Mitsubishi Catalogue VRF-21
Mitsubishi Catalogue VRF-21
Mitsubishi Catalogue VRF-21
Y-series
Specifications
Model
Power source
PUMY-CP100VKM PUMY-CP125VKM
1-phase 220-230-240 V, 50 Hz; 1-phase 220 V, 60 Hz
PUMY-CP140VKM
PUCY/PUHY
Outdoor/Heat
Cooling capacity *1 kW 11.2 14.0 15.5
(Nominal) *1 BTU/h 38,200 47,800 52,900 These models are provided with
Power input kW 2.80 3.84 4.70
Current input A 12.99-12.42-11.90, 12.99 17.81-17.04-16.33, 17.81 21.80-20.85-19.98, 21.80 high-performance inverter compressors to
Outdoorsource
EER kW/kW 4.00 3.65 3.30
Temp. range of Indoor temp. W.B. 15 to 24°C (59 to 75°F)
achieve high energy-saving performance.
cooling Outdoor temp.
Indoor unit Total capacity
D.B. 10 to 52°C (50 to 126°F)
50 to 130% of outdoor unit capacity
A wide lineup of models with up to 60 HP
can be applied to various usage.
unit unit
connectable Model/ CITY MULTI
15–125/7 15–140/10 15–140/12
Quantity
Sound pressure level *2
dB <A> 52/- 53/- 54/-
(measured in anechoic room)
Refrigerant piping Liquid pipe mm (in.) 9.52 (3/8)
diameter Gas pipe mm (in.) 15.88 (5/8)
Fan Type x Quantity Propeller Fan × 1
Air flow rate m3/min 78.8
L/s 1,313
cfm 2,782
*3 Motor output kW 0.20 x 1
Compressor Type x Quantity Twin rotary hermetic compressor × 1
Starting method Inverter
Indoor unit
Motor output kW 2.2 2.7 3.0
External finish Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1
External dimension H x W x D mm 981 × 1050 × 330 (+25)
in. 38-5/8 × 41-3/8 × 13 (+1)
Protection High pressure protection High pressure switch
devices Inverter circuit
Overcurrent detection, Overheat detection (Heat Sink thermistor)
(COMP./FAN)
Compressor Compressor thermistor, Overcurrent detection
Fan motor Overheating, Voltage protection
Refrigerant Type x original charge R410A 2.9kg
Net weight kg (lbs) 86 (190) *4
Heat exchanger Micro Slit Fin and Copper tube
Defrosting method ―
Optional parts Joint: CMY-Y62-G-E, Header: CMY-Y64/68-G-E
Remote Controller
Lossnay
Notes:
*1 Nominal conditions
39 40