Characteristics
Product data sheet
LC1D25M7
V 25 A - 220 V AC coil

1
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Range TeSys
Product name TeSys D
Product or component Contactor
type
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-1
AC-3
AC-4
Poles description 3P
Power pole contact 3 NO
composition
[Ue] rated operational Power circuit <= 690 V AC 25...400 Hz
voltage Power circuit: <= 300 V DC
[Ie] rated operational 25 A 140 °F (60 °C)) <= 440 V AC AC-3 power
current circuit
40 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
Motor power kW 5.5 KW 220...230 V AC 50/60 Hz AC-3)
11 KW 380...400 V AC 50/60 Hz AC-3)
11 KW 415...440 V AC 50/60 Hz AC-3)
15 KW 500 V AC 50/60 Hz AC-3)
15 KW 660...690 V AC 50/60 Hz AC-3)
5.5 kW 400 V AC 50/60 Hz AC-4)
Motor power HP (UL / 3 Hp 230/240 V AC 50/60 Hz 1 phase
CSA) 2 Hp 115 V AC 50/60 Hz 1 phase
7.5 Hp 230/240 V AC 50/60 Hz 3 phase
15 Hp 460/480 V AC 50/60 Hz 3 phase
20 Hp 575/600 V AC 50/60 Hz 3 phase
7.5 hp 200/208 V AC 50/60 Hz 3 phase
Control circuit type AC at 50/60 Hz
[Uc] control circuit 220 V AC 50/60 Hz
voltage
Auxiliary contact 1 NO + 1 NC
composition
[Uimp] rated impulse 6 kV IEC 60947
withstand voltage
Overvoltage category III
[Ith] conventional free 10 A 140 °F (60 °C) signalling circuit
air thermal current 40 A 140 °F (60 °C) power circuit
Irms rated making 140 A AC for signalling circuit conforming to IEC
capacity 60947-5-1
250 A DC for signalling circuit conforming to IEC
60947-5-1
450 A 440 V power circuit IEC 60947
Rated breaking capacity 450 A 440 V power circuit IEC 60947
[Icw] rated short-time 240 A 104 °F (40 °C) - 10 s power circuit
withstand current 380 A 104 °F (40 °C) - 1 s power circuit
50 A 104 °F (40 °C) - 10 min power circuit
120 A 104 °F (40 °C) - 1 min power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC
60947-5-1
63 A gG <= 690 V type 1 power circuit
40 A gG <= 690 V type 2 power circuit
Average impedance 2 mOhm - Ith 40 A 50 Hz power circuit
[Ui] rated insulation Power circuit 690 V IEC 60947-4-1
voltage Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified

2
Electrical durability 1.65 Mcycles 25 A AC-3 <= 440 V
1.4 Mcycles 40 A AC-1 <= 440 V
Power dissipation per 3.2 W AC-1
pole 1.25 W AC-3
Front cover With
Mounting support Plate
Rail
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Product certifications BV
GL
LROS (Lloyds register of shipping)
GOST
UL
DNV
CCC
CSA
RINA
Connections - terminals Control circuit screw clamp terminals 1 0.00…
0.01 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 2 0.00…
0.01 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 1 0.00…
0.01 in² (1…4 mm²)flexible with cable end
Control circuit screw clamp terminals 2 0.00…
0.00 in² (1…2.5 mm²)flexible with cable end
Control circuit screw clamp terminals 1 0.00…
0.01 in² (1…4 mm²)solid without cable end
Control circuit screw clamp terminals 2 0.00…
0.01 in² (1…4 mm²)solid without cable end
Power circuit screw clamp terminals 1 0.00…0.02 in²
(2.5…10 mm²)flexible without cable end
Power circuit screw clamp terminals 2 0.00…0.02 in²
(2.5…10 mm²)flexible without cable end
Power circuit screw clamp terminals 1 0.00…0.02 in²
(1…10 mm²)flexible with cable end
Power circuit screw clamp terminals 2 0.00…0.01 in²
(1.5…6 mm²)flexible with cable end
Power circuit screw clamp terminals 1 0.00…0.02 in²
(1.5…10 mm²)solid without cable end
Power circuit screw clamp terminals 2 0.00…0.02 in²
(2.5…10 mm²)solid without cable end
Tightening torque Control circuit 15.05 lbf.in (1.7 N.m) screw clamp
terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp
terminals Philips No 2
Power circuit 22.13 lbf.in (2.5 N.m) screw clamp
terminals flat Ø 6 mm
Power circuit 22.13 lbf.in (2.5 N.m) screw clamp
terminals Philips No 2
Operating time 12...22 ms closing
4...19 ms opening
Safety reliability level B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical
load conforming to EN/ISO 13849-1
Mechanical durability 15 Mcycles
Maximum operating rate 3600 cyc/h 140 °F (60 °C)

3
Complementary
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 2…3 W at 50/60 Hz
Auxiliary contacts type Type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
Type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non-overlap time 1.5 Ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Insulation resistance > 10 MOhm for signalling circuit
Contact compatibility M2
Compatibility code LC1D
Motor power range 4…6 KW 200…240 V 3 phase
7…11 KW 380…440 V 3 phase
7…11 kW 480…500 V 3 phase
Motor starter type Direct on-line contactor
Contactor coil voltage 220 V AC standard

Environment
IP degree of protection IP20 front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Ambient air temperature for operation -40…60 °C
60…70 °C with derating
Ambient air temperature for storage -76…176 °F (-60…80 °C)
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 UL 94
Mechanical robustness Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 8 Gn for 11 ms
Height 3.35 in (85 mm)
Maximum Width 1.77 in (45 mm)
Depth 3.62 in (92 mm)
Net Weight 0.82 lb(US) (0.37 kg)

Ordering and shipping details


Category 22354 - CTR,TESYS D,OPEN,9-38A AC
Discount Schedule I12
GTIN 00785901207160
Nbr. of units in pkg. 1
Package weight(Lbs) 0.92 lb(US) (0.42 kg)
Returnability Yes
Country of origin ID

4
Packing Units
Unit Type of Package 1 PCE
Package 1 Height 2.17 in (5.5 cm)
Package 1 width 3.54 in (9 cm)
Package 1 Length 3.94 in (10 cm)
Unit Type of Package 2 S02
Number of Units in Package 2 20
Package 2 Weight 18.90 lb(US) (8.574 kg)
Package 2 Height 5.91 in (15 cm)
Package 2 width 11.81 in (30 cm)
Package 2 Length 15.75 in (40 cm)
Unit Type of Package 3 P06
Number of Units in Package 3 320
Package 3 Weight 324.74 lb(US) (147.3 kg)
Package 3 Height 31.50 in (80 cm)
Package 3 width 31.50 in (80 cm)
Package 3 Length 23.62 in (60 cm)

Offer Sustainability
Sustainable offer status Green Premium product
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide
& Antimony trioxide, which is known to the State of California to cause cancer. For
more information go to www.P65Warnings.ca.gov
REACh Regulation
REACh Declaration
REACh free of SVHC Yes
EU RoHS Directive
Compliant EU RoHS Declaration
Toxic heavy metal free Yes
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
WEEE The product must be disposed on European Union markets following specific
waste collection and never end up in rubbish bins.
PVC free Yes

Contractual warranty
Warranty 18 months

5
Product data sheet LC1D25M7
Dimensions Drawings

Dimensions

(1) Including LAD 4BB


(2) Minimum electrical clearance

LC1 D25…D38 (3-pole)

b without add-on blocks 85

b1 with LAD 4BB 98

with LA4 D●2 114


(1)

with LA4 DF, 123


(1)

DT

with LA4 DW, 130


(1)

DL

c without cover or add-on blocks 90

with cover, 92
without add-on
blocks

c1 with LAD N or C (2 or 4 contacts) 123

c2 with LA6 DK10, LAD 6K10 135

c3 with LAD T, R, S 143

with LAD T, R, 147


S and sealing
cover

(1) Including LAD 4BB.

6
Product data sheet LC1D25M7
Connections and Schema

Wiring