Emcp 2+ Password Entry OP3
Emcp 2+ Password Entry OP3
Shutdown SIS
Previous Screen
Systems Operation
Electronic Modular Control Panel II+ (EMCP II+)
Media Number -RENR2484-05 Publication Date -01/04/2002 Date Updated -19/04/2002
i00828416
OP3 is the option for entering the password that is required for accessing OP4 through OP11. Options for the
service modes OP4 through OP11 are protected with passwords. The passwords reduce the possibility of
mistakenly altering information. Options OP1 and OP2 are used to view information. OP1 and OP2 are not
protected with passwords.
The "SCROLL" keys must be actuated in the correct sequence in order to gain access to OP4 through OP11.
The password is identical for every GSC+. The password cannot be changed. After the password is entered,
the OP4 through OP10 options can be accessed. If a mistake is made during the entry of the password, "PE
FAIL" is briefly shown on the upper display. The operator can restart the process of entering the password
by pressing the "SELECT" key.
Note: Service mode cannot be entered when the ECS is in the "AUTO" position.
Note: Any active shutdown fault must be made inactive in order to access Service Mode. A shutdown fault
is active if the shutdown indicator for the fault is FLASHING. To temporarily change a shutdown fault from
an active shutdown fault to an inactive shutdown fault, turn the ECS to the OFF/RESET position. To
permanently change a shutdown fault from an active shutdown fault to an inactive shutdown fault, the fault
must not be occurring. Also, the ECS must be turned to the OFF/RESET position. If the jumper from
terminal 6 to terminal 9 is not installed on the ECS, the GSC+ will not power up in OFF/RESET and any
active shutdown fault must be corrected before entering Service Mode.
1. Press "Service Mode" key in order to enter service mode. "OP1" is showing on the lower display. See
Systems Operation, "Service Mode " for more information.
3. Press the "SELECT" key. "P E _ _ _ _ _" is showing on the display. The first dash is flashing.
4. Press "SCROLL RIGHT" key. "P E 1 _ _ _ _" is showing on the display. The second dash is flashing.
5. Press "SCROLL DOWN"key. "P E 1 3 _ _ _" is showing on the display. The third dash is flashing.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 2/7/2009
Media Search - RENR2484 - Electronic Modular Control Panel II+ (EMCP II+) Page 2 of 2
6. Press "SCROLL UP" key. "P E 1 3 2 _ _"is showing on the display. The fourth dash is flashing.
7. Press "SCROLL DOWN" key. "P E 1 3 2 3 _" is showing on the display. The fifth dash is flashing.
Note: Once the password is entered, any option can be accessed. The password remains activated until
Service Mode is exited.
Copyright 1993 - 2009 Caterpillar Inc. Sat Feb 7 09:35:37 UTC+0300 2009
All Rights Reserved.
Private Network For SIS Licensees.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/... 2/7/2009