General Specifications:: Legend

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

S C H E D U L E O F L O A D S

NO. OF OUTLET NO. OF SWITCHES AMPERE SIZE OF CONDUCTORS U-PVC CB


PB-1 DESCRIPTION VOLTS VOLTS PER CKT. PIPE SIZE RATING
L.O C.O A.C S1 S2 S3 AMP. & CONDUITS
C1 21W 3U PINLIGHT 6 2 2 220 600 2.73 ² THHHN WIRE STRANDED COPPER WIRE
3.5mm 20mmØ 15 AT

C2 21 W 3U PINLIGHT 5 1 2 220 500 2.27 ² THHHN WIRE STRANDED COPPER WIRE


3.5mm 20mmØ 15 AT

C3 2 GANG CONVENIENCE OUTLET 4 220 1440 6.55 ² THHHN WIRE STRANDED COPPER WIRE
3.5mm 20mmØ 20 AT

C4 2 GANG CONVENIENCE OUTLET 6 220 2160 9.82 ² THHHN WIRE STRANDED COPPER WIRE
3.5mm 20mmØ 20 AT

C5 AIRCON OUTLET 1 220 2750 12.50 ² THHHN WIRE STRANDED COPPER WIRE
5.5mm 20mmØ 30 AT

TOTAL 11 10 1 3 4 220 7450 42.37 ² THHHN WIRE STRANDED COPPER WIRE


8.0mm 20mmØ 60 AT

COMPUTATION THEREFORE USE =


: 8.0mm² THHHN STRNDED COPPER WIRE
= 60 Amp. MAIN CIRCUIT BREAKER
IT = (2.73 + 2.27 + 6.55 + 9.82 + 12.50)(1.25) = 6 BRANCHES CIRCUIT BREAKER
= (33.87) (1.25)
IT = 42.34 AMP. 220 - 240 VOLTZ, 60HZ

2 - 8.0 sq. mm THHN COPPER WIRE IN 25 mm DIA. RSC PIPE

SERVICE ENTRANCE M

GENERAL SPECIFICATIONS: MAIN


C1
60A 15A

ALL ELECTRICAL MATERIALS TO BE USE SHALL BE NEW


C2 15A 20A C3 LEGEND:
AND APPROVED TYPES AS TO USED AND LOCATION. C4 20A 30A C5

MOUNTING HEIGHTS SHALL BE AS FOLLOWS: M KILOWATT HOUR METER

a. PANEL BOARD-1.70m. FROM FINISHED FLOOR. SERVICE ENTRANCE CAP

b. LIGHTING SWITCHES - 1.30m. FROM FINISHED FLOOR. GROUND


DUPLEX CONVINIENCE OUTLET
c. CONVENIENCE OUTLETS - 0.30m. FROM FINISHED FLOOR. PIN LIGHT

RISER DIAGRAM DUPLEX CONVINIENCE OUTLET


MOUNTING HEIGHTS SHALL BE AS FOLLOWS: (ACU) AIR CONDITIONING UNIT
ACU
a. SERVICE ENTRANCE - EXPOSED USING PVC CONDUITS.
RANGE GAS RANGE
b. BRANCH CIRCUITS - CONCEALED USING PVC CONDUITS. S1 SINGLE GANG SWITCH
S2 TWO GANG SWITCH
WORK SHALL BE IN CONFORMITY WITH THE LATEST PHILIPPINE
ELECTRICAL CODE (PEC) NATIONAL BUIDING CODE AND S
SWITCH LINE

MOALCE RULES AND REGULATION. OUTLET LINE


LIGHT LINE
WORK SUPERVISION SHALL BE UNDER TAKEN BY A DULY CIRCUIT BREAKER PANEL BOARD
LICENSED ELECTRICAL ENGINEER OR MASTER ELECTRICIAN.

Checked & Reviewed by: PRC REG. No. Seal Project: Conformed by: Sheet No.:
PTR No.

ISSUED ON: E-2


ISSUED AT: ELECTRICAL INSTALLATION JUDETH A. BALDERAS 10
REGISTERED ELECTRICAL ENGINEER
TIN: Location: MOLICAY, OZAMIS CITY, MIZ. OCC. OWNER