Product characteristics
Number of inputs and outputs Number of analogue outputs: 2
Measuring range 0.1...25 l/min 0.03...6.6 gpm
Process connection threaded connection G 1/2 DN15 flat seal
Application
Special feature Gold-plated contacts
Application for industrial applications
Installation connection to pipe by means of an adapter
Media conductive liquids; water; hydrous media
Note on media conductivity: ≥ 20 µS/cm
viscosity: < 70 mm²/s (40 °C)
Medium temperature [°C] -10...70
Pressure rating [bar] 16
Pressure rating [MPa] 1.6
MAWP (for applications [bar]
17.7
according to CRN)
Electrical data
Operating voltage [V] 20...30 DC; (to SELV/PELV)
Current consumption [mA] 120; (24 V)
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 5
Inputs / outputs
Number of inputs and outputs Number of analogue outputs: 2
Outputs
Total number of outputs 2
Output signal analogue signal
Number of analogue outputs 2
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — SM6004-02 — 13.04.2023 —
SM6004
Magnetic-inductive flow meter
SMR12GGX50KG/US-100
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — SM6004-02 — 13.04.2023 —
SM6004
Magnetic-inductive flow meter
SMR12GGX50KG/US-100
Mechanical data
Weight [g] 481.5
Housing cylindrical
Dimensions [mm] Ø 54 / L = 110
Materials stainless steel (316L/1.4404); PBT-GF20; PC; FKM; TPE
Materials (wetted parts) stainless steel (316L/1.4404); PEEK; FKM
Process connection threaded connection G 1/2 DN15 flat seal
Displays / operating elements
Display Display unit 6 x LED, green (l/min, m³/h, gpm, gph, °C, °F)
measured values alphanumeric display, 4-digit
programming alphanumeric display, 4-digit
Display unit l/min; m³/h; gpm; gph; °C; °F
Remarks
Remarks MW = measured value
MEW = Final value of the measuring range
Pack quantity 1 pcs.
Electrical connection
Connector: 1 x M12; coding: A; Contacts: gold-plated
Connection
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — SM6004-02 — 13.04.2023 —
SM6004
Magnetic-inductive flow meter
SMR12GGX50KG/US-100
dP Pressure loss
Q volumetric flow quantity
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — SM6004-02 — 13.04.2023 —