, and
L.A. Soltis. 1984. Racking performance of
light-frame walls sheathed on two sides. Res.
Paper FPL 448. USDA Forest Serv., Forest
Prod. Lab., Madison, WI.
Salenikovich, A.J. 2000. The racking perfor-
mance of light-frame shear walls. PhD diss.
Figure 13. — Tension forces in anchor bolts. Virginia Polytechnic Inst. and State Univ.,
Blacksburg, VA.
should use higher grade lumber or dense tion (NDS) for wood construction. AF&PA, __________ and J.D. Dolan. 2003. The packing
Washington, DC. performance of shear walls with various as-
wood species for framing members in pect ratios. Part 2. Cyclic tests of fully-an-
American Society for Testing and Materials
narrow shear wall segments when they (ASTM). 1995a. Standard test methods of chored walls. Forest Prod. J. (in press).
are critical components in the lateral conducting strength tests of panels for build- Simpson Strong-Tie Company. 1995. Wood
force resisting system (such as ground- ing construction. ASTM E 72-95. ASTM, construction connectors. Simpson Strong-Tie
floor shear walls with large openings) to West Conshohocken, PA. Company, Pleasanton, CA. 76 pp.
ensure acceptable performance. __________. 1995b. Standard practice for Tissel, J.R. 1990. Structural panel shear walls.
static load test for shear resistance of framed Report 154. American Plywood Assoc., Ta-
Comparison of monotonic test results walls for buildings. ASTM E 564-95. ASTM, coma, WA. 19 pp.
with published design values proved the West Conshohocken, PA.
Andreason, K.R. and J.D. Rose. 1994. __________ and J.D. Rose. 1994. Wood struc-
traditional design practice for seg- tural panel sheathing for narrow-width wall
mented shear walls to be sufficiently Northridge, California earthquake. Structural
performance of buildings in San Fernando bracing. Research Report 156. American Ply-
conservative. However, using the effec- Valley, California (January 17, 1994). APA wood Assoc., Tacoma, WA. pp. 20
tive wall length in shear wall analysis Rept. T94-5. American Plywood Assoc., Ta- White, M.W. and J.D. Dolan. 1994. Effect of
would enhance the accuracy and would coma, WA. 34 pp. openings and aspect ratio on the dynamic re-
equalize the safety levels of walls with Breyer, D.E., K.J. Fridley, and K.E. Cobeen. sponse of timber shear walls. Presented at the
1999. Design of Wood Structures ASD. 4th Forest Products Society 48th annual meeting.
various aspect ratios. Forest Prod. Soc., Madison, WI.
ed. McGraw-Hill, New York.
Commins, A.D. and R.C. Gregg. 1994. Cyclic Wolfe, R.W. 1983. Contribution of gypsum
Literature cited performance of tall-narrow shearwall assem- wallboard to racking resistance of light-frame
American Forest and Paper Association blies. Simpson Strong-Tie Co., Pleasanton, walls. Res. Paper FPL 439. USDA Forest Ser-
(AF&PA). 1997. National design specifica- CA. 12 pp. vice, Forest Prod. Lab., Madison, WI.