Reinforced Concrete Column: C1 2Nd FLR
Reinforced Concrete Column: C1 2Nd FLR
Reinforced Concrete Column: C1 2Nd FLR
C1 2ND FLR
Design Parameters:
Main Bars Loc -Z Ast
h= 500 mm d' = 60 mm fs1 = 2 - 440.00 628.319
b= 300 mm Main bars = 20 mm Ø fs2 = 2 - 345.00 628.319
fc' = 21 Mpa Mux = 2.79 KNm fs3 = 2 - 250.00 628.319
fy = 415 Mpa Pu = 71.85 KN fs4 = 2 - 155.00 628.319
b₁ = 0.85 Escon = 600 Mpa fs5 = 2 - 60.00 628.319
Es = 200 Gpa Shear parameters
Therefore use, 500x300mm 10-20mm Ø longitudinal bars (GRADE 60) with 10mm Ø lateral ties space at,
1@50, 10@70mm , and Rest 100mm O.C, BOTH ENDS.