PEM575 - Manual
PEM575 - Manual
PEM575 - Manual
PEM575
PEM575_D00016_00_M_XXEN/03.2015
Bender GmbH & Co. KG
Londorfer Str. 65 • 35305 Gruenberg • Germany
P.O. Box 1161 • 35301 Gruenberg • Germany © Bender GmbH & Co. KG
Tel.: +49 6401 807-0
All rights reserved.
Fax: +49 6401 807-259
Reprinting only with permission
E-Mail: [email protected] of the publisher.
www.bender.de Subject to change!
Table of Contents
2. Safety ...................................................................................................... 13
2.1 Intended use ........................................................................................................... 13
2.2 Qualified personnel .............................................................................................. 13
2.3 General safety instructions ................................................................................ 14
PEM575_D00016_00_M_XXEN/03.2015 3
Table of Contents
5. Commissioning ...................................................................................... 27
5.1 Check proper connection ................................................................................... 27
5.2 Before switching on .............................................................................................. 27
5.3 Switching on ............................................................................................................ 27
5.4 System ....................................................................................................................... 28
6. Operation ............................................................................................... 29
6.1 Getting to know the operating elements .................................................... 29
6.2 LCD testing ............................................................................................................... 30
6.3 Getting to know standard display areas ....................................................... 31
6.4 Power and current demands (demand display) ......................................... 33
6.5 LED indication ......................................................................................................... 34
6.6 Standard display .................................................................................................... 34
6.7 Data display ............................................................................................................. 34
6.7.1 "V/I" button ..................................................................................................... 35
6.7.2 "POWER"button ............................................................................................ 37
6.7.3 "HARMONICS" button ................................................................................. 39
6.7.4 "ENERGY" button .......................................................................................... 41
6.8 Setup configuration via the front panel ........................................................ 42
6.8.1 Setup: Function of buttons ....................................................................... 42
6.8.2 Setup: Overview diagram menu ............................................................. 43
6.9 Setup: adjustment possibilities ........................................................................ 44
6.10 Configuration example: ....................................................................................... 50
4 PEM575_D00016_00_M_XXEN/03.2015
Table of Contents
8. Logging ................................................................................................... 61
8.1 Peak demand log ................................................................................................... 61
8.2 Max/Min log ............................................................................................................. 61
8.3 Data recorder (DR) ................................................................................................. 63
8.3.1 Setup parameters ......................................................................................... 63
8.3.2 Selectable measured quantities for data recorders DR .................. 64
8.4 Energy log ................................................................................................................ 76
8.5 Waveform recording (WFR) ................................................................................ 77
8.6 Power Quality log (PQ log) ................................................................................. 79
8.7 Event log (SOE log) ................................................................................................ 79
5 PEM575_D00016_00_M_XXEN/03.2015
Table of Contents
6 PEM575_D00016_00_M_XXEN/03.2015
Table of Contents
7 PEM575_D00016_00_M_XXEN/03.2015
1. Making effective use of this document
Although great care has been taken in the drafting of this operating manual, it may
nevertheless contain errors and mistakes. The Bender Group cannot accept any li-
ability for injury to persons or damage to property resulting from errors or mistakes
in this manual.
Each of the registered trademarks which appear in this document remains the
property of its owner.
PEM575_D00016_00_M_XXEN/03.2015 9
Making effective use of this document
Commissioning
Troubleshooting
Repair service
Repair, calibration, update and replacement service for all Bender products
Repair, calibration, testing and analysing Bender products
Extended warranty for Bender devices with in-house repair service resp. replace-
10 PEM575_D00016_00_M_XXEN/03.2015
Making effective use of this document
Field service
On-site service for all Bender products
Commissioning, parameter setting, maintenance, trouble shooting for Bender
products
Analysis of the electrical installation in the building (power quality test, EMC test,
thermography)
Practical training courses for customers
*Available from 7.00 a.m. to 8.00 p.m. on 365 days of the year (CET/UTC+1)
**Mo-Thu 7.00 a.m. - 8.00 p.m., Fr 7.00 a.m. - 13.00 p.m.
1.3 Workshops
Bender would be happy to provide training in respect of the use of the universal
measuring device.
Current dates of training courses and workshops can be found on the Internet at
http://www.bender.de -> Know-how -> Seminars.
PEM575_D00016_00_M_XXEN/03.2015 11
Making effective use of this document
12 PEM575_D00016_00_M_XXEN/03.2015
2. Safety
As a compact device for front panel mounting, it is a replacement for analogue in-
dicating instruments. Das PEM575 is suitable for 2, 3 and 4-wire systems and can be
used in TN, TT and IT systems. The current measurement inputs of the PEM are con-
nected via external ../1 A or ../5 A measuring current transformers. In principle,
measurements in medium and high voltage systems are carried out via measure-
ment transformers and voltage transformers.
Use for the intended purpose also includes:
Device-specific settings according to local equipment and operating conditions.
PEM575_D00016_00_M_XXEN/03.2015 13
Safety
14 PEM575_D00016_00_M_XXEN/03.2015
3. Device description
plants)
energy-intensive equipment and parts of installation
sensitive equipment
Password protection
16 programmable setpoints
6 digital inputs
3 digital outputs
Data recorder
Event log: 512 events, setup changes, setpoint alarming, DI status changes, DO
switching operations
Sag/swell detection
PEM575_D00016_00_M_XXEN/03.2015 15
Device description
Communication:
– Galvanically isolated RS-485 interface (1,200 … 19,200 bit/s)
– Modbus/RTU protocol
– Modbus/TCP (10/100 Mbit/s)
Measured quantities
– Phase voltages UL1, UL2, UL3 in V
– Line-to-line voltages UL1L2, UL2L3, UL3L1 in V
– Phase currents I1, I2, I3 in A
– Neutral current (calculated) I0 in A
– Neutral current (measured) I4 in A
– Frequency f in Hz
– Phase angle for U and I in °
– Power per phase conductor P in kW, Q in kvar, S in kVA
– Total power P in kW, Q in kvar, S in kVA
– Displacement factor cos (φ)
– Power factor λ
– Active and reactive energy import in kWh, kvarh
– Active and reactive energy export in kWh, kvarh
– Voltage unbalance in %
– Current unbalance in %
– Harmonic distortion
(THD, TOHD, TEHD) for U and I
– K-factor for I
3.3 Versions
PEM575 230/400 V;
Current input 5 A
PEM575-251 230/400 V
Current input 1 A
PEM575-455 400/690 V, 50 Hz
Current input 5 A
PEM575-451 400/690 V, 50 Hz
Current input 1 A
16 PEM575_D00016_00_M_XXEN/03.2015
3.4 Application example
PEM7xx PEM7xx
U U
Ethernet
I I
Datenbank
Modbus TCP Modbus TCP
NSHV
L
PEN CP700
PE
PAS
BMS 1…12
1…12
Modbus TCP Modbus TCP
Modbus RTU Modbus RTU
3 3
PEM3xx PEM3xx
U U
I I
PEM575_D00016_00_M_XXEN/03.2015 17
Device description
The accuracy of the active energy metering corresponds to class 0.2 S in compli-
ance with the DIN EN 62053-22 (VDE 0418 Part 3-22):2003-11.
The large display of the panel mounting device makes the relevant measured
quantities easily legible and enables fast configuration. In addition, the RS-485 in-
terface allows a central evaluation and processing of data. Switching operations
can be monitored or initiated via the digital inputs and outputs (Example: Switch-
ing off uncritical loads if the peak load limit value is exceeded).
ment
Allocation of energy costs
Power quality monitoring for cost reduction and increased plant availability
SH • l41 l42 L1 L2 L3 N
OK
Fig. 3.2: Front view (left) and rear view (right) PEM575
18 PEM575_D00016_00_M_XXEN/03.2015
4. Installation and connection
106
91
88
96
96
PEM575_D00016_00_M_XXEN/03.2015 19
Installation and connection
18 88 18
91 96
92
92
20 PEM575_D00016_00_M_XXEN/03.2015
Installation and connection
PEM575_D00016_00_M_XXEN/03.2015 21
Installation and connection
US
ETH RS-485
D+ D- SH
DO34 DO33 DO24 DO23 DO14 DO13 2
7
SH • l41 l42 L1 L2 L3 N
L1
L2 DO13 DO14
L3
DO23 DO24
N 4
5 DO33 DO34
L1 L2 L3 N
22 PEM575_D00016_00_M_XXEN/03.2015
Installation and connection
AC 400 V / 230 V
L1 L2 L3 N
Ri
PEM
PEM575_D00016_00_M_XXEN/03.2015 23
Installation and connection
AC 400 V
L1 L2 L3 N
Ri
PEM
24 PEM575_D00016_00_M_XXEN/03.2015
Installation and connection
LV / MV / HV
L1 L2 L3 N
Ri
PEM
PEM575_D00016_00_M_XXEN/03.2015 25
Installation and connection
DO13 DO14
Rated operational
AC 230 V DC 24 V AC 110 V DC 12 V
voltage
DO23 DO24
Rated
DO33 DO34 5A 5A 6A 5A
operational current
26 PEM575_D00016_00_M_XXEN/03.2015
5. Commissioning
5.3 Switching on
After switching on, proceed as follows:
1. Connect the supply voltage.
2. Set the bus address/IP address.
3. Set the CT transformation ratio (for each channel).
4. Change the measuring current transformer's counting direction, if required.
5. Set the nominal voltage (line-to-line voltage ULL).
6. Select wye connection or delta connection.
PEM575_D00016_00_M_XXEN/03.2015 27
Commissioning
5.4 System
The universal measuring device PEM575 can be programmed and queried via Mod-
bus RTU. For details refer to "chapter 10. Modbus Register Map" or the Internet
www.modbus.org.
In addition, it is possible to integrate the device into Bender's own BMS (Bender
measuring device interface) bus protocol via additional communication modules.
In this way, communication with (already existing) Bender devices for device pa-
rameterisation and visualisation of measured values and alarms can be achieved.
Help and examples of system integration can be found on the Bender homepage
www.bender.de or you can contact our Bender Service for personal advice (see
"chapter 1.2 Technical support: Service and support").
28 PEM575_D00016_00_M_XXEN/03.2015
6. Operation
OK
4 5 6 7
Fig. 6.1: Operating elements
PEM575_D00016_00_M_XXEN/03.2015 29
Operation
During testing, all LCD segments are illuminated for one second and then turned
off for 1 second. This cycle will be repeated 3 times. After completion of the test run,
the device automatically returns to its normal display mode.
30 PEM575_D00016_00_M_XXEN/03.2015
Operation
No. Description
2 Measured values
PEM575_D00016_00_M_XXEN/03.2015 31
Operation
DI open DI closed
1
DO open DO closed
kW, MW, kvar, kVA,
V, kV, A, %, Hz
MVA
Measurement units for
Measurement units for
U, I, THD, f
P, Q, S
NET kvarh
TOT kvarh
Reactive kVAh
Total reactive
energy net Apparent
energy
amount energy
32 PEM575_D00016_00_M_XXEN/03.2015
Operation
4 2
PEM575_D00016_00_M_XXEN/03.2015 33
Operation
First line
Second line
Third line
Fourth line
Fifth line
Left column Right column
34 PEM575_D00016_00_M_XXEN/03.2015
Operation
PEM575_D00016_00_M_XXEN/03.2015 35
Operation
Left Right
First line Second line Third line Fourth line
column column
I1
DMD 2 A Demand I1 Demand I2 Demand I3 Ø Demand I
3
DMD I4 A Demand I4
A
DMD Peak demand I1
A JJJJ.MM.TT hh:mm:ss
MAX this month
TM
b
DMD Peak demand I2
A JJJJ.MM.TT hh:mm:ss
MAX this month
TM
C
DMD Peak demand I3
A JJJJ.MM.TT hh:mm:ss
MAX this month
TM
A
DMD Peak demand I1
A JJJJ.MM.TT hh:mm:ss
MAX last month
LM
b
DMD Peak demand I2
A JJJJ.MM.TT hh:mm:ss
MAX last month
LM
C
DMD Peak demand I3
A JJJJ.MM.TT hh:mm:ss
MAX last month
LM
36 PEM575_D00016_00_M_XXEN/03.2015
Operation
6.7.2 "POWER"button
Left Right
First line Second line Third line Fourth line
column column
* P1
2 W PL1* PL2* PL3* Pges
3
TOT
*q1
2 var QL1* QL2* QL3* Qges
3
TOT
*S1
2
VA SL1* SL2* SL3* Sges
3
TOT
*PF1
2 λL1* λL2* λL3* λges
3
TOT
d1
2 W PL1 (f0) PL2 (f0) PL3 (f0) Pges (f0)
3
TOT
d1
2 var QL1 (f0) QL2 (f0) QL3 (f0) Qges (f0)
3
TOT
d1
2
VA SL1 (f0) SL2 (f0) SL3 (f0) Sges (f0)
3
TOT
*dPF1
Displacement Displacement Displacement Displace-
2
ment factor
3 factor cos (φ)L1 f(0)* factor cos (φ)L2 f(0)* factor cos (φ)L3 f(0)* cos (φ)
f(0)
TOT
W
TOT var Pges Qges Sges λges
VA
PEM575_D00016_00_M_XXEN/03.2015 37
Operation
Left Right
First line Second line Third line Fourth line
column column
W
d
var Pges (f0) Qges (f0) Sges (f0) λges (f0)
TOT
VA
W
DMD Demand
var Demand Pges Demand Qges Demand Sges
TOT λges
VA
P W Predicted
Predicted demand Predicted demand Predicted demand
DMD var demand
Pges Qges Sges
TOT VA λges
P
DMD Peak demand P
kW YYYY.MM.DD hh:mm:ss
MAX this month
TM
q
DMD Peak demand Q
kvar YYYY.MM.DD hh:mm:ss
MAX this month
TM
S
DMD Peak demand S
kVA YYYY.MM.DD hh:mm:ss
MAX this month
TM
P
DMD Peak demand P
kW YYYY.MM.DD hh:mm:ss
MAX last month
LM
Q
DMD Peak demand Q
kvar YYYY.MM.DD hh:mm:ss
MAX last month
LM
S
DMD Peak demand S
kVA YYYY.MM.DD hh:mm:ss
MAX last month
LM
Table6.2: Display possibilities via the "POWER" button
38 PEM575_D00016_00_M_XXEN/03.2015
Operation
Left Right
First line Second line Third line Fourth line
column column
THD U1
2 % THDUL1 THDUL2 THDUL3 Ø THDULN
3
AVG
THD I1
2 THDI1 THDI2 THDI3 Ø THDI
%
3
AVG
PEM575_D00016_00_M_XXEN/03.2015 39
Operation
Left Right
First line Second line Third line Fourth line
column column
HD31 U1
2 % 31st 31st 31st Ø 31st
3
AVG
*HD31 I1
2
% 31st 31st 31st harmonic I3 Ø 31st harmonic I
3
AVG
40 PEM575_D00016_00_M_XXEN/03.2015
Operation
Left
Right column Value
column
IMP kWh Active energy import
EXP kWh Active energy export
Active energy net
NET kWh
amount
TOT kWh Total active energy
Reactive energy
IMP kvarh
import
Reactive energy
EXP kvarh
export
Reactive energy net
NET kvarh
amount
TOT kvarh Total reactive energy
S kVAh Apparent energy
PEM575_D00016_00_M_XXEN/03.2015 41
Operation
"V / I": arrow button " " moves the cursor to the left by one position if
the parameter being changed is a numerical
value
"POWER": arrow button " " advances to the next parameter in the menu
or increments a numerical value
"HARMONICS": arrow button " " goes back to the last parameter in the menu or
decrements a numerical value
"ENERGY": OK to confirm the value entered
42 PEM575_D00016_00_M_XXEN/03.2015
Operation
ENERGY/OK >3s
PEM575_D00016_00_M_XXEN/03.2015 43
Operation
Display screen
Adjustment Default
Level 1 Parameters Description
possibilities setting
Level 2
WYE/DELTA/
TYPE Wiring mode Select wiring mode WYE
DEMO
Select CT transformation
I4 Neutral current 1…10,000 1
ratio for I4
Reverse phase I1
I1 REV I1 CT YES/NO NO
CT polarity
44 PEM575_D00016_00_M_XXEN/03.2015
Operation
Display screen
Adjustment Default
Level 1 Parameters Description
possibilities setting
Level 2
Reverse phase I2
I2 REV I2 CT YES/NO NO
CT polarity
Reverse phase I3
I3 REV I3 CT YES/NO NO
CT polarity
0…60
BLTO SET Display backlight Backlight timeout 3
(minutes)
1200/2400/
BAUD1 Baud rate Set baud rate 4800/9600/ 9600
19200 bps
8N2/8O1/8E1/
CONFIG1 Parity bit Parity bit configuration 8E1
8N1/8O2/8E2
MODBUS/
PRO Protocol Modbus
EGATE
PEM575_D00016_00_M_XXEN/03.2015 45
Operation
Display screen
Adjustment Default
Level 1 Parameters Description
possibilities setting
Level 2
0…
kVAh Apparent energy Preset apparent energy 0
999,999,999
46 PEM575_D00016_00_M_XXEN/03.2015
Operation
Display screen
Adjustment Default
Level 1 Parameters Description
possibilities setting
Level 2
CLR MXMN Clear Max and Min values of this month YES/NO NO
PEM575_D00016_00_M_XXEN/03.2015 47
Operation
Power factor (-) Power factor (+) Power factor (+) Power factor (-)
Active power export (-) Active power import (+) Active power export (-) Active power export (+)
Reactive power import (+) Reactive power import (+) Reactive power import (+) Reactive power import (+)
Power factor (-) Power factor (+) Power factor (-) Power factor (+)
Active power export (-) Active power import (+) Active power export (-) Active power import (+)
Reactive power export (-) Reactive power export (-) Reactive power export (-) Reactive power export (-)
IEC IEEE
48 PEM575_D00016_00_M_XXEN/03.2015
Operation
FUND Uk
"Fundamental": THD U(k) = x 100 %
U1
THD calculation of an individual harmonic (related to
fundamental U1 resp. I1) Ik
THD I(k) = x 100 %
I1
RMS Uk
"Root Mean Square": THF
U(k)
= x 100 %
∞
Distortion factor calculation of an individual ΣU
k=1
2
k
harmonic (THF, related to the total value Uges
resp. Iges)
Ik
THF
I(k)
= x 100 %
∞
ΣI
k=1
k
2
PEM575_D00016_00_M_XXEN/03.2015 49
Operation
50 PEM575_D00016_00_M_XXEN/03.2015
Application/inputs and outputs
PEM575_D00016_00_M_XXEN/03.2015 51
Application/inputs and outputs
Pulse constant
Pulses per kWh =
ratio VT x ratio CT Note:
VT = voltage transformer
ratio VT x ratio CT CT = measuring current
Amount of energy
= transformer
per pulse Pulse constant
three-phase currents
three-phase power
Neutral current
Frequency
52 PEM575_D00016_00_M_XXEN/03.2015
Application/inputs and outputs
7.4.4 Energy
Basic energy parameters include
active energy (import, export, net energy and total energy in kWh)
reactive energy (import, export, net energy and total energy in kvarh) as well as
PEM575_D00016_00_M_XXEN/03.2015 53
Application/inputs and outputs
Frequency
Voltage unbalance
Current unbalance
The demand period can be set using the buttons on the front panel or via the com-
munications interface. The following options are available:
1, 2, 3, 5, 10, 15, 30, 60 minutes
In addition to the demand period also the demand cycles (sliding window) be-
tween 1 and 15 are to be specified.
During the total demand period (duration multiplied by the number), the con-
sumption resp. the imported power is measured. Then the average demand value
is indicated on the display and output via the communications interface.
The maximum demand value (peak demand) determined over the whole recording
period will be saved and displayed. The peak demand can be reset manually.
Setting possibilities: Chapter 6.9 Setup: adjustment possibilities.
54 PEM575_D00016_00_M_XXEN/03.2015
Application/inputs and outputs
three-phase currents
three-phase frequencies
three-phase power
Voltage unbalance
Current unbalance
All recorded measuring values can be accessed via the communications interface.
7.6 Setpoints
The PEM575 features 24 user-programmable control setpoints (registers
6600…6839) which provide extensive control by allowing a user to initiate an ac-
tion in response to a specific condition. The alarm symbol at the right side of
the LC display is lit if there are any active setpoints.
The first 16 setpoints (1…16) are standard setpoints, the other setpoints (17…24)
are high-speed setpoints.
Typical setpoint applications are alarming, fault location and power quality moni-
toring (PQ monitoring).
Setpoints can be programmed via the communications interface.
The following setup parameters are provided:
PEM575_D00016_00_M_XXEN/03.2015 55
Application/inputs and outputs
Setpoints
Key for setpoint Parameters Factor; Unit
1 ULN x 100; V
2 ULL x 100; V
3 I x 1000; A
4 I4 x 1000; A
5 Δf x 100, Hz
6 Pges kW
7 Qges kvar
8 λ x1,000
9 DI1
Over setpoint
10 DI2 active limit: DI= 1 (close)
inactive limit: DI = 0 (open)
11 DI3
14 DI6
15 Reserved
16 Demand Pges kW
18 Demand λ x1,000
22 THDU x 100, %
23 TOHDU x 100, %
56 PEM575_D00016_00_M_XXEN/03.2015
Application/inputs and outputs
25 THDI x 100, %
26 TOHDI x 100, %
27 TEHDI x 100, %
28 Unbalance U x 10, %
29 Unbalance I x 10, %
30 ΔU x 100, %
Over setpoint
active limit: negative phase sequence
inactive limit: positive phase sequence
31 Phase sequence
Under setpoint
active limit: positive phase sequence
inactive limit: negative phase sequence
Table7.1: Setpoint parameters
PEM575_D00016_00_M_XXEN/03.2015 57
Application/inputs and outputs
6. Delay on release: Specifies the minimum period that the setpoint return
condition must have met before returning to normal condition.
Each status change generates an event which is stored in the event log. The
delay on release can be indicated for standard setpoints in the range of
0…9.999 seconds. The delay on release for high-speed setpoints can be indi-
cated in the range of 0…9.999 cycles.
7. Setpoint trigger: Specifies what action the setpoint will take when it becomes
active. This action includes "No Trigger" and "Trigger DOx".
0 - 12 DR 9
1 DO1 13 DR 10
2 DO2 14 DR 11
3 DO3 15 DR 12
4 DR 1 16 DR 13
5 DR 2 17 DR 14
6 DR 3 18 DR 15
7 DR 4 19 DR 16
8 DR 5 20 WFR1
9 DR 6 21 WFR2
Alarm
10 DR 7 22
e-mail
11 DR 8
58 PEM575_D00016_00_M_XXEN/03.2015
Application/inputs and outputs
Logical expression =
The alarm symbol at the right side of the LC display appears when there are ac-
tive logic modules. Logic modules are programmed via the communications inter-
face.
Details about the applied registers and their data structure you will find on
page 126.
PEM575_D00016_00_M_XXEN/03.2015 59
Application/inputs and outputs
60 PEM575_D00016_00_M_XXEN/03.2015
Logging
8. Logging
PEM575_D00016_00_M_XXEN/03.2015 61
Logging
62 PEM575_D00016_00_M_XXEN/03.2015
Logging
12 standard recorders
Each of these recorders can record 16 parameters. The data recorders are pro-
grammed solely via the communications interface.
Details about the applied registers and their data structure you will find on
page 129.
PEM575_D00016_00_M_XXEN/03.2015 63
Logging
1) "Recording delay":
In Trigger mode 1, a fixed time can be set in seconds to delay the start of the measurement
(triggered by timer). Example: "300" means that the recording will take place at 5 minutes
after the DR is enabled. In order to obtain evaluable results, the programmed value of the
recording offset parameter should be less than that of the recording interval parameter.
For Trigger mode 2, recording delay is ignored.
For details refer to
- Modbus register 7000…7383 (page 129).
- Data structure high speed data recorder (page 131)
- Data standard data recorder (page 132)
64 PEM575_D00016_00_M_XXEN/03.2015
Logging
PEM575_D00016_00_M_XXEN/03.2015 65
Logging
66 PEM575_D00016_00_M_XXEN/03.2015
Logging
PEM575_D00016_00_M_XXEN/03.2015 67
Logging
68 PEM575_D00016_00_M_XXEN/03.2015
Logging
PEM575_D00016_00_M_XXEN/03.2015 69
Logging
70 PEM575_D00016_00_M_XXEN/03.2015
Logging
PEM575_D00016_00_M_XXEN/03.2015 71
Logging
72 PEM575_D00016_00_M_XXEN/03.2015
Logging
PEM575_D00016_00_M_XXEN/03.2015 73
Logging
74 PEM575_D00016_00_M_XXEN/03.2015
Logging
PEM575_D00016_00_M_XXEN/03.2015 75
Logging
Apparent energy
These measured values are stored in a non-volatile memory and will not suffer any
loss in the event of power failure. For the recording of the total energy values such
as Pges or Qges the data recorder has to be used.
The programming of the energy log is only supported over communications.
The following set-up parameters are supported:
76 PEM575_D00016_00_M_XXEN/03.2015
Logging
The energy log will only become active when the values of the Setup settings 1…5
are all non-zero.
For details refer to Modbus registers 7700…7712.
Undervoltage/overvoltage (sag/swell)
Transient events
During this process the control via communications interface has the highest
priority. Other WFR triggers will be ignored until recording is completed.
Each WFR log has a capacity of 32 entries. If there are more than 32 entries, the new-
est entry will replace the oldest entry on a first-in-first-out basis: Der 33rd entry
overwrites the 1st entry, the 34th the 2nd etc.
WFR data is stored in a non-volatile memory and will not suffer any loss in the event
of power failure.
The programming of the waveform recorder log is only supported by the commu-
nications interface. For details about the applied registers and their data structure
refer to page 133.
PEM575_D00016_00_M_XXEN/03.2015 77
Logging
The total capacity of WFR1 and WFR 2 is 32 entries. The valid formats from the
number of samples per cycle and number of cycles are:
16 x 320
32 x 160
64 x 80
128 x 40
256 x 20
When the WFR format is 256 samples per cycle, the "number of pre-fault cycles" can
only be set between 0 and 5.
78 PEM575_D00016_00_M_XXEN/03.2015
Logging
Relay actions
Setup changes
Each event record includes the event classification, the relevant parameter values
and a timestamp in 1 ms resolution.
All event entries can be retrieved via the communications interface. For details
about the applied registers and their data structure refer to page 139.
The event log can be cleared using the buttons on the front panel or via communi-
cations interface.
PEM575_D00016_00_M_XXEN/03.2015 79
Logging
80 PEM575_D00016_00_M_XXEN/03.2015
Power Quality
9. Power Quality
9.1 Fundamentals
PEM575 also provides the fundamental components (related to f(0)) for the meas-
ured quantities listed in the following table.
Fundamental components
UL1(f0) UL2(f0) UL3(f0) Ø ULN (f0)
UL1L2(f0) UL2L3(f0) UL3L1(f0) Ø ULL(f0)
I1(f0) I2(f0) I3(f0) Ø I (f0)
k-factor
rd
all harmonics up to the 63 order
An evaluation of the harmonic components takes place provided that there is a cur-
rent flow of at least 150 mA (current input 1 A) resp. 750 mA (current input 5 A).
Individual harmonic distortions (THD) or individual distortion factors (THF) are de-
termined.
PEM575_D00016_00_M_XXEN/03.2015 81
Power Quality
THD U(k) =
Uk
x 100 % ΣU
k=1
2
k
U1
Ik
Ik THF
I(k)
=
∞
x 100 %
THD I(k) =
I1
x 100 %
ΣI
k=1
k
2
k-factor calculation
h=hmax
Σ (I h)
h=1
h
2
Ih = Effektivwert I der h-ten Harmonischen
k-Faktor = hmax = Nummer größte Harmonische
h=hmax
Σ (I )
2
h = h-te Harmonische
h
h=1
All harmonics parameters are available through the communications interface. For
details about the applied registers and their data structure refer to page 94.
Up to the 31stharmonic the values can also be accessed through the buttons on the
front panel.
The following parameters are supported:
L1 L2 L3
THD THD THD
TEHD TEHD TEHD
82 PEM575_D00016_00_M_XXEN/03.2015
Power Quality
L1 L2 L3
THD THD THD
TEHD TEHD TEHD
TOHD TOHD TOHD
Harmonics, k-factor k-factor k-factor
current
2nd harmonic 2nd harmonic 2nd harmonic
… … …
63rd harmonic 63rdharmonic 63rd harmonic
Table9.2: Parameters, harmonic distortion
U - Unom
Spannungsabweichung ΔU = x 100 %
Unom
f - fnom
Frequenzabweichung Δf = x 100 %
fnom
Application:
Register 0072…0075
Table 10.26
PEM575_D00016_00_M_XXEN/03.2015 83
Power Quality
84 PEM575_D00016_00_M_XXEN/03.2015
Power Quality
Event description
Event timestamp
The programming of the e-mail is only supported via the communications inter-
face. The following set-up parameters are supported:
* Factory setting
PEM575_D00016_00_M_XXEN/03.2015 85
Power Quality
86 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
This chapter provides a complete description of the Modbus register (protocol ver-
sion 6.0) for the PEM575 series to facilitate access to information. In general, the
registers are implemented as Modbus Read Only Registers (RO = read only). with
the exception of the DO control registers, which are implemented as Write Only
Registers (WO = write only).
The PEM575 supports the 4-digit addressing scheme and the following Modbus
functions.
1. Holding register for reading values
(Read Holding Register; function code 0x03)
2. Register for DO status setup
(Force Single Coil; function code 0x05)
3. Register for device programming
(Preset Multiple Registers; function code 0x10)
4. Read general reference
(Read General Reference; function code 0x14)
For a complete Modbus protocol specification, visit
http://www.modbus.org.
energy log
PEM575_D00016_00_M_XXEN/03.2015 87
Modbus Register Map
0002 RO 1) Float V
UL2
88 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
0042 RO 1) Float VA
SL2
PEM575_D00016_00_M_XXEN/03.2015 89
Modbus Register Map
0086 RO 4) UINT16
Status digital outputs
0087 RO Alarm 5) UINT32
0089 RO 6) UINT32
SOE Pointer
0091 RO 7) UINT32
PQ Log Pointer
0093 RO 8) UINT32
WFR1 Log Pointer
0095 RO 8) UINT32
WFR2 Log Pointer
0097 RO 9) UINT32
Energy Log Pointer
0099 RO 10) UINT32
DR1 Pointer (highspeed)
0101 RO DR2 Pointer (highspeed)10) UINT32
90 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 91
Modbus Register Map
6)
The SOE pointer points to the last entry added. The event log can store up to 512 events. It
works like a ring buffer according to the FIFO principle: The 513rd value overwrites the first
value, the 514th the second one and so on. The event log can be reset in the setup parameter
menu (see page 47).
7)
Der PQ log pointer points to the last value added. The PQ log can store up to 1000 events. It
works like a ring buffer according to the FIFO principle: The 1001st value overwrites the first
value, the 1002nd the second one and so on. A reset of the PQ log can be carried out in the
set-up parameters (see page 47).
8)
The PEM575 utilises two waveform recorders (WFR). Each WFR has its own pointer that indi-
cates the most recently added entry in each case. The two WFR together can store up to 32
events. It works like a ring buffer according to the FIFO principle: the 33rd entry overwrites
the first value, the 34th the second and so on. The WFR log can be reset via the communica-
tions interface.
9)
The range of the Energy Log Pointer can be between 0 and 0xFFFFFFFF. As soon as the
maximum value is reached, it starts again with 0. The Energy Log can always be reset via the
communications interface.
10)
The PEM575 provides 16 data recorders (DR1…DR16). Each DR has its own pointer that
points to the last entry in each case. Each DR can be reset via the communications interface.
11)
The total memory size of the PEM575 is 4 MB (4096 kB).
Used memory = 3936 kB–Available memory.
92 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
Note:
After reaching the maximum value of 999.999.999 kWh/kvarh/kVAh, the measure-
ment starts again with 0.
PEM575_D00016_00_M_XXEN/03.2015 93
Modbus Register Map
94 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
Table 10.6Notes:
1)
Only when the wiring mode is WYE.
2)
Only when the wiring mode is DELTA.
3) Only if the device is equipped with the I4 input, otherwise it is reserved.
PEM575_D00016_00_M_XXEN/03.2015 95
Modbus Register Map
96 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
… RO … UINT16 x 10,000
PEM575_D00016_00_M_XXEN/03.2015 97
Modbus Register Map
0934 RO 1) Float V
UL3
0936 RO Ø ULN 1) Float V
0938 RO UL1L2 Float V
0940 RO UL2L3 Float V
0942 RO UL3L1 Float V
0944 RO Ø ULL Float V
0946 RO I1 Float A
0948 RO I2 Float A
0950 RO I3 Float A
0952 RO ØI Float A
0954 RO I4 2) Float A
or reserved
0956 RO PL1 1) Float W
0976 RO 1) Float VA
SL3
0978 RO Sges Float VA
98 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
10.7 Demand
10.7.1 Present demand
PEM575_D00016_00_M_XXEN/03.2015 99
Modbus Register Map
100 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 101
Modbus Register Map
102 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 103
Modbus Register Map
104 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 105
Modbus Register Map
106 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 107
Modbus Register Map
108 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 109
Modbus Register Map
1) Register 2372…2377 are valid only if the device is equipped with the I4 input, otherwise it is
reserved.
110 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
1) Register 2672…2677 are valid only if the device is equipped with the I4 input, otherwise it is
reserved.
PEM575_D00016_00_M_XXEN/03.2015 111
Modbus Register Map
112 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
1) Register 2972…2977 are valid only if the device is equipped with the I4 input, otherwise it is
reserved.
PEM575_D00016_00_M_XXEN/03.2015 113
Modbus Register Map
1*…6,000
Measuring current transformer (current input 5 A)
6001 RW UINT16
transformation ratio 1*…30,000
(current input 1 A)
Measuring current transformer 1…10,000
6002 RW UINT16
transformation ratio I4 (2*)
0 = WYE*
6003 RW Wiring mode UINT16 1 = DELTA
2 = DEMO
6004 RW Unom UINT16 100*…700 V (ULL)
0 = 50 Hz*
6005 RW fnom UINT16
1 = 60 Hz
0* = Modbus
6006 RW Port 1 protocol (RS-485) UINT16
1 = EGATE
1…247
6007 RW Port 1, device address (RS-485) UINT16
(100*)
0 = 1200
1 = 2400
2 = 4800
6008 RW Port 1, baud rate (RS-485) UINT16
3 = 9600*
4 = 19200
5 = 38,400
0 = 8N2; 1 = 8O1
6009 RW Port 1, parity (RS-485) UINT16 2 = 8E1* ; 3 = 8N1
4 = 8O2 ; 5 = 8E2
6010…6012 Reserved
192.168.8.97*
Contents of register
6013 RW IP address UINT32
for factory setting:
0xC0A80861
114 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 115
Modbus Register Map
116 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 117
Modbus Register Map
Table 10.21Notes:
Register 6000 and 6001
Current input 5 A: Transformation ratio current x transformation ratio voltage < 1,000,000
Current input 1 A: Transformation ratio current x transformation ratio voltage < 5,000,000
Register 6078 is disabled if not equipped with an Ethernet port
118 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 119
Modbus Register Map
Register 6142: The string register specifies the destination address of the alarm e-mail. This string
may be up to 35 characters long. Add the value "0000" at the end of the string as the string
terminator for the destination address.
Example:
The e-mail address "[email protected]" is coded in hexadecimal form as
0050 0045 004D 0035 0037 0035 0040 0062 0065 006E 0064 0065 0072 002E 0064 0065
0000.
120 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 121
Modbus Register Map
Table10.23: Setpoints
122 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 123
Modbus Register Map
124 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 125
Modbus Register Map
2)
Trigger
The trigger specifies what action the setpoint will take when it becomes active.
8 DR5 19 DR16
9 DR6 20 WFR1
10 DR7 21 WFR2
11 DR8 22 Alarm e-mail
126 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 127
Modbus Register Map
128 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 129
Modbus Register Map
130 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 131
Modbus Register Map
132 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 133
Modbus Register Map
The waveform recorder data contains the values of the secondary side. The voltage
data returned is 10 times of the actual secondary voltage and the current data is
1,000 times of the actual secondary current. The voltage and current values of the
primary side are calculated as follows:
Uprimary = Usecondary x voltage transformer transformation ratio/10
Iprimary = Isecondary x CT transformation ratio/1,000
134 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 135
Modbus Register Map
136 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 137
Modbus Register Map
10.16 PQ log
Range/
Offset Property Description Format
options
+0 RO Reserved UINT16
RO HiWord: Classification
+1
RO LoWord: sub classification 1)
0…99
RO HiWord: Year (year –
+2 UINT16 2000)
138 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
3 Transient event
PEM575_D00016_00_M_XXEN/03.2015 139
Modbus Register Map
140 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 141
Modbus Register Map
Event value
Event Event sub
Unit Description
classification classification
Option
1 DO 1 close/open by communica-
1/0
tions interface
2 DO2 close/open by communica-
1/0
tions interface
3 DO3 close/open by communica-
1/0
tions interface
4 1/0 DO1 close/open by setpoint
5 1/0 DO2 close/open by setpoint
6 1/0 DO3 close/open by setpoint
2
7 DO1 close/open by undervoltage/
1/0
overvoltage
8 DO2 close/open by undervoltage/
1/0
overvoltage
9 DO3 close/open by undervoltage/
1/0
overvoltage
10 1/0 DO1 close/open by transient event
11 1/0 DO2 close/open by transient event
12 1/0 DO3 close/open by transient event
1 Trigger value x 100 >-Setpoint ULN exceeded
2 Trigger value x 100 >-Setpoint ULL exceeded
3 Trigger value x 1000 >-Setpoint I exceeded
3 4 Trigger value x 1000 >-Setpoint I4 exceeded
5 Trigger value x 100 >-Setpoint Δ f exceeded
6 Trigger value >-Setpoint Pges exceeded
7 Trigger value >-Setpoint Qges exceeded
142 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
Event value
Event Event sub
Unit Description
classification classification
Option
8 Trigger value x 1000 >-Setpoint λges exceeded
9 1 Close setpoint DI1 active
10 1 Close setpoint DI2 active
11 1 Close setpoint DI3 active
12 1 Close setpoint DI4 active
13 1 Close setpoint DI5 active
14 1 Close setpoint DI6 active
15 Reserved
16 Trigger value >-Demand setpoint Pges exceeded
17 Trigger value >-Demand setpoint Qges exceeded
18 Trigger value x 1000 >Demand setpoint λges exceeded
19 Trigger value >-Predicted setpoint Pges exceeded
PEM575_D00016_00_M_XXEN/03.2015 143
Modbus Register Map
Event value
Event Event sub
Unit Description
classification classification
Option
31 1 >-Phase reversal setpoint exceeded
32
33
34
35
36
37
38
39
40
41
Reserved
42
43
44
45
46 Return value x 100 >-Setpoint ULN return
47 Return value x 100 >-Setpoint ULL return
48 Return value x 1000 >-Setpoint I return
49 Return value x 1000 >-Setpoint I4 return
50 Return value x 100 >-Setpoint Δ f return
51 Return value >-Setpoint Pges return
52 Return value >-Setpoint Qges return
144 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
Event value
Event Event sub
Unit Description
classification classification
Option
66 Return value x 1000 >-Predicted setpoint λges return
67 Return value x 100 >-Setpoint THDU return
68 Return value x 100 >-TOHDU setpoint return
69 Return value x 100 >-Setpoint TEHDU return
70 Return value x 100 >-Setpoint THDI return
71 Return value x 100 >-Setpoint TOHDI return
72 Return value x 100 >-Setpoint TEHDI return
73 >-Voltage unbalance setpoint return
Return value x 10
3 79
80
81
82
83
84
85
Reserved
86
87
88
89
90
PEM575_D00016_00_M_XXEN/03.2015 145
Modbus Register Map
Event value
Event Event sub
Unit Description
classification classification
Option
102 1 DI4 open setpoint active
103 1 DI5 open setpoint active
104 1 DI6 open setpoint active
105 Reserved
106 Trigger value Under <-Setpoint demand Pges
107 Trigger value Under <-Setpoint demand Qges
108 Trigger value x 1000 <-Under λges demand setpoint
109 Trigger value <-Under Pges predicted setpoint
110 Trigger value <-Under Qges predicted setpoint
111 Trigger value x 1000 <-Under λges predicted setpoint
112 Trigger value x 100 Under <-Setpoint THDU
3 113 Trigger value x 100 Under <-Setpoint TOHDU
114 Trigger value x 100 Under <-Setpoint TEHDU
115 Trigger value x 100 Under <-Setpoint THDI
116 Trigger value x 100 Under <-Setpoint TOHDI
117 Trigger value x 100 Under <-Setpoint TEHDI
118 Trigger value x 10 <-Under voltage unbalance setpoint
119 Trigger value x 10 <-Under current unbalance setpoint
120 Trigger value x 100 <-Under voltage deviation setpoint
121 1 <-Under phase reversal setpoint
122
123
124
125
126
127
128
129
130
Reserved
131
132
133
134
135
146 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
Event value
Event Event sub
Unit Description
classification classification
Option
136 Return value x 100 <-Setpoint ULN return
137 Return value x 100 <-Setpoint ULL return
138 Return value x 1000 <-Setpoint I return
139 Return value x 1000 <- I4 setpoint return
140 Return value x 100 <- Δ f setpoint return
141 Return value <-Setpoint Pges return
142 Return value <-Setpoint Qges return
143 Return value x 1000 <-Setpoint λges return
144 1 DI1 open setpoint return
145 1 DI2 open setpoint return
146 1 DI3 open setpoint return
147 1 DI4 open setpoint return
PEM575_D00016_00_M_XXEN/03.2015 147
Modbus Register Map
Event value
Event Event sub
Unit Description
classification classification
Option
159 Return value x 100 <-Setpoint TEHDU return
160 Return value x 100 <-Setpoint THDI return
161 Return value x 100 <-Setpoint TOHDI return
162 Return value x 100 <-Setpoint TEHDI return
3
163 <-Voltage unbalance setpoint return
Return value x 10
148 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
Event value
Event Event sub
Unit Description
classification classification
Option
8 Energy values cleared via device but-
0
tons
9 0 Data recorder cleared via front panel
10 Waveform recording cleared via
0
front panel
11 0 Energy log cleared via front panel
12 Max/Min value log of this month
0
cleared via device buttons
13 Peak demand of this month cleared
0
via device buttons
14 Setup changed via communications
0
interface
15 DI counter cleared via communica-
0
tions interface
16 Event log cleared via communica-
5 0
tions interface
17 PQ log cleared via communications
0
interface
18 Energy values cleared via communi-
0
cations interface
19 Data recorder cleared via communi-
0
cations interface
20 Waveform recording cleared via
0
communications interface
21 Energy log cleared via communica-
0
tions interface
22 Max/Min value log of this month
0 cleared via communications inter-
face
23 Peak demand of this month cleared
0
via communications interface
PEM575_D00016_00_M_XXEN/03.2015 149
Modbus Register Map
Event value
Event Event sub
Unit Description
classification classification
Option
1 Waveform recording triggered by
0
communications interface
2 Waveform recording triggered by
Setpoint 1…24
setpoint
3 Waveform recording triggered by
0
undervoltage/overvoltage
4 Data recorder (standard) triggered
Setpoint 1…24
by setpoint
5 Data recorder (highspeed) triggered
Setpoint 1…24
by setpoint
6 Data recorder (standard) triggered
0
by undervoltage/overvoltage
6 7 Data recorder (highspeed) triggered
0
by undervoltage/overvoltage
8 Setpoint 1…24 Alarm e-mail triggered by setpoint
9 Alarm e-mail triggered by
0
undervoltage/overvoltage
10 Waveform recording triggered by
0
transient event
11 Data recorder (standard) triggered
0
by transient event
12 Data recorder (highspeed) triggered
0
by transient event
13 Alarm e-mail triggered by transient
0
event
150 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
If all the registers 9000…9004 are set, both timestamp registers will be updated to
reflect the new time specified in the UNIX time register set. Time specified in the
first display format will be ignored.
Optionally, the register 9003 displays milliseconds. When broadcasting time, the
function code has to be set to 0x10 (Preset Multiple Register). Incorrect date or time
values will be rejected by the universal measuring device.
Register Property Description Format Note
Year and HiWord: Year - 2000
9000 RW UINT16
month LoWord: Month (1…12)
Day and HiWord: day (1…31) LoWord: Hour
9001 RW UINT16
Hour (0…23)
Minute and HiWord: minute (0…59)
9002 RW UINT16
second LoWord: Second (0…59)
9003 RW Millisecond UINT16 0…999
Time in seconds elapsed since Jan-
9004 RW UNIX time UINT32 uary 01, 1970 (00:00:00 h)
(0…4102444799)
PEM575_D00016_00_M_XXEN/03.2015 151
Modbus Register Map
Each command to be executed sent to an output not being activated before, will
be ignored by the PEM575 and returned as an exception code 0x04.
152 PEM575_D00016_00_M_XXEN/03.2015
Modbus Register Map
PEM575_D00016_00_M_XXEN/03.2015 153
Modbus Register Map
154 PEM575_D00016_00_M_XXEN/03.2015
Technical data
PEM575_D00016_00_M_XXEN/03.2015 155
Technical data
156 PEM575_D00016_00_M_XXEN/03.2015
Technical data
PEM575_D00016_00_M_XXEN/03.2015 157
Technical data
158 PEM575_D00016_00_M_XXEN/03.2015
INDEX
A Description of function 17
Apparent power, calculation 48 Device features 15
Application example 17 Digital inputs 25, 51
Area of application 15 Digital output 26
- Modbus control 151
Digital outputs 51
B
Dimension diagram 19
Back-up fuses 21 Display 31, 33
Button Display mode
- "ENERGY" 41 - Data display 34
- "HARMONICS" 29, 39 - Standard display 34
- "POWER" 29 DOx control 151
- "V/I" 29, 35
E
C
Energy log 76
Calculation individual harmonic distortion 49 Energy pulsing
Commissioning 27 - Display 52
Configuration example - enable/disable 46
- 50 - LED indication 34
Connection Event
- Three-phase 4-wire system 23 - Classification 141
Connection diagram - Logging 79
- Connection via voltage transformers 25 - Modbus register 139
- Three-phase 3-wire system 24
- Three-phase 3-wire systems 25
F
- Three-phase 4-wire system 23
Connection of measuring current transformers 21 Front panel mounting 20
Connection via voltage transformers 25 Front view 18
Control
- Digital outputs 151 H
Harmonics 39, 81
D How to use this manual 9
Demand 53
Demand display 33 I
Demand period 54 Icons 9
PEM575_D00016_00_M_XXEN/03.2015 159
INDEX
K O
k-factor 39 Operating elements 29
Output, digital 26
L
LC display P
- Power and current demands 33 Phase angle
- Standard display areas 31– 32 - Current 53
- testing 30 - Voltage 53
LED indication 34 Power factor rules 48
Logging Power Quality 81, 94
- data recorder 63 Pulse counter 94
- Event 79
- Max and Min values 61 R
- Peak demand 61
Rear view 18
- Power Quality 79
- Waveform recording 77
Logic modules 59 S
Safety instructions 14, 19, 21
M Service 10
Set demand period 54
Measured quantities for data recorders 64
Setpoint trigger 58
measuring current transformers 21
Setup
Modbus
- Setting options 44– 48
- Basic measurements 88
Sliding Window 54
- Clear/reset 120
SOE log
- Energy measurement 92
- Data structure 107
- Event log 139
- Modbus 139
- High-speed measurement 98
Standard display areas 31
- Logic module 126
Start
- Max/Min log 108
- Function of the buttons 42
- Measuring device information 152
- Overview diagram menu 43
- Peak demand 106
- SETUP mode 42
- Power Quality (Fundamental) 94
Support 10
- Power Quality (Harmonics) 96
- Register Map 87
- Setpoint setup 122
160 PEM575_D00016_00_M_XXEN/03.2015
INDEX
T
Technical data 155
TEHD 39, 81
Testing LCD 30
THD 39
Time setting 151
Time zones 119
TOHD 39, 81
Total harmonic distortion 39
U
Unbalance 83
V
Versions 16
W
Wiring diagram 22
Work activities on electrical installations 13
Workshops 11
PEM575_D00016_00_M_XXEN/03.2015 161
INDEX
162 PEM575_D00016_00_M_XXEN/03.2015
Bender GmbH & Co. KG
Londorfer Str. 65 • 35305 Gruenberg • Germany
Postfach 1161 • 35301 Gruenberg • Germany
Tel.: +49 6401 807-0
Fax: +49 6401 807-259
E-Mail: [email protected]
www.bender-de.com