SECTION 27 51 16 Public Address and Mass Notification Systems Part 1 - General 1.1 Section Summary
SECTION 27 51 16 Public Address and Mass Notification Systems Part 1 - General 1.1 Section Summary
SECTION 27 51 16 Public Address and Mass Notification Systems Part 1 - General 1.1 Section Summary
SECTION 27 51 16
PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS
PART 1 - GENERAL
1.1 SECTION SUMMARY
A. Work covered by this document includes design, engineering, labor,
material and products, equipment warranty and system guarantee, training
and services for, and incidental to, the complete installation of new
and fully operating National Fire Protection Association (NFPA) – Life
Safety Code 101.3-2 (a) Labeled and (b) Listed Emergency Service Public
Address System (PAS) and associated equipment (here-in-after referred to
as the System) in approved locations indicated on the contract
drawings. These items shall be tested and certified capable of
receiving, distributing, interconnecting and supporting PAS
communications signals generated local and remotely as detailed herein.
B. Work shall be complete, Occupational Safety and Health Administration
(OSHA), National Recognized Testing Labatory (NRTL – i.e. Underwriters
Laboratory [UL]) Listed and Labeled; and VA Central Office (VACO),
Telecommunications Voice Engineering (TVE 005OP3B) tested, certified and
ready for operation.
C. The System shall be delivered free of engineering, manufacturing,
installation, and functional defects. It shall be designed, engineered
and installed for ease of operation, maintenance, and testing.
D. The term “provide”, as used herein, shall be defined as: designed,
engineered, furnished, installed, certified, and tested, by the
Contractor.
E. Specification Order of Precedence: In the event of a conflict between
the text of this document and the Project’s Contract Drawings outlined
and/or cited herein; THE TEXT OF THIS DOCUMENT TAKES PRECEDENCE.
HOWEVER, NOTHING IN THIS DOCUMENT WILL SUPERSEDE APPLICABLE EMERGENCY
LAWS AND REGULATIONS, SPECIFICALLY NATIONAL AND/OR LOCAL LIFE AND PUBLIC
SAFETY CODES. The Local Fire Marshall and/or VA Public Safety Officer
are the only authorities that may modify this document’s EMERGENCY CODE
COMPLIANCE REQUIREMENTS, on a case by case basis, in writing and
confirmed by VA’s PM, RE and TVE-005OP3B. The VA PM is the only
approving authority for other amendments to this document that may be
granted, on a case by case basis, in writhing with technical
275116 - 1
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 2
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 3
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 4
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 5
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 6
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 7
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 8
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
OEM to pass thru the OEM’s warranty of the installed equipment to VA.
In addition, the OEM and Contractor shall accept complete responsibility
for the design, installation, certification, operation, and physical
support for the System. This documentation, along with the System
Contractor and OEM certifications must be provided in writing as part of
the Contractor’s Technical submittal.
C. The Contractor’s Communications Technicians assigned to the System shall
be fully trained, qualified, and certified by the OEM on the
engineering, installation, operation, and testing of the System. The
Contractor shall provide formal written evidence of current OEM
certification(s) for the installer(s) as a part of the submittal or to
the RE before being allowed to commence work on the System.
D. The Contractor shall display all applicable national, state and local
licenses.
E. The Contractor shall submit copy (s) of Certificate of successful
completion of OEM’s installation/training school for installing
technicians of the System’s PA equipment being proposed.
1.6 CODES AND PERMITS
A. Provide all necessary permits and schedule all inspections as identified
in the contract’s milestone chart, so that the system is proof of
performance tested and ready for operation on a date directed by the
Owner.
B. The contractor is responsible to adhere to all codes described herein
and associated contractual, state and local codes.
C. The Contractor shall display all applicable national, state and local
licenses and permits.
1.7 SCHEDULING
A. After the award of contract, the Contractor shall prepare a detailed
schedule (aka milestone chart) using “Microsoft Project” software or
equivalent. The Contractor Project Schedule (CPS) shall indicate
detailed activities for the projected life of the project. The CPS
shall consist of detailed activities and their restraining
relationships. It will also detail manpower usage throughout the
project.
B. It is the responsibility of the Contractor to coordinate all work with
the other trades for scheduling, rough-in, and finishing all work
specified. The owner will not be liable for any additional costs due to
275116 - 9
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 10
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 11
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
Other
Outside
Locations
Other
Horn
Locations
Other
275116 - 12
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
Power Supply(s)
Location
Other
UPS(s)
Location
Other
Radio Paging Access (when pre-
approved by TVE-
005OP3B)
Wireless Access (when pre-approved
by TVE-005OP3B)
Maintenance/Programming Console
Location(s)
Other
3) The required PA Cable Plant/Connections:
The Contractor shall clearly and fully indicate this category
for each item identified herein as a part of the technical
submittal. For this purpose, the following definitions and
sample connections are provided to detail the system’s
capability:
275116 - 13
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
Maintenance/Program Console
Location(s)
Other
LAN (Local Facility)
Access/Equipment/Location (when pre-
approved by TVE-005OP3B)
Wireless Access/Equipment/Location
(when pre-approved by TVE-005OP3B)
Other
1.9 PROJECT RECORD DOCUMENTS (AS BUILTS)
A. Throughout progress of the Work, maintain an accurate record of changes
in Contract Documents. Upon completion of Work, transfer recorded
changes to a set of Project Record Documents.
B. The floorplans shall be marked in pen to include the following:
1. All device locations with UL labels affixed.
2. Conduit locations.
3. Head-end equipment and specific location.
4. Each interface and equipment specific location.
5. Facility Entrance (aka DEMARC) Room(s) interface equipment and
location(s).
6. Telephone Equipment Room (TER) interface equipment and specific
location.
7. Main Computer Room (MCR) interface equipment and specific location.
8. Police Control Room (PCR) interface equipment and specific location.
9. Engineering Control Room (ECR) interface equipment and specific
location
10. Telecommunication Outlet (s –TCO) equipment and specific location
11. TIP Wiring diagram(s).
12. Warranty certificate.
13. System test results.
14. System Completion Document(s) or MOU.
1.10 WARRANTIES / GUARANTY
A. The Contractor shall warrant the installation to be free from defect in
material and workmanship for a period of two (2) years from the date of
acceptance of the project by the owner. The Contractor shall agree to
remedy covered defects within four (4) hours of notification of major
failures or within twenty-four (24) hours of notification for individual
station related problems.
275116 - 14
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 15
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
B. The specific location for each PA: Central Control Cabinet is indicate
like locations on the contract drawings.
C. Coordinate features and select interface components to form an
integrated PA system. Match components and interconnections between the
systems for optimum performance of specified functions.
D. Expansion Capability: The PA equipment interfaces and cables shall be
able to increase number of enunciation points in the future by a minimum
of 50 percent (%) above those indicated without adding any internal or
external components or main trunk cable conductors.
E. Equipment: Active electronic type shall use solid-state components,
fully rated for continuous duty unless otherwise indicated. Select
equipment for normal operation on input power usually supplied between
110 to 130 VAC, 60 Hz.
F. Meet all FCC requirements regarding low radiation and/or interference of
RF signal(s). The system shall be designed to prevent direct pickup of
signals from within and outside the building structure.
G. Weather/Water Proof Equipment: Listed and labeled by an OSHA certified
National Recognized Testing Labatory (NRTL – i.e. UL) for duty outdoors
or in damp locations.
H. Deliver a fully functioning and operable PA in the specific locations
shown on the drawings.
2.1 SYSTEM DESCRIPTION
A. Furnish and install a complete and fully functional and operable HF
Radio System. Provide additional require conduit(s) according to
Specification 27 11 00.
B. The Contractor is responsible for interfacing the MATV, RED, Patient Bed
Service Walls, SSC Room and FA systems with the System and shall be the
interface points for connection of the radio interface cabling from the
interface unit(s). The interface unit(s) shall be provided by the
Contractor.
C. The Contractor shall continually employ interfacing methods that are
approved by the OEM and VA. At a minimum, an acceptable interfacing
method requires not only a physical and mechanical connection, but also
a matching of signal, voltage, and processing levels with regard to
signal quality and impedance. The total PA system shall be configured
and installed so that the combination of equipment actually employed
does not produce any undesirable visual or aural effects such as signal
275116 - 16
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 17
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 18
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
2. The System shall allow voice pages to be made within a single zone,
across programmed multiple zones or a global page (all zones) by
using preset codes entered into the keypad of any telephone
instrument attached to the PBX.
K. The System shall interface with the Facility’s existing PAS so that a
global page (aka “all call” page) is communicated to the existing PAS
and the new System of this project. Arrangements for interconnection of
the System and the telephone system(s) shall be coordinated with the
owner and the PBX provider.
L. The system shall be designed to provide continuous electrical
supervision of the complete and entire system (i.e. light bulbs, wires,
contact switch connections, master control stations, wall stations,
circuit boards, data, audio, and communication busses, main and UPS
power, etc.). All alarm initiating and signaling circuits shall be
supervised for open circuits, short circuits, and system grounds. Main
and UPS power circuits shall be supervised for a change in state (i.e.
primary to backup, low battery, UPS on line, etc.). When an open, short
or ground occurs in any system circuit, an audible and visual fault
alarm signal shall be initiated at the main supervisory panel, nurse
control station and all remote amplifier locations.
M. When the System is approved to connect to a separate communications
system (i.e. LAN, WAN, Telephone, Nurse Call, radio raging, wireless
systems, etc) the connection point shall be at one location and shall
meet the following minimum requirements for each hard wired connection
(note each wireless system connection MUST BE APPROVED PRIOR TO CONTRACT
BID BY VA HEADQUARTERS 005OP3B AND 005OP2B):
1. UL 60950-1/2.
2. FIPS 142.
3. FCC Part 15 Listed Radio Equipment is not allowed.
N. All passive distribution equipment shall meet or exceed -80 dB radiation
shielding (aka RFI) shielding specifications and be provided with screw
type audio connectors.
O. All equipment face plates utilized in the system shall be stainless
steel, anodized aluminum or UL approved cycolac plastic for the areas
where provided.
275116 - 19
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
P. All trunk, branch, and interconnecting cables and unused equipment ports
or taps shall be terminated with proper terminating resistors designed
for RF, audio and digital cable systems without adapters.
Q. Noise filters and surge protectors shall be provided for each equipment
interface cabinet, headend cabinet, control console and local and remote
amplifier locations to insure protection from input primary AC power
surges and to insure noise glitches are not induced into low voltage
data circuits.
R. Plug-in connectors shall be provided to connect all equipment, except
coaxial cables and RF transmission line interface points. Coaxial cable
distribution points and RF transmission lines shall use coaxial cable
connections recommended by the cable OEM and approved by the system OEM.
Base band cable systems shall utilize barrier terminal screw type
connectors, at a minimum. As an alternate, crimp type connectors
installed with a ratchet type installation tool are acceptable provided
the cable dress, pairs, shielding, grounding, connections and labeling
are the same as the barrier terminal strip connectors. Tape of any type,
wire nuts or solder type connections are unacceptable and will not be
approved.
S. Audio Level Processing: The control equipment shall consist of audio
mixer(s), volume limiter(s) and/or compressor(s), and power amplifier(s)
to process, adjust, equalize, isolate, filter, and amplify each audio
channel for each sub-zone in the system and distribute them into the
System’s RF interfacing distribution trunks and amplification circuits.
It is acceptable to use identified Telephone System cable pairs
designated for Two-Way Radio interface and control use or identified as
spare telephone cable pairs by the Facility’s Telephone System
Contractor. The use of telephone cable to distribute RF signals,
carrying system or sub-system AC or DC voltage is not acceptable and
will not be approved. Additionally, each control location shall be
provided with the equipment required to insure the system can produce
its designed audio channel capacity at each speaker identified on the
contract drawings. The Contractor shall provide: a spare set of
telephone paging modules as recommended by the OEM (as a minimum provide
one spare module for each installed module); one spare audio power
amplifier, one spare audio mixer, one spare audio volume limiter and/or
275116 - 20
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
compressor, and one spare audio automatic gain adjusting device, and
minimum RF equipment recommended by the OEM.
T. Contractor is responsible for pricing all accessories and miscellaneous
equipment required to form a complete and operating system. Unless
otherwise noted in this Part, equipment quantities shall be as indicated
on the drawings.
2.2 SYSTEM PRFORMANCE:
A. At a minimum, each distribution, interconnection, interface, terminating
point and TCO shall be capable of supporting the Facility’s PA system
voice and data service as follows:
1. Shall be compliant with and not degrade the operating parameters of
the Public Switched Telephone Network (PSTN) and the Federal
Telecommunications System (FTS) at each PSTN and FTS interface,
interconnection and terminating locations in the TERs.
2. Audio Input: The signal level of each audio input channel at each
input point shall be a MINIMUM of zero decibels measured (dBm), +0.10
dBm across 150 Ohms, balanced.
3. Audio Output: The audio signal level at each speaker shall be a
MINIMUM of +0.25 Watt (W) and a maximum of +20 W, 600 Ohms balanced
impedance, on a 70.7 V audio distribution line Contractor to
determine and set each speaker’s proper audio signal level (top)
based on speaker location and the ambient noise level in speaker
coverage area.
4. The system shall meet the following MINIMUM parameters at each
speaker:
a. Cross Modulation: -46 dB
b. Hum Modulation: -55 dB
c. Isolation (outlet-outlet): 24 dB
d. Impedance:
1) Distribution: 600 Ohm balanced @ 70.7 V audio line level.
2) Speaker: Selectable, as required.
e. Audio Gain: 10 dB minimum @ mid-range measured with a sound
pressure level meter (SPL)
f. Signal to noise (S/N) ratio: 35 dB, minimum
B. Audio Level Processing: The head-end equipment shall consist of audio
mixer(s), volume limiter(s) and/or compressor(s), and power amplifier(s)
to process, adjust, equalize, isolate, filter, and amplify each audio
275116 - 21
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
channel for each zone or sub-zone in the system and distribute them into
the system’s distribution trunks. It is acceptable to use identified
telephone system cable pairs designated for PA use or identified as
spare telephone cable pairs by the Facility’s Telephone System
Contractor.
1. THE USE OF TELEPHONE CABLE TO DISTRIBUTE PA SIGNALS CARRYING AC OR
DC VOLTAGE IS NOT ACCEPTABLE AND WILL NOT BE APPROVED.
2. Additionally, each remote location shall be provided with the
equipment required to ensure the system supervision and designed
audio channel capacity at each speaker identified on the contract
drawings.
2.3 MANUFACTURERS
A. The products specified shall be new, FCC and UL Listed, labeled and
produced by OEM of record. An OEM of record shall be defined as a
company whose main occupation is the manufacture for sale of the items
of equipment supplied and which:
1. Maintains a stock of replacement parts for the item submitted,
2. Maintains engineering drawings, specifications, and operating manuals
for the items submitted, and
3. Has published and distributed descriptive literature and equipment
specifications on the items of equipment submitted at least 30 days
prior to the Invitation for Bid (IFB).
B. Specifications contained herein as set forth in this document detail the
salient operating and performance characteristics of equipment in order
for VA to distinguish acceptable items of equipment from unacceptable
items of equipment. When an item of equipment is offered or furnished
for which there is a specification contained herein, the item of
equipment offered or furnished shall meet or exceed the specification
for that item of equipment.
C. Equipment Standards and Testing:
1. The System has been defined herein as connected to systems identified
as an Emergency performing Public Safety Support Functions.
Therefore, at a minimum, the system shall conform to all
aforementioned National and/or Local Public and Life Safety Codes
(which ever are the more stringent), NFPA, NEC, this specification,
JCAHCO Life Safety Accreditation requirements, and the OEM
recommendations, instructions, and guidelines.
275116 - 22
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 23
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 24
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 25
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 26
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 27
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 28
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 29
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 30
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 31
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
1. System Speakers:
a. Ceiling Cone-Type:
1) Minimum Axial Sensitivity: 91 dB at one meter, with 1-W input.
2) Frequency Response: Within plus or minus 3 dB from 70 to 15,000
Hz.
3) Minimum Dispersion Angle: 100 degrees.
4) Line Transformer: Maximum insertion loss of 0.5 dB, power
rating equal to speaker's, and at least four level taps.
5) Enclosures: Steel housings or back boxes, acoustically
dampened, with front face of at least 0.0478-inch steel and
whole assembly rust proofed and factory primed; complete with
mounting assembly and suitable for surface ceiling, flush
ceiling, pendant or wall mounting; with relief of back
pressure.
6) Baffle: For flush speakers, minimum thickness of 0.032-inch
aluminum with textured white finish. Completely fill the baffle
with fiberglass.
7) Vandal-Proof, High-Strength Baffle: For flush-mounted speakers,
self-aging cast aluminum with tensile strength of 44,000 psi,
0.025-inch minimum thickness; countersunk heat-treated alloy
mounting screws; and textured white epoxy finish.
8) Size: 8 inches with 1-inch voice coil and minimum 5-oz. ceramic
magnet.
9) Have a minimum of two (2) safety wires installed to a solid
surface or use a flexible conduit from ceiling / wall back box
to the speaker back box.
10) The speakers and mounting shall be self contained and wall
mounted with flush back box at a minimum of 10 meter intervals
and shall match (or contrast with, at the direction of the RE)
the color of the adjacent surfaces.
11) Provide one spare speaker, mount, and back box for each 50
speakers or portion thereof.
b. Wall Mounted Horne-Type:
1) Each horn speaker shall be provided with a means of adjusting
the output level over the rated horn speaker range to an
appropriate audio level in the area installed.
275116 - 32
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 33
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 34
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 35
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 36
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 37
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
PART 3 - EXECUTION
3.1 PROJECT MANAGEMENT
A. Assign a single project manager to this project who will serve as the
point of contact for the Owner, the General Contractor, and the
Engineer.
B. The Contractor shall be proactive in scheduling work at the hospital,
specifically the Contractor will initiate and maintain discussion with
the general contractor regarding the schedule for ceiling cover up and
install cables to meet that schedule.
C. Contact the Office of Telecommunications, Special Communications Team
(005OP3B) at (301) 734-0350 to have a VA Certified Telecommunications
CONTRACTING OFFICER’S REPRESENTATIVE (COR) assigned to the project for
telecommunications review, equipment and system approval and co-
ordination with VA’s Spectrum Management and OCIS Teams.
3.2 COORDINATION WITH OTHER TRADES
A. Coordinate with the cabling contractor the location of the PA system
faceplate and the faceplate opening for the PA system back boxes.
B. Coordinate with the cabling contractor the location of TIP equipment in
the TER, TCR, PA, PCR, SCC, ECR, STRs, NSs, HER and TCOs in order to
connect to the TIP cable network that was installed as a part of Section
Specification 27 11 00. Contact the RE immediately, in writing, if
additional location(s) are discovered to be activated that was not
previously provided.
C. Before beginning work, verify the location, quantity, size and access
for the following:
1. Isolated ground AC power circuits provided for systems.
2. Junction boxes, wall boxes, wire troughs, conduit stubs and other
related infrastructure for the systems.
3. System components installed by others.
4. Overhead supports and rigging hardware installed by others.
D. Immediately notify the Owner, GC and Consultant(s) in writing of any
discrepancies
3.3 NEEDS ASSESSMENT
Provide a one-on-one meeting with the particular manager of each unit
affected by the installation of the new PA system. Review the floor
plan drawing, educate the nursing manager with the functions of the
equipment that is being provided and gather details specific to the
275116 - 38
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 39
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 40
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
3. Provide vent panels and cooling fans as required for the operation of
equipment within the OEM' specified temperature limits. Provide
adequate ventilation space between equipment for cooling. Follow
manufacturer’s recommendations regarding ventilation space between
amplifiers.
4. Provide insulated connections of the electrical raceway to equipment
racks.
5. Provide continuous raceway/conduit with no more than 40% fill between
wire troughs and equipment racks for all non-plenum-rated cable.
Ensure each system is mechanically separated from each other in the
wireway.
6. Ensure a minimum of 36 inches around each cabinet and/or rack to
comply with OSHA Safety Standards. Cabinets and/or Racks installed
side by side – the 36” rule applies to around the entire assembly
C. Distribution Frames.
1. A new stand-alone (i.e., self-supporting, free standing) PA
rack/frame may be provided in each TR to interconnect the PA, TER,
TCR, PCR, SCC, STRs & ECRs. Rack/frames shall be wired in accordance
with industry standards and shall employ "latest state-of-the-art"
modular cross-connect devices. The PA riser cable shall be sized to
satisfy all voice/digital requirements plus not less than 50% spare
(growth) capacity in each TR which includes a fiber optic backbone.
2. The frames/racks shall be connected to the TER/MCR system ground.
D. Wiring Practice - in addition to the MANDATORY infrastructure
requirements outlined in VA Construction Specifications 27 10 00 – TIP
Structured Communications Cabling, 27 11 00 – TIP Communications Rooms
Fittings and 27 15 00 – TIP Horizontal and Vertical Communicators
Cabling, the following additional practices shall be adhered too:
1. Comply with requirements for raceways and boxes specified in Division
26 Section "Raceway and Boxes for Electrical Systems."
2. Execute all wiring in strict adherence to the National Electrical
Code, applicable local building codes and standard industry
practices.
3. Wiring shall be classified according to the following low voltage
signal types:
a. Balanced microphone level audio (below -20dBm) or Balanced line
level audio (-20dBm to +30dBm)
275116 - 41
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 42
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 43
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 44
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 45
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 46
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 47
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 48
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 49
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
D. Install fireproofing where low voltage cables are installed in the same
manholes with high voltage cables; also cover the low voltage cables
with arc proof and fireproof tape.
E. Use approved fireproofing tape of the same type as used for the high
voltage cables, and apply the tape in a single layer, one-half lapped
or as recommended by the manufacturer. Install the tape with the coated
side towards the cable and extend it not less than 25 mm (one inch) into
each duct.
F. Secure the tape in place by a random wrap of glass cloth tape.
3.8 GROUNDING
A. Ground PA cable shields and equipment to eliminate shock hazard and to
minimize ground loops, commonmode returns, noise pickup, cross talk, and
other impairments as specified in CFM Division 27, Section 27 05 26 –
Grounding and Bonding for Communications Systems.
B. Facility Signal Ground Terminal: Locate at main room or area signal
ground within the room (i.e. head end and telecommunications rooms) or
area(s) and indicate each signal ground location on the drawings.
C. Extend the signal ground to inside each equipment cabinet and/or rack.
Ensure each cabinet and/or rack installed item of equipment is connected
to the extended signal ground. Isolate the signal ground from power and
major equipment grounding systems.
D. When required, install grounding electrodes as specified in CFM Division
26, Section 26 05 26 –Grounding and Bonding for Electrical Systems.
E. Do not use “3rd or 4th” wire internal electrical system conductors for
communications signal ground.
F. Do not connect the signal ground to the building’s external lightning
protection system.
G. Do Not “mix grounds” of different systems.
H. Insure grounds of different systems are installed as to not violate OSHA
Safety and NEC installation requirements for protection of personnel.
PART 4 – TESTING / GUARANTY / TRAINING
4.0 SYSTEM LISTING
The PA System is NFPA listed as an “Emergency / Public Safety”
Communications system. Where Code Blue signals are transmitted, that
listing is elevated to “Life Support/Safety.” Therefore, the following
testing and guaranty provisions are the minimum to be performed and
provided by the contractor and OEM.
275116 - 50
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 51
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
3) Zone Equipment/Systems.
4) Sub-Zone Equipment/Systems.
5) Remote Control Panels.
a.)TCR.
b.)PCR/SCC.
c.)ECR.
6) All Networked locations.
7) System interface locations (i.e. TELCO, two way radio, etc.).
8) System trouble reporting.
9) System Electrical Supervision.
10)UPS operation.
11)STRs.
12)NSs
13)TCOs.
3. The Contractor shall provide four (4) copies of the recorded system
pretest measurements and the written certification that the System is
ready for the formal acceptance test shall be submitted to the RE.
C. Acceptance Test:
1. After the PA System has been pretested and the Contractor has
submitted the pretest results and certification to the RE, then the
Contractor shall schedule an acceptance test date and give the RE 30
day’s written notice prior to the date the acceptance test is
expected to begin. The System shall be tested in the presence of TVE
005OP3B and an OEM certified representatives. The System shall be
tested utilizing the approved test equipment to certify proof of
performance and Emergency / Public Safety compliance. The tests shall
verify that the total System meets all the requirements of this
specification. The notification of the acceptance test shall include
the expected length (in time) of the test.
2. The acceptance test shall be performed on a "go-no-go" basis. Only
those operator adjustments required to show proof of performance
shall be allowed. The test shall demonstrate and verify that the
installed System does comply with all requirements of this
specification under operating conditions. The System shall be rated
as either acceptable or unacceptable at the conclusion of the test.
Failure of any part of the System that precludes completion of system
testing, and which cannot be repaired in four (4) hours, shall be
275116 - 52
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 53
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 54
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 55
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 56
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
275116 - 57
Coatesville VAMC March 29, 2013
Renovate Building 69 Issued for Bid
Coatesville, PA 19320 Project No. 542-CSI-203
4.3 TRAINING
A. Provide thorough training of all biomed engineering and electronic
technical staff assigned to those nursing units receiving new networked
nurse/patient communications equipment. This training shall be
developed and implemented to address two different types of staff. Floor
nurses/staff shall receive training from their perspective, and
likewise, unit secretaries (or any person whose specific
responsibilities include answering patient calls and dispatching staff)
shall receive operational training from their perspective. A separate
training room will be set up that allows this type of individualized
training utilizing in-service training unit, prior to cut over of the
new system.
B. Provide the following minimum training times and durations:
1. 48 hours prior to opening for BME / Electronic Staff (in 8-hour
increments) – split evenly over 3 weeks and day and night shifts.
Coordinate schedule with Owner.
2. 32 hours during the opening week for Telephone Staff – both day and
night shifts.
3. 24 hours for supervisors and system administrators.
- - - E N D - - -
275116 - 58