Protec Driver Manual
Protec Driver Manual
The Protec driver connects to the Protec Fire Detection range of digital addressable fire control
panels. Available for Commander and ObSys.
Please read the Commander Manual or ObSys Manual alongside this document, available from
www.northbt.com
Contents
Compatibility with the Protec System ......................................................................................... 3
Equipment ........................................................................................................................................ 3
Values ................................................................................................................................................ 3
Prerequisites ..................................................................................................................................... 3
Alarms ........................................................................................................................................... 7
Format ............................................................................................................................................... 7
Examples ........................................................................................................................................... 7
Point Field ......................................................................................................................................... 7
Condition and Priority Field ............................................................................................................. 8
North
device
RS232
Protec
panel
Equipment
Protec Fire Detection control panels compatible with the driver include:
• Algo-tec 6500 series
• Algo-tec 5400/6400 series
• Algo-tec 6300 and AN95
Values
Depending on the series of fire control panel, the driver can typically access the following values:
• Reset panel • Loop state
• Sounders • Loop device state
• Date & Time • Zone state
• System state • Output group (5400/6400 and 6500 series only)
• Panel state • Damper state (5400/6400 and 6500 series only)
States for fire, pre-alarm, fault, and isolation conditions are available.
Fire control panels can send alarms to the Protec driver.
Prerequisites
Algo-tec 6300 panel only: this has limited capacity when communicating that a large number of devices
have changed state. Typically, this is when all devices in a zone have been isolated/de-isolated. After this
type of operation, use the Resync Driver object (RST) to re-synchronise the driver with the Protec system.
The Algo-tec 6300 panel uses a 600 baud serial connection. On Commander, this requires version 2.0
build 15/06/16 or later.
Alarms
When an event is received from the Protec panel, the driver sends this as a North-format alarm to the
device’s alarm processing.
Output Groups
Output groups are used by the panel to control groups of output devices, such as sounders, dampers etc.
The driver can be used to override an output group from its automatic state to either ‘on’ or ‘off’. When
you override an output on panels up to 99, the driver remembers this state so you can read it. The driver
does not listen to output groups events from the panel.
When the fire system is reset all output groups return to their automatic state, cancelling any overrides.
When integrating the fire panel with an HVAC system, outputs are typically used to open ventilation
dampers. If the advanced driver object Resend Output Group Overrides (A.OG) is enabled, then any
output group overridden by the driver (on panels up to 99) will be re-commanded to its override state
whenever the fire system is reset.
Output group overrides are remember during a power-cycle. Use the Resync Driver object (RST) to clear
the driver’s memory of overridden output groups.
Protec may supply an RS232 opto-isolator device with the panel. On the Commander platform, this is not
required as Commander’s RS232 ports are isolated. The cable connecting pins 4 & 7 is only required when
an opto-isolator is used.
Connector types at each end of the cable are shown.
North Protec
DB9 Female DB9 Male
2 2
3 3
5 5
4 7
Fig. 2 North to Protec cable
Checking Communications
The Protec Setup object contains a Comms Online (DS) objects. A value of ‘Yes’ indicates the driver has
connected to, and is communicating with the Protec system.
Format
North-format alarms contain six text fields. The Protec driver places the following information into these
fields:
System – copied from System Label object (DL) within driver setup
Point – see Point Field section below
Condition – see Condition and Priority Field section below
Priority – see Condition and Priority Field section below
Date & Time – from connected panel
Examples
System Point Condition Priority Date Time
Protec System Zone 1 Isolated 2 10/03/14 14:29:48
Protec System Zone 1 De-Isolated 2 10/03/14 14:35:12
Protec System Panel 12 Loop 1 Dev 12 Zone 12 Pre-Alarm 2 10/03/14 14:26:26
Protec System Panel 2 Loop 1 Dev 1 Zone 16 Fire 1 10/03/14 15:06:59
Protec System Panel 2 Alarms Silenced 3 10/03/14 15:07:35
Protec System Panel 2 Reset 1 10/03/14 15:07:40
Protec System Panel 2 Loop 1 Dev 1 Zone 16 Fire Cleared 1 10/03/14 15:07:40
Protec System Panel 12 Loop 1 Dev 12 Zone 12 Pre-Alarm Cleared 2 10/03/14 16:26:26
Point Field
Selected by Alarm Point Field object (AT) within driver setup.
If ‘PLD reference’ option is selected, Point Field contains:
System
Panel a
Panel a Loop b
Panel a Loop b Dev c
Panel a Loop b Dev c Zone d
Zone d
System
If ‘Label from panel’ option is selected, Point Field contains:
device-location
Panel a device-location
Zone isolations may indicate a part isolation by appending the condition with ‘(Auto)’ to indicate
automatic detection devices, or ‘(MCP)’ to indicate manually operated devices.
Each event from the Protec Fire Detection system must be remembered by the driver. On a large Protec
system with more than 800 active events at any one time, use this object to select which event types are
ignored by the driver – isolation, fault, damper events, etc.
If more event storage is required, use multiple connections to Protec, with each Protec driver configured
to store events for a particular range of panels.
Description Reference Type
Ignore Isolation events I.C1 Obj\NoYes; Adjustable
Enable to ignore isolation events from the
system. This provides more event storage
for other event conditions
Ignore Fault events I.C2 Obj\NoYes; Adjustable
Enable to ignore fault events from the
system
Ignore Pre-Alarm events I.C3 Obj\NoYes; Adjustable
Enable to ignore pre-alarm events from
the system
Ignore Fire events I.C4 Obj\NoYes; Adjustable
Enable to ignore fire events from the
system
Ignore Damper events I.C5 Obj\NoYes; Adjustable
Enable to ignore damper events from the
system. This provides more event storage
for other event conditions
Store events from panel (start) PS Obj\Num: 0…99; Adjustable
Lowest address of network interface panel
to store events from
Store events from panel (end) PE Obj\Num: 1…99; Adjustable
Highest address of network interface panel
to store events from
The Protec series 6500 system is a network of Protec 6500 fire detection panels. It contains objects to
view the status of the whole system (P) and objects to access information from each connected panel
(Px).
Description Reference Type
Zone & System Summary P Fixed container can be one of the following types:
[Protec v15\6600\System]
Panel x Px Fixed container, can be one of the following types:
The panel number, x, can be in the range [Protec v15\6600\Panel]
1…160
The Protec series x400 system is a network of Protec 6400 or 5400 fire detection panels. It contains
objects to view the status of the whole system (P) and objects to access information from each
connected panel (Px).
Description Reference Type
Zone & System Summary P Fixed container can be one of the following types:
[Protec v15\X400\System]
Panel x Px Fixed container, can be one of the following types:
The panel number, x, can be in the range [Protec v15\X400\Panel]
1…99
The Protec series x300 system is a network of Protec 6300 or AN95 fire detection panels. It contains
objects to view the status of the whole system (P) and objects to access information from each
connected panel (Px).
Description Reference Type
Zone & System Summary P Fixed container can be one of the following types:
[Protec v15\AN95\System]
Panel x Px Fixed container, can be one of the following types:
The panel number, x, can be in the range [Protec v15\AN95\Panel]
1…64
The Protec Zone and System Summary object contains zone and network-wide status for the Protec
system. Objects are also available to perform network-wide commands – reset, silence, etc.
Description Reference Type
Commands A Fixed Container:
Contains objects for resetting latched On a 6500 series panel network this will be
events, and silencing sounders [Protec v15\6600\Actions]
On a x400 series panel network this will be
[Protec v15\X400\Actions]
On a x300 series panel network this will be
[Protec v15\AN95\Actions]
System Alarm State C Obj\Enum: 0…4
Where: 0=OK,1=Isolate,2=Fault,3=Pre-alarm,4=Fire
System Ok C0 Obj\NoYes
Isolation C1 Obj\NoYes
MCP Devices Isolated C1.M Obj\NoYes
Indicates one or more manual call-point
devices within the zone are isolated
Auto Devices Isolated C1.A Obj\NoYes
Indicates one or more automatic detection
devices within the zone are isolated
Fault C2 Obj\NoYes
Pre-Alarm C3 Obj\NoYes
Fire C4 Obj\NoYes
Zone x Zx Fixed container:
The zone number, x, is in the range 1…800 [Protec v15\Zone]
for x400 panels; and 1…255 for x300
panels
Compatibility Objects
The Protec system also contains the following objects for backward compatibility.
A Protec Command object allows an action to be set within the Protec system:
Description Reference Type
Reset R Obj\NoYes; Adjustable only
Performs a reset on the panel
Sounders S Obj\OffOn
Silences or re-sounds the sounders
Accept A Obj\NoYes; Adjustable only
Accept alarms, and silence the panel
buzzer.
Object available in x400 series panels only
Date and Time TIME Obj\DateTime; Adjustable
Set the system date and time
Compatibility Objects
A Protec zone also contains the following objects for backward compatibility.
Compatibility Objects
A Protec panel also contains the following objects for backward compatibility.
Compatibility Objects
A Protec loop also contains the following objects for backward compatibility.
Compatibility Objects
A Protec panel also contains the following objects for backward compatibility.
Compatibility Objects
A Protec loop also contains the following objects for backward compatibility.
Compatibility Objects
A Protec loop device also contains the following objects for backward compatibility.
A Protec Output Group object controls devices connected to the panel, such as dampers.
The driver remembers the last override state set (on panels up to 99), reading the object returns this
state. If the output group has not been overridden using the driver, then an automatic state is returned.
The Protec fire panel reverts all output group overrides to automatic when reset, use the Advanced Driver
Setup object (A.OG) to enable resending of overrides after a reset. Refer to Driver Operation for more
details.
The following objects are available to control the same output group. Select the object most suited to
your application.
Description Reference Type
Override S Obj\Enum: 0…3; Adjustable only
Override the output group state to ‘Off’, Where: 0=Override to Off, 1=Override to On,
‘On’, or release to automatic control. 3=Automatic (release override)
Override to On N Obj\NoYes; Adjustable
Override the output group state to ‘On’, or Where: 0=Automatic (release override), 1=Override to On
release to automatic control.
Override to Off F Obj\NoYes; Adjustable
Override the output group state to ‘Off’, or Where: 0=Automatic (release override), 1=Override to
release to automatic control. Off
Next Steps…
If you require help, contact support on 01273 694422 or visit www.northbt.com/support