WD# Transformer Technical Specification and Data Sheet Customer: Ercon Industries Pvt. Ltd. lnquiry Ref. & Date : Q-113-0424 SPECIFICATION Rated Output KVA 3000 Step Down Phases No. 3/3 Frequency Hz. 50 Primary Voltage KV 11 Secondary Voltage KV 0.415 Primary Current A 78.73 Secondary Current A 4173.62 Tappings on HV side % ±2.5, ±5, -7.5 Connection Vector group Dyn-11 Insulation Class A Ambient Temp. °C 45 Temperature rise Oil / Winding °C 50/60 Type of Cooling ONAN Typr of Tank Tubular with Conservator Terminals HV/LV No. 3/4 On Top Cover Neutral bought out Yes On L.V Side Basic insulation Level (BIL) system/ Power Freq. /LI 12/28/75 kv PERFORMANCE Copper Losses (Load Losses) Watts 29000 Iron Losses (No Load Losses) Watts 2900 Impedance Voltage at rated Current. % 7.00 Regulation at 100% Load and unity P.F. % 1.34 Regulation at 100% Load and 0.8 P.F. % 4.46 Efficiency at Unity P.F.and 100% Load. % 98.73 - Efficiency at 0.8 P.F.and 100% Load. % 98.42 Efficiency at Unity P.F.and 75% Load. % 98.98 Efficiency at 0.8 P.F.and 75% Load. % 98.73 Efficiency at Unity P.F.and 50% Load. % 99.19 Efficiency at 0.8 P.F.and 50% Load. % 98.99 Price Includes 1)Filling of Transformer Oil according to standard IEC-60296. 2) Transformer tank, inner & outer side, cooling tubes and core clamping channels are painted with primer plus anti-Oxidant paint. 3) Core material used is Prime quality Silicon Steel Sheet of grade M-4 Components and Accessories are as follows. Oil level gauge. Earthing Terminals Oil filling hole with cap. 3 Sets of Arcing Horns 3 H.V. bushings. Bi Directional Roller Wheels 4 L.V. bushings. Oil Conservator Off load tap changer. Double Float Buchholz Relay Oil drain valve Dial Type Thermometer with alarm and trip contacts Rating & Diagram plate Marshalling Box Lifting Lugs Pressure Relief Device without contacts