View Whole Thesis
View Whole Thesis
View Whole Thesis
1
ERRATA
STEEL PILES
By
Abolghasem Nezamian
B.Sc(Hons), CPEng, MIIStructE, MIISeismicE
!-•••
Monash University
August 2003
11
STATEMENT OF ORIGINALITY
This thesis contains no material, which has been accepted for the award of any
Degree or Diploma in any university. To the best my knowledge and belief the
thesis contains no material previously published or written by another person
except where due to reference is made in the text.
Abolghasem Nezamian
August 2003
m
Ill
SUMMARY
Pull-out and push out test results are presented and discussed. Test results are
i
examined against the current code provisions and recommendations.
Mathematical expressions are adopted to calculate the bond strength of concrete
plugs in steel tubular piles. The failure mechanisms and models are discussed.
Experimental tests on fifteen concrete plug specimens subjected to cyclic loading
reported. The purpose of these tests was to investigate the behavior of the
concrete plug in the steel tube under repeated loading
The ultimate capacity and load slip response of specimens under cyclic loading
can be reasonably approximated from the static ultimate strength and load slip of
l.'i '•
IS
the specimen by reducing the ultimate strength values of the static test by a cyclic
reduction factor. The cyclic reduction factor is defined as the factor by which the
cyclic strength of the specimen may be obtained from the static strength for a
given displacement. Based upon the test results from the cyclic tests, an average
cyclic reduction was obtained.
['•••
IV
A non linear finite element solution scheme with axi-symmetric elements was
developed. It included a time dependant shrinkage model based on European
Code MCI990, and a linear tension-softening model for concrete and Coulomb
friction model for the interface. The model is used to predict the ultimate strength,
load-slip response and longitudinal and hoop strains along the outer surface of the
steel tube. The numerical values agreed well with the measured values from the
tests. This tool is suitable for the investigation of parameter variations on the
ultimate strength of a concrete plug in a steel tube specimen subjected to a static
pull-out and push-out force.
(!•:•
ACKNOWLEDGEMENTS
Dr. Riadh Al-Mahaidi first suggested that I undertake an investigation into the
behavior of concrete plugs embedded in tubular steel piles, and through the
project he has provided great support and guidance. I wish also to thank Professor
Paul Grundy for his guidance and support through the project.
The experimental testing required extensive support from the staff of the Monash
University Department of Civil Engineering. Chris Powel, Roger Doulis, Max
Graham, Jeff Doddrel and Alan Taylor all helped to achieve a successful outcome
for the testing program. I extend thanks to the staff of the structure group and
main office in the Department of Civil Engineering for their support,
encouragement and useful discussion.
Finally thanks to my family and my partner Leyla for their strong support ana
encouragement in this endeavor.
Table of content VI
CONTENTS
1 INTODUCTION
1.1 General 1.1
1.2 Background 1.2
1.2.1 Behavior under push out loading 1.3
1.2.2 Behavior under pull out loading 1.4
1.2.3 Cyclic loading 1.5
1.3 Report Organization 1.5
2 LITERATURE REVIEW
2.1 Introduction 2.1
2.2 Composite Columns 2.1
2.3 Bond Strength of Concrete Filled Steel Tube 2.4
2.4 The Influence of Shape, Aspect Ratio of the Steel Tube and Length to
Depth of Concrete Plug 2.7
2.5 The Influence of Surface Roughness and Imperfection of the Steel
Tube 2.10
2.6 The Influence of the Concrete Strength, Age and Shrinkage 2.12
2.7 Confinement Effects on Concrete 2.13
I
II 2.8 Cyclic Loading Effects 2.17
2.9 Nonlinear Finite Element Analysis 2.19
2.9.1 Concrete material model 2.22
2.9.2 Steel tube material model 2.27
2.9.3 The interface model 2.27
2.10 Current Codes Provisions and Recomniendations on Bond Strength
Value 2.29
2.10.1 Bond strength recommendation for pile sleeve connections
2.31
2.11 Objective of This Research 2.34
Table of content Vil
Jh.
Table of content
R REFERENCES
A6 LIST OF PUBLICATION
4
A
J
i
A
t
'••". . 1
•' 1
Table of content Xll
LIST OF FIGURES
Figure 1.1 A typical connection between steel pile and concrete pile cap 1.2
Figure 1.2 Bond strength mechanisms in push out 1.4
Figure 1.3 Bond strength mechanisms in pull-out 1.5
Figure 2.1 Uniaxial Stress-Strain Curves for Concrete 2.22
Figure 2.2 The Concrete Material Model 2.23
Figure 2.3 Description of interface bond element 2.29
Figure 2.4. Roeder's (1999) proposed bond stress evaluation models 2.30
Figure 3.1 A typical pull-out test specimen 3.3
Figure 3.2 Pull-out test arrangement 3.4
Figure 3.3 Bond strength mechanisms in pull-out tests 3.7
Figure 3.4 Load - Slip relationship of specimens S250 3.9
Figure 3.5 Load - Slip relationship of specimens S500 3.9
Figure 3.6 Load - Slip relationship of specimens S750 3.10
Figure 3.7 A close up of load - slip relationship of specimens S250 3.10
Figure 3.8 Arrangement of strain gauges 3.11
Figure 3.9 Measured load - longitudinal strains for specimens S250-1 3.13
Figure 3.10 Measured load - longitudinal strains for specimens S250-2 3.14
Figure 3.11 Measured load - longitudinal strains for specimens S500-1 3.14
Figure 3.12 Pulled out r^icrete plug 3.18
Figure 3.13 Failure of the concrete plug in the pull-out test 3.19
Figure 3.14 A typical push-out test specimen 3.21
Figure 3.15 Push-out test arrangement 3.22
Figure 3.16 Bond strength mechanisms in push-out tests 3.25
Figure 3.17 Load - slip relationship of specimens S1000 3.27
Figure 3.18 Load - slip relationship of specimens S750 3.28
Figure 3.19 Load - slip relationship of specimens S500 3.28
Figure 3.20 A close up of load - slip relationship of specimens S1000 3.29
Figure 3.21 A close up of load - slip relationship of specimens S750 3.29
Figure 3.22 A close up of load - slip relationship of specimens S500 3.30
/ JL,
Table of content Xlll
Figure 4.1 A typical test specimen for the cyclic test 4.6
Figure 4.2 Cyclic loading test arrangements 4.8
Figure 4.3 Support Stand 4.8
Figure 4.4 Placement of a specimen into the test rig 4.9
Figure 4.5 Specimen bolted on head plate of the support stand 4.9
Figure 4.6 Support stand bolted to the strong floor 4.10
Figure 4.7 A typical load versus time function for Stage 1 4.13
Figure 4.8 A typical load versus time function for Stage 2 4.18
Figure 4.9 Slip measurement at the bottom of concrete plug 4.20
Figure 4.10 Slip measurement at the top of concrete plug 4.20
Figure 4.11 A typical data acquisition set up 4.21
Figure 4.12 Data taker box 4.21
Figure 4.13 Wired strain gauges 4.22
Figure 5.1 Load-slip responses for specimens S1.0D 5.7
Figure 5.2 Load-slip responses for specimens S 1.5D 5.8
Figure 5.3 Slip versus cycles for specimens SI.OD-2 5.9
Figure 5.4 Slip versus cycles for specimens SI.OD-2 5.10
Figure 5.5 Slip versus cycles for specimens SI.5D-2 5.10
Figure 5.6 Slip versus cycles for specimens S1.5D-3 5.11
Figure 5.7 Load range versus rate of slip growth (Stage 1) 5.13
Figure 5.8 Hysteric load-slip behavior for specimens S1 .OD-2 5.14
Figure 5.9 Hysteric load-slip behavior for specimens S1 .OD-2 5.15
Figure 5.10 Hysteric load-slip behavior for specimens S1.5D-2 5.16
Figure 5.11 Hysteric load-slip behavior for specimens S1.5D-2 5.16
Figure 5.12 Load-slip behavior of specimen S1.0D-3, first cycle at ±250 kN 5.18
Figure 5.13 Load-slip behavior of specimen S1.0D-3, fifth cycle at ±250 kN 5 J 8
Figure 5.14 Load-slip behavior of specimen S1.0D-3, tenth cycle at ±250 kN 5.19
Figure 5.15 Load-responses for specimens SI.25D 5.27
Figure 5.16 Load-responses for specimens S1.75D 5.28
Figure 5.17 Load-response for specimens S2.0D 5.29
Figure 5.18 Slip versus cycles for specimens S1.25D-2 5.30
Figure 5.19 Slip versus cycles for specimens SI.75D-2 5.31
Table of content XIV
Figure 7-14 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S250 of the pull-out test at load level
of333kN 7.16
Figure 7-15 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S250 of the pull-out test at load level
of662kN 7.17
Figure 7-16 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S750 of the push-out test at load level
of 1452 kN 7.18
Figure 7-17 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S750 of the push-out test at load level
of 2747 kN 7.19
Figure 7-18 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.5D of the Stage 1 at load level of
572 kN 7.20
Figure 7-19 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.5D of the Stage 1 at load level of
1000 kN 7.21
Figure 7-20 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.25D of the Stage 2 at load level of
222 kN 7.22
Figure 7-21 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.25D of the Stage 2 at load level of
440 kN 7.23
Figure 7-22 Bending moment distribution along the steel tube for specimen S250
of the pull-out test 7.27
Figure 7-23 Bending moment distribution along the steel tube for specimen S750
of the push-out test 7.28
Figure 7-24 Bending moment distribution along the steel tube for specimen
S1.5D (Stage 1) 7.29
Figure 7-25 Bending moment distribution along the steel tube for specimen
S1.25D(Stage2) 7.30
Table of content XVI
Figure 7-26 Longitudinal stress distributions along the steel tube for specimen
S250 of pull-out test 7.32
Figure 7-27 Longitudinal stress distribution along the steel tube for specimen
S750 of push-out test 7.33
Figure 7-28 Longitudinal stress distribution along the steel tube for specimen
S1.5DofStageltest 7.34
Figure 7-29 Longitudinal stress distribution along the steel tube for specimen
S1.25D of Stage 2 test 7.35
Figure 7-30 Load-slip behaviours of varying the aspect ratio of the steel tube for
specimen S500 in pull-out test 7.38
Figure 7-31 Load-slip behaviours of varying the aspect ratio of the steel tube for
specimen S750 in push-out test 7.38
Figure 7-32 Load-slip behaviours of varying the aspect ratio of the steel tube for
specimen S1.5D in Stagel test 7.39
Figure 7-33 Load-slip behaviours of varying the aspect ratio of the steel tube for
specimen S750 in push-out test 7.39
Figure Al-1 Strain gauge arrangement for specimen S250 Al. 1
Figure A1-2 Strain gauge arrangement for specimen S500 Al. 1
Figure A1-3 Strain gauge arrangement for specimen S750 A1.2
Figure A1-4 Strain gauge arrangement for specimen S1.0D Al .3
Figure A1-5 Strain gauge arrangement for specimen S1.5D A1.3
Figure A1-6 Strain gauge arrangement for specimen S1.25D A1.4
Figure A1-7 Strain gauge arrangement for specimen S1.75D A1.4
Figure A1-8 Strain gauge arrangement for specimen S2.0D A1.5
Figure A2-1 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S250 of the pull-out test at load level
of333kN A2.2
Figure A2-2 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S250 of the pull-out test at load level
of662kN A2.3
Figure A2-3 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S500 of the pull-out test at load level
of334kN A2.4
Table of content XVll
Figure A2-4 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S500 of the pull-out test at load level
of 1008 kN A2.5
Figure A2-5 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S750 of the push-out test at load level
of 1452 kN A2.6
Figure A2-6 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S750 of the push-out test at load level
of 2747 kN A2.7
Figure A2-7 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1,0D of the Stage 1 at load level of
275 kN A2.8
Figure A2-8 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.0D of the Stage 1 at load level of
663 kN A2.9
Figure A2-9 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.5D of the Stage 1 at load level of
572 kN A2.10
Figure A2-10 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.5D of the Stage 1 at load level of
1000 kN A2.ll
Figure A2-11 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.25D of the Stage 2 at load level of
222 kN A2.12
Figure A2-12 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.25D of the Stage 2 at load level of
440 kN A2.13
Figure A2-13 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.75D of the Stage 2 id load level of
225 kN A2.14
Figure A2-14 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.75D of the Stage 2 at load level of
363 kN A2.15
Table of content XVlll
Figure A2-15 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S2.0D of the Stage 2 at load level of
481 kN A2.16
Figure A2-16 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S2.0D of the Stage 2 at load level of
920 kN " A2.17
Figure A3-1 Bending moment distribution along the steel tube for specimen S250
of the pull-out test A3.2
Figure A3-2 Bending moment distribution along the steel tube for specimen S500
of the pull-out test A3.3
Figure A3-3 Bending moment distribution along the steel tube for specimen S750
of the push-out test A3.4
Figure A3-4 Bending moment distribution along the steel tube for specimen
S1.0D (Stage 1) A3.5
Figure A3-5 Bending moment distribution along the steel tube for specimen
S1.5D (Stage 1) A3.6
Figure A3-6 Bending moment distribution along the steel tube for specimen
S1.25D(Stage2) A3.7
Figure A3-7 Bending moment distribution along the steel tube for specimen
il S1.75D(Stage2) A3.8
Figure A3-8 Bending moment distribution along the steel tube for specimen
S2.0D(Stage2) A3.9
Figure A4-1 Longitudinal stress distributions along the steel tube for specimen
s Figure A4-5 Longitudinal stress distributions along the steel tube for specimen
S1.5D of Stage 1 A4.6
Table of content XIX
Figure A4-6 Longitudinal stress distributions along the steel tube for specimen
S1.25DofStage2 A4.7
Figure A4-7 Longitudinal stress distributions along the steel tube for specimen
S1.75DofStage2 A4.8
Figure A4-8 Longitudinal stress distributions along the steel tube for specimen
S2.0DofStage2 A4.9
Figure A5-1 Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S250 in pull-out test A5.1
Figure A5-2 Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S500 in pull-out test A5.2
Figure A5-3 Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S750 in pull-out test A5.2
Figure A5-4 Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S750 in push-out test A5.3
Figure A5-5 Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S1000 in push-out test A5.3
Figure A5-6 Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S1.0D in pull-out test (Stage 1) A5.4
Figure A5-7 Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S1.5D in pull-out test (Stage 1) A5.4
Figure A5-8 Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S1.25D in push-out test (Stage 2) A5.5
Figure A5-9 Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S2.0D in push-out test (Stage 2) A5.5
Table of content XX
LIST OF TABLES
Table 7-1 The most suitable material properties combinations for the interface
elements 7.3
Table 7-2 Ultimate strength comparison 7.5
Table 8.1 Calculated factors and bond strength from formulation 8.2
Table 8-2 Comparison of bond strength from different methods 8.3
Table 8-3 Comparison of bond strength from calibrated surface condition factor
with experiment 8.6
Introduction 1.1
INTRODUCTION
1.1 General
This research project is concerned with the bond strength of reinforced concrete
plugs embedded in tubular steel piles subjected to pull-out, push-out and cyclic
loadings.
In calculating the bond strength, slip, bond stress distribution and incremental slip
due to repeated loading, the model can also take into account the effect of the
shrinkage of the concrete plug. This contribution to the body of knowledge of the
behavior of reinforced concrete plugs embedded into steel pipes will lead to a
greater confidence in the prediction of bond strength in applications such as the
substructure of offshore facilities.
Introduction 1.2
1.2 Background
The legs of platforms of many offshore and coastal structures are usually founded
on tubular steel piles through reinforced concrete pile caps. Wave, wind and
earthquake loads tend to induce compressive and uplift forces in the legs, that in
turn, subject the piles to compression and tension. This transfer of forces takes
place through a concrete "plug" embedded in the top of the pile. The resistance of
the embedded concrete plug is made up of the steel-concrete bond strength through
the plug length, (see Figure 1).
Reinforcing
bars
R10 rings
R.L.
Figure 1.1 A typical connection between steel pile and concrete pile cap
The composite action in such a system is due to the chemical adhesions between
the concrete and the internal surface of steel pile and mechanical interlock.
Investigations have shown that these mechanisms depend on the surface
roughness of the steel tube and the variation of shape of the cross section of the
Introduction 1.3
steel tube. Values of bond strength for non reinforced concrete plugs in
compression reported in the literature, varied from 0.4 to 1.0 Mpa.
Due to lack of reliable allowable bond strength for design purposes, the
investigation of pull out bond strength within concrete filled circular steel sections
was initiated in 1997 in the Civil Engineering Department of Monash University.
The investigation continued through 1998 and 1999 to evaluate the bond strength
of push out and cyclic loading conditions. Dr. Riadh Al- Mahaidi and Professor
Paul Grundy have supervised students to accomplish experimental investigations.
The investigations at Monash University indicated that the bond strength between
concrete and steel is lower in compression than tension. The bond strength of the
reinforced concrete plug embedded in steel tube in compression is a function of
both chemical adhesion of the steel - concrete interface and mechanical
interlocking between the concrete core and steel surface.
The micro adhesion of the interface relates to the surface roughness of the steel
section and the mechanical interlocking of the concrete plug in the steel tube
during push out is attributed mainly to the dilation through Poisson's ratio effect
of the concrete within the steel tube, causing an increase in contact stresses, which
results in an increase in friction. Load transfer through bond in the vicinity of the
load source is higher than that near the base of the concrete plug due to the same
Poisson effect. At the top of the typical specimen, there is very little vertical load
transfer to the steel tube. The concrete, which is subject to very high compression
stresses, expands laterally, so that top of the steel section is forced to grip the
concrete plug. In the vicinity of the base of the plug, the steel tube carries most of
the longitudinal load. This causes the tube to expand, while the expansion of the
concrete plug is very small due to the low level of compressive stress in the
concrete core. This leads to separation between the steel and concrete at the
bottom.
Introduction 1.4
I Separation
Due to the Poisson's effect
J L
In the tension (pull out) case, the reverse h expected to occur. That is, near the
base of the concrete plug, the steel tube contraction is much higher than that of the
concrete core, causing it to grip the concrete plug. Near the top part of the plug,
the tension force is transferred to the concrete through the reinforcing bars
embedded in the concrete plug and in the pile cap. The tensile stresses that
develop in the concrete core result in the contraction of the concrete, while the
steel tube contraction is relatively very small. This should result in the occurance
of separation between the steel tube and the concrete.
The main mechanism that is believed to contribute to the high bond strength in
pul?. out tests was the dilation of concrete due to the wedging action exerted by the
deformed steel bars against the concrete layer between the steel bars and the steel
tube.
Introduction 1.5
Pull-out Force
Separation
i1 XDue to the Poisson's effect
Concrete
. * D "-. * ' » ' • ' •
' : . * • • '
A
.'4 ', •>
High tensile stress in the steel tube
... A
' . . . •
Low tensile stress on concrete
lTube
. .1. i
l l l
Generally, the cyclic loading reduced the ultimate capacity of specimens. The
cyclic loading was shown to reduce the stiffness of the system consistently with
each and every cycle. Variations between the degradation of the stiffness of the
specimens of the different depths were minimal, when subjected to similar
stresses.
Areas of the literature that were particularly important to the conduct of this
research are reviewed in Chapter 2 of the report. These areas are the behavior of
concrete plugs embedded in steel tubes under tension, compression and cyclic
loading, the effective parameters on bond strength and finite element analysis.
In Chapter 3 the previous static pull-out and push-out tests are presented and
explained. In Chapter 4, the experimental program that was undertaken on the
combination of pull - out, push - out and cyclic loading tests in stages 1 and 2 of
Introduction 1.6
the experimental set are described. The results of that testing program are
presented and discussed in Chapter 5. The objective of the implementation of Non
linear finite element analysis (NLFEA), the physical model, its geometry and
simplification are presented in Chapter 6.
In Chapter 7 the results from the NLFEA models are compared with the data from
the experimental tests on concrete plug specimens under axial static loading.
LITERATURE REVIEW
2.1 Introduction
This chapter is intended to give the reader an insight into previous research on the
behavior and strength of concrete filled circular steel tubes. As outlined in
Chapter 1, the particular focus of this research is the bond strength of concrete
plug steel tubular piles and significant attention is given to previous investigations
that have included the bond between concrete plug and steel tube interface.
Experimental investigations that have been undertaken as well as
recommendations, analytical models and formulation of bond strength predication
are discussed.
The basis of these recommendations is discussed in this section and the ability
that these methods have in prediction of bond strength and therefore the ultimate
strength of this type of structure is assessed.
Concrete filled steel tubular columns are a composite column made by filling steel
tubes with plain or reinforced concrete. This gives the advantage of combining the
properties of steel hollow sections with the confined concrete. Concrete filled
steel tubular (CFST) columns offer a number of advantages in both design and
construction.
• Confines the hardened concrete, which increases its strain capacity and
strength
• Protects the surface of the concrete from damage and deleterious
environmental effects, such as carbonation
In turn, the concrete increases the critical buckling stress of the (imperfect) steel
tube by changing its buckling mode, particularly for noncircular sections.
In recent years, many mvestigations have proposed analysis and design rales for
concrete filled steel columns based on experimental models of steel tubes filled
with concrete and tested in compression.
One of the concerns associated with composite columns is the influence of bond
strength between inside of the steel tube and infill concrete upon the behavior
under different loadings. Most of past experimental investigations in behavior of
CFST columns assumed full bond and a complete continuity of strains between
steel and concrete.
In fact, the composite action in CFST columns is due to the chemical bond
strength and mechanical interlock. Investigations have shown that the ultimate
capacity of the column and the bond strength effective mechanisms depend on the
following parameters.
The bond between the concrete core and the steel tube is an important
characteristic of the response of composite CFST columns. It is believed that the
bond strength has a significant effect on the behavior of composite members.
However, careful examination of previous test results indicates that there is still
uncertainly about the effect of bond strength on the response of CFSTs.
The bond stress demand varies for different structural systems and different
locations in a structure. Demand was always greatest in regions of geometric
discontinuously such as connections and foundation supports. Far less bond stress
demand is required in connections where elements penetrate concrete filled or
concrete fill the tube partially.
The earliest experimental study of bond strength of concrete filled steel tubes was
carried out by Virdi and Dowling (1975). A number of parameters were varied to
study their effects on the bond strength between concrete and steel. It was
concluded that the resistance to the push out test in filled tubes derives primarily
from the interlocking of concrete in two types of imperfections in steel. The first
relates to the surface roughness of the steel and the second relates to variation in
the shape of the cross section, away from the ideal cylindrical surface. The
interlocking of concrete in the surface roughness of steel, that is micro locking,
contributes a useful component of the ultimate bond strength related to the
initially stiff region of the load deflection characteristics. This bond is broken
when the concrete interface attains a local strain of 0.0035 associated with the
compressive crushing of concrete. This component of bond resistance is
distinguished from the resistance obtained due to the interlocking of the concrete
in the undulating surface of the steel tube. This latter type of interlocking, termed
macro locking is, related to the later stage of the load-deflection characteristics
associated with the primarily frictional movement. The remarkable parallel nature
of the characteristics in this region tends to confirm this relationship. It was also
noted by Virdi and Dowling, that by better compaction both micro locking and
macro locking could be enhanced, resulting in a higher value of ultimate bond
literature review 2.5
strength. It was suggested that ultimate bond strength is not influenced to any
appreciable degree by factors such as the length of concrete and steel interface,
steel tube diameters or thickness, or the concrete strength. Virdi and Dowling
proposed the bond strength of 1 MPa for design.
Morishita et al (1979) conducted tests based on measuring the strain in the steel
rather than a relative movement of concrete to the steel. The reason for this was to
more accurately mirror conditions in composite construction. The aim of this
experimental study was to investigate the relationship between concrete strength
and bond. The results showed that, contrary to the Virdi and Dowling (1975)
study, there was a relationship between strength and bond. The quoted bond
strength was 0.2 to 0.4 MPa. This is considerably lower than that found by Virdi
and Dowling. The second study by Morishita et al (1980) was aimed at increasing
the bond strength between steel and concrete. This was achieved by using
expansive concrete and checker plate steel tubes. Both these measures enhance
the micro locking described by Virdi and Dowling (1975). The conclusion of this
study was that both methods improved initial bond. When only expansive
concrete was used, the resistance dropped to levels that normal concrete attained
after the initiation of slipping. It also showed that expansive concrete bond
increased with concrete strength.
Okamato and Maeno (1988) investigated the effect of bond strength between the
steel tube and concrete core on the behavior of O T columns filled with high
strength concrete. The objective of this study was to investigate the effects of
aspect ratio, level of axial force and bend strength on the bending capacity of the
columns. Tests were conducted on nine square columns filled with high strength
concrete ( / / =98.1 MPa). In order to control the bond strength, a mortar layer
with a thickness of 10 mm was placed between the steel tube and the concrete
core. According to the test results, it was concluded that; (1) the bond strength has
no significant effect on the flextural capacity of CFT columns, (2) the flextural
capacity considerably increased by increasing axial load, (3) the steel tube has a
significant effect on improving the compressive strength of concrete and
cfe*
Literature review 2.6
preventing the brittle failure that is normally associated with unconfined high
strength concrete. The range of variables used in Okamoto's study was limited.
Moreover, for each test the two main variables (level of axial force and mortar
strength) were changed at the same time. In this situation, a solid conclusion is
difficult to be made.
variables involved were the diameter of the concrete core, the wall thickness of
the steel tube and the shrinkage of the concrete core. It was concluded that
shrinkage can be very detrimental to bond stress capacity, and the importance of
shrinkage depends upon the characteristics of the concrete, the diameter of the
tube and the surface condition inside the tube. It also was noted that the bond
capacity is smaller with large diameter tubes and large D/t ratios. The bond
capacity is interrelated with slip at the steel concrete interface. An exponential
distribution of bond stress prior to slip was expected, and more uniform
distribution occurs after slip. Eventually a bond strength formulation was
suggested that estimates the bond stress capacity and design recommendations at
different performance levels.
Kilpatrick and Rangan (1999) undertook a series of tests to study the influence of
the shear transfer by bond between the infill concrete and the inner surface of the
circular steel tube. Three different case of bond were examined together with four
different loading regimes and slenderness ratios. Companion tests on similar
empty steel tubes were also undertaken to highlight the synergistic effect of the
steel and concrete acting compositely together. It was concluded that the bond
strength might be a consideration for stub columns because it appeared to
influence both the strength of the column and its load-shortening response, as
indicated by the discontinuities. It was also noted that the bond did not play a
significant role in the behavior of beams and eccentrically loaded short and
slender columns because the concrete was longitudinally confined.
2.4 The Influence of Shape and Aspect Ratio of the Steel Tube
and Length to Depth of Concrete Core
Tests to investigate the axial strength of CFT columns have been performed on
Varieties of cross sectional shapes, steel tube diameter to thickness (D/t) and plug
length to diameter L/D ratios. Furlong (1967) investigated 13 specimens with D/t
ratios ranging from 29 to 98. Results indicated that each component of the
Literature review 2.8
composite column resisted load independent of each other, and consequently there
was no bond between the steel tube and concrete and no increase in the load
resisting capacity due to confinement of the concrete core. Knowels and Park
(1969) studied 12 circular and seven square columns with D/t ratios of 15,22, and
59, and L/D ratios ranging from 2 to 21. Results indicated that the tangent
modulus method accurately predicted the capacity for columns with L/D ratios
greater thanl 1 but were slightly conservative for columns with small slenderness
ratios. It was concluded that this larger than expected capacity for composite
columns with L/D less than 11 was due to the increase of concrete strength
resulting from triaxial confinement effects. It was observed that for certain values
of longitudinal strain the concrete began to increase in volume due to micro
cracking, which induced concrete confinement by the steel tube. This confinement
increased the bond strength and the overall load resisting capacity of the CFT
column. However this increase was noted for circular tubes only, not for square or
rectangular shapes. Furthermore, it was determined that this increase occurred
only in short columns. For columns with large L/D ratios the composite section
failed by column buckling before reaching the strains necessary to cause an
increase in concrete core volume.
Sakino et al. (1985) tested 18 circular specimens with D/t ratios ranging between
18 and 192. In this investigation, three otherwise identical specimens were
subjected to different load conditions. Axial load was applied to the concrete and
the steel tube simultaneously for the first specimen group. The load was applied
exclusively to the concrete core in the second specimen group, and the load
application was similar to this in the third group except that the inside tube wall
was greased before casting the concrete. Results indicated that when the steel tube
and the concrete core were loaded simultaneously, the tube provided no
confinement and bond between the steel tube and the concrete core until post-
yielding behavior. In the concrete loaded only specimens, some longitudinal
stresses were noted in the steel tube even for the columns with the greased wall.
Therefore, regardless of the loading condition, the wall of the steel tube appeared
to be primarily in a biaxial stress state. The test results indicated that the bond
strength is a function of mechanical interlocking between steel tube and the
Literature review 2.9
Although test results indicated that the axial stiffness of the concrete loaded only
columns were about half that of the other CFFs tested, the concrete loaded only
columns obtained a greater yield and ultimate axial load capacity.
The above research demonstrated that slender columns did not exhibit the
beneficial effects of composite behavior, in which concrete strength increased
over that of the cylinder strength due to confinement. Thus, it was concluded that
the concrete core and the steel tube acted independently of each other. Short
columns however, exhibited greater than predicted capacity, generally associated
with the higher concrete strength due to the bond strength between th? ieel tube
and the concrete core and also confinement offered by the steel tube.
Virdi and Dowling (1975) tested three specimens each of five different lengths to
study the influence of contact length on bond strength. The contact length was
varied from 149 to 445 mm corresponding to length to diameter ratios of 1.0,1.5,
2.0, 2.5, and 3.0. Average bond strengths of 1.96, 1.76, 2.09, 2.3, and 2.63 MPa
were respectively reported. Test results indicated that except for the shortest
contact length the bond strength appeared to increase with contact length.
However it was concluded that the contact length of the concrete core and steel
tube interface does not have any appreciable influence on the bond strength.
Eighteen specimens with D/t ratios of 17.7,26.5, 31.2, 34.3, 34.5 and 34 were
tested. Test results suggested that the aspect ratio has no significant effect on
average bond strength.
length was not a significant factor on the bond strength. Further, it was shown that
circular sections are much more effective than rectangular sections in resisting
push out forces. This was probably due to the fact that the resistance of the
circular section to a push out force is greatly enhanced as a result of any
longitudinal variation in the internal dimensions of the steel tube.
Roeder .<£ al.'s (1999) test results in an analytical study to examine the bond stress
capacity of circular CFT members indicated that the maximum average bond
stress capacity is somewhat smaller with longer column lengths and larger D/t
ratios and diameters due to the lack of the stiffness to enforce the benefits of
irregularity in the cross section.
Test results of the above references showed that the average bond stress for
rectangular tubes was approximately 70% smaller than the average for circular
tubes. It also indicated that the influences of the steel tube aspect ratio (D/t) and
concrete core length to depth (L/D) on the bond strength are not completely
understood.
In this thesis, circular steel tube with the steel tube aspect ratio (D/t) of 21 was
used for all specimens in experiment and a parametric study of the steel tube
aspect ratio (D/t) of 20 to 40 was then investigated using NLFEA solution
scheme. The concrete core length to diameter (L/D) varied from 1 to 4 to
investigate effect of (L/D) on bond strength of partially filled steel tube with
reinforced concrete.
The bond transfer between the steel tube and the concrete core depends on the
radial displacements due to the pressure of the concrete on the shell and the
shrinkage of the concrete core, together with the rugosity (or internal surface
irregularities) of the interior surface of the tube.
literature review 2.11
Virdi and Dowiing (1975) concluded from a large number of tests results that
mechanical interlock of the concrete core increases with the irregularities in the
steel tube. This mechanical keying could however, arise due to two different types
of irregularities. The first type occurred due to the roughness of the steel surface.
The rupture of this primary interlocking may then be related to local crushing of
the concrete layer in contact with the steel tube. This lends substance to the
adoption of the strain of 0.0035 as a critical value for the definition of ultimate
bond strength. The second type of bond resistance occurred due to the
imperfection of the steel tube. This type of interlocking contributed in essence to
the factional resistance associated with the later flat portion of the load-deflection
response.
Shakir - Khalil (1993a) tested specimens with two types of interface conditions.
The interface of half of the specimens in this series was covered with oil prior to
the casting of the concrete core. The average bond strength result for each group
indicated that the 'dry' specimens give average bond strengths that are about
twice those of 'oiled' specimens for both rectangular and circular specimens. It
was concluded that the push out resistance of concrete filled steel hollow sections
is rather sensitive to the roughness and conditions of the steel-concrete interface
and also to the irregularities in the internal dimensions of the steel hollow section.
These factors respectively affected the micro- and macro-resistances of the
section to the push out force. It was also noted that the 'oiled' specimens
exhibited a longer transitional curve between the linear part of load-slip response
and the point at which the maximum load was reached.
Roeder et al. (1999) concluded that the roughness and conditions of the steel-
concrete interface and also the irregularities on the inside of the tube significantly
increase the bond strength on specimens of small diameter (150 mm) and small
d/t ratios. However, the evidence of the experiments suggested that tubes with
larger d/t ratios and diameters lack the stiffness to enforce the benefits of
irregularities in the cross section.
literature review 2.12
Kilpatrick and Rangan (1999) tested a series of stub CFST columns with three
different concrete-steel interfaces. For the first specimens as a maximum bond
condition, self-tapping screws were inserted through holes in the wall of the steel
tube. For the second group as a partial bond condition, an intermediate level of
shear transfer was achieved by a thorough degreasing of the inside of each
specimen in the as received condition. Chemical adhesion between the concrete
and the inner surface of the steel tube in the as received condition was minimized
by heavily coating the surface with oil for third specimens as a minimum bond
condition. The measured strengths of the stub columns (L/D=3.5) ranged from
990 kN for the minimum bond case to 1063 kN for the maximum bond case,
which is a range of ±36.5kN, or 3.6%. The maximum forces sustained for short
columns (L/D slO) varied between 440 kN for the minimum bond column and
450 for the partial-bond column. It was concluded that concrete-steel interface
conditions, which was called bond conditions in this investigation, did not
significantly influence the strength of the composite columns tested.
Results of the above references showed that the average bond stress improved
with the increase of the roughness and irregularities of the internal surface of steel
tube.
Virdi and Dowling (1975) tested three specimens each of six different design
concrete strengths varying from 24 to 41 MPa. Test results indicated that the bond
strength was not greatly influenced by the variation in the concrete compressive
strength. It was also noted that higher strength concrete, due to its naturally higher
shrinkage, will tend to diminish the mechanical interlocking, thereby reducing the
influence of concrete strength on bond strength. In another series of tests
specimens were tested at different ages of the concrete to study the influence of
concrete age on the bond. It was concluded that the bond strength increased with
age of concrete up to 21 days of age and decreased thereafter. The results showed
Literature review 2.13
noticeably lower values of bond strength for the group of specimens tested at the
age of 47-48 days.
Roeder et al. (1999) concluded that shrinkage could be very detrimental to the
bond stress capacity. Care must be exercised about the shrinkage potential of the
concrete mix when the use of bond stress is being relied upon in large diameter
steel tubes. It was also noted that the bond strength was not related to the strength
of concrete.
Results of the above references show that the concrete compressive strength has
no consistent effect on the bond strength. On the contrary, shrinkage of the
concrete seemed to be very detrimental to bond stress capacity and CFTS
behavior.
Multi-axial stress states govern in many cases the load resistance of concrete
structures. It is known that under multi-axial compression the load resistance and
the deformation capacity of concrete are increased. There is a strong interaction of
the non-linear deformation and the activation of confining stresses. Hence, a
realistic description of the deformations of concrete in tri-axial compression is as
important as the formulation of the strength envelope.
Literature review 2.14
It has been observed that the ultimate axial capacity of CFT columns is larger than
the sum of uncoupled steel and concrete failure loads. The confining of the steel
tube on the concrete causes the increase in the failure load. The structural
behavior of CFST columns is considerably affected by the difference between the
Poisson's ratios of the steel tube and concrete. In the initial stage of loading, the
Poisson's ratio for the concrete is lower than that of the steel tube. Thus the steel
tube has no confinement effect on the concrete. As longitudinal strain increases,
the lateral expansion of concrete gradually becomes greater than expansion of
steel tube. At this stage the concrete becomes tri-axially stressed and the steel tube
biaxially stressed.
It was suggested that the ACI equation for estimating the secant modulus of
elasticity Ec =0.043w h5 jf^ predicts values as much as 20% too high for
concrete with a compressive strength in the vicinity of 80 MPa. Furthermore, the
ACI code current expression for the modulus of rupture f, = 0.4 JfJ may be too
It was proposed that the anticipated (theoretical) failure stress for each case be
estimated using the Mohr-Coulomb failure criterion. Consider a tri-axial failure
literature review 2.15
state of stress with isotropic stresses in the horizontal orientation (/ 2 ' = / 3 ')- The
(2-1)
Where c is the cohesion intercept; Kp = tan2 (45+0/ 2); and <j) is the angle of
It was concluded by Mei et al. (2001) that HSC is pressure sensitive with an
internal friction angle of 49.5 degrees base on Mohr-Coulomb failure envelope. It
exhibited, however, a much smaller Poisson type of lateral expansion due to axial
compression. As a result, interactive confinement is slow to develop unless larger
than common amount of confining steel is used. When interactive confinement
due to lateral reinforcement is developed, it results in significant gains in ductility,
which for the experiments conducted in this investigation developed in a linear
relation to the amount of confining reinforcement.
Mender et al. (1988) proposed a unified stress-strain approach to predict the pre-
yield and ^ost-yield behavior of confined concrete members subjected to axial
compressive stresses. The model utilizes the equation given by Popovics in 1973,
originally developed to represent the stress-strain response of unconfirmed
concrete. This model is oased on a constant confining pressure <jR. The axial
stress of the confined concrete / cc for any given strain £cc is related to peak
fccXr (2-2)
Jcc ~~
r-\
— _££. (2-3)
literature review 2.16
r = (2-4)
where Eco is the tangent elastic modulus of unconfined concrete, and can be
estimated as 5000-y/Tf (MPa). Esec is the secant modulus of confined strength and
The peak confined strength f'cc is a function of the unconfined strength / / and
The strain at peak-confined strength e'cc is given as a function of the strain at peak
(2-6)
Given a value of the unconfine^ strength / / , and constant confining pressure oR,
can be used to evaluate j ' c c . The corresponding strain e'cc can be estimated by Eq.
(2-6). This model can predict the behavior under a constant confinement pressure.
Dynamic tests are quite useful in the evaluation of the behavior of structural
elements subjected to accidental or dynamic loading. This type of dynamic test,
for which loading conditions differ significantly from those of conventional static
loading, allows the degree of damage of the structural element to be measured
under the effect of repeated cyclic loading.
During static loading it has been established that concrete confinement in a steel
tube is more efficient than confinement by conventional reinforcement (Lahlou
1994). However, the potential role of the autogenous shrinkage of the concrete
and the effect of the tube-concrete interface on the behavior of the composite
element are still ignored by most researchers. This would not hold true in the case
of load cycling, which may lead to localized failure that can increase the damage
under repeated loading and unloading cycles.
steel tube show a great capacity for absorbing and dissipating energy input from
dynamic loading excitations.
The previous work on behavior of the CFT columns in cyclic loading was
concluded that the key attributes of behavior include the following:
The purpose of this section is to give a brief overview of the current state of the
art models of non-linear finite element analysis to determine axial capacity
available in literature. The models that are considered in this section are those that
are capable of accounting for variation of the geometry and materials
specifications of a cross section.
slip. The calibration and verification of the slip formulation were presented, and
the finite element model was verified against experiments of CFT beam columns
subjected to monotomc loading. The fiber element approach discretely models the
CFT element end cross section into a grid of fibers, and the steel and concrete
stress-strain behavior is tracked explicitly at each fiber. The calibrated parameters
suggested that little slip is experienced in a CFT member before the bond strength
of the slip interface is breached. In addition, the calibration value of bond strength
used for analysis is higher than the value recommended by design codes,
suggesting that the recommended design values may be conservative. However,
regarding the previous studies, even for the more extreme conditions, slip is seen
to have little effect on the global behavior of a composite CFT member subjected
to flexure. Nevertheless, understanding the effect of slip more fully on the
behavior of CFTs in composite structures warrants further compressive
parametric studies.
elongation of the steel shell and the concrete core, and the second was the
difference between curvatures in the cross section for the concrete core and the
steel shell. These effects are integrated over the perimeter and were added to the
virtual work expression of the basic element. The model was used to analyse
several CFT columns under constant concentric axial load and cyclic lateral load.
The effect of semi- and perfect bond was investigated and compared with
experiments. The results showed that the use of a studded or ribbed steel shell
caused greater ultimate strength and higher dissipation of energy than the columns
with non-studded steel shell. It was also noted that under the assumption of uni-
axial state of stress-strain properties of the constituent materials are required to
define the properties of any cross section.
Hajjar et al. (1996 and 1998) used empirical uni-axial nonlinear stress-strain
models to represent implicitly the multi-axial stress-strain behavior of the steel.
2.
CO
w
2
0}
Strain
Figure 2.1 illustrates the basic form used to represent implicitly the multiaxial
stress-stain curve for various combinations of concrete strength and D/t ratio. The
rupture strength of the concrete,/r, is given as 0.623jfJ, with all stress quantities
inMPa.
Schneider (1998) modeled the concrete core using 20-node brick elements, with
three translation degrees of freedom at each node. The three-dimensional concrete
material model available in ABAQUS was developed to simulate conditions with
uniaxial strain and relatively low confining pressure. Therefore, reasonable results
were expected with confinement on the order of one fourth of the uniaxial
compressive stress or less. Since the experimental results suggested that little
confinement was observed for the concrete prior of the yield, this material model
for the concrete was considered adequate. The unconfined uniaxial stress-strain
curve for the concrete used in this analysis is shown in Fig. 2.2.
COtyPRESSlbN
The stifftiess beyond the ultimate strength of the concrete was indicative of the
amount of confinement expected. This portion of the curve was adjusted
according to experimental results.
To consider the increased concrete strength and strain due to confinement the
following empirical formulation were used (Richard et al. 1928)
lat
(2-7)
where fcc is axial compressive strain of the concrete confined by the lateral stress
°im •> fc<,is uni-axial compressive strength of the concrete, and k is the so-called
tri-axial factor and is found to be 4.1.
(2-8)
where ecc is axial compressive strength at peak stress, sco is axial compressive
(2-9a)
i=0
(2-9b)
/=o
The first function scaled the strength K according to the current confinement
while the second function scales the hardening parameter K. In equations (2-9a)
and (2-9b) the constants a, and b{ were calibrated from pertinent test data.
The values for fcc and ecc were calculated using equations (2-7) and (2-8) and
Aval et al. (2002) and Shams and Saadegvaziri (1999) used a model based on the
obtained results relating confinement ratio and D/t (aspect ratio), and between
confinement ratio and uniaxial compressive strength. The following empirical
formulations were used to consider the increased concrete strength and strain due
to confinement.
(2-10)
i+
.* J J
where f'cc is axial compressive strain of the concrete confined by the lateral stress
steel tube, or is the shape factor and A and B are empirical parameters expressed in
terms of / ..
3.51
(2-11)
. 60 J
strain at peak uni-axial stress. For circular columns a =1 and the empirical
equations A and B are as follows:
510
B = -32.517 + (2-13)
Jc
The tensile behavior of the model talces into account tension stiffening and the
degradation of the unloading and reloading stiffness for increasing values of the
maximum tensile strain after initial cracking. A linear rate of tensile strength
reduction is adopted in this model.
During the initial parametric study, it was found that the level of compressive
stressing concrete is lower than the compressive strength of the concrete.
Therefore, to minimize the numerical errors, it was decided to model the
shrinkage of the concrete considering with only cracking criteria and non-linearity
of the interface. It assumes that the compressive response of the concrete is elastic
prior to cracking.
Literature review 2.27
Hajjar et al. (1996 and 1998) assumed the compressive branch of the steei tube
stress-strain curve to retain stress of fy after yielding, but strain hardening
neglected to account indirectly for the biaxial stress state in the steel due to
confinement of the concrete.
Schneider (1998) and Johansson and Akesson (2001) modeled the steel tube using
8-node shell element with five degrees of freedom at each node. Inelastic material
and geometric nonlinear behavior were used for this element, von Mises yield
criteria defined yield surface, and the Prandtl-Reuss flow rule was used to
determine inelastic deformations. No strain hardening characteristic were
assumed for the steel tube.
Aval et al. (2002) and Shams and Saadegvaziri (1999) used the Von Mises elastic-
plastic model with kinematic hardening for the steel tube.
In this thesis, the Von Mises elastic plastic material model and shell element were
used for the steel tube.
Hajjar et al. (1998) used a model based on the assumption that the steel and
concrete are separated by a layer of springs, which determine the load transfer
between the two materials based on nonlinear spring stiffness. Thus, to track the
differential movement between these materials for a three-dimensional
geometrically nonlinear CFT arbitrary oriented in space, and to allow for
automated assembly of CFT elements into a global stiffness matrix of a composite
frame during geometrically nonlinear analysis. The value of initial slip stiffness of
ksiip of 104 MPa was chosen for the computation model.
Literature review 2.28
Shams and Saadegvaziri (1999) modeled the interface between the concrete and
steel tube using a gap contact elements. The gap contact elements is a special
purpose contact elements that allow the nodes to be in contact or separate with
respect to particular directions and separation condition. For this analysis, gap
elements were placed between adjacent nodes of steel tube and the concrete with
a fixed contact direction perpendicular to surface of the steel tube. The initial
separation distance was specified as zero, in which case the gap initially closed
(i.e. the concrete and steel tube are initially in contact with each other).
Aval et al. (2002) used a distributed bond interface element to represent relative
slippage. The bond behavior were modeled by elastic-perfect plastic behavior
with a yield point of 0.8 N/mm2 and elastic stiffness of Eb = 1.6 N/mm3 (See
Figure 2.3.)
Literature review 2.29
i.e. -
E 0.8 •
I
(5
o
0.4
0 •
0.5 1.5
Slip (mm.)
In this thesis, the interface was modeled with the Coulomb friction material model
and gap element.
The codes provisions of British standard BS5400, Steel, concrete and composite '
bridges (1979) were developed based on Shakir - Khalil's experimental work. It
is recommended that shear connectors should be provided where the shear
stresses at the steel / concrete interface, due to the design ultimate loads, would
otherwise exceed 0.4 N/mm2 for concrete filled steel sections.
Literature review 2.30
Both codes recommend the same value for bond/shear strength between concrete
and steel regardless of concrete properties, length of concrete embedment, shapes
of steel hallow section and roughness of steel hollow section internal surface.
Roeder et al. (1999) proposed a bond stress evaluation model for ultimate and
serviceability design stages (see Figure 2.4.).
f* Length No
Length No Greater
Greater Than d/2
Than The
Length of
the Column
or 3.5
Tines the
Diameter of
the Tube
For Serviceability
For Ultimate Load Behavior During
Resistance Multiple Loads
The following equation was suggested to calculate maximum average bond stress
capacity as a function of aspect ratio.
Literature review 2.31
where d, is the diameter of the steel tube and t, is thickness of steel tube. This
equation suggested that no reliable bond could be achieved with d/t ratios greater
than 80.
One of the applications of this research project is the connection of cast in steel
shell (CISS) piles to the pile cap. The applied loads transfer thorough bond
strength of the concrete plug embedded in the tubular steel pile. Silva and Seible
(2001) conducted an experimental and analytical study to evaluate the seismic
response of CISS piles and its connection to the pile cap. To develop the tensile
forces present in the steel shell, average bond strength juave of 2.07 MPa (300 psi)
was assumed for analysis, which leads to development length ld shell given by
where D, and Z), are the outside and inside diameter of the steel shell, respectively
and fyj is the steel shell yield strength.
Other researchers recommended the bond strength of concrete core into the steel
tube values between 0.4 to 1.0 MPa, based on the push out tests.
The connections between the piles and the pile skirt sleeves are generally made by
grouting to provide load transfer between structure and piles. In pull out tests of
reinforced concrete plugs embedded in tubular steel tube, the concrete layer
between the reinforcement and the steel tube can be simulated as a grouted
connection. The concrete layer mainly provides load transfer between the
reinforcement and steel tube.
literature review 2.32
Offshore technical (OT) report (OTO 2001 016) recommended the following
formulation for the characteristic bond strength of grouted connection, with or
without mechanical shear connectors.
(2-16)
where:
fbuc is the characteristic bond strength (in N/mm2)
(2~17>
where:
m is the modular ratio of steel to grout
D is the outside diameter
t is the wall thickness
The available data on the parameter C, is limited. In the absence of data relating
to a specific tubular and shear connector geometry, the following values of C,
should be assumed.
;
K2
Literature review 2.33
UDp c,
2 1.0
4 0.9
8 0.8
>12 0.7
i. If shear connector are present and satisfy the requirements h/s > 0.005
then Cs may be taken as 1.0.
ii. For plain pipe connections and for connections with shear connectors but
with h/s < 0.005, then in the absence of the test data, Cs should be taken
as 0.6.
The values in i. And ii. Above refer to shotblasted or lightly rusted surface
conditions. Other conditions (e.g. painted surfaces) should receive special
consideration.
Literature review 2.34
In summary then, previous research has identified that the following factors may
affect the bond strength of concrete plugs embedded in steel tubular piles:
In light of the above comments relating to existing studies that have included the
effective parameters on the bond strength of concrete plugs into the steel tubes, as
well as current state of the art analytical methods that have capacity to predict the
strength of CFT columns and bond strength, several outstanding issues are to be
addressed in this research.
7) Discuss the contributions of the concrete and the steel tube to the bond
strength
Pull-out and Push-out tests 3.1
3.1 Introduction
This chapter presents the results of pull-out (Bean 1997) and push-out
(O'Loughlin 1998) tests that were carried out in the Department of Civil
Engineering of Monash University. Subsequent analysis of these results is also
presented in this chapter. The primary focus of this discussion is to isolate the
effect of concrete plug length on the ultimate strength and failure mechanisms of
the specimens tested. The mechanisms, which contribute to bond strength, are
discussed in this section.
Test results are examined against current code provisions and recommendations.
Mathematical expressions are adopted to calculate the bond strength of concrete
plugs in steel tubular piles.
Previous investigations of bond strength within concrete filled steel tubes were
limited to push-out tests of unreinforced plugs. The pull-out investigation aimed
to evaluate the bond strength of reinforced concrete plugs in the steel tubular piles
in pull-out loading.
Eleven specimens were initially constructed for pull-out tests, of which seven were
prepared eventually for push-out tests after completion of the pull-out tests. The
principal variable was the length of concrete plug, L. Only one circular steel tube
size and concrete strength were used. The tubes had an average outside diameter
Dj of 237 mm, with an average thickness of 11.5 mm (Sectionl). Two of the
Pull-out and Push-out tests 3.2
supplied steel tubes had an average thickness of 10 mm with an out side diameter
of 237mm (section 2). Internal diameter and thickness of all tubes were measured.
The following is a summary of these measurements for section 1.
Measurements taken = 28
Mean diameter = 214.1 mm
Standard of Deviation = 0.7 mm
Mean thickness =11.5 mm
Standard Deviation = 0.6 mm
In table 3.1 below, the letter S followed by a number designates the test specimen
by the length of concrete plug. The pull-out test specimens were divided into three
groups, with different tube and concrete plug lengths. The first group included
three specimens with tube length of 500 mm and concrete plug length of 250 mm,
the second group included three specimens with tube length of 750 mm and
concrete plug length of 500 mm and the third group included two specimens with
tube length of 1000 mm and concrete plug length of 750 mm.
Concrete Plug
Specimen ID Tube Length L/Di Strain gauging
Length (mm)
Excess rust slag within the steel tubes was removed with a wire brush. The
average concrete compressive cylinder strength was 50 MPa and the slump of 75
mm was reported on delivery. The reinforcing bars in all specimens consisted of 6
Y 24 bars (24 mm diameter deformed bar with yield strength of 400 MPa). Based
on the net area at the threaded end of bars, the steel ratio is 5.2 % of the gross area
of the concrete plug. In pull-out tests, the tension was applied by an attachment to
the threaded ends of the rebars.
T3
_ Concrete
3 0 MPa Compresive Strength
2
u
3
©
p
©
m
20 nun.
A string LVDT (linear variable deferential transducer) was located at the top of the
concrete plug to measure the relative movement between the concrete core and the
steel tube. Most specimens were strain gauged along the outer surface of steel tube
within the length of concrete plug. Both longitudinal and hoop strain gauges were
used. The purpose of these gauges was to determine the load transfer mechanism
from the concrete plug to the steel tube. Additional strain gauges were used on the
opposite side of the tubes in order to establish whether the loading arrangement
introduced significant eccentricity in the specimen. As shown in Figure 3.2
below, the loads were applied through a thick disc plate bolted to the top of
reinforcing bars.
<t>60mm
High Strength bar
Local Cell
h— Jack
Strong Floor
Cage Frame
Concrete Plug in
Steel Tube
, Base Plate
Two specimens having a concrete plug embedment of 750 mm were tested. When
the applied pull-out load reached 1222 kN, the threaded portions of the steel bars
of specimen S750-1 failed explosively. No significant slip was recorded at this
load level. Slip of the concrete core measured from the center of the specimen
was observed to be linear with respect to load and the plot relating slip to applied
load gave no indication of pull-out failure. The maximum slip at 1000 kN load
level ranged from 0.44 to 0.57 mm, which corresponds to an average bond stress
2.42 MPa. To avoid the explosive failure of the steel bar, specimen S750-2 was
loaded to 1000 kN only.
Three specimens with 250 mm length of concrete plugs were the only specimens
that achieved full bond failure. They carried maximum loads of 810, 720 and
1035 kN, with corresponding average bond strength of 5.1 MPa. Table 2 lists the
values of peak loads achieved and the corresponding average bond strength. The
slip values are also tabulated.
Pull-out and Push-out tests 3.6
Not
S500-2 500 2.11 1000 No failure 2.95 0.58
Gauged
Not
S500-3 500 2.11 1000 No failure 2.95 0.43
Gauged
It should be noted that the bond resistance is a function of both the micro
chemical adhesion and mechanical macro locking between the concrete core and
the steel surface. The former depends on the surface roughness of the steel
section, and the latter related to the frictional resistance to movement along the
steel - concrete interface and dependent on the dilation/contraction due to
Poisson's ratio effect of the concrete plug and steel tube.
high tension stresses contracts laterally, and this leads to separation between the
steel and concrete. On the other hand, in the vicinity of the base of the plug, the
steel tube carries most of the longitudinal load. This causes the tube to contract,
while the expansion of the concrete plug is very small due to the low level of
tension stress in the concrete core. This results in a gripping mechanism between
the steel tube and the concrete plug at the bottom (see figure 3.3).
Pull-oiit Force
1 1
Separation
XDue to the Poisson's effect
• • * • • . • " - * . "
A• "
* ' ^ • * • • •* * *"'
High tensile stress on concrete
•
* ' *
•
•
. ' " • • / •
:
*£ '<
•
ON • • - . '
• • *
.
• .
' * . *
a
High tensile stress in the steel tube
Low tensile stress on concrete
SteeI Tube
' .-IT
,
1 II 1
Considering the fact that deformed bars was used as reinforcement, the ribs on the
bars tend to impart wedge pressure on the outer concrete layer, causing dilation of
this layer. This dilation enhances the frictional stresses between the steel tube and
the concrete.
After rising to a peak load, the load response of S250-1 was characterized by a
gradual decrease in load transfer as slip increased. Specimens S250-2 and S250-3
exhibited a stick-slip mechanism of bond failure. Sudden slip occurred with sharp
decrease in the load capacity followed by gradual increase in resistance. This
process continued until the slip values exceeded 30 mm. The plugs for these two
specimens were then pulled out to examine the concrete surface in contact with
the steel tube. Inspection showed that voids up to 25 mm in size were present on
the contact surface, and this might have contributed to the type of bond failure
exhibited by these specimens. However the load - slip curves of the specimens of
this group are seen to exhibit a nearly bilinear response prior to peak load (Figure
3.4). The position of the change of slope seems to indicate that bond resistance of
the specimen changes from a non-slip mechanism action (chemical adhesion
between the interface of concrete plug and steel tube) to the very small - slip
mechanism action (mechanical macro locking between the concrete core and steel
surface).
The slip response of specimens S500 also shows a nearly bilinear response. A
permanent slip is evident upon unloading the specimens. The change of slope of
the load - slip curves during loading is assumed to commence with the breaking
of chemical adhesion and activation of the mechanical locking mechanism, which
was also observed in S250 specimens (Figure 3.5). As can be seen from the
figure, the load-slip response of specimens S750 shows a nearly linear
relationship between load and slip, with a permanent small slip remaining on
S750-2 after unloading. The linear slope of the load - slip curves suggests that the
bond resistance of these specimens comes mostly from chemical adhesive (micro
lock between concrete core and steel surface) for the limited applied load of 1000
KN (Figure 3.6).
Pull-out and Push-out tests 3.9
S250-1
1000- .' *-» - - S250-2
X
1 X
- - - S250-3
800- ! **
600
m \
o
400- i
j
L
200- V
X
• i
0- :I
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Slip (mm.)
1200
1200-
1000-
| 800-
Loadi
400-
S750-1
^ ^ . • ' . . , ' • • • " "
200-
S750-2
0-
0.1 0.2 0.3 0.4 0.5 0.6 0.7
Slip (mm.)
J' * la I
Pull-out and Push-out tests 3.11
Figure 3.9 to Figure 3.11 show the load - longitudinal strain relationship of
specimens S250-1, S250-2, and S500-1 along the length of the steel tube. The
number that follows the follows the letter V indicates the distance of the strain
gauge from bottom of concrete plug (see Figure 3.8).
200
500
150
o
o o
I
©
o
in
1
H
1
C/D
As can be seen form the figures, the load - longitudinal strain relationships
exhibit two different stages of shear transfer stress distributions. At the first stage,
all longitudinal strain gauges along the steel tube experienced a steady increase of
longitudinal strain as the applied load increased, which indicates a nearly uniform
shear/bond stress distributions along the interface surface. At the second stage,
strains near the top and bottom of the concrete plug have risen sharply. This is
attributed to dilation through the Poisson's ratio effect at the bottom and dilation
of the concrete layer surrounding the steel bar cage caused by wedging effect of
the ribs of the deformed bars. A sudden increase of shear/bond stress occurs at the
Pull-out and Push-out tests 3.12
transition point of first and second stage, whereas the applied load reached around
the load level of 23o KN for specimens S250 and 470 KN for specimen S500-1.
The two stages of load - longitudinal strain relationship indicated that initially the
resistance of the specimens against pull-out comes from chemical adhesion
between the concrete and the inner surface of the steel tube. As the applied load
reaches a maximurn capacity of bond strength due to the micro chemical
adhesion, some of the microscopic connections on the interface surface break,
leading to a mechanical locking mechanism. This causes the change of slope of
the load - slip relationships. From the load - longitudinal strain and load - slip
relationship, the average chemical adhesion bond strength of 1.36 MPa and 1.38
MPa were achieved for specimens S250 and S500, respectively.
600 V-450
V-0 y^C^ 1 V-100
V250
500-
V100
V50
400 j. IV-250
c VO
I 300
15
c .
"•5 200 '^y , V-450
3
5>
§ 100
it
200 400 600 800 1000 1200
LOAD (KN)
The pull-out test results are presented in Figures 3.4 to 3.6 and Table 3.2. The
measured mean ultimate strength of specimens S250 was 855 kN.
Using the recommendation for the ultimate bond strength of the CFT column
given by equation (2-24) (Roeder et al. 1999), the minimum average bond stress,
f2ff, is determined as follows:
f2ff =2.019-0.026(^/0
•*ultimate ~ (3-1)
Where d is steel tube diameter, t is steel tube thickness, Tuitimate is ultimate pull-out
strength, Dcp is diameter and L is length of the concrete plug. Table 3.3 shows
calculated values for the bond stress and corresponding ultimate pull-out force
based on Roeder's (1999) recommendation.
It is evident that Eq. (3-1) gives higher estimates of ultimate bond strength than the
code (BS 5400) value of 0.4 MPa. However, Eq. (3-1) still underestimates the
bond strength, when compared with the measured values. The estimated ultimate
pull-out strength of specimens S250 is equal to 29% of the experimental average
ultimate strength. The estimated ultimate pull-out strength of specimens S500 and
S750 are also lower than the achieved level of average bond strength in the
experiment.
The results indicate that Roeder's (1999) recommendation for the bond strength is
very conservative for the case of reinforced concrete plugs embedded in steel
tubular piles subjected to pull-out. The recommendation was made regardless of
the concrete plug length, concrete material characteristics and internal surface
Pull-out and Push-out tests 3.15
condition of the steel tube, which seem to influence the bond strength of the
concrete plug.
Table 3.3 Roeder's (1999) recommendations against the pull-out test results
Average Ultimate
Concrete Peak Calculated
Specimen Failure Bond pull-out
ID
Plug D/t Load
Condition Strength
bond stress
strength
Length (KN) (Roeder)
(MPa) (Roeder)
1/2
(3-2)
where:
Pull-out and Push-out tests 3.16
(3-3)
Where:
The available data on the parameter C, are limited. In the absence of data relating
UDP
2 1.0
4 0.9
8 0.8
0.7
For normal internal surface of the pile, in the absence of test data, Cs could be
taken as 0.6.
Pull-out and Push-out tests 3.17
Table 3.4 below shows calculated values for the bond stress and ultimate pull-out
force based on the adopted OTO (2001) report recommendation.
Table 3.4 The OTO's (2001) recommendations against the pull-out test results
Average Ultimate
Concrete Peak Calculated
Specimen Failure Bond pull-out
Plug D/t Load bond stress
ID Condition Strength strength
Length (KN) (OTO)
(MPa) (OTO)
The estimated ultimate pull-out strength of specimens S250 is equal to 80% of the
experimental average ultimate strength.
The estimated ultimate pull-out strength of specimens S500 and S750 are higher
than the achieved level of the bond strength with a reasonable margin.
Pull-out and Push-out tests 3.18
The results indicate that the OTO's (2001) recommendation for the bond strength
is in agreement with the test results. Furthermore, the concrete plug length,
concrete material characteristics and internal surface condition of the steel tube
bi were considered in the recommendation.
H
I;>
,1
[1
N
1
The failure mechanism displayed by the specimens was at the base of the concrete
plug, where the steel tube contraction is much higher than that of the concrete
1 core, causing it to grip the concrete plug. The diagonal tension crack that formed
in the concrete layer between the longitudinal reinforcement and the steel tube
extended to the end of the embedded longitudinal reinforcement where it began
running in hoop direction. This crack appeared to correspond to a tension splitting
Pull-out and Push-out tests 3.19
of the concrete plug at ultimate pull-out capacity of the specimen. This type of
mechanism is shown in Figure 3.13 below.
Pull-out
Failure
Crack Pattern Based on Experiments
As a result of the failure of the concrete plug in the pull-out test, the following
formulation is proposed based on free body diagram of the concrete plug at the
failure.
Where Tuit is ultimate pull-out strength, fbuc is the bond stress, Dcp is concrete plug
diameter,/r is tensile strength of the concrete, 1 is length of concrete plug and tr is
thickness of concrete layer between the tube and reinforcement.
Pull-out and Push-out tests 3.20
Table 3.5 below shows the ultimate pull-out capacity of the specimens using
above formulation and bond stresses recommended by the adopted OTO (2001)
method.
Table 3.5 Ultimate pull-out strength of the specimens based on the failure model
The estimated ultimate pull-out strength from proposed failure model for
specimens S250 is 700 kN, which is only 17% lower than the experimental results.
The estimated ultimate pull-out strengths for specimens S500 and S750 are higher
than achieved pull-out loads. However, it was not possible to evaluate the results
from different estimation methods with ultimate pull-out force for specimens S500
and S750 due to the limited ultimate capacity of longitudinal reinforcement to
apply the pull-out force.
However, the estimated values from the proposed failure model are slightly (%2)
higher than values from OTO's (2001) recommendations. Therefore, it would be
Pull-out and Push-out tests 3.21
The ultimate strength of the specimens subjected to pull-out force was not reached,
du, to the higher than expected strength of the specimens and the limited ultimate
capacity of longitudinal reinforcement to apply the pull-out force. Therefore, it
was decided to test the remaining specimens to determine the push-out capacity of
the specimens (O'Loughlin 1998).
•I 1
:
*
4i
Concrete
4 II i Ik <50 MPa Compresive Strength
ii. r II .
ir. • II
'il-
i::f-:
4t-
Seven specimens were prepared for ths push-out test, which initially were
constructed for the pull-out tests. A typical test specimen for push-out testing is
shown in Figure 3.14.
The pile head applied the push-out force on the concrete plug, which was cast on
top of specimens after specimens were tested on the pull-out test. The average
concrete compressive strength was 60 MPa for pile head concrete. The loads were
increased through the pile head to ensure that the additional concrete would only
be applying pressure on the embedded concrete (see Figure 3.15 below).
Amsler Machine
Concrete Floor
The test specimens had three different tube and concrete plug lengths. The first
group included two specimens with tube lengths of 750 mm and concrete plug
lengths of 500 mm. Both had already been tested for pull-out. The second group
had three specimens with tube lengths of 1000 mm and concrete plug lengths of
750 mm, of which two had already been tested for pull-out. The third group had
two specimens with tube lengths of 1250 mm and concrete plug lengths of 1000
mm. (See Table 3.6)
Concrete Plug
Specimen ID Tube Length L/Di Strain gauging
Length (mm)
Two LVDTs were located on the steel tube to measure the relative movement
between the pile head and the steel tube.
Pull-out and Push-out tests 3.24
The two specimens having a concrete plug embedment of 1000 mm were not the
subject of prior pull-out tests. They carried maximum loads of 1360 and 1350
kN, with a corresponding average ultimate shear/bond strength of 2.01 MPa.
Two of the three specimens having a concrete plug embedment of 750 mm had
already been subjected to a pull-out force of lOOOKN without failure or noticeable
damage. They carried maximum loads of 3445, 3700 and 2503 kN, with a
corresponding average ultimate shear/bond strength of 6.37 MPa.
The two specimens having a concrete plug embedment of 500 mm had already
been subjected to a pull-out force of lOOOKN. They carried maximum loads of
694 and 681 kN, with a corresponding average ultimate shear/bond strength of
2.04 MPa. Table 3.7 lists the values of peak loads achieved and the corresponding
average bond strength. The slip values at peak load and previous pull-out test
situations are also tabulated
The push-out strength is attributed mainly to the dilation through the Poisson's
ratio effect of the concrete within the steel iube, causing an increase in radial
contact pressure, which enhances friction resistance. Load transfer through the
bond in the vicinity of the load source is higher than that near the base of the
concrete plug due to the n*me Poisson ratio effect. At the top of a typical
specimen very little longitudinal load is transferred to the steel tube. The concrete,
which is subject to very high compression stresses, expands laterally, so that the
top of the steel section is forced to grip the concrete plug. In the vicinity of the
base of the base of the plug, the steel tube carries most of the longitudinal load.
This causes the tube to expand, while the expansion of the concrete plug is very
small due to the low level of compressive stress in the concrete core. This leads to
separation between the steel and concrete (see Figure 3.16).
"• I 4
u • . <
4 . -• • '•
' . •'•'•"•'.•
High compressive stress in the steei tube
• 4
•A
•* 'A Low compressive stress on concrete
H \ Separation
Due to the Poisson's effect
_ 1.
11 1
Figures 3.17 to 3.19 show the load - slip relationships of all specimen groups with
different plug and steel tube lengths. Figures 3.20 to 3.22 show the initial phase of
the relationship in more detail.
The significantly different behavior associated with the three different lengths of
embedment is amenable to only partial explanation.
The SI000 series exhibited a decaying shear/bond stress after peaking at a slip of
1.0-1.25 mm. This is the expected result associated with plugs in a properly
circular straight pile. The fretting of the cemented matrix on the steel surface has
a powdering effect removing the interlock with asperities on the steel surface, and
lowering the effective coefficient of friction. The lower pull-out strength of
specimens S1000 compared to S750 could be due to higher effect of shrinkage
and initial pull-out test on specimens S750-1 and S750-2.
The S750 series did not exhibit the decay in shear/bond stress after an initial peak.
A possible explanation is that the tubular member was not as straight or truly
circular in cross-section as in the other two series. Macro interlock effects are
then created when the slip becomes significant. These raise the contact stress
between the pile and the concrete plug, which increases the frictional resistance.
Although two of the three specimens in this series had been subjected to prior
pull-out loads of 1000 kN, this was considered to be insufficient to generate
permanent reverse slip and interface damage to affect the result.
The S500 series exhibited some slip at quite low initial load (less than 100 kN).
This is attributed to reversal of permanent slip created by a prior pull-out load of
1000 kN which must have been close to peak capacity. These specimens had a
push-out capacity 681 kN and 694 kN - significantly less than the pull-out
capacity. The initial slip of 0.2 to 0.5 mm is believed to be the recovery of
permanent pull-out slip. Finally in this series, the push-out load dipped after an
Pull-out and Push-out tests 3.27
early peak at about 2 mm slip, but then recovered, indicating some macro effects
previously discussed.
The ultimate shear/bond strength was approximately 2.0 MPa for the SI000 and
S500 series, and 5.0-7.3 MPa for the S750 series. This apparently anomalous
behavior is attributed to the mechanical model of shear transfer and the significant
prior damage to the plug pile interface of the S500 series.
1600 i
1400-
1200-
Load (KN)
4UU -
I S1000-1
i.
200-
! S1000-2 .
I
() 5 10 15 20
Slip (mm.)
4500
4000- S750-2
3500-
3000-
2500-
2000-
1500
1000
500
0
6 8 10 12 14
Slip (mm.)
900 i
800-
700-
600-
§ 500-
•o
g 400-
300
200- S500-1
100-
0-
1 S500-2
5 10 15 20
Slip (mm.)
1600 i
1400-
1200-
1000-
Load(K
800-
600-
400-
200-
i S1000-1
S1000-2
ft
0-
c) 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2
Slip (mm.)
3000 i
S750-2 ..
2500-
^ ^ ^ 8 7 5 0 - 3
2000-
^ 1500-
ra
r
1000-
y S750-1
S750-2
500-
n
/ S750-3
800 i
700
600-
g> 500 -
^ 400-
S
- 1 300-
200- S500-1
100 - S500-2
0-
C) 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2
Slip (mm.)
The push-out test results are presented in Figures 3.17 to 3.22 and Table 3.6. The
measured mean ultimate strength of 1355 kN, 3216 kN and 687 kN were achieved
for specimens S1000, S750 and S500 respectively.
Using the Reoder et al. (1999) recommendation for the ultimate bond strength of
the CFT column given by equations (2-24) and (3.1), the minimum average bond
stress, f2a, and corresponding ultimate push-out strength Tuit;mate> are calculated
(see Table 3.8)
Pull-out and Push-out tests 3.31
Table 3.8 Roeder's (1999) recommendations against the push-out test results
It is evident that Eq. (3-1) gives higher estimates of ultimate bond strength than the
code (BS 5400) value of 0.4 MPa. However, Eq. (3-1) still underestimates the
bond strength, when compared with the measured values. The estimated ultimate
push-out strengths from this recommendation are much lower than the
experimental average ultimate strength.
The results indicated that the Roeder's (1999) recommendation for the bond
strength is not accurate for the case of reinforced concrete plug embedded in steel
tubular piles subjected to push-out. The recommendation was made regardless of
the concrete plug length, concrete material characteristics and internal surface
condition of the steel tube, which seem to influence on the bond strength of the
concrete plug.
Pull-out and Push-out tests 3.32
Table 3.4 shows calculated values for the bond stress and corresponding ultimate
push-out force based on the adopted OT report recommendations.
Table 3.9 The OTO's (2001) recommendations against the push-out test results
The estimated ultimate push-out strength of specimens S750 is 1851 kN and lower
than experimental -«sult of 3216 kN by 42 %. This was due to consolidation of the
concrete from initial pull-out tests. The initial pull-out tests increased the radial
pressure on the concrete and contact pressure between the concrete and the steel.
This affected the macro resistance of the section in push-out tests.
The estimated ultimate push-out strengths of specimens S500 are higher than the
achieved level of the bond strength in experiments due to initial pull-out tests. In
this case, the initial pull-out tests damaged the interface as the specimen reached
around the ultimate pull-out strength load.
The results indicated that the OTO's (2001) recommendation for the bond strength
is more closely correlated with test results compared to the Roeder's(1999)
recommendation and codes provisions.
3.5 Conclusion
This study of the bond resistance in reinforced concrete filled steel tubes indicates
that a mechanical interlock mechanism, which is dependent on the length of the
concrete plug, might be a feasible concept when dealing with the bond strength of
reinforced concrete plugs embedded in steel tubular piles.
The pull-out bond strength tested in specimens having concrete plug embedment
length to tube inner diameter UD -I ranged from 4.3 to 6.2 MPa and average of
5.1 MPa. It was not possible to determine the pull-out bond strength for
specimens with L/D >1, due to yielding and rupture of the embedded steel bars
preceding the development of full bond strength.
The push-out strength of reinforced concrete plugs embedded in tubular steel piles
revealed capacities higher than reported by others, attributed in part to the
presence of reinforcement in the plug. Bond strengths from 2.0 to 7.3 MPa and
Pull-out and Push-out tests 3.34
average of 3.89 MPa were achieved. The possibility that the push-out strength of
the S500 (short plug) series was affected by prior pull-out loading has been
considered.
However, the main mechanism that is believed to contribute to the high bond
strength in pull-out and push-out te^; was the pronounced Poisson effect
increasing radial contact stress at the bise of the connection. A second factor was
the presence of reinforcement in the plug.
The adopted bond strength formulation showed a good correlation with test
results. The recommendation needs to be calibrated more accurately for an
application of concrete plugs embedded in steel tubular pile.
In this chapter the previous pull-out and push-out test results have been presented
and discussed. In the next chapter the experimental program for cyclic loading is
outlined.
Experimental program 4.1
Achieving the objective of the research outlined in Section 2.11 required two
stages of experimental work. The first stage of the experimental work focused on
the determination of the effect of the initial cyclic loading on the ultimate pull out
strength (Whitburn 1999). The second stage of the experimental work required
detailed instrumentation of specimens to determine the shear transfer between the
concrete plug and the steel tube. The determination of the effect of shrinkage on
bond strength is also explored in this set of experiments. A total of fifteen
specimens were tested for the purpose of investigating the effect of cyclic loading
on the bond strength of concrete plugs embedded in tubular steel piles. The
specimens were the subject of a combination of push out, pullout and cyclic
loadings. The tests were carried out in accordance with the previous test results
contained in Chapter 3, dealing with pull-out, push-out and cyclic loading tests.
A special purpose test rig was designed and constructed. ihis chapter describes
the design and construction of the specimens and the test rig, together with a
description of the experimental procedure. The selection of variable concrete plug
length and fixed length of steel tubes, material properties, and loading
arrangements, as well as instrumentation are considered in this section.
Concrete was ordered from a local concrete distributor. The measured mean
strength at 38 days was 39.7 MPa. The concrete had a slump vi:1ue of 100 mm on
arrival.
Experimental program 4.2
Austral Piling supplied the required circular steel tubes. Sections supplied can be
classified into two categories, both with external diameters of approximately 232
mm. Three of the supplied sections were slightly thicker than the other sections.
The first category "section 1" has an average internal diameter of 222.1 mm and
average tube thickness of 11.0 mm. The second category "section 2" has an
average internal diamelsr of 218 mm and average tube thickness of 13.0 mm. The
steel tube was manufactured by cold-forming and high-frequency electric
resistance welding to produce a strong pipe to tight dimensional tolerances, and
confirmed with Australian Standards. It has minimum yield strength of 350 MPa
and minimum ultimate strength of 450 MPa.
4.2.3 Reinforcement
In practice stirrups are usually wire tied to the reinforcement bars, but in order to
maintain uniformity between specimens, the stirrups were tack welded to main
bars.
4.2.4 Formwork
Formwork was made from plywood. The plywood sheeting was cut into circular
discs that sat snugly in the steel tubes. Timber blocks were glued and screwed to
the base of the ply forms to provide the necessary clearance at the end.
Experimental program 4.3
The selected base plates were found in the laboratories, being 100 mm thick they
were assumed to be rigid enough for application to testing. Six 22 mm holes were
drilled on each base plate to connect the bottom of the specimens on the test rig
during the pull out and cyclic loading tests using six M20.
4.3.1 Introduction
As discussed, previous research has identified that the specimens subjected to pull
out, push out or cyclic loading should meet certain requirements, and these are
restated here.
When these requirements are met, the longitudinal and transverse strain gauges
should record the longitudinal and transverse strains on the steel tube, caused by
longitudinal and hoop stresses when a specimen is subjected to pull-out, push-out
or cyclic loading. Bond strength would be calculated based on the ultimate failure
load in each loading case.
The pull out load will apply on six Y 24 deformed bars, therefore the ultimate pull
out force can be calculated as follows;
u = A s xF u = 6 x 7 t x l 2 2 x 6 0 0 =
Effective area on threaded end of bars govern the ultimate Pull out force
For safety purposes the ultimate pull out and push out test are limited to 1000 KN
The steel tubes were cut to the length of 600 mm. The inner surfaces of the steel
tubes were scrubbed with a wire brush to remove any excess rust, dirt or any other
material.
The formwork was fabricated and placed at the bottom of the specimens
considering the different depth of concrete plugs. The specified reinforcing cages
were placed into the specimens and tack welded in position, to insure the cage
would not move during the pouring of the concrete.
Experimental program 4.5
One cubic meter of 32 MPa concrete with slump of 80 - 100 mm, was ordered
from CSR concrete to pour the concrete into each specimen. The result of the
slump test on the concrete batch on arrival showed a slump of 100 mm and the
cylinder compressive strength test results indicated 39.7 MPa at age of 38 days.
The concrete was carefully placed and then vibrated into each specimen, to ensure
satisfactory compaction of the concrete (the machinery used was a poker
vibrator).
The top surface was plastered to provide a level surface, and to ensure even
distribution of the compressive forces. The supporting timber formwork was
removed, and the base plates were then welded to each sample. This process
involved placing the samples into the test rig to ensure the reinforcement bars
were correctly aligned with the testing rig. The base plate was then tack welded
and removed from the rig and fully welded with three passes afterward.
11 nun Thickness
The connection between the specimens and the test rig should transfer pull out,
push out and cyclic loadings from actuator to the specimens. To achieve these
requirements, six holes of 22 mm diameter were drilled in the base plate of each
specimen, to be bolted to the test rig using six M20 high strength bolts after the
specimen was lowered and placed into the testing apparatus. Six holes of 22 mm
diameter were also drilled in the loading plate of the actuator with the same
positioning of the threaded deformed bar of specimens. As a result, the loading
plate can be placed on the top concrete surface of the specimens to apply
compression on the concrete plugs. The threaded deformed bars are bolted to the
loading plate to apply pull out force on the concrete plug.
The support stand was designed as a vertical 40 mm steel head plate (to connect
to the bottom of specimens), welded and braced to a 20 mm steel base plate. The
base plate was bolted to the strong floor using four bolts. Figures 4.2 to 4.6 show
the placement and connection of a specimen to the test rig.
Experimental program 4.8
Support stand
Y////////////////////////////////////////A
Strong Floor
4.5.1 Steps
The steps involved in performing a test on initial cyclic loading and pull-out tests
in Stage one are listed below:
1. Full weld the base plate to the steel tube at bottom of each constructed
specimen.
2. Prepare the specified locations for applying the strain gauges.
3. Place strain gauges on the specified locations using super glue.
4. Place the specimen into the test rig, bolting loosely.
Experimental program 4.11
5. Extend the actuator so that the loading plate is pushed against the concrete
plug with a force of 5 kN, and bolted to the bars, to ensure the specimen is
aligned and positioned properly.
6. Tighten the bolts that secure the specimen to the test rig.
7. Repeat the previous two steps
8. Fully retract the actuator, switch off the supply to the actuator, and fully
tighten the bolts securing the specimen to the support stand and actuator.
9. Wire up all strain gauges
10. Connect the wires to the data acquisition box to record strain on steel tube.
11. Set up the linear differential transducer on top of concrete plug to measure
slip directly between the steel tube and the concrete plug at top of concrete
plug.
12. Connect the LVDT to the data acquisition system
13. Test all strain gauges
14. Set the actuator load to zero.
15. Run the data acquisition computer program to record the required data
16. Run the actuator control program to apply pull out and cyclic loading on
specimen.
17. Stop the data acquisition program at the preset point of displacement.
18. Un tighten the bolts, cut off wires from the specimen
19. Remove the specimen from the test rig.
The monotonic tests (pull out) were conducted at a displacement rate (as
measured by the linear variable differential transducer inside the actuator) of
0.015 mm/sec. The time taken to reach the peak load was varied in the order of 5
to 40 minutes.
The cyclic tests were conducted with a symmetric cyclic loading. For every cyclic
test, the loading was repeated for a predetermined number of cycles, with data
being continuously recorded. The load range was then increased, and the new
Experimental program 4.12
loading was repeated, usually for the same number of cycles. Each initial cyclic
loading included two load ranges.
For the cyclic tests the load versus time function was triangular. A typical
function is shown in Figure 4.7 below. Each completed cyclic test had 10 cycles
at each load range, with a cycle time of 4 minutes. The total elapsed time for a
complete cyclic loading test for a load range was typically of the order of 20
minutes.
Type of tests on each specimen and the loading rates and number of cycles per
load range in Stage one are summarized in Table 4.2.
Time (min)
• Time
• Load from the actuator load cell
• Ram displacement from the built- in linear variable differential transducer
in the actuator (this displacement included movement due to the
compliance of the test rig, and was not used in any subsequent data
analysis)
• Longitudinal displacement (slip) between the steel tube and the concrete
plug, measured by monitoring a linear variable differential transducer
directly on the top of the concrete plug
Experimental program 4.14
The data acquisition was controlled using the software " HP VEE" version 5.01.
A typical acquisition set up is shown in Figure 4.11 below.
4.6.1 Steps
The steps involved in performing a test on pull out, push out or cyclic loading are
listed below:
1. Full weld the base plate to the steel tube at bottom of each constructed
specimen.
2. Cut a hole on the base plate and a hole on bottom part of steel tube to locate
one linear differential transducer at the bottom of concrete plug.
3. Prepare the specified locations for applying the strain gauges.
4. Place strain gauges on the specified locations using super glue.
Experimental program 4.15
The monotonic tests (pull out and push out) were conducted at a displacement rate
(as measured by the linear variable differential transducer inside the actuator) of
0.015 mm/sec. The time taken to reach the peak load was varied in the order of 5
to 40 minutes.
Experimental program 4.16
The cyclic tests were conducted with a symmetric cyclic loading. For every cyclic
test, the loading was repeated for a predetermined number of cycles, with data
being continuously recorded. The load range was then increased, and the new
loading was repeated, usually for the same number of cycles. The number of load
ranges in one test varied from 2 to a maximum of 9 depending on the failure of
the specimen at the preset slip between the steel tube and the concrete plug,
measured by the linear variable differential transducer on top of the concrete plug.
For the cyclic tests the load versus time function was triangular. A typical
function is shown in Figure 4.8- Each completed cyclic test had 10 cycles at each
load range, with a cycle time of 2 minutes. Some specimens were subjected to 10
cycles at each load range, with a cycle time of 4 minutes. The total elapsed time
for a complete cyclic loading test for a load range was typically of the order of 20
minutes.
The type of tests on each specimen and the loading rates and number of cycles per
load range are summarized in Table 4.3.
Specimen Type of test Maximum Max. of Hold time Time for No. of cycles
ID of Load slip (mm.) (min) one cycle per load range
S1.25D-1 1- Push out 443 kN 2.75 mm. 51 min
2- Pull out 460 kN 24.5 mm. 36 min - -
S1.25D-2 1- Cyclic loading 260 kN 1.05 mm. 20 min 2 min 10
2- Cyclic loading 310 kN 7.95 mm. 20 min 4 min 5
3- Pull out 439 kN 24.1 mm. 20 min
S1.25D-3 1-Cyclic loading 245 kN 8.02 mm. 7 min 4 1.75
2- Pull out 540 kN 20.9 mm. 12 min
S1.75D-1 1- Push out 395 kN 7.48 mm. 7 min
2- Pull out 330 kN 12 mm. 12 min. - -
Experimental program 4.17
600
400 H
200-
I
•o
CO
o
-200-
-400
-600
Time (min)
• Time
• Load from the actuator load cell
• Ram displacement from the built- in linear variable differential transducer
in the actuator (this displacement included movement due to the
compliance of the test rig, and was not used in any subsequent data
analysis)
Experimental program 4.19
• Longitudinal displacement (slip) between the steel tube and the concrete
plug, measured by monitoring a linear variable differential transducer
directly onto top and bottom of the concrete plug (refer to Figures 4.9 and
4.10) (in this way the compliance of the test rig was excluded from the slip
measurements)
• Longitudinal and transverse strain along the steel tube, measured by
monitoring the voltage differential through the strain gauges (refer to
Figure 4.13). A data taker essentially used to convert the analog voltage
input into digital data that can be recorded on the computer (refer to
Figure 4.12).
The two linear variable differential transducers' measuring slips were sampled at
20 Hz and a continuous moving average over twenty values was taken to return a
slip value every two second. The LVDTs needed to be calibrated to obtain the
slope factors between the voltage and the displacement of the LVDT. This simply
involved using a micrometer and moving the LVDT between 0 and 24 mm at 2
mm intervals, and recording the milli volt reading at each point. The process was
completed three times, and average of the three trials was used to calculate the
slip.
The data acquisition was controlled using the software " HP VEE" version 5.01.
A typical acquisition set up is shown in Figure 4.11 below.
i .
Experimental program 4.21
§
i
i
i
1
H
<*3
-5
1
:i
, j
i !
Strain gauges are useful devices for monitoring strain/stress at certain points
along a specimen's face. Longitudinal gauges and hoop gauges were used in
combination to record strains in the principal directions (longitudinal and
transverse plane) of the specimen. Using the two dimensional form of Hookes'
law, stresses in the principal directions would then be calculated. Longitudinal
i ;
gauges were also used on alternate sides of the specimen; these gauges were used
to confirm that the applied load contained no eccentricity.
CEA- student series were used. These gauges are in the general purpose family of
constantan alloy strain gauges widely used in experimental stress analysis.
Extremely thin and flexible [0.0022 in (0.056mm)], CEA-Series gauges feature
polyimide - encapsulated grids and exposed copper-coated integral solder tabs to
which lead wires could be soldered directly. The normal use temperature range
Experimental program 4.23
The cyclic loading test results are presented in the next chapter.
Presentation and interpretation of the test results 5.1
5.1 Introduction
This chapter presents the results of Stages 1 and 2 of experimental work, and
subsequent analysis of these results. The primary focus of this discussion is to
isolate the effect of cyclic loading on the ultimate bond strength of the concrete
plug and the steel tube.
The following are key findings from the cyclic loading test results
1. The average bond strength betv/een concrete plug and the steel tube
2. The ultimate pill-out strength
3. The ultimate push-out strength
4. The longitudinal and transverse strains on steel tube
5. Slip at the top and bottom of concrete plug (only for stage two) into the steel
tube, and the rate of slip growth per cycle increased with the pick load.
6. Cyclic reduction factor
7. The failure mechanisms
8. The relationships were obtained between the load and the rate oi slip growth
per cycle under repeated load.
This stage aimed to evaluate the effect of initial cyclic loading on ultimate pull-
out strength. Three specimens each of two different concrete plug lengths of 1 .OD
and 1.5D were tested. The first specimen of each plug length group was tested for
Presentation and interpretation of the test results 5.2
static tension capacity to enable the assessment of cyclic load effects. The other
two specimens were then initially subjected to two ten cycles of 150 and 250 for
series 1.0D specimens and 250 and 400 for series 1.5D specimens. This was
followed by monotonic pull-out tests.
A total of six successful tests were conducted, comprising two monotonic tests to
determine the pull-out strength of the concrete plug and four puli-out tests with
initial symmetric cyclic loadings. Table 5.1 summarizes the Stage 1 tests.
In order to calculate the ultimate pull out capacity of the specimens, it was
decided that specimen Sl.OD-1 and S1.5D-1 be subjected to a static pull out test
at first and then to a static push out test.
The Instron machine was set at a displacement rate (as measured by the linear
variable differential transducer inside the actuator) of 0.015 mm/sec. Specimen
Sl.OD-1 failed at an ultimate pull out strength of 665 kN, giving an average
ultimate bond strength of 4.2 MPa. This was followed by a push out test, which
resulted in ultimate push out capacity of 525 kN, giving average ultimate bond
strength of 3.3 MPa.
Specimen S1.5D-1 achieved ultimate pull out strength of 1000 kN at slip of 1.7
mm. This was followed by a push out test, which resulted in ultimate push out
capacity of 1000 kN at slip of 1.5 mm. The corresponding ultimate bond strength
of 4.0 MPa was achieved in both pull out and push out.
The Instron machine was set to the load control for cyclic tests. Specimens
S1.0D-2 and S1.0D-3 then were initially subjected to ten symmetric cycles of
±150 kN followed by another 10 symmetric cycles of ±250 in tension and
compression. This was followed by pull out tests, which resulted in ultimate load
711 kN and 405 kN for specimens S1.0D-2 and S1.0D-3, respectively
corresponding ultimate bond strengths are 4.5 and 2.6 MPa.
Specimen S1.5D-2 was initially subjected to ten symmetric cycles of ±250. This
was followed by a pull out test, which resulted in ultimate load of 500 kN, and an
ultimate bond strength of 2.2 MPa. Specimen S1.5D-3 was initially subjected to
ten symmetric cycles of ±250 kN followed by another 10 symmetric cycles of
±400 kN. The specimen failed at the end of the cyclic loading test, giving average
ultimate bond strength of 1.8 MPa.
I , > !
Presentation and interpretation of the test results 5.4
Table 5.2 lists the value of peak loads achieved and corresponding average bond
strength. The slip values at peak load, initial cyclic loading test situations and age
of the concrete on date of test are also tabulated.
Average bond strengths of 4.25 MPa for static pull-out test and 2.77 MPa for pull-
out test with cyclic loading effect were achieved. The test results indicated that
pre-cyclic loading tests reduced the bond strength due to the prior damage to the
plug pile interface.
Presentation and interpretation of the test results 5.5
Figures 5.1 and 5.2 show the load-slip responses of specimen series S1.0D and
S1.5D respectively.
As can be seen from the figure, the load-slip response of specimen S1.5D-1 shows
a typical behavior in pull-out test with peak load of 1000 kN at a slip of 1.7 mm.
The test procedure stopped at 1000 kN as the specimen reached the limitation of
the test instrumentation. The load-slip of the specimen in push-out shows gradual
reversal slip to load level of 300 kN. This is attributed to the reversal of
Presentation and interpretation of the test results 5.6
permanent slip created by prior pull-out test. The specimen then reached a load
level of 1000 kN at a slip of 1.0 mm.
Specimen S1.5D-3 failed at the end of the second ten cycles. The load-slip
response of the specimen indicates that the initial cyclic loading reduced the
ultimate strength of the specimen to the level of the second cyclic load of 400 kN.
This was due to the significant damage to the plug pile interface. The post failure
response shows an almost constant shear transfer in pull out test after cyclic
loading. This behavior continued until the slip values reached 9.2 mm.
The load-slip response of the specimens indicated that the load slip curves of the
pull-out test with cyclic effect is similar to the load slip curve obtained for
monotonic static tests. The shifting between these two curves in the ordinate load
axis is due to the different cyclic loading rate and concrete plug length. The
effects of cycling rate and the damage model will be discussed in the following
sections.
The ultimate capacity and load slip response of specimens under cyclic loading
can be reasonably approximated from the ultimate strength and load slip of static
test results by reducing the ultimate strength values of static test by a cyclic
reduction factor. The cyclic reduction factor is defined as the factor by which the
cyclic strength of a specimen may be obtained from the static strength for a given
displacement. The cyclic reduction factor seems to depend on the rate of load,
number of cycles, the concrete characteristics and shrinkage, the imperfection of
the steel tube, the length of plug and perhaps the presence of reinforcement.
Presentation and interpretation of the test results 5.7
-eee-r
Slip (mm)
800 |
—- — • — .
———
.—
—^- 1
/ — -.
0>
I
-2 .0 0 20 40 0 8 0 10 .0 12 .0 V .0
Jo j _ L j
-400
Slip (mm)
I
1
t
• — ^ _ _ _
— * ~ ^ _
-___
1
I
2.
0 1 -
J
1
-2 J 20 40 60 80 10 .0 12..0 V .0
i
i
i
i
i
.inn .
Slip (mm)
Slip (mm)
600-
o -8
-600-
Slip (mm)
600-i 1
I
400--
. _< 1
>^-JIIII
-
H
1
_ J — J -1
i
.0 -2 .0 20 4 Q_ ___6 0 _ _ 80 .0
—- -
--
M
4rmnl
_ _
•500-
Slip (mm)
During cyclic loading, damage to the concrete plug and the pile/plug interface
became apparent either by progressive loss of stiffness through the accumulation
of microcracking or by progressive plastification that appeared as an irreversible
residual strain that increased with each additional cycle.
The slip versus cycles behavior for each of the specimens is plotted in Figures 5.3
to 5.6. The time for one load cycle was typically 4 minutes. The rate of loading
increased as the load range increased in order to keep the cycle time constant.
The load was applied for 10 cycles at each load range.
P/Pu=0.377
10 15 20
Cycle number
0.6-
P/Pu=0.377
0.4- i 1 1 I I
0.2 -
P/Pu=0.226
1 1 ft
LAA AA AAA
0- AAAAAAA/
E
vVWWW
vvvvVVVV
1 "f 1 HpTTTl f~~T
if
Slip
-0.2 -
-0.4-
-0.6 -
M 11I t
-0.8 -
I) 5 10 15 20
Cycle number
P/Pu=0.25
-0.15 J
6 8 10 12
Cycle number
1-
P/Pu=0.40
0.5 - P/Pu=0.23
AAAA AAA
I ° V v v v
w
-0.5 1
-1.5
10 15 20
Cycle number
From the figures it is clear that slip increased with load cycles, and that the rate of
slip growth increased with the peak load. Tne non-symmetric behavior may be
due to differences in the local stiffness of the concrete plug adjacent to the steel
tube. A concentration of coarse aggregate or of voids immediately adjacent to the
top or botium of the steel tube would have an effect on the concrete stiffness and
on the rate of slip growth (decreasing and increasing it respectively).
It was observed from Figures 5.3 to 5.6 that, after the first few cycles at any load
range, the slip increased approximately linearly with cycles. The exception to this
is specimen S1.5D-3 at the second 10 cycles, where the slip increased more
rapidly with cycles as the test approached failure.
Presentation and interpretation of the test results 5.12
A line of best fit to the rate of slip growth with cycles was calculated for every
test at every load range. The values are presented in Table 5.3. These data are
plotted in Figure 5.7, with the rate of slip growth plotted on a logarithmic scale.
Although there is considerable scatter in the data, there is a clear trend that the
rate of slip growth increased with the peak load. The scatter in the data is
probably a reflection of the variation in the characteristics of the concrete plugs.
A line of best fit to the data (plotted in the figure) gave equation (5.1),
(0.3584—Q.0754)
Symmetric cyclic loading, slip growth per cycle = 1 0 " mm/cycle
(5.1)
Various forms of representing the data were trialed, including higher order
functions to fit uV; log-linear representing of the data given in Figure 5.7.
••
Presentation and interpretation of the test results 5.13
c) 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
ii (mm/cycle) 1 1
•
0.1 -
A «^»
.
**-"
o
te of siipgi
A
0.01 • A
R2 = 0.2977 /
10
A
oc
0.001 •
Load range, P/Pu
While slightly higher correlation could be achieved using higher order functions,
the correlation was not significantly better, and in the absence of a physical
model, which supports a particular relationship, an exponential function was
adopted as providing a simple function that could be consistently applied across
different data series.
Equation (5.1) does not strictly satisfy the boundary condition for the rate of slip
growth that when P=0, the slip growth per cycle could be zero. This is not
possible with an exponential function. The discrepancy arises because the
equation is derived empirically, and not from the fundamental physical model of
the behavior. When P=Pu the slip growth per cycle, calculated from the equation,
is finite (but large). This is consistent with the observed behavior - the slip does
not approach infinity as the specimen approaches failure.
Presentation and interpretation of the test results 5.14
The load-slip response for all specimens was plotted to show the relationship
between load and slip. The specimens exhibited pinched hysteretic behavior. This
is illustrated in Figures
Slip (mm)
Tin
t
i
- r - i -
ono 1
i
i
i
i •\(\r\
r "i
- i
(NX)
i a ^
ll|l ir ^>
3-1- 00 -0 80
g^*fe>-- ," -ton
DO 0.20 0.
---200-
1
I i 1
: | I inn
"OuU
Slip (mm)
0.20
Slip (mm)
0.60
Slip (mm)
-see-
0.25
300
Slip (mm)
Slip (mm)
To understand this behavior better, Figures 5.12 to 5.14 plot three cycles (first,
fifth and tenth) of loading for specimens Sl.OD-3 at the same load range. These
figures show that the region of low stiffness (the 'pinch' in the hysteresis curve)
grows larger with increasing number of cycles, and at higher peak loads.
Based upon this representation of the slip behavior, a simplified model for the
behavior of concrete plugs embedded in steel tubular piles under repeated load
was adopted as follows;
Under repeated loading the load-slip behavior of the specimen can be idealized as
a region of slip with zero stiffness, followed by a constant shear transfer region.
The constant shear transfer between concrete plug and the steel tube has the same
value as the shear transfer of the linear region in the monotonic tests.
The region of zero stiffness in the model will be referred to as the damage. The
damage accumulates with increasing numbers of cycles, and the rate at which it
accumulates is a function of peak load. An empirical equation to calculate the rate
of damage (or slip) growth per cycle was presented in equation 4.2 (Section
5.3.4), for the case of symmetric cyclic loading.
The piecewise linear representation of the load slip behavior under repeated
loading will be used to develop the mathematical relationships necessary to
describe the behavior of concrete plugs in steel tubes under repeated loading.
Presentation and interpretation of the test results 5.18
300-,
200-
-100-
/ / /
-200 -
-300-
Slip (mm)
300 -
200 -
/ /
U '
+
-100 -
-200 •
-300-
Slip (mm)
300 -I
200-
A
f
•; -0.80 -jreo
/
/ -0.40 -0.20 0. 30 \
-100-
\
/1
0.20
__ _ -••
/ 0.40
< ."
Slip at shear transfer \
of1000kN/mm -200- Slip with zero
shear transfer
-300-
Slip (mm)
This stage aimed to evaluate the effect of initial cyclic loading on ultimate push-
out strength. Three specimens each of three different concrete plug lengths of
1.0D and I.5D were tested. The first specimen of each plug length group was
tested for static compression capacity to enable the assessment of cyclic load
effects. The other two specimens were then initially subjected to a variety of
different cyclic loading. This was followed by monotonic pull-out tests.
This stage of the experiment took place about two years after construction of the
specimens. Therefore, the determination of the effect of shrinkage on bond
strength of concrete plugs can also be evaluated with this set of test data.
Presentation and interpretation of the test results 5.20
A total of nine successful tests were conducted, comprising three nionotonic tests
to determine the push out strength of the concrete plug, six tests with symmetric
cyclic loading of the specimens, and three tests with extra pull out tests to
evaluate effect of cyclic loading. Table 5.1 summarizes the tests.
In order to calculate the ultimate push out capacity of the specimens, it was
decided that specimens S1.25D-1, S1.75D-1 and S2.0D-1 be subjected to a static
push out test first and then to static pullout test.
The Instron machine was set at a displacement rate (as measured by the linear
variable differential transducer inside the actuator) of 0.015 mm/sec. The push out
test stopped at 2.75 mm slip of concrete plug with ultimate push out strength of
443 kN, giving average bond strength of 2.29 MPa. This was followed by a pull
out test, which resulted in an ultimate pull out capacity of 460 kN, giving average
bond strength of 2.38 MPa.
Specimen S1.75D-1 failed at an ultimate push out force of 395 kN and slip of 7.5
mm, giving an average bond strength of 1.45 MPa. This was followed by a pull-
out test, which resulted in Ultimate push out force of 330 kN and average bond
strength of 1.21 MPa.
Presentation and interpretation of the test results 5.22
Specimen S2.0D-1 achieved push out force of 1000 kN at slip of 1.9 mm, giving
an average bond strength of 3.29 MPa. This was followed by a pull-out test,
which resulted in a pull-out force of 1000 kN (instrumentation capacity) at slip of
1.2 mm. The specimen then was subjected to a set of cyclic loadings, which are
listed in Table 5.5.
The Instron machine was set to the load control for cyclic tests. Specimen
S1.25D-2 was initially subjected to ten symmetric cycles or ±260 kN followed by
five symmetric cycles of ±310 kN in tension and compression. This was followed
by a pull-out test, which resulted in ultimate pull-out force of 439 kN, giving an
average bond strength of 2.27 kN. Specimen S1.25D-3 was initially subjected to
1.75 symmetric cycles of ±245 kN. The cyclic test stopped as the specimen
reached slip of 8 mm. This was followed by a pull-out test, which resulted in an
ultimate pull out force of 540 kN at slip of 20 mm. The corresponding ultimate
bond strength of 2.79 MPa was achieved in pull-out.
Specimen 1.75D-2 was subjected to five symmetric cycles each of nine load
ranges from ±100 to ±300kN. The specimen failed at the fourth cycle of 300 kN,
giving an average bond strength of 1.11 MPa. Specimen S1.75D-3 initially was
subjected to a pull-out test to evaluate the pull-out capacity of the specimen, and
the pull-out test stopped at a load level of 431 kN whereas the concrete plug slip
reached 1.37 mm. This was followed by five symmetric cycles each of four load
ranges from ±150 kN to ±250 kN. The specimen failed at a cyclic load of 250 kN.
Specimen S2.0D-2 failed at a pull-out force of 479 kN before reaching the first
cycle's peak load of the initial cyclic loading of ±500. Specimen S2.0-3 was
subjected to five symmetric cyclic loadings, each of four cyclic loading ranged
from 200 kN to 350 kN. The specimen failed at the first cycle of cyclic loading of
350 kN, giving an average bond strength of 1.15 MPa
Table 5.5 lists the value of peak loads achieved and corresponding average bond
strength. The slip values at peak load, initial cyclic loading test and age of
concrete on the date of test are also tabulated.
Presentation and interpretation of the test results 5.23
A total of 35 tests were carried out on 9 specimens. The pull-out bond strength
was a maximum 3.29 MPa, minimum 1.21 MPa and average of 2.26 MPa for
seven pull-out tests. The push out bond strength was a maximum 3.29 MPa,
minimum 0.93 MPa and average of 2.34 for three push out tests. The cyclic bond
strength was a maximum 1.97 MPa, minimum 0.93 MPa and average of 1.34 MPa
for six cyclic loading tests.
The test results indscaled that cyclic bond strength is lower than ultimate static
pull-out or push out bond strengths. This is due to the incremental damage to the
plug pile interface.
Presentation and interpretation of the test results 5.25
Figures 5.15 to 5.17 show the load-slip response of specimen series S1.25D,
SI .75D and S2.0D respectively.
In static push out tests, specimen S1.25D-1 exhibited a decay shear transfer after
peaking at a slip of 1.0-1.5 mm. This is the expected result associated with a plug
in a properly circular straight pile. This fretting of the cement matrix on the steel
surface has a powdering effect, removing the interlock with asperities on the steel
surface, and lowering the effective coefficient of friction. In the following pull-
out test, the specimen experienced a reversal slip at a load level of 300kN. The
slip is believed to be a recovery of permanent push out slip. The specimen then
showed a gradual increase in load transfer as slip increased. This is due to the
initial push out test, which consolidated the concrete into the steel tube. Macro
interlock effects were then created when the slip became significant. These raised
the contact stress between the steel tube and concrete plug, which increase the
friction resistance.
Specimen S1.25D-2 reached its ultimate strength at the end of initial symmetric
cyclic loading of ±310 kN. The specimen then showed a smooth decay shear
transfer after peaking at a slip of 8 mm in the following pull-out test. This was
due to significant damage to the plug / pile interface during the initial cyclic
loading. Specimen S1.25D-3 failed at the second cycle of first cyclic loading
range after reaching a slip of 8 mm. In the following pull-out test, the specimen
exhibited a gradual increase in load transfer as slip increased.
Load-slip response of specimen S1.75D-1 shows that the push out load dipped
after an early peak at about 2 mm slip but then recovered, indicating some macro
effects previously discussed. In the following pull-out test, the plug locked into
the steel tube with no reversal slip before peaking at a pull-out load of 330 kN.
The shear transfer then dipped down but then partly recovered after reversal of the
permanent push out slip. The locking of the plug was due to a mechanical
interlock mechanism.
Presentation and interpretation of the test results
Push out load - slip curve of specimen S2.0D-1 was seen to exhibit a nearly
bilinear response prior to peak load (set limitation of the test machine). The
change of slope of the load-slip curve during the loading was assumed to commit
with the breaking of chemical adhesion (non-slip mechanism) and activation of
the mechanical interlock mechanism (very small - slip mechanism). Li the
following pull-out test, specimen experienced a reversal slip at a load level of 700
kN. The slip is believed to be a recovery of permanent push out slip. The
specimen then showed a load transfer increase as slip increased before reaching
the test machine limitation of 1000 kN. The specimen S2.0D-2 unexpectedly
failed at the first pull-out force of cyclic loading. However, the specimen
exhibited a decay shear transfer after peaking at a slip of 1.0-1.5 mm.
The load-slip response of the specimens indicated that the load slip curves of
cyclic loading tests are similar to the load slip curve obtained for monotonic static
tests. The shifting between these two curves in the ordinate load axis is due to the
different cyclic loading rate and concrete plug length. The effects of cycling rate
and the damage model will be discussed in following sections.
The ultimate capacity and load slip response of specimens under cyclic 'oading
can be reasonably approximated from the ultimate strength and load slip of static
test results by reducing the ultimate strength values of static test by cyclic
reduction factor. The cyclic reduction factor is defined as the factor by which the
cyclic strength of specimen may be obtained from the static strength for a given
displacement. The cyclic reduction factor seems to depend on the rate of load,
number of cycles, the concrete characteristics and shrinkage, the imperfection of
the steel tube, the length of the plug and perhaps the presence of the
reinforcement. However this rule does not apply to some of the specimens due to
their irregular peak loads. These irregularities might be mainly caused by the
effect of shrinkage.
Presentation and interpretation of the test resu 5.27
-see-
Slip (mm)
-see-
I
0
o
Slip (mm)
696- 1 j
j f i
Crtft _ i |
" 1
— -. — ^
Ana
1 i
OrtO _
- OrtQ _
9- -**
i 1
i i 1b 15 20 25
io 100
L_ _ _L
nnn
Slip(mm.)
4ee-
-500-
SUp (mm.)
I ! 1
I 1 1 1
t
I _
I/ t _
1
I 1
I 1
I ( 1 1
Force (kN)
I 1
I
-— 1
I
1
5 c 15
r
-10 - !> Ml ' "
i
> <
i
c—-
ffr
\e\f\
1
1
1
1
1
1
Slip (mm)
• •' • • • " • • •
!
596- 1 • 1
Af\r\ /I ! '•-
I
-3G0--
2.
5
-"ess sa
V
-10
is r -
5_
^-=9.
—••—
1 II 1
n •
•
——
MM
—1
am
•)
1
i ~
TC T - -
/I
2
.
•-300-
Slip (mm)
,'
; 4f\r\r\
TLI
_L
1 QAft—
! ^ . 1
/
r ~
L _j
|r " r~——. _
«—
. / -
s L 1 u — — ^i O/W-
| I / 0j
14.-1- .5 ^h 05 15 ;i
1 1
L ./.
1 -/-
Slip (mm)
cnn _
|
450-
I
400-
r r ^^**^ _ 1r ~r ~ ~
i i
350-
2 300- i/ r~ ~1 ~r
|250- L i
i
£ 200- t
i
1 CC\ - /.""" i
i
100-
50-
f -- i
0-
() 2 4 B 8 10 12 14 16 18
Slip (mm.)
... j
,J|!
0>
a. t 5 -10 \ 1P 15
o -
u. - ---^•ii
— ^ — .
__
i - O\J\J—p .
i
i
......................«4QQ..J...... -
Slip (mm)
Cyclic loading reduced the bond strength and ultimate capacity of the specimens.
This was due to damage of the concrete plug and pile plug interface either by
progressive loss of stiffness through the accumulation of microcracking or by
progressive plastification that appears as an irreversible residual strain that
increases with each additional cycle.
The slip versus cycles behavior for each of the specimens is plotted in Figures
5.18 to 5.22. The time for one load cycle was typically 4 minutes. The rate of
loading increased as the load range increased in order to keep the cycle time
constant.
P/Pu=0.587
12
Cycle number
1- P/Pu=0.696
0.5-
P/Pu=0.569
P/Pu=0.443
P/Pu=0.316
-1 - P/Pu=0.632
-1.5
10 15 20 25 30 35 40
Cycle number
6 i
P/Pu=0.569
4-
P/Pu=0.38
2 •
1°
P/Pu=0.506
-2 -
-4-
-6 -
0 5 10 15
Cycle number
P/Pu=0,550
0 2 8 10 12 14 16 18 20
Cycle number
1.5 n
P/Pu=0.626
1-
P/Pu=0.418
-0.5- P/Pu=0.522
-1
5 10 15
Cycle number
From the figures it is clear that slip increased with load cycles, and that the rate of
slip growth increased with the peak load. The non-symmetric behavior in some
specimens may be due to differences in the local stiffness of the concrete plug
adjacent to the test tube.
It was observed from Figures 5.18 to 5.22 that, after the first few cycles at any
load range, the slip increased approximately linearly with cycles. The exceptions
to this are specimens S1.25D-2, S1.25D-3 and S2.0D-2.
The concrete plug of specimen S1.25D-2 slipped into the steel tube therefore the
slip increased in the compression part and decreased in the tension part of each
cycle. Specimens S1.25D-3 and S2.0D-3 failed at the start of the cyclic loading.
A line of best fit to the rate of slip growth with cy<° : was calculated for every
test at every load range. The rate of slip values and load ranges are presented in
Table 5.6. These data are plotted in Figure 5.23, with the rate of slip growth
plotted on a logarithmic scale. Although there is considerable scatter in the data,
there is a clear trend that the rate of slip growth increased with the peak load.
A line of best fit to the data (plotted in the figure) gave equation (5.2).,
(0.255 0.899)
Symmetric cyclic loading, slip growth per cycle = 1 0 " mm/cycle
(5.2)
i •;•
Presentation and interpretation of the test results 5.35
Various forms of representing the data were trailed, including higher order
functions to fit the log-linear representation of the data given in Figure 5.23.
o
0.1 -
R2 = 0.4634
-=- 0.01 -
I
.9- 0.001
• A
A
(0
A
"5
! •
g 0.0001
0.00001 -
Load range, P/Pu
While slightly higher correlation could be achieved using higher order functions,
the correlation was not significantly better, and in the absence of a physical
model, which supports a particular relationship, an exponential function was
adopted as providing a simple function that could be consistently applied across
different data series.
Equation (5.2) does not strictly satisfy the boundary condition for the rate of slip
growth that when P=0, the slip growth per cycle could be zero. This is not
possible with an exponential function. The discrepancy arises because the
equation is derived empirically, and not from a fundamental physical model of the
behavior. When P=Pu the slip growth per cycle, calculated from the equation, is
finite (but large). This is consistent with the observed behavior - the slip does not
approach infinity as the specimen approaches failure.
Presentation and interpretation of the test results 5.36
The results so far presented are all the peak values in a loading cycle - that is the
peak load and slip between the concrete plug and the slip tube. When the behavior
during a loading cycle is investigated, some unusual characteristics are revealed,
all of which can be explained by concrete shrinkage.
Because the specimens have axial symmetry, the compression or tension will
cause radial deflection, A,Ube, of the tube and Aconcrete, of the concrete plug. The
radial forces and deflections of concrete plug and steel tube depend on applied
axial force, viscosity and compressive strength of the concrete, length of concrete
plug and the tube diameter. The shrinkage of the concrete will involve a radial
reduction AShrhika8e, of the concrete plug.
| In State A, the concrete pressure persists on the interface after the shrinkage is
complete, and the initial bond strength is provided by adhesion between the steel
and the concrete. This is often termed chemical bond. With increasing shear, this
chemical bond is exceeded, and the subsequent strength depends on the
mechanical interlock characteristics at the interface. Here two features exist: the
bond that depends on the interface pressure and the coefficient of friction, and the
bond provided by the mechanical interlock of the concrete and steel.
In state C, separation of two materials exists after shrinkage, and relatively rigid
body motion occurs with little bond strength or resistance.
^shrinkage - cd / 2 (5.3)
where c is the linear shrinkage strain of the concrete and d is the concrete plug
diameter. The shrinkage also depends on the concrete components and the curing
procedure.
Given c and d values of 0.0003 and 2220 mm, the minimum rugosity needed to
avoid state C and separation is 0.33 mm. Actual surface roughness of the used
tubes are between 0.2 to 0.4 mm. This indicated that the interface condition of the
most unloaded specimens tend to be in State B. Further, these comparisons show
that specimens with large amounts of shrinkage and smaller tube imperfections
may be in State C.
State B produces variable behavior, based upon the degree of interlock between
the surface irregularities of the steel and the concrete in its shrunken state. As
noted earlier, the mechanical interlock will be smaller and possibly non-existent at
Presentation and interpretation of the test results 5.38
To sum up, the shrinkage reduces the contact area and increased separation
between the concrete and the steel tube along the interface, which means less
shear/bond transfer. This decreased the chemical bond and effect of mechanical
interlock. Therefore specimens showed non-consistent and lower ultimate
capacity.
The ultimate capacity and load response of the specimens under pull-out, push out
9 and cyclic loading are presented in Figures 5.1, 5.2, 5.15 to 5.17 and Tables 5.2
and 5.5. The ultimate capacity and load slip response of specimens under the
cyclic loading can be reasonably approximated from the static ultimate strength
and load slip of the specimen by reducing the ultimate strength vabes of static
test by the cyclic reduction factor. The cyclic reduction factor is defined as the
factor by which the cyclic strength of the specimen may be obtained from the
static strength for a given displacement. The cyclic reduction factor seems to
depend on the rate of load, number of cycles, the concrete characteristics and
I shrinkage, the imperfection of the steel tube, the length of the plug and perhaps
the presence of reinforcement. However, this rule does not apply to all specimens
;•
due to irregular peak loads. These irregularities might be caused by either steel
U
tube imperfections or the effect of shrinkage
•a,
r.J
"A Table 5.7 shows calculated cyclic reduction factors for specimens with different
concrete plug lengths based on the ultimate pull-out, push out and cyclic strength
of specimens. The slip values at peak point are also tabulated.
Presentation and interpretation of the test results 5.39
S1.75D-3 Cycling with pre pull-out test 395 250 0.63 18.6
S2.0D-1 Cycling with pre pull-out test 1000 600 0.60 16.0
The cyclic reduction factors for the above ten specimens indicate that the
symmetric cyclic loading reduces the shear / bond transfer between concrete plug
and the steel tube. This is due to the accumulation of damage to the plug pile
interface. The exception to this is specimens S1.0D-2 and S1.25D-3. It may be
caused by either the steel tube imperfections or effect of shrinkage. However an
average (mean) cyclic reduction factor of 0.74 with standard deviation of 1.90
was achieved.
Presentation and interpretation of the test results 5.40
The following formulation was used to calculate the bond strength regarding the
adopted equation (Section 3.2.5).
1/2
Where:
The available data on the parameter C, are limited. In the absence of data relating
to a specific tubular geometry and with regard to the test results of previous pull-
out and push out tests (Chapter 3), the following values of Cz were assumed.
Presentation and interpretation of the test results 5.41
UDP C,
< 1.50 1.0
1.5-2.0 0.9
where L is the plug length.
Table 5.8 shows calculated values for the bond stress and ultimate strength based
on the adopted formulation. The calculated values of ultimate strength were then
examined against measured values and the calculated / measured ultimate
strengths. The cyclic reduction factor of 0.74 was used to adjust the cyclic bond
strength. The adopted formulation assumes a uniform bond distribution along and
around the inside perimeter of the steel tube at the ultimate load performance
level. This is justified because it can be later used in practice.
The predicted results for specimens S1.0D show that the predicted static ultimate
strength is 18% and cyclic ultimate strength is 28% lower than test results. For
specimens S1.25D the predicted values are 2% and 33% lower than static and
cyclic ultimate strengths respectively. The predicted static ultimate strength of
specimens S1.5D is 28% lower than test results but the predicted cyclic strength is
17% higher than test results. For specimens S1.75D the predicted values are 32%
and 38% higher than the average test results of ultimate static and cyclic strengths
respectively. The predicted values for specimens S2.0D are 15% and 2% lower
than the average test results of ultimate static and cyclic strengths respectively.
The higher than predicted values of bond and ultimate strengths in the test results
could be related to the irregularities in the diameter and shape of the steel tube
used for the specimens. The lower than predicted values of bond and ultimate
strengths in test results might be related to the imperfection of the steel tube, and
the effects of shrinkage.
Presentation and interpretation of the test results 5.42
Figures 5.24 to 5.26 show the completely pulled out concrete plug from steel tube
for specimen S2.0D-1. The specimen reached the set limitation of 1000 kN in
static pull-out and push out tests and failed in cyclic loading of 600 kN. The main
failure mechanism displayed by the specimen was at the base of the concrete plug,
where the steel tube contraction in pull-out is much higher than that of the
concrete core, causing it to grip the concrete plug. The diagonal tension crack that
formed in the concrete layer between the longitudinal reinforcement and the steel
tube extended to the end of the embedded longitudinal reinforcement where it
began running in hoop direction. This crack appeared to correspond to a tension
splitting of the concrete plug at ultimate pull-out capacity of the specimen. This
type of failure was discussed in Chapter 3.
The secondary failure mechanism displayed by the specimen was at the top of the
concrete plug where the expansion of the concrete in push out is much higher than
that of the steel tube, causing an increase in radial contact pressure. The micro-
cracks formed and developed at the interface extended to the top of concrete plug.
This type of mechanism was discussed in Chapter 3.
In cyclic loading the initial top and bottom cracks formed at the certain P/Pu and
then developed and extended at each cycle. This resulted in an incremental slip of
the concrete plug into the steel tube. However the damage on the concrete plug
indicated that the failure was a combination of the above failure mechanisms,
which were observed at the top and bottom of the specimen.
Presentation and interpretation of the test results 5.44
1. The average ultimate bond strength of 4.25 MPa for static load and 2.77
MPa for cyclic load for Stage 1 and the average static bond strength of
2.37 MPa and average cyclic bond strength of 1.70 MPa for Stage 2 were
achieved.
2. The push-out and pull-out tests conducted under symmetric cyclic loading
demonstrated that slip between concrete plug and the steel tube increased
with repeated loading, and the rate of slip growth increased with the peak
load.
3. Empirical relationships between the load and the rate of slip growth
(mm/cycle) were obtained from the experimental data as follows,
(0.255-^-0.899)
Symmetric cyclic loading, slip growth per cycle = 1 0 "
(5.2)
4. The ultimate capacity and load slip response of specimens under cyclic
loading can be reasonably approximated from the static ultimate strength
and load slip of the specimen by reducing the ultimate strength values of
the static test by the cyclic reduction factor. The cyclic reduction factor is
defined as the factor by which the cyclic strength, of specimen may be
obtained from the static strength for a given displacement. The average
cyclic reduction factor of 0.74 was achieved.
Numerical Modeling using Nonlinear Finite Element Analysis 6.1
6.1 Introduction
The finite element method (FEM) has become an effective tool used in virtually
every field of engineering analysis. It provides a powerful and general analytical
tool for studying the behavior of the structure in a cost-effective manner.
Experimental results would be used to calibrate the variables and for comparison
against the results of the finite element analysis. FEM analysis then allows
important parameters to be varied systematically and conveniently, v/hich greatly
reduces the number of costly large-scale testing whilst gaining new insights into
the behavior. In the past, the majority of analyses have been restricted or carried
out only in the linear elastic range. Concrete is a heterogeneous material with a
complex behavior that is closely related to the grain size and shape, and the
physical characteristics of its constituents. Therefore, Linear elastic analysis is
simply inadequate in describing the complete behavior of concrete and hence non-
linear analysis is required. In a concrete plug embedded in a steel tubular pile,
non-linear behavior is due primarily to cracking and time dependent effects such
Numerical Modeling using Nonlinear Finite Element Analysis 6.2
6.2 Scope
Although a necessary part of the investigation, the experimental work may have
sources of potential error and variations in material properties and specifications.
This makes it impossible to draw solid conclusions from the test results.
Numerical modeling in this research was also used as an investigative method to
aid in the assessment of key parameters in this investigation.
Two sets of finite element analysis studies were carried out. In the first set,
models with a given set of material properties were generated and analyzed to
verify whether or not the models were simulating the behavior of the concrete
plug specimens properly. The development of a calibrated modeling strategy that
uses nonlinear finite element analysis (NLFEA) has potential in the accurate
evaluation of the structural behavior of concrete plugs into steel piles under axial
pull-out and push out force.
In the second set of finite element analysis, selected material properties and
specifications of the models of the first study were varied and the effects on bond
strength investigated. The aim was to determine qualitatively the sensitivity of the
results with respect to variations in the material properties adopted in the first set
Numerical Modeling using Nonlinear Finite Element Analysis
of analyses. The effect, of varying the steel tube aspect ratio on the ultimate load,
effective bond length, load slip behavior and strain distribution profiles was
investigated. The main aim of the investigation was to use the results and
findings of the numerical analyses in the development and understanding of the
finite element models of the actual concrete plugs embedded in steel tubular piles.
It also aimed to justify the adopted formulation for bond strength calculation.
To ensure that the procedure achieved satisfactory results, the specimens used in
experimental work were modeled with this procedure. The following additional
objectives were set to achieve satisfactory prediction of bond strength.
The first step of finite element modeling is to define the geometry and boundary
conditions. An axisymmetric model was developed by revolving a plane figure
about the centerline of the concrete plug. In this case geometry, material
properties, loads and supports are axisymmetric. Thus the analysis problem is
mathematically two-dimensional.
The model boundaries were intended to model the specimens that were tested
throughout the experimental work. Several factors were considered in ensuring
this replication of the experimental specimens, as well as providing an efficient
model to reduce computational time.
A schematic of the FE model and interface element are illustrated in Figure 6.1.
Reobar
Steel tube
\ o
\
\ i
n
Concrete
• • 9 ^Interface
Steel tube element
The next step would be to discretize the specimen into the appropriate type,
number and size elements. To investigate the ability of the NLFEA solution to
predict the behavior of the specimens, the models that were developed required
distributions of stresses and strains to be produced in the axisymmetry plane of
the concrete and the steel tube. It was therefore decided that axisymmetric
elements be employed.
T
Y i
These elements have a node at each corner, as well as a midside node that is
located at half of the length of each side of the element. Each element has sixteen
degrees of freedom (DOF) with two displacements ux and uy, at each point. A 2 x
2 Gaussian integration scheme was employed. The polynomial for the
displacements ux and uy can be expressed as:
(6.1)
I Numerical Modeling using Nonlinear Finite Element Analysis 6.7
This element is embedded within the DIANA software, has shape functions of the
following characteristics.
(1) The strain exx varies linearly in the x-direction, and quadratically in the
y direction.
(2) The strain eyy varies linearly in the y-direction, and quadratically in the
x direction.
(3) The strain ezz varies quadratically in both x and y directions.
Selection of a mesh size that was capable of capturing the stress distributions in
the regions required in a computationally efficient manner dictated the selection
of the mesh density.
The steel tube and longitudinal reinforcement were represented by the use of a
three-node numerically integrated axisymetical shell of revolution element shown
in Figure 6.3. The longitudinal reinforcement was modeled as a circular ring.
These elements have a node at each end, as well as a middle node that is located
at half of the length of the element. Each element has nine degrees of freedom
(DOF) with three displacements ux, uy and <>
| z at each point. A 2 x 2 Gaussian
integration scheme was employed.
I
X
This element is embedded within the DIANA software. Typically this polynomial
yields a strain exx, which varies linearly in £ direction.
Selection of a mesh size that was capable of capturing the stress distributions in
the regions required in a computationally efficient manner dictated the selection
of the mesh density.
The pile/concrete plug interface was represented by the use of 3 + 3 nodes, two
dimensional line structural interface element shown in Figure 6.4.
(b) (c)
Figure 6.4 - 3+3 nodes structural interface elements (a) topology (b)
displacements (c) tractions
r Numerical Modeling using Nonlinear Finite Element Analysis 6.9
The element describes a relation between the tractions (a stress), t, and the relative
displacements, Au, across the interface, based on quadratic interpolation. For this
element type, the 4-point Newton-Cotes integration scheme was used.
This element is embedded within the DIANA software. Selection of a mesh size
that was capable of capturing the stress distributions in the regions required in a
computationally efficient manner dictated the selection of the mesh density.
Aspects of the material behavior were obtained from the tensile tests on steel
samples and the concrete cylinders. Instrumentation of the specimens provided
information regarding the longitudinal and Hoop strains along the steel tube,
therefore providing information into criteria required for a suitable constitutive
model. This section summarizes the material models that were used in the
solution scheme based on these results.
The concrete embedded in the steel tube has a very complex material behavior:
nonlinear stress-strain behavior in a triaxial state of stress where the confining
pressure is not constant. Due to this complexity, selection of a proper constitutive
model describing the concrete behavior under confining condition is a challenging
task for developing an accurate finite element model.
DIANA provides several constitutive models that are appropriate in modeling the
compressive response of concrete. These are divided into two categories, the
plasticity based formulations, and the total strain formulations. It assumes that
the tensile response of concrete is elastic prior to cracking, but offers a variety of
constitutive modeling approaches to the post-cracking response of tension
Numerical Modeling using Nonlinear Finite Element Analysis 6.10
concrete. These models can also be divided into two categories, linear tension
softening models, and nonlinear tension softening ir.odels.
Owing to the lack of agreement of the constitutive relations in literature that exist
describing the comprcssive and tensile response of concrete, and also the lack of
agreement on the contribution of aggregate interlock to the resistance of shear, a
parametric study of the above variables was performed as part of this research.
The Drucker - Prager model was chosen as a representative model for the
capability of the plasticity models to predict the response of the concrete in
compression. This model describes the yield surface for plain concrete in terms
of the first normal invariant of stress (10, the second deviatoric invariant of stress
(J2), and the hardening parameter (K). The general form of the failure surface is
given in Equation 6.3. The condition F=0 represents failure of concrete. It is
noted that associative plasticity was considered in this implementation of the
modelling so that the internal angle of friction (<j>) is equal to the dilatancy angle
(¥)•
(6.3)
The coefficient otf is a scalar quantity that is dependent on the internal angle of
friction (this angle is dependent on the hardening parameter, i.e. (J)(K)) and is
given in Equation 6.4. The coefficient |3 is also a scalar quantity that is dependent
on the initial angle of internal friction (<J>0), it is shown in Equation 6.4. The
parameter c is the cohesion and is defined in Equation 6.5.
Numerical Modeling using Nonlinear Finite Element Analysis 6.11
2 sin 0(fc)
<*/ = (6.4)
3 - sin
Strain hardening is included in the model by the relation of the cohesion to the
equivalent plastic strain, K. DIANA makes this relation within the software. This
requires relation of the effective cohesion, and the equivalent plastic strain to a
level of applied strain. The implementation of this requires an assumption
regarding the stress strain response of the concrete. For the purpose of this
analysis, it is assumed that the Thorenfeldt (1987) uniaxial curve describes the
compressive response of all elements within a specimen. This assumption implies
that the shape of the stress strain curve of the concrete elements within the model
will not be affected by the existence of a multi-axial stress state. Application of
this assumption yields the relation given in Equation 6.5 between the cohesion
and the uniaxial compressive concrete stress (crc).
1-a,
(6.5)
Assuming that the friction angle (<|>) and the dilatancy angle (y) remain constant
for all states of stress, and equal to the initial values ((J>0 and \j/0), a relation of the
equivalent plastic strain to the uniaxial plastic stress can be made. This is shown
in Equation 6.6.
K-- (6.6)
1-cr
In this equation, ocg is equal to the scalar quantity (Xf (this is since associative
plasticity is assumed), and the strain 63P is the plastic component of the principal
compressive strain.
The confined compressive strength of the concrete was then calculated based on
assuming constant lateral pressure of 10%. The yield condition of Drucker-Prager
was expressed using the confined compressive strength.
cr ._
(6.8)
Gcr = (6.9)
—Y
The 28 day cylinder strength for each concrete batch was obtained as part of the
testing program. From this value, the basic properties consist of Young's
modulus, Poisson's ratio, tensile and compressive strength was calculated using
the following formulation. Young's modulus was determined in accordance with
AS3600 (1995) reproduced herein as Equation 6.10. The density of concrete, p,
was assumed as 2400kg/m3. Poisson's ratio, v, was taken as equal to 0.2. The
tensile strength of the concrete was determined using Equation 6.8 using
compressive strength, which is essentially a modification of the equation reported
in AS36OO (1995). The concrete compressive strength of 50 MPa for pull-out and
push-out tests and 40 MPa for Stage 1 and Stage 2 experimental sets were
investigated.
(6.10)
(6.11)
Results from instrumentation on the steel tube throughout the experimental work,
as well as results of tensile tests on samples of the reinforcing batches and the
reported specification for the steel tube indicated that if any reinforcing element
had yielded, the strain on it was not enough to produce significant hardening. The
level of stress on the steel tube also indicated that there was no significant
hardening on the steel tube. This allowed the use of an elastic perfectly plastic
constitutive model to be used that simulates a bilinear stress-strain curve. The
Von Mises relation was considered appropriate to model these reinforcing and
steel tube elements. Since this constitutive model is very accurate in the
T Numerical Modeling using Nonlinear Finite Element Analysis 6.15
prediction of the bilinear stress strain curve, any variations in this model were not
considered in the parametric study. Poisson's ratio for steel was assumed to
remain constant throughout the analysis at a value of v=0.3.
The interface element set a nonlinear relation between tractions (normal and
tangential tractions) and relative displacement. The behavior of the interface
between the steel pile and the concrete plug is governed by friction behavior. This
behavior was modeled to the Coulomb friction model, which has closed
resemblance with the Mohr-Coulomb plasticity model. Coulomb friction is
illustrated in Figure 6.7.
c/tan§
The Coulomb friction model is basically given by the yield surface and the plastic
potential surface.
Numerical Modeling using Nonlinear Finite Element Analysis 6.16
(6.12)
(6.13)
with tan (ftic) the friction coefficient as a function of the internal parameter K, and
C{K) the cohesion as a function of the internal parameter K. The direction of the
irreversible displacements is given by the plastic potential function g where the
"uplift" is determined by the dilatancy angle y/.
To simulate the separation between concrete plug and steel tube, gap contact
criterion was used with Coulomb friction criterion. DIANA assumes that a gap
arises if the tensile traction tn normal to the interface exceeds a certain value.
After gap formation, tn is reduced to zero immediately. The tensile strength of 1
MPa was used for bond between the concrete and steel tube in normal direction.
As discussed in Section 5.4.6,results from the tests showed evidence of the effect
of concrete shrinkage on the deflection, slip and interface stiffness and shear/bond
transfer between concrete plug and the steel tube. Therefore, to compare the
measured results with the theoretical model and to evaluate the effect of
shrinkage, it was necessary to model the effect of shrinkage in the analytical
model.
The measurable effect of shrinkage had not been anticipated when the tests were
planned, and therefore no shrinkage or creep had been measured for the concrete
in these tests. The shrinkage and creep material properties were assumed based on
computer compressive strength and measured slump of the concrete batch.
„' 1 . L
r Numerical Modeling using Nonlinear Finite Element Analysis
The finite element program "Diana" has the capability to do time dependent
6.17
shrinkage and creep analysis. During the initial parametric study, it was found
that the level of compressive stressing concrete is lower than the compressive
strength of the concrete. Therefore, to minimize numerical errors, it was decided
to model the shrinkage and creep of the concrete considering only cracking
criteria and non-linearity of the interface. It assumes that the compressive
response of the concrete is elastic prior to cracking.
In the analysis of the concrete plugs embedded into the steel tube using the finite
element software DIANA, a method based on the European model code MC-1990
has been used to specify the creep and shrinkage behavior of the concrete material
on the basis of the physical parameters involved. Following is the brief
background of the model.
The mean shrinkage strain, which occurs within the time interval to to t is given
by
(6.14)
where
esho = basic shrinkage coefficient obtained from the product of 2 functions eShi and
(6.29)
Numerical Modeling using Nonlinear Finite Element Analysis 6.18
Psh {t) = function describing the development of shrinkage with time, which is
dependant on the notional thickness.
• Compressive strength 40 MPa for Stages 1 and 2, 50 MPa for pull-out and
push-out tests
• Hypothetical thickness h = 2Ag / u = 2 x length of concrete plug
• Loading age 28 days
• Relative humidity RH 60 %
• Average ambient temperature 20°
• Slump of 90 for pull-out and push out and 110 for Stage 1 and Stage 2
tests
The model allowed the specimens to undergo shrinkage after pouring the concrete
into the steel tube.
To account for the nonlinear response of the specimens to load, the NLFEA
solution procedure uses an incremental scheme. This scheme requires applying
incremental displacements to the specimen, and within each increment of
displacement, iterating to ensure that the internal and external forces balance.
IIS
T Numerical Modeling using Nonlinear Finite Element Analysis 6.19
Section 6.7.2 outlines the method used to determine the magnitude of the
increment of displacement, and this section outlines the iterations within each
displacement increment.
Section 6.7.2 outlines the displacement increments that were investigated during
the implementation of this numerical model. Within each increment of
displacement, the solution was iterated until satisfactory convergence was
achieved.
Through preliminary analysis, it was found that the Constant Stiffness Iteration
procedure was the most stable prior to the peak load for this implementation. At
each increment of displacement, the increment of external load is calculated using
a value of stiffness equal to the initial stiffness of the previous load step. This
stiffness is used to calculate the increment of applied external force (AFext)
corresponding to the applied displacement increment (Au). Application of the
shape functions leads to values of strain at the Gauss points which can be used to
calculate the increment of stress, hence the increment of internal force (AFjnt).
The relative energy calculated from these quantities (described in Section 6.6.2
below) is used to determine if a correct estimate of the internal forces, hence
stress field, has been achieved.
DIANA has three choices of criteria for checking convergence. These are the
force norm method, the displacement norm method, and the energy norm method.
The former of these >.wo criteria check only the force convergence, and
displacement convergence respectively. The latter of the options checks a
combination of the both (as energy is the product of force and displacement), and
was considered to be a stricter, hence more accurate means of checking
convergence; therefore, the latter was adopted.
Numerical Modeling using Nonlinear Finite Element Analysis 6.20
The variables of the initial parametric study are of three types. Firstly the interface
properties variable and then the concrete material properties variables as outlined
in Section 6.4, and the size of the load step. This division broke up the parametric
study on these variables into three parts. Firstly the material model variations for
the interface were examined. Secondly, the material model variables for concrete
were examined, and thirdly, the size of the load step was examined. The shrinkage
model was introduced after the material models and load steps calibrated against
test results. This section discusses the methodology of these studies.
It was considered that the experimental specimens that were chosen for the
purpose of comparison with the results of this parametric study should have the
failure mechanisms, ultimate strength and load-slip response that were obtained
throughout the experimental work.
In the absence of the basis experimental data, the material model variations for
interface outlined in Section 6.4.3 were varied as follows.
1) The values of initial stiffness were assigned values from lxlO 4 to lxlO8
N/mm in normal direction and from 1x10 to 1x10 in ngential direction.
2) The value of the cohesion c was varied from 0.1 to 3.0 MPa
The implementation considered firstly the value of the initial stiffness of the
interface, secondly, the value of the cohesion was considered, and finally, the
friction coefficient was considered
Numerical Modeling using Nonlinear Finite Element Analysis 6.21
The produced load-slip responses and ultimate strengths of the specimens from
the parametric study were examined against the test results. The best combination
of the material was then used to determine the effect of load step size on the load-
slip response as well as ultimate strength predictions.
The size of the subsequent steps was governed by two issues; firstly, the size had
to be reduced cracking and sudden slip on the interface influenced the results, and
if this was not done solutions schemes were found to be unstable: secondly, the
ratio between the initial step size when the specimen is uncracked, and that when
the specimen is cracked could not be too large. Trial and error in preliminary
analysis indicated that size of 0.01mm displacement increment resulted in a stable
scheme.
As stated in the objectives in Section 6.2, this research used NLFEA to examine
the results of ultimate strength, load-slip response, and bond/shear transfer along
the interface of specimens with different concrete plug lengths. To do this, three
stages of modeling were implemented as described below.
The first stage of modeling was the application of the solution scheme using the
material models, shrinkage factors and incremental scheme found to be best suited
using the parametric study outlined in Section 6.7 to representative specimens of
the experimental work to determine the best combination of the material
properties models as well as the best increment of displacement.
In the second stage of the modeling, the optimum combination of the above
model characteristics was applied to the experimental specimens to determine the
mmm; ;/
I Numerical Modeling using Nonlinear Finite Element Analysis 6.22
capability of NLFEA to predict the results. In this thesis, static test results from
pull-out, push-out, Stage 1 and Stage 2 were used to compare the ultimate
strength, load slip response, longitudinal and Hoop strains along the outer surface
of the steel tube and failure mechanisms. The NLFEA results then were used to
determine the bond stress distribution along the interface and effective
mechanisms in bond strength of the specimens.
The third and final stage of the modeling implemented the optimum modeling
scheme determined in Stages 2 and 3 specimens of the same material properties
model used in the experiments but with different aspect ratios for the steel tube.
The final results also are used for implementation of the bond strength adopted
formulation outlined in Sections 3.2.5, 3.4.5 and 5.6.
It should be noted that it was not possible to study the effect of varying the
percentage of longitudinal reinforcement. This was due to use of the highest
allowed percentage of reinforcement in the specimens. In NLFEA the incremental
deflection applied through the end of longitudinal reinforcement to simulate the
test procedure. Reduction of longitudinal reinforcement caused yielding of the
reinforcement and therefore, NLFEA cannot predict the ultimate strength and
complete load slip response of the specimens to be compared.
The specimens in stage two of the analysis (the experimental specimens) will be
labeled with the same identifying mark that was used in the experimental work;
e.g. Specimens S250 is the specimen with 250 length of concrete plug and
specimen S1.25D is a specimen with concrete plug length of 1.25 times of the
steel tube internal diameter. This is summarized in Tables 6.1.
Numerical Modeling using Nonlinear Finite Element Analysis 6.23
Table 6.1 Specimen numbers and material properties for Stage 2 numerical mode
The specimens in Stage three of the analysis (those models with different aspect
ratio) will be given the same tags, but these will be followed with the letters AS
and aspect ratio of the steel tube for variations of the aspect ratio of the steel tube.
This is summarized in Table 6.2.
Numerical Modeling using Nonlinear Finite Element Analysis 6.24
Table 6.2 Specimen numbers and material properties for final stage of numerical
model
Concrete
Tube Tube Tube Wall
Plug Aspect
Specimen ID Length Diameter Thickness
Length Ratio
(mm) (mm) (mm)
(mm)
AST-S250-15 500 250 14.8 15
to to to to to to to to to to to to
to to to to to to to to to to to to
to to to to to to to to to to to to
S250-PuJl-out
Concrete
Tube Tube Tube Well
Plug Aspect
Specimen ID Length Diamete Thickness
Length Ratio
(mm) r(mm) (mm)
(mm)
ON ON ON ON ON ON
en en en en en en
en en en en en en
en en en en en en
AST-S1.5D-15 222 14.8 15
S1.5D-Pull-out
ilili
Comparison of experimental results and theoretical models
7.1 Introduction
This chapter intends to verify the finite element analysis that was outlined in
Chapter 6. The following steps summarize the methodology adopted in the finite
element study.
1. Determine the ability of the selected material model combination and step
increment to predict the ultimate strength, load-slip response and failure
mechanisms of four series of specimens tested in experimental work.
3. Determine the effect of aspect ratio of the steel tube on the ultimate
strength, load slip response, failure mechanisms and bond stress
distribution along the pile/plug interface.
I iiS
r Comparison of experimental results and theoretical models 7.2
This study applied to all specimens of each experimental set. These are specimens
S250, S500 and S750 for pull-out tests, specimens S750 and S1000 for push-out
tests, specimens S1.0D and S1.5D for Stagel and S1.25 for Stage 2. Each
experimental set displayed different behavior and bond strengths that were
observed from the experimental work. This is due to the different curing
environments, specimen age (shrinkage), concrete characteristics and test
arrangements. The material properties of the interface elements were calibrated
against experimental results for each set of experiments to adjust these variations.
1. Comparison of the load vs. slip of the concrete plug into the steel tube
plots obtained for each of the material combinations with those produced
in the experimental work.
2. Comparison of the ultimate strength from experiment (Pu) with the peak
load obtained from NLFEA, (PU)NLFEA-
It would be useful to compare the longitudinal and Hoop strains, however, the
results from the experimental work only gave strains at a few points along the
steel tube. It was also possible that eccentricity in the specimen caused different
strains around the steel tube outside diameter. Therefore it was decided that these
factors would not be considered in this parametric study.
11. i'iii
Comparison of experimental results and theoretical models
Table 7-1 shows the most suitable material properties combinations for the
interface resulting from the initial parametric study. Dn and D22 are initial
stiffness in normal and tangential directions (N/mm), Ch is cohesion (MPa) and
tPh, tps are friction coefficients.
Table 7-1 The most suitable material properties combinations for the interface
elements
Specimens S750-2 and S750-3 in the push out test series were subjected to prior
pull-out load of 1000 kN. This is considered to be sufficient to partially overcome
the effect of shrinkage and improve the interface behavior. Therefore two finite
element models (push out and pre pull-out + pushout) with slightly different
interface element properties were used for specimen S750 of the push-out tests.
The interface element properties for the rest of the specimens were calibrated to
be equal in each test series.
r Comparison of experimental results and theoretical models
The present finite element model was verified by simulating four experimental
programs conducted at Monash University as outlined in Chapters 3V 4 and 5. To
verify the finite element models, which are simulating the behavior of concrete
plug specimens, four items are compared between the experimental and numerical
results. These are the ultimate strength, load-slip response, longitudinal and hoop
strains along the steel tube and failure mechanisms.
Table 7-2 below shows the comparison between the peak loads obtained from
experimental work with those obtained from the numerical analysis as well as the
relative error between these. In general, the NLFEA procedure has closely
predicted values of the peak load with a small amount of relative error; the
average relative error was 8.5 %, with a standard deviation of 6.0%.
NFELA over predicted the peak load of specimens S250-1 and S250-2 of the push
out test. This may be due to the higher effect of shrinkage on these specimens.
However, the predicted ultimate strength for this set of specimens is very close to
the experimental average ultimate strength of 855 kN for specimens S250. The
ultimate load was under predicted for specimens S250-3, S750-1 and S750-2.
Figure 3.7 in Chapter 3 shows that the ultimate strength for specimen S250-3 did
not adhere to the usual trend displayed through experimental results, and was
higher than the usual trend. Specimens S750-1 and S750-2 were subjected to prior
Comparison of experimental results and theoretical models 7.5
pull-out load. This was considered sufficient to overcome the effect of shrinkage
and improve the interface behavior. The higher relative error from NLFEA for
these specimens is thought to arise from this experimental inconsistency and
might also be caused by inconsistency of shrinkage. The NEFLA predicted the
ultimate load well for the rest of the specimens.
CO
S1.75D 395 368 0.93 6.8
S2.0D 1000 948 0.95 5.2
Average 0.99 8.5
Standard Deviation 6.0
For the purpose of this discussion, load-slip response comparisons for all
specimens of each series are presented in this section. Figure 7-1 to Figure 7-10
below show the load-slip comparison between the numerical model and test
results. Note that the load presented in the finite element results is the sum of
reactions.
Comparison of experimental results and theoretical models 7.6
S250-1
S250-3
1000-1
— S250-2
S250-3
-*-FEModel
800 -j
x 600-J
FEModel
400 •{
200 -I
1200 1
S500-2
1000-1
S500-1
S500-2
S500-3
*-FEModel
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
Slip (mm.)
S750-2
S750-1
-*-FEModel
S750-2
0.2 0.3
Slip (mm.)
Slip (mm)
-4.5 -4 -3.5 -3 -2.5 -2 -1.5 -1 -0.5 0
i i -T 1 1 1
S750-1
S750-2
S750-3
-*-FEModel
S750-1
Slip (mm)
-3 -2.5 -2 -1.5 -1 -0.5 0
S1000-1
s1000-2
-*-FEModel
800 i
Experimental Curve
700-
-*-FEMod ; »!
Experimental Curve
1 1.5
Slip (mm)
ti'-V.I&i'ij
Comparison of experimental results and theoretical models 7.9
Experimental Curve
-*-FEMode!
-i 1 1 r 1 1
Slip (mm)
-1.5 -1.3 -1.1 -0.9 -0.7 -0.5 -0.3 -0.1
Experimental Curve
-*-FEModel
Experimental Curve
T
Comparison of experimental results and theoretical models 7.10
Slip (mm)
-1.5 -1.25 •1 -0.75 -0.5 -0.25
-*-FEModel
Experiment Curve
Experimental Curve
Slip (mm)
-1.3 -1.1 -0.9 -0.7 -0.5 -0.3 -0.1
-*-FEModel
Experimental curve
J
-1200
In general NLFEA has produced results of the load slip response that capture the
trend of the experimental results. The results of all the specimens shown above
indicate that the slope of the load slip response from the NFELA is very close to
that of the experiments.
The results can be divided into two groups. The first group are specimens with
lower shrinkage effect, including S250, S500, S750 in pull out and S750 in push
out tests. For this group, although the ultimate load was closely predicted, the
initial stiffness was not as well predicted for the analytical model as it was for the
test specimen. However both analysis and experiment suggest a simple bilinear
relation. The position of the change of slope seems to indicate that the bond
resistance of the specimen changes from a non-slip action (chemical adhesion
between the interface of the concrete plug and the steel tube) to a very small slip
action (mechanical macro locking between the concrete core and the steel
surface). The higher initial stiffness (non-slip mechanism) in NFELA might be
due to the higher effect of shrinkage of the concrete plug in the tests. It could also
be due to different methods of slip measurements in NLEFA and the experiment.
However the analytical model closely predicted the ultimate load and stiffness of
the pile/plug interface after the mechanical macro interlock became active.
The second group are specimens with higher shrinkage effect due to the higher
age of the specimens and slump of concrete at the time of pouring. In this group,
both analysis and experiment suggest a simple bilinear relation. The position of
the change of slope seems to indicate that the bond resistance of the specimen
changes from a chemical adhesion to a mechanical macro locking between
concrete core and the steel surface.
The analytical model exhibited the same trend as the test results. It also showed
similar initial stiffness (non-slip mechanism), ultimate load and stiffness of
pile/plug interface after the mechanical macro interlock became active. The
results for specimens S1.25D, S1.75D and S2D from Stage 2 obtained from the
finite element study show that the reactions decrease when the peak load is
reached. This might be due to the limitation of NLFEA to model the post failure
Comparison of experimental results and theoretical models 7.12
It was clear that the load-slip behavior of the analytical model was close to that of
the experimental specimens, thereby providing an opportunity to investigate
trends in shear/bond transfer between the concrete plug and the steel tube.
The failure mechanisms were studied only for specimens S250 and S1.5D by
pulling the concrete plug out of the steel tube.
Figure 7-11 shows the completely pulled out concrete plug from the specimen
after the specimen failed in pull-out tests, and Figure 7-12 shows the principal
strain of the concrete plug after failure of the specimen from the finite element
analysis.
The specimens exhibited very similar failure mechanisms in both analytical model
and experiment. The failure mechanism displayed by the specimen in pull-out was
at the base of the concrete plug, where the steel tube contraction is much higher
than that of the concrete core, causing it to grip the concrete plug. The diagonal
tension crack formed in the concrete layer between the longitudinal reinforcement
and the steel tube. This crack appeared to correspond to a tension splitting of the
concrete plug at ultimate pull-out capacity of the specimen.
In push out failure, it was not possible to accurately investigate the failure of the
specimen due to damage of the interface by pulling the concrete plug out of the
steel tube. However, the observation during the test and results from NLFEA both
indicated that the failure occurred when the concrete plug separated at the
interface.
Comparison of experimental results and theoretical models 7.13
It can be concluded that the analytical model reasonably predicted the failure of
the specimen, particularly for the pull-out tests.
ID
Most of the specimens were strain gauged along the outer surface of the steel tube
within the length of the concrete plug. Both longitudinal and Hoop strain gauges
were used. The purpose of these gauges was to determine the load transfer
mechanism from the concrete plug to the steel tube. Figure 7-13 illustrates the
strain gauge arrangements for specimens S1.0D and S1.5D. Appendix 1 shows
the strain gauge arrangements for all specimens.
t ~J CoL .
1
s
IB
1 : .
I—I—I
H Specimen
I
gji Specimen
S222 S333
Figure 7-13 Strain gauge locations for specimens S1.0D and S1.5D
NLFEA also produced the longitudin?J and Hoop strains along the outer surface
of the steel tube. The experimental and numerical longitudinal and hoop strains
along the outer surface of the steel tube element at two selected load levels for
one specimen of each experimental set are compared in Figure 7-14 to Figure
7-21. At each load level, the experimental and numerical load levels are selected
to be as close as possible.
T Comparison of experimental results and theoretical models 7.16
2.50E-04 -1
c 1.50E-04-
'jo
Logit udina
1.00E-04- •
5.00E-05 •
n nnPaj^n .
1.20E-04
A Hoop strain from NLFEA
1.00E-04- • Hoop strain of S250-3
8.00E-05 -
6.00E-05 -
4.00E-05 -
2
2.00E-05 -
X O.OOE+00
Figure 7-14 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S250 of the pull-out test at load level of 333 kN
Comparison of experimental results and theoretical models 7.17
5.00E-04
A Longitudinal srain from NLFEA
• longitudinal strain of S250-3
4.00E-04
3.00E-04-
«
1
|
O 1.00E-C4
0.00E+00
-1.00E-04
50 100 150 200 250
Distance from bottom of the concrete plug (mm)
3.00E-04
A Hoop strain from NLFEA
2.50E-04 H • Hoop strain of S250-3
2.00E-04 -
c 1.50E-04H
Figure 7-15 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S250 of the pull-out test at load level of 662 kN
Comparison of experimental results and theoretical models 7.18
-0.0002 -
2 -0.0004-
(0
0.00035
& Hoop strain from NLFEA
• Hoop strain from S750-2
0.0001 -
0.00005 -
Figure 7-16 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S750 of the push-out test at load level of 1452 kN
Comparison of experimental results and theoretical models 7.i9
0
-0.0002 A Longitudinal strain from NLFEA
• | -0.0006
5 -0.0008
a
•E -0.001
« -0.0012
O -0.0014
0.0006
& Hoop strain from NLFEA
0.0005 - • Hoop strain from S750-2
0.0004 -
I 0.0003 •
0.0002 -
0.0001 -
0
100 200 300 400 500 600 700
Distance from the bottom of the concrete plug (mm)
Figure 7-17 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S750 of the push-out test at load level of 2747 kN
Comparison of experimental results and theoretical models 7.20
0.0004
A Longitudinal Strain from the NLFEA
0.00035^ • Longitudinal strain from test result
0.0003 -
0.00025 -
0.0002 -
CO
| 0.00015 -
0.0^01 -
o>
O 0.00005 -
0
-0.00005 -
-0.0001
50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm.)
A
A Hoop strain from NLFEA A
0.00025 - A
• Hoop strain from the test results A
0.0002 -
£
c 0.00015-
0.0001 - AA
A
A
O 0.00005 - £ AAAAAAAAAi
O
u • ' A ^ '
AA
-0.00005 - AA
-0.0001 -
-0.00015 -
() 50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm.)
Figure 7-18 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.5D of the Stage 1 at load level of 572 kN
Comparison of experimental results and theoretical models 7.21
0.0008 -1
0.0007 - A Longitudinal Strain from the NLFEA
A
0.0005 - A
0.0004-
cu A
0.0003 - • A
AA^^ A A A A A A
0.0002 •
A A
A # .
<j 0.0001 -
o- ' A
A A
-0.0001 • • A
* ^
-0.0002 J
() 50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm.)
0.0003 -
0.0002 -
| 0.0001 H
a
§
X 0
-0.0001 •
A Hoop strain from NLFEA
• Hoop strain from the test results
-0.0002
50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm.)
Figure 7-19 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.5D of the Stage 1 at load level of 1000 kN
Comparison of experimental results and theoretical models 7.22
0
-0.0001
-0.0002
c
'jo -0.0003
J? -0.0004
n
£ -0.0005
.•§ -0.0006
O -0.0007
-0.0008 Longitudinal strian from NLFEA
-0.0009 Longitudinal strain from the test results
-0.001
-100 -50 0 50 100 150 200 250 300
Distance from bottom ofjhe concrete plug (mm.)
0.00035
A Hoop strain from NLFEA
0.0003 [__ 9 Hoop strainjrom the test results
0.00025
£
S 0.0002
v>
§ 0.00015
X
0.0001
0.00005
Figure 7-20 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.25D of the Stage 2 at load level of 222 kN
Comparison of experimental results and theoretical models 7.23
0
A A.A
A A
-0.0002 A
A**
-0.0004 -
*ain
A ^
w -0.0006 -
jdinal
-0.0008 -
A
-0.001
AAA^W
Lot
A LAAAAA
-0.0012
ft nr\c\a
0.0005
0.0004 AA
c
2
•
£ 0.0003
0.0002
A
0.0001 A
A Hoop strain from NLFEA A
A
• Hoop strain from the test results A
A
0 I 1 1 1 1 1 1 1 1
-100 -50 0 50 100 150 200 250 300
Distance from bottom of the concrete plug (mm)
Figure 7-21 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.25D of the Stage 2 at load level of 440 kN
Comparison of experimental results and theoretical models 7.24
The load slip response curves indicate that the specimens exhibited a bilinear
response of two bond resistance mechanisms of an early micro locking (non-slip
action) and later a mechanical interlocking mechanism. The comparisons between
numerical and experimental longitudinal and Hoop strains were made first at a
load level before change of slope in load slip response (micro locking mechanism)
and then at the peak load (mechanical macro interlocking mechanism).
In most, cases, gauge readings from the experiments are in better agreement with
the numerical model at the peak load. The reason might be the application of the
Coulomb friction model for the interface element. In other words, the Coulomb
friction model for the pile/plug interface closely predicted the behaviour after the
macro mechanical interlocking mechanism became active.
In general, NLFEA has produced results of the longitudinal and hoop strains that
follow the trend of the experimental results. The results of the specimens shown
above indicate that the strain distributions from the analytical model were close to
that of the experimental specimens, thereby providing an opportunity to
investigate trends in shear transfer distribution along the interface. Appendix 2
shows the longitudinal and Hoop strain comparisons for all specimens.
The finite element models with the material models and properties adopted
produced comparable results to the experiment. The numerical peak loads were in
very good agreement with the experimental peak loads. The load-slip response,
failure mechanisms and longitudinal and hoop strain distributions along the outer
surface of the steel tube profiles of the numerical models were similar to the
experimental results, with the trends simulated adequately. Therefore, the results
of the finite element models are valid. In the sections to follow, the bond stress
distribution along the interface is studied and a parametric study is carried out
using the models with material properties outlined earlier as the basis for
comparison.
Comparison of experimental results and theoretical models 7.25
In the pull out case, the reverse is expected to occur. That is, near the base of the
concrete plug, the steel tube contraction is much higher than that of the concrete
core, causing it to grip the concrete plug. Near the top part of the plug, the tension
force is transferred to the concrete through the reinforcing bars embedded in the
concrete core and in the pile cap. The tensile stresses that develop in the concrete
core result in contraction of the concrete, while the steel tube contraction is
relatively small. This should result in separation occurring between the steel tube
and the concrete. Considering the fact that deformed bars are used as
reinforcement, the ribs on the bars tend to impart wedge pressure on the outer
concrete layer, causing dilation of this layer. This dilation enhances the frictional
stresses between the steel tube and the concrete along of the length equal to
embedment of the longitudinal reinforcement from the top of the specimen.
Consider that the steel tube is subjected to radial contact forces along an arbitrary
circle of the tube. Because of the symmetry of such loading, every section normal
to the axis will remain circular, while the radius R will undergo a change AR = y,
varying along the length of the plug. The radial displacement y can be regarded as
deflection for a longitudinal element of the tube, and hence it is seen that the
Comparison of experimental results and theoretical models 7.26
assumed loading will set up bending stresses in the longitudinal elements. This
situation is analogous to the case of beams on elastic foundations (Heteyni, 1964).
It can be seen that mechanical macro interlock mechanisms at the top and bottom
of the specimens caused the radial pressure on the steel tube. The differential of
radial pressure along the steel tube applied longitudinal bending moment on the
tube. Since the bending of the tube wall is a plane strain environment, it follows
that Mc = -ju My in the circumferential ring, where My is the longitudinal bending
moment and ju is Poisson's ratio for the steel tube. The analytical model clearly
demonstrated this phenomenon.
Distribution of bending moment along the steel tube indicates that at an early
stage of loading, the pronounced Poisson's ratio effect increases radial contact
stress and mechanical interlock at the top and bottom of the interface. In pull-out
at top, the dilation of the concrete increased the contact pressure between the steel
bars and the steel tube, due to the wedging action exerted by the deformed steel
bars against the concrete layer.
The bending moment distribution at ultimate load level indicated that the diagonal
tension crack had formed and extended in the concrete layer between the
longitudinal reinforcement and the steel tube before the failure of the specimens.
It should be noted that the measured longitudinal and Hoop strains on the outer
surface of the steel tube from the experiment is due to the axial pull out force,
together with longitudinal bending moment along the steel tube. Therefore, the
measured strain could not be used to obtain the bond stress distribution along the
interface.
Comparison of experimental results and theoretical models 7.27
40 A^ A
20
E
0
Jk ^AA^jAUWJAAaAA^
-20
-40 A \
-60 A
\
-80 - A
A
A
A A
A
-100
-120
50 100 150 200 250
Distance from bottom of the concrete plug (mm)
-200
50 100 150 200 250
Distance from bottom of the concrete plug (mm)
Figure 7-22 Bending moment distribution along the steel tube for specimen S250
of the pull-out test
Comparison of experimental results and theoretical models 7.28
400
-100-
-200
100 200 300 400 500 600 700
Distance from the bottom of concrete plug (mm)
300
200
Figure 7-23 Bending moment distribution along the steel tube for specimen S750
Figure 7-24 Bending moment distribution along the steel tube for specimen S1.5D
(Stage 1)
Comparison of experimental results and theoretical models 7.30
500
-A-Longitudinal bending moment
400
300
•A - * - Circumferential bending moment
1 " 200
Z 100
1 -100
-200
-300
-400
V
-100 -50 0 50 100 150 200 250 300
Distance from bottom of the concrete plug (mm.)
700
500
E 300
\
10
§ °
2 -100
Figure 7-25 Bending moment distribution along the steel tube for specimen
S1.25D(Stage2)
Comparison of experimental results and theoretical models 7.31
To calculate the bond stress distribution along the interface, longitudinal stress
along the steel tube at outer surface, centre line and inner surface of steel tube's
wall are plotted. Figure 7-26 to Figure 7-29 illustrate the computed longitudinal
stress distribution for one specimen for each experimental set. Appendix 4 shows
the longitudinal stress distribution for all specimens at ultimate load level and at
load level of changing the slope of load-slip response. The longitudinal stress
distributions are shown at outer and inner surfaces and centre of the steel tube's
wall. The stress distribution at the outer and inner surfaces of the steel tube cannot
present the bond stress distribution due to the effect of bending moment. The
stress distribution at the centre of the steel tube wall is used to determine the
shear/bond stress distribution along the interface.
In the pull-out case, there is little shear transfer at the top of the specimens at an
early stage, which indicates that the main mechanism is the pronounced Poisson's
effect increasing radial contract stress at the base of the concrete plug. The
longitudinal stress distributions at ultimate load level show that the cracking of
the concrete at the base of the concrete plug due to tension splitting, reducing the
shear transfer. The main mechanism which is believed to contribute to the bond
strength in pull out tests was the dilation of the concrete due to the wedge action
exerted by the deformed steel bars against the concrete layer between the steel bar
and the steel tube. For the push-out tests and specimens with longer length of
concrete plug, the longitudinal stress distributions illustrated almost a uniform
bond stress distribution along the steel tube.
In general, the results of longitudinal stress distribution from the NLFEA at the
centre of the steel tube's wall show almost a linear distribution along the length of
the tube. Therefore, it can be adopted and idealized that the shear/bond stress
distribution is a uniform distribution along the interface, particularly at ultimate
load level. The slope of the longitudinal stress distribution along the steel tube at
the centre of the steel tube's wall can be used to determine the value of uniform
bond stress between the steel tube and the concrete plug along the pile/plug
interface.
Comparison of experimental results and theoretical models 7.32
2.
sN
§. 30
w
w
2
1a 20
Stress at inner surface
'•5
•5, 10
I
Stress at outer surface
-10
-100 -50 0 50 100 150 200 250
Distance from bottom of the concrete plug (mm)
100
Stress at outer surface
90
80
70
/
60 Stress at the center
50
40
30
20
10
o i—
-100 -50 0 50 100 150 200 250
Distance from bottom of the concrete plug (mm)
Figure 7-26 Longitudinal stress distributions along the steel tube for specimen
S250 of pull-out test
Comparison of experimental results and theoretical models 7.33
-20
1 -40 -
-60 -
u
-80
jdinal sti
7 jy^
/ ij^
1 Ww
-120
5 -140
-160
-
/ *r
3 X
V
-180 • ^^^^
^ ^ ^ ^
(A
W Stress at inner surface
S!
5 CO
xi
Stress at the centre
'5)
o
-400
-100 0 100 200 300 400 500 600 700
Distance from the bottom of the concrete plug (mm)
Figure 7-27 Longitudinal stress distribution along the steel tube for specimen
1 (<
Comparison of experimental results and theoretical models 7.34
70
Pa)
60
Stress at inner surface
CA 50
Stress at the
ICff
40 center
15 30
20
O>
10
Stress at outer surface
0
-10
-100 -50 0 50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm)
140 .L.++H-
Stress at outer surface
S. 120
(A 100
5M
CO
80 Stress i
center
60 Stress at inner surface
3
'5> 40
o
20
0
-100 -50 0 50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm)
Figure 7-28 Longitudinal stress distribution along the steel tube for specimen
/<vi" 1 •
Comparison of experimental results and theoretical models 7.35
-20
.•A
S. -40
XT -60
(A
Stress at outer surface
§ -140
-180
-100 -50 0 50 100 150 200 250 300
Distance from bottom of the concrete plug (mm)
« -50
vr
a.
1 -150
CO Stress at the
centre
| -200
5>
9 -250
Stress at inner surface
-300
-100 -50 0 50 100 150 200 250 300
Distance from bottom of the concrete plug (mm)
Figure 7-29 Longitudinal stress distribution along the steel tube for specimen
S1.25DofStage2test
Comparison of experimental results and theoretical models 7.36
Examination of the results of NLFEA from the modelling of the specimens tested
as part of the experimental work in this research indicates the following:
Since good correlation between NLFEA and the test results was obtained in
regards to the ultimate strength, load-slip response and longitudinal and Hoop
strain, the solution scheme was applied to specimens identical to those of the
experiments but without the unintentional variations in the material properties.
This study investigates the effect of varying the aspect ratio of the steel tube on
the ultimate strength and load-slip response of the specimens outlined in Section
6.7. The failure, ultimate strength and slip were determined based on the criterion
used for the base models described earlier.
As established in Section 7.3.2, the load slip curves give an indication of the bond
mechanisms and behaviour of the concrete plug in the steel tube that is predicted
by implementation of the NLFEA procedure. Figure 7-30 to Figure 7-33 illustrate
the load-slip relationship produced from the numerical models for one specimen
from each experimental set with aspect ratio of 15 to 40 for steel tube. Appendix 5
shows the produced load-slip response form NFLEA for all specimens with aspect
ratios of 15 to 40.
It can be seen that the specimens with higher aspect ratio show smaller relative
slip at the same displacement increments. Consequently, the relative slip between
the concrete plug and the steel tube at the end of the numerical procedure is
smaller for higher aspect ratios. This was due to the lower circumferential
stiffness of the steel tube with higher aspect ratio, which allows the concrete plug
and the steel tube to expand laterally and reduce longitudinal deflections.
The load-slip curves also indicated that the specimens with shorter concrete plug
length and higher shrinkage are more sensitive to variation of the aspect ratio of
the steel tube.
i
Comparison of experimental results and theoretical models 7.38
1400
Aspect ratio of 15
Aspect ratio of 20
Aspect ratio of 25
Aspect ratio of 30
Aspect ratio of 35
Aspect ratio of 40
Figure 7-30 Load-slip behaviours of varying the aspect ratio of the steel tube for
specimen S500 in pull-out test
Aspect ratio of 15
Aspect ratio of 20
Aspect ratio of 25
Aspect ratio of 30
Aspect ratio of 35
Aspect ratio of 40
-3 -2
Slip (mm)
Figure 7-31 Load-slip behaviours of varying the aspect ratio of the steel tube for
specimen S750 in push-out test
Comparison of experimental results and theoretical models 7.39
1000
900
800-
700-
' 600-
-Aspect ratio of 15
500-
-Aspect ratio of 20
o 400
-Aspect ratio of 25
300 -Aspect ratio of 30
200 -Aspect ratio of 35
100 -Aspect ratio of 40
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Slip (mil)
Figure 7-32 Load-slip behaviours of varying the aspect ratio of the steel tube for
specimen S1.5D in Stage 1 test
- • - Aspect ratio of 20
-*-Aspect ratio of 25
-••-Aspect ratio of 30
-•-Aspect ratio of 35
- • - Aspect ratio of 40
-1000
-0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1
Slip (mm)
Figure 7-33 Load-slip behaviours of varying the aspect ratio of the steel tube for
specimen S750 in push-out test
Comparison of experimental results and theoretical models 7.40
In general, the solution procedure does not predict any significant variation in the
ultimate strength of the specimens due to variation of the steel tube aspect ratio of
15 to 40. It can also be seen that the load slip responses of specimens with aspect
ratios ranging from 15 to 40 exhibited a similar trend. The solution scheme
predicts a smaller relative slip for specimens with the greater aspect ratio.
However, it might be concluded that the variation of the steel tube aspect ratio
ranging from 15 to 40 has no major influence on ultimate strength and load slip
behaviour of the concrete plug embedded in the tubular steel pile.
The above sections presented an investigation into the suitability of non linear
finite element analysis to predict the response of concrete plugs embedded into
the steel tubular piles subjected to a pull-out or push-out load regimes. The study
examined the sensitivity of the solution scheme to combinations of the material
models that described the tension and compression response and shrinkage of the
concrete as well as the frictional behaviour of the interface and displacement
increment on the. solution obtained. Once the optimum combination of these was
established, the procedure was implemented to investigate the accuracy of
predicting ultimate strength, load slip response, failure mechanisms and
longitudinal and Hoop strains along the steel tube as compared with the
experimental work. After the capabilities and limitations of the numerical scheme
were established, it was applied to a set of specimens with only the aspect ratio of
the steel tube as the variable. The following were concluded from this study:
1. The accuracy of the scheme and the prediction of the load deflection
response are highly dependent on the choice of the frictional behaviour of
the interface and shrinkage of the concrete. It is concluded that an
application of a combination of the crack model and shrinkage based on
European code of MC1990, for the concrete and Coulomb friction model
for the interface are most suited to the specimen above.
Comparison of experimental results and theoretical models 7.41
5. NLFEA has shown that mechanical macro interlock mechanisms at the top
and bottom of specimens caused the radial pressure on the steel tube. The
differential of radial pressure along the steel tube applied longitudinal and
circumferential bending moment on the tube. The measured longitudinal
and Hoop strains on the outer surface of the steel tubes are due to the axial
pull out force, together with longitudinal bending moment along the steel
tube.
6. NLFEA has shown that the longitudinal stress distribution at the centre of
the tube's wall is almost a linear distribution along the length. Therefore,
it can be assumed that the shear/bond stress distribution is a uniform
distribution along the interface particularly at ultimate load level.
7. NLFEA predicts that varying the aspect ratios of the tubes from 15 to 40
has no significant effect on ultimate strength and load slip response of a
concrete plug.
T
Bond Strength Formulation 8.1
8.1 Introduction
In the 'Pull-out and push-out tests' (Chapter 3) and 'Presentation of cyclic loading
test results' (Chapter 5), the OTO's formulation (2001) was adopted to calculate
bond stress between the concrete plug and the steel tube. The bond stress was
assumed to be distributed uniformly around the inside diameter and along the
interface. This was also suggested by NLFEA results.
(8-1)
where:
(8-2)
Where:
m is the modular ratio of steel to plug
Dp is the pile diameter
tp is the pile wall thickness
The available data on the parameter C, are limited. In the absence of data relating
to a specific tubular geometry and with regard to ths test results of previous pull-
out and push out tests (Chapter 3), the following values of Ct were assumed:
UDP
<1.50 1.0
1.5-3.0 0.9
>3.0 0.8
where L is the plug length.
COMPRESSIVE BOND
SPECIMEN K L/D cL STRENGTH Cs STRESS
(MPA) MPA
S250-1 0.1 1.06 1.0 50 0.6 4.07
S250-2 0.1 1.06 1.0 50 0.6 4.07
S250-3 0.1 1.06 1.0 50 0.6 4.07
S750-1* 0.1 3.37 0.9 50 0.6 3.46
S750-2* 0.1 3.37 0.9 50 0.6 3.46
S750-3 0.1 3.37 0.9 50 0.6 3.46
S1000-1 0.1 4.50 0.8 50 0.4 2.04
S1000-2 0.1 4.50 0.8 50 0.4 2.04
S1.0D 0.1 1.0 1.0 40 0.6 3.43
S1.5D 0.1 1.5 1.0 40 0.6 3.43
S1.25D 0.1 1.25 1.0 40 0.4 2.29
S1.75D 0.1 1.75 0.9 40 0.4 2.06
S2.0D* 0.1 2.0 0.9 40 0.6 3.09
Bond Strength Formulation 8.3
For normal internal surface of the pile, in the absence of the test data, Cs was
taken as 0.6 for pull-out and Stage 1 pull-out tests and 0.4 for push out and Stage
2 push out tests to consider the effect of shrinkage and age of concrete, which
reduce the contact area of the interface. Table 8.1 shows factors and bond strength
calculated from previous chapters.
This formulation will be calibrated again based on test results and new findings
from the NLFEA. Table 8-2 shows comparisons of bond strength obtained from
the experiment, numerical procedure and formulation and relative errors between
the experiment and the calculated bond strength. The bond strength formulation
has closely predicted values of the bond stress with a small relative error of 21.5
and standard deviation of 17.8.
In this section, the factors in the Eq. (8-1) will be reviewed and calibrated against
experimental results and NLFEA results and findings.
= [m{D/t)tY+[D/t)p - l
NLFEA predicts that varying aspect ratios of the steel tubes from 15 to 40 has no
significant effect on ultimate strength and load slip response of a concrete plug in
the steel tube (Section 7.6).
In the case of long-term loading, the values of m must be modified to account for
creep effect of concrete. A creep factor of 2 is considered acceptable. This results
in an m value of m = 2 x 5.5 =11. Accordingly, Eq. (8-3) may be written as:
The test results and NLFEA study indicated that the surface condition is a very
important parameter in calculating the bond strength of the specimen. This is due
to the effect of surface condition on macro mechanical interlock between the
concrete and the steel tube. The study shows that the shrinkage highly reduces the
surface condition factor. The most suitable material properties for the interface
element were obtained from the initial parametric study of numerical modeling
(Section 7.2).
The results of the initial study are used to calibrate the surface condition factor.
Specimens S750, two of which were subjected to prior pull-out load were
excluded
Table 8.3 shows the calibrated value for surface condition factors and comparison
between new calculated bond strength using Equation (8-3) and the experiment.
Bond Strength Formulation 8.6
The comparison of the experimental bond strength with calculated bond strength
from Equation (8-3) using the calibrated surface condition factors shows that the
calculated values for the bond stress are in a better agreement with the
experimental results. The relative error is 13.7 with a standard deviation of 15.1.
Table 8-3 Comparison of bond strength from calibrated surface condition factor
with experiment
CALCULATED BOND
CALCULATED/ RELATIVE
BOND STRENGTH
SPECIMEN cL Cs STRENGTH FROM
MEASURED ERROR
BOND (%)
(MPA) EXPERIMENT
S250-1 1.0 0.7 4.45 4.8 0.93 7.2
S250-2 1.0 0.7 4.45 4.3 1.04 3.6
S250-3 1.0 0.7 4.45 6.2 0.72 28.1
S750-1 0.9 0,7 4.01 6.83 0.59 41.3
S750-2 0.9 0.7 4.01 7.33 0.55 45.3
S750-3 0.9 0.7 4.01 4.96 0.81 19.2
S1000-1 0.8 0.4 2.04 2.06 0.99 1.1
S1000-2 0.8 0.4 2.04 2.02 1.01 0.8
S1.0D 1.0 0.7 3.98 4.2 0.95 5.1
S1.5D 1.0 0.7 3.98 4.3 0.93 7.3
S1.25D 1.0 0.45 2.56 2.38 1.08 7.6
S1.75D 0.9 0.3 1.54 1.45 1.06 6.0
S2.0D 0.9 0.6 3.07 3.27 0.94 6.0
Average 0.89 13.7
Standard Deviation 15.1
variation of the material properties, this study suggests that no reliable surface
condition factor can be achieved. Therefore, in the absence of experimental and
numerical analysis results, it is recommended to use minimum values of surface
condition factors for design purposes.
The test results and the NLFEA study showed that the coefficient of concrete plug
length is also an effective parameter in the bond strength of the specimen. This is
due to the effect of concrete plug length on maximizing the macro mechanical
interlock between the concrete and the steel tube.
The comparison of calculated bond strength from Equation (8-3) using the
calibrated surface condition factors and the OTO's(2001) recommendations for
coefficient of plug length with experimental bond strength shows that the
calculated values for the bond stress are in a good agreement with the experiment.
Therefore the OTO's recommendations would be used in the bond strength
formulation.
The sections above presented a revision of the suitability and calibration of the
bond strength formulation, which was initially developed in Chapters 3 and 5.
The formulation was examined to match the experimental results with NLFEA
results. The following formulation was concluded from this study:
And
where:
L/Dp c,
<L50 1.0
1.5-3.0 0.9
>3.0 0.8
and
The surface condition factor from 0.3 to 0.7 is proposed in this investigation. In
the absence of experimental and numerical analysis results, it is recommended to
use minimum values of surface condition factor for design purposes.
I
Conclusions and further work 9.1
The research presented in this thesis implemented strategies to examine the bond
strength of concrete plugs embedded in tubular steel piles subjected to pull-out,
push-put and cyclic loadings. This task was undertaken in four tiers of work, as
follows.
• Evaluation of the bond strength and bond stress distribution along the
interface in different loading regimes, by development of an experimental
technique, associated analytical relation and a bond strength formulation
that enable calculation of the bond strength.
.
Conclusions and further work 9.2
It is the purpose of this section to draw general conclusions from this research.
The conclusions specific to each of the four tiers of the work are presented at the
end of the relevant section. These general conclusions are as follows:
Failure Mechanisms
The failure mechanism displayed by the specimen in pull out was at the base of
the concrete plug, where the steel tube contraction is much higher than that of the
concrete core. The diagonal tension crack formed in the concrete layer between
the longitudinal reinforcement and the steel tube, where it extended to the end of
the steel bars and then in the hoop direction. This crack appears to correspond to a
tension splitting of the concrete plug at ultimate pull-out capacity of the
specimen.
Effect of shrinkage
Shrinkage in the concrete plug was shown to contribute to loss of composite
action and ultimate strength. Shrinkage caused an increase in slip, and a reduction
in shear/bond transfer and stiffness of the inter/ace. Shrinkage increased the effect
of repeated loading on the rate of slip growth between the concrete plug and the
steel tube.
the rate of slip growth (mm/cycle) were obtained from the experimental data as
follows:
(0.255—-0.899)
Symmetric cyclic loading, slip growth per cycle = 1 0
Where,
And
where:
UDD
The surface condition factor from 0.3 to 0.7 is proposed in this investigation. In
the absence of experimental and numerical analysis results, it is recommended to
use minimum values of surface condition factor for design purposes.
1. The work of this thesis is based on steel tube with 244 mm diameter and
aspect ratio of 22. Tests need to be undertaken on 200 to 600mm steel tube,
and aspect ratio of 20 to 50, as these are the sizes used by industry, to see if
the phenomenon exists to the same degree.
2. The tests in this thesis were all aimed at two concrete strengths, when the
other parameters varied. A range of tests should be conducted with concrete
strength as the variable to investigate the effect that concrete has on ultimate
strength, bond strength, load slip response and shear transfer distribution
along the interface in pull-out and push-out tests as well as incremental slip in
cyclic loading.
3. The twelve specimens tested in cyclic loading were only tested under
symmetrical cyclic loading. Tests should be undertaken on specimens with
different cyclic load regimes.
4. The tests in this thesis were all aimed at similar interface surface condition.
Tests need to be undertaken on different conditions of the interface surface to
study the effect that surface condition has on bond strength, load slip response
and bond stress distribution along the interface.
5. The specimens in this investigation were all tested under concentric axial
loads. Tests should be undertaken on specimens under eccentric loads.
Conclusions and further work 9.7
REFERENCES
ACI committee 318, "Building Code Requirements for structural Concrete (ACI
318-99) and commentary (318R-99)," American Concrete Institute,
Farmington Hill, Mich., 1999, pp391
Al-Mahaidi5 R., Grundy, P., Bean, W. (1999) " Pullout Strength of Concrete
Plugs in Tubular Piles" Proceeding, International Offshore and Polar
Engineering Conference, Brest, France, pp. 24-29
BSI 1979, BS5400 Steel, Concrete and Composite Bridges. Part 5 Code of
practice for design of composite bridges, British Standards Institution,
London
DIANA (1998) Finite Element Analysis User's Manual, Release 7.0, TNO
Building and Construction Research.
Fam, A. Z., and Rizkalla, S. H. (2001). "Confinement Model for Axially Loaded
Concrete Confined by Circular Fiber-Reinforced polymer tubes." ACI
Structural Journal, V. 98, No. 4, July-August 2001,451-461
Hajjar, J. F.; and Gourley, B. C. (1999). " A Cyclic Nonlinear Model for
Concrete-Filled Tubes." Journal of Structural Engineering, ASCE, Vol.
123, No.6, June 1997, pp. 736-744
Knowels, R. B., and Park, R. (1969). " Strength of concrete filled steel tubular
columns." J. Struct. Div., ASCE, 95(12), 2565-2587
Knowels, R. B., and Park, R. (1970). " Axial load design for concrete filled steel
tubes." J. Struct. Div., ASCE, 96(10), 2125-2153
Lahlou, K.; Lachemi, M. ; and Aitcin. P.-C. (1999). " Confined High-Strength
Concrete under Dynamic Compressive Loading." Journal of Structural
Engineering, ASCE, Vol. 125, No.10, October.1999, pp. 1100-1108
m
References R.4
Mender, J. E.; Priestley, M. J. N.; and Park. R. (1988). " Observed Stress-Strain
Behavior of Confined Concrete." Journal of Structural Engineering.,
ASCE, V.114, No.8, Aug.1988, pp. 1827-1849
Sakino, K., Tomii, M., and Wananabe, K. (1985). " Sustaining load capacity of
plain concrete stub columns by steel tubes." Proc, Int. Spec. Conference
on Concrete-Filled Steel Tubular Struct., 112-118.
Shams, M., and Saadeghvaziri, A (1997). " State of the Art of Concrete-Filled
Steel Tubular Columns." ACI Structural Journal, V. 94, No. 5, September-
October 1997, 558-571
Tomii, M., Yoshimura, K., and Morishita, Y. (1977). " Experimental studies on
concrete filled steel tubular stub columns under concentric loading.'' Proc,
Int. Colloquium on Stability of Struct. Under Static and Dynamic Loads,
718-741.
•m
Appendix 1 -Strain gauge arrangements Al.l
This appendix presents the strain gauge arrangements for all specimens.
SECTION A-A
SECTION A-A
s?
o
m
100
|
S
175
SECTION A-A
E
| _
c
6
175
_100
A I M
& CO
CO
SECTION A-A
One longitudinal gauge
One transverse gauge
SECTION A-A
One longitudinal gauge
One transverse gauge
SECTION A-A
One longitudinal gauge
One transverse gauge
SECTION A-A
One longitudinal gauge
One transverse gauge
SECTION A-A
One longitudinal gauge
One transverse gauge
2.50E-04
J 1.00E-04-
3
O)
3 5.00E-05-
1 20E-04 -l
A Hoop strain from NLFEA
t
1.00E-04- • Hoop strain of S250-3 A
A
A
8.00E-05 - A
A
A
A
6.O0E-O5 -
c 4.00E-05 •
s J
2.00E-05 •
a
o
o
X
-2.00E-05 - • * —
-4.00E-05 •
-6.00E-05 m ^
Q nnc AC .
-O.UUC-UO
Figure A2-1 Comparison of longitudinal and Hoop strain's along the outer surface
of the steel tube for specimen S250 of the pull-out test at load level of 333 kN
i :
Appendix 2 -Comparison of longitudinal and Hoop strains A2.3
5.00E-04
A Longitudinal srain from NLFEA
• longitudinal strain of S250-3
-1.00E-04
50 100 150 200
Distance from bottom of the concrete plug (mm)
3.00E-04
Hoop strain from NLFEA
2.50E-04 • Hoop strain of S250-3
2.00E-04 -
c 1.50E-04 -
i
1.00E-04
Figure A2-2 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S250 cf the pull-out test at load level of 662 kN
Appendix 2 -Comparison of longitudinal and Hoop strains A2.4
2 1.50E-04 -
w
75
•j= 1.00E-04 -
I * 5.00E-05 -I
O.OOE+00
-5.00E-05
100 200 300 400 500
Distance from bottom of the concrete plug (mm)
1.20E-04
1.00E-04 - A Hoop srain from NLFEA
• Hoop strain of S500-1
8.00E-05 -
6.00E-05 -
•C 4.00E-05 -
CO
* 2.00E-05 -
§ O.00E+0O
-2.00E-05 -
-4.00E-05
-6.00E-05
-8.00E-05
50 100 150 200 250 300 350 400 450 500
Distance from bottom off the concrete plug (mm)
Figure A2-3 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S500 of the pull-out test at load level of 334 kN
Appendix 2 -Comparison of longitudinal and Hoop strains A2.5
8.00E-04 7
-1.00E-04H
-2.00E-04
0 50 100 150 200 250 300 350 400 450 500
Distance from bottom of the concret plug (mm)
1.50E-04 -
arin
1.00E-04 •
5.00E-05 • • A
O
n
-5.00E-05 •
-1.00E-04 •
f
0 50 100 150 200 250 300 350 400 450 500
Distance from bottom of the concrete plug (mm)
Figure A2-4 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S500 of the pull-out test at load level of 1008 kN
Appendix 2 -Comparison of longitudinal and Hoop strains A2.6
n -,
-0.0002 -
c
i -0.0004 •
Longitudinai
-0.0006 •
-0.0008 •
-0.001 i
r A Longitudinal Strain from NLFEA
• Longitudinal Strain from S750-2
-0.0012 -I
() 100 200 300 400 500 600 700
Distance from the bottom of the concrete plug (mm.)
0.00035
A Hoop strain from NLFEA
• Hoop strain from S750-2
Figure A2-5 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S750 of the push-out test at load level of 1452 kN
Appendix 2 -Comparison of longitudinal and Hoop strains A2.7
0.0006
Hoop strain from NLFEA
Hoop strain from S750-2
Figure A2-6 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S750 of the push-out test at load level of 2747 kN
Appendix 2 -Comparison of longitudinal and Hoop strains A2.8
0.0002
A Longitudinal strain from NLFEA
• Longitudinal Strain from test result
0.00015 -
2
idinal S
0.0001 -
'5> 0.00005 -
-0.00005
50 100 150 200 250
Distance from bottom of the concrete plug (mm)
0.00014
A Hoop strain from NLFEA
0.00012 -
• Hoop strain from test result
0.0001 -
0.00008 -
c
75 0.00006 -
(0
0.00004 -
a
O 0.00002 H
-0.00002 -
-0.00004 - AAAAA^
-0.00006
50 100 150 200 250
Distance from bottom of the concrete plug (mm)
Figure A2-7 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen Sl.OD of the Stage 1 at load level of 275 kN
Appendix 2 -Comparison of longitudinal and Hoop strains A2.9
0.0006 !
A Longitudinal strain from NLFEA
0.0005 - • Longitudinal strain from test result
c 0.0004
5
55 0.0003 A
a
£ 0.0002
0.0001 - A
• A A AA
5 A i
•AAA
-0.0001 -
I
-0.0002 !
;
50 100 150 200 250
Distance from bottom of the concrete plug (mm)
0.
0.00035 -
0.0003 -
0.00025 -
1 0.0002 -
j® 0.00015 -
§ 0.0001 -
A Hoop strain from NLFEA
0.00005 - • Hoop strain from test result
0
-0.00005 •
-0.0001
50 100 150 200 250
Distance from bottom of the concrete plug (mm)
Figure A2-8 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.0D of the Stage 1 at load level of 663 kN
Appendix 2 -Comparison of longitudinal and Hoop strains A2.10
0.0004
A Longitudinal Strain from the NLFEA
0.00035 ' \ • Longitudinal strain from test result
0.0003 -
"I 0.00025 -
5 0.0002 -
— 0.00015 H
••i 0.0001 -\
O 0.00005 -J
-0.00005 •
-0.0001
50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm.)
0.0003 - -
Hoop strain from NLFEA
0.00025 -
Hoop strain from the test results
0.0002 -
0.00015 -
0.0001 -
o" 0.00005 H
o
o
-0.00005 -
-0.0001 -
-0.00015
50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm.)
Figure A2-9 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen SI .5D of the Stage 1 at load level of 572 kN
Appendix 2 -Comparison of longitudinal and Hoop strains A2.ll
0.0008 '"' |
0
-0.0001
-0.0002 50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm.)
0.0003 -
0.0002 -
£ 0.0001 -\
Q.
o
o
X 0
-0.00C1 -
A Hoop strain from NLFEA
• Hoop strain from the test results
-0.0002
50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm.)
Figure A2-10 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen SI .5D of the Stage 1 at load level of 1000 kN
Appendix 2 -Comparison of longitudinal and Hoop strains A2.12
0
-0.0001
-0.QQQ2
c
"n -0.0003
2 -0.0004
ra
| -0.0005
i -0.0006
O -0.0007
-0.0008 A Longitudinal strian from NLFEA
-0.0009 • Longitudinal strain from the test results
-0.001
-100 -50 0 50 100 150 200 250 300
Distance from bottom of the concrete plug (mm.)
0.
A Hoop strain from NLFEA
0.0003 Hoop strain from the test results
0.00025
2 0.0002
Q.
§ 0.00015
X
0.0001
0.00005
Figure A2-11 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.25D of the Stage 2 at load level of 222 kN
Appendix 2 -Comparison of longitudinal and Hoop strains A2.13
U.UUUO
0.0005
0.0004
c
S
(0 0.0003
Q.'
O
o
X - A
0.0002 A
A
0.0001 A Hoop strain from NLFEA A
A
• Hoop strain from the test results A
A
0
-100 -50 0 50 100 150 200 250 300
Distance from bottom of the concrete plug (mm)
Figure A2-12 Comparison of longitudinal and Hoop strains along the outer surface of
the steel tube for specimen SI .25D of the Stage 2 at load level of 440 kN
,i
Appendix 2 -Comparison of longitudinal and Hoop strains A2.14
0.0002
tra
-0.0002
(0
"5
c -0.0004
"•5
o> -0.0006
0.00035
A Hoop strain from NLFEA
0.0003 iftA. • Hoop strain from test result
0.00025
= 0.0002
1
S 0.00015 • #
o
I 0.0001 _ ^
0.00005 i t 1
AA ii
A i
A j
-0.00005
-100 0 100 200 300 400
Distance from bottom of the concrete plug (mm)
Figure A2-13 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen SI .75D of the Stage 2 at load level of 225 kN
T
Appendix 2 -Comparison of longitudinal and Hoop strains A2.15
0.0002
0 1
c -0.0002
S
«5 -0.0004
75
•| -0.0006
3
"tj> -0.0008
c
0.0005
0.00045
0.0004
0.00035
c
'5 0.0003
£ 0.00025
O 0.0002
0.00015
0.0001
A Hoop strain from NLFEA
0.00005
• Hoop strain from test result
Figure A2-14 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S1.75D of the Stage 2 at load level of 363 kN
Appendix 2 -Comparison of longitudinal and Hoop strains A2.16
a
§ 0.0003
0.00025
0.0002
0.00015
0.0001
-100 0 100 200 300 400
Distance from bottom of the concrete plug (mm)
Figure A2-15 Comparison of longitudinal and Hoop strains along the outer surface
of the steel tube for specimen S2.0D of the Stage 2 at load level of 481 kN
T
Appendix 2 -Comparison of longitudinal and Hoop strains A2.17
q -0.0025
0.0012
Figure A2-16 Comparison of longitudinal and Hoop strains along the outer
surface of the steel tube for specimen S2.0D of the Stage 2 at load level of 920 kN
Appendix 3 - Longitudinal and circumferential bending moment A3.1
40 A
A A
A
20 A
E
Z 0
g -20
!*O A ^ ^ ^ ^
5 -40 %k A
A
-60 A
\
-80 - A
-100
-120
50 100 150 200 250
Distance from bottom of the concrete plug (mm)
A
A x Circumferential bending moment
300 •
A A
A A
200- A
A
N-mm
A
A
A
*s 100- V* ^ < A
a A jC* y
\, A
o ^ A
S
U
A AA^V,
A ££&&
A
-100! ^A ^A Vi v ^ ^
^ A A A A ^ ^ ^ ^
<yytfA
-200 - .................
(D 50 100 150 200 250
Distance from bottom of the concrete plug (mm)
Figure A3-1 Bending moment distribution along the steel tube for specimen S250
of the pull-out test
Appendix 3 - Longitudinal and circumferential bending moment A3.3
200-
Figure A3-2 Bending moment distribution along the steel tube for specimen S500
of the pull-out test
Appendix 3 - Longitudinal and circumferential bending moment A3.4
400-i
| 200-
Moment (N-i
\
XV
o
-100-
•200-
() 100 200 300 400 500 600 700
Distance from the bottom of concrete plug (mm)
300 -r —
200 \
100 4
k[A
(UI
f] A M&
z. °1
Moment
-100 -
-200 •
Figure A3-3 Bending moment distribution along the steel tube for specimen S750
of the push-out test
Appendix 3 - Longitudinal and circumferential bending moment A3.5
-200 -
-400
50 100 150 200 250
Distance from bottom of the concrete plug (mm)
Figure A3-4 Bending moment distribution along the steel tube for specimen
SI.0D (Stage 1)
Appendix 3 - Longitudinal and circumferential bending moment A3.6
J
-200
50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm)
Figure A3-5 Bending moment distribution along the steel tube for specimen
SI. 5D (Stage 1)
Appendix 3 - Longitudinal and circumferential bending moment A3.7
500
- A - Longitudinal bending moment jj
400
-^-Circumferential bending moment | j
300
-400
-100 -50 0 50 100 150 200 250 300
Distance from bottom of the concrete plug (mm.)
700
Figure A3-6 Bending moment distribution along the steel tube for specimen
Sl.25D(Stage2)
Appendix 3 - Longitudinal and circumferential bending moment A3.8
300
250
J
200
*g 150
? 100
•T 50
0
-50 ? ^
-100
-k- Longitudinal bending moment
-150
-x-Circumferential bending moment
-200
-100 -50 0 50 100 150 200 250 300 350 400
Distance from bottom of the concrete plug (mm)
350
250
Figure A3-7 Bending moment distribution along the steel tube for specimen
S1.75D(Stage2)
1,1
Appendix 3 - Longitudinal and circumferential bending moment A3.9
600
-100
-300
-500
-100 0 100 200 300 400
Distance from bottom of the concrete plug (mm.)
Figure A3-8 Bending moment distribution along the steel tube for specimen
S2.0D (Stage 2)
Appendix 4 - Longitudinal stress distributions A4.1
This appendix presents the longitudinal stress distributions for all specimens at
ultimate load level and at load level of changing the slope of load-slip response.
The longitudinal stress distributions are shown at the outer and inner surfaces and j
centre of the steel tube wall. The stress distribution at the centre of the steel tube j
wall is used to determine the shear/bond stress distribution along the interface. No ;
discussion is provided in this appendix as the relevant discussion has been j
presented in Chapter 7. j
Appendix 4 - Longitudinal stress distributions A4.2
2
S. 30
(A
i2 20
CO
Stress at inner surface
•"I 10
Figure A4-1 Longitudinal stress distributions along the steel tube for specimen
S250 of pull-out test
Appendix 4 - Longitudinal stress distributions A4.3
50-
Stress at the centre
10
c
Figure A4-2 Longitudinal stress distributions along the steel tube for specimen
S500 of pull-out test
Appendix 4 - Longitudinal stress distributions A4.4
-40 -
-60 -
-80 -
£
Stress at inner surface JHr Stress at the centre
-100
jdina
-120 -
-140 -
c
o -160
X
-400
-100 0 100 200 300 400 500 600 700
Distance from the bottom of the concrete plug (mm)
Figure A4-3 Longitudinal stress distributions along the steel tube for specimen
240
^ 30 Stress at outer surface
to
CO
£ 20
CO
1 10
I o.
-10 Stress at inner surface
-20
-100 -50 0 50 100 150 200 250
Distance from bottom of the concrete plug (mm)
10 -
A X*
\J | 1 r ~ i " i ~r i **
Figure A4-4 Longitudinal stress distributions along the steel tube for specimen
S1.0D of Stage 1
~
70
60
Stress at inner surface
CO 50
CO Stress at the
I 40 center
75 30
20
10
Stress at outer surface
-10
-100 -50 0 50 100 150 200 250 300 350
Distance from bottom of the concrete plug (mm)
140
++, A * ^ . ^ Stress at outer surface
+++ A A 2^
(0
cu 120
"5
•c^
^ ^ 1
CO 100 I
CO
2 /
CO 80 Stress at the -
75 center
c 60 - Stress at inner surface ^$£ + +
'•5
itui
A
V^4,
40
c
3 20 -
0 i i . i i i i
Figure A4-5 Longitudinal stress distributions along the steel tube for specimen
S1.5D of Stage 1
Appendix 4 - Longitudinal stress distributions A4.7
-20
to
Q. -40
-60
w
1 Stress at the
centre
3 -120
-140
-180
-100 -50 0 50 100 150 200 250 300
Distance from bottom of the concrete plug (mm)
« -50
£
f -150
cs
c Stress at the
centre
1 -200
'5)
3 -250 Stress at inner surface
Figure A4-6 Longitudinal stress distributions along the steel tube for specimen
S1.25DofStage2
Appendix 4 - Longitudinal stress distributions A4.8
-200
-100 -50 0 50 100 150 200 250 300 350 400
Distance from bottom of the concrete plug (mm)
-50
to
Q.
Figure A4-7 Longitudinal stress distributions along the steel tube for specimen
S1.75DofStage2
Appendix 4 - Longitudinal stress distributions A4.9
! 'j
to -100
I
- -150
Stress at the
centre
Stress at outer surface
§
'•5
3 -200
I
•3 -250
-300
-100 0 100 SrjO 300 400
Distance from bottom of the concrete plug (mm)
A -100
a.
-200
-600
-100 0 100 20° 300 400
Distance from bottom of the concrete plug (mm)
Figure A4-8 Longitudinal stress distributions along the steel tube for specimen
S2.0DofSta§ e 2
Appendix 5 - Comparison of load slip response in parametric study A5.1
The aim of this appendix is to give the reader a complete comparison of load-slip
response of all specimens in aspect ratio parametric study using the NLFEA
solution scheme. No discussion is provided in this appendix as the relevant
discussion has been presented in Chapter 7.
-•-Aspect ratio of 15
-•-Aspect ratio of 20
-*-Aspect ratio of 25
- * - Aspect ratio of 30
-•-Aspect ratio of 35
-•-Aspect ratio of 40
Figure A5-1: Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S250 in pull-out test
Appendix 5 - Comparison of load slip response in parametric study A5.2
1400
Aspect ratio of 15
Aspect ratio of 20
Aspect ratio of 25
Aspect ratio of 30
Aspect ratio of 35
Aspect ratio of 40
Figure A5-2: Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S500 in pull-out test
1200
-»-Aspect ratio of 15
-*-Aspectratioof20
- * - Aspect ratio of 25
-H-Aspect ratio of 30
-•-Aspect ratio of 35
-•-Aspect ratio of 40
0.3
Slip (mm)
Figure A5-3: Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S750 in pull-out test
Appendix 5 - Comparison of load slip response in parametric study A5.3
-•-Aspect ratio of 15
-•-Aspect ratio of 20
- * - Aspect ratio of 25
-*-Aspect ratio of 30
- * - Aspect ratio of 35
-•-Aspect ratio of 40
-2500 ii
l 1
-3000
-3 -2 -1
Slip (mm)
Figure A5-4: Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S750 in push-out test
o
-•-Aspect ratio of 15
-100
- * - Aspect ratio of 20
-200
-•-Aspect ratio of 25
-300 -M-Aspect ratio of 30
-400 -•-Aspect ratio of 35
-500 - « - Aspect ratio of 40
"600
-700
-800
-900
-1000
-0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1
Slip (mm)
Figure A5-5: Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen SI000 in push-out test
4
:1
Appendix 5 - Comparison of load slip response in parametric study A5.4
-Aspect ratio of 15
- Aspect ratio of 20
-Aspect ratio of 25
•Aspect ratio of 30
- Aspect ratio of 35
-Aspect ratio of 40
Figure A5-6: Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S1.0D in pull-out test (Stage 1)
1000
900-
800-
700-
600-
-•-Aspect ratio of 15
500-
- » - Aspect ratio of 20
400-
- * - Aspect ratio of 25
300- -••-Aspect ratio of 30
200- - « - Aspect ratio of 35
100- -•-Aspect ratio of 40
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Slip (mm)
Figure A5-7: Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S1.5D in pull-out test (Stage 1)
Appendix 5 - Comparison of load slip response in parametric study A5.5
Figure A5-8: Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S1.25D in push-out test (Stage 2)
-•-Aspect ratio of 20
-^Aspect ratio of 25
-H-Aspect ratio of 30
Aspect ratio of 35
Aspect ratio of 40
! i
i!
-1000
-0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1
Slip (mm)
Figure A5-9: Load-slip behaviors of varying the aspect ratio of the steel tube for
specimen S2.0D in push-out test (Stage 2)
Appendix 6- List of publication A6.1
Nezamian, A., Al-Mahaidi, R. and Grundy, P., " Pull out strength of concrete
plugs in tubular piles". 2nd International Conference On Mechanics of
Structures, Mater a; and Systems, MSMS 2001, February 14 to 16,
2001, AUSTRALIA pp. 67-73