NOTES:

1. THIS DRAWING IS FOR ELECTRIC LAYOUT ONLY.DIMENSIONS OF ROOM,TOILETS ETC.


SHOULD BE CROSS CHECKED FROM WORKING DRAWING BEFORE EXECUTION.
2. HEIGHTS AS MENTIONED ALONG WITH EACH FIXTURES ARE FROM FINISHED FLOOR LEVEL
TO THE BOX BOTTOM.
3. FAN BOXES AND OTHER CEILING POINTS MUST BE PLACED AS PER EXACT GEOMETRIC
CENTER AND DIMENSIONS AVAILABLE AT SITE.
4. ALL THE CONDUIT SIZES ARE 25MM UNLESS MENTIONED OTHERWISE.
5. EACH TELEPHONE POINT SHOULD BE WIRED WITH SEPARATE 0.51MM 4 PAIR TEL. WIRE FROM
TEL. JT. BOX.
6. EVERY TV POINT SHALL BE WIRED WITH 2 NOS. RG-6 COAXIAL SHIELDED CABLE FROM TV
JOINT BOX TO POINT.
7. CONDUITS FOR TELEPHONE AND TV WIRING SHALL PREFERABLY BE LAID IN FLOOR.
8. WIRING SHOULD BE DONE WITH PVC INSULATED COPPER FLEXIBLE WIRE IS:694 MARKED AS
PER THE FOLLOWING SCHEDULE:
A) POINT WIRING- 1.0SQMM RED[PHASE] , BLACK[NEUTRAL] , 0.75SQMM GREEN[EARTH]
B) CIRCUIT WIRING- 2.5SQMM BLUE[PHASE] , BLACK[NEUTRAL] , 1.5SQMM GREEN[EARTH]
C) AC WIRING- 6.0SQMM BLUE[PHASE] , BLACK[NEUTRAL] , 4.0SQMM GREEN[EARTH]
9. EACH CONDUIT FROM MCB DB TO SB SHALL CARRY UPTO 3 NO.S 2.5SQMM CIRCUITS AND
UPTO 2NOS. CIRCUITS OF 4.0SQMM.
10. MINIMUM DISTANCE BETWEEN BARE CONDUCTORS OF 230 VOLTS AC SUPPLY AND TV/
TELEPHONE/LAN CABLES SHOULD BE 1.0 MTR. AND IN NO CASE THESE WIRES SHOULD RUN IN
SAME CONDUIT OR BOX.
11. LAYOUT OF GEYSER, WATER PURIFIER , WASHING MACHINE , MIRROR LIGHT POINTS IS
DEPENDENT UPON SANITARY LAYOUT AND MUST BR CROSS CHECKED BEFORE EXECUTION.
12. ALL THE GEYSERS SHALL BE INSTALLED ON THE WALL WITH 16A SOCKET NEAR THE
GEYSER AND 16A SWITCH ON THE MAIN SWITCH BOARD.
13. FOR THE AC/COOLER POINTS 25A SOCKET WILL BE OUTSIDE WITH 25 A STARTER ON THE
INSIDE.

LEGENDS:
1'-9"

1'-9"

1'-9"

1'-9"

1'-9"

1'-9"
6'-93 " 5'-03 " 5'-03" 6'-93 "
1'-3" 4 4 4 4 1'-3"

1'-341" 1'-121" MOUNTING HEIGHT NO ID SYMBOL DESCRIPTION


6"
CONTROL WIRING FOR
Ht. 42"

IN CONDUIT WIRE LIGHT POINT


7'-63 "
6'-934 " 4
CONTROL WIRING FOR

4'-63 "

4'-6 "
4

3
4
IN CONDUIT WIRE LIGHT POINT

2'-7 "
1
2
3'
521" 5'-034 " 5'-034 " CONTROL WIRING FOR
IN CONDUIT WIRE GY
GEYSER
CONTROL WIRING FOR
1'-3"
IN CONDUIT WIRE FAN

4'-7 "
1
2
1'-3"

3'-54 "
CONTROL WIRING FOR

3
3
7'-64 " IN CONDUIT WIRE
2'-10 "
3
4

6'-934 "
AC
CONTROL WIRING FOR

2'-8 1"
4
IN CONDUIT WIRE BZ

4'-6"
3 BELL PUSH
5'-04 "

5'-7 1"
2
CEILING 4 FAN 48" CEILING FAN 48"

6'-24"
1
9"

6"
Ht. 42"

CEILING 6 FAN 30" CEILING FAN 30"

1'-3"

1'-3"
4 "

4 "
1

1
2

2
1'-3"
1'-3" 1'-3"
3" 3'-1 1"
2
+7'6" 10 WP WALL POINT

2'-4 1"

2'-4 1"
2

2
3
6'-94 "

1'-33 "
4
1'-3" 3
6'-934 " 4'-24"

Conduits for all


Conduits for all
4 flats above
+90" 0 TL 1X40W TUBE LIGHT

1'-3"

1'-3"

4'-2 1"
3'-11"

4
4 flats above
1'-3" 1'-9"
1'-3" 1'-3" WALL BRACKETS AS
+90" 4 BULB
5'-03"
4

1'-3"

1'-3"
DESIGN LIGHT
Ht. 42"
Ht. 42"
WALL BRACKETS AS
6" +90" 0 GL GANESH LIGHT

2'
934 "
32"

4'-9"
1
1
3'-84 " 1'-3" CEILING 78 CFL CFL CEILING LIGHTS

6"
Ht. 42"

2'
3'-034 "

2'-92 "
1
26 SB
4'-11 "

+42" SWITCH BOARD

4'-10"
1
2

2'

1'-3" Conduits for all 3 1X11 W CFL


1
4'-10 2" 4 flats above 1'-3" 1'-64 " +78" 0 ML
Ht. 42"

3 MIRROR LIGHT

3'-84"
3
4'-34 "
3'-3 "

UP
1
2

6"

6"
934 " VENTILATOR MT. 0 CEILING ROSE

5'-93 "
4
Ht. 18"

7'-8 "
1
4
9" DIA FRESH AIR
VENTILATOR MT. EXF
6'-94 "

0
3

3
41"
3'

2'-9 "
4 2 FAN
1'-3"

+24" TEL

Ht. 42"
TELEPHONE POINT

2'-04 "
2

1
1' 2'-14"
1

6"
2'-541"
4'-2 1"

4'-24 "
1
4

+27" EXF
4 1"

0 TV COAXIAL POINT
2

2'-4"
2'-5 1"

4'-102"
4

1'-10 1" 1
42 "
Ht. 42"

2 2'-3"
1'-3"
+24" 12 LP 6A PLUG POINT
6"

2'-334 "
6'-12"

6A PLUG POINT FOR


1
1'-22 "
1

5"
+27" 4 LP.AC AC
Ht. 42"

1 6A PLUG POINT FOR


1 4'-10 1"
2'-114 " 1'-3" +24" 0 LP.TEL
6"

1'-11 "
4 2 TELEPHONE
1'-10 1"

1'-104 "
2'-921"
2

3
2'-1 1"

2'-1 "

6A PLUG POINT FOR


1
2

2'-10 21" 2'-1021"


+72" 0 LP.B BED SIDE
2'-33 " 3 6A PLUG POINT FOR
2'-12"

2'-1 1"
1

2'-3 "
64 "

LP.CH
3

1'-3" 4 4
0 CHIMNEY
1'-6 "

1'-621"
1
2

1'-6"

6A PLUG POINT FOR


+42" 0 LP.MIX MIXER
6A PLUG POINT FOR
+78" 0 LP.G GEYSER
6A PLUG POINT FOR
+54" 0 LP.F FRIDGE
6A PLUG POINT FOR
+78" 0 LP.WP WATER PURIFIER
6A PLUG POINT FOR
+48" 0 LP.WM WASHING MACHINE

+42" 0 BP BELL PUSH SWITCH

6" Sleves for +90" 0 BZ BUZZER POINT


Plumbing
+24" 4 AC AC STARTER
Conduits for all MCB DISTRIBUTION
+60" 1 MCB
4 flats above BOARD
SWITCH BOARD/LIGHT
0 SB1/C1
CIRCUIT
LEGENDS: POWER CIRCUIT
Mounting
Height
No. ID Symbol Description 0 P1
NUMBER
Rigid PVC Conduit 25mm/1.0
IN RCC SLAB
sqmm wire for Light points AC CIRCUIT NO.
IN RCC SLAB Rigid PVC Conduit 25mm/2.5 0 ACP1

sqmm wire for Light Circuits


Rigid PVC Conduit25mm/4.00 E EMERGENCY LIGHT
IN RCC SLAB
sqmm wire for POWER Circuits POINT
Submain wire to DB from Main

STILT FLOOR ELECTRICAL PLAN IN RCC SLAB Panel on Ground Floor in 2 nos.
25 mm dia conduits
IM MODULE NO.

NOTES:
1. THIS DRAWING IS FOR ELECTRIC LAYOUT ONLY.DIMENSIONS OF ROOM,TOILETS ETC.
SHOULD BE CROSS CHECKED FROM WORKING DRAWING BEFORE EXECUTION.
2. HEIGHTS AS MENTIONED ALONG WITH EACH FIXTURES ARE FROM FINISHED FLOOR LEVEL
TO THE BOX BOTTOM.
3. FAN BOXES AND OTHER CEILING POINTS MUST BE PLACED AS PER EXACT GEOMETRIC
CENTER AND DIMENSIONS AVAILABLE AT SITE.
4. ALL THE CONDUIT SIZES ARE 25MM UNLESS MENTIONED OTHERWISE.
5. EACH TELEPHONE POINT SHOULD BE WIRED WITH SEPARATE 0.51MM 4 PAIR TEL. WIRE FROM
TEL. JT. BOX.
6. EVERY TV POINT SHALL BE WIRED WITH 2 NOS. RG-6 COAXIAL SHIELDED CABLE FROM TV
JOINT BOX TO POINT.
7. CONDUITS FOR TELEPHONE AND TV WIRING SHALL PREFERABLY BE LAID IN FLOOR.
8. WIRING SHOULD BE DONE WITH PVC INSULATED COPPER FLEXIBLE WIRE IS:694 MARKED AS
PER THE FOLLOWING SCHEDULE:
A) POINT WIRING- 1.0SQMM RED[PHASE] , BLACK[NEUTRAL] , 0.75SQMM GREEN[EARTH]
B) CIRCUIT WIRING- 2.5SQMM BLUE[PHASE] , BLACK[NEUTRAL] , 1.5SQMM GREEN[EARTH]
C) AC WIRING- 6.0SQMM BLUE[PHASE] , BLACK[NEUTRAL] , 4.0SQMM GREEN[EARTH]
Ht = 84" Ht = 84"
9. EACH CONDUIT FROM MCB DB TO SB SHALL CARRY UPTO 3 NO.S 2.5SQMM CIRCUITS AND
Ht = 21" Ht = 21" Ht = 21" Ht = 21"
UPTO 2NOS. CIRCUITS OF 4.0SQMM.
A/C Otudoor

2'-9" 2'-9" 2'-9" 2'-9"

10. MINIMUM DISTANCE BETWEEN BARE CONDUCTORS OF 230 VOLTS AC SUPPLY AND TV/
1'-9"

1'-9"

1'-9"

1'-9"

7' 7'
3 3 7' 7'
3'-12 "

3'-1 1"

1'-11 " 1'-11 "


1

2'-2" 4 4 2'-2"
TELEPHONE/LAN CABLES SHOULD BE 1.0 MTR. AND IN NO CASE THESE WIRES SHOULD RUN IN
4'-9"
5'-1 1"
2

2'-6"
1 1'-1 1"
2'-6" SAME CONDUIT OR BOX.
1'-34" 2'-3" 2'-3"
2
11. LAYOUT OF GEYSER, WATER PURIFIER , WASHING MACHINE , MIRROR LIGHT POINTS IS
1'-6"

1'-6"

6" 6"
6" 1 6"
6'-11 3"
Ht = 84" Ht = 84"
6'-7 "
Ht = 84"
Ht = 42"
1
6'-72"
Ht = 42"
8 1"
A/C Otudoor A/C Otudoor
81"
Ht = 42" 2 4
Ht = 42"
Ht = 84"
DEPENDENT UPON SANITARY LAYOUT AND MUST BR CROSS CHECKED BEFORE EXECUTION.
10 "

103 "

7' 4 4
3
4

4
Ht = 84"

Ht = 84"
1'

1'

1' 1'
Ht = 42"

12. ALL THE GEYSERS SHALL BE INSTALLED ON THE WALL WITH 16A SOCKET NEAR THE
3'-2 "
1
4

GEYSER AND 16A SWITCH ON THE MAIN SWITCH BOARD.


2'-54 "

2'-54 "
1

1
4'-4 "

4'-4 2"

4'-9"
1

1
2

13. FOR THE AC/COOLER POINTS 25A SOCKET WILL BE OUTSIDE WITH 25 A STARTER ON THE
1'-8"

1'-8"
Ht = 84"

Ht = 84"
Ht = 84"

Ht = 84"
5'-1 1"
2

2'-6" 2'-6"
A/C

A/C

1 INSIDE.
2'-3"

2'-7 " 3
521"
3 3 2 4'-9 "
1 4'-11 " 4'-11 " 4
4 4
3'-2 4"

3'-2 4"
1

3 2'-7 " 6"


4'-9 " 2
Ht = 42"

Ht = 42"

4
Ht = 42"

Ht = 42"
Ht = 84"

4'-6" Ht = 21" 4'-6"


Point For

Point For

Ht = 42"1 Ht = 84" Ht = 21"


Chimney

Chimney

LEGENDS:
6" 2'-7 "
6"

6"

2 A/C Ht = 84" 9"


3
6"

6"

Ht = 21"
Ht = 84"
6"
Ht = 84" Ht = 21" Ht1= 42" 4'-9 "
4
9" 2'-7 "
A/C 2
3 Ht = 84"
4'-9 "
4
4'-7 "
1
2
4'-7 "
1
2

2'-6"
5'-3" 5'-3"
MOUNTING HEIGHT NO ID SYMBOL DESCRIPTION
Ht = 84" Ht = 21" Ht = 21" Ht = 84"
7' 7'
6' A/C 1'-3" 1'-3" A/C 6'
2'-6"

1
CONTROL WIRING FOR
Ht = 84" Ht = 84"
6'-7 "
7' 2

A/C Otudoor
2'-6"
Ht = 84"
A/C Otudoor
IN CONDUIT WIRE LIGHT POINT
Ht = 84" 1'
4'-7 "

Ht = 84"
1
2

2'-6"
5'-9"

5'-9"

3
5'-4 "

5'-4 "
1

1'
CONTROL WIRING FOR
2

5'-64 "
2'-9 "
3
4
4'-7 "

WIRE
1
2

3 IN CONDUIT
2'-9 3"

LIGHT POINT
4

5'-6 4 " 3'


6"
Ht = 42"

2'-6"
Ht = 21"
6"

3' Ht = 42" Ht = 84" Ht = 21" Ht = 42"


Ht = 84"

1 3 3 1 6"
CONTROL WIRING FOR
Ht = 42"

2'-6" 6" 5'-2 " 4'-11 " 4'-11 " 5'-2 "
4 4 4 4 1 A/C

WIRE
6"

5'-4 "
Ht = 42"
6"
1'-6"
Ht = 21"
Ht = 21" Ht = 84"

Ht = 21"
Ht = 42"
1'-6"
2
3'-7"
IN CONDUIT GY
GEYSER
5'-4 1" 4'-6"
2'-10 "

2'-10 "
1

1
2

2
4'-6" Ht = 42"
6"
A/C Otudoor CONTROL WIRING FOR
1'-5"
IN CONDUIT WIRE
Ht = 84"
5'-4 "

5'-4 "
1

1
Ht = 84"

6" FAN
Ht = 84"

3
3 2'-34 "
2'-6"

6'-9 "
2'-10 "
1

CONTROL WIRING FOR


2

4
2'-10 "
1

WIRE
2

3'-5"
IN CONDUIT
2'-9"

2'-9"

3'-5" 6"
3
2'-3 "
4
6' 6"
Ht = 96" Ht = 96" Ht = 42" Ht = 21"
AC
Ht = 21" Ht = 42" 1'
4'-10 "

Ht = 84"
4'-10 "

CONTROL WIRING FOR


2
1
2
4'-7 2"
1

1'-6"
WIRE
Ht = 84"
1
IN CONDUIT
Ht = 84"

2'-10 "
1'

2 BZ
BELL PUSH
3'

1
6'-1 "
4
5'-3"

A/C Otudoor 2'-3" 1 9"


3'-8 " 3'-3"
Ht = 96"

Ht = 84" 4
6"
1
8'-4 "
2
Ht = 84"
CEILING 4 FAN 48" CEILING FAN 48"
2'-4 "

Ht = 21" Ht = 21"
1
2

Ht = 84"
4'-6" A/C
2'-9 "
3
4

5'
A/C Ht = 21"
2'-3 4"
3

2'-6"

Ht = 84"
Ht = 42"

Ht = 42" Ht = 84" Ht = 42" Ht = 21" Ht = 42"


1'
Ht = 84"

6" 6" 6"


FAN 30" CEILING FAN 30"
Point For
Chimney

1
3'-1 "
2 3' 3
3'-2 " CEILING 6
6"

4
Ht = 21"
Ht = 42"
Ht = 90" 6"
2'-8 "

2'-9"
1
4

1'-6 "
3
4

1'-6"

+7'6" 10 WP WALL POINT


3'-1 "

Ht = 96"
1
4

1
3'-1 "
2
3'-10 "
1
2

5'-4 "
1
2

1 1 6"
1 3'-84 " 3'-8 4"
4'-10 " Ht = 42" A/C Otudoor
2
2'-8 "
1
4

6"
1'-5"
+90" 0 TL 1X40W TUBE LIGHT
Ht = 84"

Ht = 42"
6"

5'
1
3'-1 "
1'-9"

2
1
Ht = 42" Ht = 84"

3'-11 " 1
2 3'-0 "
2
WALL BRACKETS AS
4'-8 "
1
4

+90" 4 BULB
6"

Ht = 42"
2'-8 "
1
4

1'

DESIGN LIGHT
Ht = 90"

3'-6" 9"
6"

5'-3"
1'-1 3"
4

6'-9"

9"
Ht = 84"
6"
1
Ht = 90" WALL BRACKETS AS
+90" GL
Ht = 21"
3'-1 "
Ht = 84" 4
0 GANESH LIGHT
3'-7 "
1
2

1 1
2'-11 " 4'-4"
Ht = 21" 1'-11 "
4 4
9" 9"
1'

6"
CEILING 78 CFL CFL CEILING LIGHTS
4'-6"

1 Ht = 90" Ht = 90" Ht = 42" Ht = 90"


Ht = 42"
6"

1'-5 4" 6"


2'-3 4"
2'-5 "

3
1
4

A/C 1'-3" 1
Ht = 21" 3'-7 "
1'-9 1"
Ht = 84"
6'-1 "

1
1

2
2
Ht = 42"

A/C Otudoor 2'-11 " 2


4 Ht = 84"
Ht = 84"

2'-1 1"

A/C
4
6"

Ht = 84"

26 SB
1'

Ht = 42"
Ht = 84"
+42" SWITCH BOARD
Ht = 84" Ht = 84"
3 6"
6"

Ht = 21"
Ht = 21"

2'-3 "
A/C
Ht = 84" 4 Ht = 21"
1'-6"

1 6"
1'-5 "
Ht = 42"
Ht = 21"

6"

2
1
Ht = 84"
2'-6 4"
1

4'-10 "
1X11 W CFL
1'-3"

2
Ht = 84"

1 1
+78" 0 ML
2'-9 3 "

3'-8 " 3'-8 "


4

4 4
2'-3 3"
MIRROR LIGHT
5'-9 "

4
1
4

1'-3 "
1
2

Ht = 84"
Ht = 84"

Ht = 84"
2'-8"
Ht = 42"
6"

4'-2 "

4'-3"
1
4

1
4'-8 4"
1
VENTILATOR MT. 0 CEILING ROSE
Ht = 21"

5'-4 "
2
2'-7 "
1
4
3'-6"
Ht = 84"

6"
1
Ht = 21"

5'-1 "
Ht = 21" 4'-8 4"

2
1

6" A/C Otudoor


6"
VENTILATOR MT. 9" DIA FRESH AIR
0 EXF
1'-4 "
1
2

6'-2 "
1

1
2

2'-4 "
2
FAN
4'-9"
Ht = 84"

2'-1 4"

6'-1 1"

9"
1

Ht = 21"

Ht = 84"
1'
Ht = 90"

A/C
2'-3 3"
4
Ht = 42" A/C Otudoor
6"
+24" TEL
5'-8"

2 TELEPHONE POINT
6"
Ht = 21"

3'-3" 9"
Ht = 84"

2'-3"
2'-7"

2'-6"

10 "
1
2

Ht = 21" Ht = 21"
Ht = 90"
1'

1
4'-7 "
6'-4 "
1
2

4
6"
+27" 0 EXF TV COAXIAL POINT
5'-6"

64 "

1'-11 4"
1
4'-2 4"

3
1

1
3'-9" 1'-3 "
4
Ht = 42"
6"

Ht = 84" Ht = 84"
+24" 12 LP 6A PLUG POINT
A/C Otudoor

2'-3"
1'-1 1"
2

6A PLUG POINT FOR


+27" 4 LP.AC AC
6A PLUG POINT FOR
+24" 0 LP.TEL TELEPHONE
6A PLUG POINT FOR
+72" 0 LP.B BED SIDE
6A PLUG POINT FOR
0 LP.CH CHIMNEY
6A PLUG POINT FOR
+42" 0 LP.MIX MIXER
6A PLUG POINT FOR
+78" 0 LP.G GEYSER
6A PLUG POINT FOR
+54" 0 LP.F FRIDGE
6A PLUG POINT FOR
+78" 0 LP.WP WATER PURIFIER
6A PLUG POINT FOR
+48" 0 LP.WM WASHING MACHINE

+42" 0 BP BELL PUSH SWITCH

6" Sleves for +90" 0 BZ BUZZER POINT


Plumbing
+24" 4 AC AC STARTER
Conduits for all MCB DISTRIBUTION
+60" 1 MCB
4 flats above BOARD
SWITCH BOARD/LIGHT
0 SB1/C1
CIRCUIT
LEGENDS: POWER CIRCUIT
Mounting
Height
No. ID Symbol Description 0 P1
NUMBER
Rigid PVC Conduit 25mm/1.0
IN RCC SLAB
sqmm wire for Light points AC CIRCUIT NO.
IN RCC SLAB Rigid PVC Conduit 25mm/2.5 0 ACP1

sqmm wire for Light Circuits


Rigid PVC Conduit25mm/4.00 E EMERGENCY LIGHT
IN RCC SLAB
sqmm wire for POWER Circuits POINT
Submain wire to DB from Main

TYPICAL FLOOR ELECTRICAL PLAN IN RCC SLAB Panel on Ground Floor in 2 nos.
25 mm dia conduits
IM MODULE NO.