PROJECT: PROPOSED INDUSTRIAL PARK AT SALEMPUR HATHRAS ROAD, HATHRAS

CLIENT: UTTAR PRADESH STATE INDUSTRIAL DEVELOPMENT AUTHORITY, KANPUR


BILL OF QUANTITIES FOR ELECTRICAL WORK
SL.NO Approve
ITEM NO DESCRIPTION UNIT QTY
. d by

11) H.T. PANEL 11KV INDOOR TYPE

Design, manufacturing, testing at works, supply and delivery, installation, testing


and commissioning of 11KV HT Panel Extensible Type as per specification and
comprising of the following :-

A. Incomer - 2 Nos.

1250 A Vacuum circuit breaker of (350 MVA) 18.4 KA rupturing capacity at 11 KV


rated, totally enclosed, air insulated metal clad housing, floor mounting, vertical
isolation, vermin proof, fully interlocked horizontal drawout type having double
isolation features and control devices complete with the following:

i. Manually and motor operated, spring charged( release closing mechanism) trip free
type, triple pole truck mounted draw out, vacuum circuit breaker, incorporating
mechanical as well as electrical ON/OFF indication. Spring charge/discharge
mechanical indication "OFF" push buttons for emergency trip (shrouded)
test/service position limit switches with 6 NO/6NC breaker auxiliary contacts in
service position,24 Volts DC shunt trip coil and strip heater to prevent moisture
absorption, power pack unit.

ii. 1250 amp air insulated but encapsulated,PVC insulated copper bus bars.

iii. C.T. chamber with double wound, dual ratio C.T.'s 540/270/5+5 (separate core for
metering and separate core for protection.

a. 15 VA burden for protection (class 5P 10).

iv. Protection arrangement for the incoming breaker shall comprise of the following:

a. 2 nos.outer elements for over current and one middle earth-fault element with
IDMT self power Relay with shunt trip on 30/24 Volts, D.C., (CDG - 31 of Alstom or
51,51N approved equivalent,Hi set) consisting 2 element overcurrent relay with
setting from 400 to 2000% and earth fault with setting from 200 to 800%)

b. Anti pumping relay (94)

c. Master trip relay (86)

d. Restricted earth fault relay.

v All wiring necessary for the above including inter-connections. The size of the
conductor should not be less than 2.5 sq. mm. copper wire where required.

vi Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps
etc. as per standard practice as under.

a. Red - Breaker close (ON)

b. Amber - auto trip

c. Clear - trip circuit healthy

d. white - 3 nos. one per phase

e. Blue spring charged

vii 6-window annunciation panel with audio and visual indicator.

a. Over current & earth fault - 2 windows

b. Spare - 4 windows

viii Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication
arrangement.

ix. Terminal boxes with single gland trifurcating cable box suitable(Raychem make) for
11 KV Aluminium XLPE (E) cable of size 2 x 3 x 300 Sq. mm. for incoming
breaker.

x. HT Danger Plate.(as per IS specification)

xi. 2 Runs of 50 X 6 mm earth bus shall be provided for the full length of the panel.

B. BUS COUPLER - 1 Nos.


SL.NO Approve
ITEM NO DESCRIPTION UNIT QTY
. d by

1250 A Vacuum circuit breaker of (350 MVA) 18.4 KA rupturing capacity at 11 KV


rated, totally enclosed, air insulated metal clad housing, floor mounting, vertical
isolation, vermin proof, fully interlocked horizontal drawout type having double
isolation features and control devices complete with the following:

i. Manually and motor operated, spring charged( release closing mechanism) trip free
type, triple pole truck mounted draw out, vacuum circuit breaker, incorporating
mechanical as well as electrical ON/OFF indication. Spring charge/discharge
mechanical indication "OFF" push buttons for emergency trip (shrouded)
test/service position limit switches with 6 NO/6NC breaker auxiliary contacts in
service position, strip heater to prevent moisture absorption

ii. 630 amp air insulated but encapsulated,PVC insulated copper bus bars.

iii. All wiring necessary for the above including inter-connections. The size of the
conductor should not be less than 2.5 sq. mm. copper wire where required.

iv. Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps
etc. as per standard practise as under.

a. Red - Breaker close (ON)

b. Amber - auto trip

c. Clear - trip circuit healthy

d. white - 3 nos. one per phase

e. Blue spring charged

v. Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication
arrangement.

C. Outgoing - 10 Nos.

i. 630 A Vacuum circuit breaker of (350 MVA) 18.4 KA rupturing capacity at 11 KV


rated, totally enclosed, air insulated metal clad housing, floor mounting, vertical
isolation, vermin proof, fully interlocked horizontal draw out type having double
isolation features and control devices complete with the following:

ii Manually and motor operated, spring charged( release closing mechanism) trip free
type, triple pole truck mounted draw out, vacuum circuit breaker, incorporating
mechanical as well as electrical ON/OFF indication. Spring charge/discharge
mechanical indication "OFF" push buttons for emergency trip (shrouded)
test/service position limit switches with 6 NO/6NC breaker auxiliary contacts in
service position,24 Volts DC shunt trip coil and strip heater to prevent moisture
absorption, power pack unit.

iii 630 amp air insulated but encapsulated,PVC insulated copper bus bars.

iv. C.T. chamber with double wound, dual ratio C.T.'s 300/150/5+5 (separate core for
metering and separate core for protection.

a. 15 VA burden for protection (class 5P 10).

v. Following protection shall be provided:

a. 1 Nos IDMT relay with instantaneous 2 nos. over current (50) element and 1 no.
instantaneous earth fault element(50N).(O/C setting 50%-200% and E/F setting
20%-80%)

vi All wiring necessary for the above including inter-connections. The size of the
conductor should not be less than 2.5 sq. mm. copper wire where required.

vii Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps
etc. as per standard practice as under.

a. Red - Breaker close (ON)

b. Amber - auto trip

c. Clear - trip circuit healthy

d. white - 3 nos. one per phase

e. Blue spring charged

viii 6-window annunciation panel with audio and visual indicator.

a. Over current & earth fault - 2 windows

b. Spare - 4 windows
SL.NO Approve
ITEM NO DESCRIPTION UNIT QTY
. d by

ix. Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication
arrangement.

a. Spare

x. Terminal boxes with single gland trifurcating cable box suitable for(Raychem make
cable termination) 11 KV Aluminium XLPE(E) cable of size 3 x 300 Sq. mm for
outgoing breakers.

stock S403996 + HT Panel switchboard complete with all interconnections,labels,wiring Set 1


issue S401910 etc ,complete as described above in item nos.A ,B , C and as per specifications.
rate 59
+60

Total of HT PANEL
4NOS. HT PANEL

Part-2 ( Distribution System)


RMU (RING MAIN UNIT)
Supply, Installation, Testing and Commissioning of Outdoor Type Ring Main
Unit 6 way as detailed below
6Way 11kV , 3Phase, 50Hz, 3 wire , earthed neutral, oudoor type floor mounted,
non extensible, having hinged arc proof cable doors, breaking capacity 18.4 kA,
SF6 / VCB Ring Main Unit enclosed in robotically laser welded stainless steel tank
having IP67 degree of protection consisting of following and as per UPPCL norms:-

(i) 2 Nos. 630Amps Fault making load breaking spring assisted SF6 Ring Switches,
fitted with fixed type voltage indicator device as per IEC 61958 along with
associated sensor and fault passage indicator.
(ii) 4 No. 630Amps tee off spring assisted type vacuum/SF6 circuit breaker
unit with self powered series trip microprocessor based numerical over current
and Earth fault relay for protection, fitted with fixed type voltage indicator device
as per IEC 61958 and ring core type protection Current transformer along with LV
compartment with Ammeter with selector switches. (Contractor/Supplier is liable
to get GTP and Drawing approval from UPPCL authorized representative and
also get inspected at manufactrur works.)

Set 74

Supply, Installation, Testing and Commissioning of Outdoor Type Ring Main


Unit 5 way as detailed below
5Way 11kV , 3Phase, 50Hz, 3 wire , earthed neutral, oudoor type floor mounted,
non extensible, having hinged arc proof cable doors, breaking capacity 18.4 kA,
SF6 / VCB Ring Main Unit enclosed in robotically laser welded stainless steel tank
having IP67 degree of protection consisting of following and as per UPPCL norms:-

(i) 2 Nos. 630Amps Fault making load breaking spring assisted SF6 Ring Switches,
fitted with fixed type voltage indicator device as per IEC 61958 along with
associated sensor and fault passage indicator.
(ii) 3 No. 630Amps tee off spring assisted type vacuum/SF6 circuit breaker
unit with self powered series trip microprocessor based numerical over current
and Earth fault relay for protection, fitted with fixed type voltage indicator device
as per IEC 61958 and ring core type protection Current transformer along with LV
compartment with Ammeter with selector switches. (Contractor/Supplier is liable
to get GTP and Drawing approval from UPPCL authorized representative and
also get inspected at manufactrur works.)
Set 9
Supply, Installation, Testing and Commissioning of Outdoor Type Ring Main
Unit 4 way as detailed below.
4Way 11kV , 3Phase, 50Hz, 3 wire , earthed neutral, oudoor type floor mounted,
non extensible, having hinged arc proof cable doors, breaking capacity 18.4 kA,
SF6 / VCB Ring Main Unit enclosed in robotically laser welded stainless steel tank
having IP67 degree of protection consisting of following and as per UPPCL norms:-

(i) 2 Nos. 630Amps Fault making load breaking spring assisted SF6 Ring Switches,
fitted with fixed type voltage indicator device as per IEC 61958 along with
associated sensor and fault passage indicator.
(ii) 2 No. 630Amps tee off spring assisted type vacuum/SF6 circuit breaker
unit with self powered series trip microprocessor based numerical over current
and Earth fault relay for protection, fitted with fixed type voltage indicator device
as per IEC 61958 and ring core type protection Current transformer along with LV
compartment with Ammeter with selector switches. (Contractor/Supplier is liable
to get GTP and Drawing approval from UPPCL authorized representative and
also get inspected at manufactrur works.)
Set 14

Supply, Installation, Testing and Commissioning of Outdoor Type Ring Main


Unit 3 way as detailed below.
SL.NO Approve
ITEM NO DESCRIPTION UNIT QTY
. d by

3 Way 11kV , 3Phase, 50Hz, 3 wire , earthed neutral, oudoor type floor mounted,
non extensible, having hinged arc proof cable doors, breaking capacity 18.4 kA,
SF6 / VCB Ring Main Unit enclosed in robotically laser welded stainless steel tank
having IP67 degree of protection consisting of following and as per UPPCL norms:-

(i) 2 Nos. 630Amps Fault making load breaking spring assisted SF6 Ring Switches,
fitted with fixed type voltage indicator device as per IEC 61958 along with
associated sensor and fault passage indicator.
(ii) 1 No. 630Amps tee off spring assisted type vacuum/SF6 circuit breaker
unit with self powered series trip microprocessor based numerical over current
and Earth fault relay for protection, fitted with fixed type voltage indicator device
as per IEC 61958 and ring core type protection Current transformer along with LV
compartment with Ammeter with selector switches. Contractor/Supplier is laible
to get GTP and Drawing approval from UPPCL authorized representative and
also get Inspected at manufactrur works)
Set 7

TOTAL OF RMU ( RING MAIN UNIT

Supply, Installation, Testing and Commissioning of. 11 KV/433 V, 630 KVA three
phase, 50 HZ, DYn11, +/-5% in 4 equal steps in 5 positions off load tap changer,
oil cooled, outdoor mounting type, design low loss transformer with Cu winding &
standard fittings as per IS 1180 Level-3 and as per UHBVN Norms
(Contractor/Supplier is laible to get GTP Approval, inspection of transformers
from UPPCL authorized representative and also get approved at manufactrur
works.)
Set R/O

Stock V 101257 Supply, Installation, Testing and Commissioning of. 11 KV/433 V, 400 KVA three
Issue phase, 50 HZ, DYn11, +/-5% in 4 equal steps in 5 positions off load tap changer,
Rate oil cooled, outdoor mounting type, design low loss transformer with Cu winding &
73 standard fittings as per IS 1180 Level-3 and as per UPPCL Norms
(2023- (Contractor/Supplier is laible to get GTP Approval and Stage inspection of
24) transformers from UPPCL authorized representative at manufactrur worksand
also get approvel)
Nos 44

5.0 Feeder Pillar Cum Meter Board


MR Supply, Installation, Testing and Commissioning of Outdoor type weather proof
cubicle front oprated non- compartmentalized design, with cable and bus bar
alleys, water & dust proof feeder pillar made out of 2 mm thick M.S. sheet, with
suitable stiffners Powder coated painted complete with pad lock arrangement,
mounted on the brick pedestal, grouting etc as per specification & drawings and
UPPCL spacification complete as per following details. (Contractor/Supplier is
laible to get GTP Approval and inspection of Panels from UPPCL authorized
representative at manufactrur works and get approvel)

A Type - I : FP-1,
Comprising of :
Incoming :
- One (1) No. 315 Amps TPN MCCB (36 KA).with thermal megnatic release
One (1) set of phase indicating lamps with 6A MCB.
Digital electronic VAF meter DM-6100 of Schneider make with inbuilt selector
switch and 3 Nos, 300/5 amps 5 VA, CL 1 CTs . - 1 Set
Bus Bar :

- One (1) set 500 Amps 415 Volts, 3 phase 4 wire colour coded PVC sleeved
aluminium bus bars suitable for Single/three phase connection.
Four (4) set 25 Sqmm wire colour coded suitable for three phase connection
including lugs etc..
Outgoings :
Space for Four (4) Nos. Three phase energy meter with CT, non-compartmentalized
as per UPPCL norms with provision of 100A MCCB for outgoing
-
Earthing Bus :
- One (1) No. of earthing bus of suitable size all along the feeder piller with 2 earthing Set 1
bolts of suitable size..

B MR Type - 2 : FP-2
Comprising of :
Incoming :
One (1) No. 125 Amps TPN MCCB (36 KA).with thermal megnatic release
One (1) set of phase indicating lamps with 6A MCB.
Digital electronic VAF meter DM-6100 of Schneider make with inbuilt selector
switch and 3 Nos,125/5 amps 5 VA, CL 1 CTs . - 1 Set
Bus Bar :

One (1) set 200 Amps 415 Volts, 3 phase 4 wire colour coded PVC sleeved
aluminium bus bars suitable for Single/three phase connection.
One (1) set 25 Sqmm wire colour coded suitable for three phase connection
including lugs etc..
Three (3) set 16 Sqmm wire colour coded suitable for three phase connection
including lugs etc..
Outgoings :
SL.NO Approve
ITEM NO DESCRIPTION UNIT QTY
. d by

Space for Four (4) Nos. Three phase energy meter with CT, non-compartmentalized
as per UPPCL norms with provision of 63/100A MCCB for outgoing

Earthing Bus :
One (1) No. of earthing bus of suitable size all along the feeder piller with 2 earthing Set 1
bolts of suitable size..

C MR Type - 3 : FP-4, FP-35


Comprising of :
Incoming :
One (1) No. 125 Amps TPN MCCB (36 KA).with thermal megnatic release
One (1) set of phase indicating lamps with 6A MCB.
Digital electronic VAF meter DM-6100 of Schneider make with inbuilt selector
switch and 3 Nos,125/5 amps 5 VA, CL 1 CTs . - 1 Set
Bus Bar :

One (1) set 200 Amps 415 Volts, 3 phase 4 wire colour coded PVC sleeved
aluminium bus bars suitable for Single/three phase connection.
Four (4) set 16 Sqmm wire colour coded suitable for three phase connection
including lugs etc..
Outgoings :

Space for Four (4) Nos. Three phase energy meter with CT, non-compartmentalized
as per UPPCL norms with provision of 63 MCCB for outgoing

Earthing Bus :
One (1) No. of earthing bus of suitable size all along the feeder piller with 2 earthing Set 2
bolts of suitable size..

D Type - 4 : FP-9, 10, 11, 17, 18, 19, 20, 21, 27, 28, 29, 30, 31, 33, 34, 80, 89,
90, 91, 92, 93
Comprising of :
Incoming :
One (1) No. 250 Amps TPN MCCB (36 KA).with thermal megnatic release
One (1) set of phase indicating lamps with 6A MCB.
Digital electronic VAF meter DM-6100 of Schneider make with inbuilt selector
switch and 3 Nos, 250/5 amps 5 VA, CL 1 CTs . - 1 Set
Bus Bar :

One (1) set 400 Amps 415 Volts, 3 phase 4 wire colour coded PVC sleeved
aluminium bus bars suitable for Single/three phase connection.
Four (4) set 16 Sqmm wire colour coded suitable for three phase connection
including lugs etc..
Outgoings :

Space for Four (4) Nos. Three phase energy meter with CT, non-compartmentalized
as per UPPCL norms with provision of 63 MCCB for outgoing

Earthing Bus :
One (1) No. of earthing bus of suitable size all along the feeder piller with 2 earthing Set 21
bolts of suitable size..

E MR Type - 5 : FP-12, 32, 81


Comprising of :
Incoming :
One (1) No. 250 Amps TPN MCCB (36 KA).with thermal megnatic release
One (1) set of phase indicating lamps with 6A MCB.
Digital electronic VAF meter DM-6100 of Schneider make with inbuilt selector
switch and 3 Nos, 250/5 amps 5 VA, CL 1 CTs . - 1 Set
Bus Bar :

One (1) set 400 Amps 415 Volts, 3 phase 4 wire colour coded PVC sleeved
aluminium bus bars suitable for Single/three phase connection.
Six (6) set 16 Sqmm wire colour coded suitable for three phase connection
including lugs etc..
Outgoings :

Space for Six (6) Nos. Three phase energy meter with CT, non-compartmentalized
as per UPPCL norms with provision of 63 MCCB for outgoing

Earthing Bus :
One (1) No. of earthing bus of suitable size all along the feeder piller with 2 earthing Set 3
bolts of suitable size..

F MR Type - 6 : FP-6, 7, 8, 13,14, 15, 16, 22, 23, 24, 25, 26, 36, 37, 38, 39, 40, 41,
42, 43, 44, 45, 46, 47, 48, 49, 50, 51, 52, 53, 60, 61, 62, 63, 64, 65, 66, 67,
68, 69, 70, 71, 72, 73, 74, 75, 76, 77, 78, 79, 82, 83, 84, 85, 86, 87, 88

Comprising of :
Incoming :
One (1) No. 315 Amps TPN MCCB (36 KA).with thermal megnatic release
One (1) set of phase indicating lamps with 6A MCB.
SL.NO Approve
ITEM NO DESCRIPTION UNIT QTY
. d by

Digital electronic VAF meter DM-6100 of Schneider make with inbuilt selector
switch and 3 Nos, 300/5 amps 5 VA, CL 1 CTs . - 1 Set
Bus Bar :

One (1) set 500 Amps 415 Volts, 3 phase 4 wire colour coded PVC sleeved
aluminium bus bars suitable for Single/three phase connection.
Six (6) set 16 Sqmm wire colour coded suitable for three phase connection
including lugs etc..
Outgoings :

Space for Six (6) Nos. Three phase energy meter with CT, non-compartmentalized
as per UPPCL norms with provision of 63 MCCB for outgoing

Earthing Bus :
One (1) No. of earthing bus of suitable size all along the feeder piller with 2 earthing Set 57
bolts of suitable size..

G MR Type - 7 : FP-54, 55, 56, 57, 58, 59, 94, 95, 96, 97, 98, 99, 100, 101, 102,
103
Comprising of :
Incoming :
One (1) No. 500 Amps TPN MCCB (36 KA).with thermal megnatic release
One (1) set of phase indicating lamps with 6A MCB.
Digital electronic VAF meter DM-6100 of Schneider make with inbuilt selector
switch and 3 Nos, 300/5 amps 5 VA, CL 1 CTs . - 1 Set
Bus Bar :

One (1) set 500 Amps 415 Volts, 3 phase 4 wire colour coded PVC sleeved
aluminium bus bars suitable for Single/three phase connection.
Six (6) set 16 Sqmm wire colour coded suitable for three phase connection
including lugs etc..
Outgoings :

Space for Six (6) Nos. Three phase energy meter with CT, non-compartmentalized
as per UPPCL norms with provision of 125 MCCB for outgoing

Earthing Bus :
One (1) No. of earthing bus of suitable size all along the feeder piller with 2 earthing Set 16
bolts of suitable size..

H MR Type - 8 : FP-5
Comprising of :
Incoming :
One (1) No. 315 Amps TPN MCCB (36 KA).with thermal megnatic release
One (1) set of phase indicating lamps with 6A MCB.
Digital electronic VAF meter DM-6100 of Schneider make with inbuilt selector
switch and 3 Nos, 300/5 amps 5 VA, CL 1 CTs . - 1 Set
Bus Bar :

One (1) set 500 Amps 415 Volts, 3 phase 4 wire colour coded PVC sleeved
aluminium bus bars suitable for Single/three phase connection.
Six (6) set 25 Sqmm wire colour coded suitable for three phase connection
including lugs etc..
Outgoings :

Space for Six (6) Nos. Three phase energy meter with CT, non-compartmentalized
as per UPPCL norms with provision of 100 MCCB for outgoing

Earthing Bus :
One (1) No. of earthing bus of suitable size all along the feeder piller with 2 earthing Set 1
bolts of suitable size..

I MR Type - 10 : FP-51
Comprising of :
Incoming :
One (1) No. 400 Amps TPN MCCB (36 KA).with thermal megnatic release
One (1) set of phase indicating lamps with 6A MCB.
Digital electronic VAF meter DM-6100 of Schneider make with inbuilt selector
switch and 3 Nos, 400/5 amps 5 VA, CL 1 CTs . - 1 Set
Bus Bar :

One (1) set 600 Amps 415 Volts, 3 phase 4 wire colour coded PVC sleeved
aluminium bus bars suitable for Single/three phase connection.
Eight (8) set 16 Sqmm wire colour coded suitable for three phase connection
including lugs etc..
Outgoings :

Space for Eight (8) Nos. Three phase energy meter with CT, non-compartmentalized
as per UPPCL norms with provision of 63 MCCB for outgoing

Earthing Bus :
One (1) No. of earthing bus of suitable size all along the feeder piller with 2 earthing Set 1
bolts of suitable size..
TOTAL OF Feeder Pillar Cum Meter Board
SL.NO Approve
ITEM NO DESCRIPTION UNIT QTY
. d by

MR Main LT Panels
Supply, Installation, Testing and Commissioning of Main LT Panels Outdoor type
weather proof cubicle front oprated compartmentalized design, with cable and bus
bar alleys made out of 2 mm thick M.S. sheet, with suitable stiffners Powder
coated painted complete with pad lock arrangement, mounted on the brick
pedestal, grouting etc as per specification & drawings and UPPCL spacification
complete as per following details. (Contractor/Supplier is laible to get GTP
Approval and inspection of Panels from UPPCL authorized representative at
manufactrur works and get approvel)

6 C) Main LT Panels
A MR For Transformer 400KVA
50 KA at 415 volt Incomer's, MCCB's Buscoupler switching, interlocking complete
with following switchgear.
ONE NO. INCOMING TRANSFORMER FEEDER EQUIPPED WITH
- 1 Nos.630 Amp 4 Pole 50 KA MCCB complete with Microprocessor based release

Degital VAF meter DM-6100 of Schneider make with inbuilt selector switch 415V
AC with CT ratio 600/5 lass 1.0 for metering, 15 VA Burden.
1 set of three R Y B indicating lamps.
Red and green ON / OFF indicating lamps.
Terminal to receive 800Amp Al. Cables

Bus-Bar
800 AMP, 500 Volts, 3 phase 50 HZ TPN high conductivity electrolytic Aluminium
bus bar of suitable length, insulated by heat shrinkable sleeves. The current
density of bus bar shall be minimum 1.00 sq mm / amp.
Earthing Bus :
One (1) No. of earthing bus of suitable size all along the feeder piller with 2 earthing
bolts of suitable size..
Outgoing:
All outgoing feeders shall be provided with ON indication lamp with protection
MCB 6A
MLTP-1
2 nos 315 AMP TP MCCB (50 KA) with thermal megnatic release
1 no 125 AMP TP MCCB (50 KA) with thermal megnatic release
2 no 63 AMP TP MCCB (50 KA) with thermal megnatic release Set 1

B MR MLTP-2
2 nos 250 AMP TP MCCB (50 KA) with thermal megnatic release
- 1 no 125 AMP TP MCCB (50 KA) with thermal megnatic release
2 no 63 AMP TP MCCB (50 KA) with thermal megnatic release Set 1

C MLTP-3, 4, 7, 10, 11, 16, 17, 18, 19, 20, 21, 22, 24, 26, 27, 28, 29, 30, 31,
32, 33, 34, 35, 36, 37, 38
3 nos 315 AMP TP MCCB (50 KA) with thermal megnatic release
2 no 63 AMP TP MCCB (50 KA) with thermal megnatic release Set 26

D MR MLTP-9, 13, 14
4 nos 250 AMP TP MCCB (50 KA) with thermal megnatic release
2 no 63 AMP TP MCCB (50 KA) with thermal megnatic release Set 3

E MR MLTP-6, 8, 39
2 nos 315 AMP TP MCCB (50 KA) with thermal megnatic release
1 nos 250 AMP TP MCCB (50 KA) with thermal megnatic release
2 no 63 AMP TP MCCB (50 KA) with thermal megnatic release Set 3

F MR MLTP-10
2 nos 315 AMP TP MCCB (50 KA) with thermal megnatic release
1 nos 250 AMP TP MCCB (50 KA) with thermal megnatic release
1 nos 125 AMP TP MCCB (50 KA) with thermal megnatic release
2 no 63 AMP TP MCCB (50 KA) with thermal megnatic release Set 1

G MR MLTP-15
3 nos 250 AMP TP MCCB (50 KA) with thermal megnatic release
1 nos 125 AMP TP MCCB (50 KA) with thermal megnatic release
2 no 63 AMP TP MCCB (50 KA) with thermal megnatic release Set 1

H MR MLTP-23
2 nos 400 AMP TP MCCB (50 KA) with thermal megnatic release
1 nos 315 AMP TP MCCB (50 KA) with thermal megnatic release
2 no 63 AMP TP MCCB (50 KA) with thermal megnatic release Set 1

I MR MLTP-33,
2 nos 400 AMP TP MCCB (50 KA) with thermal megnatic release
2 no 63 AMP TP MCCB (50 KA) with thermal megnatic release Set 1

J MR MLTP-40, 41, 42
3 nos 250 AMP TP MCCB (50 KA) with thermal megnatic release
2 no 63 AMP TP MCCB (50 KA) with thermal megnatic release Set 3
K MR MLTP- 25, 43, 44,
6 nos 250 AMP TP MCCB (50 KA) with thermal megnatic release
2 no 63 AMP TP MCCB (50 KA) with thermal megnatic release Set 3
TOTAL OF Main LT Panels
SL.NO Approve
ITEM NO DESCRIPTION UNIT QTY
. d by

EXTERNAL LIGHTING
MR WEATHER PROOF STREET LIGHT FEEDER PILLAR
Supply, Installation, Testing and Commissioning of outdoor type weather proof
cubicle double door, front oprated, with cable and bus bar alleys, water & dust
proof feeder pillar made out of 2 mm thick M.S. sheet, with suitable stiffners
Powder Coating painted complete as required.
Comprising of :
in built control panel for smart lighting system having
compatibility with optical fibre,GSM,GPS,Wi-Fi,Wi-max,Ethernet
as per specifications attached including concentrator,convertor and other items
required for successful operation as per entire satisfaction of EngineerIncharge
INCOMING:
One (1) No. 63 Amps.TP MCCB (25 KA) .with thermal megnatic release.
Three (3) Nos. LED type (R/Y/B) Phase indicating lamps with protection 2A SP
MCBs.
Bus Bar :
100 A TPN Aluminium Bus bar with colour coded heat shrinkable PVC sleeves.
Outgoings :
24Nos. 16A SP MCB (10KA) 6 Nos. on each phase.)
2 nos. 32A FP MCB (10KA)
Saprate Neutral Busbar for each phase.
Controls:
Triple pole contactor 63A rating- 1 nos
Time switch with daily dial suitable for opration on 415V, Single Phase, 50Hz, AC
supply- 1 nos
Auto-Mannul selector switch- 3 no.
Earthing Bus :
One (1) No. of earthing bus of suitable size all along the feeder piller with 2 earthing Set 50
bolts of suitable size.
TOTAL OF Main LT Panels