Air System Sizing Summary for GR-AHU-01

Project Name: 479-16 Quran Memorization center AWQAF-20230129 02/14/2023


Prepared by: APG 04:34PM

Air System Information


Air System Name GR-AHU-01 Number of zones 3
Equipment Class CW AHU Floor Area 835.0 m²
Air System Type VAV Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 93.7 kW Load occurs at Jul 0900
Sensible coil load 86.8 kW OA DB / WB 38.9 / 28.5 °C
Coil L/s at Jul 0900 5515 L/s Entering DB / WB 22.7 / 14.7 °C
Max block L/s at Jul 0900 6056 L/s Leaving DB / WB 9.6 / 8.9 °C
Sum of peak zone L/s 6094 L/s Coil ADP 8.2 °C
Sensible heat ratio 0.926 Bypass Factor 0.100
m²/kW 8.9 Resulting RH 45 %
W/m² 112.3 Design supply temp. 12.0 °C
Water flow @ 5.6 °K rise 4.04 L/s Zone T-stat Check 3 of 3 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s at Jul 0900 6056 L/s Fan motor BHP n/a
Standard L/s 6049 L/s Fan motor kW 13.67 kW
Actual max L/(s-m²) 7.25 L/(s-m²)

Outdoor Ventilation Air Data


Design airflow L/s 910 L/s L/s/person 8.43 L/s/person
L/(s-m²) 1.09 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 2


Zone Sizing Summary for GR-AHU-01
Project Name: 479-16 Quran Memorization center AWQAF-20230129 02/14/2023
Prepared by: APG 04:34PM

Air System Information


Air System Name GR-AHU-01 Number of zones 3
Equipment Class CW AHU Floor Area 835.0 m²
Air System Type VAV Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
G-RECEPTION HALL 36.7 3383 380 Jul 0900 4.1 400.0 8.46
G-TOILET 05 1.3 82 1 Jan 2300 0.0 43.0 1.90
G-MULTI PURPOSE HALL 27.2 2508 530 Jul 2000 3.5 392.0 6.40

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
G-RECEPTION HALL 7.3 0.16 0.0 0.00 0
G-TOILET 05 0.0 0.00 0.0 0.00 0
G-MULTI PURPOSE HALL 8.0 0.17 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
G-RECEPTION HALL
G-RECEPTION HALL 1 36.7 Jul 0900 3383 4.1 400.0 8.46
G-TOILET 05
G-TOILET 05 1 1.3 Jan 2300 82 0.0 43.0 1.90
G-MULTI PURPOSE HALL
G-MULTI-PURPOSE HALL 1 27.2 Jul 2000 2508 3.5 392.0 6.40

Hourly Analysis Program v4.90 Page 2 of 2