0% found this document useful (0 votes)
12 views23 pages

Protec Driver Manual

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views23 pages

Protec Driver Manual

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 23

The Protec Driver

The Protec driver connects to the Protec Fire Detection range of digital addressable fire control
panels. Available for Commander and ObSys.

This document relates to Protec driver version 1.5

Please read the Commander Manual or ObSys Manual alongside this document, available from
www.northbt.com
Contents
Compatibility with the Protec System ......................................................................................... 3
Equipment ........................................................................................................................................ 3
Values ................................................................................................................................................ 3
Prerequisites ..................................................................................................................................... 3

Driver Operation ........................................................................................................................... 4


Events from the Panel ...................................................................................................................... 4
Alarms ............................................................................................................................................... 4
Reading from the Protec System...................................................................................................... 4
Commands to the Protec System .................................................................................................... 4
Output Groups .................................................................................................................................. 4

Using the Driver ............................................................................................................................ 5


Making the Cable .............................................................................................................................. 5
Starting the Interface........................................................................................................................ 5
Setting up the Driver ......................................................................................................................... 6
Checking Communications .............................................................................................................. 6

Alarms ........................................................................................................................................... 7
Format ............................................................................................................................................... 7
Examples ........................................................................................................................................... 7
Point Field ......................................................................................................................................... 7
Condition and Priority Field ............................................................................................................. 8

Object Specifications .................................................................................................................... 9


Example Object Reference ............................................................................................................... 9
Device Top-Level Objects ................................................................................................................. 9
Protec Driver Setup......................................................................................................................... 10
Protec Driver Filter Events .............................................................................................................. 11
Protec Advanced Setup .................................................................................................................. 11
6500 Series System ......................................................................................................................... 12
x400 Series System ......................................................................................................................... 12
x300 Series System ......................................................................................................................... 12
Zone & System Summary ............................................................................................................... 13
Commands ...................................................................................................................................... 14
Zone ................................................................................................................................................ 15
6500 Series Panel ............................................................................................................................ 16
6500 Series Loop ............................................................................................................................. 17
x400 Series Panel ............................................................................................................................ 18
x300 Series Panel ............................................................................................................................ 19
x400/x300 Series Loop .................................................................................................................... 20
Device .............................................................................................................................................. 21
Output Group .................................................................................................................................. 22

Driver Versions ............................................................................................................................ 23

The Protec Driver 2


Compatibility with the Protec System
The Protec driver allows North to interface with a Protec Fire Detection system.
The driver connects to a Protec digital addressable fire control panel (Fig. 1), and can communicate with
a network of panels.

North
device

RS232

Protec
panel

Fig. 1 North to Protec panel

Equipment
Protec Fire Detection control panels compatible with the driver include:
• Algo-tec 6500 series
• Algo-tec 5400/6400 series
• Algo-tec 6300 and AN95

Values
Depending on the series of fire control panel, the driver can typically access the following values:
• Reset panel • Loop state
• Sounders • Loop device state
• Date & Time • Zone state
• System state • Output group (5400/6400 and 6500 series only)
• Panel state • Damper state (5400/6400 and 6500 series only)
States for fire, pre-alarm, fault, and isolation conditions are available.
Fire control panels can send alarms to the Protec driver.

Prerequisites
Algo-tec 6300 panel only: this has limited capacity when communicating that a large number of devices
have changed state. Typically, this is when all devices in a zone have been isolated/de-isolated. After this
type of operation, use the Resync Driver object (RST) to re-synchronise the driver with the Protec system.
The Algo-tec 6300 panel uses a 600 baud serial connection. On Commander, this requires version 2.0
build 15/06/16 or later.

The Protec Driver 3


Driver Operation
Events from the Panel
The driver connects to a Protec Algo-tec fire control panel, and listens for change-of-state events. These
events are processed by the driver to maintain a database of active alarm states in the Protec system.
Events are grouped and stored in the database using one of the following states: fire, pre-alarm, fault, or
isolation.
On starting the interface, the driver synchronises its database with the Protec system by requesting the
current active alarms. You can also force a re-synchronisation at any time by using the Resync Interface
object (RST).
Both the Protec fire panel and driver monitor the communication between each other. If communication
is lost, then the panel and driver report the fault. Once regained, missed events are resent and operation
resumes.

Alarms
When an event is received from the Protec panel, the driver sends this as a North-format alarm to the
device’s alarm processing.

Reading from the Protec System


On reading an object from the Protec System, the driver responds with the state from its database. No
request is sent to the panel.

Commands to the Protec System


Commands can be sent to the Protec System. These can be to: accept, silence, or reset active events on
the system; isolate a loop-device; or override an output group.
On 6400 series panels and earlier, a pause is required between commands. The driver will pause up
to 10 seconds between each command to the panel. Be aware of this pause when configuring Essential
Data or Data Transfer modules.

Output Groups
Output groups are used by the panel to control groups of output devices, such as sounders, dampers etc.
The driver can be used to override an output group from its automatic state to either ‘on’ or ‘off’. When
you override an output on panels up to 99, the driver remembers this state so you can read it. The driver
does not listen to output groups events from the panel.
When the fire system is reset all output groups return to their automatic state, cancelling any overrides.
When integrating the fire panel with an HVAC system, outputs are typically used to open ventilation
dampers. If the advanced driver object Resend Output Group Overrides (A.OG) is enabled, then any
output group overridden by the driver (on panels up to 99) will be re-commanded to its override state
whenever the fire system is reset.
Output group overrides are remember during a power-cycle. Use the Resync Driver object (RST) to clear
the driver’s memory of overridden output groups.

The Protec Driver 4


Using the Driver
On ObSys and Commander, the Protec driver is pre-installed. On both these North devices, you can use
the driver to create an interface to Protec. Once started, you will need to set up the driver before it can
communicate with the Protec system.

Making the Cable


Using the RS232 cable specification (Fig. 2), connect the North device COM port to the Protec panel DB9
port.
Algo-tec 6500 panels:
The COM port, labelled ‘RS232’, is located on the main backplane PCB.
Algo-tec 5400/6300/6400 panels:
The COM port, labelled ‘Graphics port’, is located on the inside of the panel at the hinge-edge of the door,
facing the hinge itself. Not to be confused with ‘Commissioning Port 1’, which faces inwards from the
door.

Protec may supply an RS232 opto-isolator device with the panel. On the Commander platform, this is not
required as Commander’s RS232 ports are isolated. The cable connecting pins 4 & 7 is only required when
an opto-isolator is used.
Connector types at each end of the cable are shown.

North Protec
DB9 Female DB9 Male
2 2
3 3
5 5
4 7
Fig. 2 North to Protec cable

Cables are available from North, order code CABLE/PROTEC.


The maximum RS232 cable length is 15m.

Starting the Interface


 To start an interface using the Protec driver, follow these steps:
 Start Engineering your North device using ObSys
 Navigate to Configuration, Interfaces, and set an unused Interface to ‘Protec’ to start the
particular interface
 Navigate to the top-level of your North device and re-scan it
The driver setup object (Mc), labelled Protec Setup, should now be available. If this object is not
available, check an interface licence is available and the driver is installed.

The Protec Driver 5


Setting up the Driver
 To set up the driver, follow these steps:
 Navigate to the Protec Setup object (Mc). For example, if you started interface 1 with the driver
earlier, then the object reference will be ‘M1’
 Set the RS232 COM Port (RS.COM) to select the serial port number on the North device the panel is
connected to
 Set the Baud Rate (RS.BR) to match that of the Protec panel graphics port
 Set the Panel Type (P.T) to match the series of panel the driver is connected to. Set this to ‘6500’,
‘5400/6400’, or ‘AN95/6300’.

Checking Communications
The Protec Setup object contains a Comms Online (DS) objects. A value of ‘Yes’ indicates the driver has
connected to, and is communicating with the Protec system.

The Protec Driver 6


Alarms
When the Protec system reports an event to the driver, the driver sends a North-format alarm to the
device’s alarm processing.

Format
North-format alarms contain six text fields. The Protec driver places the following information into these
fields:
System – copied from System Label object (DL) within driver setup
Point – see Point Field section below
Condition – see Condition and Priority Field section below
Priority – see Condition and Priority Field section below
Date & Time – from connected panel

Examples
System Point Condition Priority Date Time
Protec System Zone 1 Isolated 2 10/03/14 14:29:48
Protec System Zone 1 De-Isolated 2 10/03/14 14:35:12
Protec System Panel 12 Loop 1 Dev 12 Zone 12 Pre-Alarm 2 10/03/14 14:26:26
Protec System Panel 2 Loop 1 Dev 1 Zone 16 Fire 1 10/03/14 15:06:59
Protec System Panel 2 Alarms Silenced 3 10/03/14 15:07:35
Protec System Panel 2 Reset 1 10/03/14 15:07:40
Protec System Panel 2 Loop 1 Dev 1 Zone 16 Fire Cleared 1 10/03/14 15:07:40
Protec System Panel 12 Loop 1 Dev 12 Zone 12 Pre-Alarm Cleared 2 10/03/14 16:26:26

Point Field
Selected by Alarm Point Field object (AT) within driver setup.
If ‘PLD reference’ option is selected, Point Field contains:
System
Panel a
Panel a Loop b
Panel a Loop b Dev c
Panel a Loop b Dev c Zone d
Zone d
System
If ‘Label from panel’ option is selected, Point Field contains:
device-location
Panel a device-location

The Protec Driver 7


Condition and Priority Field
The following alarm conditions can be sent by the driver:
Active Condition Inactive Condition Priority
Fire Fire Cleared 1
Reset 1
RS232 Comms Failure RS232 Comms Failure Cleared 1
Isolated De-Isolated 2
Pre-Alarm Pre-Alarm Cleared 2
General Alarm General Alarm Cleared 2
Technical Alarm Technical Alarm Cleared 2
Alarm Fault Alarm Fault Cleared 3
Evacuate 3
Alarms Silenced 3
Aux 24V Supply Fault Aux 24V Supply Fault Cleared 3
Earth Fault Earth Fault Cleared 3
Fault Fault Cleared 3
RS485 Fault RS485 Fault Cleared 3
Signalling Error Signalling Error Cleared 3
Supply Fault Supply Fault Cleared 3
System Fault System Fault Cleared 3
System Fault: Clock System Fault Cleared 3
System Fault: EEPROM System Fault Cleared 3
System Fault: Event System Fault Cleared 3
System Fault: Flash System Fault Cleared 3
System Fault: IO System Fault Cleared 3
System Fault: LCD System Fault Cleared 3
System Fault: LDU System Fault Cleared 3
System Fault: Local System Fault Cleared 3
System Fault: Menu System Fault Cleared 3
System Fault: Printer System Fault Cleared 3
System Fault: Software System Fault Cleared 3
Type Fault Type Fault Cleared 3
Zone Fault Zone Fault Cleared 3
Alarms Outputs Disabled Alarms Outputs Enabled 4
Buzzer Isolated Buzzer De-Isolated 4
Control Outputs Disabled Control Outputs Enabled 4
Device Added Device Added Cleared 4
Engineer Test Engineer Test Cleared 4
Event Accepted 4
Fault Links Disabled Fault Links Enabled 4
Fire Links Disabled Fire Links Enabled 4
Fire Protection Disabled Fire Protection Enabled 4
High-Level Access Login High-Level Access Logout 4
Initialisation Initialisation Cleared 4
Missing Loop Devices 4
Non-Fire Outputs Disabled Non-Fire Outputs Enabled 4

A panel may not send all conditions listed.

Zone isolations may indicate a part isolation by appending the condition with ‘(Auto)’ to indicate
automatic detection devices, or ‘(MCP)’ to indicate manually operated devices.

The Protec Driver 8


Object Specifications
Once an interface has been started, one or more extra objects become available within the top-level
object of the device. As with all North objects, each of these extra objects may contain sub-objects, (and
each of these may contain sub-objects, and so on) - the whole object structure being a multi-layer
hierarchy. It is possible to navigate around the objects using the ObSys Engineering Software.
Each object is specified below, along with its sub-objects.

Example Object Reference


An example of a reference to an object in the same device: the Protec System (S1) contains Panel 1 (P1),
which contains Loop 2 (L2), which has Device 22 (D22), which contains an alarm state (C). Therefore, the
complete object reference will be ‘S1.P1.L2.D22.C’.
An example of a reference to an object in a different device: the IP network object (IP) contains Default
Commander object (CDIP), which contains the object above (S1.P1.L2.D22.C) – therefore the complete
object reference is ‘IP.CDIP.S1.P1.L2.D22.C’.

Device Top-Level Objects


When an interface is started using the Protec driver, the objects below become available within the top-
level object of the device. For example, if Interface 1 is started, then the object with references ‘M1’ and
‘S1’ become available.
Description Reference Type
Protec Setup Mc Fixed Container:
Set up the Protec driver, started on On the Commander platform this will be
interface c (c is the interface number) [CDM v20\Protec v15]
On the ObSys platforms this will be
[OSM v20\Protec v15]
Protec System Sc Fixed Container:
Access Protec system connected to On a 6500 series panel network this will be
interface c (c is the interface number) [Protec v15\6600]
On a x400 series panel network this will be
[Protec v15\X400]
On a x300/AN95 series panel network this will be
[Protec v15\AN95]

The Protec Driver 9


Protec Driver Setup
Object Type: [OSM v20\Protec v15]
Object Type: [CDM v20\Protec v15]

The Protec driver contains the following objects:


Description Reference Type
RS232 COM port RS.COM Obj\Num: 1…8; Adjustable

Baud Rate RS.BR Obj\Num: 600…19200; Adjustable


Baud rate of the connected fire panel,
typically 9600 or 19200 baud.
Algo-tec 6300 panels use 600 baud.
System Label DL Obj\Text: 20 Chars; Adjustable
Label displayed when scanning the system
and within alarms
Comms Online DS Obj\NoYes
Indicates whether communication is
established with the panel
Panel Type PT Obj\Enum: 0…1; Adjustable
Select the series of Protec panel Where: 0=AN95/6300, 1=5400/6400, 2=6500
connected
Alarm Point Field AT Obj\Enum: 0…1; Adjustable
Selects source of the alarm message point Where: 0=PLD reference,1=Label from panel
field.
When set to ‘1’ (Label from panel), alarms
sent include the panel/loop/device label if
provided from the panel
Alarm include Panel AP Obj\NoYes; Adjustable
Prefixes loop and device alarms with the
panel number, when Alarm point field (AT)
is set ‘1’ (Label from panel)
Event storage available SC Obj\Num: 0…800
Each event from the system must be
remembered by the driver. If no storage is
available for a new event, the driver will
not be able to remember it.
Resync Interface RST Obj\NoYes; Adjustable
Clears the driver’s internal database or
event and output group overrides, then re-
requests the current state from the Protec
system.
Filter Events FE Fixed Container:
Stop the driver listening for particular On the Commander platform this will be
event types or panels. This provides more [CDM v20\Protec v15\Filter]
event storage for other event types. On the ObSys platforms this will be
[OSM v20\Protec v15\Filter]
Advanced Setup A Fixed Container:
Additional configuration options On the Commander platform this will be
[CDM v20\Protec v15\Advanced]
On the ObSys platforms this will be
[OSM v20\Protec v15\Advanced]

The Protec Driver 10


Protec Driver Filter Events
Object Type: [OSM v20\Protec v15\Filter]
Object Type: [CDM v20\Protec v15\Filter]

Each event from the Protec Fire Detection system must be remembered by the driver. On a large Protec
system with more than 800 active events at any one time, use this object to select which event types are
ignored by the driver – isolation, fault, damper events, etc.
If more event storage is required, use multiple connections to Protec, with each Protec driver configured
to store events for a particular range of panels.
Description Reference Type
Ignore Isolation events I.C1 Obj\NoYes; Adjustable
Enable to ignore isolation events from the
system. This provides more event storage
for other event conditions
Ignore Fault events I.C2 Obj\NoYes; Adjustable
Enable to ignore fault events from the
system
Ignore Pre-Alarm events I.C3 Obj\NoYes; Adjustable
Enable to ignore pre-alarm events from
the system
Ignore Fire events I.C4 Obj\NoYes; Adjustable
Enable to ignore fire events from the
system
Ignore Damper events I.C5 Obj\NoYes; Adjustable
Enable to ignore damper events from the
system. This provides more event storage
for other event conditions
Store events from panel (start) PS Obj\Num: 0…99; Adjustable
Lowest address of network interface panel
to store events from
Store events from panel (end) PE Obj\Num: 1…99; Adjustable
Highest address of network interface panel
to store events from

Protec Advanced Setup


Object Type: [OSM v20\Protec v15\Advanced]
Object Type: [CDM v20\Protec v15\Advanced]

The Protec driver contains the following advanced configuration options.


Description Reference Type
Resend Output Group Overrides OG Obj\NoYes; Adjustable
Set to ‘Yes’ to send Output Group Default value: ‘No’
overrides when the panel is reset
Pause between commands (ms) PT Obj\Num: 0…10000; Adjustable
The delay between sending commands to Default value: ‘0’
the panel. On 5400/6300/6400 panels this
should be set to ‘10000’ ms (10 seconds).
On 6500 panels this can be set to ‘0’.
Enable platform time sync TS Obj\NoYes; Adjustable
Enable to set the North device’s date and Default value: ‘No’
time when commanded from the Protec
system.

The Protec Driver 11


6500 Series System
Object Type: [Protec v15\6600]

The Protec series 6500 system is a network of Protec 6500 fire detection panels. It contains objects to
view the status of the whole system (P) and objects to access information from each connected panel
(Px).
Description Reference Type
Zone & System Summary P Fixed container can be one of the following types:
[Protec v15\6600\System]
Panel x Px Fixed container, can be one of the following types:
The panel number, x, can be in the range [Protec v15\6600\Panel]
1…160

x400 Series System


Object Type: [Protec v15\X400]

The Protec series x400 system is a network of Protec 6400 or 5400 fire detection panels. It contains
objects to view the status of the whole system (P) and objects to access information from each
connected panel (Px).
Description Reference Type
Zone & System Summary P Fixed container can be one of the following types:
[Protec v15\X400\System]
Panel x Px Fixed container, can be one of the following types:
The panel number, x, can be in the range [Protec v15\X400\Panel]
1…99

x300 Series System


Object Type: [Protec v15\AN95]

The Protec series x300 system is a network of Protec 6300 or AN95 fire detection panels. It contains
objects to view the status of the whole system (P) and objects to access information from each
connected panel (Px).
Description Reference Type
Zone & System Summary P Fixed container can be one of the following types:
[Protec v15\AN95\System]
Panel x Px Fixed container, can be one of the following types:
The panel number, x, can be in the range [Protec v15\AN95\Panel]
1…64

The Protec Driver 12


Zone & System Summary
Object Type: [Protec v15\6600\System]
Object Type: [Protec v15\X400\System]
Object Type: [Protec v15\AN95\System]

The Protec Zone and System Summary object contains zone and network-wide status for the Protec
system. Objects are also available to perform network-wide commands – reset, silence, etc.
Description Reference Type
Commands A Fixed Container:
Contains objects for resetting latched On a 6500 series panel network this will be
events, and silencing sounders [Protec v15\6600\Actions]
On a x400 series panel network this will be
[Protec v15\X400\Actions]
On a x300 series panel network this will be
[Protec v15\AN95\Actions]
System Alarm State C Obj\Enum: 0…4
Where: 0=OK,1=Isolate,2=Fault,3=Pre-alarm,4=Fire
System Ok C0 Obj\NoYes
Isolation C1 Obj\NoYes
MCP Devices Isolated C1.M Obj\NoYes
Indicates one or more manual call-point
devices within the zone are isolated
Auto Devices Isolated C1.A Obj\NoYes
Indicates one or more automatic detection
devices within the zone are isolated
Fault C2 Obj\NoYes
Pre-Alarm C3 Obj\NoYes
Fire C4 Obj\NoYes
Zone x Zx Fixed container:
The zone number, x, is in the range 1…800 [Protec v15\Zone]
for x400 panels; and 1…255 for x300
panels

Compatibility Objects
The Protec system also contains the following objects for backward compatibility.

Description Reference Type


System Value V1 Obj\ENum
System alarm state Value: 0=OK, 8=Damper activated, 10=Earth fault,
12=System fault, 13=Supply fault, 15=Detector fault,
16=Loop fault, 19=Alarms sounding, 20=Devices
Isolated, 21=Pre-Alarm, 22=Fire
Devices in Fault b condition Fb Obj\NoYes
The fault condition, b, is in the range
8…22, where: 8=Damper activated,
10=Earth fault, 12=System fault, 13=Supply
fault, 15=Detector fault, 16=Loop fault,
19=Alarms sounding, 20=Devices Isolated,
21=Pre-Alarm, 22=Fire

The Protec Driver 13


Commands
Object Type: [Protec v15\6600\Actions]
Object Type: [Protec v15\X400\Actions]
Object Type: [Protec v15\AN95\Actions]

A Protec Command object allows an action to be set within the Protec system:
Description Reference Type
Reset R Obj\NoYes; Adjustable only
Performs a reset on the panel
Sounders S Obj\OffOn
Silences or re-sounds the sounders
Accept A Obj\NoYes; Adjustable only
Accept alarms, and silence the panel
buzzer.
Object available in x400 series panels only
Date and Time TIME Obj\DateTime; Adjustable
Set the system date and time

The Protec Driver 14


Zone
Object Type: [Protec v15\Zone]

A Protec zone contains the following objects:


Description Reference Type
Zone Alarm State C Obj\Enum: 0…4;
Where: 0=Ok, 1=Isolated, 2=Fault, 3=Pre-Alarm, 4=Fire
Zone OK C0 Obj\NoYes
Zone Devices Isolated C1 Obj\NoYes
Indicates one or more devices within the
zone are isolated
Zone MCP Devices Isolated C1.M Obj\NoYes
Indicates one or more manual call-point
devices within the zone are isolated
Zone Auto Devices Isolated C1.A Obj\NoYes
Indicates one or more automatic detection
devices within the zone are isolated
Zone Devices in Fault C2 Obj\NoYes
Zone Devices in Pre-Alarm C3 Obj\NoYes
Zone Devices in Fire C4 Obj\NoYes

Compatibility Objects
A Protec zone also contains the following objects for backward compatibility.

Description Reference Type


Zone Value V1 Obj\ENum
Zone alarm state Value: 0=OK, 8=Damper activated, 15=Detector fault,
16=Loop fault, 20=Devices Isolated, 21=Pre-Alarm,
22=Fire
Zone Devices in Fault b condition Fb Obj\NoYes
The fault condition, b, is in the range
8…22, where: 8=Damper activated,
15=Detector fault, 16=Loop fault,
20=Devices Isolated, 21=Pre-Alarm,
22=Fire

The Protec Driver 15


6500 Series Panel
Object Type: [Protec v15\6600\Panel]

A Protec 6500 series panel contains the following objects:


Description Reference Type
Panel Alarm State C Obj\Enum: 0…4
Where: 0=Ok,1=Isolate,2=Fault,3=Pre-alarm,4=Fire
Panel Ok C0 Obj\NoYes
Isolation C1 Obj\NoYes
Fault C2 Obj\NoYes
Pre-Alarm C3 Obj\NoYes
Fire C4 Obj\NoYes
Loop x Lx Fixed container:
The Loop number, x, is in the range 1…4 [Protec v15\6600\Loop]
Output Group y Oy Fixed container:
The Output Group number, y, is in the [Protec v15\Output]
range 1…255

Compatibility Objects
A Protec panel also contains the following objects for backward compatibility.

Description Reference Type


Panel Value V1 Obj\ENum
Panel alarm state Value: 0=OK, 8=Damper activated, 10=Earth fault,
12=System fault, 13=Supply fault, 15=Detector fault,
16=Loop fault, 19=Alarms sounding, 20=Devices
Isolated, 21=Pre-Alarm, 22=Fire
Devices in Fault b condition Fb Obj\NoYes
The fault condition, b, is in the range
8…22, where: 8=Damper activated,
10=Earth fault, 12=System fault, 13=Supply
fault, 15=Detector fault, 16=Loop fault,
19=Alarms sounding, 20=Devices Isolated,
21=Pre-Alarm, 22=Fire

The Protec Driver 16


6500 Series Loop
Object Type: [Protec v15\6600\Loop]

A Protec panel loop contains the following objects:


Description Reference Type
Loop Alarm State C Obj\Enum: 0…4;
Where: 0=Ok, 1=Isolated, 2=Fault, 3=Pre-Alarm, 4=Fire
Loop Ok C0 Obj\NoYes
Loop Devices Isolated C1 Obj\NoYes
Indicates one or more devices are isolated
Loop/Devices in Fault C2 Obj\NoYes
Loop Devices in Pre-Alarm C3 Obj\NoYes
Loop Devices in Fire C4 Obj\NoYes
Device x Dx Fixed container:
The device address, x, is in the range [Protec v15\Dev]
1…512

Compatibility Objects
A Protec loop also contains the following objects for backward compatibility.

Description Reference Type


Loop Value V1 Obj\ENum
Loop alarm state Value: 0=OK, 8=Damper activated, 13=Supply fault,
15=Detector fault, 16=Loop fault, 20=Devices Isolated,
21=Pre-Alarm, 22=Fire
Loop Devices in Fault b condition Fb Obj\NoYes
The fault condition, b, is in the range
8…22, where: 8=Damper activated,
13=Supply fault, 15=Detector fault,
16=Loop fault, 20=Devices Isolated,
21=Pre-Alarm, 22=Fire

The Protec Driver 17


x400 Series Panel
Object Type: [Protec v15\X400\Panel]

A Protec x400 series panel contains the following objects:


Description Reference Type
Panel Alarm State C Obj\Enum: 0…4
Where: 0=Ok,1=Isolate,2=Fault,3=Pre-alarm,4=Fire
Panel Ok C0 Obj\NoYes
Isolation C1 Obj\NoYes
Fault C2 Obj\NoYes
Pre-Alarm C3 Obj\NoYes
Fire C4 Obj\NoYes
Loop x Lx Fixed container:
The Loop number, x, is in the range 1…4 [Protec v15\X400\Loop]
on x400 panels
Output Group y Oy Fixed container:
The Output Group number, y, is in the [Protec v15\Output]
range 1…255

Compatibility Objects
A Protec panel also contains the following objects for backward compatibility.

Description Reference Type


Panel Value V1 Obj\ENum
Panel alarm state Value: 0=OK, 8=Damper activated, 10=Earth fault,
12=System fault, 13=Supply fault, 15=Detector fault,
16=Loop fault, 19=Alarms sounding, 20=Devices
Isolated, 21=Pre-Alarm, 22=Fire
Devices in Fault b condition Fb Obj\NoYes
The fault condition, b, is in the range
8…22, where: 8=Damper activated,
10=Earth fault, 12=System fault, 13=Supply
fault, 15=Detector fault, 16=Loop fault,
19=Alarms sounding, 20=Devices Isolated,
21=Pre-Alarm, 22=Fire

The Protec Driver 18


x300 Series Panel
Object Type: [Protec v15\AN95\Panel]

A Protec x300 series panel contains the following objects:


Description Reference Type
Panel Alarm State C Obj\Enum: 0…4
Where: 0=Ok,1=Isolate,2=Fault,3=Pre-alarm,4=Fire
Panel Ok C0 Obj\NoYes
Isolation C1 Obj\NoYes
Fault C2 Obj\NoYes
Pre-Alarm C3 Obj\NoYes
Fire C4 Obj\NoYes
Loop x Lx Fixed container:
The Loop number, x, is in the range 1…8 [Protec v15\AN95\Loop]
on x300 panels

The Protec Driver 19


x400/x300 Series Loop
Object Type: [Protec v15\X400\Loop]
Object Type: [Protec v15\AN95\Loop]

A Protec panel loop contains the following objects:


Description Reference Type
Loop Alarm State C Obj\Enum: 0…4;
Where: 0=Ok, 1=Isolated, 2=Fault, 3=Pre-Alarm, 4=Fire
Loop Ok C0 Obj\NoYes
Loop Devices Isolated C1 Obj\NoYes
Indicates one or more devices are isolated
Loop/Devices in Fault C2 Obj\NoYes
Loop Devices in Pre-Alarm C3 Obj\NoYes
Loop Devices in Fire C4 Obj\NoYes
Device x Dx Fixed container:
The device address, x, is in the range [Protec v15\Dev]
1…127

Compatibility Objects
A Protec loop also contains the following objects for backward compatibility.

Description Reference Type


Loop Value V1 Obj\ENum
Loop alarm state Value: 0=OK, 8=Damper activated, 13=Supply fault,
15=Detector fault, 16=Loop fault, 20=Devices Isolated,
21=Pre-Alarm, 22=Fire
Loop Devices in Fault b condition Fb Obj\NoYes
The fault condition, b, is in the range
8…22, where: 8=Damper activated,
13=Supply fault, 15=Detector fault,
16=Loop fault, 20=Devices Isolated,
21=Pre-Alarm, 22=Fire

The Protec Driver 20


Device
Object Type: [Protec v15\Dev]

The Protec loop device contains the following objects:


Description Reference Type
Device Alarm State C Obj\Enum: 0…4; Adjustable
Where: 0=Ok, 1=Isolated, 2=Fault, 3=Pre-Alarm, 4=Fire
Adjustable values: 0=Deisolate, 1=Isolate
Device Ok C0 Obj\NoYes
Device Isolated C1 Obj\NoYes; Adjustable on 5400/6400 and 6500 series
panels only
Device in Fault C2 Obj\NoYes
Device in Pre-Alarm C3 Obj\NoYes
Device in Fire C4 Obj\NoYes
Damper Activated C5 Obj\NoYes

Compatibility Objects
A Protec loop device also contains the following objects for backward compatibility.

Description Reference Type


Device Value V1 Obj\ENum
Device alarm state Value: 0=OK, 8=Damper activated, 13=Supply fault,
15=Detector fault, 20=Device Isolated, 21=Pre-Alarm,
22=Fire
Device in Fault b condition Fb Obj\NoYes
The fault condition, b, is in the range
8…22, where: 8=Damper activated,
13=Supply fault, 15=Detector fault,
20=Device Isolated, 21=Pre-Alarm, 22=Fire
Isolate Device I Obj\NoYes: Adjustable only
Object available in 5400/6400 and 6500
series panels only

The Protec Driver 21


Output Group
Object Type: [Protec v15\Output]

A Protec Output Group object controls devices connected to the panel, such as dampers.
The driver remembers the last override state set (on panels up to 99), reading the object returns this
state. If the output group has not been overridden using the driver, then an automatic state is returned.
The Protec fire panel reverts all output group overrides to automatic when reset, use the Advanced Driver
Setup object (A.OG) to enable resending of overrides after a reset. Refer to Driver Operation for more
details.
The following objects are available to control the same output group. Select the object most suited to
your application.
Description Reference Type
Override S Obj\Enum: 0…3; Adjustable only
Override the output group state to ‘Off’, Where: 0=Override to Off, 1=Override to On,
‘On’, or release to automatic control. 3=Automatic (release override)
Override to On N Obj\NoYes; Adjustable
Override the output group state to ‘On’, or Where: 0=Automatic (release override), 1=Override to On
release to automatic control.
Override to Off F Obj\NoYes; Adjustable
Override the output group state to ‘Off’, or Where: 0=Automatic (release override), 1=Override to
release to automatic control. Off

The Protec Driver 22


Driver Versions
Version Build Date Details
1.0 1/9/2000 Driver released
1.1 9/8/2007 Added damper control status objects (6000 damper interface)
1.2 25/10/2010 Increased database size.
Added System object (P) and moved zones from per panel to this common object.
Updated driver to use new North fire object model.
Added objects to ignore isolations, event free count, and resync.
6300 panels now supported with panel firmware after March 2009.
1.2 24/9/2011 Alarm events now include more text from panel
1.3 28/5/2013 Updated for protocol issue 15 – new events
Improved damper support
Added ignore damper events object
1.3 11/2/2015 Updated for protocol issue 16 – removed unused alarms
Added support for MICCO damper states
Resolved issue when setting output group to ‘off’
1.4 1/3/2016 Updated for protocol issue 18
Added support for Algo-tec 6000PLUS protocol (version 3)
Added support for zone part-isolation (added objects Zx.C1.A and .M)
Added support for larger MICCO modules
Increased event storage
Driver object IDP changed to EDP (Enable damper events)
Driver object ETD (Enable platform time sync) added
Driver object AP (prefix loop/dev alarms with panel number) added
Added support for more events – passed as alarm messages
1.4 7/7/2017 Added objects Oy.N and Oy.F to provide conversion on override outputs
1.4 21/1/2019 Resolved issue with protocol device text field length. Previously, this may have
caused a loss of communications with the panel if the device text field was
corrupt.
1.5 29/3/2019 Updated for protocol issue 19
Added support for General Alarm and Technical Alarm events. Indicated using pre-
alarm state.
10 second pause between commands enforced for 5400/6300/6400 panels.
Option to re-send output group overrides when the panel is reset.
Modified and added driver objects for filtering events (objects from previous
versions still valid).
For isolations, .C objects are now adjustable

Next Steps…
If you require help, contact support on 01273 694422 or visit www.northbt.com/support

This document is subject to change without notice and does not


represent any commitment by North Building Technologies Ltd.
ObSys and Commander are trademarks of North Building
Technologies Ltd. All other trademarks are property of their respective
owners.
North Building Technologies Ltd
+44 (0) 1273 694422 © Copyright 2023 North Building Technologies Limited.
[email protected] Author: BS
www.northbt.com Checked by: JF
Document issued 22/03/2023.

The Protec Driver 23

You might also like