0% found this document useful (0 votes)
100 views24 pages

Manual Eriz

Manual controlador eriz cxt12

Uploaded by

kevin torres
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views24 pages

Manual Eriz

Manual controlador eriz cxt12

Uploaded by

kevin torres
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

VM-10C

Installation, Operation
and Maintenance
Instructions

N12-G & HW SERIES


FREQUENCY
CONTROLLERS
115/230 VAC FOR
30, 40, 50 & 60 HZ
ELECTROMAGNETIC
FEEDERS

ERIEZ HEADQUARTERS: 2200 ASBURY ROAD, ERIE, PA 16506–1402 U.S.A.


WORLD AUTHORITY IN SEPARATION TECHNOLOGIES

COMPLIANT CONTROLLERS

N12- G & HW Series Frequency Controllers 115/230VAC

1
Table of Contents
ERIEZ N12-G SERIES & HW CONTROLS

WARNING ........................................................................................................................4
Technical Data............................................................................................................4
INSTALLATION ............................................................................................................ 5-6
Mounting.....................................................................................................................5
Wiring..........................................................................................................................5
Connections ...............................................................................................................5
Set-up .........................................................................................................................5
Adjustments................................................................................................................5
Parameter Adjustment Procedure .............................................................................6
CONTROL ELEMENTS............................................................................................... 7-8
Settings...................................................................................................................7-8
COMMISSIONING .....................................................................................................9-10
Preliminary Steps .......................................................................................................9
Important Points .........................................................................................................9
Operating Frequency of the Feeder Coil ..................................................................9
Measurement of the Output Voltage and Current ....................................................9
Adjustments................................................................................................................9
Putting the Equipment into Operation .......................................................................9

2
Table of Contents (cont.)

SETTING INSTRUCTIONS .....................................................................................10-17


User Enable, Remote ON/OFF ............................................................................. 10
User Adjustment of Throughput...............................................................................11
Tuning the Feed System Feeder Settings ..............................................................11
Track Control ........................................................................................................... 12
Sensor Time Out ..................................................................................................... 12
Set Point Source ..................................................................................................... 12
Regulation Mode ..................................................................................................... 13
Instructions for Using Regulation Mode ................................................................. 13
Mounting the Accelerometer................................................................................... 14
Relationship Between Acceleration and Amplitude ............................................... 15
Instructions for Setting up the Controller in Regulation Mode............................... 15
Determining the Resonant Frequency ................................................................... 15
Optimizing Controller in Regulation Mode .............................................................15
Displays ................................................................................................................... 16
Display Actual Current and Frequency .................................................................. 16
Save Selected Parameters..................................................................................... 17
Recall User or Factory Settings.............................................................................. 17
Hide Parameter Menus........................................................................................... 17
ERROR MESSAGES / ERROR RESET ..................................................................... 18
FAULT TROUBLESHOOTING ......................................................................................19
Troubleshooting - Frequency Controllers............................................................... 19
TRAY REGULATION MODE SETUP WITH LOCAL SETPOINT............................... 20
EXTERNAL SETPOINT MODE WITH REMOTE 4-20MA SETPOINT...................... 20
TRAY REGULATION MODE WITH REMOTE 4-20MA SETPOINT .......................... 21
TECHNICAL DRAWINGS........................................................................................22-23

N12-G & HW Series Frequency Controllers 115/230VAC

3
WARNING
This control is capable of variable output voltage over
a wide range of frequencies. This model should only be

frequency is needed, we suggest that the user contact

may still be charged due to capacitance. Wait at least

capacitors to discharge.

General Description
This control is a variable voltage frequency controller. A front
panel display and keypad make set-up and operation an
easy task. This control can be used for manual or remote set
point control. Other features include amplitude regulation and
track control. Control of the vibratory feeder is accomplished
by using sinusoidal waveform impulses (modulated). This
method results in quiet operation.

Technical Data
DESCRIPTION FREQUENCY CONTROL (RE)
Input Voltage 115/230 V 50/60 Hz
Output voltage 0-110 or 0-220 VAC
Output current 12.0 A max.
Soft start 0-4 sec.
Sensor supply 24 V, 25Ma
Switch on time delay 0-10 sec.
Switch off time delay 0-10 sec.
Empty time 30-1 80 sec.
Set point source Keys/ 0-10 V, 0(4)-20mA DC
Enable 12-24 V, DC/ Switch
Status relay Form “C” 250V, 1A
Operating temperature 0-113 degrees F

4
Installation Adjustments
• Soft start ramp up time 0,1-4 Sec.
Mounting
The controller should be mounted in a reasonably dry, • Soft stop ramp down time 0,1-4 Sec.
minimum dust area, if possible, where the ambient • Maximum control limit (Umax)
temperature does not exceed 100°F. It is designed • Minimum control (Umin)
for vertical mounting. Refer to the supplied schematic
and outline drawing for mounting dimensions. The • Changeover for using an external set point source
mounting site should be relatively free of vibration or 0-10VDC (or potentiometer)/0-20mA, 4-20mA
steps should be taken to isolate the unit. • Switch on time delay (for track control)
Wiring • Switch off time delay (for track control)
Refer to the supplied schematic and outline drawing • Invert sensor function
for connections. The installation of a fused safety
• Empty time delay, if the material sensor does not
switch or branch circuit breaker ahead of the controller
see product
is recommended.
• Return to factory settings
Connections
Input Cable 120/230 VAC supply voltage
Output Cable Output - Eriez feeder
Set-up
Using the buttons and the LED display located on
a touch plate on the front panel sets up this unit.
The feeder throughput adjustment and setting of
other parameters can be carried out by using these
components. The control can also be operated by
external means, such as potentiometers and signal
sources. The parameters can be changed by scrolling
through the menu, which is accessed by a user
password. The various functions within the menu are
identified with capital letters for ease of recognition.
Enable and fault contacts are located inside the
control enclosure along with other user connection
points. The output power is shown in percent (%) on
the LED display during normal operation. Changed
settings are saved when leaving programming mode
or after a 100 second delay from when the last key
was pressed.

N12-G & HW Series Frequency Controllers 115/230VAC

5
Installation (cont.) 4. Return to saved settings

Parameter Adjustment Procedure Press P key, using cursor key move to “C 210”
Press P key to select required parameter
1. Amplitude adjustment “FAC” = factory settings, using cursor key select
Press the programming Mode key (P) “SAFE” (loads factory settings)
Observe a “C 000” in the display Press P key to observe “USPA”, using cursor key
Using Cursor keys select “C 002” select “SAFE” (return to user parameters)

Press P key, observe “A 000” Press P key to return to normal operating model

Now an amplitude setting in percent can be entered


Press P key to return controller to normal operation 5. Storing user parameters
Press P key, using cursor key move to “C 143”

2. Other feeder values Press P key to select required parameter

Press P key, using cursor key move to “C 096” “PUSH” = save parameters, using cursor key select
“SAFE” (parameters are saved)
Press P key to select required parameter
Press P key to return to normal operating model
“A 000” = Amplitude (Feeder) [%]
“P 000” = Maximum control limit [%],
adjustable 20-100% 6. When an "OFF" is displayed and will not clear
“Ґ 000” = Soft start time Go to code "003" and select EN=1
“L 000” = Soft stop time [sec.], operates when unit If control is wired for remote, the remote switch
switched off by track sensor should be closed or a jumper placed between term's
5 and 6 (user enable).
Press P key to return to programming mode

3. Set source and output waveform


Press P key, using cursor key move to “C 003”
Press P key to select required parameter
“E.S.P.” = external set point, 0 for keys,
1 for external
If 1 is selected, control will operate with
potentiometer. If remote potentiometer is used
SET Amplitude “A” to 0%. Bias upward by raising
amplitude level.
If 1 is selected, press P key and select “4.20 0”
Select 1 for set point values 0-10 v, dc or 0-20mA
Select 0 for set point values 4-20mA DC
Press P key to select “SP.2 0” for track control mode
and “SP.2 1” for dual set point operation
Output waveform is factory set and should
not be adjusted
Please consult Eriez for more information
concerning Track Control.

6
Control Elements
Settings
The six buttons and a LED display found in the front
panel are used for operating and setting up the unit.
All operating methods and adjustable parameters can
be set up through this panel. The “I” and “O” buttons
are used for switching the unit ON and OFF, however,
these do not provide mains isolation, they simply
inhibit the power semiconductors.
The “P”, “F” and “Cursor Buttons” are used for
parameter adjustment. Parameters are set by
using menu controls, which are called up by
entering operator codes. The functions are
described in greater detail in the section on
setting instructions. The display value can be
increased or decreased by units, or tenths of units,
by a short press of the cursor buttons. Holding the
buttons down will cause the display to change in units
of ten.
To prevent accidental or unauthorized adjustment,
the adjustment parameters in the user menus are
protected. A code must be entered to open the user
menus. There are different pass codes for each
function group.
Setting adjustments are automatically saved upon
leaving the programming mode or if no button is
pressed for a period of 100 seconds.

N12-G & HW Series Frequency Controllers 115/230VAC

7
Control Elements (cont.)
Settings (cont.)
All setting routines are commenced by pressing the
programming button “P”. The following diagram should
clarify the sequence in which keys are pressed:

1. Press the “P” key.


2. Select the code number with the cursor keys.
3. Press the “P” key. This displays the first menu
point. The required menu point can be found by
repeatedly pressing the “P” key (scrolling).
4. The value in the menu point can be changed with
the cursor keys.
5. Scroll to the next menu point or to the end of the
menu, which returns the display to the set point
value, by pressing the “P” key. To exit the menu
and return back to the normal display, quickly
depress the “P” key for 5 seconds.
6. To return back to the previous position in the
menu, press the “F” key.

8
Commissioning Putting the Equipment into Operation
1. Establish the vibrating frequency.
Preliminary Steps
• Check that the unit is correct for the local mains 2. Establish the power of the feed system (maximum
supply (rating plate information) and that it is permissible current draw).
correctly rated for the feed system. For a new feeder where settings are unknown
• Connect the controller according to the (see also comments below).
connection diagram.
Without connecting the feeder, select parameter
Important Points FAC in menu C210 (reset factory settings), press the
Using the control units described in this cursor key to reset (SAFE) and press the P key to
document, it is possible to adjust the feed leave the menu. The factory settings are listed in the
system so that it runs at resonance. In this table in section 7, headed settings.
condition, it is possible to obtain excessive output for
a very low set point setting. Therefore, extreme care It is possible that a special parameter set, for a
should be taken to avoid causing damage to the drive machine manufacturer, has been pre-stored under
coil through hammering. a user code and these can be recalled. In such
instances, specific machine settings will be loaded and
In practice, it is not possible to run at resonant so the next steps are not relevant.
frequency without accelerometer feedback because
the system would be unstable and uncontrollable. The Basic settings:
system must be set safely off resonance i.e. either
• Connect feeder.
above or below the natural frequency.
• Set frequency (refer to feeder data sheet).
Resonant frequency: Depending on the spring and Menu C096 parameter F.
mass design of the feeder system, it is possible to
have resonance at more than one frequency. These • Check current limit (refer to feeder data sheet).
additional resonance points are multiples of the main Menu C040 parameter I (shows the current limit
frequency. For this reason, in critical situations, it is as a percentage of maximum). If applicable, use
possible that the automatic frequency search will not service menu for setting.
find true resonance and in such cases the natural • Increase set point, observe feeder, check running.
frequency must be determined manually. • Increase set point to maximum and check if power
Operating Frequency of the Feeder Coil needs limiting (hammering). If necessary, adjust
It is possible that the current flowing through the coil the limit as follows:
will increase for a small frequency adjustment. So this • Adjust set point to zero.
should be checked with a true RMS instrument for each
• Set parameter P (maximum limit) in
new application as well as monitoring the coil for heat
Menu C096 to 50.
build-up.
• Adjust set point A to 100%.
The coil should be designed for the correct operating
frequency to prevent excessive current draw and the • Increase the maximum limit P from 50% until the
consequential overloading of the coil. required amplitude is reached.
• The full set point range of 0-100% can now
Measurement of the Output Voltage and Current be used.
The voltage and current cannot be measured with a
regular instrument because the controller output uses Additional settings e.g. soft start, time delays etc. can
an electronic inverter with a pulse width modulation be set to suit the particular equipment.
signal. An effective measuring instrument such as
a moving iron meter (analog) must be used. It is
recommended that an analog instrument is used
rather than an electronic multi-meter which will give
a misleading reading.

N12-G & HW Series Frequency Controllers 115/230VAC

9
Commissioning (cont.)
Determining the output frequency
(vibrating frequency)
It is essential that the output frequency is adjusted
with the set point set at a low frequency, otherwise on
hitting the resonant frequency, it is possible to achieve
a high amplitude with a low output voltage. An analog,
effective value, current indicating unit (moving iron
meter) must be connected into the output circuit.
Resonant is reached when there is a maximum
amplitude for a minimum output current. To
achieve a stable feed system, there must be
an offset between the vibrating frequency and
resonance (approx. 1-2Hz). This offset must be
determined by the user because different feeders
have different running characteristics.

Setting Instructions
User Enable, Remote ON/OFF

To turn the feeder or conveyor ON/OFF remotely with a contact:


Refer to the control schematic on page 23 of this IOM.
The wire jumper between terminal 5 and 6 should be removed.
Dry contact to be connected between terminals 5 and 6.
Manual switch on face plate of controls to be in ON position.

To turn the feeder or conveyor ON/OFF remotely with a 24V DC signal:


Refer to the control schematic on page 23 of this IOM.
The wire jumper between terminal 5 and 6 should be removed.
24V DC signal to be connected to terminal 5 and ground to terminal 4.
Manual switch on face plate of control to be in ON position.

10
Setting Instructions (cont.)
User Adjustment of Throughput

Tuning the Feed System Feeder Settings

N12-G & HW Series Frequency Controllers 115/230VAC

11
Setting Instructions (cont.)
Track Control

Sensor Time Out

Set Point Source

12
Setting Instructions (cont.)
Regulation Mode

Instruction for Regulation Mode • Resonant frequencies: It is possible to have


• An accelerometer e.g. SW11 must be fitted to the several vibrating frequencies, where resonance
vibratory feeder in order to run in regulation mode. occurs, depending on the springing and masses
The accelerometer should have a frequency range of the system. The additional resonant points are
corresponding to that of the feeder. at multiples of the dominant resonant frequency.
• All vibratory signals, that are picked up by Under extreme circumstances, the automatic
the accelerometer, are used by the regulator frequency search may be unable to differentiate
circuit. Stray signals generated by neighboring between these frequencies and so in these
machinery, a flimsy accelerometer mounting, or instances, the frequency must be set manually.
an unstable support frame, can cause incorrect
regulation to occur. It is especially important to
ensure that there are no external influences
of this type during the automatic frequency
search routine.

N12-G & HW Series Frequency Controllers 115/230VAC

13
Setting Instructions (cont.)
Mounting the Accelerometer
The accelerometer should generate signals for the
movement and acceleration of the feeder, which are
fed back to the regulator circuit of the control unit.
Therefore, it is very important that no other extraneous
vibration signals are picked up by the sensor.
The sensor should be positioned so that it moves in
the same direction as the feeder, ideally in the same
plane as the springs, and it should be fitted on a solid
block that will not generate vibration signals.

the feeder, produces a feedback loop, whereby


the signal generated from the sensor determines
the control range of the set point i.e. the regulator
or controls the feeder so that the effective value (feeder
power or intensity of vibration) relates to the provided
set point value. Because the effective value is
dependent on the feeder (frequency, acceleration and
amplitude) and in addition depends on the mounting
position of the sensor, the regulator must be adapted
to suit the output control range.
Bracket Mount Block Mount
(must be rigid and not flex)

In regulation mode the magnitude of the output Linear Feed Example


signal has a direct affect on the maximum
amplitude of the feeder. 1. Small amplitude
because sensor is
On bowl feeders, it is advisable to fit the sensor as mounted vertically.
near as possible to the outside diameter and in this
position, it will be subjected to the greatest movement. 2. Larger amplitude
because sensor is
The control range of the set point will be considerably mounted in the same
reduced when the sensor signal is weak. plane as the springs.

This is achieved by using the parameter P in Menu C


008. The measured sensor signal range is adjusted
by changing this value. In most instances, a value of
less than 100 must be entered, so that the set point
can reach 100% or can go as high as possible. When
it is not possible to achieve an acceptable range, the
accelerometer should be mounted in the location
which gives the greatest movement (see the bowl
feeder example).

s = deflection The importance of scaling this value is demonstrated


Mounting position 1 = small deflection when, for example, a feeder takes a very long time to
Mounting position 2 = large deflection ramp up, after it has been switched on.

14
Setting Instructions (cont.) Determining the Resonant Frequency
Manual setting of the vibrating frequency
Relationship Between
It is essential that the output frequency is adjusted
Acceleration and Amplitude
with the set point set at a low frequency, otherwise
The sensor measures the momentary acceleration
on hitting the resonant frequency it is possible to
of the feeder. It generates a sinusoidal output
achieve a high amplitude with a low output voltage.
voltage signal. The acceleration gets higher as the
An analog, effective value, current indicating unit
frequency increases. The sensor signal is greater for
(moving iron meter) must be connected into the
a higher frequency and lower amplitude that for a low
output circuit. Resonant frequency is reached
frequency with a higher amplitude.
when there is a maximum amplitude for a
minimum output current.
Automatic frequency search
• The feeder should be empty for a
frequency search.
• Adjust the set point to zero.
• Select regulation mode (Menu C 008,
Parameter ACC = I ).
• The optimum frequency of the feeder is found
automatically by initiating the frequency search
(Menu C 008, Parameter A.F.S.). When this has
been found, the controller resets the set point back
to its original value (0).
Optimizing Controller in Regulation Mode
Setting the control range:
1. In Menu C. 096 set parameter P
(Max Limit) to 50%.
2. Set A (Feeder throughput) to 100%.
3. Increase limit P from 50% until the required
maximum feeder throughput is achieved.
The full set point adjustment range of 0-100%
can now be used.

Using an accelerometer with an output signal of 0.3 Optimizing regulation: For unwanted feeder
V/g the sensor generates a peak voltage of 4.5V for a oscillation (hunting) or inadequate feedback
peak acceleration of 15g (Example 1), corresponding regulation for load changes
to a 3.18V RMS value.
Example 1: => 15 g => 4,5 V => 3, 18 Veff. The response of the regulation circuit can be adjusted
Example 2: => 11 g => 3,3 V => 2, 33 Veff. in menu C008 using the parameter PA (Proportional
characteristic or circuit gain) and IA (Integral
Because of the vastly different acceleration values of characteristic).
various feeders, there is a big difference in the feed
back signals, which makes scaling necessary. In menu C008 reduce PA until the oscillations
are reduced.
Instructions for Setting up the Controller Parameter IA should be set to 100 if possible.
in Regulation Mode
• Connect control unit.
• Install sensor and connect to controller.
N12-G & HW Series Frequency Controllers 115/230VAC

15
Setting Instructions (cont.)
Displays

Display Actual Current and Frequency

16
Setting Instructions (cont.)
Save Selected Parameters

Recall User or Factory Settings

Hide Parameter Menus

N12-G & HW Series Frequency Controllers 115/230VAC

17
Error Messages / Error Reset Error Reset through Menu C009

Errors are indicated by an alternating code and


Error display.

Sensor time out


After sensor time out has elapsed.
Overload limit Error Reset is achieved by pressing touch panel
Output level exceeded e.g. incorrect frequency setting, keys 0 or I during normal operation or by using
coil air-gap to wide. Menu C009.
In the event of an error check that this is not caused
by incorrect wiring or cable faults. The error message,
Error ACC, can also occur if regulation mode is
Short circuit trip chosen (in Menu C008) and an accelerometer is not
Faulty coil, short circuit or defective cable. connected, for example.
Reset the error in the following manner:
Error Reset
Clear Error
Over voltage
Supply voltage too high or back EMF from the coil at
lower frequencies.

Current spike limit


Frequency set too low for installed coil or frequency
altered too rapidly during setting up.

Sensor fault (only when regulation mode is selected)


Accelerometer not working or faulty.

18
Fault Troubleshooting
Troubleshooting - Frequency Controllers

PROBLEM POSSIBLE REASON REMEDY

Feeder does not vibrate Incorrect frequency setting Resonate frequency search
Feeder hammers when throughput is set high. • Feeder is working too close to its • Adjust frequency.
resonate frequency. • Reduce maximum limit [P]
• Air gap too small. (Menu “C 096”).
• Check air gap (Caution: too big an
air gap increases the current).
Magnet gets warm. • Frequency setting is too low for the • Adjust to a higher frequency or fit a
coil type. more suitable coil.
• Air gap is too large. • Reduce the air gap.
"OFF" displayed and feeder does not run. • No enable signal. • Provide enable signal using contacts
of 24VDC signal.
• Fit a link between enable terminals.
• Or invert parameter “-En”.
After running for a short time the feeder stop and • Sensor time out has been activated, • Cancel sensor time out parameter
"Error SE" flashes in the display. no material available. “EE”.
• No track sensor fitted. • Check sensor.
• Defective track sensor. • Check sensor.
After enabling the feeder or calling from a sensor, • Maximum limit [P] in Menu “C 008" • Set the maximum limit to match
it only runs slowly, even though the soft start is set or “C 096" has not been set correctly. the amplitude.
at "0". (applies to regulation mode only)
Maximum amplitude is achieved with a very low • The mounting position of the sensor • Reduce maximum limit [P]
throughput setting. has a small deflection. (Menu “C096”).
• Maximum limit [P] has not been set • Reduce maximum limit [P]
for the feeder. (Menu “C096”).
ERROR MESSAGE TYPE OF FAULT

ERROR - OL Output power too high Coil power too high. Controller with a higher power
rating required.
Selected frequency too low. Increased frequency.
Air gap too large. Reduce air gap.
Short circuit. Check circuit and drive coil.
ERROR - OC Over current Output short circuit due to Check circuit and drive coil.
drive coil failure.
ERROR - OU Over voltage in DC link Supply voltage too high. Check mains voltage.
Back emf from drive coil Control unit may have to be changed for
(possible at lower frequencies). another type – contact manufacturer.
ERROR - ACC Sensor fault Sensor failure. Test sensor.
Defective sensor.
ERROR - SE Sensor time out Sensor time out is activated but Switch off sensor time out in
exceeded not required. Menu “C 167”.
The sensor has detected no product. Check mechanical system.
ERROR - EEP Memory failure Component problems. Contact manufacturer.

N12-G & HW Series Frequency Controllers 115/230VAC

19
Tray Regulation Mode Setup External Setpoint Mode with
with Local Setpoint Remote 4-20mA Setpoint
OPERATION RESULT (OR DISPLAY) OPERATION RESULT (OR DISPLAY)

Turn the green power Control is energized Press green “I” Feeder is energized
switch “ON”
Press “P” A 0.0
Press the red “O” Feeder is turned “off” (STOP)
Press  scroll to A 100.0
Press “P” C 000 (This is full amplitude of the
feeder and should be noted)
Press  scroll to C 003
Press red “O” Feeder is turned “off” (STOP)
Press “P” ESP 0
Press “P” SP2 0 Turn the green power switch “OFF”, disconnect the power
supply, and make sure controller is wired for an external signal
Press “P” EN 0 for the setpoint (ie 4-20mA) Turn the power source back on.
Press “P” STOP
Turn the green power switch Control is energized
Press “P” C 000 “ON”
Press  scroll to C 008 Press the red “O” Feeder is turned “off” (STOP)
Press “P” A 0.0 Press “P” C 000
(set A to 0.0 using arrow keys)
Press  scroll to C 003
Press “P” P 100.0 (set P to 100.0 using
arrow keys) Press “P” ESP 1 (set ESP to 1 using
arrow keys)
Press “P” F ** (should be factory set to
operating frequency) Press “P” 4.20.1 (set 4.20 to 1 using
arrow keys)
Press “P” ACC 1 (set ACC to 1 using
arrow keys) Press “P” repeatedly until EN 1 (set EN to 1 using
arrow keys)
Press “P” PA 40 (set PA to 40 using
arrow keys) Press “P” C 003

Press “P” IA 50 Press  scroll to C 000


(set IA to 50 using arrow keys) Press “P” A 100.0
Press “P” STOP Press  scroll to A 0.0
Press “P” C 008 Press “P” STOP
Press  C 000 Press green “I” Enables controller (0.0)
Press “P” A 0.0
Using minimum external signal (i.e. 4mA) Feeder is energized.
Increase signal to maximum slowly (i.e. 20mA) Maximum feeder
The controller can now be operated in the regulation output 100.0 on display.
mode by pressing the green “I” to turn the controller
Press “P” C 000
on. Press the  to set the desired amplitude of the
feeder. Read the amplitude sticker on the feeder to Press  scroll to C 008
confirm the displacement. Press “P” repeatedly until P 100.0 (set P to 100.0 using
arrow keys)
Press  To achieve maximum federate
desired or leave at 100.0
(A = max)

Reduce external signal to minimum (i.e. 4mA) Minimum federate


(A = min)

Press “P” repeatedly until A 0.0


Press  To achieve minimum federate
desired or leave at 0.0
Press “P” C 008
Press  C 000
Press red “O” To turn feeder off (C 000)
Press “P” repeatedly until (STOP)

20
Tray Regulation Mode with
Remote 4-20mA Setpoint
Perform the setup for external 4-20mA setpoint.
Connect accelerometer to the socket in the bottom
of the control.

OPERATION RESULT (OR DISPLAY)

Press “P” C 000


Press p scroll to C 008
Press “P” repeatedly until ACC 1 (set ACC to 1 using
arrow keys)
Press “P” PA 40 (set PA to 40 using
arrow keys)
Press “P” IA 50
(set IA to 50 using arrow keys)
Press “P” STOP
Press green “I” Enable controller (0.0)
Apply minimum signal (4mA) Feeder is energized (A = min)
Increase signal to max 100.0 (A = max)
(20mA) slowly (maximum amplitude set in
C 008 of External Setpoint
Mode procedure)
Press “P” repeatedly until P 100.0
Press q repeatedly until Amplitude starts to decrease.
Confirm by reading amplitude
sticker
Press “P” repeatedly until 100.0
NOTE: if – is displayed or
flashing in upper lefthand
corner, reduce “P” parameter
until gone.
Press “P” repeatedly until C 008
Press q scroll to C 000
Press “P” repeatedly until 99.0-100.0 or maximum
amplitude is achieved
Reduce signal to minimum 0.0 or minimum federate set
(4mA) in C 008 of External Setpoint
procedure

Adjust external signal to achieve the desired feed rate.

N12-G & HW Series Frequency Controllers 115/230VAC

21
Technical Drawings
Connection Acceleration Sensor range SW - on Plug M12

Sensor wire color to pin correlation: Previous plug design included the following
sensor wire to pin correlation:

PIN NO LEADWIRE COLOR PIN NO LEADWIRE COLOR

1 Red 1 Brown
2 Orange 2 White
3 Black 3 Blue
4 Brown 4 Black

22
Technical Drawings (cont.)

N12-G & HW Series Frequency Controllers 115/230VAC

23
Note: Some safety warning labels or guarding may have been removed before photographing this equipment.
Eriez and Eriez Magnetics are registered trademarks of Eriez Manufacturing Co, Erie, PA ©2019 Eriez Magnetics All Rights Reserved

World Authority in Separation Technologies 


Headquarters: 2200 Asbury Road, Erie, PA 16506-1402 U.S.A.
Telephone: 814-835-6000 • Fax: 814-838-4960
Web Site: www.eriez.com e-mail: [email protected]
Manufacturing Facilities: AUSTRALIA • BRAZIL • CANADA • CHINA • INDIA • JAPAN • MEXICO • SOUTH AFRICA • UNITED KINGDOM • UNITED STATES

719-AHA-Web ERIEZ MANUFACTURING CO ©2019 PRINTED IN USA

24

You might also like