Dss - Chapter 7
Dss - Chapter 7
Subramanian
EXERCISE 7.1
What is the net area An for the tension member shown in Fig. 7.43, when (a) the holes are made
of drilling, (b) holes are made by punching, Assume M20 bolts.
SOLUTION
Hole diameter = 22 + 2 = 24 mm
Path 1-1: Net area = 4800 -24×20 = 4320 mm2
Path 2-2: (2 holes and one stagger)
Net area = 4800 -2×24×20 + [1002/(4×120)]×20= 4256.6 mm2
EXERCISE 7.2
Determine the minimum net area of the plates as shown in Fig. 7.44 with 16 mm bolts.
SOLUTION
a. Chain bolting
EXERCISE 7.3
Determine the net area An for the 150 × 75 × 8 angle with M20 bolt holes as shown in Fig. 7.45.
SOLUTION
Path AC:
Net area = 1750 – 2 × 22 × 6 = 1486 mm2
Path ABC:
Net area = 1750 – 3 × 22 × 6 + [602 / (4 ×65) + 602 / (4 × 87)] × 8 = 1547.53 mm2
Since the smallest An is 1486 mm2 for path AC, that value governs.
Note that as the pitch is increased, the addition due to stagger increases, and hence the net area
increases.
EXERCISE 7.4
Determine the design tensile strength of plate (160 × 6 mm) connected to an 8-mm thick gusset
using 16-mm bolts as shown in Fig. 7.46, if the yield and the ultimate stress of the steel used are
250 MPa and 410 MPa respectively.
SOLUTION
fy = 250 MPa
fu = 410 MPa
EXERCISE 7.5
A single equal angle 75 × 75 × 6 is connected to an 8-mm thick gusset plate at the ends with
four 20-mm diameter bolts to transfer tension as shown in Fig. 7.47. Determine the design tensile
strength of the angle. Assume that the yield and the ultimate stress of steel used are 250 MPa and
410 MPa.
SOLUTION
Thus, the design tensile strength of the angle = 192.04 kN (least of 196.82, 192.04 and
204.19)
The efficiency of the tension member = 192.04 × 1000 × 100 / (866 × 250 / 1.10)
= 97.57%
EXERCISE 7.6
Determine the tensile strength of a roof truss diagonal 200 × 100 × 10 mm (fy = 250MPa)
connected to the gusset plate by 6-mm welds as shown in Fig. 7.48.
SOLUTION
Area of connected leg = (200 – 10/2) × 10 = 1950 mm2
Area if outstanding leg = (100 – 10/2) × 10 = 950 mm2
Ag = 2920 mm2
(a) Strength governed by yielding of cross-section
Tdg = Ag fy / γmo = (2920 × 250 / 1.10) × 10-3 = 663.64 kN
(b) Strength governed by rupture of critical section
Tdn = 0.9 fu Anc / γm1 + β Ago fy / γmo
Assuming Average length of weld Lc = 200 mm
β = 1.4 – 0.076 (w / t) (fy / fu) (bs / Lc)
= 1.4 – 0.076 [(100 – 5) / 10] (250 / 410) (100 / 200)
= 1.18 > 0.7
Hence Tdn = [0.9 × 410 × 1950 / 1.25 + 1.18 × 950 × 250 / 1.10] × 10-3
= 830.41 kN
Or Alteratively
Tdn = α An fu / γm1 = [0.8 (2920) × 410 / 1.25] × 10-3
= 766.21 kN
Hence Tdn = 830.41 kN
(c) Strength governed by block shear
Since the member is welded to the gusset plate, no net areas are involved and hence A vn
and Atn in equation for Tdb (Section 6.4.1 of Code) should be taken as the corresponding
gross areas (Gaylord, et al, 1992). Assuming Average length of weld on each side as 200
mm and the gusset plate thickness as 12 mm
Tdb1 = [12 × (200 x 2) × 250 / (√3 × 1.1) + 0.9 × 410 × 12 × 200 / 1.25] × 10-3
= 1338.32 kN
Tdb2 = [0.9 × 410 × 12 × 200 × 2 / (√3 × 1.25) + 250 × 12 × 200 / 1.1] × 10-3
= 1363.54 kN
Hence Tdb = 1338.32 kN
Thus tensile strength = 663.64 kN (least of 663.64, 830.41 and 1338.32)
The efficiency of tension member = 663.64 × 1000×100 / (2920 × 250 / 1.10)
= 100%
It is seen that since there is no reduction in area in welded connection, the efficiency of
the tension member is not reduced.
Note that in the calculation, we have assumed the average length of weld as 200 mm on
each side. However, the welding should be proportioned based on the position of neutral
axis.
Thus for the tensile capacity = 663.64 kN, with capacity of 6 mm weld = 0.793 kN/mm
Length of weld at the upper side of angle (with Cz = 69.8 mm)
= (663.64 × 69.8 / 200) / 0.793 = 292 mm say 295 mm
Length of weld at the bottom side of angle
= [663.64 × (200 – 69.8) / 200] / 0.793 = 545 mm
EXERCISE 7.7
Select a suitable angle section to carry a factored tensile force of 150 kN assuming (a) single row
of M20 bolts, (b) welded end condition. Assume design strength as fy = 250 N/mm2
SOLUTION
EXERCISE 7.9
A tie member in a bracing system consists of two angles 90 × 90 × 10 bolted to 12-mm gusset,
one on each side using single row of bolts (See Fig. 7.49a) and tack bolted. Determine the tensile
capacity of the member and the number of bolts required to develop full capacity of the member.
What will be the capacity if the angles are connected on the same side of the gusset plate and
tack bolted (Fig. 7.49b)?
SOLUTION
(a) Two angles connected to opposite side of the gusset as in Fig. 7.49(a)
Let us assume 20 mm diameter bolts
(i) Design strength due to yielding of gross section Tdg = fy(Ag/γm0)
Ag = 1700 mm2 (for a single angle)
Tdg = 250 × 2 × (1700/1.10) × 10-3
Tdg = 772.73 kN
(ii) The design strength governed by tearing at net section
Tdn = αAn(fu/γm1)
Assume single line of four numbers of 20 mm diameter bolts (α =0.8)
An = [(90 – 10/2 - 22) 10 + (90 – 10/2) 10]2
An = (630 + 850)2 = 2960 mm2
Tdn = [0.8 × 2960 × 410/1.25] × 10-3 = 776.70 kN
Therefore Tensile capacity = 776.70 kN
Fig.7.49 Contd.
Block shear strength Tdb of connection shall be taken as the smaller of,
Tdb1 = [Avgfy / √3γm0) + (0.9 Atnfu / γm1)]
Tdb2 = [(0.9fu Avn /√3γm1) + (fyAtg / γm0)]
Avg = (8 × 50 + 35) 10 = 4350 mm2
Avn = (8 × 50 + 35 – 8.5 × 22) 10 = 2480 mm2
Atn = (40.0 -22/2) 10 = 290 mm2
Atg = (40 × 10) = 400 mm2
Tdb1 = {[(4350 × 250) / (√3 × 1.10)] + [(0.9 × 290 × 410) / 1.25]} × 10-3 = 656.40 kN
Tdb2 = {[ (0.9 × 410 × 2480)/ (√3 × 1.25)] + [(250 × 400) / 1.10]} × 10-3 = 513.58 kN
(b) Two angles connected to the same side of the gusset plate [Fig. 7.49(b)]
Though the tensile capacity of both the arrangements (angles connected on the same
side and connected to the opposite side of gusset) are same, as per the code though the
load application is eccentric in this case. Moreover, in this case the number of bolts are
18 whereas in case (a) we used only 9 bolts since the bolts were in double shear.
EXERCISE 7.10
Design a single angle to carry a tensile load of 500 kN. Assume that the length of the member is
3m.
SOLUTION
Required area = 1.1 ×500×1000/250 = 2200 mm2
Let us choose an unequal angle of size 130 × 130 × 10 mm with a weight of 177 N/m and area =
2510 mm2 rxx = 39.9 mm.
Step 1: Design strength due to yielding of cross-section
Tdg = fy Ag /γm0 = [250 × 2510 / 1.10] × 10-3 = 570.45 kN > 500 kN
Fig
EXERCISE 7.11
Fig. 7.50
SOLUTION
The two channels should be tied effectively at regular intervals with tie plates so as to
function as a single unit (See Clause 7.7.2.3 of Code)
Effective depth of tie plate = distance between centroids of the main components
= 280 - 2×23.5 = 233 mm
Assuming 16 mm bolts and with edge distance = 30 mm
Overall depth = 233 + 2 × 30 = 293 mm 300 mm
Length of plate = width of the member = 280 mm
Thickness of tie plate = (1/50) distance between innermost connecting line of bolts)
= (1/50) (280 - 2 × 50) = 3.6 mm
Provide 300 x 280 x 8 mm tie plates.
EXERCISE 7.12
Design sag rods for consecutive purlins near the supported end of a roof truss systems as shown
in Fig. 7.40. The purlins are supported at one-third points by sag rods. Also design the ridge rod
between ridge purlins. The data given are: c/c spacing of truss = 8 m, spacing of purlin = 1.4 m,
self weight of roofing = 160 N/m2, intensity of wind pressure = 1000 N/m2, slope of the roof
truss = 30o, and no access is provided to the roof.
SOLUTION
EXERCISE 7.13
A diagonal member of a roof carries an axial tension of 500 kN. Design the section and its
connection with a gusset plate and lug angle. Use fy = 250 MPa and fu = 410 MPa.
SOLUTION
Without lug angle, the length of the gusset plate is 610 mm. If the bolts are staggered and
arranged in two rows, the length of the gusset plate may be reduced. We shall now provide
a lug angle (see Fig. 7.51).
Fig. 7.51
In an unequal angle, the load gets distributed in the ratio of the gross area of connected and
outstanding legs.
Load shared by outstanding leg of main angle
= 500 × 700 / (1450 + 700) = 162.8 kN
Load on lug angle = 1.2 × 162.8 = 195.4 kN (Clause 10.12.2)
Required net area for lug angle = 195.4 × 103 × 1.25 / (0.9 × 410)
= 662 mm2
Use ISA 150 × 75 × 8 angle with A = 1750 mm2
Assuming that the section is weakened by one row of 20 mm diameter bolt
Net area = 1750 - 22 × 8 = 1574 mm2 > 662 mm2
Note: For simplicity the effect of ∑ 𝑝2 /4𝑔 is not considered here but has to be considered as
explained in the examples of the book.
The lug angle is also kept with its 75 mm long leg as outstanding leg
Number of bolts to connect 150 mm leg of lug angle with gusset plate = 195.4 / 45.3 4.3
Provide five bolts of 20 mm diameter to connect lug angle with gusset plate.
Check
Load on connected leg = 500 × 1450 / (1450 + 700) = 337 kN
Required number of bolts = 337 / 45.3 = 7.4
Hence provide eight 20 mm diameter bolts to connect the diagonal tension member with the
gusset.
Required number of bolts to connect outstanding legs of the two angles (Clause 10.12.2)
= 1.4 × 162.8 / 45.3 5
Provide five bolts of 20 mm diameter.
Required length of gusset plate = 6 × 50 + 2 ×30 = 360 mm (compared with 480 mm without lug
angle).