Tubular Battery Data Sheet

Model-12V100AH@C10

Product Features: -

1. Robust Tubular with High Pressure die-casted spine-resulting low rate of spine corrosion.

2. Spill Proof Vent plug–resulting in no spillage on top and low controlled acid fumes.
3. Optimized Negative paste receipt for fast charge acceptance

4. Consistent backup throughout life

5. Excellent behavior in PSOC condition as compare to AGMVRLA.

6. Low Self Discharge

7. Excellent performance on deep cyclic applications to AGMVRLA.


8. Very High Design & Service Life

9. Low water loss

Technical Specifications

Rated Capacity Dimensions in mm Finished Battery Terminal


Nominal Battery
10 Hr Gross Type
Model Voltage Weight (kg) Weight [Kg]
@ 27°C (Ah) Length Width Height
(± 3 mm) (± 3 mm) up to (± 3%) (±3%)
terminal
(± 3 mm)

12V100Ah 12 100 505 192 410 52.5 54.0 L


Tubular Battery Data Sheet

Electrical Parameters & Charging Profile

Battery Specified Capacity Test @ 27 °C

400Watt (33A)
Model C10 C7@10. C5 C3 @ C1 @10.5V
@10.5V 5V @10.5V 10.5V @10.5V Backup Time
(In Minimum
3Cyles)
12V100Ah 100 88 80 69 48 1Hrs 40Min.

Ah &Wh Efficiency

Ah Efficiency >90% Wh Efficiency >75%

1.190
Tubular Battery Data Sheet

DOD VS LIFE CYCLE ExpectedCapacityVsTemperature

5000

4000

3000
No.Of Cycles

2000

1000

0
10% 20% 30% 40% 50% 60% 70% 80% 90%
Depth Of Discharge Temperature (°C)

Charging Instructions

Charger Voltage
Settings(at 77° F/ 25°C)
System Voltage 12V 24V 48V

Maximum Charge Current 10% of rated capacity

Float Voltage 13.6 27.2 54.4


Cyclic Use 14.4 28.8 57.6

Equalization Voltage 15.2 30.4 60.8

Do not install or charge batteries in a sealer or non-ventilated compartment. Constant under or


over charging will damage the battery and shorten its life as with any battery.

Periodic Charge Provide a periodic freshening charge to maintain a SOC greater than
the threshold of 70%

Note: Test results are based on battery tested in lab as per BIS 13369 & 1669.

Zunax Energy Products LLB certified by Aambitious Assessments Pvt. Ltd.

ISO900 CERTIFIED ISO 14001


ENVIRONMENTAL Aambitious
Aambitious
ambitious Assessments Pvt. MANAGEMENT Assessments
Ltd. Pvt. Ltd.

Unit 1:Sy No 806, Farooq Nagar Mandal, Mahbub Nagar, Burgulla Village,
Dist. Rangareddy, Telangana - 509202 India

Unit 2: Plot no 24, IDA Kothur, Dist Ranga Reddy, Telengana – 509228, India

You might also like