Gasmonitor Manual 1
Gasmonitor Manual 1
M07210
Issue 5
February 2006
Gasmonitor + Operation and Installation Preliminary
Notes:
This product has been tested and found to comply with the
European Directive 89/336/EEC and the EMC requirements of
EN50270.
Issue 5
Gasmonitor+ Operation & Installation Contents
CONTENTS
CONTENTS
General 1
System Overview 1
What is Gasmonitor+? 1
What are the Main Components? 2
Specification Sheet (Sample Only) 5
HARDWARE
19” Control Rack 7
Description 7
Mounting Detail 9
Electrical Connections 10
Jumper Settings 10
Display Module 12
Description 12
Routine Operation 13
Common Alarm Relay and LED Operation 14
Dedicated Audible and Visual Alarm Drive Operation 15
Voted Relay Operation 16
Fault Messages 16
Mounting Detail 17
Electrical Connections 18
Issue 5
Gasmonitor+ Operation & Installation Contents
CONTENTS
Page No.
Input/Output Module 32
Description 32
Mounting Detail 34
Electrical Connections 35
Relay Module 38
Description 38
Mounting Detail 39
Electrical Connections (General) 40
Electrical Connections (Individual Channel Alarms – Gas Only) 41
Electrical Connections (Individual Channel Alarms – Fire Only) 42
Electrical Connections (Voted Relays) 43
Page No.
Issue 5
Gasmonitor+ Operation & Installation Contents
CONTENTS
Power Distribution 44
Description 44
Routine Operation 45
Mounting Detail 46
Power Module 46
Power Supply Unit 48
Batteries 50
Electrical Connections 51
Calculation of Power Supply Requirements and Battery Backup 52
Typical Power Consumption of Gasmonitor+ Modules 52
Example Power/Battery Backup Calculation 53
FIELD DEVICES
General 55
Issue 5
Gasmonitor+ Operation & Installation Contents
CONTENTS
Setting to Work 72
Calibration 72
Routine Functional Testing 73
Set-up and Operation: TXgard IS 75
General 75
Cabling Requirement 75
Earthing 76
Universal Gas Input Card Jumper Settings 77
Electrical Connections 78
Setting to Work 83
Calibration 83
Routine Functional Testing 84
Set-up and Operation: TXgard D 87
General 87
Cabling Requirement 87
Earthing 88
Universal Gas Input Card Jumper Settings 88
Setting to Work 89
Calibration 89
Routine Functional Testing 90
Issue 5
Gasmonitor+ Operation & Installation Contents
CONTENTS
Page No.
APPENDICES
A Display Module Menu Operation 107
LIST OF ILLUSTRATIONS
Figure Page No.
1 Gasmonitor+ Block System Schematic 4
2 Specification Sheet Example 6
3 Gasmonitor+ General Isometric View 8
4 19” Rack Mounting Detail 9
5 19” Control Rack Electrical Connections Front/Rear View 11
6 Display Module General View 12
7 Display Module Mounting Detail 17
8 Display Module Electrical Connections 18
9 Universal Gas Input Card General View 19
10 Universal Gas Input Card Mounting Detail 23
11 Universal Gas Input Card Jumper Locations 25
12 Twin Zone Fire Card General View 26
13 Twin Zone Fire Card Mounting Detail 29
14 Twin Zone Fire Card Jumper Locations 31
15 Input/Output Module General View 33
16 Input/Output Module Mounting Detail 34
Issue 5
Gasmonitor+ Operation & Installation Contents
CONTENTS
Issue 5
Gasmonitor+ Operation & Installation Introduction
1 INTRODUCTION
1.1 General
This manual describes the installation, configuration and operation of a
Gasmonitor+ gas and fire detection system with serial number 0568GM or
INTRODUCTION
higher.
Systems with serial numbers lower than this may not include all the features
described in this manual.
A Gasmonitor+ gas and fire control system is normally fitted into a wall
mounted or floor standing control cabinet. The physical arrangement depends
on the size and complexity of the system, which is beyond the scope of this
manual.
This manual details the operation of Gasmonitor+ with a range of field devices
available from Crowcon. Other devices may be used as advised by Crowcon.
Gasmonitor+ is a 19” rack mounted gas and fire control system. It is designed
to control remote gas and fire detectors and raise audible/visual alarms should
pre-set alarm levels be exceeded.
Issue 5 1
Gasmonitor+ Operation & Installation Introduction
The alarm status of the remote detectors is displayed on the front panel of the
associated input card via LEDs. Actual readings of the gas concentration at
INTRODUCTION
each gas detector are displayed on a common Display Module mounted on the
left in each control rack.
The main components of a Gasmonitor+ gas and fire control system are:
Issue 5 2
Gasmonitor+ Operation & Installation Introduction
Relay Module
Flammable Gas Detectors
Toxic Gas Detectors
Fire Detectors
INTRODUCTION
Issue 5 3
Gasmonitor+ Operation & Installation Introduction
INTRODUCTION
Issue 5 4
Gasmonitor+ Operation & Installation Introduction
INTRODUCTION
Issue 5 5
Gasmonitor+ Operation & Installation Introduction
INTRODUCTION
Issue 5 6
Gasmonitor+ Operation & Installation Hardware
2 HARDWARE
2.1.1 Description
All Gasmonitor+ control cards are mounted in a 3U high, 19” rack. The rack
includes a drop down front panel, card guides and motherboard into which the
control cards are fitted. The drop down panel is held in place by three locking
screws located at the top of the panel.
Self adhesive labels are fitted to the front of the drop down panel detailing the
control card mounted behind that particular label. The labels are fitted with
pushbuttons that are wired to the control card in that position via a flexible
HARDWARE
connector.
The drop down front panel and motherboard are electrically bonded to the
chassis. This ensures that EMC/RFI regulations are met.
The Display Module is always fitted to the left of the control rack. Subsequent
slots are filled with either the Universal Gas Input Card or Twin Zone Fire
Input Card as required by the application.
Issue 5 7
Gasmonitor+ Operation & Installation Hardware
HARDWARE
Issue 5 8
Gasmonitor+ Operation & Installation Hardware
HARDWARE
The Input/Output module and the Power Supply are shown mounted at the
rear of the Gasmonitor+ rack. These can be removed and mounted in a more
suitable location during the system installation.
Issue 5 9
Gasmonitor+ Operation & Installation Hardware
All electrical connections to field equipment are made via the DIN rail
mounted modules mounted in the control cabinet (see later sections). These in
turn are connected to the control rack motherboard via ribbon cables. Power
connections are wired separately (see Power Distribution, Electrical
Connections, section 2.7.4).
All control cards are fitted with appropriate plugs that slot into mating sockets
on the motherboard when inserted into the rack.
Issue 5 10
Gasmonitor+ Operation & Installation Hardware
HARDWARE
Issue 5 11
Gasmonitor+ Operation & Installation Hardware
2.2.1 Description
Each Gasmonitor+ control rack is fitted with a Display Module that in normal
operation details the status of the control rack and provides local user control
of the system. Figure 6 gives a general view of the Display Module.
Issue 5 12
Gasmonitor+ Operation & Installation Hardware
The Display Module holds the systems configuration in battery backed RAM.
The majority of the system settings may be adjusted using the menu system,
e.g., calibration of individual channels or adjustment of alarm set points. For
details on how to make system configuration changes via the pushbutton on the
Display Module see Appendix A.
A PC may be connected to the RS232 port and using the SetGmon software
provided gives the user full access to all of the system settings. For SetGmon
installation and operation details please refer to Appendix B.
HARDWARE
the Display Module menu system is used for subsequent minor adjustments.
The Display Module controls the internal sounder, common alarm relays and
dedicated audible and visual alarm drives on the Input/Output Module (see
Input/Output Module, Description, section 2.5.1).
The four pushbuttons allow the user to navigate through the menu system
shown on the LCD display. The function of each pushbutton changes
depending on which menu is displayed. The function of each pushbutton is
shown adjacent to that pushbutton on the LCD display. For a detailed
explanation of all Display Module menus and pushbutton operations please
refer to Appendix A.
Issue 5 13
Gasmonitor+ Operation & Installation Hardware
The Display Module monitors the status of each gas and fire input card. Should
any input card detect an alarm or fault condition the relevant LED will
illuminate on the Display Module, the internal sounder and the appropriate
common alarm relay will operate.
Mixed gas and fire input cards in the same control rack share common LEDs
and alarm relays as follows:
Issue 5 14
Gasmonitor+ Operation & Installation Hardware
Pressing the RESET button on the Display Module silences the audible alarm.
If on pressing the RESET button, the alarm condition has cleared, the common
alarm relays will reset and the appropriate LED will turn off.
The Display Module can be used to drive audible and visual alarms mounted in
the field. Field connections are made at the Input/Output Module (see Figure
17).
HARDWARE
LEVEL 1 Any zone 1 fire detected Audible alarm drive 1
OR Press RESET to silence
Level 1 gas detected
LEVEL 2 Any zone 2 fire detected Audible alarm drive 2
OR Press RESET to silence
Level 2 gas detected
LEVEL 3 Any level 3 gas detected Audible alarm drive 3
Press RESET to silence
VIS Any zone fire detected Visual alarm drive
OR Can only be RESET once
alarm condition has cleared
Any gas level detected
Issue 5 15
Gasmonitor+ Operation & Installation Hardware
The operation of the relay is dependant upon the configuration, for example, a
relay may be set to operate given any 2 level 1 gas alarms being detected in a
control rack (i.e., 2 out of 16 voting). Other voting or grouping arrangements
are available (see Appendix B).
Should any input card be removed while the system is in normal operation then
the Display Module will indicate a ‘Card XX Fail’ (where XX is the position of
the control card in the rack), the internal sounder and common fault relay will
operate. To reset the system re-insert the input card and press RESET after
waiting 10 seconds.
If the main 24 VDC power supply is lost, the system automatically switches
over to the battery back-up (stand-by battery). The Display Module then
monitors the battery voltage until it has discharged to a point where any further
discharge will prevent the operation of the Gasmonitor+. At this stage, the
internal audible alarm is initiated (this can be accepted by pressing the RESET
button) and the display message changes to “DC IN nn.nn VOLTS”. If loss of
power continues, the battery isolation relay on the Input/Output Module
disconnects the stand-by battery from the Gasmonitor+ rack to prevent it from
being over-discharged and permanently damaged.
Issue 5 16
Gasmonitor+ Operation & Installation Hardware
The Display Module is mounted behind the drop down front panel of the
control rack in the leftmost position. It is held in position by four pins as shown
in Figure 7.
HARDWARE
Issue 5 17
Gasmonitor+ Operation & Installation Hardware
All connections are made via the Input/Output and Relay Modules. Refer to
Input/Output Module, Electrical Connections, section 2.5.3, and Relay Module,
Electrical Connections, section 2.6.3.
HARDWARE
Issue 5 18
Gasmonitor+ Operation & Installation Hardware
2.3.1 Description
The Universal Gas Input Card is used to power and control remote flammable
or toxic gas detectors. The control card has been designed to drive any of
Crowcon’s remote gas detectors but may be used to drive other devices given
advice from Crowcon. The type of gas monitored by the detector fitted to the
input card is labelled at the top of the front display.
Figure 9 gives a general view of the input card with the drop down front panel
of the control rack closed.
HARDWARE
Issue 5 19
Gasmonitor+ Operation & Installation Hardware
The Universal Gas Input Card includes three levels of gas alarm and fault
monitoring as standard. Three red LEDs indicate gas alarms (levels 1, 2 and 3)
and a single yellow LED indicates the fault alarm.
The bar graph provides the user with an immediate indication of the gas level
at the detector, in relation to the first alarm level.
The Universal Gas Input Card is able to drive individual channel relays
including 3 levels of gas alarm and a fault output. These relays are user
configurable (see Appendix A and B). The relays are mounted on optional
Relay Modules in the control cabinet (see Relay Module, Mounting Detail,
section 2.6.2).
Upon triggering an alarm the relevant LED will flash until the RESET button
on the Display Module has been pressed. If, on pressing the RESET button, the
alarm condition has cleared, the system resets. If not, then the alarm LED will
change from flashing to a steady state.
Once the alarm condition has cleared. Pressing the RESET button on the
Display Module will reset the LED.
Issue 5 20
Gasmonitor+ Operation & Installation Hardware
The bar graph provides operators with an approximate indication of gas levels
in the field. For flammable and toxic gas detectors the bar graph is scaled such
that no LEDs are lit when there is no gas present and all LEDs are lit when the
first level of alarm is reached. For oxygen detectors no LEDs are lit when
normal levels of oxygen are present at the detector, i.e., 20.9%vv. Should the
oxygen level fall or rise, a single LED on the bar graph will move down or up
from the centre of the bar graph which is scaled from level 1 alarm (oxygen
deficiency) to level 2 alarm (oxygen enrichment).
HARDWARE
The INHIBIT pushbutton is mounted on the drop down front panel. Pressing
the INHIBIT pushbutton on the input card and the RESET pushbutton on the
Display Module simultaneously places the input card into standby mode. This
is indicated by the Status LED remaining lit. In this state any alarm condition
detected by the input card is not transmitted to the Display Module and no
individual channel alarm relays can be activated. Pressing the INHIBIT
pushbutton alone returns the control card to normal operation.
The Universal Gas Input Card can drive optional individual channel relays
mounted on Relay Modules in the control cabinet (see Relay Module,
Mounting Detail, section 2.6.2). Outputs include gas alarm level 1, 2 and 3 and
fault.
Issue 5 21
Gasmonitor+ Operation & Installation Hardware
The Universal Gas Input Card is mounted behind the drop down front panel of
the control rack. Input cards slot into the control rack to the right of the Display
Module using the card guides provided and are locked into position by a lever
and catch. This is shown in Figure 10.
Issue 5 22
Gasmonitor+ Operation & Installation Hardware
Issue 5 23
Gasmonitor+ Operation & Installation Hardware
To remove or insert input cards the lever must be in position 1. Once the card
is inserted fully into the rack pushing the lever down into position 2 locks the
card into place.
The Universal Gas Input Card slots into the control rack. Electrical connections
are made via the motherboard to the Input/Output Module and Relay Modules
if fitted. All field connections are made via these modules.
LK3 adjusts the gain of the input amplifier of the control card. It is normally
set to STD. Should a detector/input card be calibrated to a gas which gives a
low signal when exposed to gas (e.g., pentane) then it may be necessary to set
LK3 to HIGH or V.HIGH. Contact Crowcon for advice on setting this link.
Incorrect positioning of LK3 will cause the CAL FAIL message to appear after
a calibration attempt.
Issue 5 24
Gasmonitor+ Operation & Installation Hardware
HARDWARE
Figure 11: Universal Gas Input Card Jumper Locations
Detector Type
24 V 24 V
Issue 5 25
Gasmonitor+ Operation & Installation Hardware
2.4.1 Description
The Twin Zone Fire Input Card is used to power and control conventional fire
detectors including ionisation, optical and heat detectors. The input card can
also be used to monitor manual alarm call points and unitised flame detectors.
Figure 12 gives a general view of the input card with the drop down front panel
of the control rack closed.
HARDWARE
Issue 5 26
Gasmonitor+ Operation & Installation Hardware
The Twin Zone Fire Input Card can monitor 2 loops of up to 20 conventional
fire detectors. Each loop is used to monitor a specific area called a Zone. Each
zone is monitored for fire alarms and loop faults (open and short circuit). These
are indicated on the front of the card.
Fire LEDs (red) and LOOP FAULT LEDs (yellow) to the left of the input card
show the status of detectors in zone 1, those on the right show the status of
zone 2.
The Twin Zone Fire Input Card is able to drive individual zone alarm relays for
fire and fault. These relays are user configurable (see Appendix A and B). The
relays are mounted on optional Relay Modules in the control cabinet (see Relay
Module, Description, section 2.6.1).
HARDWARE
2.4.2 Routine Operation
Upon triggering a fire alarm or fault alarm the relevant LEDs will illuminate.
If, on pressing the INHIBIT/RESET button on the Twin Zone Fire Input Card,
the alarm condition has cleared, the system resets. If not, then the alarm LED
will remain on.
Issue 5 27
Gasmonitor+ Operation & Installation Hardware
The INHIBIT pushbutton is mounted on the drop down front panel. Pressing
the INHIBIT pushbutton on the input card and the RESET pushbutton on the
Display Module simultaneously places the input card into standby mode. This
is indicated by the Status LED remaining lit. In this state any alarm condition
detected by the input card is not transmitted to the Display Module and no
individual channel or zone alarm relays can be activated. Pressing the INHIBIT
button alone returns the control card to normal operation.
The Twin Zone Fire Input Card can drive optional individual zone alarm relays
mounted on Relay Modules in the control cabinet. Outputs include fire
detected zone 1, fire detected zone 2, fault detected zone 1, fault detected zone
HARDWARE
Issue 5 28
Gasmonitor+ Operation & Installation Hardware
The Twin Zone Fire Input Card is mounted behind the drop down front panel
of the control rack. Input cards slot into the control rack to the right of the
Display Module using the card guides provided and are locked into position by
a lever and catch. This is shown in Figure 13.
HARDWARE
Issue 5 29
Gasmonitor+ Operation & Installation Hardware
To remove or insert input cards the lever must be in position 1. Once the card
is inserted fully into the rack pushing the lever down into position 2 locks the
card into place.
The Twin Zone Fire Input Card slots into the control rack. Electrical
connections are made via the motherboard to the Input/Output Module and
Relay Modules if fitted. All field connections are made via these modules. See
Input/Output Module, Electrical Connections, section 2.5.3, and Relay Module,
Electrical Connections, section 2.6.3.
Issue 5 30
Gasmonitor+ Operation & Installation Hardware
HARDWARE
Issue 5 31
Gasmonitor+ Operation & Installation Hardware
2.5.1 Description
Analogue outputs 4 - 20 mA or 1 - 5 V dc
Issue 5 32
Gasmonitor+ Operation & Installation Hardware
HARDWARE
Figure 15: Input/Output Module General View
Issue 5 33
Gasmonitor+ Operation & Installation Hardware
The IO Module is mounted on standard TS32 or TS35 DIN rail in the control
cabinet. Figure 16 gives overall mounting detail.
HARDWARE
Issue 5 34
Gasmonitor+ Operation & Installation Hardware
The IO Module is connected to the control rack motherboard via ribbon cable
as detailed in Figure 15. For details on motherboard connections see Figure 5.
HARDWARE
Issue 5 35
Gasmonitor+ Operation & Installation Hardware
HARDWARE
Issue 5 36
Gasmonitor+ Operation & Installation Hardware
All terminals are suitable for use with 0.5mm2 to 2.5mm2 cable.
For details on connecting field devices to the IO Module refer to the following
sections:
HARDWARE
Issue 5 37
Gasmonitor+ Operation & Installation Hardware
2.6.1 Description
The Relay Module includes 8 x DPCO (Double Pole Change Over) relays and
HARDWARE
A yellow LED next to each relay indicates the relay status (LED on =
energised, LED off = de-energised).
Issue 5 38
Gasmonitor+ Operation & Installation Hardware
Relay Modules are mounted on standard TS32 or TS35 DIN rail in the control
cabinet. Figure 19 gives the overall mounting detail.
HARDWARE
Issue 5 39
Gasmonitor+ Operation & Installation Hardware
The relay module is connected to the control rack motherboard via ribbon
cable. The maximum length of ribbon cable allowed is 10m.
All terminals are suitable for use with 0.5mm2 to 2.5mm2 cable.
Issue 5 40
Gasmonitor+ Operation & Installation Hardware
The Universal Gas Input Card can drive individual channel relays mounted on
the Relay Module (see Universal Gas Input Card, Routine Operation,
Individual Channel Alarm Relays, section 2.3.2.3). Figure 21 summarises the
connections.
HARDWARE
Issue 5 41
Gasmonitor+ Operation & Installation Hardware
The Twin Zone Fire Input Card can drive individual channel relays mounted on
the Relay Module (see Twin Zone Fire Input Card, Routine Operation,
Individual Channel and Zone Alarm Relays, section 2.4.2.3). Figure 22
summarises the connections.
HARDWARE
Issue 5 42
Gasmonitor+ Operation & Installation Hardware
The Display Module can drive individual Voted Relays mounted on the Relay
Module (see Display Module, Routine Operation, Voted Relay Operation,
section 2.2.2.3). Figure 23 summarises the connections.
HARDWARE
Issue 5 43
Gasmonitor+ Operation & Installation Hardware
2.7.1 Description
The Power Module is mounted in the control rack. It accepts a nominal 24Vdc
supply smoothes and filters it before distribution to control cards via the
motherboard.
The Power Module also holds system fuses and driving circuitry for dedicated
audible/visual field devices.
A Gasmonitor+ gas and fire system may be powered from a main supply of
100-260Vac, 50/60Hz. Depending upon the system configuration a 150W or
300W Power Supply Unit is mounted in the control cabinet and is used to
convert the main supply to 24Vdc (nominally). See Power Distribution,
Calculation of Power Supply Requirements and Battery Backup, Example
Power/Battery Backup Calculation, section 2.7.5, for calculating power supply
requirements.
Issue 5 44
Gasmonitor+ Operation & Installation Hardware
Each Gasmonitor+ control rack is supplied with two 12Vdc, 7Ah sealed lead
acid batteries (wired in series to provide a 24Vdc, 7Ah backup supply). The
available backup time depends on the configuration of the system. See Power
Distribution, Calculation of Power Supply Requirements and Battery Backup,
Example Power/Battery Backup Calculation Step 3, in section 2.7.5.2, for
typical backup calculations.
If the main ac power supply is lost, the system automatically switches over to
the stand-by battery operation.
The Display Module monitors the battery voltage until it has discharged to a
point where any further discharge will prevent the operation of the system. At
this stage, the internal audible alarm is initiated (this can be accepted by
HARDWARE
pressing the RESET button on the Display Module) and the message “DC IN
nn.nn VOLTS” is displayed on the Display Module.
Under total power failure all system set up, configuration and logged data is
protected by means of a battery-backed RAM in the Display Module.
During periods of power loss, further data will not be logged until power is
reinstated.
Issue 5 45
Gasmonitor+ Operation & Installation Hardware
Issue 5 46
Gasmonitor+ Operation & Installation Hardware
The Power Module Slots into the control rack behind the Display Module. See
Figure 25 for detail.
HARDWARE
Figure 25: Power Module Mounting Detail
Issue 5 47
Gasmonitor+ Operation & Installation Hardware
One of two standard Power Supply Units may be supplied depending on the
system configuration. Both are mounted in the control cabinet.
50/60Hz
Auto-ranging
Issue 5 48
Gasmonitor+ Operation & Installation Hardware
HARDWARE
Figure 26 (a): 300W Power Supply Mounting Detail (mm)
Issue 5 49
Gasmonitor+ Operation & Installation Hardware
2.7.3.3 Batteries
Figure 27 shows the overall dimensions of a 12V, 7Ah battery. Fixing details in
the control cabinet vary from system to system.
HARDWARE
Issue 5 50
Gasmonitor+ Operation & Installation Hardware
Figure 28 details the typical power supply connections for a Gasmonitor+ gas
and fire control system.
HARDWARE
Issue 5 51
Gasmonitor+ Operation & Installation Hardware
Issue 5 52
Gasmonitor+ Operation & Installation Hardware
HARDWARE
Universal Gas Input Card 8 325mA 355mA 2600mA 2840mA
With Flammable Detector
Audible Alarm 1 - 120mA - 120mA
Visual Alarm 1 - 150mA - 150mA
Total Current Consumption (mA) 2700mA 3230mA
Total Current Consumption (A) 2.7A 3.3A
When the mains supply is healthy the Power Supply Unit must be able to
power the system in full alarm (3.3A) and trickle charge the batteries. 10% of
the battery capacity should be allocated to the charging of the batteries.
Issue 5 53
Gasmonitor+ Operation & Installation Hardware
Assuming a power Supply Unit efficiency of 80% then the minimum power
supply requirement is (4 x 27.6)/80% = 138W.
In this example the system would be fitted with a 300W Power Supply Unit.
Note: Battery amp-hour ratings are specified with no more than 10% of
maximum load applied i.e. a 7Ah battery will last for 10hours @ 700mA. As
HARDWARE
more current is drawn so the capacity is de-rated. Typical de-rating factors are:
The backup time should no alarms occur = 7Ah/2.7A * 0.58 = 1 hrs, 30 mins
The backup time under full alarm = 7Ah/3.3A * 0.58 = 1 hrs, 13 mins
The above calculations are based on a worst case scenario, as it is unlikely that
all channels will go into full alarm at the same time.
Issue 5 54
Gasmonitor+ Operation & Installation Field Devices
3 FIELD DEVICES
3.1 General
Prior to installing field devices users should be familiar with the operation and
configuration of Gasmonitor+ using the Display Module pushbuttons and
SetGmon software supplied. Detailed operating instructions are given in
Appendices A and B.
Local regulations and installation practices vary from country to country. The
relevant codes of practice in the country concerned should be observed. Further
advice is available from Crowcon if required.
Dummy loads can be fitted in place of detector heads for test purposes. See
section 3.3.3.6.
Issue 5 55
Gasmonitor+ Operation & Installation Field Devices
Crowcon manufacture a wide range of flammable and toxic gas detectors. The
Gasmonitor+ Universal Gas Input Card is able to control all detectors
manufactured by Crowcon.
The following list details detectors currently manufactured by Crowcon for use
with Gasmonitor+.
Issue 5 56
Gasmonitor+ Operation & Installation Field Devices
Issue 5 57
Gasmonitor+ Operation & Installation Field Devices
OTHER
Detectors not listed may still be used with Gasmonitor+. For further details
contact Crowcon.
There are no rules which dictate the siting and location of detectors, however,
considerable guidance is available from BS EN 50073:1999 ‘Guide for
FIELD DEVICES
The detector should be mounted where the gas is most likely to be present. The
following points should be noted when locating gas detectors:
To detect gases which are lighter than air, e.g., methane, detectors should be
mounted at high level and Crowcon recommend the use of a Collector Cone.
Issue 5 58
Gasmonitor+ Operation & Installation Field Devices
To detect heavier than air gases, e.g., butane, detectors should be mounted at
low level. The use of additional sampling equipment such as the 87ESU may
improve the detection rate of heavier than air gases. Contact Crowcon for
details.
To detect gases with similar weight to air, e.g., hydrogen sulphide mount the
detector at normal breathing height.
Consider how the escaping gas may behave due to natural or forced air
currents. Mount detectors in ventilation ducts if appropriate.
Consider the process conditions. Gases that are normally heavier than air, but
released from a process line that is at an elevated temperature and/or under
pressure may rise rather than fall. FIELD DEVICES
Issue 5 59
Gasmonitor+ Operation & Installation Field Devices
3.2.3.1 General
These detectors are all pellistor/catalytic bead type and operate on the
Wheatstone bridge principle. The detectors are 3 wire and provide a mV output
proportional to the gas concentration. For details on each type of gas detector
please refer to the relevant Installation, Operating and Maintenance
Instructions provided with each detector.
These detectors are simple devices, i.e., these detectors must be used with a
dedicated control card to supply power and process the signal before raising
alarms should gas be detected.
Crowcon recommend the use of steel wire armoured (SWA) cable and suitable
explosion proof glands must be used.
Issue 5 60
Gasmonitor+ Operation & Installation Field Devices
Notes:
1
Approximate c.s.a. in awg given in brackets.
2
Approximate distance in feet given in brackets.
3.2.4 Earthing
The junction box and cable armour must be earthed at either the detector or
control panel to limit the effects of radio frequency interference. It is good
practice to provide the earth connection at the safe area only, so as to avoid
earth loops.
FIELD DEVICES
For details of all jumper settings refer to Hardware, Universal Gas Input Card
Jumper Settings, section 2.3.5.
Issue 5 61
Gasmonitor+ Operation & Installation Field Devices
Link Position
LK 1 None
LK 2 E, I, K, E-F, I-J,
K-L
LK 3 STD
LK 4 PELL
LK 5 REG
LK 6 and 7 24V C/C
Note:
FIELD DEVICES
Issue 5 62
Gasmonitor+ Operation & Installation Field Devices
FIELD DEVICES
Issue 5 63
Gasmonitor+ Operation & Installation Field Devices
Setting to work requires that the system has been turned on and allowed to
stabilise for at least 2 hours.
Each pellistor/catalytic bead type flammable gas detector requires the correct
head voltage to be applied across terminals 1 and 3 (Figure 29). The detector
Installation, Operation and Maintenance Instructions will detail the correct
head voltage for the type of detector installed.
It is assumed that the detector has been powered and allowed to stabilise for at
least 2 hours.
be set up.
5. At this point one LED on the bar graph of the input card to be set up
may or may not illuminate.
6. Measure the head volts at the detector across terminals 1 and 3 using a
digital voltmeter (DVM).
7. Using an instrument screw driver adjust the HEAD CURRENT
potentiometer (see Figure 11) on the input card until the DVM measures
the correct head voltage at the detector.
Issue 5 64
Gasmonitor+ Operation & Installation Field Devices
3.2.7.1 Calibration
When calibrating an input card and detector for the first time Crowcon
recommend that two persons be used, one at the detector and the other at the
control panel. When gas is applied to the detector in the field the person at the
control panel can check that the detector is connected to the correct input card
by observing the gas reading or bar graph on the front panel. FIELD DEVICES
Once the link between the detector and input card has been proved one person
can carry out future calibrations and routine functional testing (see Routine
Functional Testing, section 3.2.7.2).
Issue 5 65
Gasmonitor+ Operation & Installation Field Devices
12. Return the Display Module and input card to normal operation using the
pushbuttons mounted on the front panel.
Issue 5 66
Gasmonitor+ Operation & Installation Field Devices
1. Inhibit all input cards in any single control rack by pressing the
INHIBIT button on each input card and the RESET button on the
Display Module simultaneously.
2. Ensure that the detectors to be checked are in clean air and re-zero as
necessary.
3. Using the four pushbuttons on the Display Module select HOLDALL
CAL?
4. Pressing the YES button instructs the Display Module to log the peak
gas reading from each input card. The message ‘Collecting Peaks’ is
displayed during this operation.
5. Apply calibration gas to each detector to be checked in turn and return
to the control panel.
6. Pressing the DONE button on the Display Module displays the message
‘ADJ Ch1 > XXX?’ where XXX is the name given to that channel.
7. Upon pressing the YES button on the Display Module the user may
adjust the reading by pressing them UP and DOWN buttons until the
reading displayed matches the calibration gas used.
8. Press the YES button on the Display Module to calibrate the channel.
9. This can be repeated for each channel in the control rack.
10. Once the system has been fully checked return the Display Module and
input cards to normal operation using the pushbuttons mounted on the
FIELD DEVICES
front panel.
Issue 5 67
Gasmonitor+ Operation & Installation Field Devices
3.2.8.1 General
Each detector includes a local amplifier which accepts power from the
Universal Gas Input Card and provides a 4-20 mA output proportional to the
gas concentration at the detector.
The following instructions assume that each detector has been configured in a 3
wire, 4-20 mA source configuration.
Crowcon recommend the use of steel wire armoured (SWA) cable and suitable
explosion proof glands must be used.
Issue 5 68
Gasmonitor+ Operation & Installation Field Devices
The minimum acceptable supply voltage measured at the detector and the
maximum current drawn by that detector is different for each device.
Gasmonitor+ supplies a guaranteed minimum supply voltage of 22 Vdc. Please
refer to the relevant Installation, Operating and Maintenance Instructions
provided with each detector to calculate the maximum cable distances allowed
for different cable types.
3.2.8.3 Earthing
The junction box and cable armour must be earthed at either the detector or
control panel to limit the effects of radio frequency interference. It is good
practice to provide the earth connection at the safe area only, so as to avoid
earth loops.
For details of all jumper settings refer to Hardware, Universal Gas Input Card
Jumper Settings, section 2.3.5.
Link Position
LK 1 B, D, B-C, D-E
LK 2 E, I, K,E-F, I-J, K-L
LK 3 STD
LK 4 4-20
LK 5 24V
LK 6 and 7 24V C/C
Issue 5 69
Gasmonitor+ Operation & Installation Field Devices
Note:
Issue 5 70
Gasmonitor+ Operation & Installation Field Devices
Issue 5 71
Gasmonitor+ Operation & Installation Field Devices
The detector must be calibrated before calibration of the associated input card.
For calibration details of each detector please refer to the relevant Installation,
Operating and Maintenance Instructions provided with each detector.
3.2.8.7 Calibration
Calibration of the input card may be performed via the four pushbuttons or the
SetGmon software provided. Where single channels require calibration
Crowcon recommend the following procedure. Where many channels are to be
calibrated Crowcon recommend the use of SetGmon
(see Appendix B).
When calibrating an input card and detector for the first time Crowcon
recommend that two persons be used, one at the detector and the other at the
control panel. When gas is applied to the detector in the field the person at the
control panel can check that the detector is connected to the correct input card
by observing the gas reading or bar graph on the front panel.
FIELD DEVICES
Once the link between the detector and input card has been proved one person
can carry out future calibrations and routine functional testing (see section
3.2.8.8).
To calibrate the input card for use with a 4-20mA type detector:
Issue 5 72
Gasmonitor+ Operation & Installation Field Devices
One person may check a detector with a local amplifier at the detector and no
adjustment at the control panel should be required.
Issue 5 73
Gasmonitor+ Operation & Installation Field Devices
1. Inhibit all input cards in any single control rack by pressing the
INHIBIT button on each input card and the RESET button on the
Display Module simultaneously.
2. Ensure that the detectors are reading zero gas, i.e., detector output set to
4mA.
3. Using the four pushbuttons on the Display Module re-zero each input
card as necessary.
4. Using the four pushbuttons on the Display Module select HOLDALL
CAL?
5. Pressing the YES button instructs the Display Module to log the peak
gas reading from each input card. The message ‘Collecting Peaks’ is
displayed during this operation.
6. Apply calibration gas to each detector in turn and return to the control
panel.
7. Pressing the DONE button on the Display Module displays the message
FIELD DEVICES
‘ADJ Ch1 > XXX?’ where XXX is the name given to that channel.
8. Upon pressing the YES button on the Display Module the user may
adjust the reading by pressing them UP and DOWN buttons until the
reading displayed matches the calibration gas used.
9. Press the YES button on the Display Module to calibrate the channel.
10. This can be repeated for each channel in the control rack.
11. Once the system has been fully checked return the Display Module and
input cards to normal operation using the pushbuttons mounted on the
front panel.
Issue 5 74
Gasmonitor+ Operation & Installation Field Devices
3.2.9.1 General
Each detector is 4-20mA loop powered and includes a local amplifier. The 4-
20 mA output is proportional to the gas concentration at the detector. Such
devices are sink only.
The device must be used with a suitable line isolator, i.e., Zener barrier or
galvanic isolator, when used in a hazardous atmosphere.
Crowcon recommend the use of twisted pair cable with overall screen and
sheath. Suitable weatherproof glands must be used.
Issue 5 75
Gasmonitor+ Operation & Installation Field Devices
The maximum cable distance allowed is dependent upon the installation, i.e.,
whether Zener barriers or galvanic isolators are required or not.
The following table summarises the maximum theoretical cable distance for
different installations.
3.2.9.3 Earthing
Issue 5 76
Gasmonitor+ Operation & Installation Field Devices
When the detector is mounted in a safe area (no line isolators), or is used with a
galvanic isolator, the junction box and cable screen must be earthed at either
the detector or control panel to limit the effects of radio frequency interference.
It is good practice to provide the earth connection at the safe area only, so as to
avoid earth loops.
When the detector is used with a Zener barrier a certified IS earth is required at
the Zener barrier. The junction box and cable screen must be earthed at the IS
earth to meet intrinsic safety requirements and to limit the effects of radio
frequency interference.
When Zener barriers are used the link GND2 must be removed from the
motherboard of the 19” control rack.
For details of all jumper settings refer to Hardware, Universal Gas Input Card
Jumper Settings, section 2.3.5.
The following table summarises the link settings required when using 2 wire 4-
20 mA devices with a Universal Gas Input Card.
Issue 5 77
Gasmonitor+ Operation & Installation Field Devices
Note:
Issue 5 78
Gasmonitor+ Operation & Installation Field Devices
FIELD DEVICES
Issue 5 79
Gasmonitor+ Operation & Installation Field Devices
Figure 31 (b): Gasmonitor+ to TXgard via Zener Barrier Typical Wiring Detail
FIELD DEVICES
Issue 5 80
Gasmonitor+ Operation & Installation Field Devices
FIELD DEVICES
Issue 5 81
Gasmonitor+ Operation & Installation Field Devices
Issue 5 82
Gasmonitor+ Operation & Installation Field Devices
The detector must be calibrated before calibration of the associated input card.
For calibration details of each detector please refer to the Installation,
Operating and Maintenance Instructions provided with each detector.
3.2.9.7 Calibration
Calibration of the input card may be performed via the four pushbuttons or the
SetGmon software provided. Where single channels require calibration
Crowcon recommend the following procedure. Where many channels are to be
calibrated Crowcon recommend the use of SetGmon (see
Appendix B).
When calibrating an input card and detector for the first time Crowcon
recommend that two persons be used, one at the detector and the other at the
control panel. When gas is applied to the detector in the field the person at the
control panel can check that the detector is connected to the correct input card
by observing the gas reading or bar graph on the front panel.
FIELD DEVICES
Once the link between the detector and input card has been proved one person
can carry out future calibrations and routine functional testing (see Routine
Functional Testing, section 3.2.9.8).
To calibrate the input card for use with 2 wire 4-20 mA detector:
Issue 5 83
Gasmonitor+ Operation & Installation Field Devices
Only one person is required to check a detector fitted with a local amplifier and
no adjustment at the control panel should be required.
Issue 5 84
Gasmonitor+ Operation & Installation Field Devices
1. Inhibit all input cards in any single control rack by pressing the
INHIBIT button on each input card and the RESET button on the
Display Module simultaneously.
2. Ensure that the detectors are reading zero gas, i.e., detector output set to
4 mA.
3. Using the four pushbuttons on the Display Module re-zero each input
card as necessary.
4. Using the four pushbuttons on the Display Module select HOLDALL
CAL?
5. Pressing the YES button instructs the Display Module to log the peak
gas reading from each input card. The message ‘Collecting Peaks’ is
displayed during this operation. FIELD DEVICES
6. Apply calibration gas to each detector in turn and return to the control
panel.
7. Pressing the DONE button on the Display Module displays the message
‘ADJ Ch1 > XXX?’ where XXX is the name given to that channel.
8. Upon pressing the YES button on the Display Module the user may
adjust the reading by pressing them UP and DOWN buttons until the
reading displayed matches the calibration gas used.
9. Press the YES button on the Display Module to calibrate the channel.
10. This can be repeated for each channel in the control rack.
Issue 5 85
Gasmonitor+ Operation & Installation Field Devices
11. Once the system has been fully checked return the Display Module and
input cards to normal operation using the pushbuttons mounted on the
front panel.
FIELD DEVICES
Issue 5 86
Gasmonitor+ Operation & Installation Field Devices
3.2.10.1 General
Each detector is 4-20 mA loop powered and includes a local amplifier. The 4-
20 mA output is proportional to the gas concentration at the detector. The 2
wire 4-20 mA flameproof devices are 4-20 mA sink devices.
Crowcon recommend the use of steel wire armoured (SWA) cable and suitable
explosion proof glands must be used.
Issue 5 87
Gasmonitor+ Operation & Installation Field Devices
3.2.10.3 Earthing
The junction box and cable armour must be earthed at either the detector or
control panel to limit the effects of radio frequency interference. It is good
practice to provide the earth connection at the safe area only, so as to avoid
earth loops.
For details of all jumper settings refer to Hardware, Universal Gas Input Card,
Jumper Settings, section 2.3.5.
Link Position
LK 1 A, C, A-B, C-D
LK 2 E, I, K, E-F, I-J, K-
L
LK 3 None
FIELD DEVICES
LK 4 4-20
LK 5 24V
LK 6 and 7 24V C/C
Issue 5 88
Gasmonitor+ Operation & Installation Field Devices
The detector must be calibrated before calibration of the associated input card.
For calibration details of 4-20 mA gas detectors please refer to the Installation,
Operating and Maintenance Instructions provided with each detector.
3.2.10.6 Calibration
Calibration of the input card may be performed via the four pushbuttons or the
SetGmon software provided. Where single channels require calibration
Crowcon recommend the following procedure. Where many channels are to be
calibrated Crowcon recommend the use of SetGmon (see Appendix B).
When calibrating an input card and detector for the first time Crowcon
recommend that two persons be used, one at the detector and the other at the
control panel. When gas is applied to the detector in the field the person at the
control panel can check that the detector is connected to the correct input card
by observing the gas reading or bar graph on the front panel.
Once the link between the detector and input card has been proved one person
can carry out future calibrations and routine functional testing (see Routine
FIELD DEVICES
To calibrate the input card for use with a 4-20mA type detector:
Issue 5 89
Gasmonitor+ Operation & Installation Field Devices
4. Using the four pushbuttons on the Display Module select the channel to
be zeroed.
5. Zero the channel by following the commands on the Display Module.
On completion the message ‘Zero successful’ is displayed.
6. Using the four pushbuttons on the Display Module select
CALIBRATE?
7. Using the four pushbuttons on the Display Module select the channel to
be calibrated.
8. Apply calibration gas to the detector (normally half scale).
9. Allow the gas level reading on the Display Module to stabilise and then
adjust the displayed value by pressing the UP and DOWN pushbuttons
on the Display Module until the displayed value corresponds to the
calibration gas applied.
10. Press the YES button on the Display Module to calibrate the channel.
11. The detector and input card are now configured and calibrated
correctly.
12. Return the Display Module and input card to normal operation using the
pushbuttons mounted on the front panel.
One person may check a detector with a local amplifier at the detector and no
adjustment at the control panel should be required.
Issue 5 90
Gasmonitor+ Operation & Installation Field Devices
1. Inhibit all input cards in any single control rack by pressing the
INHIBIT button on each input card and the RESET button on the
Display Module simultaneously.
2. Ensure that the detectors are reading zero gas, i.e., detector output set to
4 mA.
3. Using the four pushbuttons on the Display Module re-zero each input
card as necessary.
4. Using the four pushbuttons on the Display Module select HOLDALL
CAL?
5. Pressing the YES button instructs the Display Module to log the peak
gas reading from each input card. The message ‘Collecting Peaks’ is
displayed during this operation.
6. Apply calibration gas to each detector in turn and return to the control
panel.
7. Pressing the DONE button on the Display Module displays the message FIELD DEVICES
‘ADJ Ch1 > XXX?’ where XXX is the name given to that channel.
8. Upon pressing the YES button on the Display Module the user may
adjust the reading by pressing them UP and DOWN buttons until the
reading displayed matches the calibration gas used.
9. Press the YES button on the Display Module to calibrate the channel.
10. This can be repeated for each channel in the control rack.
11. Once the system has been fully checked return the Display Module and
input cards to normal operation using the pushbuttons mounted on the
front panel.
Issue 5 91
Gasmonitor+ Operation & Installation Field Devices
Gasmonitor+ has been tested for use with the Series 60 range of fire detectors
available from Apollo. Other manufacturer detectors may be suitable, contact
Crowcon for further details.
A switch operating in series or parallel with sense resistors may represent a fire
detector. This is shown in Figure 32.
FIELD DEVICES
Issue 5 92
Gasmonitor+ Operation & Installation Field Devices
Issue 5 93
Gasmonitor+ Operation & Installation Field Devices
With no detectors in alarm (all switches open) a small current flows in the
circuit through the end of line resistor (REOL). If a short circuit or open circuit
cable fault occurs, the current in the loop increases or decreases. The input card
detects this and a fault alarm is raised.
Should a fire be detected (switch closes) then the current flowing in the loop
changes and the input card detects this and a fire alarm is raised.
Gasmonitor+ has been designed to operate fire detectors given the following
characteristics of the Twin Zone Fire Input Card.
Up to 20 Series 60 fire detection devices may be used on the same loop at any
time. Devices on the loop may be mixed provided electrical characteristics are
compatible and fire regulations allow.
FIELD DEVICES
Where manual alarm call points or other switched devices are used series and
end of line resistors should be fitted to ensure correct alarm detection by the
Twin Zone Fire Input Card (series resistor = 470 Ohms, end of line resistor =
1K8 Ohms)
Issue 5 94
Gasmonitor+ Operation & Installation Field Devices
It is beyond the scope of this manual to describe the rules and regulations
governing the installation of fire detection equipment.
Assistance and guidance should be sought from the governing body in the
country concerned before fire detection equipment is installed.
Crowcon recommend the use of twisted pair, screened with overall protective
sheath which is fireproof, e.g., Pirelli FP200 or similar. Suitable weatherproof
FIELD DEVICES
The maximum acceptable loop resistance is 100 Ohms. The following table
summarises the maximum cable length allowed for up to 1.0 mm2 cross
sectional area (c.s.a.) cable.
Issue 5 95
Gasmonitor+ Operation & Installation Field Devices
Notes:
1
Approximate c.s.a. in awg given in brackets.
2
Approximate distance in feet given in brackets.
3.3.3.2 Earthing
When mounted in a safe area (no line isolators), or is used with a galvanic
isolator, the junction box and cable screen must be earthed at either the
detector or control panel to limit the effects of radio frequency interference. It
is good practice to provide the earth connection at the safe area only, so as to
avoid earth loops.
FIELD DEVICES
When used with a Zener barrier a certified IS earth is required at the Zener
barrier. The cable screen must be earthed at the IS earth to meet intrinsic safety
requirements and to limit the effects of radio frequency interference.
When Zener barriers are used the link GND2 must be removed from the
motherboard of the 19” control rack.
Issue 5 96
Gasmonitor+ Operation & Installation Field Devices
When using Zener barriers ensure that the link LK1 on the Twin Zone Fire
Input Card is fitted.
For details on how to test different fire detectors please refer to the relevant
Installation, Operation and Maintenance Instructions provided with the
detector. FIELD DEVICES
Issue 5 97
Gasmonitor+ Operation & Installation Field Devices
FIELD DEVICES
Figure 33 (a): Gasmonitor+ to Series 60 Fire Detectors Wiring Detail (Safe Area
Only)
Issue 5 98
Gasmonitor+ Operation & Installation Field Devices
FIELD DEVICES
Issue 5 99
Gasmonitor+ Operation & Installation Field Devices
For test purposes, and to prevent fault alarms on channels that have no heads
connected, detectors can be simulated by dummy resistive loads as shown
below. Figure 34 (a) to (d) shows terminal numbers on the input/output module
for channel 1, but of course dummy loads can be fitted in the same manner to
any channel.
60
62
60
61
Issue 5 100
Gasmonitor+ Operation & Installation Field Devices
60
61
Notes:
60
FIELD DEVICES
62 Zone 1
Issue 5 101
Gasmonitor+ Operation & Installation Field Devices
Gasmonitor+ is able to drive audible and visual alarms via common alarm relay
outputs. The type and function of these alarm devices is beyond the scope of
this manual.
Any 24 V dc field device may be driven by the dedicated outputs provided the
maximum current drawn on each output is less than 200 mA.
The type of cable used and the size of conductors should be chosen to suit the
field device installed. Please refer to the Installation, Operation and
Maintenance Instructions of the audible/visual alarm to be used for details.
FIELD DEVICES
Issue 5 102
Gasmonitor+ Operation & Installation Field Devices
FIELD DEVICES
Issue 5 103
Gasmonitor+ Operation & Installation Field Devices
3.4.1.2 Earthing
Where the field device is driven through a Zener barrier then the screen must
be earthed at the IS earth at the barrier. Remove link GND2 on the 19” rack
motherboard when using Zener barriers.
Issue 5 104
Gasmonitor+ Operation & Installation Field Devices
FIELD DEVICES
Figure 36 (a): Audible/Visual Alarms Typical Wiring Detail (Safe Area Only)
Issue 5 105
Gasmonitor+ Operation & Installation Field Devices
FIELD DEVICES
Issue 5 106
Gasmonitor+ Operation & Installation Appendix A
APPENDIX A
DISPLAY MODULE MENU OPERATION
This Appendix should be read in conjunction with the relevant Set-up and Operation
procedures given in Field Devices, section 3.
Issue 5 107
Gasmonitor+ Operation & Installation Appendix A
Note:
The three red alarm LEDs will flash
Issue 5 108
Gasmonitor+ Operation & Installation Appendix A
Issue 5 109
Gasmonitor+ Operation & Installation Appendix A
Issue 5 110
Gasmonitor+ Operation & Installation Appendix A
APPENDICES
Issue 5 111
Gasmonitor+ Operation & Installation Appendix A
assistance.
8. Press ‘CONT’ to calibrate another
channel or ‘END’ to return to normal
Issue 5 112
Gasmonitor+ Operation & Installation Appendix A
APPENDICES
Issue 5 113
Gasmonitor+ Operation & Installation Appendix A
Issue 5 114
Gasmonitor+ Operation & Installation Appendix A
Issue 5 115
Gasmonitor+ Operation & Installation Appendix A
The following features are also available for adjustment via the 4 pushbuttons,
however, Crowcon recommend the use of SetGmon.
See Appendix B for details.
>ALARM LEVEL ?
>ALARM LATCH ?
>ALARM SENSE ?
>RELAY DRIVE ?
>CHAN FLAGS ?
APPENDICES
Issue 5 116
Gasmonitor+ Operation & Installation Appendix B
APPENDIX B
WINDOWS BASED SOFTWARE FOR THE PC
Contents
General 118
Software Installation 118
Electrical Connections 119
SetGmon Software 119
Overview 119
Running SetGmon for the First Time 120
Establishing Communications 121
Configuration Files 123
General 123
Editing Configuration Files 128
Making System Adjustments via SetGmon 134
Special Functions 137
LogManager Software 138
Overview 138
Running LogManager 138
Viewing a Logged File 139
‘Convert’ing Files to .CSV Format 140
‘Save As’ .CSV Files to Disc 141
‘Print’ing Logged Data 141
APPENDICES
Issue 5 117
Gasmonitor+ Operation & Installation Appendix B
General
Each Gasmonitor+ system is supplied with:
Software Installation
To install the Windows software under Windows 95 or later:
The software will be loaded automatically and the following programs will
appear in the ‘Programs’ menu.
APPENDICES
Issue 5 118
Gasmonitor+ Operation & Installation Appendix B
Electrical Connections
Gasmonitor+ is connected to the PC using the 9 way D type connecting lead
provided (Crowcon part no. C01327).
The other end of the connecting lead is plugged into the 9 way D port (COM1)
on the PC.
If COM1 is being used e.g. by the mouse, COM2 may be used but the WIN.INI
file must be amended to include the following instructions:
[setgmon]
port=2 (A carriage return is required after the number 2)
SetGmon Software
Overview
All functions are carried out using the on screen pop up menus which are
discussed in the following sections.
Issue 5 119
Gasmonitor+ Operation & Installation Appendix B
Select ‘SetGmon’ from the ‘Start’ menu. The following screen will appear:
If upon running SetGmon the following error message occurs, check the cable
is connected securely, the correct COM port is being used or that the COM
port is not already in use by another program.
APPENDICES
Issue 5 120
Gasmonitor+ Operation & Installation Appendix B
Establishing Communications
3 Enter the address of the Gasmonitor+ control rack to talk to (e.g. ‘0’ for
a single rack) and press ‘OK’
Issue 5 121
Gasmonitor+ Operation & Installation Appendix B
4 Select ‘Link’ and then ‘Connect’ from the drop down menu and the
following display appears.
7 Should an error box appear, check the cable is connected securely, the
APPENDICES
correct COM port is being used or that the COM port is not already in
use by another program. If necessary use another COM port.
Issue 5 122
Gasmonitor+ Operation & Installation Appendix B
Configuration Files
General
The specification sheet for that system details the configuration supplied.
Should the Display Module ever need to be changed then this backup copy
may be required.
When configuration files are opened and then transferred to/from the
Gasmonitor+ control rack the background colour behind the title ‘FILE’,
‘EDIT’ and ‘Gasmonitor+’ change. The difference in colour signifies a
difference in the configuration held by the computer and/or Gasmonitor+.
When all editing is complete and files have been saved correctly all
background colours will be the same. At this time the user may close the
application knowing that all files have been updated to the same level.
To create a new configuration file select ‘Files’ from the SetGmon toolbar and
press ‘New’ on the drop down menu. Press ‘OK’ on the pop up warning box to
start editing the configuration as required.
Issue 5 123
Gasmonitor+ Operation & Installation Appendix B
3 Select ‘Upload…’ from the drop down menu. The following display
appears.
4 After a short delay the following screen will appear. If, instead, an error
box appears, check the cable is connected securely, the correct COM
port is being used or that the COM port is not already in use by another
program. If necessary use another COM port.
APPENDICES
Issue 5 124
Gasmonitor+ Operation & Installation Appendix B
5 Those channels not fitted with input cards are greyed out.
1 To open a configuration file from disc select ‘Files’ from the SetGmon
toolbar and then ‘Open’, the following display will appear.
2 Select the configuration file to open and press ‘OK’. A screen similar to
that shown below will appear.
APPENDICES
Issue 5 125
Gasmonitor+ Operation & Installation Appendix B
Issue 5 126
Gasmonitor+ Operation & Installation Appendix B
3 If, instead, an error box appears check the cable is connected securely,
the correct COM port is being used or that the COM port is not already
in use by another program. If necessary use another COM port.
2 Type a new file name in the ‘File Name’ box and press ‘OK’ to save the
modified file.
APPENDICES
Issue 5 127
Gasmonitor+ Operation & Installation Appendix B
Open the configuration file from disc or upload the configuration from a
Gasmonitor+ to be edited.
Select ‘Edit’ from the SetGmon toolbar and the following screen will appear.
The following table summarises the parameters that may be set from this
screen.
Logging period Defines the interval between Changing the logging period
samples in seconds. Entry automatically clears the log.
must be between 5 and 32000.
Issue 5 128
Gasmonitor+ Operation & Installation Appendix B
Issue 5 129
Gasmonitor+ Operation & Installation Appendix B
2 Pressing any of the numbered tabs (1 to 16) at the top of the pop up
screen allows that specific channel to be configured.
3 Greyed out boxes represent options which are not available for the type
of card selected.
4 The software defaults to the input card being configured as a flammable
or toxic gas input card. If the input card is connected to an oxygen
detector or is a fire card the relevant check box must be selected.
5 Channel settings may be copied from one channel to another as follows:
• Select the channel tab to be copied by clicking the left hand
mouse button over the tab.
• Press the left hand mouse button again over the tab. This stores
the channel information.
• Select the channel that the information is to be copied to by
clicking the left mouse button over the tab.
• To copy the information right click the mouse button over the
tab of the channel to be copied to.
6 The following table summarises the parameters for each channel that
may be set from this screen.
APPENDICES
Issue 5 130
Gasmonitor+ Operation & Installation Appendix B
Scale Sets the full scale range for E.g. Oxygen is normally
the detector fitted. set to 25%vv.
Alarm 1 (2 or 3) Value Sets the alarm trip point. The lowest alarm set point
Issue 5 131
Gasmonitor+ Operation & Installation Appendix B
Issue 5 132
Gasmonitor+ Operation & Installation Appendix B
1 To edit the configuration of the Voted Relays select ‘Edit’ from the
SetGmon toolbar and then press the ‘Alarms’ button. The following
screen will appear.
Issue 5 133
Gasmonitor+ Operation & Installation Appendix B
2 The screen represents the Display Module LCD display and associated
pushbuttons.
3 To set the new password click the left mouse button over the numbers 1
to 4 in any sequence of up to 4 presses.
4 The screen will automatically disappear and return the user to the ‘Set
Parameters’ menu.
Online system adjustments other than configuration changes can be made using
the SetGmon software.
Issue 5 134
Gasmonitor+ Operation & Installation Appendix B
Issue 5 135
Gasmonitor+ Operation & Installation Appendix B
Issue 5 136
Gasmonitor+ Operation & Installation Appendix B
Special Functions
‘Timezone’
Select ‘Timezone’ from the ‘Link’ menu on the SetGmon toolbar to open the
‘Time Zone’ dialog box.
In the appropriate box enter the time shift in hours and press ‘OK’.
When the ‘Clock’ function is now selected from the ‘Adjust’ menu on the
SetGmon toolbar the offset will be applied and the Gasmonitor+ clock reset.
The Display Module holds the system configuration data and calibration data
for each channel fitted to the system.
The calibration data is used to scale readings from the input cards before
displaying the information on the Display Module LCD.
APPENDICES
Issue 5 137
Gasmonitor+ Operation & Installation Appendix B
LogManager Software
Overview
Running LogManager
Select ‘LogManager’ from the ‘Start’ menu. The following screen will appear:
APPENDICES
Issue 5 138
Gasmonitor+ Operation & Installation Appendix B
Select ‘Open Log’ from the ‘Files’ menu on the LogManager toolbar. The
following screen will appear.
Select the logged file to open and press ‘OK’. The logged data will be shown
graphically as follows.
The vertical scale is ranged to display the largest range of the displayed
channels.
Select ‘View’ from the LogManager toolbar to turn on or off specific channels.
Moving the cursor over the screen displays the exact time, date and reading at
APPENDICES
Issue 5 139
Gasmonitor+ Operation & Installation Appendix B
This function converts the logged data into a comma separated variable file
format. This file can then be imported into spreadsheet applications such as
Lotus 123 or Microsoft Excel.
Selecting ‘Convert’ from the LogManager toolbar. The following screen will
appear.
As default the ‘Convert Selection’ menu includes data from the first to the last
value recorded. These can be over-typed if required to convert a smaller
selection.
Upon pressing ‘OK’ the logged data is converted and must then be saved.
APPENDICES
Issue 5 140
Gasmonitor+ Operation & Installation Appendix B
Once the logged data has been converted select ‘Save As’ from the ‘File’ menu
and the following dialog box will appear.
Enter the required filename and destination directory and press ‘OK’ to save
the file in .CSV file format.
Select ‘Print’ from the ‘File’ menu on the LogManager toolbar to print the
logged data in tabular format.
APPENDICES
Issue 5 141
Gasmonitor+ Operation & Installation Appendix C
APPENDIX C
SPARE PARTS LIST
Figure 37 shows an exploded view of a typical Gasmonitor+ system. To obtain any
spare parts not detailed please contact Crowcon directly.
Issue 5 144
Gasmonitor+ Operation & Installation Appendix C
Issue 5 143
Gasmonitor+ Operation & Installation Appendix C
APPENDICES
Issue 5 144
Gasmonitor + Operation and Installation Warranty
WARRANTY
This equipment leaves our works fully tested and calibrated. If within a period
of one year from the date of purchase it is proved to be defective by reason of
faulty workmanship or material, we undertake at our option either to repair or
replace it free of charge, subject to the conditions below.
3 The guarantee does not cover the accuracy of calibration after the system
has been put into use. The system must be maintained in accordance with the
Installation, Operating and Maintenance Instructions.
4 The guarantee does not include the cosmetic finish of the product, and is
dependant upon installation and operation of the product in accordance with
the procedures set out in the Installation, Operating and Maintenance
Instructions.
Issue 5
Gasmonitor + Operation and Installation Warranty
6 Units that are returned to Crowcon as faulty, and are subsequently found
to be fault-free may be subject to a small handling charge to cover inspection
and return shipping costs.
Issue 5
UK Office USA Office
Crowcon Detection Instruments Ltd Crowcon Detection Instruments Ltd
2 Blacklands Way, 21 Kenton Lands Road,
Abingdon Business Park Erlanger,
Abingdon Kentucky 41018-1845
Oxfordshire OX14 1DY USA
United Kingdom Tel: +1 800 527 6926 or
Tel: +44 (0)1235 557700 1-800-5-CROWCON
Fax: +44 (0)1235 557749 +1 859 957 1039
Email: [email protected] Fax: +1 859 957 1044
Web site: www.crowcon.com Email: [email protected]
Web site: www.crowcon.com