Control System Manual Aritco 6-7000 - EN RevAC
Control System Manual Aritco 6-7000 - EN RevAC
Control System Manual Aritco 6-7000 - EN RevAC
©Aritco Lift AB
Date: 2018-12-13
Contents
7000 400en-GBAC i
This page is intentionally left blank
List of functions
1 LIST OF FUNCTIONS
The control system consists of 3 types of modules,
the control system (U1) placed in the cabin as well as
shaft modules (U3) placed at every landing and one
U5 module (or optional ext U6) is connected between
the U1 and U3 modules.
7000 400en-GBAC 1
List of functions
2 7000 400en-GBAC
Start-up, 3-phase
2 START-UP, 3-PHASE
To check if the phase sequence is correct for 3-phase lifts, do the following:
1. Check that the DIP-switch for Freq control is in Off position.
2. Run the lift up and down from the platform buttons.
3. While the lift is running, note which of the indicators UP/DOWN is lit up on the U1 module (main control).
4. If the lift moves in the same direction as indicated, then the 3-phase sequence is OK; otherwise change
the phase sequence.
7000 400en-GBAC 3
This page is intentionally left blank
Start-up, check direction
CAUTION
Be careful when checking the running direction, wrong direction can cause damage to
the lift.
2. Check the running direction by pushing the up and down platform buttons.
3. While the lift is running, note that the correct LED-indicator UP/DOWN is lit up on the U1 module (main
control).
4. If the lift moves in the same direction as the up and down platform buttons, then the phase sequence is
OK; otherwise change the phase sequence.
CAUTION
Be careful when checking the running direction, wrong direction can cause damage to
the lift.
2. Check the running direction by pushing the up and down platform buttons.
3. While the lift is running, note that both of the LED-indicators UP/DOWN and Up- or Down-LED on connec-
tor 25 is lit up on the U1 module (main control).
4. If the lift moves in the same direction as the up and down platform buttons, then the phase sequence is
OK; otherwise change the phase sequence on the motor.
7000 400en-GBAC 5
This page is intentionally left blank
Power off
4 POWER OFF
When a Power down is required for more than 1 hour, make sure that fuses E2 and E3 are switched off.
Otherwise the battery will be discharged and may get damaged. A fully-charged battery supplies the system
with power for up to 7 hours.
Only use Lead-acid batteries with a 3,2 – 3.4 Ah capacity if the battery must be replaced.
Battery test.
There is a check every minute that the battery is present and has a sufficient voltage.
The battery is also tested once a month by turning on the emergency light for 2,5 hours while the power con-
sumption is measured.
7000 400en-GBAC 7
This page is intentionally left blank
Stop switch
5 STOP SWITCH
The stop switches consists of 3 bi-stable switches, 1 (b31), X (b33) and TOP(b36). Switch X is only used
when the lift has more than 2 landings, if there are only two landings there shall be a jumper plug in connec-
tor 2 on U1 PCB.
The figure to the left shows the placement of the magnets in the shaft.
The distance between the sensor and the magnet should be 15-20 mm to assure correct functionality. If the
distance it too small, a double-click may result in the sensor.
The position of the magnets can be seen in the figure to the right.
7000 400en-GBAC 9
This page is intentionally left blank
Shaft modules
6 SHAFT MODULES
6.1 U5 FUNCTIONS
Up/down buttons The up and down buttons are used for emergency
run and to force the platform back into the operating
zone if it has exceeded the limits, i.e. gone too far
up or down.
Emergency run limit The button Emergency run limit switch, in combi-
switch nation with the up or down button makes it possible
to force the lift back into the operating zone if it has
exceeded the limits, i.e. gone too far up or down.
Exceeded limit is indicated by a flashing Emergency
run limit switch when you press on the up or down
button.
Friction Test To test the friction brake, press and hold the Friction
test button down. The lift will move downwards for
approx. 2 s. Then the motor stops without activating
the brakes and leaving the platform to stop by itself
after max. 1 m due to the screw friction.
7000 400en-GBAC 11
Shaft modules
6.2 U5 CONNECTIONS
Fig. 3 U5
Table 1 U5 connectors
Connector Function
12 7000 400en-GBAC
Shaft modules
When the error alarm is activated the Service alarm reset button will light up, Error relay R1 is triggered and
all call buttons will begin to flash green/red.
7000 400en-GBAC 13
Shaft modules
6.5 U3 CONNECTIONS
The shaft modules U3 are identical and interchangeable.
Table 2 U3 connectors
Connector Function
Connectors and are used for communications to and from the U3-module. It does not
matter in which order they are connected.
14 7000 400en-GBAC
Shaft modules
If the number of indicated U3 modules does not match the actual number, there is an error - there may be a
defective connectors or faulty U3-module. The number of U3–s depends on the number of landings and
doors.
U3.x connections:
An actual, ongoing communication is indicated by a random flashing U5.6, U5.8, U5.10 and U1.9.
If U5.8, U5.10 or Front panel 9 (Signal) is lit up continuously or is shut-off, then this indicates an error.
7000 400en-GBAC 15
This page is intentionally left blank
Front panel U1 PCB
7000 400en-GBAC 17
This page is intentionally left blank
U1-control system functions
Connector Function
plug 1 , 2–pin b31 Stop switch 1 Input for stop switch on first landing. When lift is on this land-
ing the switch is open and control light 1 is not lit.
Plug 2 , 2–pin b33 Stop switch X Input for stop switch on intermediate landing. When lift is on
this landing the switch is open and control light X is not lit..
Add a jumper on U1–connector 2 if there are no intermediate
landings.
Plug 3 , 2–pin b36 Stop switch, top Input for stop switch on top landing. When lift is on this land-
ing the switch is open and control light Top is not lit.
Plug 4 , 8–pin b11–b16 Cabin call Input for cabin calls. Button is connected between pin 7 and
desired landing.
Plug 5 , 4–pin Communication Used for programming with U10 & U11. (only on Aritco 9000
lift ).
Plug 8 , 2–pin Contactor Input for check of main contactors on Aritco 4000. The con-
trol light is lit when a contactor is activated. If the indicator
lights up when the lift stands still it is because a contactor is
stuck, battery is missing or fuse E3 is off.
If the control light is not lit when the lift is running, an error in
the Error memory will appear and the control system will be
blocked at the next level.
Plug 10, 2–pin H1 Cabin lighting Cabin lighting (230VAC) is connected here.
Plug 11, 8–pin Flat cable connection to Connection of flat cable 4–10.
the cabin on the mast
Pin 1, 2: Connection 230VAC supply.
Pins 3, 4: Output H1 shaft light (option).
Pins 6–8: Control for main contactors.
Plug 12, 2–pin S2 Battery Connector for a 24V 3,2 — 3,4 Ah Lead-Acid battery.
Plug 13, 4–pin E2, E3 Fuses Connecting fuses for safety chain and battery.
Plug 15, 3–pin b8.1-n Door, b8.1-n Lock Connecting the cabin cable for measuring the door and lock
series 1–3.
Plug 16, 2–pin b60 Safety switch Connector for service hatch switch.
Plug 17, 2–pin b6 Safety switch Connector for platform right switch.
Plug 18, 2–pin b5 Safety switch Connector for platform left switch.
7000 400en-GBAC 19
U1-control system functions
Connector Function
Plug 19, 2–pin b4 Safety switch Connector for top left switch.
Plug 20, 2–pin b3 Safety switch Connector for top right switch.
Plug 21, 2–pin b2 Safety switch Connector for Emergency stop platform switch.
Plug 22, 2–pin b19 Overload Connector, overload switch. Control lamp should normally be
lit.
Plug 23, 6–pin Cabin panel Connector for Emergency alarm button. Output for Overload
light, platform light and Alarm control light.
Plug 24, 2–pin H2 Emergency lighting Output for emergency lighting 24VDC.
Plug 25, 4–pin F1 Frequency inverter Output for control of frequency inverter.
20 7000 400en-GBAC
DIP-switch settings
9 DIP-SWITCH SETTINGS
There are 16 DIP-switches on the control system
where a number of variables can be changed accord-
ing to the following:
1: off 2: off = 10 %
1: on 2: off = 20 %
1: off 2: on = 40 % (= default)
1: on 2: on = 80 %
1: on 2: off = landing 2
1: off 2: on = landing 3
1: on 2: on = landing 4
7000 400en-GBAC 21
DIP-switch settings
on off off 8 48
off on off 12 72
on on off 15 90
on off on 30 180
off on on 45 270
on on on 60 360
22 7000 400en-GBAC
Set landing indicator and watch statistics
When a landing indicator with or without speech is installed, the parameters must be set. This is done by si-
multaneous pressing the RESET button (1) and the button (2) on the U1 PCB. Keep them pressed for about
7 sec. until a long beep is heard. When this is done one of the LED indicators 1–6 on the U1 PCB is lit up.
With the button (2) you select parameters by stepping the LED indicator through 1–6.
When the LED indicator “X” (1–6) is lit the value for parameter “X” can decreased by pressing the cabin but-
ton 1 and increased by pressing the cabin button 2. The new value is shown on the landing indicator.
7000 400en-GBAC 23
Set landing indicator and watch statistics
4. The landing indicator will show the total number of starts and operating hours.
6. The trip meter will be shown; i.e. number of starts prior to the check.
7. The trip meter can be reset by pressing the Service alarm reset button and Friction test button at the same
time for approx. 3 seconds
8. The landing indicator exit the statistics and returns to normal display when the emergency stop button is
released and the lift runs to another landing.
24 7000 400en-GBAC
TROUBLESHOOTING DIAGRAM Page 1 yes= lamp on Refer to Component list
no= lamp off
LED on U1
yes
Check for
Remove plug Restart U1 board by Connect one faulty component
24 no 1-5, 7-9 and pressing hidden reset Faulty U1 by one plug
4 no
22-27 board 1-5, 7-9,
button Y behind the panel
22-27
yes
yes
5
Remove Faulty U1 board
RM School Y
5 yes no plug 26, yes or dip-switch
(LED 26) lock?
LED 26 lit? ”Reserved 2" on
no
4
Faulty S3
retiring 2
ramp
yes
1
no
Z
Next page 3
TROUBLESHOOTING DIAGRAM Page 2
no
Replace
9 Heart Light or not light
U1 board
flash
Check overload
10 Overload no
X switch b19
yes
10
Next page
TROUBLESHOOTING DIAGRAM Page 4
yes
yes
X
Next page
TROUBLESHOOTING DIAGRAM Page 5
LED UP/DOWN
One light Inverter ? no
X
Set dip switch Set dip switch Contactor C1/CD Check 48VAC Check lock Check wire 3 in
Inverter ? no no no no
”Freq control” off ”Freq control” on or C1/CU pulls U1/15.3 Circuit b9.x flat cable 20x0.752
yes
Check motor
Error memory
12 ERROR MEMORY
The Error memory can show 24 types of errors. The error messages can be viewed by a quick push on the
button (2) beside the Err-indicator at the U1 PCB..
The error message (one of 24 possible) is shown by a control LED 1-6 (1) in four different levels 1–4.
Reset the Error Memory completely by holding the button (2) down for 3 s. Errors indicated are reset auto-
matically 7 days after the latest event has occurred.
Level 1
When the button (2) is pressed the first time the Err-LED will lit continuously and the control LED 1-6 indi-
cates the following error:
LED 2 Lock switch open during run • Retiring ramp hits the locking arm
LED 3 Stop magnet switch 1 double click • Stop magnet too close to the sensor
LED 4 Stop magnet switch X double click • Stop magnet too close to the sensor
• If in combination with LED 6, short com-
munication failure with shaft module U3
during run
LED 5 Stop magnet switch Top double click • Stop magnet too close to the sensor
LED 6 Step error in stop magnet switch X • Stop magnet too close to the sensor
• If in combination with LED 4, short com-
munication failure with shaft module U3
during run
Level 2
When the button (2) is pressed a second time within 60 s. the Err-LED will repeat one flash and the control
LED 1-6 (errors 7-12) indicates the following error:
7000 400en-GBAC 31
Error memory
LED 1 Battery capacity test failed (monthly) • Battery capacity below 24,5V
• The error relay in U5/4 will be activated
and the call station buttons starts flashing
red/green after 30 seconds
• Tested monthly, the test is done automati-
cally by turning off the battery charge and
turn on the emergency light for 2.5 hours.
The battery voltage must not drop below
24,5V during this time
LED 3 Emergency lighting test failed 1 • Emergency lights missing during test
• Tested monthly and at power up
Level 3
When the button (2) is pressed for a third time within 60 s the Err-LED double-flashes and the control LED
1-6 (errors 13-18) indicates the following error:
LED 4 Fire drive is 1 /has been activated/pressed. • Firedrive input (N/O) U5/4 pin 1-2
activated
LED 5 Friction test is/has been activated • Friction test button pressed (U5)
LED 6 Overcurrent in 24V control circuit • Overcurrent at contact U1/5, U1/7, U1/
9, U1/23, U1/26, U1/27, U3/1, U5/7 or
U5/8
32 7000 400en-GBAC
Error memory
Level 4
When the button (2) is pressed down for a fourth time within 60 s the Err-lLED shuts repeatedly off and
the control LED 1-6 (errors 19-24) indicates the following error:
LED 1 Photocell switch open during run (only valid • Photocell activated during run
for B-lift/Aritco 2000).
LED 3 Lock circuit fault • Lock circuit open at start, interrupts start
after 6 seconds
After the fault finding, reset the Error Memory completely by pressing the button (2) down until the control
system responds with a beep, approximately 4 seconds.
1Lift is blocked, the error relay in U5/4 will be activated and the call station buttons starts flashing red/green
after 30 seconds
7000 400en-GBAC 33
This page is intentionally left blank
13 Safety Circuit 48VAC
48VAC 24VDC
+ -
E2 E3
19
-u-il ----------7
U1 1
48/24V
I I- - I
I I
- ----r-Mode --
Down -10·2 10.6 10�
ab/U5
L 15/_____
3 _ 1�_J
�
I
b2 I Re2 I
Stop
' I
U1/21
3
- -Sh�
,- -s� 9.1
I
b3 b9.n I b1.2 Rf I
II I
Final
U1/20
I
Edge
switch
limit
b4
:§
b9.2 1
I
9_ 1
I
L __ _JI I
-�
U1/19 u
0
I
Edge
I
--'
b5 b9.1 I Re1 I
-
U1/18
Edge
I UP/DOWN
_1
b6 I I
1.3 _J
L _ � _ _
U1/17 2
Edge
b8.1
b60
atc
U1/16
15/1_: �
L -� b8.2
I
i 91- Sh�
I b10 I
b8.n
__ _J ,-t---- I :
--t1�Ca�
I 92
Stop
I
Shafl I 1 Cab/Opti�
I I
_ _J I E4 I I cu cu I
CD CD
i Cab/us'7 I I I ---- I
I U5/2.1
I I I cu CD I
,-
E5 C1
I L __ _J I
D1 15/2
u1]
-iI --- _______
I I 94 - -Shati'] I
\
1
Door
I I b1.1 I I LED L ______ 230/ 400V3-phas�
D2
I U5/2.2
I 93
Final
limit I I Alt.
_J L_
I I
L
9
I7
_ switch
L _j _J I I
9- - - - - -� � Cab
I
1 11
--------------------------- l_-
I
9 C
0
C
:
I
L ______ 230 1-phase inverter
400 3-phase invert�
Safety Circuit 24VDC
48VAC 24VDC
+ -
E2 E3
-u-il ----------7
U 1 1
. I- 48/24V I- - I
Down
- ---- --
r Mode
I I ab/U5
-10·2 10.6 10::i"l
L 51 /3
______ 1�_J
�
I
b2
U1/21
I Re2 I
Stop
r Sh
--�
,--s�
I 9. 1
I
b3
U1/20
b9.n I b1.2 Rf I
Edge
I II
Final
limit
switch
I
b4
B
-�"' b9.2 1
I
9_ 1
I
L __ _JI I
U1/19
Edge
I I
b5 b9.1 I I
U1/18
Edge Re1
I - UP/DOWN
_1
b6
U1/17 2
I I
.1 3 _J
Edge L _ 22., __
b8.1
b60
U1/16
Hatch
b8.2
51 11
B
L _ _J -�"'
t ----- -t
�
I 9 -
1 Sh
b8.n I
- :
I b1 I I ;;-
1 ca�
0I
__ _J
I 92
Stop
Shaft i 1 Cab/Opti�
I I
L _ _J I E4 I I cu CD cu
I CD
i Cabtusl I I I ------- I
E5
,-
I U5/2. 1
I I I cu C1 CD I
I D1 L
_1I ___ _______ I
__ _J u""il
51 ,2
I i Sh
94--� I Door I I 230/ 400V3-phas
I D2
I b1.1 I I LED I L ______ �
I U5/2.2
I 93
Final
limit
switch
II I Alt. I
L_
I
L
L _j _ _J _J
I7 I
9- - - - - -�
I
1CJ Cab I
__________________ 1___
I
9 C1
0
9c11
:
I
L ______ 230 -1 phase inverter
400 3-phase invert�
CIRCUIT LINE 2 bw
Connection options
14 CONNECTION OPTIONS
14.1 ALARM BELL — EXTERNAL
7000 400en-GBAC 39
Connection options
40 7000 400en-GBAC
Connection options
Green LED shows that the phase sequence relay is connected to power and monitor the phases.
7000 400en-GBAC 41
Connection options
42 7000 400en-GBAC
List of components, Aritco 6000/7000
7000 400en-GBAC 43
List of components, Aritco 6000/7000
CD DOWN contactor
Cable colours:
vi = violet
or = orange
wh = white
gr = grey
blk = black
blu = blue
rd = red
br = brown
tr = transparent
44 7000 400en-GBAC
List of components, Aritco 6000/7000
7000 400en-GBAC 45
This page is intentionally left blank
14
54
54
ye br
blk
5
ye
2 1
blu
13
+
C1
CU 53
CD 53
7
Fältcom
1 2
b42 S5
0V GSM blu U6
4
br br
PE
4 3 2 1
8
blk b43
R1
TR2 6 6 T2
blu
7 7
17
18
(LED)
Rb
3
H1 H1 16 16 U5
2 1
PSTN blu
17 17
PSTN/T2 blk
18 18
D1 D2 br
9
1 2 3 4 5
22 64 64 22
2
Rf
CD CU CD CU b1.2
21 63 21 19
63
5 4 3 2 1
8 8 15
PE
1
2
3
A1 A1 A1
Re2
9 9 CU C1 CD 14
A2 A2 blk 13
10
10 10 vh A2 vi
gr 12
1
M2 rd 11
1 2 3 4 5 6
3 2 1
rd
Re1
12 96
E4
E5
95 L1
11
wh
wh
L3
rd
E5
L2
PE
91
92
93
94
PE
1
2
3
C1 6 5 CD
54 53 4 3
2 1
Q1
br
blk
blu
blu blu
21 CU E4
blk wh U/T1 L1 wh 2 1 or 1 C1 2 T1 blk T1 L1 blk
22 L1 L1
br or W/T3 L3 or 4 3 gr 3 4 T2 br T2 L2 br
b1.1 23 L2 L2
gr gr V/T2 L2 gr 6 5 br 5 6 T3 wh T3 L3 wh
24 U4 L3 L3 230VAC
N N blu
N
PE PE
4
wh
3
4
S4.n 5
5
1
2
E1
blu
blk
br
b40.n
1
2
3
1
1
blu
blk
br
22
1
blu
b8.n b9.n 32
blk
U3.n 3
br
blu H6 S3
1
blk
b3
blu
blk
br
5 42 H2
br
br
blk
4
3
2
1
blu
3 b4
br
blk
blu
gr
br
blk
blu
b6 b5 b2 b19 b80 H4
H5.n
b20.n
2500mm S4.2
blu
blk
br
+ 0 0 +
blu
blk
br
b40.2 2 1 2 1 2 1 2 1 2 1 2 1 6 5 4 3 2 1 2 1 4 3 2 1 3 2 1 3 2 1
1
2
3
b60
2
1
17 18 19 20 21 22 23 24 25 26 27 b31
1
1 22 1
blu
blk
br
1
blu
2
1
b8.2 b9.2 blk
b31.2
32 b33
2
1
U3.2 br 16 2
3 =
blu
b30.2
1
2
1
1
U
V
W
blk 15 3 b36
2
1
5 42 2
br
br
4
3
2
1
3
blk
3
blu
8
3 U1
7
RD
1
b16
6
RD 24VAC 2
M1
b15
H5.2
5
GR
3
b20.2
b14
4
GR 48VAC
4
S4.1 b13
3
BLU
5
14 7
b12
2
230VAC
S1
BLU
6
13 12 11 10 9 8 6 5 b11
1
1 2 3 4 1 2 1 2 3 4 5 6 7 8 1 2 1 2 3 4 5 6 7 8 1 2 1 2 3 1 2 1 2 3
blu
blk
br
b40.1 TR1
1
2
3
1
-
blu
blk
br
+
or
or
blk
rd
1 22
blu
br
blu
blk
br
blu
b31.1
b8.1 b9.1 1
blk
32
BG
4
5
6
7
8
9
b30.1
11
12
13
14
15
16
17
18
U3.1 br
10
3
br
blu
1
T1
E2
E3
+
br
blk
blu
5 42
S2.1
4
3
2
1
3
blu
br
blk
S2.2
+
19 E6 U7 6000/7000 Series Aritco
b10
H5.1
Rev Date No
b20.1
3-phase 230V 18-01-09
14
14
ye br
blk
5
ye
2 1
C11 blu
13
13
C10 +
7
Fältcom
1 2
b42 S5
0V GSM blu U6
4
br br
PE
4 3 2 1
8
blk b43
R1
TR2 6 6 T2
blu
7 7
17
18
(LED)
Rb
3
H1 H1 16 16 U5
2 1
PSTN blu
17 17
PSTN/T2 blk
18 18
D1 D2 br
9
1 2 3 4 5
2
Rf
b1.2
19
5 4 3 2 1
8 8 15
PE
1
2
3
A1 A1
Re2
9 9 C10 C11 14
A2 blk 13
10
10 10 vh A2 vi
gr 12
1
M2 rd 11
1 2 3 4 5 6
3 2 1
Re1
wh
wh
PE
91
92
93
94
PE
1
2
3
Q1
br
blk
blu
blu blu C11 C10
21
blk wh 2 1 1 2 blk L1 blk
22 L1
br or 4 3 3 4 br L2 br 230VAC
b1.1 23 L2/N
gr gr 6 5 5 6 L3
24
N
blk
PE
wh
4
4
4
3
S4.n 5
5
1
2
E1
blu
blk
br
b40.n
1
2
3
1
1
blu
blk
br
22
1
blu
b8.n b9.n 32
blk
U3.n 3
br
blu 24V H6 S3
1
blk
b3
blu
blk
br
5 42 H2
br
br
blk
4
3
2
1
blu
3 b4
br
blk
blu
gr
br
blk
blu
b6 b5 b2 b19 b80 H4
H5.n
b20.n
2500mm S4.2
L1
L2
br
R
blu
blk
br
+ 0 0 + blk F
blu
blk
br
b40.2 2 1 2 1 2 1 2 1 2 1 2 1 6 5 4 3 2 1 2 1 4 3 2 1 3 2 1 3 2 1
1
2
3
b60
2
1 blu
F1
17 18 19 20 21 22 23 24 25 26 27 b31 CC
1
1 22 1
blu
blk
br
1
blu
2
1
b8.2 b9.2 blk
b31.2
32 b33
2
1
U3.2 br 16 2
3 =
blu
b30.2
1
2
1
1
U
V
W
blk 15 3 b36
2
1
5 42 2
br
br
4
3
2
1
3
blk
3
blu
8
3 U1
7
RD
1
b16
6
RD 24VAC 2
M1
b15
H5.2
5
GR
3
b20.2
b14
4
GR 48VAC
4
S4.1 b13
3
BLU
5
14 7
b12
2
230VAC
S1
BLU
6
13 12 11 10 9 8 6 5 b11
1
1 2 3 4 1 2 1 2 3 4 5 6 7 8 1 2 1 2 3 4 5 6 7 8 1 2 1 2 3 1 2 1 2 3
blu
blk
br
b40.1 TR1
1
2
3
1
-
blu
blk
br
+
or
or
blk
rd
1 22
blu
br
blu
blk
br
blu
b31.1
b8.1 b9.1 1
blk
32
BG
4
5
6
7
8
9
b30.1
11
12
13
14
15
16
17
18
U3.1 br
10
3
br
blu
1
T1
E2
E3
+
br
blk
blu
5 42
S2.1
4
3
2
1
3
blu
br
blk
S2.2
+
19 E6 U7 6000/7000 Series Aritco
b10
H5.1
Rev Date No
b20.1
FR-230V 18-01-09
14
14
ye br
blk
5
ye
2 1
C11 blu
13
13
C10 +
7
Fältcom
1 2
b42 S5
0V GSM blu U6
4
br br
PE
4 3 2 1
8
blk b43
R1
TR2 6 6 T2
blu
7 7
17
18
(LED)
Rb
3
H1 H1 16 16 U5
2 1
PSTN blu
17 17
PSTN/T2 blk
18 18
D1 D2 br
9
1 2 3 4 5
2
Rf
b1.2
19
5 4 3 2 1
8 8 15
PE
1
2
3
A1 A1
Re2
9 9 C10 C11 14
A2 blk 13
10
10 10 vh A2 vi
gr 12
1
M2 rd 11
1 2 3 4 5 6
3 2 1
Re1
wh
wh
PE
91
92
93
94
PE
1
2
3
Q1
br
blk
blu
blu blu C11 C10
21
blk wh wh 2 1 or 1 2 blk L1 blk
22 L1
br or or 4 3 gr 3 4 br L2 br 400VAC
b1.1 23 L2
gr gr gr 6 5 br 5 6 wh L3 wh
24 L3
N blu
N
PE
4
4
S4.n 5
5
1
2
E1
blu
blk
br
b40.n
1
2
3
1
1
blu
blk
br
22
1
blu
b8.n b9.n 32
blk
U3.n 3
br
blu H6 S3
1
blk
b3
blu
blk
br
5 42 H2
br
br
blk
4
3
2
1
blu
3 b4
br
blk
blu
gr
br
blk
blu
b6 b5 b2 b19 b80 H4
H5.n
b20.n
2500mm S4.2
L1
L2
L3
br
R
blu
blk
br
+ 0 0 + blk
F
blu
blk
br
b40.2 2 1 2 1 2 1 2 1 2 1 2 1 6 5 4 3 2 1 2 1 4 3 2 1 3 2 1 3 2 1
1
2
3
b60
2
1 blu
F1
17 18 19 20 21 22 23 24 25 26 27 b31 CC
1
1 22 1
blu
blk
br
1
blu
2
1
T1
T2
T3
b31.2
32 b33
2
1
U3.2 br 16 2
3 =
blu
b30.2
1
2
1
1
U
V
W
blk 15 3 b36
2
1
5 42 2
br
br
4
3
2
1
3
blk
3
blu
8
3 U1
7
RD
1
b16
6
RD 24VAC 2
M1
b15
H5.2
5
GR
3
b20.2
b14
4
GR 48VAC
4
S4.1 b13
3
BLU
5
14 7
b12
2
230VAC
S1
BLU
6
13 12 11 10 9 8 6 5 b11
1
1 2 3 4 1 2 1 2 3 4 5 6 7 8 1 2 1 2 3 4 5 6 7 8 1 2 1 2 3 1 2 1 2 3
blu
blk
br
b40.1 TR1
1
2
3
1
-
blu
blk
br
+
or
or
blk
rd
1 22
blu
br
blu
blk
br
blu
b31.1
b8.1 b9.1 1
blk
32
BG
4
5
6
7
8
9
b30.1
11
12
13
14
15
16
17
18
U3.1 br
10
3
br
blu
1
T1
E2
E3
+
br
blk
blu
5 42
S2.1
4
3
2
1
3
blu
br
blk
S2.2
+
19 E6 U7 6000/7000 Series Aritco
b10
H5.1
Rev Date No
b20.1
FR-400V 18-01-09
14
54
54
ye br
blk
5
ye
2 1
blu
13
+
C1
CU 53
CD 53
7
Fältcom
1 2
b42 S5
0V GSM blu U6
4
br br
PE
4 3 2 1
8
blk b43
R1
TR2 6 6 T2
blu
7 7
17
18
(LED)
Rb
3
H1 H1 16 16 U5
2 1
PSTN blu
17 17
PSTN/T2 blk
18 18
D1 D2 br
9
1 2 3 4 5
22 64 64 22
2
Rf
CD CU CD CU b1.2
21 63 21 19
63
5 4 3 2 1
8 8 15
PE
1
2
3
A1 A1 A1
Re2
9 9 CU C1 CD 14
A2 A2 blk 13
10
10 10 vh A2 vi
gr 12
1
M2 rd 11
1 2 3 4 5 6
3 2 1
rd
Re1
12 96
E4
E5
95 L1
11
wh
wh
L3
rd
E5
L2
PE
91
92
93
94
PE
1
2
3
6 5 CD
4 3
2 1
Q1
br
blk
blu
blu blu
21 CU E4
blk wh U/T1 L1 wh 2 1 or 1 C1 2 T1 blk T1 L1 blk
22 L1
br or W/T3 L3 or 4 3 gr 3 4 T2 br T2 L2 br
b1.1 23 L2
gr gr V/T2 L2 gr 6 5 br 5 6 T3 wh T3 L3 wh
24 U4 L3 400VAC
N N blu
N
PE
4
4
S4.n 5
5
E1
blu
blk
br
b40.n
1
2
3
1
1
blu
blk
br
22
1
blu
b8.n b9.n 32
blk
U3.n 3
br
blu H6 S3
1
blk
b3
blu
blk
br
5 42 H2
br
br
blk
4
3
2
1
blu
3 b4
br
blk
blu
gr
br
blk
blu
b6 b5 b2 b19 b80 H4
H5.n
b20.n
2500mm S4.2
blu
blk
br
+ 0 0 +
blu
blk
br
b40.2 2 1 2 1 2 1 2 1 2 1 2 1 6 5 4 3 2 1 2 1 4 3 2 1 3 2 1 3 2 1
1
2
3
b60
2
1
17 18 19 20 21 22 23 24 25 26 27 b31
1
1 22 1
blu
blk
br
1
blu
2
1
b8.2 b9.2 blk
b31.2
32 b33
2
1
U3.2 br 16 2
3 =
blu
b30.2
1
2
1
1
U
V
W
blk 15 3 b36
2
1
5 42 2
br
br
4
3
2
1
3
blk
3
blu
8
3 U1
7
RD
1
b16
6
RD 24VAC 2
M1
b15
H5.2
5
GR
3
b20.2
b14
4
GR 48VAC
4
S4.1 b13
3
BLU
5
14 7
b12
2
230VAC
S1
BLU
6
13 12 11 10 9 8 6 5 b11
1
1 2 3 4 1 2 1 2 3 4 5 6 7 8 1 2 1 2 3 4 5 6 7 8 1 2 1 2 3 1 2 1 2 3
blu
blk
br
b40.1 TR1
1
2
3
1
-
blu
blk
br
+
or
or
blk
rd
1 22
blu
br
blu
blk
br
blu
b31.1
b8.1 b9.1 1
blk
32
BG
4
5
6
7
8
9
b30.1
11
12
13
14
15
16
17
18
U3.1 br
10
3
br
blu
1
T1
E2
E3
+
br
blk
blu
5 42
S2.1
4
3
2
1
3
blu
br
blk
S2.2
+ 6000/7000 Series
19 E6 U7 Aritco
b10
H5.1
Rev Date No
b20.1
3-phase 400V 18-01-09
14
14
ye br
blk
5
ye
2 1
C11 blu
13
13
C10 +
7
Fältcom
1 2
b42 S5
0V GSM blu U6
4
br br
PE
4 3 2 1
8
blk b43
R1
TR2 6 6 T2
blu
7 7
17
18
(LED)
Rb
3
H1 H1 16 16 U5
2 1
PSTN blu
17 17
PSTN/T2 blk
18 18
D1 D2 br
9
1 2 3 4 5
2
Rf
b1.2
19
5 4 3 2 1
8 8 15
PE
1
2
3
A1 A1
Re2
9 9 C10 C11 14
A2 blk 13
10
10 10 vh A2 vi
gr 12
1
M2 rd 11
1 2 3 4 5 6
3 2 1
Re1
wh
wh
PE
91
92
93
94
PE
1
2
3
Q1
br
blk
blu
blu blu C11 C10
21
blk wh wh 2 1 or 1 2 blk L1 blk
22 L1
br or or 4 3 gr 3 4 br L2 br 400VAC
b1.1 23 L2
gr gr gr 6 5 br 5 6 wh L3 wh
24 L3
N blu N
PE
4
4
S4.n 5
5
1
2
E1
blu
blk
br
b40.n
1
2
3
1
1
blu
blk
br
22
1
blu
b8.n b9.n 32
blk
U3.n 3
br
blu H6 S3
1
blk
b3
blu
blk
br
5 42 H2
br
br
blk
4
3
2
1
blu
3 b4
br
blk
blu
gr
br
blk
blu
b6 b5 b2 b19 b80 H4
H5.n
b20.n
2500mm S4.2
L1
L2
L3
4
R
blu
blk
br
+ 0 0 + 3
F
blu
blk
br
b40.2 2 1 2 1 2 1 2 1 2 1 2 1 6 5 4 3 2 1 2 1 4 3 2 1 3 2 1 3 2 1 2
S1
1
2
3
b60
2
1 1
F1
17 18 19 20 21 22 23 24 25 26 27 b31 CC
1
1 22 1
blu
blk
br
1
blu
2
1
T1
T2
T3
b31.2
32 b33
2
1
U3.2 br 16 2
3 =
blu
b30.2
1
2
1
1
U
V
W
blk 15 3 b36
2
1
5 42 2
br
br
4
3
2
1
3
blk
3
blu
8
3 U1
7
RD
1
b16
6
RD 24VAC 2
M1
b15
H5.2
5
GR
3
b20.2
b14
4
GR 48VAC
4
S4.1 b13
3
BLU
5
14 7
b12
2
230VAC
S1
BLU
6
13 12 11 10 9 8 6 5 b11
1
1 2 3 4 1 2 1 2 3 4 5 6 7 8 1 2 1 2 3 4 5 6 7 8 1 2 1 2 3 1 2 1 2 3
blu
blk
br
b40.1 TR1
1
2
3
1 blu
-
blu
blk
br
+ blk
blu
blk
br
Com 1
or
or
blk
rd
1 22 br
blu
br
blu
blk
br
blu
b31.1
b8.1 b9.1 1 Com 2
blk
32
BG
4
5
6
7
8
9
b30.1
11
12
13
14
15
16
17
18
br 6 3
+S-
U3.1
10
3
U11.1
br
b37
blu
1
T1
E2
E3
5 4
+
br
blk
blu
5 42
S2.1
4
3
2
1
3
blu
br
blk
S2.2
+
19 E6 U7 6000/7000 Series Aritco
b10
H5.1
Rev Date No
b20.1
FR-400V 0,25 18-01-09
Revision history
17 REVISION HISTORY
Ch. 6.1 Updated text in table for Service alarm rest, Emergency run limit
sw and Friction test
Ch. 8 Updated text at: Plug 2, plug 5, plug 6, plug 8, plug 9, plug 11,
plug 12, plug 26
Ch.9 Updated text for: Oil, Reserved 1. Added text for Reserved 2.
New table for door time/cabin light. Explanation Fire control.
Ch. 12 Updated text and new format. Tables updated and got column
possible error causes
7000 400en-GBAC 57
7000 400en-GBAC ENGLISH
last page
Aritco Lift AB, Energivägen 7, Box 18, 196 21 Kungsängen, SWEDEN, T: +46 8 120 401 00, F: +46 8 120 401 99, E: [email protected]