elmetec ELMETEC (Pvt) Limited.

19-KM, Ferozepur Road, Lahore.


WD#
Transformer Technical Specification and Data Sheet
Customer: Ercon Industries Pvt. Ltd. lnquiry Ref. & Date : Q-113-0424
SPECIFICATION
Rated Output KVA 3000 Step Down
Phases No. 3/3
Frequency Hz. 50
Primary Voltage KV 11
Secondary Voltage KV 0.415
Primary Current A 78.73
Secondary Current A 4173.62
Tappings on HV side % ±2.5, ±5, -7.5
Connection Vector group Dyn-11
Insulation Class A
Ambient Temp. °C 45
Temperature rise Oil / Winding °C 50/60
Type of Cooling ONAN
Typr of Tank Tubular with Conservator
Terminals HV/LV No. 3/4 On Top Cover
Neutral bought out Yes On L.V Side
Basic insulation Level (BIL) system/ Power Freq. /LI 12/28/75 kv
PERFORMANCE
Copper Losses (Load Losses) Watts 29000
Iron Losses (No Load Losses) Watts 2900
Impedance Voltage at rated Current. % 7.00
Regulation at 100% Load and unity P.F. % 1.34
Regulation at 100% Load and 0.8 P.F. % 4.46
Efficiency at Unity P.F.and 100% Load. % 98.73 -
Efficiency at 0.8 P.F.and 100% Load. % 98.42
Efficiency at Unity P.F.and 75% Load. % 98.98
Efficiency at 0.8 P.F.and 75% Load. % 98.73
Efficiency at Unity P.F.and 50% Load. % 99.19
Efficiency at 0.8 P.F.and 50% Load. % 98.99
Price Includes
1)Filling of Transformer Oil according to standard IEC-60296.
2) Transformer tank, inner & outer side, cooling tubes and core clamping channels are painted with primer plus anti-Oxidant paint.
3) Core material used is Prime quality Silicon Steel Sheet of grade M-4
Components and Accessories are as follows.
Oil level gauge. Earthing Terminals
Oil filling hole with cap. 3 Sets of Arcing Horns
3 H.V. bushings. Bi Directional Roller Wheels
4 L.V. bushings. Oil Conservator
Off load tap changer. Double Float Buchholz Relay
Oil drain valve Dial Type Thermometer with alarm and trip contacts
Rating & Diagram plate Marshalling Box
Lifting Lugs Pressure Relief Device without contacts