IJCRT2305473
IJCRT2305473
IJCRT2305473
org © 2023 IJCRT | Volume 11, Issue 5 May 2023 | ISSN: 2320-2882
Abstract: The main aim of our project work is to develop a MATLAB based Simulation model for analyzing 3- phase symmetrical
and unsymmetrical faults. Generally, these faults are occurred in the long transmission line system such as single line to ground
fault (L-G), double line to ground (2L-G), triple line to ground fault (3LG) and Line to line fault (L-L). Fault analysis for different
sorts of faults has been done and it impacts are appeared in simulation output e.g. voltage, current. This research approaches to the
MATLAB software in which transmission line modal is simulated. The analysis will be based on a 110KV, 100km, 50HZ 3 Phase
Transmission Line deigned for 500KVA. The system behavior in case of fault and fault current limitation techniques are also studied
and developed in this project.
conductor and the insulation. The insulator loses the insulating property due to flashover. C. Effects of electrical faults Over-current
flow: when electrical faults occur in the system, the low impedance path is results to flow of the fault current. A high amount of the
current is drawing from the power supply causes tripping of the relay, damaging the electrical equipment. Danger to operating
personnel: occurrence of electrical faults may cause shocks to the individual. The probability of the shock is depending upon the
amount of the currents and voltages at the fault point and even may leads to death. Equipment loss: due to high amount of current
flow in the line during the faults, the components of the electrical systems may burn which results in the loss of the electrical
equipment. Sometimes fire also produces which completely burnt the devices.
III. OBJECTIVES
Project has bellow design objectives that should be satisfied at the end of the project.
Understanding the design and analysis of fault current levels under different kind of symmetrical and unsymmetrical faults.
Based on fault current level design of reactors and circuit breaker trip circuit is an important part of this project.
Analysis of power transfer efficiency and voltage regulation of line for performance analysis should also be done in this project.
V. BLOCK DIAGRAM
VII. CALCULATION
Calculation of selected parameters for project .
System voltage rating = 110KV, 3 Ph
System frequency = 50HZ
System power rating = 5MVA
Line current = Power / Line voltage
= 5MVA/110KV
= 45.45 Amps = Phase current (3ph, 3 wire line)
Apparent power: S = 5MVA
Active power: P = V*I*Cos(Ø)
consider power factor = 0.85
VIII. RESULT:
6.1 Three Phase To Ground Fault Now simulation and modeling on three phases to ground fault occurs their three phases is short
to the ground. When the magnitude of the faults current line are higher than the normal input current and the voltage are change on
the magnitude is zero and the fault the impedance is not necessary zero and output waveform shows the gradually rise of current
where three phases to ground fault occur on transmission line. Figure: 6.1 three phase fault current & voltage waveform © Daffodil
International University 36 In this actual case, the Distribution system model is runs for a Three Phase to Ground Fault. The simulation
is done for 0.05 sec, so that the waveforms can be seen more clearly. The sampling frequency is taken to be 50 Hz. The system
voltage is taken as 11 kV and the line length is taken as 300 kms, with fault occurring at 150 kms. Fault is started at 0.3 secs. These
parameters have been kept constant for other test cases as well. Indicates the current and voltage waveforms for the given
specifications. Upon injecting these signals to the relay it has been seen that the relay trips after 45 ms and the status of its coil is
shown in the simulated results. As this is a self-reset relay, the trip status comes back to 0 upon clearing the fault, but for a manual
reset relay, it stays 1 till the reset button is pressed manually. The proposed matlab model can be ran standalone or on the GUI to
view the plots.
6.2 Double Line to Ground Fault Now simulation and modeling on double line to ground fault occurs their two phases is short to
the ground. When the magnitude of the faults current line are higher than the normal input current and the voltage are change on the
magnitude is zero and the fault the impedance is not necessary zero and output waveform shows the gradually rise of current where
2L-G fault occur on transmission line. Figure: 6.2 Double Line to Ground Fault current & voltage Waveform from scope © Daffodil
International University 37 In this actual case, the Distribution system model is runs for a line-line and ground Fault. The simulation
is done for 0.05 sec, so that the waveforms can be seen more clearly. The sampling frequency is taken to be 50 Hz. The system
voltage is taken as 11 kV and the line length is taken as 300 kms, with fault occurring at 150 kms. Fault is started at 0.3 secs. There
are indicates the current and voltage waveforms for the given specifications. Upon injecting these signals to the relay it has been seen
that the relay trips after 45 ms and the status of its coil is shown in the simulated results. As this is a self-reset relay, the trip status
comes back to 0 upon clearing the fault, but for a manual reset relay, it stays 1 till the reset button is pressed manually. The proposed
matlab model can be ran standalone or on the GUI to view the plots. 6.3 Line to Ground FAULT Here I have simulation and modeling
on L-G fault occurs their one phase is short to the ground and the fault the impedance is not zero. When their output waveform shows
the rise of current on L-G fault occurs on transmission line. Figure:
6.3 L-G fault Matlab current & voltage Waveform In this actual case, the Distribution system model is runs for a Line to ground
Fault. The simulation is done for 0.05 sec, so that the waveforms can be seen more clearly. The sampling frequency is taken to be 50
Hz. The system voltage is taken as 11kV and the line length is taken as 300 kms, with fault occurring at 150 kms. Fault is © Daffodil
International University 38 started at 0.3. These parameters have been kept constant for other test cases as well. There are indicates
the current and voltage waveforms for the given specifications. Upon injecting these signals to the relay it has been seen that the relay
trips after 45 ms and the status of its coil is shown in the simulated results. As this is a self-reset relay, the trip status comes back to
0 upon clearing the fault, but for a manual reset relay, it stays 1 till the reset button is pressed manually. The proposed matlab model
can be ran standalone or on the GUI to view the plots.
6.4 Three Phase To Ground Fault with Transformer Now simulation and modeling on three phases to ground fault occurs their
three phases is short to the ground. When the magnitude of the faults current line are higher than the normal input current and the
voltage are change on the magnitude is zero and the fault the impedance is not necessary zero and output waveform shows the
gradually rise of current where three phases to ground fault occur on transmission line. I see the same occurs in the transmission lines
connected to transformer and with to transformer. Figure: 6.4 Three phase to ground fault © Daffodil International University 39 In
this actual case, the Distribution system model is runs for a three phase to ground fault. The simulation is done for 0.05 sec, so that
the waveforms can be seen more clearly. The sampling frequency is taken to be 50 Hz. The system voltage is taken as 11kV and the
line length is taken as 300 kms, with fault occurring at 150 kms.
Fault is started at 0.3. These parameters have been kept constant for other test cases as well. There are indicates the current and
voltage waveforms for the given specifications. Upon injecting these signals to the relay it has been seen that the relay trips after 45
ms and the status of its coil is shown in the simulated results. As this is a self-reset relay, the trip status comes back to 0 upon clearing
the fault, but for a manual reset relay, it stays 1 till the reset button is pressed manually. The proposed matlab model can be ran
standalone or on the GUI to view the plots.
6.5 Double Line To Ground Fault Now simulation and modeling on double line to ground fault occurs their two phases is short
to the ground. When the magnitude of the faults current line are higher than the normal input current and the voltage are not change
on magnitude and the fault the impedance is not necessary zero and output waveform shows the gradually rise of current where
2L-G fault occur on transmission line. I see the same occurs in the transmission lines connected to transformer and with to
transformer. © Daffodil International University 40 Figure: 6.5 Line-Line-ground Fault In this actual case, the Distribution system
model is runs for a Line-Line-ground Fault. The simulation is done for 0.05 sec, so that the waveforms can be seen more clearly. The
sampling frequency is taken to be 50 Hz. The system voltage is taken as 11kV and the line length is taken as 300 kms, with fault
occurring at 150 kms. Fault is started at 0.3. These parameters have been kept constant for other test cases as well. There are indicates
the current and voltage waveforms for the given specifications. Upon injecting these signals to the relay it has been seen that the relay
trips after 45 ms and the status of its coil is shown in the simulated results.
IJCRT2305473 International Journal of Creative Research Thoughts (IJCRT) www.ijcrt.org d597
www.ijcrt.org © 2023 IJCRT | Volume 11, Issue 5 May 2023 | ISSN: 2320-2882
As this is a self-reset relay, the trip status comes back to 0 upon clearing the fault, but for a manual reset relay, it stays 1 till the
reset button is pressed manually. The proposed matlab model can be ran standalone or on the GUI to view the plots. 6.6 L-G FAUL
Here I have simulation and modeling on L-G fault occurs their one phase is short to the ground and the fault the impedance is not
zero. When their output waveform shows the rise of current on L-G fault occurs on transmission line. I see the same occurs in the
transmission lines connected to transformer and without to transformer. © Daffodil International University 41 Figure: 6.6 L-G
FAULT In this actual case, the Distribution system model is runs for a L-G FAULT. The simulation is done for 0.05 sec, so that the
waveforms can be seen more clearly. The sampling frequency is taken to be 50 Hz.
The system voltage is taken as 11kV and the line length is taken as 300 kms, with fault occurring at 150 kms. Fault is started at
0.3. These parameters have been kept constant for other test cases as well. There are indicates the current and voltage waveforms for
the given specifications. Upon injecting these signals to the relay it has been seen that the relay trips after 45 ms and the status of its
coil is shown in the simulated results. As this is a self-reset relay, the trip status comes back to 0 upon clearing the fault, but for a
manual reset relay, it stays 1 till the reset button is pressed manually. The proposed matlab model can be ran standalone or on the
GUI to view the plots
X. REFERENCES
[1] C. Vijaya Tharani, M. Nandini, R. Sundar and Dr. K. Nithiyananthan., “MATLAB based simulation model for three phase
power system network,” Conference Proceedings of ICAET, pp.8-22, Chennai, 2016.
[2] S. Mahapatra and M. Singh, “Analysis of symmetrical fault in IEEE 14 bus system for enhancing over current protection
scheme ,” International Journal of Future Generation Communication and Networking, Volume 9, Issue 4, pp. 51-62, 2016.
[3] Swapnil C. Naghate, Saurab M. Dhuldhar and Ashvani B. Nagdewate, “Transmission line fault analysis by using MATLAB
simulation,” International Journal of Engineering Sciences and Research Technology, Volume 4, Issue 2, pp. 330-333, 2015.
[4] S. Karekar and T. Barik, “A modelling of 440 KV EHV transmission line faults identified and analysis by using MATLAB ,”
IJAREEIE, Volume 5, Issue 3, pp. 1242-1249, , March 2016.
[5] A. Sharique, A.Sharma, Deepika and P. Rajput, “Fault Detection in Transmission line Using MATLAB,” 2nd National
Conference in Intelligent Computing & Communications, ISBN: 9788175157538
[6] A.B. Alizadeh, M. Khederzadeh and R. Razzaghi, “Fault detection during power swing in thyristor-controlled series capacitor-
compensated transmission lines,” Electric Power Systems Research, vol. 187, 2020.
[7] A. Ghorbani, H. Mehrjerdi, , H. Heydari and S. Ghanimati, “A pilot protection algorithm for TCSC compensated transmission
line with accurate fault location capability,” International Journal of Electrical Power and Energy Systems, vol. 122, 2020.
[8]I. Ibrahim, “Fault detection and location of power transmission lines using intelligent distance relay,” International Journal of
Power Electronics and Drive Systems. Vol. 11, pp. 726-734
Websites:
[1] http://www.ijrucc.org
[2] http://www.learningaboutelectronics.com
[3] https://www.arduino.cc
[4] https://github.com