Analysis report Apr

Farm - Monthly - Apr, 2024


Lake Turkana Farm 3
Production Performance

Actual Production Average Wind Speed Capacity factor

23.4 GWh 7.3 m/s 31.3 %

Availability Management - Table

Month IEC - Technical TBA (%) IEC - Operational TBA (%)

Jan-24 98.7 95.7

Feb-24 98.0 94.8

Mar-24 99.1 98.5

Apr-24 97.9 94.2

Page 1 of 7 | 05/05/2024
Downtime

Downtime Events Summary


Code Description Default Allocation Frequency Duration Loss Production (MWh) Overridden

Component: Turbine Maintenance


220 Local:SERVICE state: _, ____ IEC: Planned Corrective Action 111 402h 49m 28s n/a
Customer Loss Allocation: Unscheduled maintenance

Component: Unassigned
900 Pause through local keyboard IEC: Requested Shutdown 81 269h 41m 20s n/a
Customer Loss Allocation: Manufacturer

Component: Power Supply / Converter


397 Thermoerror Int. VCS Fan F____ IEC: Forced Outage 8 247h 51m 1s n/a
Customer Loss Allocation: Manufacturer

Component: Heaters / Coolers


169 Thermoerr. Nac. fan F___/___°C IEC: Forced Outage 20 113h 26m 36s n/a
Customer Loss Allocation: Manufacturer

Component: Gearbox
111 No offline filtrat. For__days IEC: Forced Outage 8 108h 15m 37s n/a
Customer Loss Allocation: Manufacturer

Component: Yaw System


276 Start auto-outyawing CCW IEC: Technical Standby 241 202h 29m 44s n/a
Customer Loss Allocation: Environmental

Component: Sensors
159 Ext. RPM guard, ____ RPM S_ IEC: Forced Outage 14 76h 54m 9s n/a
Customer Loss Allocation: Manufacturer

Component: External-Stop
309 Pause over RCS __ IEC: Requested Shutdown 183 56h 59m 27s n/a
Customer Loss Allocation: Utility

Component: Gearbox
214 Low oil level, ____RPM/___°C IEC: Forced Outage 635 197h 45m 12s n/a
Customer Loss Allocation: Manufacturer

Component: Gearbox
150 High temp.Gear bearing _:___°C IEC: Forced Outage 4 44h 55m 44s n/a
Customer Loss Allocation: Manufacturer

Component: Gearbox
147 High gear temp:___°C/air:___°C IEC: Forced Outage 27 33h 48m 30s n/a
Customer Loss Allocation: Manufacturer

Component: Power Supply / Converter


318 Cannot syncronize____ RPM,st__ IEC: Forced Outage 2 21h 56m 51s n/a
Customer Loss Allocation: Manufacturer

Component: Pitch / Hyd


163 Low workingpressure: ___._ bar IEC: Forced Outage 17 34h 11m 49s n/a
Customer Loss Allocation: Manufacturer

Component: Pitch / Hyd


165 Low oil-level, hydraulic IEC: Forced Outage 2 25h 26m 52s n/a
Customer Loss Allocation: Manufacturer

Component: Sensors
430 Transm. osc. ____ RPM, __ m/s IEC: Forced Outage 11 47h 33m 55s n/a
Customer Loss Allocation: Manufacturer

Component: Grid
899 Grid volt above stop lim ___% IEC: Out of Electrical Specification 58 22h 2m 1s n/a
Customer Loss Allocation: Utility

Component: Heaters / Coolers


168 High temp top ctrl.: ___°C IEC: Forced Outage 4 21h 58m 16s n/a
Customer Loss Allocation: Manufacturer

Component: Gearbox
80 Low oil pressure:____RPM/___°C IEC: Forced Outage 2 17h 55m 42s n/a
Customer Loss Allocation: Manufacturer

Component: Heaters / Coolers


324 High temp. VCP Board ___°C IEC: Forced Outage 4 17h 4m 0s n/a
Customer Loss Allocation: Manufacturer

Component: Converter
340 OVP active UDC_____V state __ IEC: Forced Outage 3 5h 10m 0s n/a
Customer Loss Allocation: Manufacturer

Component: Grid
315 ExEx low voltage L_: ___V IEC: Out of Electrical Specification 9 28h 40m 41s n/a
Customer Loss Allocation: Utility

Component: Grid
127 Extr. low voltage L_: ___V IEC: Out of Electrical Specification 2 4h 50m 0s n/a
Customer Loss Allocation: Utility

Page 2 of 7 | 05/05/2024
Code Description Default Allocation Frequency Duration Loss Production (MWh) Overridden

Component: Power Supply / Converter


338 Slip:____ above limits _ IEC: Forced Outage 27 25h 22m 20s n/a
Customer Loss Allocation: Manufacturer

Component: Contactor / Circuit Breaker / Relay


317 Cont.=___ Feedback r.failed: _ IEC: Forced Outage 1 2h 39m 39s n/a
Customer Loss Allocation: Manufacturer

Component: Generator
201 Low temperature Gen_:___°C IEC: Forced Outage 2 20h 10m 0s n/a
Customer Loss Allocation: Manufacturer

Component: Converter
901 DC Overvolt stop:____V state__ IEC: Forced Outage 3 2h 56m 13s n/a
Customer Loss Allocation: Manufacturer

Component: Sensors
212 Error temp.sensor R___, ____°C IEC: Forced Outage 3 23h 16m 20s n/a
Customer Loss Allocation: Manufacturer

Component: Yaw System


79 Max. Yaw error: ___._° IEC: Out of Environmental Specification 24 1h 49m 3s n/a
Customer Loss Allocation: Environmental

Component: Sensors
343 Encoder signal error _:_____ IEC: Forced Outage 11 2h 11m 29s n/a
Customer Loss Allocation: Manufacturer

Component: Yaw System


275 Start auto-outyawing CW IEC: Technical Standby 8 3h 57m 7s n/a
Customer Loss Allocation: Environmental

Component: Converter
334 High cur.grid inv. L_:____A IEC: Forced Outage 1 0h 34m 50s n/a
Customer Loss Allocation: Manufacturer

Component: Brakes
160 High temperature brake disc IEC: Forced Outage 2 0h 58m 8s n/a
Customer Loss Allocation: Manufacturer

Component: Converter
341 OVPHwErr UDC _____V state __ IEC: Forced Outage 2 0h 10m 43s n/a
Customer Loss Allocation: Manufacturer

Component: Grid
703 RT Dip exc.lim.:___%:_____e-2s IEC: Out of Electrical Specification 4 1h 3m 25s n/a
Customer Loss Allocation: Utility

Component: Grid
202 Frequency error 1: ___.__ Hz IEC: Out of Electrical Specification 6 0h 13m 32s n/a
Customer Loss Allocation: Utility

Component: Power Supply / Converter


336 Ext.High cur.grd inv. L_:____A IEC: Forced Outage 2 0h 2m 49s n/a
Customer Loss Allocation: Manufacturer

Component: Sensors
176 Error on all wind sensors IEC: Forced Outage 3 0h 6m 49s n/a
Customer Loss Allocation: Manufacturer

Component: Converter
725 No RT, High Rotor Cur L_:____A IEC: Forced Outage 1 0h 1m 10s n/a
Customer Loss Allocation: Manufacturer

Component: Electrical Components


125 Extr.high curr.Gen2 L_: ____ A IEC: Forced Outage 1 0h 8m 1s n/a
Customer Loss Allocation: Manufacturer

Component: Converter
339 Phase L:_ failure IEC: Out of Electrical Specification 2 0h 2m 20s n/a
Customer Loss Allocation: Utility

Component: Generator
219 Thermoerror Ext.Gen.Fan F____ IEC: Forced Outage 1 0h 11m 14s n/a
Customer Loss Allocation: Manufacturer

Component: Rotor
726 No RT, Ex.Hig.Rot.Cur L_:____A IEC: Forced Outage 1 0h 1m 46s n/a
Customer Loss Allocation: Manufacturer

Component: Contactor / Circuit Breaker / Relay


316 Cont.=___ Feedback s.failed: _ IEC: Forced Outage 1 0h 1m 33s n/a
Customer Loss Allocation: Manufacturer

Component: Pitch / Hyd


161 Max time hydr. pumping:___ sec IEC: Forced Outage 1 0h 10m 0s n/a
Customer Loss Allocation: Manufacturer

Component: Turbine-Environment
144 High windspeed: __._ m/s IEC: Out of Environmental Specification 1 0h 2m 20s n/a
Customer Loss Allocation: Environmental

Page 3 of 7 | 05/05/2024
Downtime Overview - Component Downtime Overview - Component

Downtime Hours Lost Energy


1.0 h 27.3 MWh 0.3 MWh
208.3 h 2.7 h 1.8 MWh
8.9 h 4.5 MWh
0.1 h 0.0 MWh
57.0 h 13.7 MWh
402.7 h 73.4 MWh 67.0 MWh
269.7 h

1.5 MWh
9.1 MWh
0.0 h 20.4 h
56.8 h

36.6 MWh
152.5 h
402.8 h
13.6 MWh
59.8 h
102.8 MWh

150.0 h 295.2 h
0.0 h 64.0 MWh

21.9 MWh
Brakes Contactor / Circuit Breaker / Relay
Converter Electrical Components Brakes Contactor / Circuit Breaker / Relay
External-Stop Gearbox Converter Electrical Components
Generator Grid External-Stop Gearbox
Heaters / Coolers Pitch / Hyd Generator Grid
Power Supply / Converter Rotor Heaters / Coolers Pitch / Hyd
Sensors Turbine Maintenance Power Supply / Converter Sensors
Turbine-Environment Unassigned Turbine Maintenance Unassigned
Yaw System Yaw System

Page 4 of 7 | 05/05/2024
Turbine performance

Operational PC - highest & least performer turbines


1000

Bottom 1: Lake Turkana E02 Bottom 5: Lake Turkana E05


Top 2: Lake Turkana K01 OEM - VESTAS V52
Top 1: Lake Turkana M12
750
Top 4: Lake Turkana M08
Power Output (kW)

500
Bottom 3: Lake Turkana G07

Top 5: Lake Turkana M07

250

Bottom 2: Lake Turkana D12

Farm Average Bottom 4: Lake Turkana E04


0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Normalized Wind Speed (m/s)

Farm Average OEM - VESTAS V52 Bottom 1: Lake Turkana E02 Bottom 2: Lake Turkana D12 Bottom 3: Lake Turkana G07 Bottom 4: Lake Turkana E04
Bottom 5: Lake Turkana E05 Top 1: Lake Turkana M12 Top 2: Lake Turkana K01 Top 3: Lake Turkana M13 Top 4: Lake Turkana M08 Top 5: Lake Turkana M07

Overall loss (MWh)

30k

26472.6 437.5
170.3 0 0 0 2500.6

25k
23364.1

20k
Loss (MWh)

15k

10k

5k

0
Estimate Downtime Partial Curtailment Derate Degrade Icing Performance Actual

Page 5 of 7 | 05/05/2024
Wind distribution

Wind Distribution
2400 36k

2000 30k

1600 24k

Wind Distribution (freq.)


Generation (MWh)

1200 18k

800 12k

400 6k

0 0
2

12

22
7

17
4

14
3

13

16

19
8

18
1

11

21
0

1. 5

.5

.5
10

.5

.5

.5

15

.5

.5

.5

.5

.5
20

.5

.5

.5
0.

2.

3.

4.

5.

6.

7.

8.

9.

12

22
17
14
13

16

19
18
11

21
10

15

20
Wind Speed (m/s)

Generation Wind Distribution

Wind Rose or Energy Rose - Wind Rose

NNW NNE

40

Windspeed (m/s)
30
WNW ENE < 4 m/s
4-6 m/s
20
6-8 m/s
8-10 m/s
10
10-12 m/s
12-14 m/s
W 0 E 14-16 m/s
> 16 m/s

WSW ESE

SSW SSE

Page 6 of 7 | 05/05/2024
New Chapter

Page 7 of 7 | 05/05/2024