Section 3
Section 3
Faculty of Engineering
Fourth Year- Second Term
2020-2021
Section #2
Sheet #2
4- Transformer Taps
𝑖1−𝑖2 4.54−3.78
CT mismatch error…. = *100 = *100 =15.2 %
5 5
4.54 3.78
Choose taps from : taps for 3.0, 4.0, 4.8, 5.0, 5.2, 6.0 A , ( − )*100 =0.083 %
4.8 4
𝑖1−𝑖2 4.54−3.78
CT mismatch error…. = *100 = *100 =15.2 %
5 5
4.54 3.78
Choose taps from : taps for 3.0, 4.0, 4.8, 5.0, 5.2, 6.0 A , ( − )*100 =0.083 %
4.8 4
Solution
1- Draw the differential protection
𝐼𝐴 − 𝐼𝐵 IA Ia
A a
𝐼𝐵 − 𝐼𝐶 IB ia
B (iA-iC) Ib b
𝐼𝐶 − 𝐼𝐴 IC
C (iB-iC) Ic ib c
ic
(iC-iB)
3 ∗ 𝐼𝑓.𝑙 = 3 ∗ 577.3=999.99A
𝑖1−𝑖2 4.64−4.99
CT mismatch error…. = *100 = *100 =7 %
5 5
4.64 4.99
Choose taps from : taps for 3.0, 4.0, 4.8, 5.0, 5.2, 6.0 A , ( − )*100 =3.1 %
4.8 5
𝑰𝒇𝒂𝒄𝒕 = −𝒋𝟏𝟓𝟏𝟗. 𝟒 A ic
(iC-iB)
i1 i'1
𝐼𝑎 = 1519.4∠-90 A
𝐼𝑏 = 1519.4∠30 A
i2 i'2
𝐼𝑐 = 1519.4∠-150 A (ib-ia)
i3 i'3
At 34.5 KV side (Phase current) (ia-ic)
𝐼𝐴 = 12709.4∠-90 A
𝐼𝐵 = 12709.4∠30 A + ve seq. impedance
𝐼𝐶 = 12709.4∠-150 A
X1g X1tr
(Line current)
𝐼𝐴 − 𝐼𝐵 =22013.3 ∠-120 A Vg
𝐼𝐵 − 𝐼𝐶 =22013.3 ∠0 A
𝐼𝐶 − 𝐼𝐴 =22013.3 ∠120 A
3- Internal 3-Ph fault at star side
1
𝐼𝑓 = = −𝑗2.63 𝑝𝑢
𝑗0.08 + 𝑗0.3
𝑭𝒐𝒓 𝒔𝒕𝒂𝒓 𝒔𝒊𝒅𝒆 𝑰𝒃𝒂𝒔𝒆 = 𝟓𝟕𝟕. 𝟑𝟔 𝑨 , 𝑰𝒇𝒂𝒄𝒕 = −𝒋𝟏𝟓𝟏𝟗. 𝟒 A
For Secondary of CTs sides:
At 500 KV side
𝐼𝑎 = 1519.4∠-90 A 𝑖1′ = 𝑖2′ = 𝑖3′ = 0 𝐴
𝑖1 = 𝑖𝐶 − 𝑖𝐴 = 12.2 𝐴
𝐼𝑏 = 1519.4∠30 A
𝐼𝑐 = 1519.4∠-150 A
𝑖2 = 𝑖𝐵 − 𝑖𝐶 = 12.2 𝐴
At 34.5 KV side (Phase current)
𝐼𝐴 = 12709.4∠-90 A 𝑖3 = 𝑖𝐴 − 𝑖𝐵 = 12.2 𝐴
𝐼𝐵 = 12709.4∠30 A
𝐼𝐶 = 12709.4∠-150 A
𝑖𝑜1 = 𝑖1 − 𝑖1′ = 𝑖1 =12.2 A 𝑖𝑅1 = (𝑖1 + 𝑖1′ )/2
(Line current) 𝑖𝑜2 = 𝑖2 − 𝑖2′ = 𝑖1 =12.2 A
𝐼𝐴 − 𝐼𝐵 =22013.3 ∠-120 A
𝐼𝐵 − 𝐼𝐶 =22013.3 ∠0 A
𝑖𝑜3 = 𝑖3 − 𝑖3′ = 𝑖1 =12.2 A 𝑖𝑅1 = 𝑖𝑅2 = 𝑖𝑅3
𝐼𝐶 − 𝐼𝐴 =22013.3 ∠120 A
All Relays will trip
3- External 3-Ph fault at star side
1
𝐼𝑓 = = −𝑗2.63 𝑝𝑢
𝑗0.08 + 𝑗0.3
𝑭𝒐𝒓 𝒔𝒕𝒂𝒓 𝒔𝒊𝒅𝒆 𝑰𝒃𝒂𝒔𝒆 = 𝟓𝟕𝟕. 𝟑𝟔 𝑨 , 𝑰𝒇𝒂𝒄𝒕 = −𝒋𝟏𝟓𝟏𝟗. 𝟒 A
𝑖𝑎 = ……………. A
At 500 KV side 𝑖𝑏 = …………….A For Secondary of CTs sides:
𝐼𝑎 = 1519.4∠-90 A 𝑖𝑐 = …………….A
𝐼𝑏 = 1519.4∠30 A 𝑖𝑎 − 𝑖𝑏 = ……………. A 𝑖1 = 𝑖𝐶 − 𝑖𝐴 = 12.2 𝐴 𝑖1′ = 𝑖𝐶 − 𝑖𝐴 = 6.5 𝐴
𝐼𝑐 = 1519.4∠-150 A 𝑖𝑏 − 𝑖𝑐 = ……………. A
𝑖𝑐 − 𝑖𝑎 = …………….A 𝑖2 = 𝑖𝐵 − 𝑖𝐶 = 12.2 𝐴 𝑖2′ = 𝑖𝐵 − 𝑖𝐶 = 6.5𝐴
At 34.5 KV side (Phase current)
𝐼𝐴 = 12709.4∠-90 A 𝑖3′ = 𝑖𝐴 − 𝑖𝐵 = 6.5 𝐴
𝑖3 = 𝑖𝐴 − 𝑖𝐵 = 12.2 𝐴
𝐼𝐵 = 12709.4∠30 A
𝐼𝐶 = 12709.4∠-150 A
𝑖𝑜1 = 𝑖1 − 𝑖1′ =5.7 A 𝑖𝑅1 = (𝑖1 + 𝑖1′ )/2
(Line current)
𝐼𝐴 − 𝐼𝐵 =22013.3 ∠-120 A 𝑖𝑜2 = 𝑖2 − 𝑖2′ =5.7 A 𝑖𝑅1 = 𝑖𝑅2 = 𝑖𝑅3 = 9.35𝐴
𝐼𝐵 − 𝐼𝐶 =22013.3 ∠0 A
𝑖𝑜3 = 𝑖3 − 𝑖3′ =5.7 A
𝐼𝐶 − 𝐼𝐴 =22013.3 ∠120 A
All Relays will not trip
4- For a phase-to-phase fault (outside the zone of the differential relay) on the wye side of the transformer of
problem 3, calculate the restraining and operating currents in each of the relays. Will the relay operate for this fault?
How do the fault currents compare with the three-phase fault currents determined in problem 3?
4- External Ph-Ph fault at star side
5. For a three phase- fault (inside the zone of the differential relay) on the wye
side of the transformer of problem 3, Calculate the maximum fault resistance Rf
that make the relay will not operate for this internal fault ?
Sheet (2)
5- Assume for this problem that the 69 kV system (Figure 1) is open and make the following calculation:
Draw the differential protection on the main transformer
Select CT ratio and relay setting
Calculate the internal fault current in the three phases for a solid phase-c to-ground fault on the 69 kV terminals.
Will the relay operate or not ?
Calculate the internal fault current in the three phases for phase-a to-ground fault on the 69 kV terminals through
10 Ω. Will the relay operate or not?
For the internal phase-a to-ground fault on the 69 kV terminals through 10 Ω, Find the percentage of unprotected
winding.
Xo=36 %
Xo=24 %
Sheet (2)
1- Draw the differential protection
𝐼𝐴 − 𝐼𝐵 IA Ia
A a
𝐼𝐵 − 𝐼𝐶 IB ia
B (iA-iC) Ib b
𝐼𝐶 − 𝐼𝐴 IC
C (iB-iC) Ic ib c
ic
(iC-iB)
i2 i'2
(ib-ia)
i3 i'3
(ia-ic)
Sheet (2)
2- Select CTR and determine the relay characteristics
Full load current Full load current
𝑆 50 ∗ 1000 𝑆 50 ∗ 1000
𝐼𝑓.𝑙 = = = 2091.8 𝐴 𝐼𝑓.𝑙 = = = 418 𝐴
3𝑉 3 ∗ 13.8 3𝑉 3 ∗ 69
CTR= 750/5
𝑖1−𝑖2 4.75−4.83
CT mismatch error…. = *100 = *100 =1.6 %
5 5
∑ errors = 1.6+10=11.6 %
∴ 𝑀𝑖𝑛. 𝑆𝑙𝑜𝑝𝑒 = 15 % , 𝐼𝑜𝑚𝑖𝑛 = 0.25 𝐴
Sheet (2)
3- Internal L-G fault at star side
+ ve seq. impedance
X1g X1tr
Vg
X2g X2tr
Xog Xotr
Sheet (2)
3- Internal L-G fault at star side
PU calculation:
𝑆𝑏 = 50 𝑀𝑉𝐴 , 𝑉𝑏2 = 69 𝑘𝑉, 𝑉𝑏1
∘
= 13.8 𝑘𝑉 , 𝐼𝑏2 = 418 𝐴
1∠120 ∘
𝐼𝑓 = 3 𝐼𝑜 = 3 ∗ = 4.6∠30 𝑝𝑢
2 ∗ 𝑗0.12 + 2 ∗ 𝑗0.08 + 𝑗0.24
∘
𝐼𝑓𝑎𝑐𝑡 = 1959.3∠30 A
During internal L-G:
𝐼𝑎 = 𝐼𝑏 = 0 𝐴 , 𝐼𝑐 = 𝐼𝑓
Equivalent Circuit
Vg 𝑰𝒐
Sheet (2)
3- Internal L-G fault at star side
During internal L-G:
𝐼𝑎 = 𝐼𝑏 = 0 𝐴 , 𝐼𝑐 = 𝐼𝑓
69/√3
𝐼𝐴 = 𝐼𝐵 = 0 𝐴 , 𝐼𝐶 = 𝐼𝑓 * = 5656.2∠30 ∘ 𝐴
13.8
For Secondary of CTs sides:
∘
𝐼𝐶 − 𝐼𝐵 = 5656.2∠30 𝐴 𝑖1′ = 𝑖2′ =𝑖3′ = 0 𝐴
∘
𝐼𝐴 − 𝐼𝐶 = 5656.2 ∠150 𝐴
𝐼𝐵 − 𝐼𝐴 = 0 𝐴
𝑖1 = 12.8 𝐴
𝑖2 = 12.8 𝐴
𝑖3 = 0 𝐴
Trip
No operation
Iomin
𝒊𝟏 + 𝒊𝟐
𝑰𝑹=
𝟐
Sheet (2)
3- Calculate the internal fault current in the three phases for phase-a to-ground fault on the 69 kV terminals through 10 Ω.
Will the relay operate or not?
+ ve seq. impedance IA
𝐼𝐴 − 𝐼𝐵 Ia
X1g X1tr A a
𝐼𝐵 − 𝐼𝐶 IB ia
B (iA-iC) Ib b
Vg 𝐼𝐶 − 𝐼𝐴 IC
C (iB-iC)
Ic ib c
ic
(iC-iB)
-ve seq. impedance
(ic-ib)
io2 io1
io3
X2g X2tr i1 i'1
i2 i'2
(ib-ia)
Equivalent Circuit
X1g X1tr X2g X2tr Xotr
Vg 𝑰𝒐 3 Rf
Sheet (2)
3- Internal L-G fault at star side
During internal L-G:
𝐼𝑐 = 𝐼𝑏 = 0 𝐴 , 𝐼𝑎 = 𝐼𝑓
69/√3 ∘
𝐼𝐶 = 𝐼𝐵 = 0 𝐴 , 𝐼𝐴 = 𝐼𝑓 * = 5084.2∠ − 64 𝐴
13.8
For Secondary of CTs sides:
Trip
No operation
Iomin
𝒊𝟏 + 𝒊𝟐
𝑰𝑹=
𝟐