1) INTRODUCTION
The SKYCOM micro processor has been designed based upon a rack system and using
surface mount component technology to be small and compact so that a standard size box
fits comfortably inside a control panel cabinet up to a maximum of 48 floors.
The rack system allows variable lift configurations to be implemented, which can be tailor
made to suit the application and be cost effective according to the number of floors. Also
each rack plug in board has on board identification (plug and play) which is used to
provide information and help setup the board.
A large 128*64 dot Graphical LCD display has been used to provide the user with a simple
and easy to use interface plus much more useful features such as a description for the
events and trace events, Lift Viewer showing a graphical representation of the lifts’
status/position/doors etc... and an Input viewer to show the status of each input and what it
is configured for.
A keypad switch panel has been included to allow the user to change parameters and
settings to suit the lift installation. The simple layout of the keypad and easy to use menu
interface allows changing of parameters with very little effort. However passwords are
required and maybe given upon request to change certain parameters.
LED indication is provided on each input/output of all plug in cards into the IO rack. The
colour coding is GREEN for INPUT and RED for OUTPUT. Also the CPU has LED
indication provided for the 10 Mains inputs, CPU status, Communications and Power
Supplies.
The micro processor will connect directly to ILE serial indicator and speech units,
providing full programmability of up to 48 floors and many messages and features.
Separate messages are included for doors opening, doors closing, going up and going
down, mind the doors and arrival gongs. The messages have priorities to differentiate
between levels of importance i.e. “Lift Overloaded” would have a higher priority than “Lift
On Fire Control”. These priorities also eliminate the need for extra relays in the control
panel. All these are fully re-programmable via the micro processor. Information is
transmitted serially to the units using CAN (Controller Area Network) technology.
Windows application software is available to allow the user to change parameters and
settings to suit the lift installation. The software will work on any IBM compatible P.C. or
lap top (486, 33MHZ or higher) with windows version 95 or higher. The software has been
designed to encourage and allow the user to change the lift installation setup as required
and to reduce the need for special software. However if special software is required ILE
will only be pleased to accommodate.
3
2) List of Equipment
1) Skycom Micro Processor Box with plastic enclosure, power supply board,
backplane board(s), IO cards and keypad interface.
4
3) Switching Onto Test Operation For The First Time
The Lift Viewer or Input Output Viewer from the main menu maybe used at this stage to
aid with testing.
Installation state:-
The Motor, Thermistors, Fan and Brake etc. have been connected to the Control Panel.
The safety and lock circuit are in a state where the door contacts, emergency stops etc. are
making contact providing continuity from terminals OTL to CTS (also CF to TS for
hydraulic lifts), CTS to CDC and from CDC to LDC.
The wiring has been checked and all cables are connected correctly.
The fuses are in their correct places and of the correct size and type.
The lift is switched to TEST via the Car Top Control or manually by leaving the
connection between TS and TRS open circuit.
Check there are no obstructions in the lift shaft.
Provisionally set the lift and door motor overloads.
Check that the car and landing doors are closed fully (if fitted at this stage).
Check the incoming three phase sequence is correct (PFRR relay is energised)
Check the LED's EMER, CARL, LOCK and TEST are illuminated on the CPU board, or
look on the LCD display (i.e. INPUT VIEWER).
The lift can now be driven by making the following temporary connections:-
To travel UP = TUD to TUP
To travel DOWN = TUD to TDN
The following checks should be made before continuing with moving the lift :-
1) Check that the Emergency stop buttons, Locks and Safety circuit (if applicable) will
stop the lift instantaneously shortly after the lift motor starts to rotate.
2) Run the lift and check that the direction of rotation is correct.
3) Run the lift and check that the brake and ramp voltages are correct
4) Check the door operation (if fitted) by using the car top control buttons to make contact
between terminals :-
5) Check selector stepping and levelling switches are in place and are functional.
6) After Test operation move the lift to the lowest level possible, park with doors closed
and switch off the control system.
Note :- If you have any problems at this stage please refer to the fault finding
section of this manual.
5
4) Switching Onto Normal Operation For The First Time
The Lift Viewer or Input Output Viewer from the main menu maybe used at this stage to
aid with testing.
Installation state:- The lift is complete and is to be operated normally for the first time.
The tape head, door operator, Emergency stop buttons, locks, safety circuit, shaft switches,
proximity and levelling signals have been checked on TEST control as previously
instructed and are operating correctly.
The pulsing and levelling signals are in the correct sequence as on the shaft and vane
layout drawing.
The lift is at the lowest floor level with the reset signal energised.
The lift is switched onto NORMAL operation via the car top control, i.e. a connection
should be made between terminals TS and TRS, also the lift should not be on any other
form of independent service, i.e. Fire or Service control.
Ensure no shaft obstructions exist.
The lift can now be switched on and the following suggested test procedures maybe carried
out:-
1) Purging of the Event Logger RAM:- By selecting pressing -+ and ENTER via the
keypad the previous events stored in the Event Logger are completely cleared, whilst in the
Menu Event History.
2) Testing the pulsing and levelling signals (MSU/MSD & PX) :-This can be achieved by
placing calls to each floor in turn in both the UP and DOWN direction ensuring correct
selector stepping and stopping sequence. Correct any problems with the vanes before
proceeding to the next stage.
Once correct , run the lift to the terminal floors in both directions to check vane operation.
3) Testing of Terminal limit and Slowing switches :- Press CPT button to register a top
car call and then press MENU and F3 under constant pressure to inhibit signals
MSU/MSD and PX thus forcing the lift to slow down via the slowing limit and stopping on
the terminal limit. Press CPB to register a bottom car call and repeat the above process.
Note:- If you have any problems at this stage please refer to the fault finding
section of this manual.
6
5) SKYCOM Micro Processor Box/Rack Drawing
POWER SUPPLY
CONNECTIONS (UNDERNEATH)
MAINS
MENU ESC F1 CPT INPUTS
INTERNATIONAL LIFT
EQUIPMENT LTD 1-10
SKYCOM 1- MENU F2 CPB UNDER-
NEATH
SLOTS � � F3 MODE
2 1-10
4
2
m
m
NOTE
DEPTH =
154mm
SLOTS 11-20
356mm
The SKYCOM lift controller is housed in a plastic Box as shown above. The main purpose
of the box is to provide location and housing for the boards that are fixed within it, or will
plug into the IO rack. The IO rack has grooved slots so that IO boards can slide in and out
as required. Also the lids provide support for the IO boards since they also have grooved
slots to support the IO cards from the top.
The CPU board is mounted behind the main lid with the LCD display and keypad. The
CPU provides interface with the LCD display and keypad and communications for CAN
(Controller Area Network)i.e. CAN1, CAN3 and CAN3. Also communications for RS232
and RS485 are provided.
The power supply board is mounted below the CPU board and has connections for 10
Mains inputs and connections for power from an external transformer or external power
supply (if reqd).
Backplane/Motherboards are fixed within the sections for slots(1-10 / 11-20) as required
and provide connection from the IO cards to the CPU board. Also power supplies for the
IO cards are carried by the backplane/motherboards.
7
6) Power Supply and Fusing Techniques
E4
E3
E2
0VR
+5V(C)
0V(C)
+5V
0V
+24
0VR
OUT
+24
E1
N NEUTRAL
10 TDN (TEST DOWN LIMIT)
+5V(C)
The Power Supply board as shown above is located under the main processor CPU board
and has 2 main purposes. The first is to provide low voltage power to the lift and micro
processor circuits. The second is to provide Mains inputs for the lift functions, typically
configured as shown above. However these inputs can be configured to any combination of
possible inputs. The inputs are fully opto isolated and can be either 240V or 110V as
requested, the isolated status of the inputs are then passed to the main CPU board via the
ribbon connector.
The 24V D.C. supply is derived from the 19V A.C. supply and provides a maximum
current output of 6A. If more current is required then an external 24V D.C. supply can be
used up to a maximum of 11A. There are two 5V D.C. supplies (derived from the 10V
A.C. supply) which are for logic and communications. The logic supply feeds the main
micro processor and input output cards. The communication supply feeds all
communication ports i.e. RS232, CAN ports etc..and usually contains more noise than the
logic supply, therefore the two supplies should never be connected together. Note the
terminals for 5V logic and 5V comms are provided but would not normally be connected
i.e. for reference only.
Separate Earth connections are provided to ensure the lowest path of resistance to Earth.
The function of each Earth connection is detailed above.
Terminal connections are provided to transfer power from the power supply to the IO
backplane i.e. 24V and 5V logic/comms supply.
8
6.1) General Fusing Techniques
Notes
i) All Fuses are external to the PCB boards.
ii) Fuses should not exceed the maximum current ratings.
iii) The IO backplane +24V will be protected by fuse F3=6A.
iv) The IO backplane +5V supplies will be protected by electronic short circuit
protection and F2=4A.
F1-6A QB
TRANSFORMER POWER SUPPLY
19V, 6A 19V IN
+24V and 5V
F2-4A QB supplies to IO
10V IN backplane(s)
10V, 4A 24V 24V
ET4 OUT IN
F3-6A
QB
F4-2A F5-2A F6-2A
QB QB QB
OVR
EARTH
CAR LAN PUSH POSITION
PUSH FEED FEED FEED
viii) Fuses for Car and Lan push feed would not be required if the IO boards are type
“linked” and are supplied with Over voltage and Mains protection, since
inputs/outputs are separately fused.
9
7) CPU Processor Board
(GREEN LED 25) MASTER (GREEN LED 9) DOOR TEST CLOSE
(GREEN LED 24) INT (GREEN LED 8) DOOR TEST OPEN
(RED LED 23) RS 232 (GREEN LED 7) PANEL TEST INPUT
(RED LED 22) RS 485 (GREEN LED 6) DOOR OPEN LIMIT
(GREEN LED 21) +5V C (GREEN LED 5) DOOR CLOSE LIMIT INPU
(GREEN LED 20) +5V (RED LED 4) LANDING LOCK INPUT
(RED LED 19) +24V (RED LED 3) CAR LOCK INPUT
(GREEN LED 18) LOOP (RED LED 2) EMERGENCY SAFETY CIR
RIBBON CABLE
CONNECTOR TO
CAN 1 CAN 2 CAN 3 PSU RS 485 RS 232
CONNECTOR CONNECTOR CONNECTOR BOARD CONNECTOR CONNECTOR
C C C C
CPU
C C SK1
H L H L H L
1 1 2 2 3 3 11
CONN4 CONN5 CONN6 10 CONN7
25
24 9
160087
23 8
SW
22 7
21 6
20 5
19 4
18 3
2
1
CONN2 CONN3
SW2
25
6
18 16 15 17
8 11
7
XTAL1
30
LK6
INTERNATIONAL LIFT
EQUIPMENT LTD
1 CONN8 BAT1 1
0 10
3 2
LK1 29 28
IC5
9
21
14 22
4 5 IC1 12
26 24 23
13
IC2
20 IC7
TR3 IC4
VR1
19 ISSUE 1 27
The main CPU Processor board (shown above) provides control and indication for the lift.
The Graphical LCD display combined with the keypad provides the user with an easy to
use menu interface for displaying lift information and changing parameters.
LED indication is provided for system functions i.e. Program Loop, +24Vand 5V supplies
and Master light etc..(see above). LED is also provided for the mains inputs which are
located on the power supply board underneath the CPU, i.e. EMER, LOCK, TEST INPUT
etc.. (see above).
The program memory is located on the under side of the board for easier access when
changing software(if reqd). The program memory must be removed carefully with a proper
eprom removing tool (“hook”) or with a precision screwdriver if the proper tool is not
available. Very little force is required to remove the memory devices or else damage to the
memory sockets may occur. When inserting the new memory devices ensure that the ODD
and EVEN devices (as marked) are inserted as shown. Also the slanted edges match the
slanted edges of the sockets. Once correct, the device should be pushed firmly into the
socket until it cannot go any further.
The LCD display contrast setting can be adjusted as required by changing the setting on
the LCD contrast potentiometer. However this is factory set and generally would not be
require adjustment.
10
Various connections are provided for serial communication to serial devices (see also
Communications section of the manual). The RS232 connection (fitted as standard)
provides communication to a P.C. or lap top computer. This in conjunction with the
Windows software allows the user to view and change parameters as required. Also the
RS232 connection may be used to connect to a Modem or hand held computer device i.e.
Psion organiser etc..
CAN (Controller Area Network) connections are provided to enable communication to lift
serial devices and other lifts. CAN 1 connection (fitted as standard) provides
communication to per lift devices i.e. serial Indicators/Speech Unit etc.. CAN 2 (fitted on
Duplex boards only) provides communication to other lifts i.e. Duplex, Triplex, Group
etc... CAN 3 (fitted on Duplex boards only) provides communication to motor drives and
shaft encoder.
The RS485 connection is mainly used as a dedicated motor drive serial communication
port.
11
8) IO LINK BOARD
INPUT FUSES FITTED FOR PROTECTED BOARD
LINKS FITTED FOR NON-PROTECTED BOARD
RED GREEN
+ +
F1
+24V
0VR
INPUT
F2
INPUT 1 1
INPUT 2 F3
2 BT
INPUT 3 3 RD
F4 WR
INPUT 4 4
ADDR
5 D0
INPUT 5 F5 D1
D2
INPUT 6 6 D3
7 D4
F6
INPUT 7 D5
D6
INPUT 8 8 D7
F7 1
BOARD TYPE
2
INPUT/OUTPUT
SELECT
4
ISSUE 1
F8
5
BOARD
6
7
8
OUTPUT 160088
OUTPUT 1 1
OUTPUT 2 2
OUTPUT 3 3
OUTPUT 4 4
OUTPUT 5 5
OUTPUT 6 6
OUTPUT 7 7
OUTPUT 8 8
COM COM
The Link board as shown above is so called since the input and output circuits are linked
together. This has the advantage of reducing the wiring to the lift call pushes since the call
acceptance output is provided by the processor and hence output circuit of the IO board.
The outputs are achieved by transistor switching.
Input and output connections are shown above. LED indication for each input/output is
provided at the top of the board, GREEN for Inputs and RED for outputs.
As standard the board is fitted without over voltage and mains input protection. If fitted,
the inputs/outputs are protected against over voltage of typically greater than 30V and
mains voltage up to 240V A.C. If an input/output is subjected to a high voltage then the
relevant fuse will blow. This fuse is rated at 250mA quick blow and should be replaced
with the same.
Link LK1 is required to link the common voltage of the board to the internal +24V
supplied via the IO backplane. If an external supply is required i.e. if it is desirable to fuse
the board separately, then LK1 should not be fitted and the terminal common should be
wired with the common voltage.
12
9) IO NON-LINK BOARD
IN P U T F U S E S F IT T E D F O R P R
L IN K S F IT T E D F O R N O N -P R O
O U T P U T S T A T U S L E D S
O P 1 - O P 8
R E D
IN P U T
IN P U T 1
IN P U T 2
IN P U T 3
IN P U T 4
IN P U T 5
IN P U T 6
IN P U T 7
IN P U T 8
INPUT/OUTPUT
ISSUE 1
BOARD
O U T P U T
O U T P U T 1
O U T P U T 2
O U T P U T 3
O U T P U T 4
O U T P U T 5
O U T P U T 6
O U T P U T 7
O U T P U T 8
The Non Link board as shown above is so called since the input and output circuits are not
linked together. This gives the option of configuring inputs and outputs independent of
each other, i.e. input 1 may conferred as PX whereas output maybe configured as PI1 etc..
The outputs are achieved by relay switching. The relays contacts are normally open and
are all common to the terminal COM. The contacts are rated up to ([email protected].) and
([email protected].)
Input and output connections are shown above. LED indication for each input/output is
provided at the top of the board, GREEN for Inputs and RED for outputs.
As standard the board is fitted without over voltage and mains input protection. If fitted,
the inputs/outputs are protected against over voltage of typically greater than 30V and
mains voltage up to 240V A.C. If an input/output is subjected to a high voltage then the
relevant fuse will blow. This fuse is rated at 250mA quick blow and should be replaced
with the same.
Link LK1 is required to link the common voltage of the board to the internal +24V
supplied via the IO backplane. If an external supply is required i.e. if it is desirable to fuse
the board separately, then LK1 should not be fitted and the terminal common should be
wired with the common voltage.
There are 3 other links IP1, IP2 and IP3 which are included and are as follows:-
13
IP1 = when the link is on, links input 1 (opto-isolated side) to the processor to
give a fast input used as PX. This input can then be used to provide accurate
and predictable delays when changing from high speed to low speed for use
with motor drives, in gaining accurate floor levels i.e. Direct to Floor
Control.
14
10) RELAY OUTPUT BOARD
R E L A Y S T A T U S L E D S (1 -8 )
1A
R E L A Y 1 N /O C O N T A C T
1B
2A
R E L A Y 2 N /O C O N T A C T
2B
3A
R E L A Y 3 N /O C O N T A C T
3B
4A
R E L A Y 4 N /O C O N T A C T
4B
SELECT
5A
R E L A Y 5 N /O C O N T A C T
5B
6A
R E L A Y 6 N /O C O N T A C T
6B
7A
R E L A Y 7 N /O C O N T A C T
7B
8A
R E L A Y 8 N /O C O N T A C T
The Relay Output board provides 8 normally open volt free relay contacts that can be
configured as required. The contacts are not common and must be wired to each side of the
contact i.e. A and B. The contacts are rated up to ([email protected].) and ([email protected].)
Output connections are shown above. LED indication for each output is provided at the top
of the board i.e. RED for outputs.
LK1 = when the link is on, links output 1 (opto-isolated side) to the processor to
give a fast output used as HSR. This output can then be used to provide
accurate and predictable delays when changing from high speed to low
speed for use with motor drives, in gaining accurate floor levels i.e.
Direct to Floor Control.
15
11) Backplane Board
C O N N 1 1
10
C O N N 1 0
9
C O N N 9
8
C O N N 8
7
C O N N 7
6
C O N N 6
5
C O N N 5
4
C O N N 4
3
CARD SLOTS (1) TO (10)
C O N N 3
2
The Backplane board as shown above provides a connection between Input/Output devices
and the micro processor, also it provides a connection from the power supply to the IO
boards. The backplane is fixed within the box to provide a location for the IO cards to slot
into. Generally only one backplane board will be fitted, but if more than 10 slots are
required, a second board maybe fitted to expand up to 20 slots. The difference between a
backplane board configured for slots 1-10 or 11-20 is identified by the address selector
links, i.e. fitted 1-10 for slots 1-10 or 11-20 for slots 1-20.
16
12) Menu List Description
The menu list will be in the order typically as below. Each menu list item has a purpose to
either view lift information or view and change lift parameters according to the password
entered. Each section corresponds to a block of data that is relevant to each other i.e. all
Door parameters are in Door Setup and all Door times are in Door Times etc.. All
parameters are usually factory set from ILE before despatch. A brief description of all the
menu items is shown below.
EVENT HISTORY
EVENT TRACE BUFFER
TRACE SETUP
ENTER CALLS
LIFT VIEWER
INPUT OUTPUT VIEWER
JOB DETAILS
SYSTEM DETAILS
MODIFIED PARAMETERS
GENERAL PARAMETERS
GENERAL TIMES
DOOR SETUP
DOOR TIMES
TRAVEL SETUP
HOMING SETUP
IO SETUP
OUT OF SERVICE SETUP
HYDRAULIC SETUP
ANTI NUISANCE SETUP
FIRE CONTROL SETUP
SPECIAL SERVICE SETUP
SPECIAL SERVICE TIMES
ETA PARAMETERS
EXTERNAL DEVICES
PX DELAYS SETUP
FLOOR SPEED SETUP
ENGINEER SETUP
GROUP SETUP
M.G. SEQUENTIAL START
ADVANCING SELECTOR
DATE TIME SETUP
GENERAL INFORMATION
PARAMETER CONTROL
EVENT HISTORY
All current event History can be viewed from within this menu. The data can be viewed in
list format, or as detailed information with description, time and date etc..
EVENT TRACE BUFFER
All current Trace History can be viewed from within this menu. The data can be viewed in
list format, or as detailed information with description, time and date etc.. Trace history is
a log of certain events or information that is usually viewed for diagnostic purposes.
TRACE SETUP
This is the Trace history setup menu, whereby items can be selected for trace i.e. vane info
or door info, or all if required. Once setup entering Trace History will display the
information.
ENTER CALLS
The user can enter specific or patterned calls from within this menu with the option of
repeating and viewing the calls with the Lift Viewer.
17
LIFT VIEWER
A graphical representation of the lift can be viewed showing lift position, status, door
status, vane information, calls and much more.
INPUT OUTPUT VIEWER
A graphical representation of the inputs and outputs can be viewed from this menu, Also
the information can be viewed as a whole or as usually preferred in detail of each IO slot.
JOB DETAILS
Job details such as Job Number and LCD default message etc, can be viewed and changed
if required.
SYSTEM DETAILS
System details such as Number of floors, Drive type and Collective type etc, can be viewed
and changed if required.
MODIFIED PARAMETERS
A list all relevant Parameters that have been modified can be viewed from within this
menu. The data can be viewed in list format, or as detailed information showing the default
value that the parameter has changed from.
GENERAL PARAMETERS
General parameters such as Delay, Pulse HLR etc, can be viewed and changed if required.
GENERAL TIMES
General times such as Self Test time and Dive time etc, can be viewed and changed if
required.
DOOR SETUP
Door parameters can be viewed and changed as required such as Quick close, Park open
and Nudging enabled etc.. These details are usually factory set from ILE before despatch.
DOOR TIMES
Door time parameters can be viewed and changed as required such as Door Dwell times
and Nudging time etc..
TRAVEL SETUP
Travel parameters/times mostly associated with the drive control can be viewed and
changed as required such as Brake Lift/Release times, Stop time and Journey time etc..
HOMING SETUP
Homing parameters/times such as Homing floors, Homing time and Homing ON/OFF can
be viewed and changed as required.
IO SETUP
All Input/Output parameters such as Call inputs, Relay outputs and General inputs etc, can
be viewed and changed as required.
OUT OF SERVICE SETUP
The Out Of Service Indicator can be configured to show out of service for a variety of
conditions such as Landing Lock Failure, Car Lock Failure, Fire Control and Service
Control etc.
HYDRAULIC SETUP
Hydraulic Lift parameters such as Hydraulic Homing Required, Hydraulic Homing Time
and Relevel period etc, can be viewed and changed as required.
ANTI NUISANCE SETUP
Anti nuisance parameters such as Forward car call dumping, Reverse car call dumping and
Door Open push held dumping etc, can be viewed and changed as required.
FIRE CONTROL SETUP
Fire control parameters such as Door Control, Fire return floor and Fire type etc, can be
viewed and changed as required.
18
SPECIAL SERVICE SETUP
Control parameters referring to Service Control, Priority Service and Attendant Control
etc, can be viewed and changed as required.
SPECIAL SERVICE TIMES
Parameters referring to Special Service Times i.e. door dwell times can be viewed and
changed as required.
ETA PARAMETERS
When the system is set for Duplex, Triplex or Group, parameters can be viewed and
changed as required to alter the Estimated Time of Arrival calculations e.g. Lift High
Speed, Door timing and Motion timing etc..
EXTERNAL DEVICES
Selected parameters for devices such as ILE Indicators, Speech Unit and Shaft Encoder
can be viewed and changed from this menu.
PX DELAYS SETUP
Proximity pulse delay (PX Delay) parameters for UP and DOWN direction and for various
speeds can be viewed and changed as required.
FLOOR SPEED SETUP
Floor Speed parameters for UP and DOWN direction and for various multi floor runs can
be viewed and changed as required.
ENGINEER SETUP
Special Engineering parameters such as Short Floors/Selective Doors can be viewed, but
not usually changed on site.
GROUP SETUP
Group Despatcher parameters for use with a Group despatcher can be viewed and changed
if required.
M.G. SEQUENTIAL START
Motor Generator sequential starting parameters for use with a Motor Generator Set can be
viewed and changed if required.
ADVANCING SELECTOR
Advancing Selector parameters for use with a high speed lifts can be viewed and changed
if required.
DATE TIME SETUP
The settings of time and date associated with the real time clock can be viewed and
changed if required.
GENERAL INFORMATION
General information for the lift can be viewed here. E.g. Software Version, Number of
Journeys Count , Number of Door Cycles etc..
PARAMETER CONTROL
Password Entry and the control of parameters are accessed here. A password is first
required to enable the user to change parameters. Parameters can be stored and loaded as
required, to be either Factory/User settings, First time Defaults or Current/Normal
parameters.
19
13) Setup / Programming Via the Keypad Interface
Generally the lift parameters should be setup as specified at the ILE factory. However
when required, programming of the lift controller is achieved by setting parameters from
within the menu on the LCD display. The main menu is a list of menu items, which contain
blocks of data associated with various parts of the lift program. These data blocks known
as parameters can be changed to manipulate the lift program into performing a task in the
desired way, e.g. changing door dwell times and homing times/homing floor etc..
Note the parameters are protected by the use of PASSWORDS which are required before a
parameter may be changed. Different passwords are required to access different levels of
parameters, however ILE will allow some parameters to be changed. Higher level
passwords will only then be given at the discretion of ILE.
By the use of the keypad keys:- mainly -fl, �, ENTER, ESC, -+ and MENU, parameters
can be viewed and easily changed as desired.
Parameters are selected by first moving the scroll bar over the menu item list and pressing
ENTER. This will access the user into a further section which details the parameters in that
menu item list. Again by moving the scroll bar over the required parameter and pressing
ENTER, the details of that parameter are revealed. Changing the parameter is then
achieved by using the -fl and � arrows of the keypad to select a different value for that
parameter. Pressing ENTER once again will store the new value of the parameter and a
message will be displayed to indicate that the parameter has been updated successfully.
Parameters once changed are stored in non-volatile memory(i.e. not affected by power
down)
There are three sets of parameters, which are:- first time defaults, factory/user settings,
and normal/current parameters. These three sets are identical in every way apart from
their values. First time defaults are typical job parameters that are loaded upon first time
power up of the processor board. The factory set parameters are the ones set prior to
despatch from the ILE factory(i.e. customer specific). The current parameters are ones that
are currently available from the menu. When required, it is possible to load and save
factory settings or load first time defaults into the lift program memory, via then Menu
Parameter Control.
20
Example of Changing A Parameter
The example below shows how to change the door settings from doors that park closed to
doors that park open. Before any parameters can be changed, the Engineer must “log on”
by initiating the event Engineer Present to record his/her entry. This entry is achieved by
pressing MODE and ENTER simultaneously on the keypad, hence password level 1 will
be set.
LIFT VIEWER
INPUT OUTPUT VIEWER
JOB DETAILS
SYSTEM DETAILS
MODIFIED PARAMETERS
GENERAL PARAMETERS
GENERAL TIMES
Move the menu scroll bar down to the Door Setup with the down arrow -J. on the keypad
as shown. Note the inverting of the text indicates the scroll bar position. Once over the
Door Setup as shown, press ENTER on the keypad to enter that menu.
DOOR SETUP
TYPE
ACK FEEDBACK
DCR ON WHEN CLOSED
STOP SIGNAL
Move the scroll bar down in the same way to select the parameter Park Open as shown
below:-
DOOR SETUP
DCR ON WHEN CLOSED
STOP SIGNAL
ADVANCED DOOR OPEN
QUICK CLOSE
21
DOOR SETUP
PARK OPEN
[NO]
Change the parameter value by using the 1' or -J. arrows on the keypad. Note the value
will alternate between YES and NO. Set the parameter for YES as below:-
DOOR SETUP
PARK OPEN
[YES]
Finally press Enter on the Keypad to change the parameter value and store it in memory. If
the parameter has been accepted the message “Parameters Updated” will appear on the
bottom of the LCD display for 1 second approximately and then disappear. However if
there is an error for some reason the message "Parameter Write Error" will appear. ILE
should be contacted if this message persists.
DOOR SETUP
PARK OPEN
[YES]
22
14) Password Entry, Parameter Control and Engineer Entry.
Before any parameters can be changed, the Engineer must “log on” by initiating the event
Engineer Present to record his/her entry. This entry is achieved by pressing MODE and
ENTER simultaneously on the keypad. This will then set password level 1 and the
Engineer will be able to change certain parameters e.g. door dwell times, homing
times/floors etc. The Engineer present mode will allow password level 1 for a time period
of 24 hours or until Engineer Leaving is asserted from the keypad. This entry is achieved
again by pressing MODE and ENTER simultaneously on the keypad.
Higher level passwords are achieved by entering an actual password which can be obtained
from ILE when required. Again the Engineer Present mode must be asserted to allow a
password to be entered at all. The password is entered from the menu PARAMETER
CONTROL in the main menu list.
The keypad keys (� and �) and Page up(F1 + �) and Page Dn (F1 + �) can be used
t scroll through the menu PARAMETER CONTROL. Within Parameter Control will
o
be typically the following:-
PARAMETER CONTROL
PASSWORD MODIFIER
LOAD NORMAL PARAMS
STORE NORMAL PARAMS
LOAD FACTORY/USER
STORE AS FACTORY/USER
PARAMETER CONTROL
PASSWORD ENTRY
[x ]
The keypad keys (� and �) will scroll through the list of possible characters for the
password. Pressing -+ will move onto the next character and will loop back to the
beginning once at the end. Pressing ENTER will submit the entry as displayed upon the
screen. If it is the correct password, a message “Password Level X OK” will be displayed
(where X is the level to be obtained). Otherwise a message “Password Rejected” will be
displayed
23
14.3) Changing the Password
There are three sets of parameters, which are:- first time defaults, factory/user settings,
and normal/current parameters. These three sets are identical in every way apart from
their values. First time defaults are typical job parameters that are loaded upon first time
power up of the processor board. The factory set parameters are the ones set prior to
despatch from the ILE factory (i.e. customer specific). The current parameters are ones that
are currently available from the menu. When required, it is possible to load and save
factory settings or load first time defaults into the lift program memory. The diagram
below illustrates the process of parameter control:-
NORMAL PARAMETERS
LIFT PROGRAM
PARAMETER
MEMORY FACTORY / USER
PARAMETERS
As can be seen parameters can be stored from the lift program parameter memory as
Normal or Factory/User defaults. However Normal, Factory/User or First Time Defaults
can be loaded into the lift program parameter memory as required.
24
15) Keypad Shortcut Keys
17) Page UP F1 + 1-
18) Page DN F1 + -,,
25
16) Lift Event and Fault Logging
The Skycom processor has full Event History Logging, providing many events for lift
faults and occurrences. These events are stored in non-volatile memory(i.e. not affected by
power down). A maximum of 50 events can be stored which includes the number of
occurrences the event has occurred, time/date the last occurrence, the position at which it
occurred and a full description of the event. Events are displayed as they happen as long a
menu item is not selected(i.e. at the main menu). Otherwise they will be stored and then
displayed shortly after coming out of the menu item, or by pressing the MENU button on
the keypad.
EMERGENCY STOP
Position=01 Occur=01
20:06:2000 17:50:23
Access to view the events can be gained by selecting Event History from the main menu.
A complete list of all the events can be viewed from the start of the buffer to the end of the
buffer, scrolling up and down by pressing the keypad direction arrows. Also by pressing
enter over the event, the whole event can be viewed with all its other details and
description. Scrolling up and down maybe continued whilst viewing the event in the
detailed mode.
i) Normal Events:-
+24V SUPPLY LOW/LOST :- main +24V is either less than 18V or lost.
+24V SUPPLY RESTORED :- main +24V is now restored.
+5V COMMS SUPPLY LOST :- +5V communication supply is lost.
+5V COMMS SUPPLY REST :- +5V communication supply is restored.
26
iii) Processor Events:- Contact ILE if any of these appear in the Fault Logger !!
RAM FAILURE
CPU NMI TRAP ERROR
STACK OVERFLOW TRAP
STACK UNDERFLOW TRAP
CPU HARDWARE TRAP
CPU WATCHDOG TRIPPED
RTC READ ERROR
RTC WRITE ERROR
EEPROM WRITE ERROR
I2C CLOCK 0V TIMEOUT
I2C SDATA 0V TIMEOUT
27
17) Lift Trace Buffer Event Logging
The Skycom processor has a Trace Event History Logging feature, providing many extra
events for lift diagnostics. These events are stored in volatile memory and will be erased
after loss of power or processor re-boot. A maximum of 50 events can be stored which
includes the time/date the last occurrence occurred, the position at which it occurred and a
full description of the event. A typical event will be displayed as below:-
ON PXU VANE
Position=01
20:06:2000 17:50:23
The trace buffer is setup by selecting Trace Buffer Setup from the main menu. Within this
menu parameters can be enabled/disabled to select different trace viewing options as
detailed below.
Access to view the events can be gained by selecting Event Trace Buffer from the main
menu. A complete list of all the events can be viewed from the start of the buffer to the end
of the buffer, scrolling up and down by pressing the keypad direction arrows. Also by
pressing enter over the event, the whole event can be viewed with all its other details and
description. Scrolling up and down maybe continued whilst viewing the event in the
detailed mode.
Door Task Event:- allows the trace of the door status i.e. Doors Opening, Doors
Closing, Doors Opened etc...
Door Edge Devices:- allows the trace of the door edge devices i.e. DOP, SE, and DE.
Travel Task Event:- allows the trace of the lift travel status i.e. Starting, Slowing,
Levelling etc..
Travel Vanes:- allows the trace of the lift vanes during travel i.e. ON PXU, OFF
PXU, ON MSU, ON MSD etc...
Drive Info:- allows the trace of the information controlling the drive and
information received from drives when connected serially.
28
18) LCD Default Message and Out Of Service Messages
The Default Message on the LCD display provides the user with useful information
without the need to search through various menus to find it. The default message can be
configured to show the system details or the Lift Viewer can be selected (see Default Msg
Select parameter, in Job Details from the main menu).
The message will not be displayed when within a menu item, however it will be displayed
shortly after LCD and keypad activity has ceased. Priority is given to Events which will be
displayed immediately and held for a short time period prior to the default message being
re-displayed.
If the lift is out of service for any reason, the default message changes slightly to give
details of the out of service condition. Also a suggestion is given to help rectify the out of
service condition. If the lift is out of service for more than one reason, then the message
displayed is prioritised by the processor.
INTERNATIONAL LIFT
EQUIPMENT LTD
29
19) Lift Viewer
The Lift Viewer has been designed to be a useful diagnostic tool for the Lift Engineer.
Once selected from the main menu the lift status, position, doors, calls, vanes and other
information can be viewed instantly from the Graphical representation of the lift, that the
lift viewer provides. Below is a typical example of the lift viewer showing an 8 floor lift.
The lift is going in the UP direction to answer an up call, a car call and a Priority
call(homing call) at the LB floor, from the SB floor. Indication D also shows that the
Destination of the lift is to floor LB.
The doors are closed, the safety circuit, car locks and landing lock circuits are made(Emer,
Carl and Lanl are on).
The lift is just setting off since it is still at floor level i.e. Msu and Msd vanes are on, also
the lift is still on the bottom reset limit(Rsd is on).When the lift reaches a stepping
proximity vane, Px will be on.
The processor has feedback from the direction relays or brake circuit since Str is on. The
lift is targeting high speed i.e. speed = HSR.
The Power supplies to the lift are present since 24V and 5VC are on. Also the lift is in
NORMAL operation i.e. not on any special service i.e. Overloaded, Service or Fire etc..
Priority Up/Dn
(homing) Car calls
Calls Calls
Lift 5V
Destination communications Lift Position
supply and Door
Status
24V Power Lift Shaft
supply >18V and Floor
Designations
30
20) Input Output Viewer
The Input Output Viewer has been designed to be a useful diagnostic tool for the Lift
Engineer. This viewer allows the user to view all inputs/outputs to the lift microprocessor.
Inputs and outputs can be viewed all at once via a detailed graphical screen or as usually
preferred via an enlarged screen showing one input/output slot at a time. The Inputs/
Outputs are viewed as they are set via the Input Output parameters. E.g. if Slot 1, Input 1=
car call 1 then the input viewer will show CP1 as input1.
From the main Menu list select INPUT OUTPUT VIEWER and a display similar to the
following will be shown:-
I/O VIEWER
I/O VIEWER
SLOT 6 NON-LINK
SLOT 7
SLOT 8
SLOT 9 RELEV BOARD
The Board Type is displayed next to the slot number i.e. LINK, NON-LINK, RELEV
BOARD RELAY etc.. A blank indicates that no board is fitted or detected.
One the required slot has been selected a display will be shown as follows:-
SLOT 1 LINKED
Outputs Inputs
CP1
CP2
CP3
CP4
CP5
CP6
CP7
CP8
As can be seen the inputs are set for car calls on slot 1 and CP2, CP4 and CP8 are all ON.
31
21) Enter Calls
The Enter calls menu has been designed to be a useful diagnostic tool for the Lift Engineer
when testing and setting up the lift. This option allows the user to enter calls to their
specific pattern or use the pre defined patterns such as all calls, Odds and Evens etc.. A
repeat option has been included to allow the user to repeat the patterns, and an option to
switch the lift viewer on once a call pattern has been selected has been included so that the
calls can be viewed from the lift viewer. When the Repeat option is set to yes, calls will be
repeated for a period of 30-60 minutes approx and then Enter Calls option will be
terminated.
From the main Menu list select ENTER CALLS and a display similar to the following will
be shown. As can be seen the lift viewer and repeat option is selected at this stage. By
placing the scroll bar over the desired option and pressing ENTER the option can be
selected or de-selected as required.
ENTER CALLS
REPEAT CALLS No
ENTER A CALL
CAR CALLS TOP BOT
ALL CAR CALLS
Also by scrolling down the remaining call options can be selected as shown:-
By pressing ENTER the even car calls will be entered. If the lift viewer option is set to Yes
then the lift viewer will be shown to indicate the calls entered. If the Repeat Calls option is
set to yes then the EVEN calls will be repeated until the timeout period has timed or enter
calls is terminated.
ENTER CALLS
To enter one or more specific calls as required, the menu option Enter a Call should be
selected as shown below. Once selected, the lift viewer will be displayed automatically.
ENTER CALLS
32
The Lift Viewer will be displayed as below with the bottom left hand side modified to
allow the user to select Car, Up landing or Dn landing calls as required.
Priority Up/Dn
(homing) Car calls
Calls Calls
Lift Position
and Door
Call Type Floor Status
Lift Shaft
and Floor
Designations
By pressing the right arrow ➔ on the keypad the call type is changed from CAR, UP or
DN calls. By pressing the up and down arrow keys (1- or �) the floor will change up/dn as
required. Finally pressing Enter will enter the call. In the above example a Car call to LB
would be entered.
33
22) Input Output Setup
The Input Output Setup has been designed to allow configuration of Inputs and Outputs for
Factory setup or on site for the Lift Engineer. First a slot should be selected to view the
current configuration of the Inputs and Outputs, also displayed next to the slot is the board
type. Inputs and Outputs maybe repeated as required. I.E. if it is required to have multiple
UPR outputs, many outputs can be configured to UPR.
From the main Menu list select INPUT OUTPUT SETUP and a display similar to the
following will be shown:-
I/O SETUP
MAINS INPUTS
SLOT 1 LINK
SLOT 3
SLOT 4 NON LINK
I/O SETUP
SLOT 6 NON-LINK
SLOT 7
SLOT 8
SLOT 9 RELEV BOARD
The Board Type is displayed next to the slot number i.e. LINK, NON-LINK, RELEV
BOARD RELAY etc.. A blank indicates that no board is fitted or detected.
INPUT 1 - [FAST PX
INPUT 2 [STR
INPUT 3 [MSU
INPUT 4 [MSD
INPUT 5 [RESET UP ]
INPUT 6 [RESET DN ]
INPUT 7 [PRI-SERV1]
INPUT 8 [SERV
The pointer to the current parameter is shown by the dash “-” above. To move the pointer
use the keypad keys MODE and -t. This will move the pointer upwards until it reaches the
top where it reset to the bottom. With the pointer over the selected parameter scroll
through the available parameters using the keys -tand -J until the desired input is
found(Note see list of inputs section). By pressing ENTER then the parameter will be
stored, also a message will be displayed for 1 second to acknowledge the entry.
34
By pressing ➔ whilst within the parameter screen will switch between Inputs and Outputs
if the Board type is LINKED. I.E. the switch to Outputs has just been made from the
previous screen.
OUTPUT 1 - [IU
OUTPUT 2 [ID
OUTPUT 3 [UP RELAY ]
OUTPUT 4 [DN RELAY]
OUTPUT 5 [LW90
OUTPUT 6 [OLI
OUTPUT 7 [OSI
OUTPUT 8 [FIRE
35
23) Fault Finding and Callouts
If the lift system is not working correctly, the Service Engineer must find the fault. The
Micro processor and circuitry helps the engineer in fault finding because it remembers
each fault in turn, which floor it was at, how many times it has occurred and the date and
time it happened. See Event History/Trace Buffer in the main menu for the events and
descriptions. See also Lift Viewer and Input Viewer for detailed information of the lifts’
status.
Checking procedure
1) Check the 3 phase incoming supply to the controller.
3) Check the various voltages at the Primary and Secondary of each transformer with
respect to their terminals and not earth.
4) Check the voltage going into and out of each fuse relevant to the power supply (see
Power Supply) and in the control panel, making sure they match and visually inspect
where possible for a blown fuse (Avoid switching off if possible to check fuses as this may
clear the problem, but it may return at a later date causing another callout).
5) LED EMER = Safety Circuit should be lit on the CPU Board, if not check live feeds in
order to terminals CF, TS, OTL, RWS, OS and CTS.
6) LED CARL = Lock Circuit Should be lit on the CPU Board, if not check live feeds in
order to terminals CTS and CDC.
7) LED LANL = Lock Circuit Should be lit on the CPU Board, if not check live feeds in
order to terminals CDC and LDC.
8) Check that the following functions are NOT switched on and the LED's are not
illuminated:-
a) OSI,
b) TEST, illuminated on test.
c) LW90, LW110 & OLI, illuminated when the lift is 90% and 110% loaded.
d) THERM, illuminated when the motor thermistor / shaft temperature monitoring
unit (if fitted) has tripped.
e) RET, illuminated when on Emergency Recall/Shutdown.
f) SERV, illuminated when on Service control.
g) FIRE, illuminated when on Fire Control.
h) SE, DOP and DRL are illuminated when the Safe edge, Door open Button
and Door light Ray are activated respectively, which may prevent the doors
from closing.
i) The RED led on the phase failure and reversal relay (PFRR) must not be
illuminated.
If all circuits appear to be O.K, there is a possibility of a coil burning out on a relay,
contactor, the brake, ramp or a valve coil may have burnt out. If further help is required
whilst fault finding please make a note of the following before contacting ILE.
i) LED's that are illuminated, ii) A full report of the state of the contactors and relays etc.
iii) A full report of the lift fault. iv) A full report from the fault logger.
36
24) Common Faults
A list of common faults are detailed below. To assist with fault finding see Event
History/Trace Buffer in the main menu for the events and descriptions, see also Lift
Viewer and Input Output Viewer for detailed information of the lifts’ status.
i) When car stops at floor level both MSU and MSD must be illuminated.
ii) Proximity input PX must pulse once ON and once OFF between every floor.
iii) Check Tapehead unit/floor selection switches operate correctly.
iv) Check car/landing calls are being entered to the correct floors.
i) Check safe edge, door open button and detector edge are not operated.
ii) Check door open limit has operated.
iii) Check that the parameter “PARK OPEN” within Door Setup has not been set.
iv) Check Terminal limits.
v) Note under Fire control, Service control and overload bypass the lift doors
remain open typically and will only close by initiating a car call.
i) Check car and landing locks are made LED's EMER and CARL and LOCK on
the CPU board.
ii) Check door limits.
iii) Check shaft Terminal limits.
iv) Check drive fault contact.
37
25) Micro Processor & Control Switchgear Sequencing / Interfacing
The micro processor situated on the CPU board is responsible for the co-ordination of all
the inputs / outputs of the surrounding control circuitry via the I/O rack.
It is therefore important to be able to understand the basic and typical sequence of events
surrounding the I/O rack interface in conjunction with the events generated on the fault
logger display when fault finding.
SEQUENCE
Assuming the lift is at floor level with the doors closed and ready to accept a call.
2) The micro processor accepts this and produces a call accepted indicator, then
energises the pilot relays UPR or DNR (depending upon direction) and HSR at the
same time. These relays are situated on the relevant configured relay output board.
3) The pilot relays provide a current path to the controller return for the control
relays/contactors (UP or DN and HSR).
4) The relay STR (start relay) is energised via the contacts of UP or DN. A contact of
STR relay is then used to provide a feedback input to the micro processor at the
input STR.
5) The micro processor acknowledges the start signal (STR) and energises the
pilot relay LSR on the relevant configured relay output board. This then provides a
current path to the control panel return for the LSR (low speed relay) in the control
panel (if required).
38
26) Lift Service Modes
Prepare To Test:-
The prepare to test feature is enabled by pressing MENU + F3 on the keypad. This feature
has the effect of preparing the lift for full test control by inhibiting any further landing calls
and preventing the lift from homing to the main floor, thus prevents the pickup of further
passengers. Any passenger still travelling within the lift will still be able to register car
calls to their destination. Parameters found in Special Service Setup provide options for
disabling the doors and low speed timer whilst on Prepare To Test.
Service Control:-
The Service Control Feature is selected by asserting the SERV input. When selected, the
service control feature renders the lift out of service and transfers all landing calls to other
members of the group (if any). The control of the lift is then from the car only and it
assumed that an attendant would operate the lift in a manual fashion as the car call buttons
now become constant pressure buttons. The advantage of such control is for the loading
and unloading of goods whereby the attendant has full control of the lift e.g. a porter in a
Hotel. Parameters found in Special Service Setup provide options for enabling/disabling
constant pressure door control.
Fire Control:-
The Fire Control feature is selected by asserting the FIRE input. When selected, the fire
control feature renders the lift out of service and transfers all landing calls to the other
members of the group (if any). There are many different types of Fire control but generally
the lift is interrupted from its' normal direction of travel to its' destination (any car calls
being immediately cancelled) and called automatically to a specific floor as a matter of
urgency for a fireman. Once the lift has reached this floor, full control of the lift and the
doors is assigned to the fireman via constant pressure call buttons and the door open
button. Parameters found in Fire Setup provide options for enabling/disabling constant
pressure door control and selecting fire floor etc..
The 110% overload function becomes active when the lift is stationary and the LW110
input is asserted. The event 110% overload is generated, doors are parked open, the lift is
then marked out of service.
The 90% overload function is active when the lift is either moving or stationary and the
LW90 input is asserted. The operation of the lift from then on is that landing calls are
bypassed therefore reducing the chance of another person entering the lift and fully
overloading it. Instead car calls are dispensed with so that passengers will leave the lift car
thus reducing the weight and relieving the 90% overload condition. Once this is achieved
landing calls are resumed and the lift is ready to pick up passengers once again as normal.
39
Thermistor Tripped:-
The Thermistor Tripped function becomes active when the lift is stationary and the
THERM input is asserted. The event Thermistor Tripped is generated, doors are parked
open, the lift is then marked out of service.
The Priority Service Control Features are selected by asserting the ERET 1/2/3 inputs as
required. When selected, the lift is rendered out of service and transfers all landing calls to
other members of the group (if any). The lift is interrupted from its' normal direction of
travel to its' destination (any car calls being immediately cancelled) and called
automatically to a specific floor as a matter of urgency. Once the lift has reached this floor,
full control of the lift is assigned to the user. Parameters found in Special Service Setup
provide options for enabling/disabling constant pressure door control, enabling/disabling
car calls, enabling/disabling extended door dwell times etc...
40
27) Lift Self test and Out Of Service Setup
The self test feature automatically inserts terminal floor car calls (i.e. Top and Bottom or
settable via parameters) 120 seconds after lift inactivity following a fault condition, e.g.
door open/close protection time, lock failure, failure to start etc. This cycle will be
repeated every 120 seconds up to a maximum of five attempts(parameter settable) or until
the lift is back in service. After the last attempt, self test will be inhibited until the system
is returned to normal operation via passenger intervention. Parameters found in General
Parameters provide options for Self Test.
The Out Of Service output OSI can be configured as required via the parameters found in
the Out Of Service Setup. A list of failures and service modes can be selected / de-
selected. Also by setting the parameter LISI INDICATOR (Lift in Service Indicator) in
General Parameters the Out of Service Indicator is inverted and becomes a Lift in
Service Indicator.
41
28) Lift Anti-Nuisance Control
Anti-Nuisance features have been included to enhance the operation of the system and
help reduce waiting times. All features are configurable by the parameters in the Anti
Nuisance Setup but typical values are given below. Also the features described below are
all disabled during any not normal service operations, i.e. Fire and Service control.
The " STUCK CAR BUTTON " event will be recorded typically 10 seconds after the
micro processor has attempted and failed to cancel a car call. The stuck car call is now
ignored but will be eligible for operation after the stuck condition has been removed.
However, to provide lift service to the floor with the stuck car call push, the micro
processor will reinstate the call (if still stuck), typically 240 seconds from when originally
detected.
42
29) Lift Relevelling Control
The Relevelling feature is included as standard within the Skycom control system on all
hydraulic lifts and is an optional extra on traction lift systems.
The Skycom Control System continuously monitors the relevelling operation. If a failure
occurs with the relevelling operation then the relevant fault is recorded and recovery action
is initialised. All relevelling parameters are accessible from the menu Hydraulic Setup,
but typical values are given below.
The relevelling sequence is automatically initiated via the Skycom control system and can
perform relevelling in the up or down direction depending on loss of up or down levelling
vanes. To prevent the lift from hydraulic oscillations, the relevelling sequence will not be
initiated or re-initiated until the lift has been idle for the setting of the PAUSE TIME
parameter(Travel Setup) i.e. typically 1 second. The Skycom Control System
continuously monitors the relevelling operation. If a failure occurs with the relevelling
operation then the relevant fault is recorded and recovery action is initialised. Failures
associated with relevelling can be categorised as follows:-
The Hydraulic time-out timer will time when the drive system fails to move the lift to floor
level. This may be caused by failure of the lift hydraulic pump / valve unit or it's associated
control circuit. These types of faults will cause the lift to remain in the levelling zone, but
not reach floor level within a predictable time limit. This time to reach floor level is
typically set to 20 seconds. If the lift exceeds this time it is removed from normal service,
and relevelling operation is suspended. An attempt to return the lift to the bottom floor is
then made, since the down operation could well be achievable i.e. (no pump motor
operation is required). On arrival at the bottom floor the lift will remain out of service until
the power is switched off.
b) Hydraulic Homing
The Skycom Control System will automatically home to the lowest floor level typically 12
minutes after the last lift movement. E.G. when the main homing floor is not the lowest
floor level, the lift will home to the main homing floor after the standard homing time.
However the control system will hydraulic home again to the lowest level after becoming
idle for 12 mins.
c) Hydraulic Anti-Yo-Yo.
During normal relevelling operation excessive relevelling cycles can be detected and
recovery action taken. Excessive relevelling cycles can be due to overheating hydraulic oil
or faulty proximity switches all of which when left unattended can place the lift in a
dangerous condition. The number of relevelling cycles are monitored over a period of
minutes. If the number of relevelling cycles is deemed excessive by the Skycom
programme, then the relevelling function is suspended and the lift is removed from
service. Attempts will be made to return the lift to the bottom floor, where it will remain
out of service.
43
d) Relevelling Sequence Check. (software).
Failure of the levelling vanes to operate causing the lift to stop by the release of both
vanes. This type of operation can be caused by an intermittent malfunction, or by a faulty
proximity switch. If the proximity switch operation is unreliable then the relevelling
operation is potentially dangerous. The Skycom microprocessor monitors the relevelling,
and keeps a record of occurrences when the lift stops out of level following a relevel
operation. Each time the lift stops out of level a counter is incremented by sixteen. If the
lift makes a successful relevelling operation to stop at floor level the counter is
decremented by 1. If the counter reaches a count of 48 (caused by three consecutive
relevelling errors, or frequent levelling errors), the lift is removed from service, and
relevelling is suspended. Attempts will be made to return the lift to the bottom floor, where
it will remain out of service.
44
30) Duplex, Triplex and Multi Car Group Applications
The Skycom processor has the capability and performance to provide a fast and efficient
lift despatching service from Duplex up to many cars in a lift Group. This service can be
provided with or without an external despatcher, however an external despatcher will
provide an enhanced service.
The despatching service is based upon an “Estimated Time of Arrival” (ETA) algorithm
which calculates an estimated arrival time for each landing call. The calculations are based
mainly upon lift speed, acceleration/deceleration times, levelling speed, door
opening/closing times etc.. but even down to the fine details such as car preference time
and door dwell time. The accuracy of the ETA increases despatching
efficiency/performance until the last landing call is answered, but at the same time
provides the processor with a heavy burden of calculations, thus the need for an external
despatcher for many floors and many lift cars.
The ETA’s are modelled within the micro processor to allow the user to select the type of
response required. Also parameters maybe set to give an accurate representation of lift
door timings, furthermore parameters may be set to measure accurately against times set,
for Optimum performance. All these parameters can be found in the menu ETA Setup.
The Despatcherless system operates whereby one lift becomes the Master of the group.
The decision of who is master is based upon the lowest lift number of the lifts that are
connected. If two lifts have the same lift number an error will be recorded in the fault
logger. Correct setting of the lift numbers i.e. parameter MY LIFT NUMBER in System
Details will ensure trouble free operation. If the Master is removed from operation for any
reason, then service continues since another lift will take over control, and this passing
control would continue up to the last car remaining.
The Master receives information from each lift and calculates an estimated time of arrival
for each lift to every call. The Master then allocates calls to each lift based upon the
ETA’s. The calls are despatched and updated many times a second. Homing calls are also
controlled by the Master and lifts are despatched to the homing floors based upon the
nearest, as and when required.
45
30.1) Skycom Group Algorithms
1) UP CALLS UP PEAK
When the number of up landing calls within the lift system is greater than the UP
PEAK threshold(typically half the number of floors). The SKYCOM detects an UP
CALLS UP PEAK condition and reacts by strategically parking lifts within the
Group, to give a faster response to the likelihood of further up calls. It achieves
this by detecting the lowest up call and parking the available lifts from this floor
upwards in anticipation.
2) DN CALLS DN PEAK
When the number of dn landing calls within the lift system is greater than the DN
PEAK threshold(typically half the number of floors). The SKYCOM detects a DN
CALLS DN PEAK condition and reacts by strategically parking lifts within the
Group, to give a faster response to the likelihood of further dn calls. It achieves this
by detecting the highest dn call and parking the available lifts from this floor
downwards in anticipation.
46
31) Communications
The Skycom has been designed with many types of on board communications. These
different types of communications allow a wide range of uses fro interfacing to the
processor. Details of typical uses for these are detailed below:-
The CAN communication ports provide interface to a range of serial products including
ILE Serial Speech Unit and Indicators. Also communications between lifts, specific drives,
and ILE Shaft Encoder are carried out over the CAN bus. Below is detailed the uses of the
CAN buses:-
CAN 1 CAN 2 CAN 3
RS232
PERSONAL
ORGANISER
P.C./LAP
TOP
MODEM /
WIRELESS
MODEM
31.3) RS485 Communications
RS485
DEDICATED
DRIVE
CONTROL
47
32) CAN 1 Fieldbus Connection Variations
The CAN fieldbus consists of two wires named CAN HIGH (CANH) and CAN
LOW (CANL). These two wires carry all the serial information to the ILE serial
products, and must be wired correctly for proper operation of the CAN fieldbus. In
the event of a wiring error however, they can withstand short circuits to either
+24V supply or 0V supply.
It is vital for correct operation that the bus terminators provided are connected to
either end of the CAN fieldbus as shown below. These terminators are simply
resistors of value 120Ω which are used to match the impedance of the cable.
CANH
NOTE:- FOR OPTIMUM PERFORMANCE,
USE TWISTED PAIR CABLE.
TERMINATOR TERMINATOR
120Ω 120Ω
CANL
3.3) Bus incorporating Micro Processor & CAN1 landing devices only
When there are no devices in the lift car, the micro processor is positioned at the
beginning of the bus, therefore one terminator must be placed at the control unit or
as close as possible to it. The other terminator must be placed at the other end of
the bus, or as close as possible to the last device as shown.
CAN H
µ
CAN L
Processor
TERMINATOR DIGITAL
120Ω INDICATOR
DIGITAL
INDICATOR
NOTE:- FOR OPTIMUM
PERFORMANCE, USE TWISTED
PAIR CABLE. DIGITAL
INDICATOR
DIGITAL
INDICATOR
TERMINATOR
120Ω
48
32.4) Bus incorporating Micro Processor & CAN 1 lift car device(s) only.
When there are no devices on the lift landing, the micro processor is positioned at
the beginning of the bus, therefore one terminator must be placed at the control unit
or as close as possible to it. The other terminator must be placed at the other end of
the bus, or as close as possible to the last device as shown.
TERMINATOR
120Ω
SPEECH
UNIT /
DIGITAL
INDICATOR
NOTE:- FOR OPTIMUM
PERFORMANCE, USE TWISTED PAIR
CABLE.
TERMINATOR
120Ω
CAN H
µ
Processor CAN L
32.5) Bus incorporating Micro Processor, CAN 1 lift car & landing device(s).
When there are devices on the lift landings and in the lift car , the Micro Processor
is positioned in the middle of the bus, therefore the terminators must be placed as
close as possible to the last devices as shown below.
TERMINATOR
LIFT CAR WIRING 120Ω SPEECH
AND TRAILING UNIT /
CABLES DIGITAL
INDICATOR
CAN H
µ
Processor CAN L
DIGITAL
INDICATOR
NOTE:- FOR OPTIMUM
PERFORMANCE, USE TWISTED PAIR
CABLE.
DIGITAL
LIFT SHAFT INDICATOR
WIRING
DIGITAL
INDICATOR
TERMINATOR
120Ω
49
32.6) CAN fieldbus fault finding
The CAN fieldbus driver components that reside on each of the serial products are very
robust, as they can withstand short circuits to each other (CH to CL), and short circuits to
either supply rail i.e. 0V & 24V. However they are not indestructible, and the fault finding
procedure below, is intended for the rare case that one or more driver components may
have got damaged, on one or more of the serial products.
Firstly if there is a fault, the chance of anything working correctly on the bus is rare, and
the majority of the time communication will cease.
To identify a fault on the bus is quite simple, as the LED indication on each of the boards
will flash in a specific way to indicate a CAN bus fault. The “LOOP” light LED, which is
“GREEN” in colour will flash faster than normal to indicate a CAN bus fault. The Led
should flash “ON” at a rate of once per 2 seconds if normal and once per 0.2 second if
there is a fault.
The “RED” LED “COMMS” may be flashing to indicate that it is trying to establish
communications.
This procedure should be repeated for all devices on the bus, until all faulty devices have
been identified.
Faulty devices cannot be repaired easily on site and should be returned to ILE for repair.
50
33) ILE SERIAL DIGITAL INDICATOR
LED indication is provided to indicate processor running and communication with the
micro processor.
The unit may have up to 48 floors, many messages and features, and 32 user defined
characters. These user defined characters may be used where a special floor designation is
required. Messages and floor positions may be typed as required. Direction arrows, Hall
Lanterns and user defined characters may be custom made as required.
Connections:- CL CH
These are the CAN communication connections, CL = CAN LOW and CH = CAN HIGH.
It is important that these are wired correctly for successful communication, otherwise no
information will be passed to the unit.
Connections:-A B (RELAY)
These are volt-free connections to a normally open relay contact, which may be used to
connect to an arrival gong or other external device. The relay contact works differently for
indicators fitted in the car and landing.
The indicator in the lift car will operate the relay when the micro processor gives out a
HLR signal(i.e. slowing for a landing call). Also when the passing chime
parameter(General Parameters) is set the relay will operate when the lift is passing a floor.
The indicator on the landing will operate the relay when the micro processor gives out a
HLR signal(i.e. slowing for a landing call), and the floor position setting matches the lift
position. Therefore each indicator has to be set correctly for floor position for this to work
correctly.
33.3) Digital Indicator floor position settings for car and landing
51
Landing Indicator setup
If the operation of the relay is to be required for hall lantern / arrival gong output, the floor
position DIL switches (TENS /UNITS) need to be set to the floor position the indicator is
at, i.e. floor 5 = “05”.
Otherwise the operation of the relay can be inhibited by setting the floor position DIL
switches to “61”.
FLOOR
TENS UNITS
General
The digital indicator operates in conjunction with the micro processor. Floors/ messages
are selected depending upon the information sent to it by the micro processor. The micro
processor will store information set by the relevant parameters.
Direction Arrows
Direction arrows will scroll according to the direction of the lift. However with the
“Frozen Arrows Enable” parameter set, the direction arrows will only scroll while the lift
is in high speed. This has the advantage of showing that the lift is slowing in at a floor as
well as indicating direction.
Hall Lanterns
Hall lanterns will only be displayed at the floor the lift is slowing into or at. The hall
lantern is similar in appearance to a direction arrow except it is larger and overrides the
position indication on the display. The floor position switches need to be set correctly for
this operation see (5.5 Digital Indicator floor position settings for car and landing).
52
34) SPEECH SYNTHESISER
A mono earpiece is supplied and socket fitted so that the speech can be heard, for test
purposes, when the speaker is remote from the unit. A test speech link is fitted so that the
speech memory can be tested independent of the micro processor.
LED indication is provided to indicate processor running and communication with the
micro processor. Fitted as standard are 2 volume controls for Normal and Hush modes of
operation.
The unit may have up to 48 floors, many messages, separate messages also for doors
opening, doors closing, going up, going down and arrival gong.
Speech phrases are selected by linking together phrases, so that the users may create their
own messages according to their preference. Up to 5 phrases may be linked together for
any message annunciation and 3 for any floor annunciation.
Features have been included to enable the user to switch off speech in between floors,
arrival gong, direction on closing and mind the doors(if desired).
A feature has been included to enable the user to select Hush volume between specific
times of the 24 hour clock. This works in conjunction with the on board real time clock.
Otherwise an input can be used for Hush.
Connections:- CL CH
These are the CAN communication connections, CL = CAN LOW and CH = CAN HIGH.
It is important that these are wired correctly for successful communication, otherwise no
information will be passed to the unit.
53
34.2) Speech Synthesiser operation.
The speech synthesiser operates in conjunction with the micro processor. Phrases are
selected depending upon the information sent to it by the micro processor. The micro
processor will store information according to the parameter settings.
The micro processor will send a set of phrase references (referring to speech unit memory)
to make up a complete phrase. A complete phrase may consist of up to 5 phrase references.
Phrase references are sent from the control unit to the speech synthesiser to initiate a
speech message. If a floor position phrase is to be said, the phrase will only be said once at
the slowing point of the lift journey. If a main message is to be said, it will be repeated as
long as the input for the message is still on. The number of repeats will be 5 at different
interval times of 10, 15, 20, 25 & 30 seconds. If two or more messages inputs are on with
the same priority, all messages will be repeated in sequence 5 times at the specified
interval times.
Two way communication between the micro processor and speech unit provides feedback
for uses such as the door closing sequence. e.g. the operation is as follows:-
Depending upon the set-up of the parameters speech may or may not be inhibited during
lift travel i.e. on high speed.
With regards to the volume control, only one can be selected at any one time i.e. Hush or
Normal. Hush volume is usually required to select a different audible volume of speech at
specific times during the day, i.e. quieter at night time.
i) LOOP:- this flashes every second, indicating that the main micro
processor is running. (see also CAN fieldbus fault finding).
ii) COMMS:- this is illuminated when a message is being received or sent
in conjunction with the micro processor.
iii) BUSY:- this is illuminated when a phrase is being processed by the
speech processor.
Other Info
A position phrase is never said again until after another position has been announced.
54
34.3) Speech Synthesiser standard phrase list.
The list below is a selected list of phrases stored in the speech memory to create a standard
version of the most common phrases used. However, there are many more phrases in the
speech vocabulary, and International Lift Equipment will be only pleased to accommodate
alternative phrases if required.
Version:- SRS16F3
1) THIS LIFT IS OVERLOADED 65) 17
2) THIS LIFT IS OVERLOADED PLEASE REDUCE THE LOAD 66) 18
3) THIS LIFT IS OUT OF SERVICE 67) 19
4) THIS LIFT IS UNDER FIRE CONTROL OPERATION 68) 20
5) THIS LIFT IS UNDER EVACUATION CONTROL 69) 20X
6) THIS LIFT IS UNDER PRIORITY SERVICE 70) 30
7) THIS LIFT IS RETURNING 71) 30X
8) TO 72) 40
9) TO THE 73) 40X
10) THIS LIFT IS RETURNING UNDER FIRE SERVICE 74) 50
11) THIS LIFT IS RETURNING UNDER EVACUATION CONTROL 75) 50X
12) THIS LIFT IS RETURNING UNDER PRIORITY SERVICE 76) 60
13) 77) 1ST
14) THE ALARM HAS BEEN ACTIVATED 78) 2ND
15) PLEASE BE CALM YOU ARE QUITE SAFE, HELP IS ON ITS WAY 79) 3RD
16) PLEASE EXIT LIFT 80) 4TH
17) THIS LIFT IS UNDER SERVICE CONTROL *(SRS16F2) 81) 5TH
18) 82) 6TH
19) 83) 7TH
20) PLEASE MIND THE DOORS 84) 8TH
21) FRONT DOORS ARE OPENING 85) 9TH
22) FRONT DOORS ARE CLOSING 86)
23) REAR DOORS ARE OPENING 87) A
24) REAR DOORS ARE CLOSING 88) B
25) DOORS OPENING 89) C
26) DOORS CLOSING 90) D
27) STAND CLEAR DOORS CLOSING 91) E
28) STAND CLEAR OF THE DOORS 92) F
29) THIS LIFT IS GOING UP 93) G
30) THIS LIFT IS GOING DOWN 94) H
31) GOING UP 95) I
32) GOING DOWN 96) J
33) 97) K
34) 98) L
35) 99) M
36) 100) N
37) 101) O
38) 102) P
39) LOWERX *(SRS16F3) 103) Q
40) XFLOOR 104) R
41) FLOORX 105) S
42) XLEVEL 106) T
43) LEVELX 107) U
44) SUB BASEMENT 108) V
45) LOWER BASEMENT 109) W
46) BASEMENT 110) X
47) LOWER GROUND 111) Y
48) GROUND 112) Z
49) 1 113)
50) 2 114) PODIUM
51) 3 115) CAR PARK
52) 4 116) MEZZANINE
53) 5 117) KITCHEN
54) 6 118) SERVICE
55) 7 119) SHOP
56) 8 120) FRONT ACCESS
57) 9 121) REAR ACCESS
58) 10 122) MINUS
59) 11 123) BING (ARRIVAL GONG)
60) 12 124) BONG “”
61) 13 125) BING/BONG “” *(SRS16F2)
62) 14 126)
63) 15 127)
64) 16
Note:’*’Denotes Phrases Added for Each Version
55
35) SKYCOM Serial Indicator / Speech Unit Message Priorities
When the serial Indicator and Speech Unit messages are controlled from the SKYCOM micro
processor i.e. Message 7 (Processor Specific), the following message priorities are used:-
1) INSPECTION CONTROL
2) LIFT 110% LOADED
3) FIRE CONTROL
4) EVACUATION CONTROL
5) EMERGENCY SUPPLY
6) SECURITY SERVICE
7) PRIORITY SERVICE 1
8) PRIORITY SERVICE 2
9) PRIORITY SERVICE 3
10) SERVICE CONTROL
11) LIFT 90% LOADED
12) CUSTOMISED OUT OF SERVICE
13) ALARM ACTIVATED
Notes:-
1) The Customised Out of Service is the indication settable by the Out of Service
Setup, i.e. configured for a number of different failures/service modes.
2) If message 7(processor specific) is not used the messages maybe customised and
prioritised as required.
56
36) IO INPUT TYPES LU1 UP lan calls
LU2,
NO_INPUT, LU3,
FAST_PX, LU4,
PXU, LU5,
PXD, LU6,
STR, LU7,
MSU, LU8,
MSD, LU9,
RSU, LU10,
RSD, LU11,
FRONT_DOP, LU12,
FRONT_SE, LU13,
FRONT_DLR, LU14,
FRONT_DCP, LU15,
REAR_DOP, LU16,
REAR_SE, LU17,
REAR_DLR, LU18,
REAR_DCP, LU19,
ERET1, LU20,
ERET2, LU21,
ERET3, LU22,
LW90, LU23,
LW110, LU24,
SERV, LU25,
FIRE, LU26,
SECU_SERV, LU27,
THERM, LU28,
LU29,
EMER, LU30,
CARL, LU31,
LANL, LU32,
TEST_SWITCH, LU33,
TEST_OPEN, LU34,
TEST_CLOSE, LU35,
TEST_UP, LU36,
TEST_DN, LU37,
DOL, LU38,
DCL, LU39,
DOC, LU40,
LU41,
ALARM, LU42,
EVACUATION, LU43,
EMER_SUPPLY, LU44,
SPEECH_MSG1, LU45,
SPEECH_MSG2, LU46,
SPEECH_MSG3, LU47,
SPEECH_MSG4, LU48
SPEECH_MSG5, LD1 DN lan calls
SPEECH_MSG6, LD2,
SPEECH_HUSH, LD3,
IND_MSG1, LD4,
IND_MSG2, LD5,
IND_MSG3, LD6,
IND_MSG4, LD7,
IND_MSG5, LD8,
IND_MSG6 LD9,
LD10,
LD11,
LD12,
LD13,
57
LD14, CP27,
LD15, CP28,
LD16, CP29,
LD17, CP30,
LD18, CP31,
LD19, CP32,
LD20, CP33,
LD21, CP34,
LD22, CP35,
LD23, CP36,
LD24, CP37,
LD25, CP38,
LD26, CP39,
LD27, CP40,
LD28, CP41,
LD29, CP42,
LD30, CP43,
LD31, CP44,
LD32, CP45,
LD33, CP46,
LD34, CP47,
LD35, CP48
LD36, };
LD37,
LD38,
LD39,
LD40,
LD41,
LD42,
LD43,
LD44,
LD45,
LD46,
LD47,
LD48,
CP1. Car Calls
CP2,
CP3,
CP4,
CP5,
CP6,
CP7,
CP8,
CP9,
CP10,
CP11,
CP12,
CP13,
CP14,
CP15,
CP16,
CP17,
CP18,
CP19,
CP20,
CP21,
CP22,
CP23,
CP24,
CP25,
CP26,
58
37) IO OUTPUT TYPES DNR,
DCR,
NO_OUTPUT, DOR,
PI1, NUG,
PI2, HSR,
PI3, HS2,
PI4, LSR,
PI5, RELEV,
PI6, ADV_OPEN,
PI7, STAR,
PI8, DELTA,
PI9,
PI10, STP_1STVANE,
STP_2NDVANE,
PI11, BR_LIFT_REL,
PI12, DRV_ENABLE,
PI13, QUICK_SLOW,
PI14,
PI15, DRV_ZERO_SP,
PI16, DRV_TOP_SP,
PI17, DRV_MED_SP,
PI18, DRV_TST_LEV,
PI19,
PI20, DRV_BIN_SP5,
DRV_BIN_SP6,
PI21, DRV_BIN_SP7,
PI22,
PI23, OSI,
PI24, OLI,
PI25, FIRE_IND,
PI26, TEST_IND,
PI27, LW90_IND,
PI28,
PI29, RAMP_CUT_OFF,
PI30, GATE_OP_WARN,
APB_BUSY,
PI31, LOCK_ALARM,
PI32, CHIME,
PI33,
PI34, LOCK_TIP_HI,
PI35, LOCK_TIP_LO,
PI36, START_FAIL,
PI37, STUCK_BFLRS,
PI38, SE_HELD,
PI39, DOP_HELD,
PI40, DOOR_OP_PROT,
DOOR_CL_PROT,
PI41, GATE_LCK_FLT
PI42,
PI43, HLU1, Hall lanterns UP
PI44, HLU2,
PI45, HLU3,
PI46, HLU4,
PI47, HLU5,
PI48 HLU6,
HLU7,
IU, HLU8,
ID, HLU9,
HLR, HLU10,
HLU11,
UPR, HLU12,
59
HLU13,
HLU14,
HLU15,
HLU16,
HLU17,
HLU18,
HLU19,
HLU20,
HLU21,
HLU22,
HLU23,
HLU24,
HLD1, Hall Lanterns DN
HLD2,
HLD3,
HLD4,
HLD5,
HLD6,
HLD7,
HLD8,
HLD9,
HLD10,
HLD11,
HLD12,
HLD13,
HLD14,
HLD15,
HLD16,
HLD17,
HLD18,
HLD19,
HLD20,
HLD21,
HLD22,
HLD23,
HLD24