WATTSTOPPER®

ULTRASONIC LINE VOLTAGE CEILING SENSOR


UT-355

Architecturally appealing Operates at 120, 230 (single


low-profile appearance phase), 277 or 347 VAC, 50/60 Hz

Utilizes advanced,
Terminal wiring for quick
omni-directional, ultrasonic
and easy installation
technology

Ultrasonic diffusers provide Walk-through mode


more comprehensive coverage increases savings potential

DESCRIPTION TIME DELAY OPTIONS


Wattstopper’s low-profile UT-355 Ultrasonic Line Voltage The UT-355 is factory set for a 20 minute time delay, ideal for
Ceiling Sensor automatically turns lighting on and off based both energy savings and user satisfaction in most applications.
on occupancy. The sensor mounts on the ceiling with a flat, Installers can quickly select other fixed time delays (5, 10, 15
unobtrusive appearance and provides 360° coverage. or 30 minutes) via DIP switches. Fixed time delays eliminate
the occupant dissatisfaction associated with an automatically
OPERATION adjusted time delay option, and reduce callbacks. Walk-through
mode may be enabled for added energy savings in spaces with
The UT-355 is line voltage and operates on a single phase
frequent transient traffic.
at 120, 230, 277, or 347 VAC. It uses high frequency (40 kHz)
ultrasound to sense occupancy and automatically turn lighting APPLICATIONS
on. When no occupancy is detected for the length of the time
delay, lighting automatically turns off. UT sensors offer excellent control of lighting for many spaces,
including restrooms and large offices. The UT sensors’
performance and ease of installation will provide fast paybacks
and many years of energy savings.

FEATURES
• Advanced control logic based on RISC micro-controller • Coverage 500-1,600 square feet
provides: • DIP switch simplifies sensor adjustments
– Advanced Signal Processing to eliminate false triggers
and provide immunity to RFI and EMI • Patented ultrasonic diffusion technology spreads coverage
– Walk-through Mode to turn lights off three minutes after to a wider area
the area is initially occupied, ideal for brief visits such as • Clip mounting system makes ceiling tile installation simple
mail delivery
• Terminal wiring system provides quick and easy installation
• Zero-crossing for long relay life
• Sensor coverage tested to NEMA Guide Publication
• LED indicates occupancy detection WD 7-2000

1 WWW.LEGRAND.US/WAT TSTOPPER
SENSORS | Occupancy and Vacancy

SPECIFICATIONS
• 120/230 (single phase)/277/347 VAC, 50/60 Hz • Mounting options: 4” square junction box with double-gang
• Time delays: 5, 10, 15, 20, or 30 minutes, Walk-through & mud ring; 4”octagonal junction box
Test modes • Dimensions: 4.5” x 1.45” (114.3mm x 25.9mm) diameter x depth
• Sensitivity adjustment: variable with trimpot • UL and cUL listed
• Ultrasonic frequency of 40 kHz • Five year warranty

WIRING & MOUNTING


Wiring Diagram Ceiling Mounting
1HXWUDO 4" Square, 2.25" Deep*
/RDG Junction Box with
Double Gang
Mudring attached

6ZLWFK /RDG +RW Drop Ceiling

CA-1 Adapter

*URXQG 1HXWUDO
2SWLRQDO Rear Housing
Sensor Flange

Feature
Screws Switch#
FrontDelay 1 2 3
Time
Cover
Test Mode/20 min
30 seconds
5 minutes
CONTROLS & SETTINGS 10 minutes
15 minutes
Product Controls DIP Switch Settings 20 minutes 
25 minutes
.H\KROHVORWV 30 minutes
IRUPRXQWLQJWR
',3VZLWFKHV RFWDJRQDOER[ Feature Switch# Walk-Through 4
8OWUDVRQLF Time Delay 1 2 3
VHQVLWLYLW\WULPSRW Enabled
8OWUDVRQLF (&
(

/LJKWOHYHO Test Mode/20 min Disabled 


30 seconds


WUDQVGXFHU


SXVKEXWWRQ




FRQHV
21 


5 minutes


Service 5
10 minutes
'RXEOHJDQJ Service
PXGULQJ 15 minutes
8OWUDVRQLF PRXQWLQJKROHV 20 minutes  Normal 
DFWLYLW\
/(' *UHHQ 25 minutes
30 minutes = Factory Setting
= ON
Walk-Through 4 = OFF
Enabled
Disabled 
COVERAGE & PLACEMENT
Service 5
Coverage Patterns Placement
Service
30' 16' 12' 0 12' 16' 20' 30' Normal 
20' = Factory Setting
UT-355-3 = ON
16' = OFF
UT-355-2
12'
UT-355-1
5' 30' x 30'
0
5' Typical layout for open office space would be to place UT-355-3
sensors so they control zones that overlap. For partitioned spaces, a
12' UT-355-3 typical zone is about 25’ x 25’ with an overlap on the coverage up to
16' HALLWAY
APPLICATION
30’ x 30’.
20'

Coverages shown represent half-step walking motion when sensor


is mounted 8’-10’ high. Actual coverage can vary for each application
depending on the shape and use of space and the obstacles present.

WWW.LEGRAND.US/WAT TSTOPPER 2
WATTSTOPPER®

ORDERING INFORMATION
Catalog # Voltage Load Rating Coverage
UT-355-1 120 VAC, 50/60 Hz; 0-800W Ballast/Tungsten/LED up to 500 ft2 (152,4 m2)
230 VAC (single phase) 50/60 Hz; 0-1200W Ballast/LED
UT-355-2 277 VAC, 50/60 Hz; 0-1500W Ballast/LED up to 1000 ft2 (304,8 m2)
347 VAC, 50/600 Hz
UT-355-3 up to 1600 ft2 (487,7 m2)

CA-1 Cosmetic adapter for ceiling installations with 4” square j-box or Wiremold #V5748-2 box

Sensors are white.


-U = BAA/TAA compliant; product is compliant with Buy American Act and Trade Agreement Act

27410r3 Rev 07/2023