TRANSFORMER FULL LOAD CURRENT RATINGS

Three Phase 600V Class


To calculate full load current, use this formula: To calculate KVA, use this formula:
Amps = KVA ÷ Volts ÷ 1.732 x 1000 KVA = Volts x Amps x 1.732 ÷ 1000
GENERAL PURPOSE DRIVE ISOLATION
VOLTAGE VOLTAGE
KVA KVA
208 240 480 575 600 230 460
1 2.8 2.4 1.2 1.0 1.0 7.5 18.8 9.4
2 5.6 4.8 2.4 2.0 1.9 11 27.6 13.8
3 8.3 7.2 3.6 3.0 2.9 14 35.1 17.6
5 13.9 12.0 6.0 5.0 4.8 20 50.2 25.1
6 16.7 14.4 7.2 6.0 5.8 27 67.8 33.9
7.5 20.8 18.0 9.0 7.5 7.2 34 85.3 42.7
9 25.0 21.7 10.8 9.0 8.7 40 100.4 50.2
10 27.8 24.1 12.0 10.0 9.6 51 128.0 64.0
15 41.6 36.1 18.0 15.1 14.4 63 158.1 79.1
30 83.3 72.2 36.1 30.1 28.9 75 188.3 94.1
45 124.9 108.3 54.1 45.2 43.3 93 233.5 116.7
75 208.2 180.4 90.2 75.3 72.2 118 296.2 148.1
112.5 312.3 270.6 135.3 113.0 108.3 145 364.0 182.0
150 416.4 360.9 180.4 150.6 144.3 175 439.3 219.7
225 624.6 541.3 270.6 225.9 216.5 220 552.3 276.1
300 832.7 721.7 360.9 301.2 288.7 275 690.3 345.2
500 1387.9 1202.8 601.4 502.1 481.1 330 828.4 414.2
750 2081.9 1804.3 902.1 753.1 721.7 440 1104.5 552.3
1000 2775.8 2405.7 1202.8 1004.1 962.3 550 1380.7 690.3
1500 4163.7 3608.5 1804.3 1506.2 1443.4 660 1656.8 828.4
2000 - - 2405.7 2008.2 1924.6 770 1932.9 966.5
2500 - - 3007.1 2510.3 2405.7 880 2209.1 1104.5
3000 - - 3608.5 3012.4 2886.8 990 2485.2 1242.6
3750 - - 4510.7 3765.4 3608.5
Fields containing " - " indicate the current value exceeds the capacity of some current-carrying
components such as bushings, cables, bussing, etc.

Single Phase 600V Class


To calculate full load current, use this formula: To calculate KVA, use this formula:
Amps = KVA ÷ Volts x 1000 KVA = Volts x Amps ÷ 1000

VOLTAGE
KVA
120 240 277 480 600
10 83.3 41.7 36.1 20.8 16.7
15 125.0 62.5 54.2 31.3 25.0
25 208.3 104.2 90.3 52.1 41.7
37.5 312.5 156.3 135.4 78.1 62.5
50 416.7 208.3 180.5 104.2 83.3 Alfa Transformer
75 625.0 312.5 270.8 156.3 125.0 6107 South Zero Street
100 833.3 416.7 361.0 208.3 166.7 Fort Smith, AR 72906
167 1391.7 695.8 602.9 347.9 278.3 Ph 479.646.1668
250 2083.3 1041.7 902.5 520.8 416.7 www.alfatransformer.com
333 2775.0 1387.5 1202.2 693.8 555.0
500 4166.7 2083.3 1805.1 1041.7 833.3 c:\xampp743\htdocs\alfa_new_site\Excel