HT by Natural Convection
HT by Natural Convection
AIM:
vertical cylinder in
To find out heat transfer coefficient and heat transfer rate from
alural convection.
THEORY:
Natural convection heat transfer takes place by movement of fluid particles
within to solid surface caused by density difference between the fluid particles on
Iccount of difference in temperature. Hence there is no external agency facing fluid over
the surface. It has been observed that the fluid adjacent to the surface gets heated,
resulting in thermal expansion of the fluid and reduction in its density. Subsequentiv a
buoyancy force acts on the fluid causing it to flow up the surface. Here the flow velocity
isdeveloped due to difference in temperature between fluid particles.
Thefollowing empirical correlations may be used to find out the heat transfer
APPARATUS:
a vertical
apparatus consists of astainless stccl tube fitted in a rectangular duct in
The
and serves the
The duct is open at the top and bottom and forms an enclosure
position.
sheet for
undisturbed surroundings. One side of the duct is made of acrylic
purpose of tube surface. The
the vertical tube. which heats the
Visualization. A heating element is kept in
Digital temperature
from the tube to the surrounding air by natural convection.
heat is lost temperature
temperature at different points with the help of seven
indicator measures the heater is
measuring surTOunding temperature. The heat input to the
sensors, including onefor dimner stat.
Ammeter and Digital Voltmeter and can be varied by a
mcasured by Digital
PROCEDURE:
OFF position.
ON/OFF switches given on the panel are at
Ensure that all panel.
provided on the
Ensure that variac
knob is at zero position,
Hz).
main power supply (220 V.AC, 50
Now switch on the switch given on the panel.
mains ON/OFF
thehelp of
Switch on thepanel with variac, voltmeter and ammeter
with the help of
input to the heater
FN he power
Povided.
readings when steady state is reached.
voltmeter & ammeter
Take hermocouple, first.
is over, switch off heater
WhenCxperiment
position.
Idooriac io zero
Naturalf Convvction
feat Transfer Through
). Switch off the panel with the help of MainsOn/Off switch given on thepancl.
10. Switch off povwer supply to panel.
PRECAUTIONS:
I. Never switch on main power supply before ensuring that all on/off switches given
on the panel are at off position.
2. Never run the apparatus if power supply is less than 180 or above 200 volts.
TABULAR COLUMN:
SI. VI Thermocouple readings °C
No. Volts Amps watts T3 TË Ts T6 T; Ts(an)
CALCULATIONS:
3) MEAN TEMP
m
=(Tg +T¡)/2
PROPERTIES OF AIR AT (T)in °C.
IROM DATAHAND BOOK TAKETHE
KJ/sec.
W/mk.
In/seC.
EXPANSION
) VOLUMETRIC COEFFICIENT OF THERMAL
+273)
7) NUSSELT NUMBER
Nu = hL
COEFFICIENT
8) FREE CONVECTIVEHEAT TRANSFER
h= Nuk W/m2K
BY CONVECTION
9) HEAT TRANSFER RATE
Q =h A(T, -T.)
Q=h dL (T, -T.)watt
COMMlENTS:
in
makes sure that the Variac knob Zero
Before switching ON the unit
position
switch (TSS) gently
2 Operate thermocouple selector
twice in aweek
3 Operate unit minimum
inrease the voitage slowiy
1 61 0.301 18.361 56
chamber
61 66 70 71 68 65 30
RAYLEIGH NUMBER
R. = Gr X Pr
Ra = 214.45x106 x 0.698
Ra= 1.496x108
NUSSELT NUMBER
Nu= hL/K
Use the following correlation to find Nusselt number.
Nu= 0.13(Ra) 3 for 108 < Ra< 10!2
Nu- 0.13x (1.496x 109)13
Nu= 69.011
CONVECTION
HEAT TRANSFER RATE BY
Qc= h A (Ts-Ta) L=400mm, 0.4m)
=hr DL(Ts-Ta) (where D-30mm, 0.03m ;
(65.286.-47.643)
=4.875 >x TI X0.03x0.4
Qc = 3.2424 Watts
NaturalConwtion