Kei Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

TECHNICAL DATA SHEET FOR 0.

6/1 KV AL, XLPE(ARMOURED) POWER CABLES AS PER IEC: 60502 (P-1)

Client :
Project : Dated: 20.03.2014
S.No. Description Units 4C x 16 4C x 25 4C x 35 4C x 50 4C x 70 4C x 95 4C x 120 4C x 150 4C x 185 4C x 240 4C x 300 4C x 400
1.0 GENERAL
Name of Manufacturer M/s KEI Industries Limited.
Voltage Grade kV 0.6/1 kV
Standards Applicable IEC: 60502 (P-1)

2.0 CONDUCTOR
Material Aluminium of H2 grade as per class- 2 of IEC: 60228
Nominal Cross Sectional Area sq.mm. 16 25 35 50 70 95 120 150 185 240 300 400
Shape of conductor Stranded compacted sector shaped
Nominal Diameter mm Not Applicable for sector shape
0
Max. DC Resistance at 20 C Ohms/Km 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778
0
Approx. AC Resistance at 90 C Ohms/Km 2.445 1.536 1.111 0.820 0.567 0.410 0.324 0.264 0.210 0.160 0.128 0.100
Short Circuit Current for 1 sec. KA/sec 1.504 2.35 3.29 4.7 6.58 8.93 11.28 14.1 17.39 22.56 28.2 37.6

3.0 Max CONDUCTOR TEMPERATURE


Rated DegC 90 Deg C
During short circuit DegC 250 Deg C

4.0 INSULATION
Material Extruded XLPE as per IEC: 60502 (P-1)
Thickness (Nominal) mm 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
Tolerance on thickness (-ive) mm 0.1+0.1*t (where t = nominal thickness of insulation)

5.0 CORE COLOUR For 4 Cores- Red,Yellow,Blue & Black Colour.

6.0 INNER SHEATH


Material Extruded PVC " Type ST- 2 " as per IEC: 60502 (P-1)
Thickness (Minimum) mm 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.6 0.6 0.6 0.6 0.6
Colour Black

7.0 ARMOUR
Material Galvanized Steel Flat Strip as per IEC: 60502 (P-1)
Nominal dimensions of armour mm 4 x 0.8 4 x 0.8 4 x 0.8 4 x 0.8 4 x 0.8 4 x 0.8 4 x 0.8 4 x 0.8 4 x 0.8 4 x 0.8 4 x 0.8 4 x 0.8
Type Strip Strip Strip Strip Strip Strip Strip Strip Strip Strip Strip Strip

8.0 OUTER SHEATH


Material Extruded FRLS PVC " Type ST- 2 " as per IEC: 60502 (P-1)
Thickness (Nominal) mm 1.8 1.8 1.8 1.9 2.1 2.2 2.3 2.5 2.7 2.9 3.1 3.4
Colour Black

FRLS Properties
Oxygen Index Min. 29% as per ASTM D-2863
0
Temperature Index Min. 250 C as per ASTM D-2863
Smoke Density Rating Max. 60% as per ASTM D-2843
Acid Gas Generation Max. 20% as per IEC: 754-1
Flammability Test Shall pass as per IEC: 332 P-1

9.0 CABLE DATA


Approximate overall dia of cable mm 23.0 24.0 26.2 29.7 33.5 37.3 41.0 44.8 50.0 55.9 61.5 69.0
Tolerance on overall dia mm ± 2.0 mm ± 2.0 mm ± 2.0 mm ± 2.0 mm ± 2.0 mm ± 2.0 mm ± 2.0 mm ± 2.0 mm ± 2.0 mm ± 2.0 mm ± 2.0 mm ± 3.0 mm
Approx weight of cable Kg./Km 920 960 1150 1430 1830 2250 2670 3220 3840 4750 5670 7190

10.0 Continuous current rating for


different cables when laid up
In ground @ 20 Deg.C Amps. 81 101 121 144 175 210 239 268 301 349 393 437
In air @ 30 Deg.C Amps. 74 98 120 145 185 224 264 305 350 418 488 562

11.0 Drum Details In Non returnable Wooden Drum


Standard Drum Length meters 1000 1000 1000 1000 1000 1000 1000 1000 500 500 500 250
Individual Drum tolerance % ±5%
Overall Quantity Tolerance % ±5%

12.0 Sequential length marking Shall be provided on outer sheath by printing @ every one mtr