Chilled Water Ceiling Concled Fcu

Download as pdf or txt
Download as pdf or txt
You are on page 1of 29

Engineered for flexibility and performance.

TM

HORIZONTAL TYPE CHILLED


WATER FAN COIL UNIT
FWW-V series FWW-AA series
FWW-T series FUW-A series
CONTENTS

FWW-V Horizontal Ceiling Concealed Fan Coil Unit �������� 04 FUW-A Utra-thin cealing unit for High ESP application ���� 21

FWW-T Ceiling Concealed Fan Coil Unit ������������������������� 11 Wiring ������������������������������������������������������������������������������� 26

FWW-AA Ceiling Exposed Fan Coil Unit �������������������������� 17

Introduction
For years, DAIKIN has been providing the society with multiple types of high quality air handling systems and has made
remarkable achievements in related fields. Integrating the advanced air conditioner manufacturing technology and process of
DAIKIN, DAIKIN fan coil units showcase more compact structure, more convenient installation and maintenance, more efficient
performance and lower noises, and have been widely used in public buildings, hospitals, office buildings, hotels, high-end
residences, etc.

Galaxy SOHO (Beijing) Palm Jumeirah (Dubai, UAE) White Swan Hotel (Guangzhou)

In this community, DAIKIN is renowned for its complete product series, covering the full range of air-conditioning, purifying and
refrigeration equipment. More importantly, DAIKIN boasts the most complete fan coil series and realizes product experience
covering units, valves and controls. It is easier to use for customers.

4 rows District 3+1


Installation type Outlook Series 3 Rows 4 Rows 6 Rows Application type
cooling Rows
FWW-VC √
FWW-VF √ Compact size, wide
FWW-VA √ application
Cealing
FWW-VH √
concealed unit
FWW-TC √ High air flow can be
FWW-TF √ applied for narrow
FWW-TA √ installation.

Ceiling
FWW-AA √ Exposed type
exposed unit

High ESP Large air flow and


FUW-A √ √
Ceiling unit high ESP

* We are always improving our products to make them better. Therefore all specifications and details are subject to change without prior notice. Please contact with
the sales to check if this is the latest catalogue.

2 DAIKIN
Features
X Centrifugual impeller X High-efficiency motor X Plastic-coated metal hose X Smart control (option)
The double inlet double High efficiency and energy The cable protection pipe for Several types of thermostats
width(DWDI) centrifugal saving, powerful, stable and the motor uses plastic-coated options are offered to comply
fan featuring high-efficiency quite operation; configuration metal hose; the plastic-coated with 2-pipe and 4-pipe
wide-impeller and multi-blade of the international brand metal hose is light in weight and system, they are wildly used
forward-curved is adopted to NSK bearing, ensuring well flexible, with outstanding for industrial, commerial and
implement low speed, large efficient, safe and barrier property; The hose is residential buildings, please
air flow and low noise. maintenance-free operation. resistant to corrosion, wear and refer to thermostat's catalog
high temperature; it has good for detailed information.
insulation property and can
better protect safety in use.

X High-efficiency heat X New self-slope drain pan X Manual air vent valve X 2-way/3-way valves (option)
exchanger The self-slope structure The unit is configured FCV series 2-way/3-way valve
Formed using high quality design ensures quick with manual air vent valve including electric actuator can
copper tubes and highly drainage of condensate for convenient operation, be provided as an option. The
efficient hydrophilic water; with spray on both quicker discharge, and actuator takes small space
aluminum fins through sides for anti-corrosion, the easier installation. The valve which can be installed closed
mechanical expansion joint tray surface is cleaner; the is placed at the highest to the wall. It is reliable with
to reduce heat resistance; integrated design is adopted point to guarantee thorough high quality and super low
Quasi counterflow fan coil to avoid cold bridges. discharging of air in the noise.
design enables thorough system and ensure the heat
heat exchange between air exchange effect.
and water to guarantee high
efficiency in heat exchange.

3 DAIKIN
FWW-V Horizontal Ceiling Concealed Fan Coil Unit

Our FWW-V series fan coil adopts efficient heat exchange design and standardized production process. With the advanced
motor control technology, the precise operation of the fan coil unit is guaranteed. All components of the unit are subject to
selection of quality material and strict inspection to provide intelligent control products and centralized control solutions. The unit
widely applies to all kinds of public, commercial and civil buildings.

X Ingenious and thin body X Quiet operation, comfort and enjoyment


The unit, light, shapely, thin and compact, can be even The unit is equipped with a low-noise, wide-impeller, and
mounted in a narrow ceiling, occupying less mounting space. low-speed fan. Moreover, each fan is checked and inspected
With a hidden design, the unit can match with a variety of before delivery. The interior of the fan is adhered with
decoration modes and perfectly fix to different architecture efficient damping and heat insulating material to ensure quiet
styles. and efficient operation of the unit.

Copper
pipe

Secondary
Fins
flanging
Cross flow

X Efficient heat exchange and excellent performance X Abundant configuration, safety and reliability
By covering quality copper pipes with hyperbolic louver type The unit may be equipped with a lift pump, a PTC electric
hydrophilic aluminum fins and combining a quasi-counter flow heater, an air purification component, or other devices to
design, the unit has great performance in heat exchange. meet a variety of function requirements, and be assisted by
The wide-impeller design lowers the noise of the unit. an intelligent control mode, thus being flexible and safe.

CERTIFICATE
N° 17.09.002
Certificate of Product Ratings Fan Coil Units / Ventilo-convecteurs
AHRICertifiedReferenceNumber:10296193 Date: 5/15/2017 †Status: Active
Product: Room Fan-Coil
Model Designation: MCW1400VC5-PSC Granted on September 14, 2017 - Date 1ère admission 14 septembre 2017
Manufacturer: SHENZHEN MCQUAY AIR CONDITIONING CO., LTD.
Trade/Brandname:MCQUAYCHINA This document is valid at the date of issue - Check the current validity on:
Series Name: MCW-VC Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com
Rated as follows in accordance with AHRI Standard 440-2008 for Room Fan-Coils and subject to verification of
ratingaccuracybyAHRI-sponsored,independent,thirdpartytesting: Participant/Titulaire
SHENZHEN MCQUAY AIR CONDITIONING CO. LTD
no. 10, Fangkeng Road - Longgang District
Air Flow Rating (SCFM): 1300 518111 SHENZHEN, China
Total Capacity (Btuh): 38600
Sensible Capacity (Btuh): 29200
This product performance certificate is issued by Eurovent Ce certificat de performance produit est délivré par Eurovent Certita
Temperature Rise (°F): 10 Certita Certification according to the certification rules: Certification dans les conditions fixées par le référentiel :
Motor Type: PSC
ECP FCU - « Fan Coil Units » in force at established date. ECP FCU – « Ventilo-convecteurs » en vigueur à date d’édition.
Power Input (Watts): 312
Pursuant to the decision notified by Eurovent Certita En vertu de la décision notifiée par Eurovent Certita Certification, le
Certification, the right to use the mark ECP shall be granted to droit d'usage de la marque ECP, est accordé à la société qui en est
the beneficiary company for all products inside the defined bénéficiaire pour les tous les produits entrant dans le champ
scope according to “certify-all” principle and in the conditions d'application défini selon le principe “certify-all” et dans les conditions
defined by the certification program mentioned. définies par le programme de certification mentionné.

Unless withdrawn or suspended, this certificate remains valid Sauf retrait ou suspension, ce certificat demeure valide tant que les
as long as the requirements for the certification program conditions du référentiel du programme de certification sont
framework are met. The validity of the certificate is to be respectées. La validité du certificat est à vérifier sur le site Internet
verified on www.eurovent-certification.com www.eurovent-certification.com

THIS CERTIFICATE HAS BEEN ISSUED ON 07/02/2023 CE CERTIFICAT A ÉTÉ EMIS LE 07/02/2023
THIS CERTIFICATE IS VALID UNTIL 15/02/2024 CE CERTIFICAT EST VALIDE JUSQU’AU 15/02/2024

Paris, 7 février 2023


Organisme accrédité n° 5-0517 Certification Produits et
Services selon la norme NF EN ISO/CEI 17065:2012
Portée disponible sur www.cofrac.fr MANAGING BOARD MEMBER / MEMBRE DIRECTOIRE
Accreditation #5-0517 Products and Services Certification
according to NF EN ISO/CEI 17065:2012 –
Scope available on www.cofrac.fr

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing, COFRAC est signataire des accords MLA d’EA et MLA d’IAF,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure. COFRAC is signatory of EA MLA and IAF MLA,
list of EA members is available on
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate. www.european-accreditation.org/ea-members
list of IAF members is available on
www.iaf.nu//articles/IAF_MEMBERS_SIGNATORIES/4
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;

Side withdraw Bottom withdraw


entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right. 1/2
131393783696892279
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06D06 TEMPLATE_ECP_Certify_All_Rev1.1

X Easy maintenance X Authoritative certificate


With unique design, the filter can be withdraw from either For the whole series, we comply with AHRI 400 Standard.
bottom or side. Users can clean or replace the filter much For district cooling unit. Eurovent certificate is granted.
easier.

4 DAIKIN
FWW-V Horizontal Ceiling Concealed Fan Coil Unit

Nomenclature
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
F WW 1 0 0 0 V A N R E F - A 0 A E

Sales region: E: for export

Power supply:
A- 220-240V/1 Ph/50Hz
K- 208-230V/1 Ph/60Hz

E-heater power: 0-None 1-1kW 2-2kW ……

Drain pan:
A-Standard drain pan
E-SUS drain pan
C-Extended drain pan
G-Extended SUS drian pan

Motor type: "-"-AC motor

Filter:
F-8mm nylon filer
H-25mm AL filter
G-25mm G4 filter

Return air plenum:


C-None
E-Back type (5mmXPE)
F-Back type (15mmPF)

Pipe orientation: (Facing to the air flow)


L-Left
R-Right

Rated ESP code: 50Pa

Coil type:
C-3rows
F-4rows
H-3rows+1row
A-4rows (District cooling)

Series: V-V series

Unit model: 200 300 400……1400 CFM

Horizontal type cealing concealed FCU

5 DAIKIN
FWW-V Horizontal Ceiling Concealed Fan Coil Unit

Standard Unit / 2-Pipe / 3 Rows


Model FWW200VC FWW300VC FWW400VC FWW500VC FWW600VC FWW700VC FWW800VC FWW1000VC FWW1200VC FWW1400VC
m3/h 340 510 640 850 960 1170 1360 1680 1900 2180
High
CFM 200 300 376 500 565 688 800 988 1118 1282
m3/h 320 470 600 800 920 1100 1300 1620 1870 2030
Air Flow Medium
CFM 188 276 353 471 541 647 765 953 1100 1194
m3/h 280 380 450 600 730 730 950 1100 1360 1400
Low
CFM 165 224 265 353 429 429 559 647 800 824
Pa 50
ESP Medium
in.wg. 0.2
W 2000 3100 3800 4900 5600 6500 8000 9000 10300 11500
Total Cooling Capacity
Btu/h 6824 10577 12966 16719 19107 22178 27296 30708 35144 39238
m3/h 0.34 0.53 0.65 0.84 0.96 1.11 1.37 1.54 1.77 1.97
Water Flow Rate
USGPM 1.50 2.33 2.86 3.70 4.22 4.88 6.03 6.78 7.79 8.67
kPa 16 18 18 26 22 33 35 38 27 39
Water Pressure drop
in.wg. 64 72 72 104 88 133 141 153 108 157
High W 49 68 81 103 122 163 172 238 280 315
Rated
Power Medium W 46 65 77 98 115 156 165 225 265 295
Input
Low W 42 57 71 92 107 130 150 202 243 260
High A 0.22 0.3 0.36 0.45 0.54 0.72 0.76 1.05 1.23 1.38
Rated
Running Medium A 0.2 0.29 0.34 0.43 0.51 0.69 0.73 1 1.18 1.31
Current
Low A 0.19 0.26 0.32 0.42 0.49 0.59 0.69 0.92 1.11 1.19
High dB(A) 39 39 41 43 44 47 44 47 49 49.5
Sound
Pressure Medium dB(A) 38 38 40 42 43 46 43 46 48 48.5
Level
Low dB(A) 34.5 32 35 35.5 39 37 37 37.5 41 41
Type 8mm Nylon Filter
Filter
Access Both Side & Bottom Withdraw
Row No. 3
Working
2.0 MPa
Pressure
Coil
Material Copper tube & Hydrophilic Aluminum
Water
L 0.48 0.68 0.74 0.83 0.93 0.99 1.35 1.4 1.62 1.79
Volume
Type Galvanized Steel Centrifugal Fan (Forward)
Fan
Quantity 1 2 2 2 2 2 3 3 4 4
Type 3 Speed PSC Motor

Motor Quantity 1 1 1 1 1 1 2 2 2 2
IP/
IP20 / ≥B
Insulation

NOTES:
1) All performance is tested under 230V~/50Hz and unit couple with return air plenum and 8mm nylon filter.
2) The air flow, power input, sound data is tested on standard air condition without water in coil.
3) The capacity is tested under M speed, 50Pa and below condition:
---Cooling capacity: Entering air DB/WB: 27°C/19.5°C, water inlet 7°C, water outlet 12°C
4) The sound pressure is measured according to GB/T 19232-2019 (1m below the unit bottom).

6 DAIKIN
FWW-V Horizontal Ceiling Concealed Fan Coil Unit

Standard Unit / 2-Pipe / 4 Rows


Model FWW200VF FWW300VF FWW400VF FWW500VF FWW600VF FWW700VF FWW800VF FWW1000VF FWW1200VF FWW1400VF
m3/h 340 510 640 850 960 1170 1360 1680 1900 2180
High
CFM 200 300 376 500 565 688 800 988 1118 1282
m3/h 320 470 600 800 920 1100 1300 1620 1870 2030
Air Flow Medium
CFM 188 276 353 471 541 647 765 953 1100 1194
m3/h 280 380 450 600 730 730 950 1100 1360 1400
Low
CFM 165 224 265 353 429 429 559 647 800 824
Pa 50
ESP Medium
in.wg. 0.2
W 2500 3600 4300 5100 6200 7100 8900 10500 11100 12200
Total Cooling Capacity
Btu/h 8530 12283 14672 17401 21154 24225 30367 35826 37873 41626
m3/h 0.43 0.62 0.74 0.87 1.06 1.22 1.53 1.8 1.9 2.09
Water Flow Rate
USGPM 1.89 2.73 3.26 3.83 4.66 5.37 6.73 7.92 8.36 9.20
kPa 30 34 29 24 38 36 32 39 38 38
Water Pressure drop
in.wg. 120 137 116 96 153 145 129 157 153 153
High W 49 68 81 103 122 163 172 238 280 315
Rated
Power Medium W 46 65 77 98 115 156 165 225 265 295
Input
Low W 42 57 71 92 107 130 150 202 243 260
High A 0.22 0.3 0.36 0.45 0.54 0.72 0.76 1.05 1.23 1.38
Rated
Running Medium A 0.2 0.29 0.34 0.43 0.51 0.69 0.73 1 1.18 1.31
Current
Low A 0.19 0.26 0.32 0.42 0.49 0.59 0.69 0.92 1.11 1.19
High dB(A) 39 39 41 43 44 47 44 47 49 49.5
Sound
Pressure Medium dB(A) 38 38 40 42 43 46 43 46 48 48.5
Level
Low dB(A) 34.5 32 35 35.5 39 37 37 37.5 41 41
Type 8mm Nylon Filter
Filter
Access Both Side & Bottom Withdraw
Row No. 4
Working
2.0 MPa
Pressure
Coil
Material Copper tube & Hydrophilic Aluminum
Water
L 0.64 0.91 0.98 1.1 1.25 1.32 1.8 1.87 2.16 2.38
Volume
Type Galvanized Steel Centrifugal Fan (Forward)
Fan
Quantity 1 2 2 2 2 2 3 3 4 4
Type 3 Speed PSC Motor

Motor Quantity 1 1 1 1 1 1 2 2 2 2
IP/
IP20 / ≥B
Insulation

NOTES:
1) All performance is tested under 230V~/50Hz and unit couple with return air plenum and 8mm nylon filter.
2) The air flow, power input, sound data is tested on standard air condition without water in coil.
3) The capacity is tested under M speed, 50Pa and below condition:
---Cooling capacity: Entering air DB/WB: 27°C/19.5°C, water inlet 7°C, water outlet 12°C
4) The sound pressure is measured according to GB/T 19232-2019 (1m below the unit bottom).

7 DAIKIN
FWW-V Horizontal Ceiling Concealed Fan Coil Unit

Standard Unit / 4-Pipe / 3+1 Rows


Model FWW200VH FWW300VH FWW400VH FWW500VH FWW600VH FWW700VH FWW800VH FWW1000VH FWW1200VH FWW1400VH
m3/h 340 510 640 850 960 1170 1360 1680 1900 2180
High
CFM 200 300 376 500 565 688 800 988 1118 1282
m3/h 320 470 600 800 920 1100 1300 1620 1870 2030
Air Flow Medium
CFM 188 276 353 471 541 647 765 953 1100 1194
m3/h 280 380 450 600 730 730 950 1100 1360 1400
Low
CFM 165 224 265 353 429 429 559 647 800 824
Pa 50
ESP Medium
in.wg. 0.2
Total Cooling W 1960 3140 3690 4910 5480 6400 7850 8930 9990 11030
Capacity Btu/h 6688 10714 12590 16753 18698 21837 26784 30469 34086 37634
Cooling Water Flow m3/h 0.34 0.54 0.63 0.84 0.94 1.1 1.35 1.53 1.71 1.89
Rate USGPM 1.50 2.38 2.77 3.70 4.14 4.84 5.94 6.73 7.52 8.32
Cooling Water kPa 18 25 18 31 25 33 32 40 28 35
Pressure drop in.wg. 72 100 72 124 100 133 129 161 112 141
Nominal Heating W 1910 2850 3420 4420 4390 5680 6900 7920 8880 9470
Capacity Btu/h 6517 9724 11669 15081 14979 19380 23543 27023 30299 32312
Heating Water Flow m3/h 0.16 0.24 0.29 0.38 0.38 0.49 0.59 0.68 0.76 0.81
Rate USGPM 0.70 1.06 1.28 1.67 1.67 2.16 2.60 2.99 3.34 3.56
Heating Water kPa 27 12 18 28 29 18 29 34 22 27
Pressure drop in.wg. 108 48 72 112 116 72 116 137 88 108

Rated High W 49 68 81 103 122 163 172 238 280 315


Power Medium W 46 65 77 98 115 156 165 225 265 295
Input Low W 42 57 71 92 107 130 150 202 243 260

Rated High A 0.22 0.3 0.36 0.45 0.54 0.72 0.76 1.05 1.23 1.38
Running Medium A 0.2 0.29 0.34 0.43 0.51 0.69 0.73 1 1.18 1.31
Current Low A 0.19 0.26 0.32 0.42 0.49 0.59 0.69 0.92 1.11 1.19

Sound High dB(A) 39 39 41 43 44 47 44 47 49 49.5


Pressure Medium dB(A) 38 38 40 42 43 46 43 46 48 48.5
Level Low dB(A) 34.5 32 35 35.5 39 37 37 37.5 41 41
Type 8mm Nylon Filter
Filter
Access Both Side & Bottom Withdraw
Row No.-
3
Cooling
Row No.-
1
Heating
Working
2.0 MPa
Pressure
Coil Material Copper tube & Hydrophilic Aluminum
Water
Volume- L 0.48 0.68 0.74 0.83 0.93 0.99 1.35 1.4 1.62 1.79
Cooling
Water
Volume- L 0.16 0.23 0.25 0.28 0.31 0.33 0.45 0.47 0.54 0.6
Heating
Type Galvanized Steel Centrifugal Fan (Forward)
Fan
Quantity 1 2 2 2 2 2 3 3 4 4
Type 3 Speed PSC Motor

Motor Quantity 1 1 1 1 1 1 2 2 2 2
IP/
IP20 / ≥B
Insulation

NOTES:
1) All performance is tested under 230V~/50Hz and unit couple with return air plenum and 8mm nylon filter.
2) The air flow, power input, sound data is tested on standard air condition without water in coil.
3) The capacity is tested under M speed, 50Pa and below condition:
---Cooling capacity: Entering air DB/WB: 27°C/19.5°C, water inlet 7°C, water outlet 12°C
---Heating capacity: Entering air DB: 21°C, water inlet 60°C, water outlet 50°C
4) The sound pressure is measured according to GB/T 19232-2019 (1m below the unit bottom).

8 DAIKIN
FWW-V Horizontal Ceiling Concealed Fan Coil Unit

District Cooling Unit / 2-Pipe / 4 Rows

Model FWW200VA FWW300VA FWW400VA FWW500VA FWW600VA FWW700VA FWW800VA FWW1000VA FWW1200VA FWW1400VA
m3/h 340 510 640 850 960 1170 1360 1680 1900 2180
High
CFM 200 300 376 500 565 688 800 988 1118 1282
3
m /h 320 470 600 800 920 1100 1300 1620 1870 2030
Air Flow Medium
CFM 188 276 353 471 541 647 765 953 1100 1194
m3/h 280 380 450 600 730 730 950 1100 1360 1400
Low
CFM 165 224 265 353 429 429 559 647 800 824
Pa 50
ESP Medium
in.wg. 0.2
W 1800 2600 3200 3900 4700 5400 6400 7700 8800 10200
Total Cooling Capacity
Btu/h 8871 10918 13307 16036 18425 21837 26272 30026 34802 34802
m3/h 0.17 0.25 0.3 0.37 0.45 0.51 0.61 0.73 0.84 0.97
Water Flow Rate
USGPM 1.10 1.32 1.63 1.98 2.24 2.68 3.21 3.70 4.27 4.27
kPa 19 14 22 16 24 30 18 26 25 35
Water Pressure drop
in.wg. 56 88 64 96 120 72 104 100 141 141
High W 49 68 81 103 122 163 172 238 280 315
Rated
Power Medium W 46 65 77 98 115 156 165 225 265 295
Input
Low W 42 57 71 92 107 130 150 202 243 260
High A 0.22 0.3 0.36 0.45 0.54 0.72 0.76 1.05 1.23 1.38
Rated
Running Medium A 0.2 0.29 0.34 0.43 0.51 0.69 0.73 1 1.18 1.31
Current
Low A 0.19 0.26 0.32 0.42 0.49 0.59 0.69 0.92 1.11 1.19
High dB(A) 51 51 54 58 58 59 57 60 63 64
Lw Outlet
Medium dB(A) 50 50 53 57 56 58 55 59 62 63
Duct
Low dB(A) 48 45 48 49 52 53 49 53 57 55
High dB(A) 56 56 59 61 63 65 62 66 67 69
Lw Inlet +
Medium dB(A) 55 55 58 60 62 64 61 65 66 68
Rad
Low dB(A) 52 49 53 53 57 59 54 58 60 60
High dB(A) 39 39 41 43 44 47 44 47 49 49.5
Sound
Pressure Medium dB(A) 38 38 40 42 43 46 43 46 48 48.5
Level
Low dB(A) 34.5 32 35 35.5 39 37 37 37.5 41 41
Type 8mm Nylon Filter
Filter
Access Both Side & Bottom Withdraw
Row No. 4
Working
2.0 MPa
Pressure
Coil
Material Copper tube & Hydrophilic Aluminum
Water
L 0.64 0.91 0.98 1.1 1.25 1.32 1.8 1.87 2.16 2.38
Volume
Type Galvanized Steel Centrifugal Fan (Forward)
Fan
Quantity 1 2 2 2 2 2 3 3 4 4
Type 3 Speed PSC Motor

Motor Quantity 1 1 1 1 1 1 2 2 2 2
IP/
IP20 / ≥B
Insulation

NOTES:
1) All performance is tested under 230V~/50Hz and unit couple with return air plenum and 8mm nylon filter.
2) The air flow, power input, sound data is tested on standard air condition without water in coil.
3) The capacity is tested under M speed, 50Pa and below condition:
---District Cooling capacity: Entering air DB/WB: 24°C/18°C, water inlet 5.5°C, water outlet 14.5°C
4) The sound pressure is measured according to GB/T 19232-2019 (1m below the unit bottom).
The sound power level is measured accroding to "Eurovent 8/12 Sound test methad for ducted fan coil unit ".

9 DAIKIN
FWW-V Horizontal Ceiling Concealed Fan Coil Unit

Dimensions
E

10

MOUNTING HOLE
176

536
6-16X10
HOT WATER OUTLET 127 CHILLED WATER
Rc 1/2" 83 OUTLET Rc 3/4"

17
18

53
187

62
CONDENSATE DRAIN R3/4

106
86

200
44

HOT WATERINLET
B
Rc 1/2"
D C 265 CHILLED WATER INLET
Rc 3/4"
A
4-Pipe Unit

536
104
20

17
14
WATER OUTLET 18
Rc 3/4"

53
AIR FLOW

150

106

200
235
133
265
WATER INLET
Rc 3/4" 2-Pipe Unit

Unit: mm
A Package Net Weight (kg) Gross Weight (kg)
Model Standard Extend B C D E F Dimension 4 rows / 4 rows /
(L*D*H) mm 3 rows 3 rows
drain pan drain pan 3+1 rows 3+1 rows
FWW200V 625 825 401 437 37 501 423 641*250*558 13.3 13.8 15.2 15.9
FWW300V 815 1015 591 627 37 691 613 831*250*558 16.6 17.4 18.9 19.7
FWW400V 865 1065 641 677 37 741 663 881*250*558 18.2 19 20.6 21.4
FWW500V 945 1145 721 757 37 821 743 961*250*558 19.8 20.4 22.4 22.9
FWW600V 1045 1245 821 857 37 921 843 1061*250*558 21.3 21.9 24.1 24.6
FWW700V 1095 1295 871 907 37 971 893 1111*250*558 22 23.2 24.8 26
FWW800V 1425 1625 1201 1237 37 1301 1223 1441*250*558 31.8 33.4 35.3 36.9
FWW1000V 1475 1675 1251 1289 37 1351 1273 1491*250*558 34.2 35.9 37.8 39.5
FWW1200V 1675 1875 1451 1487 37 1551 1473 1691*250*558 38.4 40.3 42.5 44.4
FWW1400V 1825 2025 1601 1637 37 1701 1623 1841*250*558 41.5 43.6 45.8 47.9

Exploded-View & Part List


Items Description
9 10
1 Drain pan

8 2 Deflector

7 12 3 Coil
4 Top panel
6
5 Fan deck
5 11
6 Fan
4 15 7 Motor

13 8 Air plenum left plate


3 9 Air plenum bottom plate

2 14 10 Air plenum top plate


11 Air plenum right plate
1 12 Filter
13 Wiring box
14 Bottom filter cover
15 Side filter cover

10 DAIKIN
FWW-T Ceiling Concealed Fan Coil Unit

FWW-T Large Air Flow Fan Coil Unit


Air duct up to 40 m in length

X Wide application X Quiet operation


By using the large air flow and high static pressure design, The unit is equipped with a low-noise, wide-impeller,
the unit can meet requirements for large air flow and high and low-speed fan. Moreover, each fan is checked and
static pressure, and flexibly meet application requirements inspected before delivery. The interior of the fan is adhered
on different occasions. with efficient damping and heat insulating material to ensure
quiet and efficient operation of the unit.
as low as 290mm

X Compact and space-saving structure X High efficiency and reliability


By using a compact structure design, the unit requires a small The coil fin, made of hydrophilic aluminum and made through
space for each unit, therefore saving the mounting space. precision machining, ensures good heat exchange. The
standard configuration includes a one-piece rubber insulating tilt
drain pan that is molded to avert condensation and leakage.

CERTIFICATE
N° 17.09.002
Certificate of Product Ratings Fan Coil Units / Ventilo-convecteurs
AHRICertifiedReferenceNumber:10296193 Date: 5/15/2017 †Status: Active
Product: Room Fan-Coil
Model Designation: MCW1400VC5-PSC Granted on September 14, 2017 - Date 1ère admission 14 septembre 2017
Manufacturer: SHENZHEN MCQUAY AIR CONDITIONING CO., LTD.
Trade/Brandname:MCQUAYCHINA This document is valid at the date of issue - Check the current validity on:
Series Name: MCW-VC Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-certification.com
Rated as follows in accordance with AHRI Standard 440-2008 for Room Fan-Coils and subject to verification of
ratingaccuracybyAHRI-sponsored,independent,thirdpartytesting: Participant/Titulaire
SHENZHEN MCQUAY AIR CONDITIONING CO. LTD
no. 10, Fangkeng Road - Longgang District
Air Flow Rating (SCFM): 1300 518111 SHENZHEN, China
Total Capacity (Btuh): 38600
Sensible Capacity (Btuh): 29200
This product performance certificate is issued by Eurovent Ce certificat de performance produit est délivré par Eurovent Certita
Temperature Rise (°F): 10 Certita Certification according to the certification rules: Certification dans les conditions fixées par le référentiel :
Motor Type: PSC
ECP FCU - « Fan Coil Units » in force at established date. ECP FCU – « Ventilo-convecteurs » en vigueur à date d’édition.
Power Input (Watts): 312
Pursuant to the decision notified by Eurovent Certita En vertu de la décision notifiée par Eurovent Certita Certification, le
Certification, the right to use the mark ECP shall be granted to droit d'usage de la marque ECP, est accordé à la société qui en est
the beneficiary company for all products inside the defined bénéficiaire pour les tous les produits entrant dans le champ
scope according to “certify-all” principle and in the conditions d'application défini selon le principe “certify-all” et dans les conditions
defined by the certification program mentioned. définies par le programme de certification mentionné.

Unless withdrawn or suspended, this certificate remains valid Sauf retrait ou suspension, ce certificat demeure valide tant que les
as long as the requirements for the certification program conditions du référentiel du programme de certification sont
framework are met. The validity of the certificate is to be respectées. La validité du certificat est à vérifier sur le site Internet
verified on www.eurovent-certification.com www.eurovent-certification.com

THIS CERTIFICATE HAS BEEN ISSUED ON 07/02/2023 CE CERTIFICAT A ÉTÉ EMIS LE 07/02/2023
THIS CERTIFICATE IS VALID UNTIL 15/02/2024 CE CERTIFICAT EST VALIDE JUSQU’AU 15/02/2024

Paris, 7 février 2023


Organisme accrédité n° 5-0517 Certification Produits et
Services selon la norme NF EN ISO/CEI 17065:2012
Portée disponible sur www.cofrac.fr MANAGING BOARD MEMBER / MEMBRE DIRECTOIRE
Accreditation #5-0517 Products and Services Certification
according to NF EN ISO/CEI 17065:2012 –
Scope available on www.cofrac.fr

† Models with an ‘Active’ status are those that are currently in production. Models with a ‘Discontinued’ status are those that the manufacturer has elected to stop producing, COFRAC est signataire des accords MLA d’EA et MLA d’IAF,
† yet stock is still available. Models with an ‘Obsolete’ status are those that the manufacturer is required to stop manufacturing due to an AHRI certification program test failure. COFRAC is signatory of EA MLA and IAF MLA,
list of EA members is available on
* Ratings followed by an asterisk (*) indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involuntary rerate. www.european-accreditation.org/ea-members
list of IAF members is available on
www.iaf.nu//articles/IAF_MEMBERS_SIGNATORIES/4
DISCLAIMER
AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for,
the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the
unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed in the
directory at www.ahridirectory.org.

Side withdraw Bottom withdraw


TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI. This Certificate shall only be used for individual, personal and
confidential reference purposes. The contents of this Certificate may not, in whole or in part, be reproduced; copied; disseminated;
entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user’s individual,
personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on “Verify Certificate” link
and enter the AHRI Certified Reference Number and the date on which the certificate was issued,
which is listed above, and the Certificate No., which is listed at bottom right. 1/2
131393783696892279
©2014 Air-Conditioning, Heating, and Refrigeration Institute CERTIFICATE NO.: EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637
S06D06 TEMPLATE_ECP_Certify_All_Rev1.1

X Easy maintenance X Authoritative certificate


With unique design, the filter can be withdraw from either For the whole series, we comply with AHRI 400 Standard.
bottom or side. Users can clean or replace the filter much For district cooling unit. Eurovent certificate is granted.
easier.
11 DAIKIN
FWW-T Ceiling Concealed Fan Coil Unit

Nomenclature
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
F WW 1 0 0 0 T A N R E F - A 0 A E

Sales region: E: forexport

Power supply:
A- 220V/1 Ph/50Hz
K- 208-230V/1 Ph/60Hz

E-heater power: 0-None 1-1kW 2-2kW ……

Drain pan:
A-Standard drain pan
E-SUS drain pan
C-Extended drain pan
G-Extended SUS drian pan

Motor type: "-"-AC motor

Filter:
F-8mm nylon filer
H-25mm AL filter
G-25mm G4 filter

Return air plenum:


C-None
E-Back type (5mmXPE)

Pipe orientation:(Facing to the air flow)


L-Left
R-Right

Rated ESP code: 50Pa

Coil type:
C-3rows
F-4rows
A-4rows(District cooling)

Series: T-T series

Unit model: 1000 1400 1600 1800 2000 CFM

Horizontal type cealing concealed FCU

12 DAIKIN
FWW-T Ceiling Concealed Fan Coil Unit

Standard Unit / 2-Pipe / 3 Rows

Model FWW1000TC FWW1400TC FWW1600TC FWW1800TC FWW2000TC


3
m /h 1670 2180 2700 3150 3600
High
CFM 982 1282 1588 1853 2118
3
m /h 1550 2000 2400 2970 3350
Air Flow Medium
CFM 912 1176 1412 1747 1971
m3/h 1200 1650 1960 2550 2500
Low
CFM 706 971 1153 1500 1471
Pa 50
ESP Medium
in.wg. 0.2
W 8800 11200 13230 14890 17700
Total Cooling Capacity
Btu/h 30026 38214 45141 50805 60392
m3/h 1.51 1.92 2.27 2.55 3.03
Water Flow Rate
USGPM 6.64 8.45 9.99 11.22 13.33
kPa 30 42 47 30 57
Water Pressure drop
in.wg. 120 169 189 120 229

Rated High W 250 410 531 612 769


Power Medium W 230 370 420 550 704
Input Low W 165 280 310 450 465

Rated High A 1.1 1.8 2.33 2.69 3.38


Running Medium A 1.02 1.64 1.86 2.44 3.12
Current Low A 0.76 1.28 1.42 2.06 2.13

Sound High dB(A) 48 50 53 55 55.5


Pressure Medium dB(A) 46 49 51 54 54
Level Low dB(A) 41 44 47 51 51
Type 8mm Nylon Filter
Filter
Access Both Side & Bottom Withdraw
Row No. 3
Working
2.0 MPa
Coil Pressure
Material Copper tube & Hydrophilic Aluminum
Water Volume L 1.29 1.51 1.66 1.89 2.29
Type Galvanized Steel Centrifugal Fan (Forward)
Fan
Quantity 2 2 2 2 2
Type 3 Speed PSC Motor
Motor Quantity 1 1 1 1 1
IP/Insulation IP20 / ≥B

NOTES:
1) All performance is tested under 230V~/50Hz and unit couple with return air plenum and 8mm nylon filter.
2) The air flow, power input, sound data is tested on standard air condition without water in coil.
3) The capacity is tested under M speed, 50Pa and below condition:
---Cooling capacity: Entering air DB/WB: 27°C/19.5°C, water inlet 7°C, water outlet 12°C
4) The sound pressure is measured according to GB/T 19232-2019 (1m below the unit bottom).

13 DAIKIN
FWW-T Ceiling Concealed Fan Coil Unit

Standard Unit / 2-Pipe / 4 Rows

Model FWW1000TF FWW1400TF FWW1600TF FWW1800TF FWW2000TF


3
m /h 1670 2180 2700 3150 3600
High
CFM 982 1282 1588 1853 2118
3
m /h 1550 2000 2400 2970 3350
Air Flow Medium
CFM 912 1176 1412 1747 1971
m3/h 1200 1650 1960 2550 2500
Low
CFM 706 971 1153 1500 1471
Pa 50
ESP Medium
in.wg. 0.2
W 10000 12900 14700 17500 20600
Total Cooling Capacity
Btu/h 34120 44015 50156 59710 70287
m3/h 1.71 2.21 2.52 3 3.53
Water Flow Rate
USGPM 7.52 9.72 11.09 13.20 15.53
kPa 37 40 45 55 63
Water Pressure drop
in.wg. 149 161 181 221 253

Rated High W 250 410 531 612 769


Power Medium W 230 370 420 550 704
Input Low W 165 280 310 450 465

Rated High A 1.1 1.8 2.33 2.69 3.38


Running Medium A 1.02 1.64 1.86 2.44 3.12
Current Low A 0.76 1.28 1.42 2.06 2.13

Sound High dB(A) 48 50 53 55 55.5


Pressure Medium dB(A) 46 49 51 54 54
Level Low dB(A) 41 44 47 51 51
Type 8mm Nylon Filter
Filter
Access Both Side & Bottom Withdraw
Row No. 4
Working
2.0 MPa
Coil Pressure
Material Copper tube & Hydrophilic Aluminum
Water Volume L 1.72 2.01 2.21 2.52 3.06
Type Galvanized Steel Centrifugal Fan (Forward)
Fan
Quantity 2 2 2 2 2
Type 3 Speed PSC Motor
Motor Quantity 1 1 1 1 1
IP/Insulation IP20 / ≥B

NOTES:
1) All performance is tested under 230V~/50Hz and unit couple with return air plenum and 8mm nylon filter.
2) The air flow, power input, sound data is tested on standard air condition without water in coil.
3) The capacity is tested under M speed, 50Pa and below condition:
---Cooling capacity: Entering air DB/WB: 27°C/19.5°C, water inlet 7°C, water outlet 12°C
4) The sound pressure is measured according to GB/T 19232-2019 (1m below the unit bottom).

14 DAIKIN
FWW-T Ceiling Concealed Fan Coil Unit

District Cooling Unit / 2-Pipe / 4 Rows

Model FWW1000TA FWW1400TA FWW1600TA FWW1800TA FWW2000TA


m3/h 1670 2180 2700 3150 3600
High
CFM 982 1282 1588 1853 2118
m3/h 1550 2000 2400 2970 3350
Air Flow Medium
CFM 912 1176 1412 1747 1971
m3/h 1200 1650 1960 2550 2500
Low
CFM 706 971 1153 1500 1471
Pa 50
ESP Medium
in.wg. 0.2
W 7700 9600 11600 13300 15600
Total Cooling Capacity
Btu/h 26272 32755 39579 45380 53227
m3/h 0.73 0.91 1.1 1.27 1.49
Water Flow Rate
USGPM 3.21 4.00 4.84 5.59 6.56
kPa 44 42 42 42 36
Water Pressure drop
in.wg. 177 169 169 169 145
High W 250 410 531 612 769
Rated Power
Medium W 230 370 420 550 704
Input
Low W 165 280 310 450 465
High A 1.1 1.8 2.33 2.69 3.38
Rated Running
Medium A 1.02 1.64 1.86 2.44 3.12
Current
Low A 0.76 1.28 1.42 2.06 2.13
High dB(A) 63 65 69 70 70
Lw Outlet Duct Medium dB(A) 61 63 67 69 69
Low dB(A) 56 60 64 68 64
High dB(A) 66 66 72 75 73
Lw Inlet + Rad Medium dB(A) 64 65 70 74 72
Low dB(A) 59 61 66 71 66
High dB(A) 48 50 53 55 55.5
Sound
Medium dB(A) 46 49 51 54 54
Pressure Level
Low dB(A) 41 44 47 51 51
Type 8mm Nylon Filter
Filter
Access Both Side & Bottom Withdraw
Row No. 4
Working Pressure 2.0 MPa
Coil
Material Copper tube & Hydrophilic Aluminum
Water Volume L 1.72 2.01 2.21 2.52 3.06
Type Galvanized Steel Centrifugal Fan (Forward)
Fan
Quantity 2 2 2 2 2
Type 3 Speed PSC Motor
Motor Quantity 1 1 1 1 1
IP/Insulation IP20 / ≥B
NOTES:
1) All performance is tested under 230V~/50Hz and unit couple with return air plenum and 8mm nylon filter.
2) The air flow, power input, sound data is tested on standard air condition without water in coil.
3) The capacity is tested under M speed, 50Pa and below condition:
---District Cooling capacity: Entering air DB/WB: 24°C/18°C, water inlet 5.5°C, water outlet 14.5°C
4) The sound pressure is measured according to GB/T 19232-2019 (1m below the unit bottom).
The sound power level is measured accroding to "Eurovent 8/12 Sound test methad for ducted fan coil unit ".

15 DAIKIN
FWW-T Ceiling Concealed Fan Coil Unit

Dimensions
E

15
K

MOUNTING HOLE
6-16X10
J

CONDENSATE DRAIN R3/4


H

B
D C
A

G
WATER OUTLET N
Rc 1"

R
AIR FLOW

M
P

S
177
WATER INLET
Rc 1" 353

A
Model Standard Extend G P B C D E F H J K M N Q R S
drain pan drain pan
FWW1000T 1195 1395 585 290 952 987 48 1085 1006 65 150 227 254 127 202 66 143
FWW1400T 1195 1395 750 345 952 987 50 1085 985 68 232 221 307 183 248 123 143
FWW1600T 1295 1495 750 345 1053 1087 50 1185 1085 68 232 221 307 183 248 123 143
FWW1800T 1445 1645 750 345 1201 1237 50 1335 1235 68 232 221 307 183* 248 123 143
FWW2000T 1445 1645 780 390 1201 1237 50 1335 1235 68 232 266 354 183* 300 62 250
Unit: mm
Package Dimension Net Weight (kg) Gross Weight (kg)
Model
(L*D*H) mm 3 rows 4 rows 3 rows 4 rows
FWW1000T 1211*305*608 34.9 35.7 38.9 39.7
FWW1400T 1211*360*773 50.5 51.6 55 56
FWW1600T 1311*360*773 51.6 52.7 56.8 57.9
FWW1800T 1461*360*773 57.6 58.7 63.3 64.4
FWW2000T 1461*405*803 62.7 64.1 68.5 70

Remark: The water pipe location of FWW1800TF and FWW2000TF is different. Please refer to below drawing.
780
750
170 39
164 36
127
132

126
390
345

73

*Water pipe location for FWW1800TF


*Water pipe location for FWW1800TA
*Water pipe location
*Water forforFWW2000TF
pipe location FWW2000TF
(only for disctrict cooling unit)
(only for disctrict cooling unit)

16 DAIKIN
FWW-AA Ceiling Exposed Fan Coil Unit

FWW-AA Horizontal Exposed Fan Coil

X Novel shape and ultra-thin size X District cooling application


The ultra-thin design reduces the space required. The novel The unique circuit design and the application of large
shape makes the interior decoration more brilliant. temperature difference optimize the overall cooling
performance of the unit.

X Primary-efficiency filter for health & comfort X Easy installation and convenient maintenance
A cleanable primary-efficiency filter of nylon screen is Due to ceiling installation, it is not required to specially
configured at the air inlet to effectively filter out the dust from decorate the wall and ceiling.
the air and guarantee the indoor air quality. The standard configuration of the unit includes a back air
return inlet where the filter can be easily removed and
replaced.

17 DAIKIN
FWW-AA Ceiling Exposed Fan Coil Unit

Nomenclature
FWW 200 AA 0 L E F -A 0 A E

E: For export

Power Supply
220-240V~/50Hz

Without Electrical Heater

Standard Drain Pan

8mm Nylon Filter

Bottom Plenum with FG and Felt Insulation

Pipe Connection
R-Facing Air Flow Right Hand
L-Facing Air Flow Left Hand

0 Pa External Static Pressure

AA-Series

Nominal Air Flow (CFM, 1CFM=1.7m3/h)

Daikin Ceiling Exposed Chilled Water FCU

18 DAIKIN
FWW-AA Ceiling Exposed Fan Coil Unit

District Cooling Unit/2-pipe/4 Rows

MODEL 200AA 300AA 400AA 600AA 800AA 1000AA 1200AA 1400AA


3
High m /h 340 510 680 1020 1360 1700 2040 2380
Air flow Medium m3/h 279 418 558 836 1115 1394 1673 1952
3
Low m /h 170 255 340 510 680 850 1020 1190
Total cooling capacity W 2125 3385 4390 6207 8096 10165 11066 13744
Sensible capacity W 1233 2059 2848 4179 5572 7125 7961 9770
3
Water flow m /h 0.21 0.33 0.43 0.6 0.79 0.99 1.07 1.32
Water pressure drop kPa 5 13 22 16 16 25 20 29
Rated power input W 39 53 72 107 142 183 217 239
Rated running current A 0.18 0.24 0.33 0.48 0.65 0.83 0.99 1.09
High dB(A) 36 40 43 46 46 50 50 51
Sound pressure
Medium dB(A) 32 36 36 42 42 47 47 46
level
Low dB(A) 23 25 29 30 32 38 36 37
Coil
Tube material Copper
Fin material Hydrophilic aluminum
Filter withdraw
Bottom return 8mm nylon filter Bottom withdraw
Max. working pressure 2.0MPa
Cooling water pipe size Rc 3/4 Female thread
Condensation water pipe size R3/4 Male thread
Fan
Type Galvanized steel double stage impeller forward centrifugal
Quantity 1 2 2 2 3 4 4 4
Motor
Type 3 speed permanent split capacitor motor
Quantity 1 1 1 1 2 2 2 2
Insulation class IP20/B
NOTES:
1) All performance is tested under 220V~/50Hz and unit couple with return air plenum and 8mm nylon filter.
2) The air flow, power input, sound data is tested on standard air condition without water in coil.
3) The cooling capacity are being tested under following condition:
H speed, entering air db/wb: 27°c/19.5°C, water inlet 5°C, water outlet 15°C
4) Sound pressure measured at 1m in front of the unit and 1m below the vertical center line of the unit, and tested in semi-
anechoic room, with background sound pressure level: 11.5db (a).
5) When the water connect direction is changed in field,the capacity should be reduced by 15%.
6) For medium speed, the capacity is about 87% of high speed.
For low speed, the capacity is about 60% of high speed.

19 DAIKIN
FWW-AA Ceiling Exposed Fan Coil Unit

Technical specifications
Dimensions
Ceiling Exposed Unit FWW-AA
CONDENSAT DRAIN PIPE
20.8

MOUNTING HOLES
10-10X16

AIR VENT VALVE

WATER RETURN
Rc 3/4

WATER SUPPLY
Rc 3/4

Unit: mm
Unit: mm
Package Dimension
UNIT Model A B C D E Net Weight (kg) Gross weight (kg)
Unit model A B C D E Package dimension (L×H×W) mm Net weight (kg)
(L*W*H) mm Gross weight (kg)
FWW200AA
FWW200AA 963 963 957 488
957 520 488 927 520 970×565×300
927 970x300x565 30 30 32 32
FWW300AA
FWW300AA 1103 1103 1097 628
1097 660 628 1067 660 1110×565×300
1067 1110x300x565 35 35 38 38
FWW400AA
FWW400AA 1203 1203 1197 728
1197 760 728 1167 760 1210×565×300
1167 1210x300x565 39 39 42 42
FWW600AA
FWW600AA 1383 1383 1377 908
1377 940 908 1347 940 1390×565×300
1347 1390x300x565 44 44 48 48
FWW800AA
FWW800AA 1713 1713 1707 1238
1707 1270 1238 1677 1270 1720×565×300
1677 1720x300x565 61 61 66 66
FWW1000AA
FWW1000AA 1813 1813 1807 1338
1807 1370 1338 1777 1370 1820×565×300
1777 1820x300x565 66 66 71 71
FWW1200AA
FWW1200AA 2013 2013 2007 1538
2007 1570 1538 1977 1570 2020×565×300
1977 2020x300x565 73 73 78 78
FWW1400AA
FWW1400AA 2273 2273 2267 1798
2267 1830 1798 2237 1830 2280×565×300
2237 2280x300x565 83 83 89 89

Exploded-View&&Part
Exploded-View PartList
List
Item Description
1 Top panel for air return plenum
11 11 1 1 Item Description
2 Motor
1 Top Panel For Air Return Plenum
12 3 Fan deck
2 Motor
12 2 4 Fan
3 Fan Deck
13 3 5 2 Terminal box
4 Fan
6 Right side plate of air return box
5 Terminal Box
14 13 4
7
3 Condensate drain pipe
5 6 Right side plate of air return box
8 Back support plate
15 14 6
4 7 Condensate drain pipe
9 Filter and grille
16 8 Back support plate
7 10 5 Right side plate
17 9 Filter and Grille
15 11 Left side plate of return air box
18 6 10 Right side plate
16 8 12 Top plate 11 Left side plate of return air box
13 7 Coil assy 12 Top plate
17 14 Deflector 13
19 Coil assy
9
18 15 Drain pan 14 Deflector

10
16 8 Left side plate
15 Drain pan
17 Front cross beam
16 Left side plate
18 Air supply grille
17 Front cross beam
19 19 Bottom panel
9 18 Air supply grille
19 Bottorn panel

10
20 DAIKIN
FUW-A Utra-thin cealing unit for High ESP application

Long-distance
air supply via
air ducts
Narrow and long Partial ceiling in
corridor irregular room

X Flat body X High static pressure air supply


The unit adopts a flat design to reduce its height and depth The unit adopts a high static pressure design to extend the
for a small drop ceiling. air supply distance, thus being applicable to a variety of
irregular rooms.

Efficient and direct driven motor Double-inlet forward centrifugal fan


with multiple wings

X Direct-driven fan motor


No belt abrasion, no maintenance, reliable operation, and low failure rate

21 DAIKIN
FUW-A Utra-thin cealing unit for High ESP application

Nomenclature
High ESP Ceiling Unit FUW-A
FUW 030 A- 4 L -A A B E

E: For Export
U: With NPT 60° Header
Design Series
Filter Type: A- 8mm Nylon Filter
B- 25mm Aluminum Filter
A: 220-240V/1 Ph/50Hz
K: 208-230V/1 Ph/60Hz
L-Left Hand (Facing Discharge)
R-Right Hand (Facing Discharge)
4-4 Rows; 6-6 Rows
A-Structure Type
Nominal Air Flow (*100CMH)
015,020,025,030,035,040,050
High ESP Ceiling Chilled Water FCU

Exploded-View & Part List

A1 FAN MOTOR ASSY. F4 BASE PANEL ASSY. F9 SIDE PANEL DRAIN


A2 FILTER ASSY. F5 R COIL BAFFLE F10 SIDE PANEL ACCESS
F1 FRONT PANEL F6 L COIL BAFFLE F11 TOP PANEL
F2 COLLAR ASSY. F7 TOP FIX F12 DRAIN PAN ASSY.
F3 SIDE PANEL WIDE F8 TERMINAL BOX H1 COIL ASSY.

22 DAIKIN
FUW-A Utra-thin cealing unit for High ESP application

Standard Unit/2-pipe/4 or 6 Rows


Model FUW015A FUW020A FUW025A FUW030A FUW035A FUW040A FUW050A
Nominal air flow m3/h 1500 2000 2500 3000 3500 4000 5000
External static pressure (ESP) Pa 70 100 100 120 120 150 150
4 Rows(return air) 7 12 13 17 20 23 30
4 Rows(fresh air) 18 27 33 41 47 53 64
Cooling
6 Rows(return air) 10 14 18 22 26 30 38
6 Rows(fresh air) 24 33 42 50 57 65 78
Nominal capacity kW
4 Rows(return air) 13 19 22 27 32 36 46
4 Rows(fresh air) 22 30 37 44 52 59 75
Heating
6 Rows(return air) 16 22 27 33 38 44 55
6 Rows(fresh air) 26 35 43 52 61 70 88
4 Rows(return air) 0.34 0.57 0.64 0.79 0.93 1.08 1.42
4 Rows(fresh air) 0.88 1.29 1.59 1.93 2.25 2.51 3.05
Cooling
6 Rows(return air) 0.48 0.67 0.86 1.05 1.23 1.43 1.83
6 Rows(fresh air) 1.15 1.59 2.01 2.38 2.72 3.08 3.72
Water flow l/s
4 Rows(return air) 0.31 0.44 0.53 0.64 0.75 0.87 1.1
4 Rows(fresh air) 0.51 0.72 0.87 1.05 1.23 1.41 1.78
Heating
6 Rows(return air) 0.38 1.51 0.65 0.78 0.91 1.04 1.31
6 Rows(fresh air) 0.61 0.83 1.03 1.24 1.45 1.67 2.08
4 Rows(return air) 1 26 5 9 13 19 37
4 Rows(fresh air) 7 80 29 46 60 66 77
Cooling
6 Rows(return air) 4 8 14 22 33 47 87
Water pressure 6 Rows(fresh air) 18 37 65 79 87 95 112
kPa
drop 4 Rows(return air) 1 14 3 5 8 11 20
4 Rows(fresh air) 2 34 8 13 19 27 49
Heating
6 Rows(return air) 2 4 7 11 16 23 41
6 Rows(fresh air) 5 10 17 26 38 53 93
Rated power 4 Rows 368 488 977 790 874 1335 1864
W
input 6 Rows 407 680 886 830 916 1450 1646
220-240V~/50Hz
Rated running 4 Rows 1.67 2.25 4.48 3.66 4.13 6.25 8.52
A
current 6 Rows 1.87 3.18 4.07 2.95 4.23 5.54 7.56
Rated power 4 Rows 305 455 601 687 833 1060 1220
W
input 6 Rows 307 509 625 765 860 1017 1217
208-230V~/60Hz
Rated running 4 Rows 1.33 2.01 2.75 2.98 3.89 3.96 5.55
A
current 6 Rows 1.34 2.22 2.68 3.45 3.91 4.44 5.31
High 44.1 50.6 55.7 52.5 53.5 53.6 57
Sound pressure level Medium dB(A) 40.7 48 52.2 50.5 52.1 51.5 56
Low 37.7 45.1 48.4 48.5 50.2 49.5 54.9
Structure Type Gaivanlzed steel coated with elextrostatlc spraying. lntemal gued with insulation PE
Type Corrugated aluminum fin mechanlcally bonded with copper tube
Max. working pressure(MPa) 1.6
Coil
Inlet/outlet pipe R1½”
Condensing water pipe R¾”
8mm nylon filter Side withdraw
Filter withdraw
25mm aluminum filter Side withdraw
Type/material Centrlfugal forward curved blower and galvanlzed steel
Fan
Fan no. 1 2
Type Single phase capacltor running
Motor Quantity 1 2
Insulation class IP20 B

NOTES:
1) All performance are tested under 220V~/50Hz and unit couple with 8mm nylon filter.
2) The air flow, power input, sound data is tested on standard air condition without water in coil.
3) The cooling capacity are being tested under following condition:
Return air cooling conditions: 27°C/19.5°C WB; fresh air cooling conditions: 34°C DB/28°C WB
Cooling water entering/leaving conditions: 7°C/12°C
Return air heating condition: 21°C DB; fresh air heating condition: 0°C DB;
Heating water entering/leaving conditions: 60°C/50°C
4) Sound pressure measured at 1m in front of the unit and 1m below the vertical center line of the unit,
And tested in semi-anechoic room with background sound pressure level: 11.5DB(a)

23 DAIKIN
FUW-A Utra-thin cealing unit for High ESP application

Dimensions
Mounting hole 4-Φ12
B 80

F
55
178

60

795
750
40

E C 15
40
18

D 37
A Terminal Box Water inlet Water outlet

358
267

420
264
84

40
28

15
Condensation pipe

Unit: mm
Dimension F Net weight (kg)
Package dimension
A B C D E
8mm nylon filter 25mm AL filter (L×H×W) mm 4 rows 6 rows
Model
FUW015A 740 540 237 666 236 77 90 930×590×930 76 79
FUW020A 900 700 317 826 236 77 90 1090×590×930 80 84
FUW025A 1060 860 397 986 236 77 90 1250×590×930 86 90

B 80
Mounting hole 4-ф12
F
55
178

60

795
750
40

E G E C 15
40
18

D 37

A Terminal Box Water inlet Water outlet


358
267

420
264
84

40
28

15

Condensation pipe

Unit: mm
Dimension F Net weight (kg)
Package dimension
A B C D E G
8mm nylon filter 25mm AL filter (L×W×H) mm 4 rows 6 rows
Model
FUW030A 1210 1010 282 1136 236 77 90 174 1400×590×930 92 96
FUW035A 1360 1160 337 1286 236 77 90 214 1540×590×930 96 101
FUW040A 1510 1310 347 1436 236 77 90 344 1700×590×930 102 107
FUW050A 1840 1640 412 1766 236 77 90 544 2030×590×930 108 113

24 DAIKIN
FUW-A Utra-thin cealing unit for High ESP application

Electric Heating Box for FUW-A Unit


X Electric Heating Box Power

Electric Box Model Power Supply Capacity(kW) Electric Box Model Power Supply Capacity(kW)
FUW-EH-020BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 2 FUW-EH-050BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 5
FUW-EH-030BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 3 FUW-EH-060BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 6
FUW-EH-040BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 4 FUW-EH-075BOX 220-240V/1Ph/50Hz; 208-230V/1Ph/60Hz 7.5

NOTES:
EACH HEATER BOX CAN ONLY BE USED FOR ONE AIR DISCHARGE DUCT.
1) FUW015/20/025 - ONLY ONE HEATING BOX IS REQUIRED.
2) FUW030/035/040/050 - NEED TO SELECT TWO BOX, AND THE HEATING CAPACITY OF EACH BOX SHOULD BE REQUIRED TOTAL
CAPACITY TO DIVIDE BY TWO.

X Dimensions of Electric Heating Box

431

430 430

348

551 516 472

239

X Scheme of Electric Heating Box Installation

Electrical Heater

Flexile Connection

FUW-A Unit

25 DAIKIN
Wiring

Electrical wiring connection must be done according to the wiring diagram on the unit.
The unit must be GROUNDED to the earth system of the building.
All field wiring must be installed in accordance with the national wiring regulation and Fire Department regulation

FWW-V

FWW-T

26 DAIKIN
Wiring

FWW-AA
MODEL: FWW 200~1400AA

HI YELLOW FAN MOTOR 1


FAN SPEED 1 BLACK
SWITCH ME BROWN
2 M
~ BLACK
LO ORANGE
3
4
POWER BLUE
5(N) FAN MOTOR 2
SOURCE
BLACK

M
~ BLACK

WARNING:
PAY ATTENTION TO THE CORRECT WIRING,
OR BURN OUT THE MOTOR! FAN MOTOR2 APPLY TO
800~1400 UNITS

FIELD WIRING DWG No.: M08024067114

FUW-A

MODEL: FUW-A

H HIGH
HF
M MIDDLE FAN
FAN MOTOR
MF MOTOR
CAPACITOR
L 1
LOW
LF
YELLOW/GREEN
FAN SPEED SWITCH
N
HIGH

MAIN POWER SWITCH L FAN


MIDDLE FAN MOTOR
POWER MOTOR
CAPACITOR
L 2
SOURCE LOW
YELLOW/GREEN

NOTE:
FIELD WIRING FAN MOTOR2 APPLY TO FUW030A/035A/040A/050A UNITS.
LF: FAN SPEED LOW
MF: FAN SPEED MIDDLE
HF: FAN SPEED HIGH

27 DAIKIN
Guide Specifications for FWW Unit

X Unit Description
Factory-assembled, horizontal, galvanized casing, ceiling ducted fan coil unit is complete with water coil, fans, motors, drain
pan, filters and all required wiring, with full access to internal components.

X Quality Assurance
Each coil is factory tested for leakage at 2.5MPa air pressure with coil submerged in water. Each unit and its moving
components (fans and motors) are factory computer-tested and recorded after unit is complete and before it is packed.

X Factory shall be certified by following standard


1. ISO 9001:2015 certification for Quality Management Systems
2. ISO 14001:2015 certification for Environmental Management Systems
3. ISO 45001:2018 certification for Occupational Health and Safety

X Component Specifications
1.Casing:
Construction is galvanized steel, lined on the inside with thermal and acoustical insulation. Return air plenum is lined with XPE
and has a collar for return duct connection. Supply duct connection also has a collar. Removable bottom panel is provided for
access to the fan/motor assembly.
2. Coil:
Standard unit is equipped with a 3-rows, 4-rows or 3+1 rows coil for installation in a 2-pipe or 4-pipe system. Coil has seamless
copper tubes, fins hydrophilic aluminum bonded to the tubes by mechanical expansion.
3. Fan:
Direct-driven centrifugal fan wheel has forward-curved blades which are statically and dynamically balanced.
The fan housing and blades are constructed of high quality hot-galvanized steel.
4.Motor:
Fan motor is 3-speed, permanent split-capacitor with ball type bearing and build-in automatic reset thermal overload protection.
Motors have permanently lubricated ball bearings.
5. Drain Pan
Drain pan shall be die-formed steel, sloped to the piping connection, which will be threaded for easy connection. Both its sides
are sprayed and outer side insulated with 6mm NBR that complies with GB 8624 B1 class requirement. It extends under the full
length and width of the coils and is pitched for positive drainage with features of high anti-corrosion, anti-condensation and high
fire reluctance.
6. Filter
Filter is with washable type Nylon filter with 8mm thickness.

28 DAIKIN
Warning ● D
 aikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world.
Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular
country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or
retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where
the product will be used. This statement does not purport to exclude, restrict or modify the application of any
local legislation.

● A
 sk a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper
installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

● U
 se only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor
to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of
parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

● R
 ead the User’s Manual carefully before using this product. The User’s Manual provides important safety
instructions and warnings. Be sure to follow these instructions and warnings.

If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. The units should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.

2. If the unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to
install the unit close to the sea shore, contact your local distributor.

Dealer DAIKIN INDUSTRIES, LTD.


Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
©All rights reserved

Printed with soy ink.

Literature No.: CA-FCU 50Hz-202301

You might also like