Catalogue - LV Cables
Catalogue - LV Cables
Catalogue - LV Cables
1
If the steel foundations are the
bones and spines of the building,
the cables are the blood vessels Part 1: Cable Construction Data
that feed life to it.
Survanabhumi, Thailand
2 3
Standards
Single Core CU/PVC
In Prysmian Group, we design and manufacture cables to the following standards:- PVC Insulated, Non-sheathed 450/750V
British Standards (BS)
BS 6004 Electric cables. PVC insulated, non-armoured cables for voltages up to and including 450/750V, for
electric power, lighting and internal wiring. 1
BS6346 Electric cables. PVC insulated, armoured cables for voltages up to 600/1000V and 1900/3300V.
Component
BS 6360 Specification for conductors in insulated cables and cords. 1. Copper Conductor
BS 6500 Electric cables, Flexible cords rated up to 300/500V, for use with appliances and equipment intended 2 2. PVC Insulation
for domestic, office and similar environments.
BS 6387 Specification for performance requirements for cables required to maintain circuit integrity
under fire conditions.
BS 5467 Electric cables. Thermosetting insulated, armoured cables for voltages of 600/1000V and 1900/3300V.
BS 6724 Electric cables. Thermosetting insulated, armoured cables for voltages of 600/1000V and 1900/3300V,
having low emission of smoke and corrosive gases when affected by fire. Standards Applied Electrical Characteristics
BS 7671 Requirements for Electrical Installations. IEE Wiring Regulations. Design Guide: IEC60227-3, BS6004, SS358-3, MS136 Operating voltage, Uo/U: 450/750V
Conductor: IEC60228, BS6360, BS EN 60228 Max. operating temperature: 70°C
BS 7211 Electric cables. Thermosetting insulated, non-armoured cables for voltages up to and including Flame Retardancy: IEC60332-1-2, IEC60332-3-24** Final short circuit temperature: 160°C
450/750V, for electric power, lighting and internal wiring, and having low emission of smoke and Test voltage: 2.5kV for 15 minutes
corrosive gases when affected by fire.
Installation Guide
International Electrotechnical Commission (IEC) Min. bending radius (mm) : 6 x Cable Overall Diameter
Max. pulling tension (kgf) : 7 x No. of Core x Conductor Size
IEC 60227-3 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and including 450/750V
Part 3: Non-Sheathed Cables for Fixed Wiring. Construction
IEC 60228 Conductors of Insulated Cables. Conductor Plain annealed copper wire
IEC 60331 Tests for electric cables under fire conditions - Circuit integrity - Insulation An extruded layer of polyvinyl chloride (PVC) compound
Part 11: Apparatus - Fire alone at a flame temperature of at least 750oC. Core Identification Black, Red, Green/Yellow, Yellow, Blue, White, Grey, Brown or other
IEC 60332-1-2 Tests on electric and optical fibre cables under fire conditions -
Part 1-1: Test for vertical flame propagation for a single insulated wire or cable Procedure for
1 kW pre-mixed flame. Dimension & Electrical Data
IEC 60332-3-22 Tests on electric and optical fibre cables under fire conditions -
Nom. Insulation Nom. Overall Approx. Cable Max. d.c. Resistance
Part 3-22: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category A. Product ID No. of Core Conductor Size
Thickness Diameter Weight at 20°C
IEC 60332-3-24 Tests on electric and optical fibre cables under fire conditions -
mm² mm mm kg/km Ω/km
Part 3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category C.
1 1.5 0.7 3.0 22 12.1
IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltages from
1 2.5 0.8 3.6 33 7.41
1kV (Um = 1,2kV) up to 30kV (Um = 36kV) -
1 4 0.8 4.2 50 4.61
Part 1: Cables for rated voltages of 1 kV (Um = 1,2kV) and 3kV (Um = 3.6kV).
1 6 0.8 4.7 70 3.08
IEC 60754-1 Test on gases evolved during combustion of materials from cables -
1 10 1.0 6.1 118 1.83
Part 1: Determination of the amount of halogen acid gas. 1 16 1.0 7.1 178 1.15
IEC 60754-2 Test on gases evolved during combustion of electric cables - 1 25 1.2 8.8 280 0.727
Part 2: Determination of degree of acidity of gases evolved during the combustion of material taken 1 35 1.2 10.1 376 0.524
from electric cables by measuring pH and conductivity. 1 50 1.4 11.7 509 0.387
IEC 61034-2 Measurement of smoke density of cables burning under defined conditions. 1 70 1.4 13.5 717 0.268
1 95 1.6 15.8 991 0.193
Malaysia Standards 1 120 1.6 17.4 1229 0.153
MS 136 PVC-insulated cable (non-armoured) for electric power and lighting. 1 150 1.8 19.4 1512 0.124
MS 274 PVC-insulated cables for electricity supply with rated voltage 0.6/1kV 1 185 2.0 21.6 1895 0.0991
1 240 2.2 24.7 2471 0.0754
Singapore Standards 1 300 2.4 27.5 3092 0.0601
SS 358-3 PVC-insulated, non-sheathed cables 450/750V. 1 400 2.6 30.9 3938 0.0470
SS 299 Specification for fire resistant cables 1 500 2.8 34.4 4945 0.0366
Part 1 - Performance requirements for cables required to maintain circuit integrity under fire conditions. 1 630 2.8 38.4 6303 0.0283
** Available upon request
4 5
CU/PVC/PVC, PVC Insulated, PVC sheathed Cable, 0.6/1kV
2-, 3-, 4-, 5-Cores
Single Core, 2-, 3-, 4-, 5-, multicores CU/PVC/PVC
PVC Insulated, PVC sheathed Cable, 0.6/1kV Dimension & Electrical Data
Nom. Insulation Nom. Sheath Nom. Overall Approx. Cable Max. d.c. Resistance
Product ID No. of Core Conductor Size
Thickness Thickness Diameter Weight at 20°C
Assembly*** Cores cabled together, supplied with filler* and covered with polyester (PETP) binder tape* mm² mm mm mm kg/km Ω/km
Outer Sheath An extruded layer of polyvinyl chloride (PVC) compound 3 1.5 0.8 1.8 10.9 159 12.1
Outer Sheath Colour Black except single core. Single core will come with grey outer sheath. 3 2.5 0.8 1.8 11.9 202 7.41
3 4 1.0 1.8 13.0 267 4.61
Dimension & Electrical Data 3 6 1.0 1.8 14.3 347 3.08
3 10 1.0 1.8 17.4 511 1.83
Nom. Insulation Nom. Sheath Nom. Overall Approx. Cable Max. d.c. Resistance
Product ID No. of Core Conductor Size 3 16 1.0 1.8 19.9 724 1.15
Thickness Thickness Diameter Weight at 20°C
3 25 1.2 1.8 23.7 1086 0.727
mm² mm mm mm kg/km Ω/km
3 35 1.2 1.8 26.2 1396 0.524
1 1.5 0.8 1.4 6.0 53 12.1
3 35 sh 1.2 1.8 21.9 1340 0.524
1 2.5 0.8 1.4 6.4 66 7.41
3 50 1.4 1.8 29.8 1847 0.387
1 4 1.0 1.4 7.4 93 4.61
3 50 sh 1.4 1.8 24.7 1770 0.387
1 6 1.0 1.4 7.9 118 3.08
3 70 1.4 1.9 33.9 2471 0.268
1 10 1.0 1.4 8.9 167 1.83
3 70 sh 1.4 1.9 27.9 2430 0.268
1 16 1.0 1.4 9.9 234 1.15
3 95 1.6 2.1 39.6 3411 0.193
1 25 1.2 1.4 11.6 347 0.727
3 95 sh 1.6 2.1 32.6 3278 0.193
1 35 1.2 1.4 12.9 451 0.524
3 120 1.6 2.2 43.3 4336 0.153
1 50 1.4 1.4 14.5 595 0.387
3 120 sh 1.6 2.2 35.4 4149 0.1530
1 70 1.4 1.4 16.3 815 0.268
3 150 1.8 2.3 47.8 5310 0.124
1 95 1.6 1.5 18.8 1113 0.193
3 150 sh 1.8 2.3 39.2 4948 0.124
1 120 1.6 1.6 20.6 1372 0.153
3 185 2.0 2.5 53.2 6618 0.0991
1 150 1.8 1.6 22.6 1670 0.124
3 185 sh 2.0 2.5 43.7 6154 0.0991
1 185 2.0 1.7 25.0 2082 0.0991
3 240 2.2 2.7 60.1 8584 0.0754
1 240 2.2 1.8 28.3 2686 0.0754
3 240 sh 2.2 2.7 49.2 7905 0.0754
1 300 2.4 1.9 31.3 3342 0.0601
3 300 2.4 2.8 66.5 10661 0.0601
1 400 2.6 2.0 34.9 4248 0.0470
3 300 sh 2.4 2.9 53.6 9685 0.0601
1 500 2.8 2.1 38.6 5307 0.0366
3 400 2.6 3.1 74.5 13510 0.047
1 630 2.8 2.2 42.8 6736 0.0283
3 400 sh 2.6 3.1 66.4 12849 0.047
1 800 2.8 2.5 47.7 8536 0.0221
1 1000 3.0 2.5 52.6 10649 0.0176
sh: sector shaped conductor
* Optional
** Available upon request
*** Not applicable for single core
6 7
CU/PVC/PVC, PVC Insulated, PVC sheathed Cable, 0.6/1kV
2-, 3-, 4-, 5-Cores
Single Core CU/PVC/PVC/AWA/PVC
Dimension & Electrical Data PVC Insulated, PVC bedded, AWA armoured, PVC sheathed Cable 0.6/1kV
Nom. Insulation Nom. Sheath Nom. Overall Approx. Cable Max. d.c. Resistance
Product ID No. of Core Conductor Size
Thickness Thickness Diameter Weight at 20°C
1
mm² mm mm mm kg/km Ω/km
2 Component
4 1.5 0.8 1.8 11.8 196 12.1 1. Copper Conductor
2. PVC Insulation
4 2.5 0.8 1.8 12.8 255 7.41 3
3. PVC Bedding
4 4 1.0 1.8 15.1 371 4.61 4. Aluminium Wire Armoured
4 6 1.0 1.8 16.5 483 3.08 4 5. PVC Sheath
4 10 1.0 1.8 19.1 667 1.83 4 3 2 1
5 5
4 16 1.0 1.8 21.6 946 1.15
4 25 1.2 1.8 25.8 1408 0.727
4 35 1.2 1.8 28.8 1818 0.524
4 35 sh 1.2 1.8 26.2 1780 0.524
4 50 1.4 1.9 33.1 2467 0.387 Standards Applied Electrical Characteristics
4 50 sh 1.4 1.9 29.0 2352 0.387 Design Guide: BS6346, MS274 Operating voltage, Uo/U: 600/1000V
Conductor: IEC60228, BS6360, BS EN 60228 Max. operating temperature: 70°C
4 70 1.4 2.1 37.9 3413 0.268 Flame Retardancy: IEC60332-1-2, IEC60332-3-24**, IEC60332-3-22** Final short circuit temperature: 160°C
4 70 sh 1.4 2.0 33.2 3251 0.268 Test voltage: 3.5kV for 5 minutes
4 95 1.6 2.2 43.4 4599 0.193
4 95 sh 1.6 2.2 38.6 4438 0.193 Installation Guide
Min. bending radius (mm) : 10 x Cable Overall Diameter
4 120 1.6 2.3 48.0 5623 0.153
Max. pulling tension (kgf) : 7 x No. of Core x Conductor Size
4 120 sh 1.6 2.3 41.8 5516 0.1530
4 150 1.8 2.5 53.1 6943 0.124 Construction
4 150 sh 1.8 2.5 46.9 6613 0.124
Conductor Plain annealed copper wire
4 185 2.0 2.7 59.1 8687 0.0991
Insulation An extruded layer of polyvinyl chloride (PVC) compound
4 185 sh 2.0 2.6 51.9 8180 0.0991
4 240 2.2 2.9 66.8 11185 0.0754 Core Identification Refer to Appendix F for details
4 240 sh 2.2 2.9 58.8 10545 0.0754 Bedding An extruded layer of polyvinyl chloride (PVC) compound
4 300 2.4 3.1 74.2 14008 0.0601 Bedding Colour Black
4 300 sh 2.4 3.1 65.1 12954 0.0601 Armour A single layer of aluminium wire armoured (AWA)
4 400 2.6 3.4 83.0 17664 0.047 Outer Sheath An extruded layer of polyvinyl chloride (PVC) compound
4 400 sh 2.6 3.4 73.3 17018 0.047
Outer Sheath Colour Black
sh: sector shaped conductor
8 9
CU/PVC/PVC/SWA/PVC, PVC insulated, PVC bedded, SWA armoured, PVC sheathed Cable 0.6/1kV
2-, 3-, 4-, 5-, multicores
2-, 3-, 4-, 5-, multicores CU/PVC/PVC/SWA/PVC
PVC insulated, PVC bedded, SWA armoured, PVC sheathed Cable 0.6/1kV Dimension & Electrical Data
1
Nom. Nom. Dia. Nom. Nom. Approx. Max. d.c.
Conductor Nom. Sheath
Product ID No. of Core Insulation after Armour Overall Cable Resistance
2 Size Thickness
Component Thickness Bedding Wire Size Diameter Weight at 20°C
3 1. Copper Conductor
mm² mm mm mm mm mm kg/km Ω/km
2. PVC Insulation
3. PVC Bedding 3 1.5 0.6 7.7 0.9 1.4 12.6 315 12.1
4 4. Galvanised Steel Wire Armoured 3 2.5 0.7 9.1 0.9 1.4 14.0 390 7.41
5. PVC Sheath 3 4 0.8 10.7 0.9 1.4 15.6 499 4.61
5 5 4 3 2 1
3 6 0.8 12.0 1.25 1.5 17.8 707 3.08
3 10 1.0 15.1 1.25 1.6 21.2 974 1.83
3 16 1.0 17.4 1.25 1.6 23.1 1235 1.15
3 25 1.2 21.6 1.6 1.7 28.2 1910 0.727
3 35 1.2 24.1 1.6 1.8 30.9 2320 0.524
Standards Applied Electrical Characteristics 3 35 sh 1.2 19.8 1.6 1.8 27.1 2149 0.524
Design Guide: BS6346, MS274 Operating voltage, Uo/U: 600/1000V 3 50 1.4 27.7 1.6 1.9 34.7 2938 0.387
Conductor: IEC60228, BS6360, BS EN 60228 Max. operating temperature: 70°C 3 50 sh 1.4 22.6 1.6 1.9 30.1 2710 0.387
Flame Retardancy: IEC60332-1-2, IEC60332-3-24**, IEC60332-3-22** Final short circuit temperature: 160°C 3 70 1.4 32.3 2.0 2.0 40.3 4123 0.268
Test voltage: 3.5kV for 5 minutes
3 70 sh 1.4 26.3 2.0 2.0 34.8 3765 0.268
3 95 1.6 37.3 2.0 2.1 45.5 5308 0.193
Installation Guide 3 95 sh 1.6 30.3 2.0 2.1 39.0 4794 0.193
Min. bending radius (mm) : 10 x Cable Overall Diameter 3 120 1.6 40.8 2.0 2.2 49.2 6311 0.153
Max. pulling tension (kgf) : 7 x No. of Core x Conductor Size
3 120 sh 1.6 32.9 2.0 2.2 41.8 5791 0.153
3 150 1.8 45.5 2.5 2.4 55.3 8048 0.124
Construction 3 150 sh 1.8 36.9 2.5 2.4 47.2 7206 0.124
Conductor Plain annealed copper wire 3 185 2.0 50.5 2.5 2.5 60.5 9622 0.0991
3 185 sh 2.0 41.0 2.5 2.5 51.5 8636 0.0991
Insulation An extruded layer of polyvinyl chloride (PVC) compound
3 240 2.2 57.0 2.5 2.6 67.2 11956 0.0754
Core Identification Refer to Appendix F for details 3 240 sh 2.2 46.5 2.5 2.6 57.2 10747 0.0754
Assembly Cores cabled together, supplied with filler* and covered with polyester (PETP) binder tape* 3 300 2.4 63.6 2.5 2.8 74.2 14513 0.0601
3 300 sh 2.4 50.5 2.5 2.8 62.0 12775 0.0601
Bedding An extruded layer of polyvinyl chloride (PVC) compound
3 400 2.6 71.0 2.5 3.0 82.0 17773 0.047
Bedding Colour Black 3 400 sh 2.4 56.7 2.5 3.0 68.7 16042 0.047
Armour A single layer of galvanised steel wire armour (SWA)
Outer Sheath An extruded layer of polyvinyl chloride (PVC) compound
Nom. Nom. Dia. Nom. Nom. Approx. Max. d.c.
Conductor Nom. Sheath
Outer Sheath Colour Black Product ID No. of Core Insulation after Armour Overall Cable Resistance
Size Thickness
Thickness Bedding Wire Size Diameter Weight at 20°C
mm² mm mm mm mm mm kg/km Ω/km
4 1.5 0.6 7.7 0.9 1.4 12.6 315 12.1
Dimension & Electrical Data 4 2.5 0.7 9.1 0.9 1.4 14.0 390 7.41
Nom. Nom. Dia. Nom. Nom. Nom. Approx. Max. d.c. 4 4 0.8 10.7 0.9 1.4 15.6 499 4.61
Conductor
Product ID No. of Core Insulation after Armour Sheath Overall Cable Resistance at 4 6 0.8 12.0 1.25 1.5 17.8 707 3.08
Size
Thickness Bedding Wire Size Thickness Diameter Weight 20°C 4 10 1.0 15.1 1.25 1.6 21.2 974 1.83
4 16 1.0 17.4 1.25 1.6 23.1 1235 1.15
mm² mm mm mm mm mm kg/km Ω/km
4 25 1.2 21.6 1.6 1.7 28.2 1910 0.727
2 1.5 0.6 7.3 0.9 1.4 12.2 287 12.1 4 35 1.2 24.1 1.6 1.8 30.9 2320 0.524
2 2.5 0.7 8.6 0.9 1.4 13.5 353 7.41 4 35 sh 1.2 19.8 1.6 1.8 27.1 2149 0.524
2 4 0.8 10.1 0.9 1.4 15.0 447 4.61 4 50 1.4 27.7 1.6 1.9 34.7 2938 0.387
2 6 0.8 11.2 0.9 1.5 16.3 542 3.08 4 50 sh 1.4 22.6 1.6 1.9 30.1 2710 0.387
2 10 1.0 14.0 1.25 1.6 20.0 783 1.83 4 70 1.4 32.3 2.0 2.0 40.3 4123 0.268
4 70 sh 1.4 26.3 2.0 2.0 34.8 3765 0.268
2 16 1.0 16.2 1.25 1.6 21.9 992 1.15
4 95 1.6 37.3 2.0 2.1 45.5 5308 0.193
2 25 1.2 20.1 1.6 1.7 26.7 1516 0.727
4 95 sh 1.6 30.3 2.0 2.1 39.0 4794 0.193
2 35 1.2 22.7 1.6 1.8 29.5 1833 0.727 4 120 1.6 40.8 2.0 2.2 49.2 6311 0.153
2 50 1.4 26.0 1.6 1.9 33.0 2261 0.387 4 120 sh 1.6 32.9 2.0 2.2 41.8 5791 0.153
2 70 1.4 30.0 1.6 1.9 37.0 2885 0.268 4 150 1.8 45.5 2.5 2.4 55.3 8048 0.124
2 95 1.6 35.1 2.0 2.1 43.3 4056 0.193 4 150 sh 1.8 36.9 2.5 2.4 47.2 7206 0.124
2 120 1.6 38.4 2.0 2.2 46.8 4717 0.153 4 185 2.0 50.5 2.5 2.5 60.5 9622 0.0991
4 185 sh 2.0 41.0 2.5 2.5 51.5 8636 0.0991
2 150 1.8 42.3 2.0 2.3 50.9 5563 0.124
4 240 2.2 57.0 2.5 2.6 67.2 11956 0.0754
2 185 2.0 47.4 2.5 2.4 57.2 7183 0.0991
4 240 sh 2.2 46.5 2.5 2.6 57.2 10747 0.0754
2 240 2.2 53.5 2.5 2.5 63.5 8829 0.0754 4 300 2.4 63.6 2.5 2.8 74.2 14513 0.0601
2 300 2.4 59.7 2.5 2.7 70.1 10607 0.0601 4 300 sh 2.4 50.5 2.5 2.8 62.0 12775 0.0601
2 400 2.6 66.6 2.5 2.9 77.4 12862 0.047 4 400 2.6 71.0 2.5 3.0 82.0 17773 0.047
4 400 sh 2.4 56.7 2.5 3.0 68.7 16042 0.047
* Optional
** Available upon request
sh: sector shaped conductor
10 11
CU/PVC/PVC/SWA/PVC, PVC insulated, PVC bedded, SWA armoured, PVC sheathed Cable 0.6/1kV
2-, 3-, 4-, 5-, multicores
Single Core, 2-, 3-, 4-, 5-, multicores CU/XLPE/PVC
Dimension & Electrical Data
XLPE insulated, PVC sheathed Cable 0.6/1kV
Nom. Nom. Dia. Nom. Nom. Approx. Max. d.c.
Conductor Nom. Sheath
Product ID No. of Core Insulation after Armour Overall Cable Resistance
Size Thickness
Thickness Bedding Wire Size Diameter Weight at 20°C
12 13
CU/XLPE/PVC, XLPE insulated, PVC sheathed Cable, 0.6/1kV CU/XLPE/PVC, XLPE insulated, PVC sheathed Cable, 0.6/1kV
2-, 3-, 4-, 5-, multicores 2-, 3-, 4-, 5-, multicores
2 1.5 0.7 1.8 9.6 117 12.1 4 1.5 0.7 1.8 11.0 172 12.1
2 2.5 0.7 1.8 10.4 147 7.41 4 2.5 0.7 1.8 12.0 223 7.41
2 4 0.7 1.8 11.5 193 4.61 4 4 0.7 1.8 13.4 304 4.61
2 6 0.7 1.8 12.7 249 3.08 4 6 0.7 1.8 14.8 403 3.08
2 10 0.7 1.8 15.2 339 1.83 4 10 0.7 1.8 17.7 594 1.83
2 16 0.7 1.8 17.3 476 1.15 4 16 0.7 1.8 20.3 856 1.15
2 25 0.9 1.8 20.8 697 0.727 4 25 0.9 1.8 24.6 1278 0.727
2 35 0.9 1.8 23.2 910 0.524 4 35 0.9 1.8 27.9 1690 0.524
2 50 1.0 1.8 25.8 1177 0.387 4 35 sh 0.9 1.8 24.3 1639 0.524
2 70 1.1 1.8 30.1 1643 0.268 4 50 1.0 1.9 31.2 2244 0.387
2 95 1.1 1.9 34.1 2220 0.193 4 50 sh 1.0 1.9 26.7 2159 0.387
2 120 1.2 2.0 38.2 2798 0.153 4 70 1.1 2.0 36.4 3173 0.268
2 150 1.4 2.2 42.4 3415 0.124 4 70 sh 1.1 2.0 31.4 3080 0.268
2 185 1.6 2.3 47.2 4249 0.0991 4 95 1.1 2.1 41.3 4278 0.193
2 240 1.7 2.5 53.2 5530 0.0754 4 95 sh 1.1 2.1 35.7 4056 0.193
2 300 1.8 2.6 58.8 6853 0.0601 4 120 1.2 2.3 46.1 5471 0.153
2 400 2.0 2.9 66.2 8714 0.047 4 120 sh 1.2 2.3 39.7 5245 0.153
4 150 1.4 2.4 51.1 6690 0.124
4 150 sh 1.4 2.4 44.6 6262 0.124
Nom. Max. d.c. 4 185 1.6 2.6 57.1 8409 0.0991
Nom. Sheath Nom. Overall Approx. Cable
Product ID No. of Core Conductor Size Insulation Resistance
Thickness Diameter Weight 4 185 sh 1.6 2.6 49.7 7807 0.0991
Thickness at 20°C
4 240 1.7 2.8 64.4 10923 0.0754
mm² mm mm mm kg/km Ω/km
4 240 sh 1.7 2.8 56.0 10027 0.0754
3 1.5 0.7 1.8 10.1 138 12.1 4 300 1.8 3.0 71.3 13567 0.0601
3 2.5 0.7 1.8 11.0 177 7.41 4 300 sh 1.8 3.0 61.8 12326 0.0601
3 4 0.7 1.8 12.2 238 4.61 4 400 2.0 3.3 80.2 17268 0.047
3 6 0.7 1.8 13.5 312 3.08 4 400 sh 2.0 3.2 69.5 16291 0.047
3 10 0.7 1.8 16.2 460 1.83
sh: sector shaped conductor
3 16 0.7 1.8 18.5 656 1.15
3 25 0.9 1.8 22.3 976 0.727
3 35 0.9 1.8 25.0 1286 0.524
Nom. Insulation Nom. Sheath Nom. Overall Approx. Cable Max. d.c. Resistance
3 35 sh 0.9 1.8 20.2 1210 0.524 Product ID No. of Core Conductor Size
Thickness Thickness Diameter Weight at 20°C
3 50 1.0 1.8 27.8 1677 0.387
mm² mm mm mm kg/km Ω/km
3 50 sh 1.0 1.8 22.6 1594 0.387
3 70 1.1 1.9 32.7 2412 0.268 5 1.5 0.7 1.8 11.9 183 12.1
3 70 sh 1.1 1.9 26.4 2276 0.268 5 2.5 0.7 1.8 13.1 240 7.41
3 95 1.1 2.0 37.1 3259 0.193 5 4 0.7 1.8 14.6 331 4.61
3 95 sh 1.1 2.0 29.8 3000 0.193 5 6 0.7 1.8 16.2 442 3.08
3 120 1.2 2.1 41.3 4077 0.153 5 10 0.7 1.8 18.8 707 1.83
3 120 sh 1.2 2.1 33.0 3874 0.153 5 16 0.7 1.8 21.7 1028 1.15
3 150 1.4 2.3 46.0 5008 0.124 5 25 0.9 1.8 26.4 1549 0.727
3 150 sh 1.4 2.3 37.1 4637 0.124 5 35 0.9 1.8 29.8 2038 0.524
3 185 1.6 2.4 51.2 6265 0.0991 5 50 1.0 1.9 34.5 2774 0.387
3 185 sh 1.6 2.4 41.3 5767 0.0991 5 70 1.1 2.1 40.2 3891 0.268
14 15
CU/XLPE/PVC, XLPE insulated, PVC sheathed Cable, 0.6/1kV
2-, 3-, 4-, 5-, multicores Single Core CU/XLPE/PVC/AWA/PVC
Dimension & Electrical Data
XLPE insulated, PVC bedded, AWA armoured, PVC sheathed Cable 0.6/1kV
Nom. Insulation Nom. Sheath Nom. Overall Approx. Cable Max. d.c. Resistance
Product ID No. of Core Conductor Size
Thickness Thickness Diameter Weight at 20°C
1
mm² mm mm mm kg/km Ω/km
2 Component
7 1.5 0.7 1.8 12.8 226 12.1 1. Copper Conductor
7 2.5 0.7 1.8 14.6 302 7.41 2. XLPE Insulation
3
3. PVC Bedding
7 4.0 0.7 1.8 15.7 419 4.61 4. Aluminium Wire Armoured
4 5. PVC Sheath
12 1.5 0.7 1.8 16.2 351 12.1 4 3 2 1
5 5
12 2.5 0.7 1.8 18.1 478 7.41
12 4.0 0.7 1.8 20.3 676 4.61
* Optional
** Available upon request
16 17
CU/XLPE/PVC/SWA/PVC, XLPE insulated, PVC bedded, SWA armoured, PVC sheathed Cable, 0.6/1kV
2-, 3-, 4-, 5-, multicores
2-, 3-, 4-, 5-, Multicores, CU/XLPE/PVC/SWA/PVC
XLPE insulated, PVC bedded, SWA armoured, PVC sheathed Cable 0.6/1kV Dimension & Electrical Data
1 Nom. Nom. Dia. Nom. Nom. Approx. Max. d.c.
Conductor Nom. Sheath
Product ID No. of Core Insulation after Armour Overall Cable Resistance
Size Thickness
2 Component Thickness Bedding Wire Size Diameter Weight at 20°C
1. Copper Conductor
3 2. XLPE Insulation mm² mm mm mm mm mm kg/km Ω/km
3. PVC Bedding 3 1.5 0.7 8.6 0.9 1.8 14.0 365 12.1
4 4. Galvanised Steel
Wire Armoured 3 2.5 0.7 9.5 0.9 1. 8 14.9 425 7.41
5. PVC Sheath 3 4 0.7 10.7 0.9 1.8 16.1 515 4.61
5 5 4 3 2 1 3 6 0.7 12.0 0.9 1.8 17.4 616 3.08
3 10 0.7 14.6 1.25 1.8 20.7 936 1.83
3 16 0.7 16.9 1.25 1.8 23.0 1194 1.15
3 25 0.9 20.7 1.6 1.8 27.5 1793 0.727
Standards Applied Electrical Characteristics 3 35 0.9 23.4 1.6 1.8 30.2 2198 0.524
Design Guide: BS5467, IEC60502-1 Operating voltage, Uo/U: 600/1000V 3 35 sh 0.9 18.6 1.6 1.8 25.4 1950 0.524
Conductor : IEC60228, BS6360, BS EN 60228 Max. operating temperature: 90°C 3 50 1.0 26.2 1.6 1.9 33.2 2708 0.387
Flame Retardancy: IEC60332-1-2, IEC60332-3-24**, IEC60332-3-22** Final short circuit temperature: 250°C 3 50 sh 1.0 20.9 1.6 1.9 27.9 2431 0.387
Test voltage: 3.5kV for 5 minutes 3 70 1.1 31.3 2.0 2.0 39.3 3963 0.268
3 70 sh 1.1 25.0 2.0 2.1 33.2 3518 0.268
Installation Guide 3 95 1.1 35.4 2.0 2.2 43.8 5019 0.193
Min. bending radius (mm) : 10 x Cable Overall Diameter 3 95 sh 1.1 28.2 2.0 2.2 36.6 4398 0.193
Max. pulling tension (kgf) : 7 x No. of Core x Conductor Size 3 120 1.2 39.5 2.0 2.3 48.1 6000 0.153
3 120 sh 1.2 31.2 2.0 2.3 39.8 5419 0.153
Construction 3 150 1.4 44.2 2.5 2.5 54.2 7715 0.124
3 150 sh 1.4 35.2 2.5 2.5 45.2 6777 0.124
Conductor Plain annealed copper wire
3 185 1.6 49.2 2.5 2.6 59.4 9264 0.0991
Insulation An extruded layer of cross-linked polyethylene (XLPE) compound 3 185 sh 1.6 39.3 2.5 2.6 49.5 8149 0.0991
Core Identification Refer to Appendix F for details 3 240 1.7 55.8 2.5 2.8 66.4 11544 0.0754
3 240 sh 1.7 44.4 2.5 2.8 55.0 10136 0.0754
Assembly Cores cabled together, supplied with filler* and covered with polyester (PETP) binder tape*
3 300 1.8 61.6 2.5 3.0 72.6 13870 0.0601
Bedding An extruded layer of polyvinyl chloride (PVC) compound 3 300 sh 1.8 48.0 2.5 3.0 59.0 12019 0.0601
3 400 2.0 69.0 3.2 3.3 81.9 18039 0.047
Bedding Colour Black
3 400 sh 2.0 58.0 2.5 3.3 69.6 15650 0.047
Armour A single layer of steel wire armoured (SWA)
Outer Sheath An extruded layer of polyvinyl chloride (PVC) compound
Outer Sheath Colour Black Nom. Nom. Dia. Nom. Nom. Approx. Max. d.c. Resis-
Conductor Nom. Sheath
Product ID No. of Core Insulation after Armour Overall Cable tance
Size Thickness
Thickness Bedding Wire Size Diameter Weight at 20°C
Installation Guide
Min. bending radius (mm) : 6 x Cable Overall Diameter
Max. pulling tension (kgf) : 7 x No. of Core x Conductor Size
20 21
CU/XLPE/LSHF, XLPE insulated, LSHF sheathed Cable, 0.6/1kV
Single Core, 2-, 3-, 4-, 5-, Multicores CU/XLPE/LSHF 2-, 3-, 4-, 5-, Multicores
XLPE insulated, LSHF sheathed Cable 0.6/1kV
Dimension & Electrical Data
Nom. Max. d.c.
Nom. Sheath Nom. Overall Approx. Cable
Product ID No. of Core Conductor Size Insulation Resistance
Thickness Diameter Weight
Thickness at 20°C
Component
1 1. Copper Conductor mm² mm mm mm kg/km Ω/km
3 2 1 2. XLPE Insulation
2 1.5 0.7 1.8 9.6 122 12.1
2 3. LSHF Sheath
2 2.5 0.7 1.8 10.4 152 7.41
3 2 4 0.7 1.8 11.5 198 4.61
2 6 0.7 1.8 12.7 255 3.08
2 10 0.7 1.8 15.2 347 1.83
2 16 0.7 1.8 17.3 484 1.15
2 25 0.9 1.8 20.8 708 0.727
2 35 0.9 1.8 23.2 922 0.524
Standards Applied Electrical Characteristics 2 50 1.0 1.8 25.8 1191 0.387
Design Guide: IEC60502-1 Operating voltage, Uo/U: 600/1000V 2 70 1.1 1.8 30.1 1659 0.268
Conductor: IEC60228, BS6360, BS EN 60228 Max. operating temperature: 90°C
Flame Retardancy: IEC60332-1-2, IEC60332-3-22 Final short circuit temperature: 250°C 2 95 1.1 1.9 34.1 2240 0.193
Low Smoke & Reduced Toxidity: IEC60754-1/2, IEC61034-2 Test voltage: 3.5kV for 5 minutes 2 120 1.2 2.0 38.2 2821 0.153
2 150 1.4 2.2 42.4 3441 0.124
Installation Guide 2 185 1.6 2.3 47.2 4281 0.0991
Min. bending radius (mm) : 6 x Cable Overall Diameter (Single Core)
2 240 1.7 2.5 53.2 5570 0.0754
Min. bending radius (mm) : 8 x Cable Overall Diameter (2-, 3-, 4-, 5-, multicores)
Max. pulling tension (kgf) : 7 x No. of Core x Conductor Size 2 300 1.8 2.6 58.8 6899 0.0601
2 400 2.0 2.9 66.2 8771 0.047
Construction
Conductor Plain annealed copper wire
Insulation An extruded layer of cross-linked polyethylene (XLPE) compound Dimension & Electrical Data
Core Identification Refer to Appendix F for details except single core. Single core will come with natural colour insulation.
Nom. Max. d.c.
Nom. Sheath Nom. Overall Approx. Cable
Assembly*** Cores cabled together, supplied with filler* and covered with polyester (PETP) binder tape* Product ID No. of Core Conductor Size Insulation Resistance
Thickness Diameter Weight
Thickness at 20°C
Outer Sheath A low smoke halogen free (LSHF) compound
Outer Sheath Colour Black mm² mm mm mm kg/km Ω/km
3 1.5 0.7 1.8 10.1 143 12.1
Dimension & Electrical Data 3 2.5 0.7 1.8 11.0 183 7.41
3 4 0.7 1.8 12.2 243 4.61
Nom. Max. d.c.
Nom. Sheath Nom. Overall Approx. Cable 3 6 0.7 1.8 13.5 319 3.08
Product ID No. of Core Conductor Size Insulation Resistance at
Thickness Diameter Weight
Thickness 20°C 3 10 0.7 1.8 16.2 468 1.83
mm² mm mm mm kg/km Ω/km 3 16 0.7 1.8 18.5 666 1.15
1 1.5 0.7 1.4 5.8 49 12.1 3 25 0.9 1.8 22.3 988 0.727
1 2.5 0.7 1.4 6.2 64 7.41 3 35 0.9 1.8 25.0 1299 0.524
1 4 0.7 1.4 6.8 80 4.61 3 35 sh 0.9 1.8 20.2 1220 0.524
1 6 0.7 1.4 7.3 103 3.08 3 50 1.0 1.8 27.8 1691 0.387
1 10 0.7 1.4 8.5 153 1.83 3 50 sh 1.0 1.8 22.6 1606 0.387
1 16 0.7 1.4 9.5 214 1.15 3 70 1.1 1.9 32.7 2430 0.268
1 25 0.9 1.4 11.2 318 0.727 3 70 sh 1.1 1.9 26.4 2290 0.268
1 35 0.9 1.4 12.5 419 0.524 3 95 1.1 2.0 37.1 3281 0.193
1 50 1.0 1.4 13.7 543 0.387
3 95 sh 1.1 2.0 29.8 3017 0.193
1 70 1.1 1.4 15.7 757 0.268
3 120 1.2 2.1 41.3 4103 0.153
1 95 1.1 1.5 18.0 1025 0.193
3 120 sh 1.2 2.1 33.0 3891 0.153
1 120 1.2 1.5 19.7 1275 0.153
3 150 1.4 2.3 46.0 5040 0.124
1 150 1.4 1.6 21.9 1565 0.124
3 150 sh 1.4 2.3 37.1 4662 0.124
1 185 1.6 1.6 24.2 1943 0.0991
3 185 1.6 2.4 51.2 6302 0.0991
1 240 1.7 1.7 27.2 2524 0.0754
3 185 sh 1.6 2.4 41.3 5796 0.0991
1 300 1.8 1.8 29.9 3140 0.0601
1 400 2.0 1.9 33.6 4003 0.047 3 240 1.7 2.6 57.8 8187 0.0754
1 500 2.2 2.0 37.3 5000 0.0366 3 240 sh 1.7 2.6 46.4 7414 0.0754
1 630 2.4 2.2 42.0 6457 0.0283
1 800 2.6 2.4 47.2 8222 0.0221
1 1000 2.8 2.5 52.4 10295 0.0176
* Optional
*** Not available for single core cable
22 23
CU/XLPE/LSHF, XLPE insulated, LSHF sheathed Cable, 0.6/1kV CU/XLPE/LSHF, XLPE insulated, LSHF sheathed Cable, 0.6/1kV
2-, 3-, 4-, 5-, Multicores 2-, 3-, 4-, 5-, Multicores
Nom.
Nom. Sheath Nom. Overall Approx. Cable
Max. d.c.
Product ID No. of Core Conductor Size Insulation Resistance
Thickness Diameter Weight
Thickness at 20°C
24 25
Single Core CU/XLPE/LSHF/AWA/LSHF 2-, 3-, 4-, 5-, Multicores, CU/XLPE/LSHF/SWA/LSHF
XLPE insulated, LSHF bedded, AWA armoured, LSHF sheathed Cable 0.6/1kV XLPE insulated, LSHF bedded, SWA armoured, LSHF sheathed Cable 0.6/1kV
1
2 Component
1 1. Copper Conductor
3 2. XLPE Insulation
2 Component 3. LSHF Bedding
1. Copper Conductor
4 4. Galvanised Steel
3 Wire Armoured
2. XLPE Insulation 5. LSHF Sheath
3. LSHF Bedding 5 5 4 3 2 1
4 4. Aluminium Wire Armoured
5. LSHF Sheath
5 5 4 3 2 1
Standards Applied Electrical Characteristics
Design Guide: BS6724, IEC60502-1 Operating voltage, Uo/U: 600/1000V
Conductor: IEC60228, BS6360, BS EN 60228 Max. operating temperature: 90°C
Flame Retardancy: IEC60332-1-2, IEC60332-3-22 Final short circuit temperature: 250°C
Standards Applied Electrical Characteristics Low Smoke & Reduced Toxidity : IEC60754-1/2, IEC61034-2 Test voltage: 3.5kV for 5 minutes
Design Guide: BS6724, IEC60502-1 Operating voltage, Uo/U : 600/1000V
Conductor: IEC60228, BS6360, BS EN 60228 Max. operating temperature : 90°C
Flame Retardancy: IEC60332-1-2, IEC60332-3-22 Final short circuit temperature : 250°C Installation Guide
Low Smoke & Reduced Toxidity : IEC60754-1/2, IEC61034-2 Test voltage : 3.5kV for 5 minutes
Min. bending radius (mm) : 10 x Cable Overall Diameter
Max. pulling tension (kgf) : 7 x No. of Core x Conductor Size
Installation Guide
Min. bending radius (mm): 10 x Cable Overall Diameter
Max. pulling tension (kgf): 7 x No. of Core x Conductor Size
Construction
Conductor Plain annealed copper wire
Construction Insulation An extruded layer of cross-linked polyethylene (XLPE) compound
Conductor Plain annealed copper wire Core Identification Refer to Appendix F for details
Insulation An extruded layer of cross-linked polyethylene (XLPE) compound Assembly Cores cabled together, supplied with filler* and covered with polyester (PETP) binder tape*
Core Identification Natural Bedding An extruded layer of low smoke halogen free (LSHF) compound
Bedding An extruded layer of low smoke halogen free (LSHF) compound Bedding Colour Black
Bedding Colour Black Armour A single layer of galvanised steel wire armour (SWA)
Armour A single layer of aluminium wire armoured (AWA) Outer Sheath An extruded layer of low smoke halogen free (LSHF) compound
Outer Sheath An extruded layer of low smoke halogen free (LSHF) compound Outer Sheath Colour Black
Outer Sheath Colour Black
1 70 1.1 14.9 1.25 1.8 21.0 986 0.268 2 4 0.7 10.0 0.9 1.8 15.4 410 4.61
2 6 0.7 11.1 0.9 1.8 16.5 493 3.08
1 95 1.1 16.8 1.25 1.8 22.9 1279 0.193
2 10 0.7 13.6 1.25 1.8 19.7 749 1.83
1 120 1.2 18.6 1.6 1.8 25.4 1552 0.153
2 16 0.7 15.7 1.25 1.8 21.8 943 1.15
1 150 1.4 20.6 1.6 1.8 27.4 1959 0.124
2 25 0.9 19.2 1.6 1.8 26.0 1268 0.727
1 185 1.6 22.9 1.6 1.8 29.7 2396 0.0991
2 35 0.9 21.6 1.6 1.8 28.4 1761 0.524
1 240 1.7 25.7 1.6 1.9 32.7 3010 0.0754
2 50 1.0 24.2 1.6 1.8 31.0 2141 0.387
1 300 1.8 28.3 1.6 2.0 35.5 3674 0.0601 2 70 1.1 28.5 1.6 2.0 35.7 2781 0.268
1 400 2.0 32.1 2.0 2.1 40.3 4725 0.047 2 95 1.1 32.7 2.0 2.1 40.9 3868 0.193
1 500 2.2 35.6 2.0 2.2 44.0 5817 0.0366 2 120 1.2 36.4 2.0 2.2 44.8 4593 0.153
1 630 2.4 40.0 2.0 2.3 48.6 7354 0.0283 2 150 1.4 40.3 2.0 2.3 48.9 5408 0.124
1 800 2.6 45.1 2.5 2.5 55.1 9432 0.0221 2 185 1.6 45.3 2.5 2.5 55.3 7039 0.0991
2 240 1.7 51.0 2.5 2.7 61.4 8640 0.0754
1 1000 2.8 50.1 2.5 2.7 60.5 11613 0.0176
2 300 1.8 56.8 2.5 2.8 67.4 10322 0.0601
* Optional
2 400 2.0 63.6 2.5 3.1 74.8 12599 0.047
* Optional
** Available upon request
26 27
CU/XLPE/LSHF/SWA/LSHF, XLPE insulated, LSHF bedded, SWA armoured, LSHF sheathed CU/XLPE/LSHF/SWA/LSHF, XLPE insulated, LSHF bedded, SWA armoured, LSHF
Cable, 0.6/1kV sheathed Cable, 0.6/1kV
2-, 3-, 4-, 5-, Multicores 2-, 3-, 4-, 5-, Multicores
Dimension & Electrical Data Dimension & Electrical Data
Nom. Nom. Nom. Nom. Approx. Max. d.c. Nom. Nom. Nom. Nom. Approx. Max. d.c.
Conductor Nom. Sheath Conductor Nom. Sheath
Product ID No. of Core Insulation Dia. after Armour Overall Cable Resistance Product ID No. of Core Insulation Dia. after Armour Overall Cable Resistance
Size Thickness Size Thickness
Thickness Bedding Wire Size Diameter Weight at 20°C Thickness Bedding Wire Size Diameter Weight at 20°C
4 95 sh 1.1 33.8 2.0 2.3 42.4 5711 0.193
4 120 1.2 44.3 2.5 2.5 54.3 8112 0.153
4 120 sh 1.2 37.8 2.5 2.5 47.8 7483 0.153
4 150 1.4 49.1 2.5 2.6 59.3 9603 0.124
4 150 sh 1.4 42.6 2.5 2.6 52.8 8741 0.124
4 185 1.6 54.7 2.5 2.8 65.3 11620 0.0991
4 185 sh 1.6 47.3 2.5 2.8 57.9 10568 0.0991
4 240 1.7 62.0 2.5 3.0 73.0 14524 0.0754
4 240 sh 1.7 53.6 2.5 3.0 64.6 13142 0.0754
4 300 1.8 68.5 2.5 3.2 79.9 17609 0.0601
4 300 sh 1.8 59.0 2.5 3.2 70.4 15768 0.0601
4 400 2.0 77.2 3.2 3.5 90.5 23072 0.047
4 400 sh 2.0 66.9 3.2 3.5 80.2 21145 0.047
28 29
Appendix A - Materials Introduction
Insulation
In the manufacture of electric cables, the two most important factors to be considered are safety and
reliability. The materials that are selected must be stable, reliable, durable, able to withstand the
environment and safe to use. Materials used as insulation for the cables must meet the following;
1. Providing safe insulation of the line conductors with minimum loss in electrical energy.
2. Exhibiting good stable mechanical properties under normal conditions.
3. Possessing consistent electrical and mechanical properties over long period of use and
over wide temperature ranges.
4. Exhibiting inert chemical properties which make it resistant to most chemicals.
Extruded insulations used for wire and cable can be classified into two categories, namely Thermoplastic
materials and Thermoset materials.
Thermoplastic materials tend to lose their form upon subsequent heating, while thermosetting materials
tend to maintain their form. Generally, cables produced with thermoset materials can operate at higher
temperature than cables produced with thermoplastic materials. The insulation range includes the below:-
Thermoplastic
Technical Information a) Polyvinyl Chloride (PVC)
PVC has high electrical strength and good insulation resistance. It
Appendix A : Materials Introduction is inherently tough and resistant to flame, moisture and abrasion.
Resistance to ozone, acids, alkalies, alcohols, and most solvents
Appendix B : Selection of Cross Sectional Area of Conductor is also adequate. Compounding can impart resistance to oils and
Appendix C : Current Rating and Voltage Drop Table (Unarmoured Cable) gasoline. Based on the specific formulation, temperature ratings
range from 60°C to 105°C. PVC with 70°C temperature rating is most commonly used.
Appendix D : Current Rating and Voltage Drop Table (Armoured Cable)
Appendix E : Short Circuit Ratings PVC materials are known to emit smoke and form hydrochloride acid (highly toxicated and corrossive
chemical) when come in contact with water. Frequently in applications where smoke is a major hazard
Appendix F : Cables Drum Handling and Storage Procedure (notably in tunnels and rapid transit areas) PVC-free cable insulation such as low smoke halogen free
Appendix G : Identification of Cores in Cables (LSHF, XLEVA) is preferred.
b) Polyethylene (PE)
Research has shown that PE exhibits excellent electrical insulating
properties, stable mechanical characteristic and resistant to
chemicals and moisture.
30 31
Materials Introduction Materials Introduction
Insulation Table A1: Table of comparison for Insulation Materials
Insulation Materials
PROPERTY Unit
PVC PE XLPE XLEVAA
Thermoset Chemical name Polyvinyl Chloride Polyethylene Cross-linked Cross-
Polyethylene linked
c) Cross-linked Polythylene (XLPE) Polyolefin
Max. Rated Normal °C 70 70 90 110B
The thermoplastic nature of the PE can be converted into a thermally Temperature
Short circuit °C 160 200 250 250
stable thermosetting compound by the process of cross-linking. In
the process of cross-linking perpendicular chemical bonds are formed
Density 1.2 - 1.4 0.92 - 0.94 0.92 - 0.95 1.5 - 1.55
between parallel chains of the PE molecules. The parallel loose two-
dimensional molecular structure is converted into a cellular three-
Volume resistivity Ohm-cm 10E 15 10E 16 10E 16 10E 14
dimensional polymeric structure.
Dielectric constant 3-5 2.0 - 2.3 2.3 - 2.5 4-6
All these properties have resulted in the rapid growth of preference of XLPE cables in the electrical
industry. Solvent resistance --- ++ + +
--- Poor
+ Fair
++ Good
The resultant XLEVA compound exhibits a more durable and excellent +++ Excellent
insulating material while maintaining its flexibility. Based on the
specific formulation, XLEVA compound can withstand a temperature
rating up to 110°C and display an excellent flame retardant capability.
It contains no halogen and has a temperature index of more than
250°C which is currently the highest among most insulation materials.
32 33
Materials Introduction Appendix B - Selection Of Cross-Sectional Area Of
Bedding and Sheathing Conductor
Jacket, also called sheaths, serve several purposes. For examples, they provide mechanical, thermal,
chemical, and environmental protection to the insulated conductors they enclose. They may act as In order to choose the right power cable, one has to consider:
electrical insulation when used over shields or armour. They ease installation and routing concerns by • the current • the ambient temperature
enclosing multiple insulated conductors. • the voltage drop • the frequency and harmonic current
• the short circuit rating • maximum safe length at short circuit
Commonly used jacket materials for low voltage power cables include extrusions of Polyvinyl Chloride • the installation methods
(PVC), High Density Polyethylene (HDPE), and Low Smoke Halogen Free (LSHF) materials. These
Current Rating
materials are applied using plastic extrusion lines that heat the compound to melting point and form it
over the core. The material is then cooled in water trough and wound onto a reel. When electric current flows through the conductor of a cable, the electrical resistance of the conductor
generates heat. When a temperature greater than that allowed is reached by the cable due to heat
Table A2: Table of comparison for Bedding/Sheathing Materials generation, a larger conductor size (with lower electrical resistance) has to be selected. Other important
Bedding / Sheathing Materials considerations are methods of installation of the cable and ambient temperature. Calculation which
PROPERTY
PVC PE LSHF takes into account all criteria are described in IEC 60287 and are rather complex. In general, preferences is
Chemical name Polyvinyl Chloride High Density Low Smoke given to standard current rating tables which are issued by national standardization bureaus.
Polyethylene Halogen Free
The current rating given in Table 4 to 14 are based on the following standard conditions of the
Density 1.35 - 1.5 0.94 - 0.95 1.4 - 1.6
installation.
Halogen Content >20% <0.5% <0.5% 1. Maximum operating temperature of conductor = 90oC
2. Ambient air temperature = 30oC
Halogen Free No Yes Yes
3. Ground temperature = 15oC
Limiting Oxygen Index (LOI) >22 ≤22 >30 4. Soil thermal resistivity = 1.2oC m/w
5. Depth of laying (For cable laid direct in the ground) = 0.5m
Smoke Generation Dark and dense Less Smoke Least Smoke
Resistance to heat deformation --- + +++ According to CP5:1998 regulation 525-01-01, it is stipulated that the total voltage drop for any particular
Note: cable run must be such that the voltage drop in the circuit of which the cable forms a part does not
Refer to normal PVC that comply with IEC60332-1-2. Higher grade PVC available upon request. exceed 4% of the nominal voltage of the supply.
Higher grade of PVC can achieve higher LOI reading.
--- Poor, + Fair, ++ Good, +++ Excellent
34 35
Selection of Cable based on Voltage Drop and Current using Tables Appendix C - Current Ratings And Voltage Drop Table
Since the actual power factor of the load is usually not known, the most practical approach to the (Unarmoured Cable)
question of the voltage drop is to assume the worst conditions, i.e. power factor equal to one and the
conductor is at maximum operating temperature. The voltage drop values given in the tables are based Cables installed in free air
on these assumptions.
Plain annealed stranded conductor, mica tape lapping, XLPE insulated, LSF cables, 600/1000V
The values of the voltage drop (Vd) are tabulated for a current of one Ampere for a 1 metre run, the value
of voltage drop needs to be multiplied by the length of the run, in metre, and by the current, in Ampere Conditions of installation:
that the cables are to carry. Ambient temperature : 30oC
Maximum Conductor temperature : 90oC
V=Vd x l x L
Table 1
INSTALLATION METHODS
Where V = Voltage
Single Core Cable Multicore Cable
Vd = Approximate Voltage drop/Ampere/metre
Nominal 2-Single Cores 2-Single Cores 3-Single Cores 3-Single Cores 3-Single Cores 2 Loaded 3 Loaded
I = Current in Ampere per phase area of Touching Touching Trefoil Spaced Horizontal Spaced Vertical Conductor Conductor
conductor
L = Route length in metres mm2 A B C D E F G
d1 d1 d1 d1 d1 d1 d1
Example: d1 d2
Given that the supply voltage is 415V, 3 phase 50Hz and that the cable used is a 4C Cu/mica/XLPE/
d2
SWA/PVC fire resistant cable. Required cable is to be installed in ground and to carry a 250 Amp load per
phase over a route length of 100m. Cable installation is to be in compliance with CP5: 1998 Regulation 1.5 27 23 22 27 23 26 23
522.08 regulation. 2.5 35 31 30 37 31 36 32
4 49 42 40 52 44 49 42
Select from Table 10 (pg 43) such that
V=Vd x l x L the Vd value is equal to, or less than the 6 63 54 52 67 55 63 54
calculated 0.66mV, at the same time 10 88 76 73 95 76 86 75
ensuring that it will carry the current. It will
16 137 100 96 150 112 115 100
Maximum permissible voltage drop be seen that this value is 0.61 giving a cable
size of 70mm2. 25 161 141 135 182 161 149 127
Vmax = 4% of 415V
35 200 176 169 226 201 185 157
Vmax = 16.6V
50 242 215 207 275 246 225 192
70 310 279 268 353 318 289 246
Voltage drop/ampere/metre 95 377 341 328 430 389 352 298
Vmax 16.6V 120 437 399 382 500 454 410 346
Vd = = = 0.66mV
lxL 250 X 100 150 504 462 443 577 527 473 399
185 575 531 509 661 605 542 456
240 679 631 604 781 719 641 538
300 783 731 699 902 833 741 620
400 940 880 839 1085 1008 - -
500 1083 1006 958 1253 1169 - -
630 1254 1117 1077 1454 1362 - -
800 1460 1262 1152 1696 1595 - -
1000 1683 1432 1240 1958 1847 - -
36 37
Correction factors for groups of more than one circuit of single core cables Correction factors for groups of more than one multicore cable
To be used in conjunction with current ratings in Table 4 for single core cables in free air for installation To be used in conjunction with current ratings in Table 1 for multicore cables in free air for installation
methods A to G. methods F to G.
Table 3
Table 2
Number of cables
Number of three-phase circuits (Note 4) Installation method Number of trays
Installation method Use as a multiplier to 1 2 3 4 6 9
(See Note 1) Numbers of 1 2 3 rating for
trays Touching
20mm
1 0.95 0.85 0.80 0.75 0.70 0.70
Touching 2 0.95 0.85 0.75 0.75 0.70 0.65
1 0.95 0.90 0.85
20mm
Unperforated trays 3 0.95 0.85 0.75 0.70 0.65 0.60
H 2 0.92 0.85 0.80
(Note 2) 3 0.90 0.80 0.75 Unperforated trays
Three cables in M
(Note 2) de
Touching horizontal formation Spaced
1 0.95 0.90 0.85 1 1.00 0.95 0.95 0.95 0.90 -
20mm
20mm
Perforated trays J 2 0.95 0.85 0.80 2 0.95 0.95 0.90 0.90 0.85 -
(Note 2) 3 0.90 0.85 0.80 3 0.95 0.95 0.90 0.90 0.85 -
Touching
Touching
20mm
Vertical perforated trays 1 0.95 0.85 - Three cables in 1 1.00 0.90 0.80 0.80 0.75 0.75
K 2 1.00 0.85 0.80 0.75 0.75 0.70
(Note 3) 2 0.90 0.85 - vertical formation
3 1.00 0.85 0.80 0.75 0.70 0.65
Perforated trays N
(Note 2) de Spaced
Touching
Ladder supports, 1 1.00 0.95 0.95 1 1.00 1.00 100 0.95 0.90 -
Three cables in
20mm
20mm
cleats, etc L 2 0.95 0.90 0.90 2 1.00 1.00 0.95 0.90 0.85 -
(Note 2) 3 0.95 0.90 0.85 horizontal formation
A
3 1.00 1.00 0.95 0.90 0.85 -
Perforated trays O
J 2 0.95 0.95 0.90 (Note 3) Spaced
(Note 2) 3 0.95 0.90 0.85
1 1.00 0.90 0.90 0.90 0.85 -
de
Three cables in 2 1.00 0.90 0.90 0.85 0.85 -
trefoil formation
Vertical perforated trays 1 1.00 0.90 0.90
K 2de Touching
(Note 3) 2 1.00 0.90 0.85 1 1.00 0.85 0.80 0.80 0.80 0.80
20mm
de 2 1.00 0.85 0.80 0.80 0.75 0.75
3 1.00 0.85 0.80 0.75 0.75 0.70
Ladder supports
Ladder supports, 2de de 1 1.00 1.00 1.00 cleats, etc. P Spaced
20mm
de
cleats, etc L 2 0.95 0.95 0.95 (Note 2) 1 1.00 1.00 1.00 1.00 1.00 -
20mm
(Note 2) 3 0.95 0.95 0.90 2 1.00 1.00 1.00 0.95 0.95 -
3 1.00 1.00 0.95 0.95 0.95 -
Notes:
1. Factors are given for single layers of cables (for trefoil groups) as shown in the tables and DO NOT apply when cables are installed in more than one layer touching
Notes:
each other. Values for such installations may be significantly lower and must be determined by an appropriate method.
1. Factors apply to single layer groups of cables as shown above and do NOT apply when cables are installed in more than one layer touching each other.
2. Values are given for a vertical spacing between trays of 300mm. For closer spacing the factors should be reduced.
Values for such installations may be significantly lower and must be determined by an appropriate method.
3. Values are given for a horizontal spacing between trays of 225mm with tray mounted back to back. For closer spacing the factors should be reduced.
2. Values are given for a vertical spacing between trays of 300mm . For closer vertical spacing the factors should be reduced.
4. For circuits having more than one cable in parallel per phase, each set of three conductors should be considered as a circuit for the purposes of this table.
3. Values are given for a horizontal spacing between trays of 225mm with trays mounted back to back. For closer spacing the factors should be reduced.
38 39
Cables in conduit and trunking, and bunched cables on a surface Correction factors for cables in conduit and trunking, and bunched cables
on a surface
Plain annealed stranded conductor, mica tape lapping, XLPE insulated, LSF cables, 600/1000V
Correction factors for groups of more than one circuit or more then one multicore cable.
Conditions of Installation: To be used in conjunction with ratings for cables in Table 4.
Ambient temperature : 30oC
Maximum conductor temperature : 90oC Table 5
Correction factors
Table 4 Arrangement
Item Number of circuits or multicore cables
Insulated conductors in Insulated conductors in Multicore cable on a wall of Cables
R S T 1 2 3 4 5 6 7 8 9 10 12 14 16 18 20
1 Bunched on a surface or
2 loaded 3 loaded 2 loaded 3 loaded 2 loaded 3 loaded enclosed in conduit 1.00 0.80 0.70 0.65 0.60 0.55 0.55 0.50 0.50 0.50 0.45 0.45 0.40 0.40 0.40
Conductor Conductor Conductor Conductor Conductor Conductor or trunking
Nominal 2
Single-layer Touching 1.00 0.85 0.80 0.75 0.75 0.70 0.70 0.70 0.70 0.70 0.70 0.70 0.65 0.65 0.65
area of 3 wall or floor Spaced 1.00 0.95 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
conductor
4 Single-layer Touching 0.95 0.80 0.70 0.70 0.65 0.65 0.65 0.60 0.60 0.60 0.60 0.60 0.55 0.55 0.55
under ceiling
5 Spaced 0.95 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85
Notes:
1. These factors are applicable to uniform groups of cables, equally loaded.
2. Where horizontal clearance between adjacent cables exceeds twice their overall diameter,
no reduction factor need be applied.
3. “Spaced” cables means a clearance between adjacent surfaces of one cable diameter.
4. The same correction factors are applied to:
mm2 Amp Amp Amp - groups of two or three single-core cables;
- multicore cables.
1.5 19 17 23 20 24 22
5. If a system consists of both two and three core cables, the total number of cables is taken as the number of circuits,
2.5 26 23 31 27 33 30 and the corresponding correction factor is applied to the tables for two loaded conductors for the two-core cables,
and to the tables for three loaded conductors for the three-core cables.
4 35 31 42 37 45 40 6. If a group consists of n loaded single-core cables it may either be considered as n/2 circcuits of two loaded
6 45 40 54 48 58 52 conductors or n/3 circuits of three loaded conductors.
10 61 54 74 66 80 71
16 81 73 100 89 107 96
25 106 95 133 117 138 119 Correction factors for ambient air temperature other than 30oC
35 131 117 164 144 171 147
50 158 141 198 175 210 179 Table 6
70 200 179 254 222 269 229
Ambient temperature 10 15 20 25 35 40 45 50 55 60 65 70 75 80
95 241 216 306 269 328 278 0
C
120 278 249 354 312 382 322 Correction factors 1.15 1.12 1.08 1.04 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41
150 318 285 - - 441 371
185 362 324 - - 506 424
240 424 380 - - 599 500
300 486 435 - - 693 576
400 579 519 - - 860 692
500 664 595 - - 994 797
630 765 685 - - 1155 923
800 885 792 - - 1349 1074
1000 1014 908 - - 1560 1237
40 41
Voltage drop table (Unarmoured Cables) Appendix D - Current Ratings And Voltage Drop Table
Voltage drop for single core cables per amp per metre
(Armoured Cable)
Table 7
Nominal For
Cables laid direct in ground
For For For
area of D D
150 0.35 0.32 0.30 For group correction factors, please refer to Table 12. Correction factors for ground temperatures other than 15oC, refer to Table 14
185 0.29 0.25 0.25
240 0.24 0.19 0.21 Conditions of installation (for Table 9 & 10):
Ground temperature : 15oC
300 0.21 0.15 0.19 Depth of laying : 0.5m
Soil thermal resistivity : 1.2oC m/w
Maximum conductor operating temperature at rated current : 90oC
Note:
Ratings given are for single circuits installed thermally independent of any other heat source.
42 43
Cables run in single way ducts Correction factors for more than one circuit, cables laid directly in the ground
Plain annealed stranded copper conductor, mica tape lapping, XLPE insulated, armoured, LSF cables, Table 12
600/1000V Cable to cables clearance (a) Single-core cables
Number Nil a a
Table 11 of One
(cables
circuits cable 0.215m 0.25m 0.5m
Nominal Single Core Two-Core Three or Four Core touch-
diameter
area of ing)
Two cables Three cables
conductor 2 0.75 0.80 0.85 0.90 0.90
ducts touching ducts touching,trefoil
3 0.65 0.70 0.15 0.80 0.85
Current Approx volt Current Approx volt Current Approx volt Current Approx volt
rating drop rating drop rating drop rating drop
per Amp per Amp per Amp per Amp
4 0.60 0.60 0.70 0.75 0.80 Multicore cables
per metre per metre per metre per metre 5 0.55 0.55 0.65 0.70 0.80
mm2 Amp mV Amp mV Amp mV Amp mV 6 0.50 0.55 0.60 0.70 0.80
16 - - - - 115 2.90 94 2.6 a a
25 - - - - 145 1.90 125 1.6
35 - - - - 175 1.30 150 1.2 Correction factors for more than one circuit,
50 255 1.10 235 0.93 210 1.00 175 0.87
70 310 0.80 280 0.70 260 0.70 215 0.61 cables laid directly in ducts in the ground
95 365 0.65 330 0.56 310 0.52 260 0.45
120 410 0.55 370 0.48 355 0.42 300 0.36 A - Multicore cables in single-way ducts
150 445 0.50 405 0.43 400 0.35 335 0.30
185 485 0.45 440 0.39 455 0.29 380 0.25 Table 13 Multicore cables
240 550 0.40 500 0.35 520 0.24 440 0.21
Duct to duct clearance (a)
300 610 0.37 550 0.32 590 0.21 495 0.19
400 640 0.35 580 0.30 - - - -
Number Nil
of cables a
500 690 0.33 620 0.28 - - - - (ducts 0.25m 0.5m 1.0m
630 750 0.30 670 0.26 - - - - touching)
800 828 0.28 735 0.24 - - - - 2 0.85 0.90 0.95 0.95
1000 919 0.26 811 0.22 - - - - 3 0.75 0.85 0.90 0.95
4 0.70 0.80 0.85 0.90
For group correction factors, please refer to Table 13 5 0.65 0.80 0.85 0.90
Correction factors for ground temperatures other than 15oC, refer to Table 14 6 0.60 0.80 0.80 0.90
Conditions of installation:
Ground temperature : 15oC B - Single-core cables in single-way ducts
Depth of laying : 0.5m Single-core cables
Soil thermal resistivity : 1.2oC m/w
Maximum conductor operating temperature at rated current : 90oC Number of Duct to duct clearance (a) a
Ambient air temperature : 25oC single-core
circuits Nil
Note: of two (ducts 0.25m 0.5m 1.0m
* Single core cables are aluminium wire armoured for a.c. systems. or three touching)
Ratings given are for single circuits installed thermally independent of any other heat source. cables a
2 0.80 0.90 0.90 0.95
3 0.70 0.80 0.85 0.90
4 0.65 0.75 0.80 0.90
5 0.60 0.70 0.80 0.90
6 0.60 0.70 0.80 0.90
Table 14
Ground
temperature 10 15 20 25 30 35 40 45 50
o
C
Correction 1.03 1.00 0.97 0.93 0.89 0.86 0.82 0.76 0.72
factor
44 45
TECHNICAL INFORMATION Appendix E - Short Circuit Ratings
Another important factor for the determination of the conductor size is the maximum allowable current
during a short circuit when the maximum allowable conductor temperature is higher than during normal
Maximum conductor resistance operation.
Table 15 The maximum permissible short circuit current of XLPE cables up to 1 kV with copper conductors can be
Conductor for fixed calculated with following formula:
Cross Section Area
wiring Class 1 (solid) S
(S) 1k =
Class 2 (stranded) K
mm2 t
ohm/km at 20oC
0.50 36.0 Where 1k = Maximum permissible short circuit current in Ampere
0.75 24.5
1.00 18.1
S = Conductor area in mm2
1.50 12.1 t = Duration of short circuit process in seconds. Maximum value for t = 5 seconds
2.50 7.41 K = Constant of 143 for copper conductors and temperature rising 90 degree C to 250 degree C
4 4.61
6 3.08
10 1.83 Copper Conductors
16 1.15
The values of fault current given in the graph are based on the cable being fully loaded at the start of the short circuit
25 0.727
(conductor temperature 90oC) and a final conductor temperature of 250oC, and it should be ensured that the accessories
35 0.524
associated with the cable are also capable of operation at these values of fault current.
50 0.387
70 0.268 100
90
95 0.193
120 0.153 80
150 0.124 70
185 0.0991
60
240 0.0754
300 0.0601 630mm2
50
400 0.0470
500 0.0366
40 500mm2
630 0.0283
Current in kiloamperes
800 0.0221
1000 0.0176 400mm2
30
300mm2
20 240mm2
Electrical Characteristics
185mm2
Table 16
150mm2
Conductor Resistance
Temperature Correction Factors 120mm2
10
TempoC Factor TempoC Factor 9
10 0.961 25 1.020 8
95mm2
11 0.965 30 1.039 7
12 0.969 35 1.059 6
70mm2
13 0.972 40 1.079
5
14 0.976 45 1.098
15 0.980 50 1.118 4
16 0.984 55 1.138 50mm2
17 0.988 60 1.157
3
18 0.992 65 1.177 35mm2
19 0.996 70 1.196
20 1.000 75 1.216 25mm2
2
21 1.004 80 1.236
22 1.008 80 1.255
23 1.012 90 1.275
24 1.016 16mm2
1
0.1 0.2 0.3 0.4 0.5 0.6 0.8 1.0 2.0 3.0
Direction of spooling
Prysmian
Roll In direction from Group
Factory
48 49
Handling Storage
• When using Forklift Truck to handle the cable drums, it must be fork in the direction of the drum front • Cables coiled in the drum must have at least min. 2” gap away from the edge of the flange.
view or across the both flanges. (see picture 1a) • Black PVC sheet to be used for wrapping over the cables before storage in the open.
• Improper handling of cables drum by forking from drum side view will cause serious damage to the • Cables drums must be stored in an upright position (see Picture 3a)
cables. (see picture 1b)
Picture 3a Picture 3b
This picture show the Cables Drum in up right This picture show the Cables Drum in lay postion is
Picture 1a postion is the correct method of storing incorrect method of storing
Drum front view
Drum side view
Picture 1b
Cable sag
Drum side view
Prysmian
Group
Prysmian
Prysmian
min. 2” gap from the drum
Wood flange edge
Choke
• Wood choke should be placed under the flanges to prevent accidental rolling. (see picture 2)
• Cables drums must be stored flanges against flange. (see picture 3a)
• Using Hoist to lift the cables drums, the correct method require a metal rode to go through the center • If improper storage, cables will be damage if flange hit against. (see Picture 3b)
hole and a certified sling belt or wire rope. (see picture 2a)
• Improper Hoisting, using two or single sling belt or wire rope over the wood battens will cause damage
to woodbattens resulted damaging the cables.(see picture 2b)
Picture 2a Picture 2b
Hoist Hook
Flange
1 x Sling Belt to
Hoist Hook or Wire Ropes Flange
Prysmian Causes
Group cable
2 x Sling Belt damage
or Wire Ropes
Use wood choke
Steel Pipe
Picture 4a Picture 4b
50 51
A Glimpse of Our Project Reference ASEAN
Australia CAPITAL SQUARE KL North South Line Extension (Mechanical), C1563
L L L3 L3 New Building For Brunei Muara District SGL CARBON BANTING Bangchat Combine Heat & Power Plant
Bangkok Bank Building
Radio TV Brunei Shell offshore Platform B11, F6, F26
N N N N RTB (Radio TV Brunei) SMART Tunnel Project Bangkok Metropolitan Administration
Bangkok Transit Systems (BTS)
SCOT Rejuvenisation SPMY - HK SL SUNPOWER
Shell Brunei Refinery SUBANG AVENUE Bangsui Waterteastment
Tutong Street Lighting SUNPOWER PROJECT SITE (SPMY-HK 8L) Baromchonranee Tunnel Road
For any new electrical installation that involved extension from existing wiring system, BS7671 has been Various Schools Tawakai Hospital BNC
Teluk Salut, Ranhill Power Chulalongkorn University
modified to align with these cable core colours where suitable marking/ labelling method eg. colour Hong Kong
Tenaga National Berhad SCADA System Expressway Thailand Authority
Glow Power 115 MW CFB#3
tapes, sleeves, discs, or by alphanumerics (letters and/or numbers) is allowed. See below figure:- Caribbean Coast
TNB
TNB SCADA System Honda New Factory - 3
Disneyland UOA Holding Berhad - 2 Block Condominium at Jasmine Telecom
Existing New Elements Shopping Center KLT - 8
Bangsar South
Enterprise Square Five Mega Box Mall
L L Four Seasons Hotel
UTUSAN MALAYSIA
Wisma Lee Rubber
Love Beach Hotal
LP Hospitality
N N Grand Promenade WISMA PERSEKUTUAN AT MITC MELAKA Mahidol University (Dentistry Department)
Harbor Front Horizon WTP Maneeya
Label & Brown sleeze shall be Hong Kong International Airport Mass Rapid Transit System (MTRA –Blue Line)
Hong Kong Science Park MEA 230 KV Transmission Tunnel
provided at interface. Hong Kong-Shenzhen Western Corridor Bridge Singapore MEA 230kV Underground Transmission Line Between
ICAC Headquarter
Cable cores colour code Kowloon, Tsingyi, lai King, Olympic, Tsuen Wan West MRT
A’Posh Bizhub
Alstom Metropolis C830
Bangkapi and Chidlom
MEA PM2-0030-WBA Modification Of 69 Kv Circuit
Function Alpha-numeric Existing Core Colour New Harmonized Core Colour Station Anchor Handling Tug/Supply AHTS – Ice Class Breaker 9 Substations.
Movie City Breadtalk Building Novetel Airport Hotel
Protective conductor Green/ Yellow Green/ Yellow One Beacon Hill CAAS Terminal 3 CCTV Pre Clinic Siriraj Hospital
Functional earthing conductor Cream Cream Pok Oi Hosiptal Changi Airport T3 Prin Narathiwas, Prin Ratchaprarob
Taiwan, Kam Sheung, Fotan MRT stations Changi International Airport PTT ESP & GSP#6 Plant
AC Power Circuit Changi PMS Electrical Works PTT Phenol Plant
- Phase L Red Brown Changi Prison CCTV Puric Latic Acid Refinery Plant
Indonesia
Changi Water Reclamation Plant Ramkamkhang University
- Neutral N Black Blue Australia Embassy Circle Line Stage 3 - Mechancial Ricoh (RMT) New Factory
Three Phase Circuit British Embassy Circle Line Stage 3,4,5 – Electrical Samart Ministry of Defense Southern
Ciputra World Common Service Tunnel - Marina Provinces CCTV
- Phase 1 L1 Red Brown DATA Centre at Surabaya Credit Suisse Datacenter SCB Data Center
- Phase 2 L2 Yellow Black Kemang Village Apt Deutsche Bank @ Mapletree Business City Siam Cement Group Chemicals _ THPP#3
Kuningan City Downtown line signal package, Suvanabhumi International Airport (SBIA)
- Phase 3 L3 Blue Grey Life Style Kuta Bali C955, C956, C960, C961 Thammasat University Rangsit
- Neutral N Black Blue LOTTE Mart Bintaro Downtown Line stage 1 (M&E) Thappline – Ethanol & Gasohol
Mall Summarecon Downtown Line stage 2 (M&E) The Room Radchada
DC Two-Wire Unearthed Circuit
Mayapada Hospital Exxon Mobile Singapore Parallel Train, Triple T Broadband Project
- Positive L+ Red Brown SILOAM Hospital Jurong Island True Multimedia
ST Moritz ExxonMobile Singapore Parallel Train 2, United International Highway
- Negative L- Black Grey
TANG City Mall Jurong Island
DC Two-Wire Earthed Circuit TEMPO Scan Formula One Grand Prix - Pitstop Vietnam
- Positive (of negative earth) L+ Red Brown TRANS Studio Bandung Formulae One Night Race
Ca Mau Pipeline
Garden by the Bay
- Negative (of negative earth) M Black Blue Can Tho Airport
Macau HDB Commercial, Industrial & Residential Buildings
Dung Quat Oil Refinery
- Positive (of positive earth) M Black Blue Ion Orchard
Macao Sands Casino Fideco Building, HCMC
Islamic Hub
- Negative (of positive earth) L- Blue Grey Macua Airport Extension Gemadept Tower
Kallang Paya Lebar Expressway
DC Three-Wire Circuit Ponte 16 Casino Hanoi Museum
LTA Circle Line C830, C414
Venetian Expo, Theater & Arena Hyatt Hotel
- Positive L+ Red Brown LTA KPE Expressway C415
Venetian Parcel 1 Casino IndoChina Plaza Hanoi
Management Development Institute of
- Mid-wire (may be earthed) M Black Blue Park Hyatt HCM
Singapore (MDIS)
RMIT University HCM
- Negative L- Blue Grey Malaysia Marina Coastal Expressway C461
Saigon Pearl Condominium
Marina Coastal Expressway C466
ALAM DAMAI Thi Vi LPG Storage Tanks Development
Marina Sands Integrated Resort
BANK NEGARA Vietcombank Tower HCM
52
Bank Negara Malaysia, Cyberjaya
MSD Pharmaceutical Facility
North South Line Extension (Electrical),
BASF Gebeng, Petronas
C1565
Certification Partners
Singapore
Singapore Cables Manufacturers Pte Ltd (SCM)
+65 6265 0707 [email protected]
Thailand
MCI Draka Cable Co Ltd (MDC)
+66 2308 0830 [email protected]
Malaysia
Draka (Malaysia) Sdn Bhd (DM)
+603 7803 7171 [email protected]
Hong Kong
Draka Cables (Hongkong) Pte Ltd (DCHK)
+852 2410 9229 [email protected]
Vietnam
Singapore Cables Manufacturers Pte Ltd, Rep Office (HCMC)
+848 39260581 [email protected]
Indonesia
PT Prysmian Cables Indonesia
+62 2643 51222 [email protected]
For enquiries outside the above territories, please email to [email protected] attn Business Development.
www.prysmiangroup.com