MCB ABB Catalogue
MCB ABB Catalogue
MCB ABB Catalogue
1
—
Electrical installation solutions for buildings
Miniature circuit-breakers
Index
Quick selection of MCBs 1/2
MCBs S 200
S 200 technical features 1/20
S 200 series, 6 kA 1/26
S 200 M series, 10 kA 1/40
S 200 MR series, 10kA 1/54
S 200 M UC series, 10 kA 1/56
S 200 P series, 15/25 kA 1/65
S 200 S screwless series, 6 kA 1/80
SU 200 MR series, 10kA 1/93
S 200 UDC series, 60 V DC 1/95
MCBs SN 201
SN 201 L series, 4.5 kA 1/102
SN 201 series, 6 kA 1/103
SN 201 M series, 10 kA 1/105
SMCBs S 750 DR
S 750 DR series 1/110
SMCBs S 700
S 700 series 1/114
S 700 + H2WR series 1/118
WT631/122
CBs S 800
S800S series, 50 kA 1/132
S800N series, 36 kA 1/157
S800C series, 25 kA 1/163
S800B series, 16 kA 1/171
S800HV series, 4 kA 1/175
S800U series, 50 kA 1/178
S804U-UCZ series, 10 kA 1/186
S800PV series, 5 kA, DC 1/188
S800PV-SD series 1/191
MCBs S 500
S500 series 1/198
S500UC series 1/200
S500HV series 1/203
1/2 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
System pro M compact®
Quick selection of MCBs for household
and industrial applications
Easy! Find the right range and the corresponding catalogue page at a glance using this selection chart.
4,5 kA
6 kA
HOUSEHOLD
10 kA
Overload + Short-circuit IEC/EN 60898-1
15 kA
20 kA
25 kA
START
INDUSTRIAL
Overload + Short-circuit IEC/EN 60947-2
1/3
1
Rated current Poles Solution Page
—
System pro M compact®
Quick selection of MCBs for household
and industrial applications
Application Breaking capacity Icn
6 kA
HOUSEHOLD
10 kA
Overload + Short-circuit IEC/EN 60898-1
15 kA
25 kA
START
30 kA
36 kA
50 kA
100 kA (with S800S and SCL)
10 kA
INDUSTRIAL
DC-applications IEC/EN 60947-2
50 kA
1/5
1
Rated current Poles Solution Page
—
System pro M compact®
Quick selection of MCBs for UL
applications (UL 489/CSA 22.2 No. 5)
10 kA
10 kA
14 kA
50 kA
DC applications UL 489B 3 kA
1/7
1
Rated current Remark Poles Solution Page
5A 4P S804U-PVS5 1/187
1/8 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
Miniature circuit-breakers
Selection table
S 200 MR
S 200 M
S 200 M
S 200 P
S 200 S
S 200
UC
Series
Characteristics
B,C,D, B,C,D, B,C,D, B,C,D, B,C,D,
B,C, K, Z K B,C
K,Z K,Z K,Z K,Z K,Z
Breaking [kA]
capacity
Reference Nr. Ue[V]
standard poles
IEC/EN 60898 Icn 230/400 6 10 10 25 15 15 6
IEC/EN Icu 1, 133 20 25 40 25 25
60947-2 1P+N 230 10 15 25 15 15 15
Alternating 253
current
2, 3, 4 230 20 25 10 *17/6 *18 40 25 25
400 10 15 25 15 15 15
440 10 15 10 *17/6 *18
2, 3, 4 500
690
Ics 1, 133 15 18.7 *8 20 18.7 18.7
1P+N 230 7.5 11.2 *8 12.5 11.2 7.5
253 7.5 *18
7.5 *17/6 *18
11.2 *17
2, 3, 4 230 15 18.7 *8 20 18.7 18.7
400 7.5 11.2 *8 12.5 11.2 7.5
440 7.5 *18
7.5 11.2 *8 7.5 *17/6 *18
11.2 *17
2, 3, 4 500
690
IEC/EN Icu 1, 24 20
60947-2 1P+N 60 10 10 15 10 10
Direct current 125
T=I/R≤5ms
220 10
for
all series, 250
except S280 2 48 20
UC and 125 10 10 15 10 10
S800S-UC, 250
where
440 10
T=I/R<15ms
500
800
3,4 375
500
750
1200
1
SU 200 MR
S 200 UDC
SU 200 M
SN 201 M
80-100A
SN 201 L
SN 201
S200
C,Z K C,Z K K K,Z B,C B,C,D B,C B,C
4.5 6 10 6
10 15 20 20
15 15 15 15 15 6 10 10 6
20
15 15 15 15 15 6
6 10 10 10
11.25 11.25 7.5 7.5 4.5 6 7.5 6
7.5 *18
11.2 *17
10
11.25 11.25 7.5 7.5 6
7.5 *18
11.2 *17
15 15 10 10 10 15 15
15 15 10 10 10 15 15
1/10 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
Miniature circuit-breakers
Selection table
S 200 MR
S 200 M
S 200 M
S 200 P
S 200 S
S 200
UC
Series
Characteristics
B,C,D, B,C,D, B,C,D, B,C,D, B,C,D,
B,C, K, Z K B,C
K,Z K,Z K,Z K,Z K,Z
IEC/EN Ics 1, 24 20
60947-2 1P+N 60 10 10 15 10 10
Direct current 125
T=I/R≤5ms
220 10
for
all series, 250
except S280 2 48 20
UC and 125 10 10 15 10 10
S800S-UC, 250
where
440 10
T=I/R<15ms
500
800
3,4 375
500
750
1200
UL 1077/ Int. 1, 120 10 *16 10 6 6
C22.2 cap. 1P+N 240
No 235 277 6 *16 6 6 10 6 6 10
Alternating
2, 3, 4 240 10 *16 10 6 6
current
480
6 *16 6 6 10 6 6 10
Y/277
UL 1077/ Int. 1, 60 10 *16 10
C22.2 cap. 1P+N 125
No 235 250 10
Direct current
2, 3, 4 125 10
250
500 10
UL 489/ C22.2 Int. 1 240
No 5 cap. 277
Alternating 2, 3, 4 240
current
480
Y/277
UL 489/ C22.2 Int. 1 48
No 5 cap. 60
Direct current 2 96
125
1
SU 200 MR
S 200 UDC
SU 200 M
SN 201 M
80-100A
SN 201 L
SN 201
S200
C,Z K C,Z K K K,Z B,C B,C,D B,C B,C
15 15 10 10 10 15 15
15 15 10 10 10 15 15
10 10 10
10 10 10 *19
10 10 10
10 10 10 *19
10 10 10 10
14
10 10 10 10
14 *15
1/12 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
High performance circuit-breakers
Selection table
S 750 DR
S800N
S800C
S800S
Series S 700
Characteristics E selective, E selective,
B,C,D K KM UCB UCK B,C,D B,C,D,K
K selective K selective
Rated current [A]
16 ≤ 10 ≤ 6≤ 6≤ 20 ≤ 10 ≤ 10 ≤ 6≤ 10 ≤
In In In In In In In In In
≤ 63 ≤ 100 ≤ 125 ≤ 125 ≤ 80 ≤ 125 ≤ 125 ≤ 125 ≤ 125
Breaking [kA]
capacity
Reference Nr. Ue[V]
standard poles
IEC/EN 60898 Icn 230/400 25 *9 25 *20 20 *20 15
IEC/EN Icu 1, 133
60947-2 1P+N 230 25
Alternating 240 50 50 50 *6 36 25
current
253
254 30 30 30 *6 20 15
400 6 (up to 80 A) 6 (up to 80 A)
6 *6 4.5
4.5 (100…125 A) 4.5 (100…125 A)
580
2, 3, 4 230
400 25
415 50 50 50 *6 36 25
440 20 15
500
580
690 6 (up to 80 A) 6 (up to 80 A)
4.5
4.5 (100…125 A) 4.5 (100…125 A)
1000
Ics 1, 133
1P+N 230 12.5 12.5 *9
240 40 40 30 18
253
254 22.5 (up to 80 A) 22.5 (up to 80 A) 15 (up to 80 A)
10
15 (100…125 A) 15 (100…125 A) 10 (100…125 A
400 4 (up to 80 A) 4 (up to 80 A)
3
3 (100 … 125 A) 3 (100 … 125 A)
580
2, 3, 4 230
400 12.5 12.5 *9 40 40
415 22.5
30 18
40 *6
440 15
500
690 4 *3 4 *3 4 3
1000
1
S800PV-
S800HV
S500UC
S804U-
S804U-
S800U
S800B
S500
UCZ
PVS
SP
B, C, D, K C, K Z, K UCZ PVS PV-SP K adjustable K adjustable
10 ≤ 5≤ 0.1 ≤ 10 ≤ 0.1 ≤
32 ≤ C: 10 ≤ In ≤ 32
In 10-80 5 In In In In
In ≤ 125 K: 6 ≤ In ≤ 125
≤ 100 ≤ 125 ≤ 11 ≤ 45 ≤ 45
10
16 50 30
30
4 (6 … 63 A)
3 (80 … 125 A)
16 50 30
50
20 15
6 6
4 (6 … 63 A)
3 (80 … 125 A)
10
25
2.5 (6 … 63 A)
2 (80 … 125 A)
30 25
10 30 25
40
15 11
3 3
2.5 (6 … 63 A)
2 (80 … 125 A)
—
High performance circuit-breakers
Selection table
S 750 DR
S800N
S800C
S800S
Series S 700
Characteristics E selective, E selective,
B,C,D K KM UCB UCK B,C,D B,C,D,K
K selective K selective
Rated current [A]
16 ≤ 10 ≤ 6≤ 6≤ 20 ≤ 10 ≤ 10 ≤ 6≤ 10 ≤
In In In In In In In In In
≤ 63 ≤ 100 ≤ 125 ≤ 125 ≤ 80 ≤ 125 ≤ 125 ≤ 125 ≤ 125
Breaking [kA]
capacity
Reference Nr. Ue[V]
standard poles
IEC/EN Icu 1, 24
60947-2 1P+N 60
Direct current 75
T=I/R≤5ms
125 30 30 20 10
for
all series, 220
except S280 250 50 50
UC and 2 48
S800S-UC, 125
where
150
T=I/R<15ms
250 30 30 20 10
440
500 50 50
800
3,4 225
300
375 30 *6 30 *6 30 *6 20 *6 10 *6
500 30 *7 30 *7 20 *7 10 *7
750 50 *6 50 *6
50 (63 ... 125 A) *7 50 (63 ... 125 A) *7
1000 50 (10 ... 50 A) *7 50 (10 ... 50 A) *7
1200
*1 only up to 40 A; 10 kA up to 50/63 A *9 relevant product standard: E DIN VDE *13 > 25 A *21 for S804U-UCZ only
*2 only for “D” characteristic 0645 *14 char. B, C *22 for S804U-PVS only
*3 values are not for all rated currents (based on IEC/EN 60898-1 *15 only 2 poles (connection in series)
*5 1500 V DC for 4P and IEC/EN 60947-2) *16 UL 1077 only
*6 3 poles *10 by 250 V DC 1-pole, 600 *17 ≤ 40 A
*7 4 poles V 3- and 4-pole *18 > 40 A
*8 max. values. Detailed *11 by 600 V DC 2-pole *19 ≤ 35 A
values on page 2/12 *12 ≤ 25 A *20 10-80 A
1/15
1
S800PV-
S800HV
S500UC
S804U-
S804U-
S800U
S800B
S500
UCZ
PVS
SP
B, C, D, K C, K Z, K UCZ PVS PV-SP K adjustable K adjustable
10 ≤ 5≤ 0.1 ≤ 10 ≤ 0.1 ≤
32 ≤ C: 10 ≤ In ≤ 32
In 10-80 5 In In In In
In ≤ 125 K: 6 ≤ In ≤ 125
≤ 100 ≤ 125 ≤ 11 ≤ 45 ≤ 45
10
30
10
30
5
10 *6
10 *7
30
5 *5
1/16 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
High performance circuit-breakers
Selection table
S 750 DR
S800N
S800C
S800S
Series S 700
Characteristics E selective, E selective,
B, C, D K KM UCB UCK B, C, D B, C, D, K
K selective K selective*9
Rated current [A] 16 ≤ 10 ≤ 6≤ 6≤ 20 ≤ 10 ≤ 10 ≤ 6≤ 10 ≤
In In In In In In In In In
≤ 63 ≤ 100 ≤ 125 ≤ 125 ≤ 80 ≤ 125 ≤ 125 ≤ 125 ≤ 125
IEC/EN Ics 1, 24
60947-2 1P+N 60
Direct current 125 30 30 20 10
T=I/R≤5ms 220
for 250 50 50
all series, 2 48
except S280 125
UC and
250 30 30 20 10
S800S-UC,
440
where
500 50 50
T=I/R<15ms
800
3,4 375 30 *6 30 *6 30 *6 20 *6 10 *6
500 30 *7 30 *7 20 *7 10 *7
750 50 *6 50 *6
50 (63 ... 125 A) *7 50 (63 ... 125 A) *7
1000 50 (10 ... 50 A) *7 50 (10 ... 50 A) *7
1200
UL 1077/ Int. 1, 120
C22.2 cap. 1P+N 240 30 (6...63 A) 30 (6...63 A) 20 (≤ 100 A)
No 235 277 14 (6...63 A) 14 (6...63 A)
Alternating 347 6 (6...63 A) 6 (6...63 A) 10 (≤ 100 A)
current 2, 3, 4 240
480 14 14
10 (≤100 A)
Y/277 (6...63 A) *27 (6...63 A) *27
600Y/347
6 (6...63 A) 6 (6...63 A)
UL 1077/ Int. 1, 60
C22.2 cap. 1P+N 125 10 (≤ 100 A)
No 235 250
Direct current 2, 3, 4 125
250 10 (2P,
≤ 100 A)
375 10 (3P,
≤ 100 A)
500 10 (4P,
≤ 100 A)
UL 489/ C22.2 Int. 1 240
No 5 cap. 277
Alternating 2, 3, 4 240
current 480
Y/277
UL 489/ C22.2 Int. 1 60
No 5 cap. 2 125
Direct current
4 600
UL489B 4 1000
Direct current
1
S800PV-
S800HV
S500UC
S804U-
S804U-
S800U
S800B
S500
UCZ
PVS
SP
B, C, D, K C, K Z, K UCZ PVS PV-SP K adjustable K adjustable
10 ≤ 5≤ 0.1 ≤ 10 ≤ 0.1 ≤
32 ≤ C: 10 ≤ In ≤ 32
In 10-80 5 In In In In
In ≤ 125 K: 6 ≤ In ≤ 125
≤ 100 ≤ 125 ≤ 11 ≤ 45 ≤ 45
5 *5
30 *12 18 *13
14 *12 14 *13
30 *12 18 *13
14 *12 14 *13
15 (3P, 10 ... 32
A) *28
30 *10
30 *11
30
50
10
*13 > 25 A *18 > 40 A *24 by 150V DC 2-pole *28 P, 10 ... 32 A - only valid with
3
*15 only 2 poles (connection in series) *19 ≤ 35 A *25 by 225V DC 3-pole XT2L 125 TMF 35-400
*16 UL 1077 only *20 10-80 A *26 by 300V DC 4-pole
*17 ≤ 40 A *23 by 75V DC 1-pole *27 certification 50A ongoing
1/18 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCB S 200. The details make the difference
A range designed to ensure efficiency and protection
Quick identification
thanks to laser printed
EAN marking.
Contact position
indication
Captive screws:
don’t loose what’s Whatever your
important for you. application need is
applicable with a wide
range of accessories.
1/19
1
Contact position indication Approvals printed on the dome Housing material
All System pro M compact® MCBs are S 200 MCBs comply to IEC/EN 60898-1 By using the state-of-the-art housing
suited with a contact position and IEC/EN 60947-2 and carry all material, ABB is taking care of the
indication (CPI) on the toggle. You can relevant approval marks for each environment. With the latest
easily identify, if the MCB is in the ON market and segment they are destined generation of thermoplastics it’s
or the OFF position – easy and safe to. The certification markings are also possible to recycle the MCBs –
maintenance work is possible. printed on the dome of the MCB. Thus especially the thermoplastic housing-
make it possible to see the markings material can be re-used. By using the
also in the mounted position. For latest generation of thermoplastics
control and acceptance procedure – the material stability of all System pro
certification marks visible on fitted M compact® MCBs is improved. S200
devices on the dome. are 100% free of halogens – no
environmental pollution.
—
MCBs
S 200 technical features
S 200 S 200 M
General Standards IEC/EN 60898-1, IEC/EN 60898-1,
Data IEC/EN 60947-2 IEC/EN 60947-2
2CDC021059S0012
Max. power frequency recovery voltage (Umax) V 1P: 253 V AC; 1P+N: 253 V AC; 2P...4P: 462 V AC;
3P+N: 462 V AC; 1P: 72 V DC; 2P: 125 V DC
Rated impulse withstand voltage Uimp. (1.2/50µs) kV 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
Dielectric test voltage kV 2 kV (50 / 60Hz, 1 min.)
Reference temperature for tripping characteristics °C B, C, D: 55°C; K, Z: 20°C
Electrical endurance ops. In < 32A: 20,000 ops (AC),
In ≥ 32A: 10,000 ops. (AC); 1,000 ops. (DC);
(1 cycle 2s - ON, 13s - OFF, In ≤ 32A),
(1 cyle 2s - ON, 28s - OFF, In > 32A)
Note:
* Only acc. to IEC/EN 60898-1
1/21
1
S 200 M UC S 200 P S 200 MR S 200 S SU 200 M SU 200 MR S 200 UDC
IEC/EN 60898-2, IEC/EN 60898-1, IEC/EN 60947-2 IEC/EN 60898-1 IEC/EN 60947-2 IEC/EN 60947-
IEC/EN 60947-2 IEC/EN 60947-2 2
UL 1077, CSA 22.2 No. UL 1077, UL 489, UL 489, UL 489
235 CSA 22.2 No. 235 CSA22.2 No.5 CSA22.2 No.5
1P, 2P, 3P, 4P 1P, 2P, 3P, 4P, 1P+N, 1P, 2P, 3P, 4P 1P, 3P 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P 1P, 2P
3P+N
B, C, K, Z B, C, D, K, Z K B, C C, K, Z K
0.2…63 A 6…20 A 0.2…63 A 0.2…25 A 0.2…63 A 1…63 A
0 / 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz DC
440 V AC (phase to phase)
--
2 --
1P: 230 V AC, 220 V DC 1P: 230 V AC, --
2P: 400 V AC, 440 V DC 3P: 440 V AC
3...4P: 400 V AC*
1P: 253 V AC, 250 V DC 1P: 253 V AC, --
2P: 440 V AC, 500 V DC 3P: 440 V AC
3...4P:440 V AC*
12 V AC --
10 kA ≤ 25 A: 25 kA 6 kA --
> 25 A: 15 kA
--
--
--
30 °C B, C: 30 °C --
20,000 ops. --
1P: 253 V AC, 220 V DC 1P: 230 V AC; 1P: 230 V AC 1P: 230 V AC 1P: 230 V AC --
2...4P: 440 V AC, 440 1P+N: 230 V AC; 2...4P: 400 V AC 2...4P: 400 V AC 2...4P: 400
V DC 2...4P: 400 V AC; V AC
3P+N: 400 V AC
1P: 266 V AC, 250 V DC 1P: 253 V AC; 1P: 253 V AC 1P: 253/440 V AC; 1P: 253 V AC --
2...4P: 462 V AC, 500 1P+N: 253 V AC; 2...4P: 440 V AC 2...4P: 440 V AC 2...4P: 440
V DC 2P...4P: 440 V AC; V AC
3P+N: 440 V AC;
1P: 72 V DC; 2P: 125
V DC
12 V AC 12 V AC --
≤ 40 A: 10 kA AC; 10 ≤ 25 A: 25 kA 15 kA 10 kA 15 kA --
kA DC ≥ 32 A: 15 kA
> 40 A: 6 kA AC; 10 kA
DC
≤ 40 A: 7,5 kA AC; 10 ≤ 25 A: 12.5 kA ≤ 40 A: 11.2 kA; 7.5 kA ≤ 40 A: 11.2 kA; --
kA DC ≤ 32…40 A: 11.2 kA > 40 A: 7.5 kA > 40 A: 7.5 kA
> 40 A: 6 kA(AC; 10 50, 63 A: 7.5 kA AC; (AC);
kA DC
--
--
B, C: 55 °C; K, Z: 20 °C 20 °C C, K, Z: 20°C 20 °C --
In < 32A: 20,000 ops In < 32A: 20,000 ops In < 25A: 20,000 In < 25A: --
(AC), (AC), In ≥ 32A: 10,000 ops (AC), 20,000 ops
In ≥ 32A: 10,000 ops. ops. (AC); In ≥ 25A: 10,000 (AC),
(AC); 1,000 ops. (DC); ops. (AC); In ≥ 25A:
1,500 ops. (DC); (1 cycle 2s - ON, 13s - 10,000 ops.
OFF, (AC);
In ≤ 32A), (1 cyle 2s -
ON, 28s - OFF, In ≥ 32A)
1/22 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S 200 technical features
S 200 S 200 M
Data acc. Rated voltage V 480Y / 277 V AC; 480Y / 277 V AC;
to UL /
2CDC021059S0012
CSA
S 200
1P: 60 V DC; 1P: 60 V DC;
2P…4P: 110 V DC 2P…4P: 125 V DC
Rated interrupting capacity acc. to UL 1077 kA 6 kA AC; 10 kA DC
Vibration resistance acc. to IEC/EN 60068-2-6 5g - 20 cycles at 5…150…5 Hz with load 0.8In
Environmental conditions (damp heat) °C/ 28 cycles with 55°C/90-96% and 25°C/95-100%
acc. to IEC/EN 60068-2-30 RH
Ambient temperature °C -25 … +55°C
Storage temperature °C -40 … +70°C
Note:
* Also fulfilling the requirement acc. to the protection degree IPXXB
** Only with accessory: IP20 terminal clip
1/23
1
S 200 M UC S 200 P S 200 MR S 200 S SU 200 M SU 200 MR S 200 UDC
480Y / 277 V AC 480Y / 277 V AC 480Y / 277 V AC 240 V AC 480 Y / 277 1P: ≤ 35 A: 277
V AC V AC;
> 35 A: 240
V AC
2...4P: ≤ 35 A:
480 / 277 V AC;
> 35 A: 240
V AC
1P: 250 V DC 480 / 277 V AC 1P: 60 V DC
2...4P: 500 V DC 2P: 125 V DC
≤ 25 A: 10 kA 10 kA --
> 25 A: 6 kA
10 kA 10 kA 14 kA (UL)
TC1, 0L0, TC2, 0L0, Ring tongue Ring tongue
SC: U1 SC: U1 terminal, terminal, not
not for general for general use
use
25 °C C, K, Z: 25 °C 25 °C
—
MCBs
S 200 technical features
S 200 S 200 M
Installa- Terminal Failsafe bi-directional cylinder-lift terminal
tion
2CDC021059S0012
*1 rior to connection of aluminium conductors (>= 4 mm2) ensure that their contact points are cleaned,
P
brushed and coated with grease.
Connection of aluminium conductors is not specifically approved by third party.
All approvals according to the product standards are carried out with copper conductors.
*2 N m-values acc. IEC / in-lbs.-values acc. UL
1/25
1
S 200 M UC S 200 P S 200 MR S 200 S SU 200 M SU 200 MR S 200 UDC
Ring Tongue Failsafe bi-directional cylinder-lift terminal Ring Tongue --
Terminal Terminal
25 mm 2 / 25 35 mm 2 / --
mm 2 35 mm 2
16 mm 2 / 16 25 mm 2 / 25 25 mm 2 / --
mm 2 mm 2 25 mm 2
18 - 4 AWG 18 - 4 AWG --
--
18 - 8 AWG --
2.8 Nm --
25 in-Ibs.
No
No No Yes No No
No Yes No
1/26 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S 200 series B characteristic
S 200 B characteristic
Function: protection and control of the circuits against overloads and short-circuits;
protection for people and large length of cables in TN and IT systems.
2CDC021059S0012
S 201
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/27
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/28 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S 200 series C characteristic
S 200 C characteristic
Function: protection and control of the circuits against overloads and short-circuits;
2CDC021058S0012
protection for resistive and inductive loads with low inrush current.
Applications: residential, commercial and industrial.
Standard: IEC/EN 60898-1, IEC/EN 60947-2
Icn=6 kA
S 201
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/29
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/30 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S 200 series C characteristic
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/31
1
—
MCBs
S 200 series D characteristic
S 200 D characteristic
Function: protection and control of the circuits against overloads and short-circuits;
protection for circuits which supply loads with high inrush current at the circuit closing
2CDC021051S0012
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/32 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S 200 series D characteristic
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/33
1
With disconnecting neutral NA
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/34 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S 200 series K characteristic
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/35
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
S 200 series K characteristic
1
—
MCBs
S 200 series Z characteristic
S 200 Z characteristic
Function: protection and control of the electronic circuits against lower and long
duration overloads and short-circuits.
2CDC021046S0012
S 201
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
S 200 series Z characteristic
1
With disconnecting neutral NA
—
MCBs
S 200 series M-B characteristic
S 201 M
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/41
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/42 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S 200 series M-C characteristic
S 201 M
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/43
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/4 4 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S 200 series M-C characteristic
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/45
1
—
MCBs
S 200 series M-D characteristic
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/46 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S 200 series M-D characteristic
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/47
1
With disconnecting neutral NA
*1 suitable for flow-type heaters 12 kW *3 suitable for flow-type heaters 21, 24 and 27 kW
*2 suitable for flow-type heaters 18 kW
1/48 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S 200 series M-K characteristic
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
S 200 series M-K characteristic
1
—
MCBs
S 200 series M-Z characteristic
S 201 M
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
S 200 series M-Z characteristic
1
With disconnecting neutral NA
—
MCBs
Supplementary protector S 200 MR series, 10kA
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
S 200 series M UC B characteristic
Universal current range
S 200 M UC B characteristic
Function: protection and control of the circuits against overloads and short-circuits;
protection for people and big length cables in TN and IT systems; version dedicated to
application
2CDC021031S0011
in direct current circuits for voltages up to 220 V DC 1 pole and 440 V DC 2, 3 and 4 poles.
Applications: Industrial.
Standard: IEC/EN 60898-2, IEC/EN 60947-2, UL1077, CSA 22.2 No. 235
S 201 M UC (for DC applications, please note polarity of device)
Icu=10 kA
1
Number Rated Bbn Order details Price Weight Pack
of poles current 401361 1 piece 1 piece unit
—
MCBs
S 200 series M UC C characteristic
Universal current range
S 200 M UC C characteristic
Function: protection and control of the circuits against overloads and short-circuits;
protection for people and big length cables in TN and IT systems; version dedicated to
application
2CDC021031S0011
in direct current circuits for voltages up to 220 V DC 1 pole and 440 V DC 2, 3 and 4 poles.
Applications: Industrial.
Standard: IEC/EN 60898-2, IEC/EN 60947-2, UL1077, CSA 22.2 No. 235
S 201 M UC (for DC applications, please note polarity of device)
Icu=10 kA
1
Number Rated Bbn Order details Price Weight Pack
of poles current 401361 1 piece 1 piece unit
—
MCBs
S 200 series M UC – Universal current range K characteristic
S 200 M UC K characteristic
Function: protection and control of the circuits against overloads and short-circuits;
protection for people and big length cables in TN and IT systems; version dedicated to
application
2CDC021031S0011
in direct current circuits for voltages up to 220 V DC 1 pole and 440 V DC 2, 3 and 4 poles.
Applications: Industrial.
Standard: IEC/EN 60898-2, IEC/EN 60947-2, UL1077, CSA 22.2 No. 235
S 201 M UC (for DC applications, please note polarity of device)
Icu=10 kA
1
Number Rated Bbn Order details Price Weight
of poles current 401361 1 piece 1 piece Pack
unit
In A EAN kg
Type code Order code pc.
2CDC021035S0011
—
MCBs
S 200 series M UC – Universal current range K characteristic
1
—
MCBs
S 200 series M UC – Universal current range Z characteristic
S 200 M UC Z characteristic
Function: protection and control of the circuits against overloads and short-circuits;
protection for people and big length cables in TN and IT systems; version dedicated to
application
2CDC021031S0011
in direct current circuits for voltages up to 220 V DC 1 pole and 440 V DC 2, 3 and 4 poles.
Applications: Industrial.
Standard: IEC/EN 60898-2, IEC/EN 60947-2, UL1077, CSA 22.2 No. 235
S 201 M UC (for DC applications, please note polarity of device)
Icu=10 kA
—
MCBs
S 200 series M UC – Universal current range Z characteristic
1
—
MCBs
S 200 series P-B characteristic
S 201 P
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
S 200 series P-B characteristic
1
S 200 P-C characteristic
Function: protection and control of the circuits against overloads and short-circuits;
protection for resistive and inductive loads with low inrush current.
Applications: commercial and industrial.
2CSC400056F0201
—
MCBs
S 200 series P-C characteristic
1
With disconnecting neutral NA
—
MCBs
S 200 series P-D characteristic
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
S 200 series P-D characteristic
1
—
MCBs
S 200 series P-K characteristic
—
MCBs
S 200 series P-K characteristic
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
S 200 series P-K characteristic
1
—
MCBs
S 200 series P-Z characteristic
—
MCBs
S 200 series P-Z characteristic
1
With disconnecting neutral NA
—
MCBs
S 200 series S - screwless range B and C characteristics
1
—
MCBs
SU 200 M series technical characteristic
General Data
Standards UL 489, CSA 22.2 No. 5, IEC/EN 60947-2
Poles 1P, 2P, 3P, 4P
Tripping characteristics C, K, Z
Rated current In 0.2 - 63 A
Rated frequency f 50 / 60 Hz, DC (0 Hz)
Rated insulation voltage Ui acc. to IEC/EN 440 V AC (phase to phase)
60664-1
Overvoltage category III
Pollution degree 3
IEC/EN 60947-2
Rated operational voltage Ue 1P: 230 V AC; 2P, 3P, 4P: 400 V AC
Max. power frequency recovery voltage Umax AC 1P: 253 V AC; 2P, 3P, 4P: 440 V AC
Min. operating voltage 12 V AC, 12 V DC
Rated ultimate short-circuit breaking capacity 15 kA
Icu
Rated service short-circuit breaking capacity Ics ≤ 40 A: 11.25 kA
> 40 A: 7.5 kA
Rated impulse withstand voltage Uimp 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
(1.2/50μs)
Dielectric test voltage 2 kV (50 / 60Hz, 1 min.)
Reference temperature for tripping 30 °C
characteristics
Electrical endurance In < 30 A: 20,000 ops (AC), In ≥ 30 A: 10,000 ops. (AC);
1 cycle (2 s - ON, 13 s - OFF, In ≤ 32 A), 1 cycle (2 s - ON,
28 s - OFF, In > 32 A)
UL / CSA
Rated voltage AC 1P: 277 V AC up to 40 A for C, Z char.,
AC 277 V AC up to 35 A for K char., 240 V AC
AC 2P, 3P, 4P: 480 Y / 277 V AC up to 40 A for C, Z char.,
AC 480 Y / 277 V AC up to 35 A for K char., 240 V AC
DC 1P: 48 V DC; 2P: 96 V DC (2p in series)
Rated interrupting capacity acc. to UL 1077 –
Short-circuit current rating acc. to UL 489 10 kA
Application –
Reference temperature for tripping 40 °C
characteristics
Electrical endurance 6,000 ops (AC), 6,000 ops. (DC); 1 cycle (1 s - ON, 9 s - OFF)
1/82 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
SU 200 M series technical characteristic
Mechanical data
Housing Insulation group II, RAL 7035
Toggle Insulation group II, black, sealable
Contact position indication Real CPI (green OFF / red ON)
Protection degree acc. to DIN EN 60529 IP20*, IP40 in enclosure with cover
Mechanical endurance 20,000 ops.
Shock resistance acc. to IEC/EN 60068-2-27 25 g - 2 shocks - 13 ms
Vibration resistance acc. to IEC/EN 60068-2-6 5g - 20 cycles at 5…150…5 Hz with load 0.8 In
Environmental conditions (damp heat cyclic) 28 cycles with 55°C/90-96% and 25°C/95-100%
acc. to IEC/EN 60068-2-30
Ambient temperature -25 … +55°C
Storage temperature -40 ... +70 °C
Installation
Terminal Failsafe bi-directional cylinder-lift terminal
Cross-section of conductors (top/bottom) solid, stranded: 35 mm² / 35 mm²
flexible: 25 mm 2 / 25 mm 2
18 – 4 AWG
Cross-section of busbars (top/bottom) 10 mm² / 10 mm²
18 – 8 AWG
Torque 2.8 Nm
AWG 18-16: 13.3 in-lbs.
AWG 14-10: 17.7 in-lbs.
AWG 8-4: 39.8 in-lbs.
Screwdriver No. 2 Pozidrive
Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip
Mounting position any
Supply optional
Dimensions and weight
Mounting dimensions acc. to DIN 43880 Mounting dimension 3
Pole dimensions (H x D x W) 111 x 69 x 17.5 mm
Pole weight approx. 125 g
Combination with auxiliary elements
Auxiliary contact Yes
Signal contact Yes
Shunt trip Yes
1
—
MCBs
SU 200 M series C characteristic
—
MCBs
SU 200 M series C characteristic
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
SU 200 M series K characteristic
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
SU 200 M series K characteristic
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
SU 200 M series Z characteristic
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCBs
SU 200 M series Z characteristic
1
—
MCBs
Circuit breaker SU 200 MR series, 10kA
The SU200 MR is a high-performance circuit breaker with ring cable lug connections
conforming to UL 489; CSA 22.2. No. 5 and IEC/EN 60947-2 standards. The integrated captive
connecting screws simplify the connection of electric lines, provides extra protection and
saves time.
2CDC021001S0015
—
MCBs
Circuit breaker SU 200 MR series, 10kA
1
—
MCBs
S 200 series UDC - Universal current range, UL, K characteristic
depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type
characteristic offers protection to damageable elements in the overcurrent range; it also
provides the best protection to cables and lines.
Applications: commercial and industrial.
S 201 UDC Standard: UL 489, CSA 22.2 No. 5
(only DC, please note polarity of device)
Short-circuit current rating (SCCR acc. to UL 489): 14 kA
—
MCBs
S 200 series UDC - Universal current range, UL, K characteristic
1
S 200 UDC-Z characteristic
Function: protection and control of the electronic circuits against lower and long duration
overloads and short-circuits.
Applications: commercial and industrial.
2CDC 021 128 F0010
S 201 UDC Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
—
MCB SN 201. The details make the difference
A range designed to ensure efficiency
and protection
Easy identification of
the product and highly
Quick identification resistant laser marking.
thanks to laser printed
EAN marking.
Contact position
indicator on the
level, with Green/
Red indicator
A wide range of
accessories is
available
1P+N protection
in only one module
1/99
1
Space for insulated screwdrivers: the larger neutral hole Two bistable fixing devices for maximum ease of use: due to
allows the use of an insulated screwdriver to tighten the larger size of the DIN rail fixing system, made with 2 bistable
screws of both wire terminals, ensuring maximum safety of fixing devices, the same screwdriver used for tightening the
the operation. terminals can also be used for assembling and
disassembling the device.
With the practical label carrier fitted in the SN201 circuit- The SN201 fully integrates with the range of System pro M
breakers you can give maximum visibility to the information compact® miniature circuit-breakers, sharing the wide
relating to the protected loads. selection of accessories available through a dedicated
interface (half module), which also can be used as auxiliary
contact.
1/100 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
Miniature circuit-breakers
SN 201 series - 1P+N in one module housing
Rated current In A
Rated frequency f Hz
Rated insulation voltage Ui acc. to DIN EN 60664-1 V
Overvoltage category
SN 201
Pollution degree
Data acc. to IEC/EN 60898-1 Rated operational voltage Un V
Max. power frequency recovery voltage (Umax) V
Min. operating voltage V
Rated short-circuit capacity Icn kA
Rated making and breaking capacity of one individual pole Icn1 kA
Energy limiting class (B, C up to 40A)
Rated impulse withstand voltage Uimp. (1.2/50µs) kV
Dielectric test voltage kV
Reference temperature for tripping characteristics °C
Electrical endurance operations
Data acc. to IEC/EN 60947-2 Rated ultimate short-circuit breaking capacity Icu kA
Rated service short-circuit breaking capacity Ics kA
Mechanical Data Housing
Toggle
Contact position indication
Protection degree acc. to EN 60529
Mechanical endurance operations
Shock resistance acc. to IEC/EN 60068-2-27
Vibration resistance acc. to IEC/EN 60068-2-6
Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30 °C/RH
Ambient temperature (with daily average ≤ +35°C) °C
Storage temperature °C
Installation Cross-section of conductors (top/bottom) Stranded / Solid mm 2
Cross-section of conductors (top/bottom) Flexible mm 2
Tightening Torque Nm
Mounting
Mounting Position
Supply
Dimensions and weight Pole dimensions (H x D x W) mm
Pole weight g
Combination with aux. ele- Auxiliary contact
ments Signal contact/auxiliary switch
Shunt trip
Undervoltage release
*1 SN201 and SN201M series in B and D characteristic are available for rated current In ≥ 6 A
1/101
1
SN 201 L SN 201 SN 201 M
IEC/EN 60898
1P + N
B, C B, C, D B, C
2…40 A *1
50 / 60 Hz
500 V AC
III
2
230 V AC
254 V AC 1P: 60 V DC 1P+N: 125 V DC
12 V AC - 12 V DC
4.5 kA 6 kA 10 kA
4.5 kA 6 kA 6 kA
3
4 kV (test voltage 6,2kV at sea level, 5kV at 2000m)
2.5 kV (50 / 60Hz, 1 min.)
30°C
10.000 operations
6 kA 10 kA 10 kA
4.5 kA 6 kA 7.5 kA
Insulation group II, RAL 7035
Insulation group IIIA, black, sealable in ON/OFF positions
Marking on toggle (I ON / 0 OFF)
Housing: IP4X; Terminals: IP2X
20.000 operations
30 g - 2 shocks - 13 ms
0,35mm or 5g - 20 cycles at 5…150…5 Hz without load
28 cycles with 55°C/90-96% and 25°C/95-100%
-25 … +55°C
-40 … +70°C
16 mm 2 / 16 mm 2
10 mm 2 / 10 mm 2
1.2 Nm
On DIN rail 35 mm acc. to EN 60715 by fast clip
any
optional (supply from top/bottom)
85 x 68.9 x 17.6 mm
ca. 110 g
Yes
Yes
Yes (with coupling interface)
Yes (with coupling interface)
1/102 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
SN 201 L series B and C characteristic
SN 201 L - B characteristic
Function: overload and short-circuit protection of circuits in final distribution; protection
of long cable lengths in TN and IT systems.
Applications: residential.
2CSC400667F0001
SN 201 L - C characteristic
Function: overload and short-circuit protection of circuits in final distribution; protection of
resistive and inductive loads with low inrush current.
Applications: residential.
Standard: IEC/EN 60898
Icn: 4.5 kA
1
—
MCBs
SN 201 series B and C characteristic
SN 201 - B characteristic
Function: overload and short-circuits protection of circuits in final distribution; protection of
long cable lengths in TN and IT systems.
Applications: residential and commercial.
2CSC400672F0001
SN 201 - C characteristic
Function: overload and short-circuit protection of circuits in final distribution; protection
of resistive and inductive loads with low inrush current.
Applications: residential and commercial.
Standard: IEC/EN 60898
Icn: 6 kA
—
MCBs
SN 201 series D characteristic
SN 201 - D characteristic
Function: protection and control of the circuits against overloads and short-circuits in final
distribution; protection for circuits which supply loads with high inrush current at the circuit
closing.
2CSC400670F0001
SN 201
Number Rated Bbn Order details Price Weight Pack
of poles current 8012542 1 piece 1 piece unit
1
—
MCBs
SN 201 M series B and C characteristic
SN 201 M - B characteristic
Function: overloads and short-circuit protection of circuits in final distribution; protection
of long cable lengths in TN and IT systems.
Applications: residential and commercial.
2CSC400665F0001
SN 201 M - C characteristic
Function: overload and short-circuit protection of circuits in final distribution; protection
of resistive and inductive loads with low inrush current.
Applications: residential and commercial.
Standard: IEC/EN 60898
Icn: 10 kA
—
MCBs
S 200 80A-100A series technical features
S 200 80A-100A
General Data
Standards IEC/EN 60898-1, IEC/EN 60947-2
Poles 1P, 2P, 3P, 4P, 1P+N, 3P+N
2CDC021037S0013
Tripping characteristics B, C
Rated current In 80 A, 100 A
Rated frequency f 50/60 Hz
S 200 80-100A Rated insulation voltage Ui acc. to IEC/EN 60664-1 440 V AC
(VDE 0110-1)
Overvoltage category III
Pollution degree 2
IEC/EN 60898-1
Rated operational voltage Un 1P: 230/400 V AC; 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC
Max. power frequency recovery voltage Umax 1P: 253/440 V AC; 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC
Min. operating voltage 12 V AC
Rated short-circuit capacity Icn 6 kA
Rated impulse withstand voltage Uimp (1.2/50µs) 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
Dielectrical test voltage 2 kV (50/60 Hz, 1 min.)
Reference temperature for tripping characteristics B, C: 30 °C
Electrical endurance 10,000 ops. (AC); one cycle 2 s - ON, 28 s - OFF
IEC/EN 60947-2
Rated operational voltage Ue 1P, 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC
Max. power frequency recovery voltage Umax 1P, 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC
Min. operating voltage 12 V AC
Rated ultimate short-circuit breaking capacity Icu 6 kA
Rated service short-circuit breaking capacity Ics 6 kA
Rated impulse withstand voltage Uimp (1.2/50 µs) 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
Dielectrical test voltage 2 kV (50/60 Hz, 1 min.)
Reference temperature for tripping characteristics B, C: 55 °C
Electrical endurance 10,000 ops. (AC); one cycle 2 s - ON, 28 s - OFF
1/107
1
Mechanical data
Housing Insulation group I, RAL 7035
Toggle Insulation group II, black, sealable
Contact position indication Real CPI (red ON/green OFF)
Protection degree acc. to DIN EN 60529 IP201), IP40 in enclosure with cover
Mechanical endurance 20,000 ops.
Shock resistance acc. to DIN EN 60068-2-27 25 g, 2 shocks, 13 ms
Vibration resistance acc. to DIN EN 60068-2-6 5 g, 20 cycles at 5…150…5 Hz at 0.8 In
Environmental conditions (Damp heat cyclic) acc. to 28 cycles with 55 °C/90-96 % and 25 °C/95-100 %
DIN EN 60068-2-30
Ambient temperature -25 ... +55 °C
Storage temperature -40 ... +70 °C
S 200 80A-100A
Installation
Terminal Failsafe bi-directional cache clamp
Cross-section of conductors (top/bottom) solid, stranded: 50 mm 2 / 50 mm 2
flexible: 50 mm 2 / 50 mm 2
Cross-section of busbars (top/bottom) 16 mm 2 / 16 mm 2
Torque 3.0 Nm
Screwdriver Nr. 2 Pozidriv
Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip
Mounting position any
Supply any
Dimensions and weight
Mounting dimensions acc. to DIN 43880 Mounting dimension 1
Pole dimensions (H x T x B) 88.8 x 69 x 17.5
Pole weight approx. 126 g
Combination with auxiliary elements
Auxiliary contact Yes
Signal/auxiliary contact Yes
Shunt trip Yes
Unervoltage release Yes
Motor Operating Device Yes
1/108 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S 200 80A-100A
The miniature circuit breakers of the System pro M compact® series S 200 provide state-of-
the-art safety and comfort. They stand out due to their high performance and the wide
range of accessories and approvals.
2CDC021037S0013
The additional electrical currents 80 A and 100 A complement the current portfolio of the
System pro M compact® and offer maximum performance in a single module width.
S 202 80-100A Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
S 203 80-100A NA
1
—
Minimum space, maximum
protection.
DS203NC: 3P+N RCBOs
in 4 modules.
Designed to be compact, DS203NC 3P+N RCBOs are suitable in all those applications
where size can be an obstacle. They provide reliable and complete protection from over-
current and earth fault currents. DS203NC RCBOS are available in two ranges with differ-
ent breaking capacities to cover all the applications in commercial and industrial installa-
tions; DS203NC L with 4.5kA and DS203NC with 6kA breaking capacity according to IEC/
EN 61009. The range includes types AC, A, APR and S and tripping curves B, C or K.
www.abb.com/lowvoltage
1/110 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
SMCBs
S750 series DR technical features
S 750 DR
General Data Standards IEC/EN 60947-2
Poles 1P, 2P, 3P, 4P
Tripping characteristics Eselective, K selective
2CDC 021 064 S0012
1
—
SMCBs
S750 series DR- selective main circuit-breakers, Eselective characteristic
S750 series DR
Selective main circuit-breakers of the S 750 DR series are SMCBs based on DIN VDE
0641-21 with voltage-independent operating principle. This means that they do not rely on a
control circuit to make or break contact (SHU) and are therefore particularly suitable for use
2CDC 021 064 S0012
S751 DR
Number Rated Bbn Order details Price Weight Pack
of poles current 4016779 1 piece 1 piece unit
S753 DR
3 16 4016779879569 S 753 DR-E16 2CDH783010R0162 1.05 1
20 4016779879576 S 753 DR-E20 2CDH783010R0202 1.05 1
25 4016779879583 S 753 DR-E25 2CDH783010R0252 1.05 1
32 4016779879590 S 753 DR-E32 2CDH783010R0322 1.05 1
40 4016779879613 S 753 DR-E40 2CDH783010R0402 1.05 1
50 4016779879620 S 753 DR-E50 2CDH783010R0502 1.05 1
2CDC 021 067 S0012
Due to the lack of international product standards for SMCB, S750DR products as given in this catalogue are certified acc.
to IEC/EN 60947-2. If requested, S750 (for 40mm busbar systems) and S750DR (for DIN rail mounting) are also available with
a certification based on a German SMCB standard. Please contact your ABB office for further information.
1/112 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
SMCBs
S750 DR series - selective main circuit-breakers, Kselective characteristic
S753 DR
4 16 4016779879866 S 754 DR-K16 2CDH784010R0467 1.4 1
20 4016779879873 S 754 DR-K20 2CDH784010R0487 1.4 1
25 4016779879880 S 754 DR-K25 2CDH784010R0517 1.4 1
32 4016779879897 S 754 DR-K32 2CDH784010R0537 1.4 1
40 4016779879910 S 754 DR-K40 2CDH784010R0557 1.4 1
50 4016779879927 S 754 DR-K50 2CDH784010R0577 1.4 1
2CDC 021 067 S0012
S754 DR
1/113
1
—
SMCBs
S700 series technical features
S 700
General Data Standards E DIN VDE 0645:2003-09,
partly acc. to IEC EN 60947-2
Poles 1P, 2P, 3P, 4P
Tripping characteristics Eselective, K selective
thermal tripping 1.05 … 1.2 x In
short-time delayed tripping E: 5 … 6.25 x In
S0029b98
K: 10 … 14 x In (≤ 50 A), 8 …12 x In (≥ 63 A)
minimum tripping delay ms 10
S700 Rated insulation voltage Ui acc.to IEC/EN V AC 690
60664-1
Rated current In A E: 10, 80, 100: K: 80, 100
Rated frequency f Hz 50 / 60
Electrical Rated operational voltage Un V AC 1P: 230 / 400; 2…4P: 400
Data Rated breaking capacity Icn kA 25
Selectivity limit current Is1 Rated breaking capactiy of the downstream MCB
(see selectivity tables)
Overvoltage category IV
Pollution degree 3
Rated impulse withstand voltage Uimp. kV 6
Impulse withstand voltage acc. to IEC 60364- kV 8
5-53, clause 536.2 (at 2000m over sea level)
Impulse withstand test voltage (1.2/50µs) at
sea level
new condition kV 12.3
after use kV 9.8
Isolation function acc. to IEC 60364-5-53 yes
Dielectric test voltage (50/60 Hz, 1 min.) kV 2
Mechanical Contact position indication Toggle (I ON / 0 OFF); Real CPI (red ON / green OFF)
Data IP protection degree acc. to IEC/EN 60529 IP40 (in enclosure with cover, cut-out dimension
46mm)
Mechanical switching cycles
without load ops. 1000
with rated current ops. 1000
Shock resistance acc. to IEC/EN 60068-2-27 25 g - 3 shocks - 13 ms
Vibration resistance acc. to IEC/EN 60068-2-6 2 g, 20 cycles 5…150…5Hz
Environmental conditions (damp heat cyclic) °C/ 28 cycles: 55°C/90…96% - 25°C/95…100%
acc. to IEC/EN 60068-2-30 RH
Ambient temperature °C -25 … +55
Storage temperature °C -40 … +70
Installation Terminal type Saddle terminal
Terminal size top / bottom mm 2 Capable to connect solid and rigid stranded
conductors incl. flexible conductors 2.5…50 / 70
Terminal screws tighning torque Nm 3…3.5
Max. torque for surface mounting Nm 2.5 … 3 (only fl at-headed screws, no circlips)
Recommended screwdriver Slot: 1 x 5.5, cross slot: PZ 2
Mounting Surface mounting with 2 screws, DIN rail mounting
(35 mm DIN rail acc. to EN 60715, 40 mm busbar
systems 4/5-pole, 5/10 mm x 12 mm)
Mounting position any
Supply side/load side any
Dimensions Size acc. to DIN 43880 5 (mounting on DIN-Rail); 6 (mounting on busbar)
and weight Width 2 modules / pole
Pole dimensions (H x D x W) see drawings
Pole weight see order tables
Accessories Optional: version with factory assembled auxiliary
switch (2 change-over contacts)
Terminal covers
Handle covers
Busbar adapters
DIN rail adapters
Locking devices
1/114 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
SMCBs
S700 series - selective main circuit-breakers, Eselective characteristic
S700 E characteristic
Breakers of the S700 series are selective main circuit-breakers (SMCB) for overcurrent
protection in electrical installations. They have total selectivity to downstream mcb’s and
outstanding selectivity to upstream protective devices due to unique current limiting
selectivity. Since S700 breakers are designed for overvoltage category IV and incorporate
isolation function, they are predestinated for the use in any main distribution cabinet or
S0029b98
meter board.
The S700 product range is completed by a broad range of accessories. With dedicated
S701 adapters, S700 products can be assembled on flat surfaces, on DIN rails or 40 mm busbar
systems. To adapt S700 to different installations, they are available 1- to 4-pole with tripping
characteristic E and K - optional with factory assembled auxiliary switch.
*1 bbn-Nr. 40 12233
1/115
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4012233 1 piece 1 piece unit
S704
1/116 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
SMCBs
S700 series - selective main circuit-breakers, Kselective characteristic
S700 K characteristic
Breakers of the S700 series are selective main circuit-breakers (SMCB) for overcurrent
protection in electrical installations. They have total selectivity to downstream mcb’s and
outstanding selectivity to upstream protective devices due to unique current limiting
selectivity. Since S700 breakers are designed for overvoltage category IV and incorporate
isolation function, they are predestinated for the use in any main distribution cabinet or
S0029b98
meter board.
The S700 product range iS completed by a broad range of accessories. With dedicated
S701 adapters, S700 products can be assembled on flat surfaces, on DIN rails or 40 mm busbar
systems. To adapt S700 to different installations, they are available 1- to 4-pole with tripping
characteristic E and K - optional with factory assembled auxiliary switch.
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4012233 1 piece 1 piece unit
S703
Number Rated Bbn Order details Price Weight Pack
of poles current 40 16779 1 piece 1 piece unit
*1 bbn-Nr. 40 12233
S0012b95
S704
1/118 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
SMCBs
S700 series - selective main circuit-breakers, Eselective characteristic + H2WR
S700 E characteristic
Breakers of the S700 series are selective main circuit-breakers (SMCB) for overcurrent
protection in electrical installations. They have total selectivity to downstream mcb’s and
outstanding selectivity to upstream protective devices due to unique current limiting
selectivity. Since S700 breakers are designed for overvoltage category IV and incorporate
S0029b98
isolation function, they are predestinated for the use in any main distribution cabinet or
meter board.
S701 + H2WR The S700 product range is completed by a broad range of accessories. With dedicated
adapters, S700 products can be assembled on flat surfaces, on DIN rails or 40 mm busbar
systems. To adapt S700 to different installations, they are available 1- to 4-pole with tripping
characteristic E and K - optional with factory assembled auxiliary switch (H2WR).
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4012233 1 piece 1 piece unit
S704 + H2WR
1/120 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
SMCBs
S700 series - selective main circuit-breakers, Kselective characteristic + H2WR
S700 K characteristic
Breakers of the S700 series are selective main circuit-breakers (SMCB) for overcurrent
protection in electrical installations. They have total selectivity to downstream mcb’s and
outstanding selectivity to upstream protective devices due to unique current limiting
S0029b98
selectivity. Since S700 breakers are designed for overvoltage category IV and incorporate
isolation function, they are predestinated for the use in any main distribution cabinet or
meter board.
S701 + H2WR The S700 product range is completed by a broad range of accessories. With dedicated
adapters, S700 products can be assembled on flat surfaces, on DIN rails or 40 mm busbar
systems. To adapt S700 to different installations, they are available 1- to 4-pole with tripping
characteristic E and K - optional with factory assembled auxiliary switch (H2WR).
1
Number Rated Bbn Order details Price Weight Pack
of poles current 4012233 1 piece 1 piece unit
S703 + H2WR Number Rated Bbn Order details Price Weight Pack
of poles current 4012233 1 piece 1 piece unit
S704 + H2WR
1/122 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
SMCBs
Selective short-circuit current limiter WT63
WT63 characteristic
WT63 is a short-circuit current limiter for 690 V AC applications.
In combination with other ABB devices WT63 offers smart solutions for coordinated motor
protection according to IEC/EN 60947-4-1. As a main limiting device, WT63 can increase the
short-circuit breaking capability for several groups of motor circuits to high values at
S0029b98
690 V AC. For further information according to selection and installation see the
WT63 coordination table.
With only 2 modules, the DS202C series of 2P residual current circuit-breakers with
overcurrent protection (RCBOs) enables to save 50 % of switchboard space compared
to the conventional 4-modules solution. Available in a technologically advanced and
comprehensive range, the DS202C can be applied in the tertiary sector, in large-sized
industrial plants and in naval applications. The series perfectly integrates with the
System pro M compact® range, starting from the same profile, ensuring a nice and
functional design in the installation. The maximum protection in only 2 modules.
www.abb.com
1/124 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
High Performance MCB S800
Incomparable performances
Interchangeable
terminal, failsafe
cage or ring lug
Clear identification of terminal
the reason of cut-off
thanks to TRIP position
of the toggle
Quick identification of
technical characteristics
thanks to laser-printing
Easy product name, of all data
easy identification,
easy life.
Clear identification of
the moving contact
position thanks to
toggle identification ON,
OFF and TRIP position
1/125
1
Housing materials Shock and vibration resistance Play it safe: display the operational
In the S800 range of MCBs for traction, Additionally to the high quality state
specific materials are used that are standards and the fl ammability The mechanical drive of the S800 high
classified with an hazard level R26/HL3 requirements, rail applications have performance MCB is equipped with a
according to EN 45545-2. Plastic specific demands that have to be to trip-free release. The trip position
materials are also classified I2-F3 fulfi lled like resistance to shocks and display thereby always reliably displays
according the NF F 16-101/102 vibrations. The resistance to vibrations the exact position of the moving
(“Railway Rolling Stock Fire Behavior- and shocks of S800 has been positively contact. The trip position provides
Choice of Materials„ and “Railway tested according to: IEC 61373 – 2010 – additional trip detection allowing to
Rolling Stock Fire Behavior- Choice of 05 Edition 2.0 Rolling stock equipment easily identify the reason for the cut-
Materials, Application to Electrical – Shock and vibration tests off. The switch lever moves to the
Equipment„) thus responding to considering Category 1, Class A and middle position in case of thermal or
exigency 3. Class B. magnetic tripping.
Cage and ring terminals Reliable: the disconnector properties Wide range of accessories
The S800 standard equipment with In OFF position (0 position), the S800 S800 MCB range is completed with a
interchangeable terminal adapter for high performance MCB guarantees wide range of accessories that enlarge
wires, cables and rigid conductors safe electrical isolation of the circuit the functions of the MCB not only as a
guarantees a high level of flexibility compliant to IEC 60947-2. protection devices, but even for con-
and comfort. Fast and safe connection trol and monitor remotely the installa-
of the conductors is ensured by the tion. The range of accessories include
“onboard terminal shutter” integrated auxiliary contacts, aux/signal contacts,
into the body of the terminal, thereby remote switching unit, short circuit
preventing incorrect underclamping of limiter, shunt operation releases, un-
the connections. dervoltage releases and busbars.
1/126 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S800 series technical features
S800S S803S-KM
Tripping characteristics B, C, D, K KM
Standards IEC/EN 60947-2 IEC/EN 60947-2
2CCC413001F0002
IEC/EN 60898-1
UL 1077
Poles 1…4 3
Rated current Ie A 6 … 125 20 … 80
Note: The minimum operating voltage for S800 is 12 VAC/VDC. *certification 50A ongoing
1/127
1
S800S-UC S800N S800C
UCB, UCK B, C, D B, C, D, K
IEC/EN 60947-2 IEC/EN 60947-2, IEC/EN 60947-2
IEC/EN 60898-1 EN 60898-1
UL 1077
1…4 1…4 1…4
10 … 125 6 … 125 10 … 125
50/60 50/60 50/60
DC 1000 AC 690 AC 500
8 8 8
IV IV IV
1- and 2-pole: 3 3 3
3- and 4-pole: 2
yes yes yes
– AC 230/400 AC 230/400
– 230/400 V (10 … 80 A) = 20 kA Char. B, C, D: 230/400 V = 15 kA
– 230/400 V Char. B, C, D:
(10 … 80 A) = 10 kA 230/400 V = 7.5 kA
1...4
AC 240 (1 -pole ... 4-pole) Δ
AC 277 (1 -pole) Y
AC 277/480 (2 -pole ... 4-pole) Y
DC 125 (1-pole)
DC 250 (2-pole)
DC 375 (3-pole)
DC 500 (4-pole)
10 ... 100
B, C, D, K
AC 240 (1 -pole ... 4-pole) Δ = 20 kA
AC 277 (1 -pole) Y = 10 kA
AC 277/480 (2 -pole ... 4-pole) Y = 10 kA
DC 125 (1-pole) = 10 kA
DC 250 (2-pole) = 10 kA
DC 375 (3-pole) = 10 kA
DC 500 (4-pole) = 10 kA
1/128 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S800 series technical features
Direct current:
int. cap.
Installation
Terminal Failsafe cage or ringlug terminal
Connections (top/bottom) – Cu only mm2 1 … 50 stranded
1 … 70 flexible
Tightening torque Nm 3.5
in-Ibs. 31
Screwdriver POZI 2
Mounting EN 60715
Mounting position any
Supply any
Dimensions and weight
Pole dimensions (H x L x W) mm 82.5 x 95 x 26.5
Pole weight g ca. 240
1/129
1
S800N S800C
B, C, D B, C, D, K
1, 1P+N
240: 20(≤ 100A)
347: 10 (≤ 100A)
2,3,4
480 Y/277: 10 (≤ 100A)
1, 1P+N
125: 10 (≤ 100A)
2, 3, 4
250: 10 (2P, ≤ 100A)
375: 10 (3P, ≤ 100A)
500: 10 (4P, ≤ 100A)
—
MCBs
S800 series technical features
S800B S800HV
Tripping characteristics B, C, D, K C, K
Standards IEC 60947-2 IEC/EN 60947-2
2CCC413001F0002
EN 60898-1 UL 1077
Poles 1…4 1…3
Rated current Ie A Char. C: 10, 32
Char. K: 6...125
S800 Rated frequency f Hz 50/60 50/60
Rated insulation voltage Ui V AC 500 AC 1000
acc. to IEC/EN 60664-1
Rated impulse withstand kV 6 8
voltage Uimp (1.2/50µs)
Overvoltage category III III
Pollution degree 3 2
Suitability for isolation yes yes
Data acc. to IEC/EN 60898-1
Rated operational voltage Ue V AC 230/400 –
Rated short-circuit capacity Icn kA 230/400 V = 10 kA –
Service short-circuit capacity Ics kA 230/400 V = 7.5 kA –
Data acc. to IEC/EN 60947-3
Rated operational voltage Ue V – –
Min. operating voltage V – –
Rated short-term withstand current Icw kA – –
Rated short-circuit making capacity Icm kA – –
Utilisation category – –
Data acc. to IEC/EN 60947-2
Rated operational voltage Ue V AC 230/400 AC 580/1000
Rated ultimate short-circuit capacity Icu kA AC 230 V = 16 kA AC 580/1000
AC 230/400 V = 16 kA (6 … 63 A) = 4kA
DC 75 V (1-pole) = 10 kA (80 … 125 A) = 3kA
DC 150 V (2-pole) = 10 kA
DC 225 V (3-pole = 10 kA
DC 300 V (4-pole) = 10 kA
Rated service short-circuit capacity Ics kA AC 230 V = 10 kA 2.5 (6 … 63 A)
AC 230/400 V = 10 kA 2 (80 … 125 A)
Data acc.to UL 1077,
Supplementary Protector
Poles 3
Rated voltage Un V AC 600
Rated current In A 10 ... 32
Characteristic C, K
Short - circuit breaking capacity Icc kA AC 600 Y = 15 kA with XT2L 125A
TMF35-400
1/131
1
S800B S800HV
B, C, D, K C, K
Mechanical Data
Housing Material group I, RAL 7035 Material group I, RAL 7035
Toggle black, lockable black, lockable
Classification acc. to NF F 126-101, I3, F2 I3, F2
NF F 16-102
Protection degree acc. to EN 60529 IP20; IP40 (actuating end only) IP20; IP40 (actuating end only)
Classification acc. to IEC 61373 Cat. 1, Class B
(shock and vibration)
Shock resistance acc. to IEC/EN Test Ea: 5 g / 30 ms
60068-2-27
Vibration resistance acc. to IEC/EN Test Fc:
60068-2-6 2–13.2 Hz/1 mm
13.2–100 Hz/0.7 g
with load 100 % x Ie
Environmental conditions (damp °C/RH 12 + 12 cycle with 55 °C/90–96 %
heat) acc. to IEC/EN 60068-2-30 and 25 °C/95–100 %
Environmental conditions (dry heat) °C/RH 16 hours 55°C / 2 hours 70°C / 55% RH
acc. to IEC/EN 60068-2-2 Test B
Ambient temperature °C –25 … +60 –25 … +60
Storage temperature °C –40 … +70 –40 … +70
Installation
Terminal Failsafe cage or ringlug terminal Failsafe cage terminal
Connections (top/bottom) – Cu only mm2 1 … 50 stranded 1 … 50 stranded
1 … 70 flexible 1 … 70 flexible
Tightening torque Nm 3.5 3.5
in-Ibs. 31
Screwdriver POZI 2 POZI 2
Mounting EN 60715 EN 60715
Mounting position any any
Supply any any
Dimensions and weight
Pole dimensions (H x L x W) mm 82.5 x 95 x 26.5 142 x 82.5 x 26.5
Pole weight g ca. 240 0.27
1/132 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
High performance MCBs
S800S series with cage terminal, B characteristic
S800S-B characteristic
Function: protection and control of the circuits against overloads and short-circuits when
2CCC413001F0002
a high breaking capacity is required; protection for people and big length cables in TN and
IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs
wired downstream.
Applications: commercial and industrial.
S801S Standard: IEC/EN 60898, IEC/EN 60947-2, UL 1077, supplementary protector
Icn=25kA (10 ... 80A)
Icu=50 kA
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612271 1 piece 1 piece unit
—
High performance MCBs
S800S series with ring terminal connection, B characteristic
S800S-B characteristic
Function: protection and control of the circuits against overloads and short-circuits when
a high breaking capacity is required; protection for people and big length cables in TN and IT
systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired
2CCC413078F0003
downstream.
Applications: commercial and industrial.
Standard: IEC/EN 60898, IEC/EN 60947-2, UL 1077, supplementary protector
Icn=25kA (10 ... 80A)
S801S
Icu=50 kA
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612271 1 piece 1 piece unit
—
High performance MCBs
S800S series with cage terminal, C characteristic
S800S-C characteristic
Function: protection and control of the circuits against overloads and short-circuits when a
2CCC413005F0002
high breaking capacity is required; protection for resistive and inductive loads with low
inrush current; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs
wired downstream.
Applications: commercial and industrial.
S801S Standard: IEC/EN 60898, IEC/EN 60947-2, UL 1077, supplementary protector
Icn=25kA (10 ... 80A)
Icu=50 kA
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612271 1 piece 1 piece unit
—
High performance MCBs
S800S series with ring terminal connection, C characteristic
S800S-C characteristic
Function: protection and control of the circuits against overloads and short-circuits when a
2CCC413082F0003
high breaking capacity is required; protection for resistive and inductive loads with low
inrush current; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs
wired downstream.
Applications: commercial and industrial.
Standard: IEC/EN 60947-2, IEC/EN 60898
Icn=25kA (10 ... 80A)
S801S Icu=50 kA
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612271 1 piece 1 piece unit
—
High performance MCBs
S800S series with cage terminal, D characteristic
S800S-D characteristic
Function: protection and control of the circuits against overloads and short-circuits when a
high breaking capacity is required; protection for circuits which supply loads with high
2CCC413009F0002
inrush current at the circuit closing (motors, LV / LV transformers, breakdown lamps); very
useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream.
Applications: commercial and industrial.
S801S Standard: IEC/EN 60898, IEC/EN 60947-2, UL 1077, supplementary protector
Icn=25kA (10 ... 80A)
Icu=50 kA
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612271 1 piece 1 piece unit
—
High performance MCBs
S800S series with ring terminal connection, D characteristic
S800S-D characteristic
Function: protection and control of the circuits against overloads and short-circuits when
a high breaking capacity is required; protection for circuits which supply loads with high
inrush current at the circuit closing (motors, LV / LV transformers, breakdown lamps); very
2CCC413086F0003
useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream.
Applications: commercial and industrial.
Standard: IEC/EN 60947-2, IEC/EN 60898
Icn=25kA (10 ... 80A)
S801S Icu=50 kA
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612271 1 piece 1 piece unit
—
High performance MCBs
S800S series with cage terminal, K characteristic
S800S-K characteristic
Function: protection and control of the circuits like motors, transformer and auxiliary
circuits, against overloads and short-circuits when a high breaking capacity is required; very
2CCC413013F0001
useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream.
Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn,
depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type
S801S characteristic offers protection to damageable elements in the overcurrent range; it also
provides the best protection to cables and lines.
Applications: commercial and industrial.
Standard: IEC/EN 60947-2, UL 1077, supplementary protector
Icu=50 kA
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612271 1 piece 1 piece unit
—
High performance MCBs
S800S series with ring terminal connection, K characteristic
S800S-K characteristic
Function: protection and control of the circuits like motors, transformer and auxiliary
circuits, against overloads and short-circuits when a high breaking capacity is required; very
useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream.
2CCC413090F0003
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612271 1 piece 1 piece unit
—
High performance MCBs
S800S series KM characteristic
very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired
downstream; version dedicated to application in direct current circuits.
Applications: commercial and industrial.
Standard: IEC/EN 60947-2
S803S
Icu=50 kA
1
—
High performance MCBs
S800S series DC range with cage terminal, UC-B characteristic
S800S-UCB characteristic
Function: protection and control of the circuits against overloads and short-circuits when a
high breaking capacity is required; protection for people and big length cables in TN and IT
2CCC413223F0001
systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired
downstream; version dedicated to application in direct current circuits.
Applications: commercial and industrial.
Standard: IEC/EN 60947-2
S801S Icu=50 kA
—
High performance MCBs
S800S series DC range with cage terminal, UC-B characteristic
1
—
High performance MCBs
S800S series DC range with ring terminal connection, UC-B characteristic
S800S-UCB characteristic
Function: protection and control of the circuits against overloads and short-circuits when
a high breaking capacity is required; protection for people and big length cables in TN and IT
systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired
2CCC413231F0001
—
High performance MCBs
S800S series DC range with ring terminal connection, UC-B characteristic
1
—
High performance MCBs
S800S series DC range with cage terminal, UC-K characteristic
S800S-UCK characteristic
Function: protection and control of the circuits like motors, transformer and auxiliary
circuits, against overloads and short-circuits when a high breaking capacity is required; very
2CCC413223F0001
useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream;
version dedicated to application in direct current circuits.
Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn,
depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type
S801S characteristic offers protection to damageable elements in the overcurrent range; it also
provides the best protection to cables and lines.
Applications: commercial and industrial.
Standard: IEC/EN 60947-2
Icu=50 kA
—
High performance MCBs
S800S series DC range with cage terminal, UC-K characteristic
1
—
High performance MCBs
S800S series DC range with ring terminal connection, UC-K characteristic
S800S-UCK characteristic
Function: protection and control of the circuits like motors, transformer and auxiliary
circuits, against overloads and short-circuits when a high breaking capacity is required;
very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired
2CCC413231F0001
—
High performance MCBs
S800S series DC range with ring terminal connection, UC-K characteristic
1
—
High performance MCBs
S800N series with cage terminal, B characteristic
S800N-B characteristic
Function: protection and control of the circuits against overloads and short-circuits when
a high breaking capacity is required; protection for people and big length cables in TN and IT
2CCC413223F0001
systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired
downstream.
Applications: commercial and industrial.
Standard: IEC/EN 60898, IEC/EN 60947-2
S801N Icn=20 kA (10 ... 80 A)
Icu=36 kA
—
High performance MCBs
S800N series with cage terminal, B characteristic
1
—
High performance MCBs
S800N series with cage terminal, C characteristic
S800N-C characteristic
Function: protection and control of the circuits against overloads and short-circuits when
a high breaking capacity is required; protection for resistive and inductive loads with low
2CCC413223F0001
inrush current; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs
wired downstream.
Applications: commercial and industrial.
Standard: IEC/EN 60898, IEC/EN 60947-2
S801N Icn=20 kA (10 ... 80 A)
Icu=36 kA
—
High performance MCBs
S800N series with cage terminal, C characteristic
1
—
High performance MCBs
S800N series with cage terminal, D characteristic
S800N-D characteristic
Function: protection and control of the circuits against overloads and short-circuits when a
high breaking capacity is required; protection for circuits which supply loads with high
2CCC413223F0001
inrush current at the circuit closing (motors, LV / LV transformers, breakdown lamps); very
useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream.
Applications: commercial and industrial.
Standard: IEC/EN 60898, IEC/EN 60947-2
S801N Icn=20 kA (10 ... 80 A)
Icu=36 kA
—
High performance MCBs
S800N series with cage terminal, D characteristic
1
—
High performance MCBs
S800C series with cage terminal, B characteristic
S800C-B characteristic
Function: protection and control of the circuits against overloads and short-circuits when
2CCC413001F0021
a high breaking capacity is required; protection for people and big length cables in TN and IT
systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired
downstream.
Applications: commercial and industrial.
Standard: IEC/EN 60947-2, IEC/EN 60898, UL 1077, supplementary protector
S801C
Icn=15 kA
Icu=25 kA
—
High performance MCBs
S800C series with cage terminal, B characteristic
1
—
High performance MCBs
S800C series with cage terminal, C characteristic
S800C-C characteristic
Function: protection and control of the circuits against overloads and short-circuits when
2CCC413001F0021
a high breaking capacity is required; protection for people and big length cables in TN and IT
systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired
downstream.
Applications: commercial and industrial.
Standard: IEC/EN 60947-2, IEC/EN 60898, UL 1077, supplementary protector
S801C
Icn=15 kA
Icu=25 kA
—
High performance MCBs
S800C series with cage terminal, C characteristic
1
—
High performance MCBs
S800C series with cage terminal, D characteristic
S800C-D characteristic
Function: protection and control of the circuits against overloads and short-circuits when
2CCC413001F0021
a high breaking capacity is required; protection for people and big length cables in TN and IT
systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired
downstream.
Applications: commercial and industrial.
S801C Standard: IEC/EN 60947-2, IEC/EN 60898, UL 1077, supplementary protector
Icn=15kA
Icu=25 kA
—
High performance MCBs
S800C series with cage terminal, D characteristic
1
—
High performance MCBs
S800C series with cage terminal, K characteristic
S800C-K characteristic
Function: protection and control of the circuits against overloads and short-circuits when
2CCC413001F0021
a high breaking capacity is required; protection for people and big length cables in TN and IT
systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired
downstream.
Applications: commercial and industrial.
S801C Standard: IEC/EN 60947-2, UL 1077, supplementary protector
Icu=25 kA
—
High performance MCBs
S800C series with cage terminal, K characteristic
1
—
High performance MCBs
S800B series with cage terminal, B characteristic
S800B-B characteristic
Function: protection and control of the circuits against overloads and short-circuits. With
2CCC413368F0001
its lower breaking capacity it is designed to meet the needs of the sub-distributions.
Applications: commercial and industrial.
Standard: IEC/EN 60947-2, EN 60898
Icn=10kA
S801B Icu=16 kA
—
High performance MCBs
S800B series with cage terminal, C characteristic
S800B-C characteristic
Function: protection and control of the circuits against overloads and short-circuits. With
its lower breaking capacity it is designed to meet the needs of the sub-distributions.
2CCC413368F0001
1
—
High performance MCBs
S800B series cage terminal, D characteristic
S800B-D characteristic
Function: protection and control of the circuits against overloads and short-circuits. With
its lower breaking capacity it is designed to meet the needs of the sub-distributions.
2CCC413368F0001
S804B
Number Rated Bbn Order details Price Weight Pack
of poles current 7612271 1 piece 1 piece unit
—
High performance MCBs
S800B series with cage terminal, K characteristic
S800B-K characteristic
Function: protection and control of the circuits against overloads and short-circuits. With its
lower breaking capacity it is designed to meet the needs of the sub-distributions.
2CCC413368F0001
1
—
High performance MCBs
S800HV series for application up to 1000V AC
S800HV-K characteristics
Function: protection and control of the circuits against overloads and short-circuits. With its
Function: S800HV is designed for voltages up to 580/1000 V AC. Due to the high rated
operational voltage, the field of application is wide – from underground mining to
distributions on high altitudes.
2CCC413368F0001
Applications: Industrial
Standard: IEC/EN 60947-2, UL 1077, supplementary protector
Icu 4 kA (6 … 63 A); 3 kA (80 … 125 A)
S801HV
Icu Rated Bbn Order details Price Weight Pack
current 76122714 1 piece 1 piece unit
—
High performance MCBs
S800HV series for application up to 1000V AC
S800HV-C characteristics
S802HV Function: protection and control of the circuits against overloads and short-circuits. With its
Function: S800HV is designed for voltages up to 580/1000 V AC. Due to the high rated
operational voltage, the field of application is wide – from underground mining to
distributions on high altitudes.
Applications: industrial
Standard: IEC/EN 60947-2, UL 1077, supplementary protector
Icu = 4 kA
srotarepo rof ytefas mumixam gnirusne elihw smetsys lacirtcele lairtsudni ni emitnwod timiL
tneicfife ein
Limit downtime raindustrial
srekaerbelectrical
tiucric esystems
cnamrofwhile
rep hensuring
gih B 00maximum
8S :secivesafety
d ot sfor
secopera-
ca fo esae dna
ni nease
tors and oitceof toraccess
p tiucrtoic-devices:
trohs dnS800
a daB
olhigh
revo performance
rof dengisedcircuit-breakers
dna tsoc elbaare nosefficient
aer a ta stcudorp
2-74products
906 NE atIEaCreasonable
dradnatS costhtiw and
ylpm designed
oc yehTfor
.ytoverload
icapac gand
nikashort-circuit
erb Ak 61 hprotection
tiw smetsyins noitubirtsid
skdistribution
nahT .sevrusystems
c citsirewith
tcara16
hckAKbreaking
dna D ,Ccapacity.
,B htiwThey
seulcomply
av tnerrwith
uc dStandard
etar A 52CEI1 oEN
t 08 erutaef dna
60947-2, 60898-1 and feature 80 to 125 A rated current values with B, C, D and K character-
,revel hctiws a ot dna ,stcatnoc gnivom lanretni fo noitisop eht gniwohs ,langis neerg/der a ot
istic curves. Thanks to a red/green signal, showing the position of internal moving con-
yhw wohs yeht ,gnippirt citengam ro lamreht fo esac ni noitisop elddim eht ni spots taht
tacts, and to a switch lever, that stops in the middle position in case of thermal or magnetic
etripping,
gatlovw o l / m o c . b ba.w w w .ecnanetniam tpmorp gnilbane ,ecnalg a ta derrucco gnippirt
they show why tripping occurred at a glance, enabling prompt maintenance. Per-
formance similar to moulded case circuit-breakers but with the advantage of the compact
dimension, S800 B are available from 1 to 4 poles versions. www.abb.com/lowvoltage
1/178 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
High performance MCBs
S800U series technical features
Tripping characteristics
Rated current Ie A
Rated frequency f Hz
Ambient temperature °C
Storage temperature °C
1/179
1
S800U S804U-UCZ S804U-PVS
UL489 UL489 UL489B (Photovoltaic)
1…4 4 4
K, Z UCZ PVS
10 - 100 10 - 80 5
50 / 60 Hz - -
690 V AC DC 1500 DC 1500
8 8 8
IV IV IV
3 3 3
yes yes yes
AC 240/415
AC 12 - -
1-pole: AC 240V 30kA - -
multipole: AC 415V 50kA - -
1-pole: AC 240V 25kA - -
multipole: AC 415V 40kA - -
25°C - -
10 … 32A: 10‘000 electrical/mechanical - -
40 …100A: 6‘000 electrical/4‘000 mechanical
125A: 4‘000 electrical/6‘000 mechanical
AC 240 DC 600 DC 1000
1-pole 30kA 10
multipole: 50kA
3
25°C 25°C 50°C
acc. to UL489 acc. to UL489 acc. to UL489
6000 electrical; 4000 mechanical 6000 electric; 4000 mechanic 1000 electrical; 1000 mechanical
Material group I, RAL 7035 Material group I, RAL 7035 Material group I, RAL 7035
black, lockable black, lockable black, lockable
IP20; IP40 (actuating end only) IP20; IP40 (actuating end only) IP20; IP40 (actuating end only)
—
High performance MCBs
S800U series technical features
Installation
Terminal
2CCC413001F0021
Tightening torque Nm
in-Ibs.
Screwdriver
Mounting
Mounting position
Supply
Dimensions and Pole dimensions (H x L x W) mm
weight Pole weight g
Combination with aux. Auxiliary contact
elements Combined auxiliary- / signal contact
Undervoltage release
Shunt open release
Motor Operating Device
1/181
1
S800U S804U-UCZ S804U-PVS
Failsafe cage or ringlug terminal Failsafe cage terminal Failsafe cage terminal
1 … 50 1 … 50
Cu only Cu only 14 AWG – 2 AWG
10 - 30 A: 14 - 2 AWG 10 - 32A: 14-2 AWG Single conductor per terminal – copper only,
40 - 100 A: 1 - 8 AWG 40 - 80A: 1 - 8 AWG 75C wire
1 … 70 1 … 70
Cu only Cu only 14 AWG – 2 AWG Single conductor per terminal –
10 - 30 A: 14 - 2 AWG 10 - 32A: 14-2 AWG copper only, 75C wire
40 - 100 A: 1 - 8 AWG 40 - 80A: 1 - 8 AWG
3,5 3,5 3,5
31 31 31
POZI 2 POZI 2 POZI 2
any any any
any any any
any any any
95 x 26.5 x 82.5 142 x 26.5 x 82.5 142 x 26.5 x 82.5
240 240 240
yes yes yes
yes yes yes
yes yes yes
yes yes yes
yes yes yes
1/182 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
High performance MCBs
S800U series with cage terminal, Z characteristic
S800U-Z characteristic
Function: protection and control of the circuits against overloads and short-circuits when a
high breaking capacity is required; protection for people and big length cables in TN and IT
2CCC413001F0021
systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired
downstream.
Applications: commercial and industrial.
S801U Standard: UL489, CSA 22.2 NO.5-02, IEC/EN 60947-2
Icu=30 kA (1 pole), 50 kA (2...4 poles)
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612271 1 piece 1 piece unit
—
High performance MCBs
S800U series with cage terminal, K characteristic
S800U-K characteristic
Function: protection and control of the circuits against overloads and short-circuits when
2CCC413001F0021
a high breaking capacity is required; protection for people and big length cables in TN
and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612271 1 piece 1 piece unit
—
High performance MCBs
S800U series UCZ characteristic
1
—
High performance MCBs
S800U series PVS characteristic
—
High performance MCBs
S800PV series technical features
S800PV-SP
General Data Standards IEC / EN 60947-2 and Annex P
Poles 2…4
2CCC413002F0021
Tripping characteristics B
Rated current Ie A 5 … 125
Rated frequency f Hz -
Rated insulation voltage Ui acc. to IEC/EN 60664-1 V DC 1500
S800PV Rated impulse withstand voltage Uimp. (1.2/50µs) kV 8
Overvoltage category III
Pollution degree 2
Suitability for isolation yes
Data acc. Rated operational voltage Ue V 2-pole DC 800V: 5 ... 125A
to IEC/EN 3-pole DC 1200V: 5 ... 125A
60947-2 4-pole DC 1500V: 5 ... 125A
Min. operating voltage V -
Rated ultimate short-circuit capacity Icu kA 5 ... 16 A acc. IEC 60947-2 Annex P., Icu 5 kA
20 ... 125 A acc. IEC 60947-2, Icu 5 kA
20 ... 125 A acc. IEC 60947-2 Annex P., Icu 3 kA
Rated service short-circuit capacity Ics kA Ics = Icu
Reference temperature for tripping characteristics °C 40°C
Electrical and Mechanical Endurance ops. acc. to Annex P:
5 ... 16A: 300 electrical cycles
9700 mechanical cycles
acc. to IEC 60947-2 (general part):
20 ... 100A: 1500 electrical cycles
8500 mechanical cycles
125A: 1000 electrical cycles
9000 mechanical cycles
Mechanical Housing Material group I, RAL 7035
Data Toggle black, lockable
Classification acc. To NF F 126-101, NF F 16-102 -
Protection degree acc. to EN 60529 IP20; IP40 (actuating end only)
Shock resistance acc. to IEC/EN 60068-2-30 IEC 61373 Cat. 1 Class B, 5g / 30ms acc. To
IEC 60068-27 Test Ea
Vibration resistance acc. to IEC/EN 60068-2-6 IEC 60068-2-6 Test Fc; 2 - 13.2Hz /1mm 13.2 -
100Hz / 0.7g with load 100% x Ie
Environmental conditions (damp heat ) acc. to °C/RH 12 + 12 cycle with 55°C / 90-96% and 25% /
IEC/EN 60068-2-30 95-100%
Environmental conditions (dry heat ) acc. to IEC/ °C/RH 16 hours 55°C / 2 hours 70°C with damp heat
EN 60068-2-2 Test B 55%
Ambient temperature °C -25 … + 60
Storage temperature °C -40 … +70
Installation Terminal Failsafe cage or ringlug terminal
Stranded Cross-section of conductors (top / mm 2 1 … 50
bottom)
Flexible Cross-section of conductors (top/ mm 2 1 … 70
bottom)
Tightening torque Nm 3,5
in-Ibs. 31
Screwdriver POZI 2
Mounting any
Mounting position any
Supply any
Dimensions Pole dimensions (H x L x W) mm 95 x 26.5 x 82.5
and weight Pole weight g 240
Combination Auxiliary contact yes
with aux. Combined auxiliary- / signal contact yes
elements
Shunt trip yes
Undervoltage release yes
Shunt open release yes
Motor Operating Device yes
1/189
1
—
High performance MCBs
S802PV-M-H and S804PV-SD technical features
S802PV-M-H S800PV-SD
General Data
Tripping characteristics none none
Standards IEC / EN 60947-3 IEC / EN 60947-3 and Annex D
Poles 2 (polarized) 2 ... 4
Rated current Ie A 32, 63, 100 32, 63, 125
Rated insulation voltage Ui acc. to IEC/EN 60664-1 V DC 1500 DC 1500
Rated impulse withstand voltage Uimp. (1.2/50 µs) kV 8 8
Overvoltage category III III
Pollution degree 2 2
Suitability for isolation yes yes
Data acc. to IEC/EN 60947-3
Rated operational voltage Ue V DC 1000 V: 2-pole DC 800V: 2-pole
DC 1200V: 3-Pole
DC 1500 V: 4-pole
Min. operating voltage V - -
Rated short-term withstand current Icw kA 1.5 1.5
Rated short-circuit making capacity Icm kA 0.5 0.5
Utilisation category DC-21 A DC-21 A, DC-PV2
Electrical and Mechanical Endurance ops. 1500 electric; 8500 mechanic 32, 63A: 1500 electric; 8500 mechanic
125 A: 1000 electrical, 7000 mechanic
acc. to IEC 60947-3
Mechanical Data
Housing Material group I, RAL 7035 Material group I, RAL 7035
Toggle black, lockable black, lockable
Classification acc. To NF F 126-101, NF F 16-102 - -
Protection degree acc. to EN 60529 IP20; IP40 (actuating end only) IP20; IP40 (actuating end only)
Shock resistance acc. to IEC/EN 60068-2-30 IEC 61373 Cat. 1 Class B, 5 g / IEC 61373 Cat. 1 Class B, 5 g /
30 ms acc. To IEC 60068-27 Test Ea 30 ms acc. To IEC 60068-27 Test Ea
Vibration resistance acc. to IEC/EN 60068-2-6 IEC 60068-2-6 Test Fc; IEC 60068-2-6 Test Fc;
2 - 13.2 Hz/1 mm 2 - 13.2 Hz/1 mm
13.2 - 100 Hz/0.7 g 13.2 - 100 Hz/0.7 g
with load 100 % x Ie with load 100 % x Ie
Environmental conditions (damp heat) °C/RH 12 + 12 cycle with 55 °C/90 - 96 % and 12 + 12 cycle with 55 °C/90 - 96 % and
acc. to IEC/EN 60068-2-30 25 °C/95 - 100 % 25 °C/95 - 100 %
Environmental conditions (dry heat) °C/RH 16 hours 55 °C/2 hours 70 °C with damp 16 hours 55 °C/2 hours 70 °C with
acc. to IEC/EN 60068-2-2 Test B heat 55 % damp heat 55 %
Ambient temperature °C -25 … +60 -25 … +60
Storage temperature °C -40 … +70 -40 … +70
Installation
Terminal Failsafe cage or ringlug terminal Failsafe cage or ringlug terminal
Connections (top/bottom) - Cu only mm2 1 … 50 stranded 1 … 50 stranded
1 … 70 flexible 1 … 70 flexible
Tightening torque Nm 3.5 3.5
in-Ibs. 31 31
Screwdriver POZI 2 POZI 2
Mounting any any
Mounting position any any
Supply any any
(taking into account the polarization) (taking into account the polarization)
Dimensions and weight
Pole dimensions (H x L x W) mm 95 x 26.5 x 82.5 95 x 26.5 x 82.5
Pole weight g 240 240
1/190 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
High performance MCBs
S800PV series with cage terminal, B characteristic
S800PV-SP
Function: protection and control of photovoltaic strings against overloads, short-circuits
and reverse currents. Ideal replacement for fuses due to comfortable string failure
2CCC413002F0021
1
S800PV-SP
Function: protection and control of photovoltaic strings against overloads, short-circuits
and reverse currents. Ideal replacement for fuses due to comfortable string failure
2CCC413003F0021
S802PV-M-H
Photovoltaic 2-pole disconnector (polarized)
2CCC413379F0001
S800PV-SD
Function: switch disconnector for DC side isolation of PV systems.
Designed for PV installations of 1500 V DC.
Applications: Photovoltaic systems.
Rated short-term withstand currend, Icw 1,5 kA
—
MCBs
S500 series technical features
S500-K
General Data Tripping characteristics K
Standards IEC 60947-2 , UL1077, CAN / CSA-C22.2 No. 35
2CSC400001F0013
Poles 1…3
Rated current Ie adjustable A 0.1 … 45
Rated frequency f Hz 50/60
Rated insulation voltage Ui acc. to IEC/EN V AC 690 V
S500 60664-1
Rated impulse withstand voltage Uimp. (1.2/50 μs) kV 6
Overvoltage category II
Pollution degree 3
Suitability for isolation yes
Data acc. Rated operational voltage Ue V –
to IEC/EN 60898-1 Min. operating voltage V –
Rated short-circuit capacity Icn kA –
Reference temperature for tripping °C –
characteristics
Electrical and Mechanical Endurance ops. –
Service short-circuit capacity Ics kA –
Data acc. Rated operational voltage Ue V 400/690 V AC
to IEC/EN 60947-2 Min. operating voltage V 12 V AC
Rated ultimate short-circuit capacity Icu
AC 230/400V kA 0.1– 11 A: 50 kA; 10–45 A: 30 kA
AC 250/440V 0.1–11 A: 30 kA; 10–45 A: 25 kA
AC 3 x 500V 0.1–11 A: 20 kA; 10–45 A: 15 kA
AC 400/690V 0.1–45 A: 6 kA
Rated service short-circuit capacity Ics
AC 230/400V kA 0.1–11 A: 30 kA; 10–45 A: 25 kA
AC 250/440V 0.1–45 A: 22 kA
AC 3 x 500V 0.1–11 A: 15 kA; 10–45 A: 11 kA
AC 400/690V 0.1–45 A: 3 kA
Reference temperature for tripping °C 40
characteristics
Electrical and Mechanical Endurance ops. 0.1 … 45 A: 1500 electric; 8500 mechanic
Data acc. Rated voltage V AC 600
to UL/CSA , Rated interrupting capacity acc. to UL 1077 kA
Supplementary
Protector AC 240/415V kA <25A: 30kA; >25: 18kA
AC 277/480V 14
AC 346/600 6
Reference temperature for tripping °C 25
characteristics
Electrical and Mechanical endurance ops. acc. to UL1077. 6000 electric; 8500
mechanic
1/193
1
S500-K
Mechanical Data Housing Material group I, RAL 7035
Toggle black, lockable
Classification acc. to NF F 16-101, NF F 16-102 I2, F1
Protection degree acc. to EN 60529 IP20; IP40 (actuating end only)
Vibration resistance acc. to IEC/EN 60068-2-30 IEC 61373 Cat. 1 Class B, 5 g/30 ms acc. to IEC
60068-27 Test Ea
Vibration resistance acc. to IEC/EN 60068-2-6 IEC 60068-2-6 Test Fc; 2–13.2 Hz/1 mm
13.2–100 Hz/0.7 g with load 100 % x Ie
Environmental conditions (damp heat) acc. to 12 + 12 cycle with 55 °C/90–96 % r.g. and 25
IEC/EN 60068-2-30 test Db %/95 –100 % r.f.
Environmental conditions (damp heat) acc. to 16 hours 55 °C/2 hours 70 °C with damp heat
IEC/EN 60068-2-2 Test B 55 %
Ambient temperature °C –25 … +55
Storage temperature °C –40 … +70
Terminal Cage terminal
Connections (top/bottom) – CU only mm 2 1 … 25
Installation Tightening torque Nm 2.5
Screwdriver POZI 2
Mounting EN 60715
Mounting position any
Supply any
Dimensions and Pole dimensions (H x L x W) mm 91 x 92 x 25
weight Pole weight g ca. 250
Combination with Auxiliary contact Yes
aux. elements Signal contact Yes
Shunt trip Yes
Undervoltage release Yes
Shunt open release Yes
Motor Operating Device Yes
1/194 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S500 series technical features
S500UC-K
General Data Tripping characteristics K
Standards IEC 60947-2
2CSC400001F0013
Poles 1…4
Rated current Ie A 0.1 … 45
Rated frequency f Hz –
Rated insulation voltage Ui acc. to IEC/EN V 1000V DC
S500 60664-1
Rated impulse withstand voltage Uimp. kV 6
(1.2/50μs)
Overvoltage category II
Pollution degree 2
Suitability for isolation yes
Data acc. Rated operational voltage Ue V –
to IEC/EN 60898-1 Min. operating voltage V –
Rated short-circuit capacity Icn kA –
Reference temperature for tripping °C –
characteristics
Electrical and Mechanical Endurance ops. –
Service short-circuit capacity Ics kA –
Data acc. Rated operational voltage Ue V DC 250 V/pol, max. DC 750 V
to IEC/EN 60947-2 Min. operating voltage V –
Rated ultimate short-circuit capacity Icu
DC 250 V L/R 15 ms (1-pole) kA 30 kA
DC 500 V L/R 15 ms (2-pole in series) 30 kA
DC 750 V L/R 15 ms (3- and 4-pole in series) 30 kA
Rated service short-circuit capacity Ics
DC 250 V L/R 15 ms (1-pole) kA 30 kA
DC 500 V L/R 15 ms (2-pole) 30 kA
DC 750 V L/R 15 ms (3- and 4-pole) 30 kA
Reference temperature for tripping °C 40
characteristics
Electrical and Mechanical Endurance ops. 0.1 … 45 A: 1500 electric; 8500 mechanic
Data acc. to UL/ Rated voltage V DC 250 V/pol, max. 600 V
CSA Rated interrupting capacity acc. to UL 1077 kA
DC 250V (1-pole) kA 30 kA
DC 500V (2-pole in series) 30 kA
DC 750V (3- and 4-pole in series) 30 kA
Reference temperature for tripping °C 25
characteristics
Electrical and Mechanical endurance ops. acc. to UL1077. 6000 electric, 4000
mechanic
1/195
1
S500UC-K
Mechanical Data Housing Material group I, RAL 7035
Toggle black, lockable
Classification acc. to NF F 16-101, NF F 16-102 I2, F1
Protection degree acc. to EN 60529 IP20; IP40 (actuating end only)
Vibration resistance acc. to IEC/EN 60068-2-6 IEC 61373 Cat. 1 Class B, 5 g/30 ms acc. to
IEC 60068-27 Test Ea
Vibration resistance acc. to IEC/EN 60068-2-6 IEC 60068-2-6 Test Fc; 2–13.2 Hz/1 mm
13.2–100 Hz/0.7 g with load 100 % x Ie
Environmental conditions (damp heat) acc. to 12 + 12 cycle with 55 °C/90 –96 % r.g. and 25
IEC/EN 60068-2-30 test Db %/95 –100 % r.f.
Environmental conditions (damp heat) acc. to 16 hours 55 °C/2 hours 70 °C with damp
IEC/EN 60068-2-2 Test B heat 55 %
Ambient temperature °C –25 … +55
Storage temperature °C –40 … +70
Terminal Cage terminal
Connections (top/bottom) – CU only mm 2 1 … 25
Installation Tightening torque Nm 2.5
Screwdriver POZI 2
Mounting EN 60715
Mounting position any
Supply any
Dimensions and Pole dimensions (H x L x W) mm 91 x 92 x 25
weight Pole weight g ca. 250
Combination with Auxiliary contact Yes
aux. elements Signal contact Yes
Shunt trip Yes
Undervoltage release Yes
Shunt open release Yes
Motor Operating Device Yes
1/196 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S500 series technical features
S500HV-K
General Data Tripping characteristics K
Standards IEC 60947-2
2CSC400001F0013
Poles 1…3
Rated current Ie A 1 … 45
Rated frequency f Hz 50/60
Rated insulation voltage Ui acc. to IEC/EN V AC 1000 V
S500 60664-1
Rated impulse withstand voltage Uimp. (1.2/50 kV 6
μs)
Overvoltage category II
Pollution degree 2
Suitability for isolation yes
Data acc. Rated operational voltage Ue V –
to IEC/EN 60898-1 Min. operating voltage V –
Rated short-circuit capacity Icn kA –
Reference temperature for tripping °C –
characteristics
Electrical and Mechanical Endurance ops. –
Service short-circuit capacity Ics kA –
Data acc. Rated operational voltage Ue V AC 580/1000 V
to IEC/EN 60947-2 Min. operating voltage V 12 V AC
Rated ultimate short-circuit capacity Icu
AC 580/1000V kA 1.5
Rated service short-circuit capacity Ics
AC 580/1000V kA 1.5
Reference temperature for tripping °C 40
characteristics
Electrical and Mechanical Endurance ops. –
Data acc. to UL/ Rated voltage V –
CSA Rated interrupting capacity acc. to UL 1077 kA –
AC 240/415V kA –
AC 277/480V –
AC 346/600 –
Reference temperature for tripping –
characteristics
Electrical and Mechanical endurance ops. –
Mechanical Data Housing Material group I, RAL 7035
Toggle black, lockable
Classification acc. to NF F 16-101, NF F 16-102 I2, F1
Protection degree acc. to EN 60529 IP20; IP40 (actuating end only)
Vibration resistance acc. to IEC/EN 60068-2-6 w
Environmental conditions (damp heat) acc. to 12 + 12 cycle with 55 °C/90 –96 % r.g. and
IEC/EN 60068-2-30 test Db 25 %/95 –100 % r.f.
Environmental conditions (dry heat) acc. to 16 hours 55 °C/2 hours 70 °C with damp
IEC/EN 60068-2-2 Test B heat 55 %
Ambient temperature °C –25 … +55
Storage temperature °C –40 … +70
Terminal Cage terminal
Connections (top/bottom) – CU only mm2 1 … 25
1/197
1
S500HV-K
Installation Tightening torque Nm 2.5
Screwdriver POZI 2
Mounting EN 60715
Mounting position any
Supply any
Dimensions and Pole dimensions (H x L x W) mm 91 x 92 x 25
weight Pole weight g ca. 250
Combination with Auxiliary contact Yes
aux. elements Signal contact Yes
Shunt trip Yes
Undervoltage release Yes
Shunt open release Yes
Motor Operating Device Yes
1/198 E L E C T R I C A L I N S TA L L AT I O N S O L U T I O N S F O R B U I L D I N G S 2CHC 000 002 C0201
1
—
MCBs
S500 series with with adjustable thermal release for motor protection,
K characteristic
very useful when it is needed selectivity vs an MCCB or back-up vs other MCBs wired
downstream; version with adjustable thermal release, dedicated to protect motors.
Advantages: No nuisance tripping in the case of functional peak currents up to 8xIn,
depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type
S501
characteristic offers protection to damageable elements in the overcurrent range; it also
provides the best protection to cables and lines.
Applications: commercial and industrial.
Standard: IEC/EN 60947-2, UL 1077
Icu up to 50 kA
1/199
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612270 1 piece 1 piece unit
—
MCBs
S500UC series DC range, K characteristic
very useful when it is needed selectivity vs an MCCB or back-up vs other MCBs wired
downstream; version with adjustable thermal release, dedicated to protect motors; version
dedicated to application in direct current circuits.
Advantages: No nuisance tripping in the case of functional peak currents up to 8xIn,
S501UC
depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type
characteristic offers protection to damageable elements in the overcurrent range; it also
provides the best protection to cables and lines.
Applications: commercial and industrial.
Standard: IEC/EN 60947-2, UL1077 (supplementary protector)
Icu up to 30 kA
1/201
1
Number Rated Bbn Order details Price Weight Pack
of poles current 7612270 1 piece 1 piece unit
—
MCBs
S500UC series DC range, K characteristic
1
—
MCBs
S500HV series for applications up to 1000 VAC, K characteristic
Icu = 1.5 kA
Number Rated Bbn Order details Price Weight Pack
of poles current 761227 1 piece 1 piece unit
2CSC400004F0013