Manual Series 3000 MVD Transmitters Controllers Micro Motion en 62818

Download as pdf or txt
Download as pdf or txt
You are on page 1of 348

Configuration and Use Manual

20001266, Rev CD
December 2020

Micro Motion™ 3000 MVD Transmitters and


Controllers
Configuration and Use Manual
©2020 The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD
Direct Connect marks are marks of one of the Emerson Automation Solutions family of companies. All other marks are property of
their respective owners.
Contents

Chapter 1 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1


1.1 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 European installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.4 Environmental standards compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.5 Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.6 Communication tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.7 Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.8 Other documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.9 Micro Motion customer service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Chapter 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Replacing an RFT9739 rack-mount transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.4 Model 3350 or Model 3700 safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.5 Environmental requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.6 Ingress protection for Model 3300 controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.7 Frequency input cable length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.8 Model 3350 or Model 3700 display cover orientation (optional) . . . . . . . . . . . . . . . . . 9
2.9 Installing the remote core processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.10 Sensor wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.10.1 Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.10.2 Cable glands in remote core processor with remote
transmitter installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.11 I/O wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.11.1 Terminals and terminal block locations . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.11.2 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.11.3 Installing relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.12 Digital communications wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Chapter 3 Digital Communications Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . 15


3.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 Supported protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.1 Obtaining the components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.2 RS-485 signal converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.3 Bell 202 signal converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3 Setting up RS-485 communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.4 Setting up Bell 202 communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Configuration and Use Manual i


Contents

Chapter 4 Using the Display and Menu System . . . . . . . . . . . . . . . . . . . . . . . 25


4.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.2 Startup display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.3 Menu systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3.1 Accessing management functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.3.2 Shortcuts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.4 Using the function buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.5 Using the cursor control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.5.1 Selecting from a list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.5.2 Changing a variable value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.5.3 Cursor control example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.5.4 Process monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.6 Scientific notation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Chapter 5 Configuring Security and Language . . . . . . . . . . . . . . . . . . . . . . . 33


5.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.2 Security menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.3 Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.3.1 Management menu access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.3.2 Write-protecting the device configuration . . . . . . . . . . . . . . . . . . . . . . . . 34
5.3.3 Controlling process totalizer and process inventory reset . . . . . . . . . . . . 35
5.4 Language menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Chapter 6 Configuring System Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37


6.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.2 System menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.3 System parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.3.1 Alarm severity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Chapter 7 Configuring Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39


7.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.2 Inputs menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.3 Configuring the core processor parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
7.3.1 Enabling and disabling core processor inputs . . . . . . . . . . . . . . . . . . . . . 42
7.3.2 Configuring process variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7.3.3 Sensor calibration data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.3.4 Sensor information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.3.5 Discrete inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.4 Configuring the frequency input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.5 Configuring the discrete inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7.6 Configuring the external inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Chapter 8 Configuring Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61


8.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
8.2 Outputs menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
8.3 Configuring the discrete outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
8.3.1 Polarity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
8.3.2 Source variable assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
8.3.3 Fault indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

ii Micro Motion® Series 3000 MVD Transmitters and Controllers


Contents

8.4 Configuring the milliamp outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66


8.4.1 Milliamp output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
8.4.2 Fault indication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
8.4.3 Process variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.4.4 Calibration span . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.5 Configuring the frequency output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
8.5.1 Frequency = flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
8.5.2 Maximum pulse width . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Chapter 9 Configuring the Petroleum Measurement Application . . . . . . . . . . . 75


9.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.2 API menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.3 About petroleum measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.3.1 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.3.2 CTL derivation methods. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.4 Configuring petroleum measurement parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.4.1 Reference tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.4.2 Temperature data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

Chapter 10 Configuring Discrete Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79


10.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
10.2 Discrete events menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
10.3 About discrete events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
10.4 Discrete event configuration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

Chapter 11 Configuring the Discrete Batch Application . . . . . . . . . . . . . . . . . . 83


11.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
11.2 Discrete batch menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
11.3 Batching configuration overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
11.4 Flow source. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
11.5 Control options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
11.5.1 One-stage versus two-stage batching . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
11.6 Configure presets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
11.6.1 Batch preset examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
11.7 Batch control methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
11.7.1 Special cases in batch control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

Chapter 12 Configuring the Process Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . 93


12.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
12.2 Monitoring menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
12.3 Process monitor screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
12.4 Process monitor variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
12.5 Update period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

Configuration and Use Manual iii


Contents

Chapter 13 Configuring Digital Communications. . . . . . . . . . . . . . . . . . . . . . . 97


13.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
13.2 Digital communication menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
13.3 Configuring RS-485 parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
13.3.1 Configuring HART, Modbus RTU, or Modbus ASCII protocol . . . . . . . . . 99
13.3.2 Configuring printer protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
13.4 Configuring Bell 202 parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
13.4.1 Loop current mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
13.4.2 Burst mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
13.4.3 Communicating with a remote device . . . . . . . . . . . . . . . . . . . . . . . . . . 104
13.5 Configuring device parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

Chapter 14 Configuring Custody Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . 105


14.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
14.2 About custody transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
14.3 Configuration options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
14.4 Configuring custody transfer (NTEP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
14.5 Configuring custody transfer (OIML) and custody transfer (OIML/batch) . . . . . . . . 108
14.6 Setting the security switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
14.6.1 Panel-mount devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
14.6.2 Rack-mount devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
14.6.3 Field-mount devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
14.7 Installing the weights and measures seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

Chapter 15 Ticket Formatting and Printing . . . . . . . . . . . . . . . . . . . . . . . . . . 117


15.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
15.2 Ticket overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
15.3 Standard tickets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
15.3.1 Formatting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
15.3.2 Printing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
15.4 Batch tickets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
15.4.1 Formatting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
15.4.2 Printing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
15.5 Batch (NTEP) tickets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
15.5.1 Formatting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
15.5.2 Printing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
15.6 Transfer (OIML) tickets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
15.6.1 Formatting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
15.6.2 Printing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
15.7 Batch (OIML) tickets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
15.7.1 Formatting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
15.7.2 Printing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131

Chapter 16 Startup Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133


16.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
16.2 Applying power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
16.2.1 Communication methods after power-up. . . . . . . . . . . . . . . . . . . . . . . . 134

iv Micro Motion® Series 3000 MVD Transmitters and Controllers


Contents

16.3 Sensor zero. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134


16.3.1 Zero failure and restoring zero values . . . . . . . . . . . . . . . . . . . . . . . . . . 135
16.3.2 Preparing for sensor zero calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
16.3.3 Performing the sensor zero calibration . . . . . . . . . . . . . . . . . . . . . . . . . 135
16.3.4 Diagnosing sensor zero failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
16.4 Testing the inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
16.4.1 Reading and testing the discrete inputs. . . . . . . . . . . . . . . . . . . . . . . . . 139
16.4.2 Reading and testing the frequency input . . . . . . . . . . . . . . . . . . . . . . . . 139
16.4.3 Reading and testing the pressure and external temperature. . . . . . . . . 139
16.4.4 Setting and testing outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
16.5 Milliamp output trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140

Chapter 17 Operation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143


17.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
17.2 Startup and display test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
17.3 Initial startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
17.4 Process monitor operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
17.5 Using the View menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
17.5.1 Active alarm log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
17.5.2 Process monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
17.5.3 Preset selections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
17.5.4 Batch inventory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
17.5.5 Process totalizers and inventories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
17.5.6 Diagnostic monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
17.5.7 LCD options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
17.5.8 Density curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
17.5.9 Applications list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148

Chapter 18 Operation Mode – Batch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149


18.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
18.2 About discrete batching. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
18.3 Batch process screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
18.3.1 Function buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
18.3.2 Cursor control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
18.4 Batch processing sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
18.5 Special cases in batch processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
18.5.1 Cleaning/purging the tubes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
18.5.2 Ending a batch while flow is present . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
18.6 Batch AOC calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157

Chapter 19 Operation Mode – Custody Transfer . . . . . . . . . . . . . . . . . . . . . . 159


19.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
19.2 Identifying a security breach . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
19.3 Secured versus unsecured . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
19.4 Custody transfer (NTEP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
19.4.1 BOL number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
19.4.2 Executing a custody transfer (NTEP) transaction . . . . . . . . . . . . . . . . . 163
19.4.3 Batch (NTEP) tickets and ticket printing . . . . . . . . . . . . . . . . . . . . . . . . 163
19.4.4 General use of Series 3000 device . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
19.4.5 Inventories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164

Configuration and Use Manual v


Contents

19.5 Custody transfer (OIML) and custody transfer (OIML/batch) . . . . . . . . . . . . . . . . . 164


19.5.1 BOL numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
19.5.2 Executing a custody transfer (OIML) transaction . . . . . . . . . . . . . . . . . 164
19.5.3 Executing a custody transfer (OIML/batch) transaction. . . . . . . . . . . . . 165
19.5.4 Transfer (OIML) and batch (OIML) tickets and ticket printing . . . . . . . . 166
19.5.5 Transfer log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
19.5.6 General use of Series 3000 device . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
19.6 Clearing a security breach . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
19.7 Reconfiguring the Series 3000 device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
19.8 Audit trail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
19.8.1 Using the audit trail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171

Chapter 20 Using Totalizers and Inventories . . . . . . . . . . . . . . . . . . . . . . . . 173


20.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
20.2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
20.3 Totalizer management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
20.4 Process totalizers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
20.5 Process inventories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
20.6 Batch inventories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176

Chapter 21 Measurement Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179


21.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
21.2 Meter verification, meter validation, and calibration . . . . . . . . . . . . . . . . . . . . . . . . 179
21.2.1 Meter verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
21.2.2 Meter validation and meter factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
21.2.3 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
21.2.4 Comparison and recommendations. . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
21.3 Performing meter verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
21.3.1 Preparing for the meter verification test. . . . . . . . . . . . . . . . . . . . . . . . . 183
21.3.2 Running the meter verification test, original version . . . . . . . . . . . . . . . 184
21.3.3 Running Smart Meter Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
21.3.4 Reading and interpreting meter verification test results . . . . . . . . . . . . 190
21.3.5 Setting up automatic or remote execution of the
meter verification test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
21.4 Performing meter validation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
21.5 Performing density calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
21.5.1 Preparing for density calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
21.5.2 Density calibration procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
21.6 Performing temperature calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201

Chapter 22 Diagnostics and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . 203


22.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
22.2 Checking process variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
22.3 Meter fingerprinting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
22.4 Sensor simulation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
22.5 Updates, upgrades, and master resets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
22.6 Alarm types and handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
22.6.1 Alarm severity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
22.6.2 Fault timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
22.6.3 Alarm categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
22.6.4 Alarm occurrences and logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
22.6.5 Help system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211

vi Micro Motion® Series 3000 MVD Transmitters and Controllers


Contents

22.7 Alarm listings by category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212


22.7.1 Electronics alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
22.7.2 Sensor alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
22.7.3 Process alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
22.7.4 Configuration alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
22.8 Restoring a working configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
22.9 A009/A026 alarms on Model 3300 or Model 3500 panel-mount. . . . . . . . . . . . . . . 224
22.10 I/O problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
22.11 Diagnosing wiring problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
22.11.1 Checking the power supply wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
22.11.2 Checking the sensor-to-transmitter wiring . . . . . . . . . . . . . . . . . . . . . . . 228
22.11.3 Checking grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
22.11.4 Checking the HART communication loop . . . . . . . . . . . . . . . . . . . . . . . 228
22.11.5 Checking for RF interference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
22.11.6 Checking the output wiring and receiving device. . . . . . . . . . . . . . . . . . 229
22.11.7 Checking the Loop Current Mode parameter. . . . . . . . . . . . . . . . . . . . . 229
22.12 Checking the sensor tubes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
22.13 Checking the flow measurement unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
22.14 Checking the calibration span . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
22.15 Checking the frequency output scale and method . . . . . . . . . . . . . . . . . . . . . . . . . 229
22.16 Checking the characterization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
22.17 Checking the calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
22.18 Checking the test points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
22.18.1 Obtaining the test points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
22.18.2 Evaluating the test points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
22.18.3 Excessive drive gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
22.18.4 Erratic drive gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
22.18.5 Low pickoff voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
22.19 Checking the core processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
22.19.1 Checking the core processor LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
22.19.2 Core processor resistance test (standard core processor only) . . . . . . 234
22.20 Checking sensor coils and RTD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
22.20.1 Remote core processor with remote transmitter installation . . . . . . . . . 235
22.20.2 4-wire remote installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236

Appendix A Specifications – Model 3300 and Model 3500. . . . . . . . . . . . . . . . 241


A.1 Housing and mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
A.1.1 Panel-mount. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
A.1.2 Rack-mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
A.2 Interface/display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
A.3 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
A.4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
A.5 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
A.5.1 Panel-mount. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
A.5.2 Rack-mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
A.6 Inputs and outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
A.6.1 Intrinsically safe input signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
A.6.2 Non-intrinsically safe input signals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
A.6.3 Non-intrinsically safe output signals. . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
A.6.4 Digital communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
A.7 Power supply options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
A.7.1 Model 3300 controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
A.7.2 Model 3500 transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
A.8 Environmental limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249

Configuration and Use Manual vii


Contents

A.9 Environmental effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249


A.10 Hazardous area classifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
A.10.1 ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
A.10.2 UL and CSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
A.11 Performance specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
A.12 Cleaning instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249

Appendix B Specifications – Model 3350 and Model 3700 . . . . . . . . . . . . . . . 251


B.1 Compartmentalized housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
B.2 Interface/display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
B.3 Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
B.4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
B.5 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
B.6 Inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
B.6.1 Intrinsically safe input signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
B.6.2 Non-intrinsically safe input signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
B.6.3 Non-intrinsically safe output signals . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
B.6.4 Digital communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
B.7 Power supply options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
B.8 Environmental limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
B.9 Environmental effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
B.10 Hazardous area classifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
B.10.1 ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
B.10.2 UL and CSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
B.11 Performance specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
B.12 Cleaning instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258

Appendix C Specifications – Model 3100 . . . . . . . . . . . . . . . . . . . . . . . . . . . 259


C.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
C.2 Relay packs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
C.3 Hazardous area classifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
C.3.1 ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
C.3.2 UL and CSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259

Appendix D Installing Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261


D.1 About this appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
D.2 Relay types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
D.2.1 Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
D.3 Hazardous area installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
D.3.1 Model 3100 relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
D.3.2 User-supplied relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
D.4 Replacing relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
D.5 Using relays with the Series 3000 device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
D.5.1 Series 3000 discrete outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
D.6 Installing the Model 3100 relay module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
D.7 Installing user-supplied relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269

Appendix E Default Values and Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273


E.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
E.2 Most frequently used defaults and ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273

viii Micro Motion® Series 3000 MVD Transmitters and Controllers


Contents

Appendix F Series 3000 Menu Flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . 277


F.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
F.2 Process monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
F.3 Menu access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278
F.4 View menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
F.5 Management menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281

Appendix G ProLink II and Pocket ProLink . . . . . . . . . . . . . . . . . . . . . . . . . . 289


G.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
G.2 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
G.3 ProLink II configuration upload/download . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
G.4 Connecting from a PC to a Series 3000 device . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
G.5 ProLink II menu flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291

Appendix H 375 Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297


H.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
H.2 DD requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
H.3 Connecting from the 375 Field Communicator to a Series 3000 device . . . . . . . . . 297
H.4 Communicator menu flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297

Appendix I Sample Tickets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305


I.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
I.2 Standard tickets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
I.3 Batch tickets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
I.4 Batch (NTEP) tickets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
I.5 Transfer (OIML) tickets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
I.6 Batch (OIML) tickets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313

Appendix J Label Maintenance and Replacement . . . . . . . . . . . . . . . . . . . . . 315


J.1 Maintaining and replacing labels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
J.2 Labels on the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315

Appendix K Return Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317


K.1 General guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
K.2 New and unused equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
K.3 Used equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317

Appendix L NE 53 History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319


L.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
L.2 Software change history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 319

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323

Configuration and Use Manual ix


x Micro Motion® Series 3000 MVD Transmitters and Controllers
Chapter 1

Before You Begin


Before You Begin

1.1 About this manual


This manual explains how to install, configure, and use the following Micro Motion® Series 3000
devices:
• Model 3500 or Model 3700 transmitter
• Model 3300 or Model 3350 controller
This manual also discusses the following optional applications:

Installation
• Discrete batching
• Petroleum measurement (API feature)
• Custody transfer
This manual does not discuss the Series 3000 Net Oil Computer. For information on this product and
application, see the Series 3000 Net Oil Computer Manual, available on the Micro Motion web site
(www.micromotion.com).
This manual does not discuss the enhanced density application. For information on enhanced density,
see the manual entitled Enhanced Density Application: Theory, Configuration, and Use, available on
the Micro Motion web site (www.micromotion.com).

Digital Communications Setup


This manual does not discuss the Marine Bunker Transfer Package. For information on this product
and application, see the manual entitled Series 3000 Transmitters: Marine Bunker Transfer Package
Supplement, available on the Micro Motion web site (www.micromotion.com).

1.2 Safety
Safety messages are provided throughout this manual to protect personnel and equipment. Read each
safety message carefully before proceeding to the next step.

WARNING
Improper installation in a hazardous area can cause an explosion.

For information about hazardous applications, refer to Micro Motion hazardous


area installation instructions, shipped with the Series 3000 device or available from
Using the Display

the Micro Motion web site.

Configuration and Use Manual 1


Before You Begin

CAUTION
Improper installation could cause measurement error or flowmeter failure.

Follow all instructions to ensure Series 3000 device will operate correctly.

1.3 European installations


This Micro Motion product complies with all applicable European directives when properly installed
in accordance with the instructions in this manual. Refer to the EC declaration of conformity for
directives that apply to this product.
The EC declaration of conformity, with all applicable European directives, and the complete ATEX
Installation Drawings and Instructions are available on the internet at www.micromotion.com/atex
or through your local Micro Motion support center.

1.4 Environmental standards compliance


To comply with EU Battery Directive 2006/66/EC, this device has been designed for safe removal of
the batteries at end of life by a waste treatment facility.

1.5 Terminology
The following terms are used in this manual:
• Series 3000 – refers to all Model 3300, 3350, 3500, or 3700 devices.
• MVD – Multi Variable Digital, Micro Motion’s advanced method of analyzing and reporting
process variables.
• Application – a specific use of the flowmeter technology, and the specialized software or
hardware required for implementation. Sample applications include enhanced density,
batching, and custody transfer.
• Platform – refers to any component that can run an application. The component may be a
transmitter or a controller (see below).
• Sensor – provides measurement functions.
• Core processor – refers to the component which provides memory and preprocessing
functions on process variable data received from the sensor. There are two versions: the
standard core processor and the enhanced core processor. To check your core processor type,
use the Applications List (see Section 17.5.9).
• Transmitter – refers to the component that accepts process variable data from the core
processor, performs additional processing, and transmits the processed data to a remote device.
In this manual, the Model 3500 and Model 3700 devices are transmitters.
• Controller – refers to the Model 3300 and Model 3350 devices. Controllers receive processed
data from a transmitter such as an IFT9701, use these data in an application that is installed on
the device, and send the results to a remote device. Controllers are not connected to a sensor or
core processor.

2 Micro Motion® Series 3000 MVD Transmitters and Controllers


Before You Begin

1.6 Communication tools

Before You Begin


You can communicate with a Series 3000 device using any of the following communication tools:
• The local display
• ProLink II v2.5 and higher (ProLink II v2.9 or higher recommended), or Pocket ProLink v1.3
and higher
• 375 Field Communicator with the appropriate DD: Micro Motion 3000 Mass flo v7 DD v2 or
higher
This manual focuses on the use of the local display. Detailed menu flowcharts for the local display are
provided in Appendix F.
For information on using ProLink II or the Communicator with a Series 3000 device, see Appendix G
or Appendix H. These appendices also provide flowcharts for the most commonly used menus and
procedures.

1.7 Using this manual

Installation
If the Marine Bunker Transfer Package is installed, use the manual entitled Series 3000 Transmitters:
Marine Bunker Transfer Package Supplement as your first guide to installation, configuration, and
use.
If the Marine Bunker Transfer Package is not installed, follow the general task sequence described
below to install, configure, and use the Series 3000 device.
1. Install the Series 3000 device (Chapter 2).
2. Set up digital communications (Chapter 3).
3. Learn to use the display and menu system (Chapter 4).
4. Configure the platform (Chapters 5 through 15).

Digital Communications Setup


Failure to perform configuration tasks in the proper sequence could result in an incomplete
configuration. Perform the configuration procedures in this order:
a. Configure security and language (Chapter 5).
b. Configure system data (Chapter 6).
c. Configure inputs (Chapter 7).
d. Configure petroleum measurement parameters, if the petroleum measurement application
(API feature) is installed (see Chapter 9), or enhanced density parameters, if the enhanced
density application is installed (see the enhanced density manual, available on the Micro
Motion web site).
Note: The Series 3000 device does not support simultaneous use of the petroleum measurement
application and the enhanced density application. If you ordered either of these applications, it
should already be installed on your Series 3000 device, but not configured or enabled.
e. Configure discrete events (Chapter 10).
f. Configure the discrete batch application, if it is present (Chapter 11).
Using the Display

g. Configure outputs (Chapter 8).


h. Configure the process monitor (Chapter 12).
i. Configure digital communications (Chapter 13).
j. Configure custody transfer (Chapter 14).
k. Configure ticket formatting and ticket printing (Chapter 15).

Configuration and Use Manual 3


Before You Begin

5. Perform startup procedures (Chapter 16).


6. Learn to use the Series 3000 device in operation mode (Chapters 17 through 19).
7. Learn how to view, start and stop, and reset totalizers (Chapter 20).
8. Establish a meter verification baseline, and calibrate the Series 3000 device, if required
(Chapter 21).
9. Learn how to respond to alarms (Chapter 22).

1.8 Other documentation


See Table 1-1 for a list of other manuals that may be useful or required to install, configure, or operate
the Series 3000 device.

Table 1-1 Additional documentation for Series 3000 devices

Topic Manual / QRG title Location


Device installation: Model 3500 Transmitter (MVD) or • Micro Motion documentation CD
• Model 3300 panel-mount Model 3300 Peripheral: Installation • Micro Motion web site
• Model 3500 panel-mount Instructions for Panel-Mount (Quick
Reference Guide)
Device installation: Model 3500 Transmitter (MVD) or • Micro Motion documentation CD
• Model 3300 rack-mount Model 3300 Peripheral: • Micro Motion web site
• Model 3500 rack-mount Installation Instructions for Rack-Mount
(Quick Reference Guide)
Device installation: Model 3700 Transmitter (MVD) or • Micro Motion documentation CD
• Model 3350 field-mount Model 3350 Peripheral: • Micro Motion web site
• Model 3700 field-mount Installation Instructions for Field-Mount
(Quick Reference Guide)
Sensor installation Varies • Micro Motion documentation CD
• Micro Motion web site
Hazardous area installation Varies • Micro Motion documentation CD
• Micro Motion web site
Enhanced density application Enhanced Density Application: Theory, • Micro Motion documentation CD
Configuration, and Use • Micro Motion web site
Marine Bunker Transfer Series 3000 Transmitters: Marine Bunker • Micro Motion documentation CD
Package Transfer Package Supplement • Micro Motion web site
Using ProLink II with the Using ProLink II Software with Micro Motion • ProLink II installation media
Series 3000 device Transmitters • Micro Motion documentation CD
• Micro Motion web site

4 Micro Motion® Series 3000 MVD Transmitters and Controllers


Before You Begin

1.9 Micro Motion customer service

Before You Begin


For customer service, phone the support center nearest you:
• In the U.S.A., phone 800-522-MASS (800-522-6277) (toll-free)
• In Canada and Latin America, phone +1 303-527-5200
• In Asia:
- In Japan, phone 3 5769-6803
- In other locations, phone +65 6777-8211 (Singapore)
• In Europe:
- In the U.K., phone 0870 240 1978 (toll-free)
- In other locations, phone +31 (0) 318 495 555 (The Netherlands)
Customers outside the U.S.A. can also email Micro Motion customer service at
[email protected].

Installation
Digital Communications Setup
Using the Display

Configuration and Use Manual 5


6 Micro Motion® Series 3000 MVD Transmitters and Controllers
Chapter 2

Before You Begin


Installation

2.1 Overview
This chapter provides supplemental installation information for all Series 3000 devices.

2.2 Installation procedure


To install your Series 3000 device:

Installation
1. Obtain the appropriate Quick Reference Guide (QRG), as listed in Table 2-1.
2. Review the specifications for your device:
• Model 3300 or Model 3500 – see Appendix A
• Model 3350 or Model 3700 – see Appendix B
3. Review the supplemental information provided in this chapter.
4. Follow the installation instructions in the QRG, making all applicable changes to your
installation procedure.

Table 2-1 Series 3000 installation QRGs

Digital Communications Setup


Series 3000 device Quick Reference Guide
Model 3300 controller (panel-mount) Model 3500 Transmitter (MVD) or Model 3300 Peripheral:
Model 3500 transmitter (panel-mount) Installation Instructions for Panel-Mount
Model 3300 controller (rack-mount) Model 3500 Transmitter (MVD) or Model 3300 Peripheral:
Model 3500 transmitter (rack-mount) Installation Instructions for Rack-Mount
Model 3350 controller (field-mount) Model 3700 Transmitter (MVD) or Model 3350 Peripheral:
Model 3700 transmitter (field-mount) Installation Instructions for Field-Mount

2.3 Replacing an RFT9739 rack-mount transmitter


Micro Motion can provide a special installation kit for installing a Model 3500 transmitter in a rack as
a replacement for an RFT9739 rack-mount transmitter. Part number 3500EXTENDEDM extends the
housing of the Series 3000 device to fit an RFT9739 rack. Contact Micro Motion for information
about obtaining this kit.
Using the Display

Configuration and Use Manual 7


Installation

2.4 Model 3350 or Model 3700 safety precautions

WARNING
Explosion Hazard.

Do not open wiring compartments when an explosive gas atmosphere is


present.

Do not remove the compartment covers in an explosive atmosphere within three


minutes after power is disconnected.

WARNING
Using a dry cloth to clean the display cover can cause static discharge,
which could result in an explosion in an explosive atmosphere.

To prevent an explosion, use a clean, damp cloth to clean the display cover in an
explosive atmosphere.

2.5 Environmental requirements


Note: This section applies to all Series 3000 devices.
In addition to the temperature requirements described in the QRG, the following environmental
requirements apply:
• Humidity: 5 to 95% relative humidity, non-condensing at 140 °F (60 °C)
• Vibration: Meets IEC 68.2.6, endurance sweep, 5 to 2000 Hz, 50 sweep cycles at 1.0 g
If possible, install the Series 3000 device in a location that will prevent the heating effects of direct
exposure to sunlight.

2.6 Ingress protection for Model 3300 controller


Note: This section applies only to Model 3300 controllers.
If you are installing the Model 3300 in a panel cutout, it may be installed outdoors, if it is installed in
a panel providing a degree of ingress protection IP 65 according to EN 50529 (IEC 529).
If you are installing the Model 3300 in a rack, it should be installed in a rack providing a degree of
ingress protection NEMA 4X according to EN 50529 (IEC 529).

2.7 Frequency input cable length


Note: This section applies only to Model 3300 or Model 3350 controllers.
The maximum length of the frequency input cable has been increased. The maximum length is now
1000 feet (300 meters) of typical 18 AWG (0,80 mm2) instrumentation cable, rather than 500 feet
(150 meters) as documented in the QRGs.

8 Micro Motion® Series 3000 MVD Transmitters and Controllers


Installation

2.8 Model 3350 or Model 3700 display cover orientation (optional)

Before You Begin


Note: This section applies only to Model 3350 or Model 3700 devices.
If desired, you can reposition the display on the Model 3350 or Model 3700 device for easier reading
and use. You can rotate it 90°, 180°, or 270°. To do this, follow the instructions below.

1. Use a flat-head screwdriver to loosen the captive


screws that secure the display cover to the housing.

2. Use a flat-head screwdriver to loosen the captive


screws that secure the back cover to the display cover.

Installation
Take note of which screw attaches the ground wire to
the back cover.

3. Pull up on the pressure relief valve while removing the


back cover. In this picture, the operator’s right hand is
touching the pressure relief valve.

Digital Communications Setup


4. Rotate the display cover to any desired position.

5. Without touching the circuit board, tuck the wiring out


of the way of the circuit board to prevent the wiring
from crimping, then reinstall the back cover.
Using the Display

Configuration and Use Manual 9


Installation

6. Pull up on the pressure relief valve while pressing the


back cover into place. Be sure to attach the ground
wire to the back cover using the correct screw.
Attaching the ground wire to the wrong screw may
result in crimping of the ground wire.

7. Tuck the wiring out of the way of the connectors to


keep the wiring from crimping, then reinstall the
display cover.

2.9 Installing the remote core processor


Note: This section applies only to Model 3500 or Model 3700 devices in remote core processor with
remote transmitter installations.
For dimensions of the remote core processor, see Figure A-4 or Figure B-4.
When mounting the core processor, you can reorient it on the bracket if desired. To do this:
1. Loosen each of the four cap screws (4 mm).
2. Rotate the bracket so that the core processor is oriented as desired.
3. Tighten the cap screws, torquing to 30 to 38 in-lbs (3 to 4 N-m).
Be sure to ground the core processor according to applicable local standards, using either the internal
or external ground screw.

2.10 Sensor wiring


Note: This section applies only to Model 3500 or Model 3700 transmitters.

2.10.1 Cable types


All installation types require 4-wire cable. Micro Motion offers two types of 4-wire cable: shielded
and armored. Both types contain shield drain wires.
User-supplied 4-wire cable must meet the following requirements:
• Twisted pair construction
• The gauge requirements as described in the installation QRG
• The applicable hazardous area requirements, if the device is installed in a hazardous area (see
the ATEX, UL, or CSA documents shipped with the transmitter or available on the Micro
Motion web site)

10 Micro Motion® Series 3000 MVD Transmitters and Controllers


Installation

Remote core processor with remote transmitter installations also require 9-wire cable. Micro Motion
offers three types of 9-wire cable: jacketed, shielded, and armored. Refer to Micro Motion’s 9-Wire

Before You Begin


Flowmeter Cable Preparation and Installation Manual for detailed descriptions of these cable types
and for assistance in selecting the appropriate cable for your installation.

2.10.2 Cable glands in remote core processor with remote transmitter installations
Depending on your transmitter model, several different cable glands may be shipped with the
transmitter and core processor. Refer to Figure 2-1 to identify the cable glands supplied by Micro
Motion. Be sure to use the appropriate cable gland for each component and location.

Figure 2-1 Cable glands supplied by Micro Motion

Transmitter model 3700*****B***** Transmitter model 3700*****C*****

Installation
Cable gland
Transmitter models
1/2˝–14 NPT or M20 x1.5
• 3500**F********
used with 4-wire conduit opening
• 3500**G********
• 3700**F********
• 3700**G********
Cable gland

Digital Communications Setup


3/4˝–14 NPT
used with 9-wire conduit opening

2.11 I/O wiring


Note: This section applies to all Series 3000 devices.

2.11.1 Terminals and terminal block locations


To locate the I/O terminal blocks on your Series 3000 platform, see Figure 2-2. To identify the I/O
terminals, see the appropriate terminal label in Figure 2-3. Using the Display

Configuration and Use Manual 11


Installation

Figure 2-2 I/O terminal locations


Model 3300 or Model 3500 Model 3300 or Model 3500 Model 3350 or Model 3700
panel-mount rack-mount field-mount

Input/output wiring terminals Input/output wiring terminals Input/output wiring terminals

Figure 2-3 I/O terminal labels

Card for Model 3300 or Model 3500 with Label for Model 3300 or Label for Model 3350
screw-type or solder-tail terminals Model 3500 with I/O cables or Model 3700

Note: The terminals labeled Comm 1, Comm 2, and Comm 3 are not for I/O wiring.
These terminals are for Micro Motion internal use only.

12 Micro Motion® Series 3000 MVD Transmitters and Controllers


Installation

2.11.2 Grounding

Before You Begin


For all Series 3000 devices, the shields from the I/O wires should be grounded at a single point.
Ground the shields at the remote device, not at the Series 3000 device.
If you are installing a Model 3300 or Model 3500 panel-mount device with I/O cables, the terminal
block ground is available for continuation of user cable shielding to I/O cable shielding. The cable
connector does not connect the I/O cable shielding to the chassis ground. See Figure 2-4.

Figure 2-4 Shield wiring for I/O cable to field device


Terminal block Model 3300 or Model 3500
Ground shields at single
point only (at the remote
device, not at the
I/O cable
Series 3000 device)

Installation
Cable shields

Chassis
Terminal marked ground

2.11.3 Installing relays


If you will install a relay to connect the Series 3000 device’s discrete outputs to control devices, see
Appendix D for installation instructions.
Specifications for the Model 3100 relay (supplied by Micro Motion) are provided in Appendix C.

Digital Communications Setup


2.12 Digital communications wiring
If you will use digital communications between your Series 3000 device and a remote device (e.g., a
ticket printer, a PLC, a temperature or pressure sensor, or a PC running ProLink II), see Chapter 3 for
wiring instructions.

Using the Display

Configuration and Use Manual 13


14 Micro Motion® Series 3000 MVD Transmitters and Controllers
Chapter 3

Before You Begin


Digital Communications Setup

3.1 About this chapter


This chapter explains how to install wiring for digital communications between the Series 3000
device and a remote device. The following are typical remote devices:
• Ticket printer
• Any PLC or control system
• PC running ProLink II

Installation
• 375 Field Communicator
• Temperature or pressure sensor
• HART Tri-Loop
Note: This chapter does not discuss configuration of digital communications. To configure digital
communications, see Chapter 13.

3.2 Supported protocols


Table 3-1 describes the digital communications support provided on the Series 3000 device.

Digital Communications Setup


HART/Bell 202 is superimposed on the primary mA output, while all RS-485 protocols are
implemented on a dedicated terminal pair.

Table 3-1 Series 3000 terminals, physical layers, and protocols

Terminals Physical layer Protocol


Primary mA output terminals Bell 202 HART
RS-485 terminals RS-485 Modbus
HART
Printer

3.2.1 Obtaining the components


Identify and obtain the required components according to the physical layers and protocols you
will use.
Using the Display

3.2.2 RS-485 signal converter

RS-232 or USB conversion


If you need to convert the RS-485 signal to an RS-232 or USB signal, signal converters are available
from Micro Motion (part number PLKUSB485KIT or PLK485KIT). Contact Micro Motion for
information about ordering these converters.

Configuration and Use Manual 15


Digital Communications Setup

You may also order the IC521A-F signal converter with a ticket printer. Contact Micro Motion for the
appropriate ETO (engineered-to-order) number.
Depending on your remote device, you may also need a 9-pin to 25-pin adapter.
Note: The ProLink PC Interface Adaptor (PCIA) cannot be used with the Series 3000 device. Because
the PCIA does not control the ready-to-send (RTS) line, communication between the Series 3000
device and the remote device cannot be initiated.

Other conversion
If you need to convert the RS-485 signal to another signal, you must supply the appropriate signal
converter.

3.2.3 Bell 202 signal converter

RS-232 conversion
If you need to convert the Bell 202 signal to an RS-232 signal, as used by a PC’s serial port, signal
converters are available from Micro Motion (part number PLKUSB202KIT or PLK202KIT). Contact
Micro Motion for information about ordering these converters.
You may also need a Bell 202 cable or a 9-pin to 25-pin adapter.

Other conversion
If you need to convert the Bell 202 signal to another signal, you must supply the appropriate signal
converter or HART interface.

3.3 Setting up RS-485 communications


Follow the steps below to set up RS-485 communications between the Series 3000 device and a
remote device.
1. Locate and identify the RS-485 terminals on the Series 3000 device. Refer to Table 3-2 and
Figure 2-2. Additionally, the Series 3000 device has a label or card that shows input/output
wiring terminal designations. See Figure 2-3.
Note: The terminals labeled Comm 1, Comm 2, and Comm 3 are not for I/O wiring. These terminals
are for Micro Motion internal use only.

Table 3-2 RS-485 wiring terminals

RS-485 terminals
Model RS-485 terminals location/description A B
Model 3300 or Model 3500 with Input/output wiring terminal block a 32 c 32
screw-type or solder-tail connectors
Model 3300 or Model 3500 with I/O terminal block on DIN rail 25 24
I/O cable
Model 3350 or Model 3700 Gray terminal block, non-intrinsically safe wiring 12 11
compartment

16 Micro Motion® Series 3000 MVD Transmitters and Controllers


Digital Communications Setup

2. Using twisted-pair shielded cable, and a signal converter if required, connect the remote device
to the RS-485 output terminals on the Series 3000 device. Maximum cable length between the

Before You Begin


Series 3000 and remote device is 4000 feet (1200 meters).
• Model 3300 or Model 3500 with screw-type or solder-tail terminals: see Figure 3-1
• Model 3300 or Model 3500 with I/O cables: see Figure 3-2
• Model 3350 or Model 3700: see Figure 3-3
3. Add resistance if required.
4. Configure RS-485 communications as described in Section 13.3.

Figure 3-1 Model 3300 or Model 3500 with RS-485 signal converter – Screw-type or solder-tail connectors

Input/output terminal block

Installation
For long-distance communication, or if noise from an
external source interferes with the signal, install a 120 , Remote
½ watt resistor at each end of the wiring loop between the device
Series 3000 device and the signal converter

RS-485 to RS-232
signal converter
RS-485 A

Digital Communications Setup


RS-485 B
Serial port connection
Wire size is 24 AWG (0,25 mm2) (with 9-pin to 25-pin
adapter if necessary)

Using the Display

Configuration and Use Manual 17


Digital Communications Setup

Figure 3-2 Model 3300 or Model 3500 with RS-485 signal converter – I/O cables
Serial port connection
(with 9-pin to 25-pin
adapter if necessary)

Wire size is 24 AWG (0,25 mm2)


Input/output terminal block RS-485 to RS-232
signal converter
RS-485 A

RS-485 B
Remote
device

For long-distance communication, or if noise


from an external source interferes with the
signal, install a 120 , ½ watt resistor at each
end of the wiring loop between the
Series 3000 device and the signal converter

Figure 3-3 Model 3350 or Model 3700 with RS-485 signal converter
Serial port connection
(with 9-pin to 25-pin
Input/output terminal block adapter if necessary)

RS-485 to RS-232
signal converter
RS-485 B
Wire size is 22 AWG (0,35 mm2)

RS-485 A
Remote
device

For long-distance communication, or if noise from an


external source interferes with the signal, install a 120 ,
½ watt resistor at each end of the wiring loop between the
Series 3000 device and the signal converter

18 Micro Motion® Series 3000 MVD Transmitters and Controllers


Digital Communications Setup

3.4 Setting up Bell 202 communications

Before You Begin


Follow the steps below to set up Bell 202 communications between the Series 3000 device and a
remote device.
1. Locate and identify the primary mA output terminals on the Series 3000 device. Refer to
Table 3-3 and Figure 2-2. Additionally, the Series 3000 device has a label or card that shows
input/output wiring terminal designations. See Figure 2-3.

Table 3-3 Bell 202 wiring terminals

Primary mA terminals
Primary mA output terminals
Model location/description + –
Model 3300 or Model 3500 with Input/output wiring terminal block c2 a2
screw-type or solder-tail
connectors
Model 3300 or Model 3500 with I/O terminal block on DIN rail 14 15
I/O cable

Installation
Model 3350 or Model 3700 Gray terminal block, non-intrinsically safe 2 1
wiring compartment

2. Determine if the primary mA output will be used to report both analog (mA) process data and
HART digital data. It may already be wired for analog output.
3. Using twisted-pair shielded cable, and a signal converter if required, connect the remote device
to the Series 3000 device’s primary mA output terminals. Maximum cable length between the
Series 3000 device and the remote device is 4000 feet (1200 meters).
If the output will be used for HART digital communications only, see the following:
• Model 3300 or Model 3500 with screw-type or solder-tail terminals: Figure 3-4

Digital Communications Setup


• Model 3300 or Model 3500 with I/O cables: Figure 3-5
• Model 3350 or Model 3700: Figure 3-6
Additionally, the following wiring examples are provided:
• Using the primary mA outputs for both digital communication and analog output
(HART/analog single-loop wiring) – see Figure 3-7
• Wiring the Series 3000 device to a HART multidrop network – see Figure 3-8
• Wiring for pressure or external temperature compensation – see Figure 3-9
• Wiring the Series 3000 device to a HART Tri-Loop – see Figure 3-10
• Wiring for pressure or external temperature compensation with HART Tri-Loop – see
Figure 3-11
Note: The HART loop is not polarity-sensitive.
4. The HART interface must be connected across a resistance of 250–600 . Add resistance to
the connection if necessary.
Using the Display

5. Configure Bell 202 communications as described in Section 13.4.

Configuration and Use Manual 19


Digital Communications Setup

Figure 3-4 Model 3300 or Model 3500 with HART interface – Screw-type or solder-tail connectors

Wire size is 24 AWG (0,25 mm2)

Remote
600  maximum loop resistance device
250 minimum loop resistance

HART interface

Input/output terminal block

Serial port connection


(with 9-pin to 25-pin
adapter if necessary)

Figure 3-5 Model 3300 or Model 3500 with HART interface – I/O cables
Serial port connection
(with 9-pin to 25-pin
adapter if necessary)

Wire size is 24 AWG (0,25 mm2)


Input/output terminal block HART interface

Remote
device

600  maximum loop resistance


250 minimum loop resistance

20 Micro Motion® Series 3000 MVD Transmitters and Controllers


Digital Communications Setup

Figure 3-6 Model 3350 or Model 3700 with HART interface

Before You Begin


Serial port connection
Wire size is 22 AWG (0,35 mm2) (with 9-pin to 25-pin
adapter if necessary)

HART interface

600  maximum loop resistance


250 minimum loop resistance Remote
device

Input/output terminal block

Installation
Figure 3-7 HART/analog single-loop wiring

Resistance:
• Analog only: 820 maximum loop resistance

Digital Communications Setup


HART device • HART only or HART/analog: HART device
(with optional - 600  maximum loop resistance (with optional signal
signal converter) - 250 minimum loop resistance converter)

+ – –
+
HART device
(with optional signal
converter)

Using the Display

Terminal block for Model 3300 or Terminal block for Model 3300 Terminal block for
Model 3500 with screw-type or or Model 3500 with IO cables Model 3350 or Model 3700
solder-tail connectors

Configuration and Use Manual 21


Digital Communications Setup

Figure 3-8 HART multidrop wiring with SMART FAMILY™ transmitters and a configuration tool

HART-compatible 24 VDC loop power


ProLink II v2.x, transmitters SMART FAMILY™ supply required for
Series 3000 HART 4–20 mA
HART Communicator, or AMS transmitters
software passive transmitters
(with HART interface)

600  maximum loop resistance


250 minimum loop resistance
Note: For optimum HART communication, make
sure the output loop is single-point-grounded to
an instrument-grade ground.

Figure 3-9 Wiring for pressure or external temperature compensation

Primary mA output terminals Resistance as required for your device

– + DC power
Series 3000 supply
device Pressure or
temperature
device –

600  maximum loop resistance


250 minimum loop resistance

22 Micro Motion® Series 3000 MVD Transmitters and Controllers


Digital Communications Setup

Figure 3-10 Wiring for HART Tri-Loop

Before You Begin


Channel 2

Primary mA output terminals


Channel 3

Channel 1

Series 3000 + DC power


device supply
HART
Tri-Loop

Burst input

Installation
600  maximum loop resistance
250 minimum loop resistance

Figure 3-11 Wiring for pressure or external temperature compensation with HART Tri-Loop

Resistance as required for your device

– + DC power

Digital Communications Setup


supply
Pressure or
temperature –
device

Channel 2
Primary mA
output terminals
Channel 3
Channel 1

DC power
Series 3000 + supply
device
HART
Tri-Loop
Using the Display

Burst input

600  maximum loop resistance


250 minimum loop resistance

Configuration and Use Manual 23


24 Micro Motion® Series 3000 MVD Transmitters and Controllers
Chapter 4

Before You Begin


Using the Display and Menu System

4.1 About this chapter


This chapter explains how to use the Series 3000 display and menu system. Using the display, you can
move through the menus, configure the application, monitor and control the application, and perform
maintenance and diagnostic tasks.

4.2 Startup display

Installation
When the Series 3000 device is powered on, it automatically tests its display. During display testing,
the screen darkens for approximately five seconds. After the display test is completed:
1. The Micro Motion logo is displayed for two to three seconds.
2. An application list is displayed for two to three seconds.
3. The device enters operation mode:
• If the discrete batch application is not installed, the process monitor screen is displayed, as
shown in Figure 4-1.
• If the discrete batch application is installed, the batch process screen is displayed (see
Figure 18-1).

Digital Communications Setup


Figure 4-1 Process Monitor screen
Alarm bar

5 DEVICE 1 2
Mass Flow Rate
2.33
g/s
Mass Total
485.88
g Security
RESET EXIT
button
Using the Display

VIEW or EXIT
button

4. If there are any active alarms, the alarm category will be displayed in the alarm bar. To view,
acknowledge, or respond to the alarms, see Chapter 22.

Configuration and Use Manual 25


Using the Display and Menu System

4.3 Menu systems


Most Series 3000 display functions are organized into two menu systems:
• The Management menu allows you to perform configuration and maintenance tasks.
• The View menu allows you to monitor and control the process.
Figures 4-2 and 4-3 show high-level views of these menu systems. For complete menu flowcharts, see
Appendix F.

Figure 4-2 Management menu

Management

Configuration Maintenance Security Language

System Active alarm log Security Language


Inputs Alarm history Passwords
Discrete batch(1) Alarm event log Weights & Measures(3)
Measurements Batch inventory(1)
Outputs Process inventory
Monitoring Meter fingerprinting(2) (1) Displayed only if discrete batch application is installed.
Digital communication Audit trail(3) (2) Available only on systems with the standard core processor.
Calibration
Diagnostics (3) Displayed only if custody transfer application is installed.
Meter verification(4) (4) Available only on systems with the enhanced core processor,
and only if the meter verification option was purchased.

Figure 4-3 View menu

View

Active alarm Preset Process Density Applications


log selections(1) totalizers curves(2) list

Process Batch Diagnostic LCD


monitoring inventory(1) monitor options

(1) Displayed only if discrete batch application is installed.


(2) Displayed only if enhanced density application is installed.

26 Micro Motion® Series 3000 MVD Transmitters and Controllers


Using the Display and Menu System

To enter the menus:

Before You Begin


• To enter the Management menu system, press the Security button. The Security button is in
the lower right corner of the display, marked with a padlock icon (see Figure 4-1). You may or
may not be required to enter a password (see the following section).
• To enter the View menu system, press the VIEW or EXIT button (see Figure 4-1).

4.3.1 Accessing management functions


You can use the Security button to access management functions from any point in the Series 3000
menus. When the Security button is pressed:
• If security is disabled, the Management menu will be displayed immediately. See Figure 4-4.
By default, security is disabled.
• If security has been enabled, you will be prompted to enter a password. See Figure 4-5. There
are two passwords:
- The configuration password enables access to all functions. When it is entered, the

Installation
Management menu is displayed.
- The maintenance password enables access to the maintenance functions. When it is
entered, the Maintenance menu is displayed.
Both passwords consist of a sequence of four cursor control button presses. To enter a password:
1. Press the four cursor control buttons in the correct sequence.
2. Press SEL.
To configure and enable security, see Chapter 5.

Figure 4-4 Pressing Security button from Process Monitor screen – Security disabled

Digital Communications Setup


5 DEVICE 1 2 DEVICE 1
Mass Flow Rate Configuration
2.33 Maintenance
Security
g/s Language
Mass Total
485.88
g
PRINT RESET EXIT SEL EXIT

Using the Display

Configuration and Use Manual 27


Using the Display and Menu System

Figure 4-5 Pressing Security button from Process Monitor screen – Security enabled

5 DEVICE 1 2
Mass Flow Rate
2.33 Enter Password
g/s
Mass Total
485.88
g
PRINT RESET EXIT SEL HELP EXIT

4.3.2 Shortcuts
From any point in the menu system, you can:
• Return to the Management menu (if security is disabled) or the password entry screen (if
security is enabled) by pressing the Security button, as described in the previous section.
• Return to the operating screen by pressing the Security button, then pressing the EXIT button.

4.4 Using the function buttons


The buttons at the bottom of the display are the function buttons. The functions performed by the
buttons vary, depending on the screen and the current state of the application. The function currently
assigned to the button is always displayed on the screen, above the button. The buttons are sometimes
referred to as F1, F2, and F3. See Figure 4-6.
Note: The left and right cursor control buttons may also be used as function buttons. See Figure 4-6.
If a cursor is shown on the display, the action performed by the function button applies to the item
where the cursor is located. Before pressing a function button, be sure the cursor is located correctly.
See Section 4.5.

28 Micro Motion® Series 3000 MVD Transmitters and Controllers


Using the Display and Menu System

Figure 4-6 Function buttons

Before You Begin


ALARMS F3 function button
DEVICE 1

Configuration F1 function button


Maintenance
Security
Language

SEL HELP EXIT

Installation
F3 function button
VIEW Access the View menu
EXIT Exit to previous menu or cancel a change
NO Cancel action
PREV Return to the previous screen
ABORT • Abort sensor zero
• Abort calibration

Digital Communications Setup


F2 function button
HELP Show a help screen
RESUME Resume a batch that has been stopped
RESET Reset total
PRINT Print a ticket
NEXT Advance to the next screen
ACKALL Acknowledge all alarms
RESET-T Complete the current custody transfer transaction

F1 function button
START Start batch or totalizers
STOP • Stop totalizers
• Stop batch before target is achieved (batch can be resumed)
END End batch before target is achieved (batch cannot be resumed)
RESET Reset total
SEL Select the highlighted menu item
CHG Make a change to the highlighted menu item
SAVE Save a change
Using the Display

YES Proceed with action


ACK Acknowledge an alarm message
PRINT Print a ticket
CLEAR Reset the rollover indicator (R) for the transfer inventory

Configuration and Use Manual 29


Using the Display and Menu System

4.5 Using the cursor control buttons


The cursor control buttons move the cursor around the display menus. In menus, the cursor is a
reverse-video highlight bar.
• Use the Up and Down buttons to locate the cursor at the menu item you want to select or
change.
• After locating the cursor at the desired menu item, press SEL or CHG, or the Right button, to
select or change the item.

4.5.1 Selecting from a list


For enumerated lists, pressing CHG will display a separate screen from which you can choose the
desired option. From that screen:
• Press SAVE to save the change and return to the previous screen, or
• Press EXIT or the Left button to return to the previous screen without saving.

4.5.2 Changing a variable value


If you need to change the value of a variable, the cursor appears as a line under a character in the
current value.
• If the variable has a value of Yes or No, all cursor control buttons toggle between the two
choices.
• If the variable has a numeric or character value, press the Up and Down cursor control buttons
to increase or decrease the value of the character at the cursor.
• If the variable has more than one digit or character, press the Left and Right cursor control
buttons to move the cursor to the next or previous character.
When the value is correct, press SAVE.
Press EXIT to return to the previous screen without saving.

4.5.3 Cursor control example


Figure 4-7 shows a typical configuration sequence involving both a menu item and a variable.
Pressing HELP produces a screen that has help for the item at the cursor.

4.5.4 Process monitor


In the process monitor, use the Left and Right cursor control buttons to scroll from one screen to the
next or previous screen. There are five screens.
• Press the Right button to scroll to the next screen.
• Press the Left button to scroll to the previous screen.
• To assign variables to each process monitor screen, see Chapter 12.

4.6 Scientific notation


Scientific notation is used on some screens for displaying values that contain more digits than the
display can show, or that exceed the precision of the floating point data type. For example, the value
1234000.000 would be displayed as 1.234E6 or 1.234+6.

30 Micro Motion® Series 3000 MVD Transmitters and Controllers


Using the Display and Menu System

Figure 4-7 Cursor control buttons

Before You Begin


Menu item EXIT

Density Move cursor up/Scroll up


Indicates items 
available to scroll Density Units
g/cm3
Density Damping
1.7 sec SELECT
Density Cutoff
Current 0.005000 g/cm3
selection is Slug Low Limit
highlighted 0.005000 g/cm3
Move cursor down/Scroll down
CHG HELP EXIT

Installation
Move cursor to left
Variable

Density Increase value at cursor


 or toggle YES/NO
Density Units
g/cm3
Density Damping
1.7 sec Move cursor to right
Density Cutoff
Current 0.005000 g/cm3
selection is Slug Low Limit
underscored 0.005000 g/cm3
Decrease value at
SAVE HELP EXIT cursor or toggle YES/NO

Digital Communications Setup


Scroll to previous screen
Process monitor

5 DEVICE 1 2
Mass Flow Rate
2.33
g/s Scroll to next screen
Mass Total
485.88
g
PRINT RESET EXIT
Using the Display

Configuration and Use Manual 31


32 Micro Motion® Series 3000 MVD Transmitters and Controllers
Configuring Security & Language
Chapter 5
Configuring Security and Language

5.1 About this chapter


This chapter explains how to configure security and select the language for the Series 3000 display.
Security and language parameters are listed in Figures 5-1 and 5-2.
Failure to perform configuration tasks in the proper sequence could result in an incomplete

Configuring System Data


configuration. See Section 1.7 for the recommended configuration sequence.

CAUTION
Changing configuration can affect device operation.

Set control devices for manual operation before changing device configuration.

5.2 Security menu


Use the Security menu, shown in Figure 5-1, to access and configure security and passwords. The
Security menu is accessed through the Management menu, as described in Chapter 4.
To configure security for weights and measures (custody transfer) applications, see Chapter 14.

Configuring Inputs
Figure 5-1 Security menu

Security

Security Passwords Weights & Measures(2) Alarm log(2)(3)


(see Chapter 14) (see Chapter 14)

Enable security Maintenance Configuration


Write protect(1) • Press 1 • Press 1
Totalizer reset(1) • Press 2 • Press 2
Configuring API

• Press 3 • Press 3
• Press 4 • Press 4

(1) Displayed only if the custody transfer application is not installed.


(2) Displayed only if the custody transfer application is installed.
(3) Displayed only if World Area is set to OIML.

Configuration and Use Manual 33


Configuring Security and Language

5.3 Security
Security can be used for the following three functions:
• To control access to the Management menu
• To write-protect the Series 3000 device configuration
• To control how process totalizers and inventories can be reset
Note: If custody transfer is implemented, the write-protection and totalizer reset control functions are
handled by the custody transfer application, and are not available here. See Chapter 14.
Note: If custody transfer (OIML) is implemented, you can also define an alarm log password to
control access to the active alarm log, the alarm event log, and alarm history. See Chapter 14.

5.3.1 Management menu access


Access to the Management menu can be controlled by two passwords:
• The configuration password enables access to all Management menus
• The maintenance password enables access to the Maintenance portion of the Management
menu system
When the Security button is pressed (see Section 4.3.1):
• If security is enabled, you will be prompted to enter a password. Depending on the password
you enter, either the Management menu or the Maintenance menu is displayed.
• If security is disabled, the Management menu is displayed immediately.
The configured passwords are stored even if security is disabled, so you can re-enable them at any
time.
It is not possible to activate only the configuration password or only the maintenance password.
To enable security for the Management menu, set Enable Security to Enable.
To disable security for the Management menu, set Enable Security to Disable.
The passwords are a combination of four button presses, using any of the four cursor control buttons:
Up, Down, Left, and Right.
To set a password:
1. Use the menu to select the password you are defining.
2. For Press 1 through Press 4, specify which cursor control button must be pressed.
To enter a password:
1. Press the four cursor control buttons in the correct sequence.
2. Press SEL.

5.3.2 Write-protecting the device configuration


When the device is in write-protect mode, the configuration data stored in the device and core
processor cannot be changed until write-protect mode is disabled.
To enable write-protection, set Write Protect to Enable.
To disable write-protection, set Write Protect to Disable.
Note: If write-protection is enabled, process totalizers cannot be reset unless the flow rate is zero.

34 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Security and Language

Configuring Security & Language


5.3.3 Controlling process totalizer and process inventory reset
This feature allows you to specify the methods that can be used to reset process totalizers and process
inventories:
• No Reset – Cannot be reset using either the display or remote communications (e.g.,
ProLink II or a HART or Modbus tool).
• Display Only – Can be reset only via the display on the Series 3000 device.
• Remote Only – Can be reset only via remote communications (e.g., ProLink II or a HART or
Modbus tool).
• Display & Remote – Can be reset using any communications method.
For definitions of process totalizers, process inventories, and other totalizer types, and additional
information on managing totalizers and inventories, see Chapter 20.

Configuring System Data


5.4 Language menu
Use the Language menu, shown in Figure 5-2, to access and configure language parameters. The
Language menu is accessed through the Management menu, as described in Chapter 4.
The configured language will be used for all Series 3000 screens. The display changes immediately.

Figure 5-2 Language menu

Language

Language

Language list

Configuring Inputs
Your choice of language affects the notation used for various units. If English is selected, English
notation is used. If French or German is selected, European notation is used.

Configuring API

Configuration and Use Manual 35


36 Micro Motion® Series 3000 MVD Transmitters and Controllers
Configuring Security & Language
Chapter 6
Configuring System Data

6.1 About this chapter


This chapter explains how to configure system data. System parameters are listed in Figure 6-1.
Failure to perform configuration tasks in the proper sequence could result in an incomplete
configuration. See Section 1.7 for the recommended configuration sequence.

Configuring System Data


CAUTION
Changing configuration can affect device operation.

Set control devices for manual operation before changing device configuration.

6.2 System menu


Use the System menu, shown in Figure 6-1, to access and configure system parameters. The System
menu is accessed through the Configuration option of the Management menu. To access the
Management menu, see Chapter 4.

Figure 6-1 System menu

Configuring Inputs
System

Tag Time Date Alarm severity

Hour Day Electronics alarms


Minute Month Process alarms
Second Year Sensor alarms(1)
Configuration alarms
Configuring API

(1) Displayed only if you are configuring a Model 3500 or Model 3700 transmitter.

Configuration and Use Manual 37


Configuring System Data

6.3 System parameters


System parameters are defined in Table 6-1.

Table 6-1 System parameters

Variable Default Description


Tag(1) Device 1 • Enter up to 8 digits and/or characters that uniquely identify this platform
• The tag will appear on operation screens
Time Current time Enter 2 digits for hours, 2 digits for minutes, and 2 digits for seconds
Date Current date Enter 4 digits for the year, a character code for the month, and 2 digits for the
day
Alarm severity Select alarm to be reclassified. See Section 6.3.1, below.
(1) This tag is also known as the HART tag or the software tag. It is not the HART polling address (also called the HART slave address).
To configure the HART polling address, see Section 13.4.

6.3.1 Alarm severity


Alarms are organized into four categories. Within each category, alarms are classified into three levels
of severity. The severity level controls device behavior when the alarm condition occurs. See
Table 6-2.

Table 6-2 Alarm severity levels

Severity level Device action


Fault If this condition occurs, an alarm will be generated and all outputs go to their configured
fault levels. See Chapter 8.
Informational If this condition occurs, an alarm will be generated but output levels are not affected.
Ignore If this condition occurs, no alarm will be generated (no entry is added to the active alarm
log).

Some alarms can be reclassified. For example:


• The default severity level for Alarm A020 (cal. factors missing) is Fault, but you can
reconfigure it to either Informational or Ignore.
• The default severity level for Alarm A102 (drive over-range) is Informational, but you can
reconfigure it to either Ignore or Fault.
If an alarm can be reclassified, the CHG function is assigned to the F1 button. If an alarm cannot be
reclassified, the F1 button is unassigned. The alarm listings in Section 22.7 also provide information
on which alarms can be reclassified.

38 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Security & Language
Chapter 7
Configuring Inputs

7.1 About this chapter


This chapter explains how to configure inputs. Inputs include all the software parameters listed in
Figures 7-1 and 7-2.
Failure to perform configuration tasks in the proper sequence could result in an incomplete

Configuring System Data


configuration. See Section 1.7 for the recommended configuration sequence.

CAUTION
Changing configuration can affect device operation.

Set control devices for manual operation before changing device configuration.

7.2 Inputs menu


Use the Inputs menu, shown in Figures 7-1 and 7-2, to access and configure input parameters. The
Inputs menu is accessed through the Configuration option of the Management menu. To access the
Management menu, see Chapter 4.
You will be:

Configuring Inputs
• Configuring core processor parameters:
- Enabling or disabling core processor inputs
- Configuring process variables
- Configuring sensor calibration data
- Configuring sensor information
- Assigning discrete inputs to actions
• Configuring the frequency input
• Configuring the discrete inputs
• Configuring external inputs
• Configuring LD Optimization
Note: If you are configuring a Model 3300 or Model 3350 controller, the core processor parameters
and external inputs parameters are not displayed. To assign a discrete input to an action on these
Configuring API

platforms, use the frequency input menu shown in Figure 7-2.

Configuration and Use Manual 39


Configuring Inputs

Figure 7-1 Inputs menu – Core processor parameters

Inputs

Core processor(1) Other inputs


See Figure 7-2

Enable/ Configure Sensor cal data Sensor Discrete inputs


Disable process var information

Flow variables Density T-Series Setup • Sensor model no.


• Flow damping • Density units • Sensor serial no.
• Flow direction • Density damping • Sensor material
• Mass units • Density cutoff • Sensor flange
• Mass low flow cutoff • Slug low limit • Sensor liner
• Volume flow type • Slug high limit
• Volume units(2) • Slug duration
• Std gas volume units(3)
• Std gas volume
cutoff(3)(4) • Start zero
• Std gas density(3) • Reset mass total
• Vol low flow cutoff(2) • Reset volume total
• Special mass units Yes No • Reset API cor vol tot(5)
• Special volume units(2) • FCF • Flow cal • Reset ED std vol tot(6)
• Special gas std units(3) • FTG • D1 • Reset ED net mass to(6)
• FFQ • D2 • Reset ED net vol tot(6)
• D1 • K1 • Reset all totals
• D2 • K2 • Start/stop all totals
Temperature • D3 • FD • Start meter verify(7)
• Temperature units • D4 • Dens temp coeff
• Temperature damping • K1 • Temp. cal factor
• K2 • Mass factor
• K3 • Density factor
• K4 • Volume factor
• FD
• DT
• DTG
• DFQ1 LD Optimization
• DFQ2
• Temp. slope
• Temp. offset
• Mass factor
• Density factor
• Volume factor

(1) Displayed only if you are configuring a Model 3500 or Model 3700 transmitter.
(2) Displayed only if Volume Flow Type = Liquid Volume.
(3) Displayed only if Volume Flow Type = Gas Standard Volume.
(4) Displayed only on systems with the enhanced core processor.
(5) Displayed only if petroleum measurement application is installed.
(6) Displayed only if enhanced density application is installed.
(7) Displayed only if Smart Meter Verification is installed.

40 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Inputs

Configuring Security & Language


Figure 7-2 Inputs menu – Frequency input, discrete input, external inputs

Inputs

Core processor inputs Frequency input


See Figure 7-1

Flow rate units Scaling method Reset all totals(1) Start/Stop all totals(1)

Configuring System Data


Frequency=flow Pulses/unit Units/pulse None
• Frequency • Pulses/unit • Units/pulse Discrete input 1
• Flow • K-factor • K-factor Discrete input 2
• K-factor

Discrete inputs External inputs(2)

Discrete input 1 2 Polling variable 1 2

Configuring Inputs
Polarity • Polling control
• Polling variable
• External tag
• Pressure compensation(3)
• Pressure units(3)
(1) Displayed only if you are configuring a Model 3300 or Model 3350 controller. • Flow factor(3)
(2) Displayed only if you are configuring a Model 3500 or Model 3700 transmitter. • Density factor(3)
(3) Displayed only if Polling Variable is set to Pressure. • Cal pressure(3)
• External temperature
(4) Displayed only if Polling Variable is set to Temperature. compensation(4)

7.3 Configuring the core processor parameters


Core processor parameters include:
Configuring API

• Core processor inputs


• Process variables
• Sensor calibration data
• Sensor information

Configuration and Use Manual 41


Configuring Inputs

7.3.1 Enabling and disabling core processor inputs


Core processor inputs are enabled by default. By disabling the core processor, you disable all core
processor input signals and alarms. Disabling them might be desirable while you are connecting the
sensor, or if you are using only the frequency input to measure flow.
Table 7-1 describes the core processor input options.

Table 7-1 Enabling or disabling inputs and alarms

Variable Default Description


Enable core processor Yes If set to No:
• The platform will not use input signals from the sensor to measure flow,
density, or temperature.
• The platform will not produce the following alarms: warming up, cal in
progress, drive overrange, temperature overrange, temperature failure,
sensor failure, transmitter failure, density overrange, density failure, mass
flow overrange, volume overrange, calibration failure, calibration complete,
calibration aborted, RTD failure, charize required, slug flow, slug timeout(1).
(1) For more information about alarms, see Chapter 22.

7.3.2 Configuring process variables


Process variables include mass flow, volume flow, density, and temperature. For each process
variable, several parameters can be configured.

Mass flow and volume flow parameters


Mass flow and volume flow parameters are listed and defined in Table 7-2. Note that you can
configure the transmitter to measure either liquid volume flow or gas standard volume flow,
depending on the setting of Volume Flow Type.
Details about the Flow Direction parameter are provided in Table 7-3. Units for mass flow and
volume flow parameters are listed in Tables 7-4 through 7-6. Special units for mass and volume are
defined and described in the section entitled Special units later in this chapter.

Table 7-2 Flow parameters

Variable Default Description


Flow damping 0.8 sec • Damping filters out noise or the effects of rapid changes in the flow rate
without affecting measurement accuracy. See the section entitled Damping
later in this chapter. For gas applications, Micro Motion recommends a
minimum flow damping value of 2.56 seconds. Range is 0.0–51.2 seconds.
• Milliamp outputs have an additional damping parameter. See Section 8.4.4.
Flow direction Forward • Controls how flow through the sensor will affect outputs and totalizers.
• For the effect of flow direction on milliamp outputs, see Figure 7-3 if the 4 mA
value of the milliamp output is set to 0, and see Figure 7-4 if the 4 mA value
of the milliamp output is set to a negative value. For a discussion of these
figures, see the examples following the figures. For information on setting the
4 mA value, see Section 8.4.4.
• For the effect of flow direction on frequency outputs, totalizers, and flow
values reported via digital communication, see Table 7-3.
Mass units g/s • Select the desired unit of mass flow. See Table 7-4.
• Mass flow outputs and displays will indicate mass flow in the selected unit.
The mass totalizer and inventory will use the corresponding mass unit.
Mass low flow cutoff 0.00000 g/s • Enter the mass flow rate below which mass flow outputs and displays will
indicate zero flow. See the section entitled Cutoffs later in this chapter.
• Milliamp outputs have an additional cutoff parameter. See Section 8.4.4.

42 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Inputs

Configuring Security & Language


Table 7-2 Flow parameters continued

Variable Default Description


Volume flow type Liquid • Select the desired volume flow type.
- If you select Liquid, only liquid volume units are available for measurement
- If you select Gas, only gas standard volume units are available for
measurement. See the section entitled Gas standard volume flow and
standard density.
• If you are using the enhanced density application or the petroleum
measurement application, select Liquid.
Volume units(1) l/s • Select the desired unit of liquid volume flow. See Table 7-5. The liquid
volume totalizer and inventory will use the corresponding volume unit.
Volume low flow 0.00000 l/s • Enter the liquid volume flow rate below which volume flow outputs and
cutoff(1) displays will indicate zero flow. See the section entitled Cutoffs later in this
chapter.
• Milliamp outputs have an additional cutoff parameter. See Section 8.4.4.

Configuring System Data


Standard gas volume SCFM • Select the desired unit of gas standard volume flow. See Table 7-6. The gas
units(2) standard totalizer and inventory will use the corresponding volume unit.
Standard gas volume 0.0000 SCFM • Enter the volume flow rate below which volume flow outputs and displays will
cutoff(3)(2) indicate zero flow. See the section entitled Cutoffs later in this chapter.
• Milliamp outputs have an additional cutoff parameter. See Section 8.4.4.
Standard gas density(2) 0.10000 g/cm3 • Enter the standard density of the gas you are measuring. See the section
entitled Gas standard volume flow and standard density
(1) Displayed only if Volume Flow Type = Liquid.
(2) Displayed only if Volume Flow Type = Gas Standard.
(3) Available only on systems with the enhanced core processor.

Figure 7-3 Effect of flow direction on milliamp outputs: 4 mA value = 0

20 20 20

Configuring Inputs
mA output

mA output

mA output

12 12 12

4 4 4

-x 0 x -x 0 x -x 0 x

Reverse Forward Reverse Forward Reverse Forward


flow(1) flow(2) flow(1) flow(2) flow(1) flow(2)
Zero flow Zero flow Zero flow

Flow direction parameter: Flow direction parameter: Flow direction parameter:


• Forward only • Reverse only • Absolute value
• Negate/Forward only • Bidirectional
• Negate/Bidirectional

Milliamp output configuration: (1) Process fluid flowing in opposite direction from flow direction arrow on sensor.
Configuring API

• 20 mA value = x (2) Process fluid flowing in same direction as flow direction arrow on sensor.
• 4 mA value = 0
To set the 4 mA and 20 mA values, see
Section 8.4.4.

Configuration and Use Manual 43


Configuring Inputs

Figure 7-4 Effect of flow direction on milliamp outputs: 4 mA value < 0

20 20 20

mA output

mA output
mA output

12 12 12

4 4 4

–x 0 x –x 0 x –x 0 x

Reverse Forward Reverse Forward Reverse Forward


flow(1) flow(2) flow(1) flow(2) flow(1) flow(2)
Zero flow Zero flow Zero flow

Flow direction parameter: Flow direction parameter: Flow direction parameter:


• Forward only • Reverse only • Absolute value
• Negate/Forward only • Bidirectional
• Negate/Bidirectional

Milliamp output configuration: (1) Process fluid flowing in opposite direction from flow direction arrow on sensor.
• 20 mA value = x (2) Process fluid flowing in same direction as flow direction arrow on sensor.
• 4 mA value = –x
• –x < 0
To set the 4 mA and 20 mA values, see
Section 8.4.4.

Example 1 Configuration:
• Flow direction = Forward only
• mA output: 4 mA = 0 g/s; 20 mA = 100 g/s
(See the first graph in Figure 7-3.)

As a result:
• Under conditions of reverse flow or zero flow, the mA output is
4 mA.
• Under conditions of forward flow, up to a flow rate of 100 g/s, the
mA output varies between 4 mA and 20 mA in proportion to (the
absolute value of) the flow rate.
• Under conditions of forward flow, if (the absolute value of) the flow
rate equals or exceeds 100 g/s, the mA output will be proportional
to the flow rate up to 20.5 mA, and will be level at 20.5 mA at
higher flow rates.

44 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Inputs

Configuring Security & Language


Example 2 Configuration:
• Flow direction = Reverse only
• mA output: 4 mA = 0 g/s; 20 mA = 100 g/s
(See the second graph in Figure 7-3.)

As a result:
• Under conditions of forward flow or zero flow, the mA output is
4 mA.
• Under conditions of reverse flow, up to a flow rate of 100 g/s, the
mA output varies between 4 mA and 20 mA in proportion to the
absolute value of the flow rate.
• Under conditions of reverse flow, if the absolute value of the flow
rate equals or exceeds 100 g/s, the mA output will be proportional

Configuring System Data


to the absolute value of the flow rate up to 20.5 mA, and will be
level at 20.5 mA at higher absolute values.

Example 3 Configuration:
• Flow direction = Forward only
• mA output: 4 mA = –100 g/s; 20 mA = 100 g/s
(See the first graph in Figure 7-4.)

As a result:
• Under conditions of zero flow, the mA output is 12 mA.
• Under conditions of forward flow:
- Up to a flow rate of 100 g/s, the mA output varies between
12 mA and 20 mA in proportion to (the absolute value of) the

Configuring Inputs
flow rate.
- If (the absolute value of) the flow rate equals or exceeds
100 g/s, the mA output is proportional to the flow rate up to
20.5 mA, and will be level at 20.5 mA at higher flow rates.
• Under conditions of reverse flow:
- Up to a flow rate of 100 g/s, the mA output varies between
4 mA and 12 mA in inverse proportion to the absolute value of
the flow rate.
- If the absolute value of the flow rate equals or exceeds 100 g/s,
the mA output is inversely proportional to the flow rate down to
3.8 mA, and will be level at 3.8 mA at higher absolute values.
Configuring API

Configuration and Use Manual 45


Configuring Inputs

Table 7-3 Effect of flow direction on frequency outputs, discrete outputs, totalizers, and
digital communications

Forward flow(1)
Frequency Flow values via
Flow direction value outputs Discrete outputs(2) Flow totals digital comm.
Forward only Increase OFF Increase Positive
Reverse only 0 Hz OFF No change Positive
Bidirectional Increase OFF Increase Positive
Absolute value Increase OFF Increase Positive(3)
Negate/Forward only Zero(3) ON No change Negative
Negate/Bidirectional Increase ON Decrease Negative

Zero flow
Frequency Flow values via
Flow direction value output Discrete outputs Flow totals digital comm.
All 0 Hz OFF No change 0
(4)
Reverse flow
Frequency Flow values via
Flow direction value outputs Flow totals digital comm.
Forward only 0 Hz ON No change Negative
Reverse only Increase ON Increase Negative
Bidirectional Increase ON Decrease Negative
Absolute value Increase OFF Increase Positive(3)
Negate/Forward only Increase OFF Increase Positive
Negate/Bidirectional Increase OFF Increase Positive
(1) Process fluid flowing in same direction as flow direction arrow on sensor.
(2) Applies only if the discrete output has been configured to indicate flow direction. See Section 8.3.2.
(3) Refer to the digital communications status bits for an indication of whether flow is positive or negative.
(4) Process fluid flowing in opposite direction from flow direction arrow on sensor.

Table 7-4 Mass flow units

Unit Software label


Grams per second g/s
Grams per minute g/min
Grams per hour g/hr
Kilograms per second kg/s
Kilograms per minute kg/min
Kilograms per hour kg/hr
Kilograms per day kg/day
Metric tons (1000 kg) per minute t/min
Metric tons (1000 kg) per hour t/hr
Metric tons (1000 kg) per day t/day
Pounds per second lb/s

46 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Inputs

Configuring Security & Language


Table 7-4 Mass flow units continued

Unit Software label


Pounds per minute lb/min
Pounds per hour lb/hr
Pounds per day lb/day
Short tons (2000 lb) per minute STon/min
Short tons (2000 lb) per hour STon/hr
Short tons (2000 lb) per day STon/day
Long tons (2240 lb) per hour LTon/hr
Long tons (2240 lb) per day LTon/day
Special unit (see the following section entitled Special units) Special

Configuring System Data


Table 7-5 Volume flow units – Liquid

Unit Software label


Cubic feet per second cuft/s
Cubic feet per minute cuft/min
Cubic feet per hour cuft/hr
Cubic feet per day cuft/day
Cubic meters per second cum/s
Cubic meters per minute cum/min
Cubic meters per hour cum/hr
Cubic meters per day cum/day
U.S. gallons per second Usgps
U.S. gallons per minute Usgpm

Configuring Inputs
U.S. gallons per hour Usgph
U.S. gallons per day Usgpd
Million U.S. gallons per day MilGal/day
Liters per second l/s
Liters per minute l/min
Liters per hour l/hr
Million liters per day MilL/day
Imperial gallons per second UKgps
Imperial gallons per minute UKgpm
Imperial gallons per hour UKgph
Imperial gallons per day UKgpd
Barrels(1) per second bbl/s
Configuring API

(1)
Barrels per minute bbl/min
(1)
Barrels per hour bbl/hr
(1)
Barrels per day bbl/day
(2)
Beer barrels per second b bbl/s
(2)
Beer barrels per minute b bbl/min

Configuration and Use Manual 47


Configuring Inputs

Table 7-5 Volume flow units – Liquid continued

Unit Software label


(2)
Beer barrels per hour b bbl/h
(2)
Beer barrels per day b bbl/d
Special unit (see the following section entitled Special units) Special
(1) Unit based on oil barrels (42 U.S. gallons).
(2) Unit based on beer barrels (31 U.S. gallons).

Table 7-6 Volume flow units – Gas standard

Unit Software label


Standard liters per second Sl/s
Standard liters per minute Sl/min
Standard liters per hour Sl/h
Standard liters per day Sl/d
Normal cubic meters per second Nm3/s
Normal cubic meters per minute Nm3/min
Normal cubic meters per hour Nm3/h
Normal cubic meters per day Nm3/d
Standard cubic feet per second SCFS
Standard cubic feet per minute SCFM
Standard cubic feet per hour SCFH
Standard cubic feet per day SCFD
Standard cubic meters per second Sm3/s
Standard cubic meters per minute Sm3/min
Standard cubic meters per hour Sm3/h
Standard cubic meters per day Sm3/d
Special unit (see the following section entitled Special units) Special

Gas standard volume flow and standard density


If you set Volume Flow Type to Gas Standard Volume, you must enter the standard density of the gas
you are going to measure (i.e., the density of the gas at reference conditions):
• If you know the standard density, you can enter that value in the Standard Gas Density field.
For optimal measurement accuracy, be sure the standard density you enter is correct and fluid
composition is stable.
• If you do not know the standard density of the gas, and you can connect to the Series 3000
device using ProLink II, you can use the Gas Wizard.
To use the Gas Wizard:
1. Click ProLink > Configure > Flow.
2. Click Gas Wizard.
3. If your gas is listed in the Choose Gas list:
a. Select the Choose Gas radio button.
b. Select your gas.

48 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Inputs

Configuring Security & Language


4. If your gas is not listed, you must describe its properties.
a. Select the Enter Other Gas Property radio button.
b. Select the method that you will use to describe its properties: Molecular Weight, Specific
Gravity Compared to Air, or Density.
c. Provide the required information. Note that if you selected Density, you must enter the
value in the configured density units and you must provide the temperature and pressure at
which the density value was determined, using the configured temperature and pressure
units.
5. Click Next.
6. Verify the reference temperature and reference pressure. If these are not appropriate for your
application, click Change Reference Conditions and enter new values for reference
temperature and reference pressure.
7. Click Next. The calculated standard density value is displayed.

Configuring System Data


• If the value is correct, click Finish. The value will be written to transmitter
configuration.
• If the value is not correct, click Back and modify input values as required.
Note: The Gas Wizard displays density, temperature, and pressure in the configured units. If required,
you can configure the transmitter to use different units.

Special units
If you need to use a non-standard unit of measure, you can create one special measurement unit for
mass flow, one special measurement unit for liquid volume flow, and one special measurement unit
for standard gas volume flow.
Note: If you create a special measurement unit for liquid volume flow and another for gas standard
volume flow, the Series 3000 will store both definitions. However, only one is available at a time.
Special measurement units consist of:

Configuring Inputs
• Base unit – a combination of:
- Base mass or base volume unit – a measurement unit that the transmitter already
recognizes (e.g., kg, m3)
- Base time unit – a unit of time that the transmitter already recognizes (e.g., seconds, days)
• Conversion factor – the number by which the base unit will be divided to convert to the special
unit
• Special unit – a non-standard volume flow or mass flow unit of measure that you want to be
reported by the transmitter
These terms are related by the following formula:
x  BaseUnit(s)  = y  SpecialUnit(s) 

x  BaseUnit(s) 
ConversionFactor = ---------------------------------------------
Configuring API

y  SpecialUnit(s) 

Configuration and Use Manual 49


Configuring Inputs

To create a special unit, you must:


1. Identify the simplest base volume or mass and base time units for your special mass flow or
volume flow unit. For example, to create the special volume flow unit pints per minute, the
simplest base units are gallons per minute:
• Base volume unit: gallon
• Base time unit: minute
2. Calculate the conversion factor using the formula below:

1 (gallon per minute)


------------------------------------------------------- = 0.125 (conversion factor)
8 (pints per minute)

Note: 1 gallon/minute = 8 pints/minute.


3. Name the new special mass flow or volume flow measurement unit and its corresponding
totalizer measurement unit:
• Special volume flow measurement unit name: Pint/min
• Volume totalizer measurement unit name: Pints
Special unit parameters are listed and defined in Table 7-7.

Table 7-7 Special unit parameters

Variable Default Description


Base mass unit g Enter the base unit to be used for the special unit for mass flow.
Base mass time Sec Enter the base time unit to be used for the special unit for mass flow.
Mass flow 1.0000 Enter the conversion factor that will be used to calculate the special unit for mass
conversion factor flow.
Mass flow text NONE Enter the name to be used for the special unit for mass flow. The name can contain
up to 8 characters.
Mass total text NONE Enter the name to be used for the mass totalizer. The name can contain up to 8
characters.
Base volume unit l Enter the base unit to be used for the special unit for liquid volume flow.
Base volume time Sec Enter the base time unit to be used for the special unit for liquid volume flow.
Volume flow 1.0000 Enter the conversion factor that will be used to calculate the special unit for liquid
conversion factor volume flow.
Volume flow text NONE Enter the name to be used for the special unit for liquid volume flow. The name can
contain up to 8 characters.
Volume total text NONE Enter the name to be used for the special unit for the liquid volume totalizer. The
name can contain up to 8 characters.
Base gas volume SCF Enter the base unit to be used for the special unit for gas standard volume flow.
unit
Base gas volume Min Enter the base time unit to be used for the special unit for gas standard volume flow.
time
Gas volume flow 1.0000 Enter the conversion factor that will be used to calculate the special unit for gas
conversion factor standard volume flow.
Gas volume flow NONE Enter the name to be used for the special unit for gas standard volume flow. The
text name can contain up to 8 characters.
Gas volume total NONE Enter the name to be used for the special unit for the gas standard volume totalizer.
text The name can contain up to 8 characters.

50 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Inputs

Configuring Security & Language


Density parameters
Density parameters are listed and defined in Table 7-8. Density units are listed in Table 7-9.

Table 7-8 Density parameters

Variable Default Description


3
Density units g/cm • Select the desired unit of density. See Table 7-9.
• Density outputs and displays will indicate density in the selected unit.
Density damping 1.6 sec • Damping filters out noise or the effects of rapid changes in density without
affecting measurement accuracy. See the section entitled Damping later in this
chapter. Range is 0.0–51.2 seconds.
• Milliamp outputs have an additional damping parameter. See Section 8.4.4.
Density cutoff 0.2 g/cm3 • Enter the density value below which density outputs and displays will indicate zero
density. See the section entitled Cutoffs later in this chapter.
Slug low limit 0.000000 • Enter the desired low limit, in g/cm3, for the process density. Range is

Configuring System Data


g/cm3 0.0–10.0 g/cm3.
• The entered value is the density below which a slug flow alarm will be generated.
• For more information about slug flow, see Slug flow alarms in Section 22.7.3.
Slug high limit 5.000000 • Enter the desired high limit, in g/cm3, for the process density. Range is
g/cm3 0.0–10.0 g/cm3.
• The entered value is the density above which a slug flow alarm will be generated.
• For more information about slug flow, see Slug flow alarms in Section 22.7.3.
Slug duration 0.0 sec • Enter the number of seconds for which flow outputs will hold their last measured
flow rate while density is outside the range specified by the slug low limit and slug
high limit. Range is 0.0–60.0 seconds.
• If a value of 0.0 is entered, flow outputs will go to the level that indicates zero flow
as soon as slug flow is detected.
• For more information about slug duration, see Slug flow alarms in Section 22.7.3.

Table 7-9 Density units

Unit Software label

Configuring Inputs
Specific gravity unit SGU (not temperature corrected)
Grams per cubic centimeter g/cm3
Kilograms per cubic meter kg/m3
Pounds per U.S. gallon lb/gal
Pounds per cubic foot lb/cuft
Grams per milliliter g/mL
Kilograms per liter kg/L
Grams per liter g/L
Pounds per cubic inch lb/CuIn
Short ton per cubic yard STon/CuYd
Degrees API deg API
Configuring API

Configuration and Use Manual 51


Configuring Inputs

Temperature parameters
Temperature parameters are listed and defined in Table 7-10.

Table 7-10 Temperature parameters

Variable Default Description


Temperature units degC • Select °Celsius, °Fahrenheit, °Rankine, or °Kelvin.
• Temperature outputs and displays will indicate temperature in the selected
unit.
Temperature damping 4.8 sec • Damping filters out noise or the effects of rapid changes in temperature
without affecting measurement accuracy. See the section entitled Damping
later in this chapter. Range is 0.0–38.4 seconds.
• Milliamp outputs have an additional damping parameter. See Section 8.4.4.

Damping
A damping value is a period of time, in seconds, over which the process variable value will change to
reflect 63% of the change in the actual process. Damping helps the transmitter smooth out small,
rapid measurement fluctuations:
• A high damping value makes the output appear to be smoother because the output must change
slowly.
• A low damping value makes the output appear to be more erratic because the output changes
more quickly.
You can change the damping values for flow (mass and volume), density, and temperature.
When configuring damping values, note the following:
• Liquid volume flow is derived from mass and density measurements; therefore, any damping
applied to mass flow and density will affect liquid volume measurement.
• Gas standard volume flow is derived from mass flow measurement, but not from density
measurement. Therefore, only damping applied to mass flow will affect gas standard volume
measurement.
• You can also configure damping specifically for the milliamp outputs (see Section 8.4.4). If
damping is configured for flow, density, or temperature, the same process variable is assigned
to a milliamp output, and added damping is also configured for the milliamp output, the effect
of damping the process variable is calculated first, and the added damping calculation is
applied to the result of that calculation.
Be sure to set damping values accordingly.
When you specify a new damping value, it is automatically rounded down to the nearest valid
damping value. Flow, density, and temperature have different valid damping values.
Valid damping values are listed in Table 7-11.

Table 7-11 Valid damping values

Process variable Valid damping values


Flow (mass and volume) 0, .2, .4, .8, ... 51.2
Density 0, .2, .4, .8, ... 51.2
Temperature 0, .6, 1.2, 2.4, 4.8, ... 38.4

52 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Inputs

Configuring Security & Language


Cutoffs
Cutoffs are user-defined values below which the transmitter reports a value of zero for the specified
process variable. Cutoffs can be set for mass flow, volume flow, or density.
When setting cutoffs, keep the following points in mind:
• The mass flow cutoff is not applied to the volume flow calculation. Even if the mass flow
drops below the cutoff, and therefore the mass flow indicators go to zero, the volume flow rate
will be calculated from the actual mass flow process variable.
• The density cutoff is applied to the volume flow calculation. Accordingly, if the density drops
below its configured cutoff value, the volume flow rate will go to zero.
• Both mA outputs have cutoffs (see Section 8.4.4). If the mA outputs are configured for mass or
volume flow, and these cutoffs are set to a greater value than the mass and volume cutoffs, the
flow indicators will go to zero when the mA cutoff is reached. If the mA cutoffs are set to a
lower value than the mass or volume cutoff, the flow indicator will go to zero when the mass or

Configuring System Data


volume cutoff is reached.
Be sure to set cutoff values accordingly.

7.3.3 Sensor calibration data


Note: This section is not applicable to the Model 3300 or Model 3350 controller.
Sensor calibration data describe the sensor’s sensitivity to flow, density, and temperature. The term
“characterization” is frequently used to refer to the process of configuring the transmitter with this
information. The characterization procedure depends on whether or not the transmitter is currently
attached to a sensor, and if it is, the sensor type: T-Series or Other.
• If a sensor is currently attached, the transmitter will automatically display the appropriate
calibration parameters for the sensor type.
• If no sensor is currently attached, you must select T-Series Setup and specify:

Configuring Inputs
- Yes – if you want to configure T-Series calibration factors
- No – if you want to configure calibration factors for any other sensor
See Figure 7-1 for a list of the sensor calibration parameters required for your sensor.

Preconfigured calibration data


If the core processor and sensor in your Series 3000 system were ordered together, then the flowmeter
has already been characterized. You need to characterize the flowmeter only if the core processor and
sensor are being paired together for the first time.

Calibration data on sensor tags


The characterization parameters are provided on the sensor tag. The format of the sensor tag varies
depending on your sensor’s date of purchase. See Figures 7-5 and 7-6 for illustrations of newer and
older sensor tags.
Configuring API

Note: On some sensors, the Temperature Coefficient (DT) is shown as TC.

Configuration and Use Manual 53


Configuring Inputs

Figure 7-5 Sample calibration tags – T-Series sensors


Newer tag Older tag

Figure 7-6 Sample calibration tags – All sensors except T-Series


Newer tag Older tag

19.0005.13
12502142824.44
0.0010 12502.000 19.0005.13
0.9980 14282.000 12500142864.44
4.44000 310

Density calibration factors


If your sensor tag does not show a D1 or D2 value:
• For D1, enter the Dens A or D1 value from the calibration certificate. This value is the
line-condition density of the low-density calibration fluid. Micro Motion uses air.
• For D2, enter the Dens B or D2 value from the calibration certificate. This value is the
line-condition density of the high-density calibration fluid. Micro Motion uses water.
If your sensor tag does not show a K1 or K2 value:
• For K1, enter the first 5 digits of the density calibration factor. In the sample tag in Figure 7-6,
this value is shown as 12500.
• For K2, enter the second 5 digits of the density calibration factor. In the sample tag in
Figure 7-6, this value is shown as 14286.
If your sensor does not show an FD value, contact Micro Motion customer service.
If your sensor tag does not show a DT or TC value, enter the last 3 digits of the density calibration
factor. In the sample tag in Figure 7-6, this value is shown as 4.44.

54 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Inputs

Configuring Security & Language


Flow calibration values
Two separate values are used to describe flow calibration: a 6-character FCF value and a 4-character
FT value. Both values contain decimal points. During characterization, these are entered as a single
10-character string that includes two decimal points.
To obtain the required value:
• For older T-Series sensors, concatenate the FCF value and the FT value from the sensor tag, as
shown below.
Flow FCF X.XXXX FT X.XX

• For newer T-Series sensors, the 10-character string is represented on the sensor tag as the FCF
value. The value should be entered exactly as shown, including the decimal points. No
concatenation is required.

Configuring System Data


• For all other sensors, the 10-character string is represented on the sensor tag as the Flow Cal
value. The value should be entered exactly as shown, including the decimal points. No
concatenation is required.

Other calibration values


Temperature calibration factors are described in Table 7-12.
Meter factors allow you to modify the transmitter’s output so that it matches an external measurement
standard. See Chapter 21 for more information.
All other values are configured exactly as they are shown on the sensor tag. Note the following:
• D3 and D4 density factors are used only if a D3 or D4 density calibration has been performed
in the field (see Section 21.5).
• K3 and K4 factors represent the calibration values at D3 and D4 respectively, and are
configured only when the D3 and D4 density factors are configured.

Configuring Inputs
Table 7-12 Temperature calibration values

Variable
T-Series sensors Other sensors Default Description
Temperature slope Temp cal 1.000000 • This value represents the temperature slope. The default
(first 7 characters) value is used for most applications. If you perform a
temperature calibration, this value is updated
automatically.
• To perform a temperature calibration, see Section 21.6.
Contact Micro Motion customer service before performing
a temperature calibration.
Temperature offset Temp cal 0.000000 • This value represents the temperature offset. The default
(last 6 characters) value is used for most applications. If you perform a
temperature calibration, this value is updated
automatically.
• To perform a temperature calibration, see Section 21.6.
Configuring API

Contact Micro Motion customer service before performing


a temperature calibration.

Configuration and Use Manual 55


Configuring Inputs

LD Optimization is a special compensation that is specifically for hydrocarbon liquids. LD


Optimization should not be used with any other process fluids. LD Optimization is available only with
certain large sensor sizes. If your sensor can benefit from LD Optimization, the enable/disable option
will appear in ProLink II or on the display.

CAUTION
If you send the transmitter to a calibration facility to perform a water
calibration, either during startup or any time thereafter, LD Optimization
must be disabled. When you have completed the calibration, re-enable LD
Optimization.

7.3.4 Sensor information


Sensor information includes parameters that serve as references without affecting calibration
parameters, totalizers, or outputs. These parameters are informational and not required.
Sensor information parameters are listed and defined in Table 7-13.

Table 7-13 Sensor information parameters

Variable Default Description


Sensor model no. Uninitialized Automatically set based on calibration data, and cannot be changed.
Sensor serial no. 0 Enter the serial number that is on the sensor serial number tag.
Sensor material Unknown Select the appropriate sensor flow tube material.
Sensor flange Unknown Select the appropriate flange.
Sensor liner None Select the appropriate liner material for the sensor flow tubes.

7.3.5 Discrete inputs


Note: Be sure to distinguish these discrete input parameters from the discrete input parameters
described in Section 7.5, which are used to describe the discrete input signal.
The discrete input parameters allow you to specify a transmitter action that will occur when:
• An ON signal is received from a discrete input (see Section 7.5 for information on configuring
the discrete input signal)
• A discrete event occurs (see Chapter 10 for information on configuring discrete events)
You can assign one or more actions to a single discrete input or discrete event. All assigned actions
will be performed. Actions and assignments for discrete inputs and discrete events are listed and
defined in Table 7-14.
Note: If you are configuring a Model 3300 or Model 3350 controller, refer to Section 7.4 to assign an
action to a discrete input.
Note: To assign a batch control function to a discrete input or a discrete event, see Chapter 11. To
assign a print function to a discrete input or discrete event, see Chapter 15.

56 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Inputs

Configuring Security & Language


Table 7-14 Discrete input actions and assignments

Action Default Assignment Description


Start zero None None Starts the sensor zero process. See Section 16.3.
Discrete input 1
Reset mass total None Resets the value of the mass totalizer to zero.
Discrete input 2
Reset volume total None Discrete event 1 Resets the value of the liquid volume totalizer to zero.
Discrete event 2
Reset GStd vol total None Discrete event 3 Resets the value of the gas standard volume totalizer
Discrete event 4 to zero.
Reset API corrected None Discrete event 5 Resets the value of the API corrected volume totalizer
volume total(1) to zero.
Reset ED standard None Resets the value of the ED standard volume totalizer
volume total(2) to zero.
Reset ED net mass None Resets the value of the ED net mass totalizer to zero.
total(2)

Configuring System Data


Reset ED net volume None Resets the value of the ED net volume totalizer to
total(2) zero.
Reset all totals None Resets the value of all totalizers to zero.
Start/stop all totals None • If totalizers are stopped, starts all totalizers.
• If totalizers are started, stops all totalizers.
Start meter verify(3) None • Starts a Smart Meter Verification test. See
Section 21.2.1.
(1) Displayed only if petroleum measurement application is installed.
(2) Displayed only if enhawnced density application is installed.
(3) Displayed only on systems with Smart Meter Verification.

7.4 Configuring the frequency input


Frequency input parameters define how the frequency input is used to represent process data.
Frequency input parameters are listed and defined in Table 7-15.

Configuring Inputs
Table 7-15 Frequency input parameters

Variable Default Description


Flow rate units kg/min Select the desired unit of mass flow or volume flow. See Table 7-4.
Scaling method Frequency = flow • Select frequency = flow, pulses/unit, or units/pulse.
• The frequency input has a range of 0 to 20,000 Hz.
Frequency 1000.000 Hz If Frequency = flow is selected as the scaling method, enter the frequency (or
pulse rate), in Hz, that represents the configured flow rate.
Flow 999.9999 kg/min If Frequency = flow is selected as the scaling method, enter the flow rate that is
represented by the configured frequency.
Pulses 60.00 pulses If Pulses/unit is selected as the scaling method, enter the number of input
pulses that represents one mass or volume unit.
Units 0.0167 kg If Units/pulse is selected as the scaling method, enter the number of mass or
volume units that is represented by one input pulse.
Configuring API

K-factor 1.0000 • The K-factor is used for proving a Model 3300 or Model 3350 controller, for
which meter factors are not available. To calculate the K-factor, see the
following example. The resulting value must be between 0.0001 and 2.0000.
• The entered value serves as a scaling factor for flow rate outputs and
displays.

Configuration and Use Manual 57


Configuring Inputs

Table 7-15 Frequency input parameters continued

Variable Default Description


(1)
Reset all totals None Specify the discrete input or discrete event that will trigger this action.
Start/Stop all None Specify the discrete input or discrete event that will trigger this action.
totals(1)
(1) Displayed only if you are configuring a Model 3300 or Model 3350 controller.

Example A Model 3300 controller indicates a flow rate of 5483 grams per
minute. Calibration of the reference flow element reveals that the actual
flow rate is 5482 grams per minute.

Use the following formula to calculate the K-factor:


Reference flow rate
K-factor = ----------------------------------------------------
Indicated flow rate

5482 g/min
K-factor = ------------------------------ = 0.9998
5483 g/min

Enter a K-factor of 0.9998.

For more assistance on configuring the frequency input parameters, see the information provided for
configuring the frequency output parameters, in Section 8.5.

7.5 Configuring the discrete inputs


Note: Be sure to distinguish these discrete input parameters from the discrete input parameters
described in Section 7.3.5, which are used to assign actions to discrete inputs and discrete events.
These parameters allow you to describe the signal used by the discrete inputs. You can configure each
discrete input separately. Discrete input options are listed and defined in Table 7-16. See
Section 7.3.5, Section 11.7, and Chapter 15 for a discussion of the different actions that can be
triggered by a discrete input.

Table 7-16 Discrete input parameters

Polarity Default Description


Active low Active low • The input is considered active when the input level is between 0.0 and 0.8 V.
• The input is considered inactive when the input level is between 3.0 and
30.0 V.
Active high • The input is considered active when the input level is between 3.0 and
30.0 V.
• The input is considered inactive when the input level is between 0.0 and
0.8 V.

58 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Inputs

Configuring Security & Language


7.6 Configuring the external inputs
External input parameters are used to configure polling. Polling is used to retrieve temperature or
pressure data from an external device over a HART/Bell 202 connection. You may poll for either
temperature or pressure, or both.
Note: Pressure compensation and external temperature are optional. Configure pressure
compensation only if your sensor is subject to pressure effect and if the operating pressure is
significantly different from calibration pressure. External temperature compensation is used to
provide an external temperature value for the petroleum measurement application or the enhanced
density application. If you have core processor v2.1 or earlier, the external temperature data is used
for all calculations that require temperature values. If you have core processor v2.2 or later, the
external temperature data is used only for calculation of the derived variable in enhanced density
applications or the CTL (Correction for Temperature on volume of Liquids) value in petroleum
measurement applications. To determine your core processor version, use the Applications List from
the View menu (see Section 17.5.9).

Configuring System Data


Note: If you poll for temperature or pressure, ensure that the external measurement device is accurate
and reliable.
To set up polling, you must configure the external input parameters and you must also ensure that the
primary milliamp output has been wired for HART protocol (see Section 3.4). The external input
parameters are listed and defined in Table 7-17.

Table 7-17 External input parameters

Variable Default Description


Polling control Do not poll You can configure polling control for an external temperature device, an
external pressure device, or both:
• Do not poll – polling will not occur.
• Poll as primary – The Series 3000 device will poll the external HART device
as a primary master. Choose this option if the external device will probably
be accessed by another device acting as a secondary master (e.g., a HART

Configuring Inputs
Communicator).
• Poll as secondary – The Series 3000 device will poll the external HART
device as a secondary master. Choose this option if the external device will
probably be accessed by another device acting as a primary master.
If polling both a temperature device and a pressure device, you must configure
the same polling control method for both. In other words, you cannot poll one
external device as a primary master and the other external device as a
secondary master. However, you can disable polling for one device, then poll
the other device as either a primary or secondary master.
Polling variable None Select the process data to be polled through this polling variable:
• Temperature
• Pressure
• None
External tag NONE Enter the HART tag of the external device to be polled for temperature or
pressure.
Pressure Disable • Select Enable to enable pressure compensation.
compensation(1) • Select Disable to disable pressure compensation.
Configuring API

Pressure units PSI Select the pressure unit that is used by the remote device that you are polling
for pressure.
Flow factor(1) 0.0000 % per PSI The percent change in the flow rate per PSI. Not all sensors or applications
require a pressure correction factor for flow. For the value to be used, see the
product data sheet for your sensor, then reverse the sign of the value listed for
pressure effect for flow (e.g., if the pressure effect is 0.000004 % per PSI,
enter a pressure correction factor of –0.000004 % per PSI).

Configuration and Use Manual 59


Configuring Inputs

Table 7-17 External input parameters continued

Variable Default Description


(1)
Density factor 0.0000 g/cm3 per The change in fluid density per PSI. Not all sensors or applications require a
PSI pressure correction factor for density. For the value to be used, see the product
data sheet for your sensor, then reverse the sign of the value listed for
pressure effect for density (e.g., if the pressure effect is 0.000004 % per PSI,
enter a pressure correction factor of –0.000004 % per PSI).
Calibration 0.0000 PSI The pressure at which the flowmeter was calibrated (which therefore defines
pressure(1) the pressure at which there will be no effect on the calibration factor). Refer to
the calibration document shipped with your sensor. If the data is unavailable,
use 20 psi.
External Disable • Select Enable to enable external temperature compensation.
temperature • Select Disable to disable external temperature compensation.
compensation(2)
(1) Displayed only if Polling Variable is set to Pressure.
(2) Displayed only if Polling Variable is set to Temperature.

60 Micro Motion® Series 3000 MVD Transmitters and Controllers


Chapter 8

Configuring Events
Configuring Outputs

8.1 About this chapter


This chapter explains how to configure outputs. Outputs include all the software parameters listed in
Figure 8-1.
Failure to perform configuration tasks in the proper sequence could result in an incomplete
configuration. See Section 1.7 for the recommended configuration sequence.

Configuring Batch
CAUTION
Changing configuration can affect device operation.

Set control devices for manual operation before changing device configuration.

8.2 Outputs menu


Use the Outputs menu, shown in Figure 8-1, to access and configure output parameters. The Outputs
menu is accessed through the Configuration option of the Management menu. To access the
Management menu, see Chapter 4. You will be configuring:
• Discrete outputs

Configuring Outputs
• Milliamp (mA) outputs
• Frequency output

Configuring Process Monitor

Configuration and Use Manual 61


Configuring Outputs

Figure 8-1 Outputs menu

Outputs

Discrete outputs Milliamp outputs Frequency output

Discrete output 1 2 3 Milliamp output 1 2 Flow source


• Mass flow rate
• Line (gross) volume flow rate(5)
• Gas standard volume flow rate(8)
• API: Temp corrected (standard)
Polarity Fault indication volume flow(6)
• Active high • Condition • ED: Standard volume flow rate(7)
• Active low • Setting • ED: Net mass flow rate(7)
• Last measured value timeout • ED: Net volume flow rate(7)
Assignment • Frequency input flow rate
• Discrete input 1 Variable assignment
• Discrete input 2 • Mass flow rate Scaling method
• Discrete event 1 • Temperature • Frequency = flow
• Discrete event 2 • Density • Pulses/unit
• Discrete event 3 • Line (gross) volume flow rate(5) • Units/pulse
• Discrete event 4 • API: Temp corrected density(6)
• Discrete event 5 • API: Temp corrected (standard) Frequency(10)
• Flow switch volume flow(6) Flow(10)
• Flow direction • API: Batch weighted average Pulses/unit(11)
• Cal in progress density(6) Units/pulse(12)
• Fault condition • API: Batch weighted average Max. pulse width
• Batch timeout(1) temperature(6)
• Batch in progress(1) • ED: Density at reference(7) Power
• Batch end warn(1) • ED: Density (fixed SGU)(7) • Active
• Batch overrun(1) • ED: Standard volume flow rate(7) • Passive
• Batch pump(1) • ED: Net mass flow rate(7)
• Batch primary valve(1) • ED: Net volume flow rate(7) Polarity
• Batch secondary valve(1)(2) • ED: Concentration(7) • Active high
• Printer job status(3) • Drive gain • Active low
• Display error(3) • External pressure
• None • External temperature Fault indication
• Gas standard volume flow rate(8) • Downscale
Fault indication • Frequency input flow rate • Upscale
• Internal zero
Flow switch source(4) Calibration span • None
• 20 mA
(4)
Flow switch setpoint • 4 mA Fault frequency(13)
• Low flow cutoff Last measured value timeout
Switch hysteresis(4) • Damping seconds
• 4.0 mA minimum(9)
• 20.0 mA maximum(9)
• Minimum span(9)

(1) Displayed only if discrete batch application is installed. May also require corresponding batch control function enabled.
(2) Displayed only if No. of Stages is set to 2.
(3) Displayed only if custody transfer application is installed and World Area is set to OIML
(4) Displayed only if Flow Switch is selected.
(5) Displayed only if Volume Flow Type is set to Liquid.
(6) Displayed only if petroleum measurement application is installed.
(7) Displayed only if enhanced density application is installed.
(8) Displayed only if Volume Flow Type is set to Gas Standard.
(9) Read-only; calculated by transmitter according to sensor model.
(10) Displayed only if Frequency = Flow is selected.
(11) Displayed only if Pulses/unit is selected.
(12) Displayed only if Units/pulse is selected.
(13) Displayed only if Fault Indication is set to Upscale.

62 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Outputs

8.3 Configuring the discrete outputs

Configuring Events
You can configure one, two, or three discrete outputs. For each discrete output, you will configure:
• Polarity
• Assignment
• Fault indication
Discrete outputs can be connected to factory-supplied or user-supplied relays. For relay installation
instructions, see Appendix D. For specifications of the Model 3100 relay supplied by Micro Motion,
see Appendix C.

8.3.1 Polarity
The discrete outputs generate two voltage levels to represent ON or OFF states. The voltage levels
depend on the output’s polarity, as shown in Table 8-1. Figure 8-2 shows a diagram of a typical
discrete output circuit.

Configuring Batch
Table 8-1 Discrete output polarity

Polarity Description
Active high • The circuit provides a pull-up to 24 V when asserted (when condition tied
to DO is true).
• The circuit provides 0 V when not asserted (when condition tied to the DO
is false).

Active low • The circuit provides 0 V when asserted (when condition tied to DO is
true).
• The circuit provides a pull-up to 24 V when not asserted (when condition
tied to the DO is false).

Figure 8-2 Discrete output circuit

Configuring Outputs
+24 V (Nom)

3.2 k

Out+
Configuring Process Monitor

Out–

Configuration and Use Manual 63


Configuring Outputs

8.3.2 Source variable assignment


The ON/OFF states of the discrete output are controlled by the discrete input, discrete event, or
process condition assigned to the discrete output as a source variable. See Table 8-2.
When the discrete batch application is installed, one or more of the discrete outputs must be used to
control the pump, primary valve, or secondary valve. See the following section entitled Discrete batch
requirements.

CAUTION
If “batch in progress” is assigned to a discrete output, connecting the output
to a system pump can cause batch overrun or a deadhead pump.

To avoid batch overrun or a deadhead pump, do not connect a discrete output to a


pump if “batch in progress” is assigned to the output.

Table 8-2 Discrete output source variables

Source variable Default Description


None None The discrete output is inactive.
Discrete input 1 The discrete output will be controlled by discrete input 1.
Discrete input 2 The discrete output will be controlled by discrete input 2.
Discrete event 1 The discrete output will be controlled by discrete event 1.
Discrete event 2 The discrete output will be controlled by discrete event 2.
Discrete event 3 The discrete output will be controlled by discrete event 3.
Discrete event 4 The discrete output will be controlled by discrete event 4.
Discrete event 5 The discrete output will be controlled by discrete event 5.
Flow switch The discrete output will be controlled by the occurrence of a flow switch.
See the section entitled Flow switch later in this chapter.
Flow direction The discrete output will be controlled by the flow direction.
Calibration in progress The discrete output ON state will indicate calibration in progress.
Fault condition The discrete output will indicate any condition that produces a fault alarm.
For information about fault alarms, see Section 22.6.
Batch timeout At start of batch or at any time before batch completion, the discrete output will
be active if no flow has been measured for the amount of time configured for
time out.
Batch in progress The discrete output will indicate the batch is in progress.
• “Batch in progress” is a status indicator only.
• Because “batch in progress” remains active until the batch is completed or
ended, using “batch in progress” to control a pump can cause batch overrun
or a deadhead pump.
Batch end warn The discrete output will indicate when the batch total has exceeded the
percent of target or quantity subtracted from target that is configured for batch
end warn.
Batch overrun The discrete output will indicate when the batch total has exceeded the
amount configured for batch overrun.
Batch pump The discrete output will control the system pump. The pump remains on while
the primary or secondary valve is open.
Batch primary valve The discrete output will control the primary valve.

64 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Outputs

Table 8-2 Discrete output source variables continued

Configuring Events
Source variable Default Description
Batch secondary valve The discrete output will control the secondary valve.
(1)
Printer job status If Printer Type is set to FDW, the discrete output will be activated if either of the
following is true:
• The last ticket print request failed.
• Flow rate is not zero.
If Printer Type is set to Epson, the discrete output will be activated if either of
the following is true:
• The printer is out of paper.
• Flow rate is not zero.
Printer job status is not supported for other printer types.
Display error The discrete output will indicate when a display error has occurred (custody
transfer only).
(1) Displayed only if custody transfer application is installed and World Area is set to OIML.

Configuring Batch
Flow switch
Flow switch is used to indicate that the flow rate of the flow switch source (e.g., mass flow, liquid
volume flow) has dropped below the flow switch setpoint.
The flow switch source specifies the flow variable that will be monitored. Any flow variable,
including gas standard volume flow and petroleum measurement or enhanced density flow variables,
can be assigned as the flow switch source.
The flow switch has a user-configurable hysteresis. Hysteresis defines a range around the setpoint
within which the flow switch will not change. The default hysteresis value is 5%. The valid range is
0.1% to 10%. At startup, the flow switch is OFF.
For example, if the flow switch setpoint is 100 g/sec and the first reading is below 95 g/sec, the flow
switch turns ON and will stay ON until the flow rate rises above 105 g/sec. At this point it turns OFF,
and will stay off until the flow rate drops below 95 g/sec.

Configuring Outputs
Note: It is possible to assign flow switch to more than one discrete output, but they will all use the
same setpoint and hysteresis.

Discrete batch requirements


If discrete batching is enabled, there are specific requirements for discrete output assignment:
• If 1-stage operation is specified, one discrete output must be assigned to either Batch Pump or
Primary Valve.
• If 2-stage operation is specified:
- One discrete output must be assigned to Primary Valve.
- One discrete output must be assigned to Secondary Valve.
- One discrete output may optionally be assigned to Batch Pump.
Configuring Process Monitor

8.3.3 Fault indication


The Fault Indication parameter specifies the state of the discrete output if a fault occurs. Options for
Fault Indication are shown in Table 8-4.

Configuration and Use Manual 65


Configuring Outputs

Table 8-3 Discrete output fault indication and values

Discrete output state


Condition Polarity = Active High Polarity = Active Low
Upscale • Fault: DO is ON (site-specific voltage) • Fault: DO is OFF (0 V)
• No fault: DO is controlled by its assignment • No fault: DO is controlled by its assignment
Downscale • Fault: DO is OFF (0 V) • Fault: DO is ON (site-specific voltage)
• No fault: DO is controlled by its assignment • No fault: DO is controlled by its assignment
None DO is controlled by its assignment

Note: The Fault Indication parameter is designed to put the discrete output in a safe state during a
fault condition, and not to indicate that a fault condition is present. If you want to use the discrete
output to indicate faults, assign Fault Condition to the discrete output as described in Section 8.3.2,
and set Fault Indication to None. If you do this, the logical state of the discrete output will be ON
whenever a fault condition is active, and OFF otherwise.

8.4 Configuring the milliamp outputs


Configuring milliamp outputs includes the following procedures:
• Specifying the milliamp output to be configured
• Configuring fault indication
• Assigning a process variable to the output
• Configuring the calibration span

8.4.1 Milliamp output


Select Milliamp Output 1 or Milliamp Output 2.

8.4.2 Fault indication


To configure fault indication, you must specify:
• Condition
• Setting (only if Condition is set to Upscale or Downscale)
• Last Measured Value Timeout
The Condition parameter specifies the fault indication, or the state of the milliamp output if a fault
occurs. Options for Condition are shown in Table 8-4.

CAUTION
Using Internal zero or None may hamper identification of fault outputs.

To make sure fault outputs can be identified, select Downscale or Upscale.

If Upscale or Downscale is specified, you must also configure the fault indication Setting. Setting
ranges and defaults are shown in Table 8-4.

66 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Outputs

By default, the Series 3000 device immediately reports a fault when a fault is encountered. You can
delay reporting faults by changing the fault timeout. Last Measured Value Timeout specifies the time,

Configuring Events
in seconds, that the milliamp output will report its last valid measurement after a fault condition has
been detected. After the timeout has expired, the milliamp output will report its configured fault
condition.

Table 8-4 Fault indication parameters for milliamp outputs

Parameter Default Description Setting(1)


Condition / Upscale Downscale • If Condition is set to Upscale, and a fault Range: 21.0 to 24.0 mA
condition occurs, the milliamp output will Default: 22.0 mA
transmit this level of current.
Condition / Downscale • If Condition is set to Downscale, and a fault Range: 1.0 to 3.6 mA
condition occurs, the milliamp output will Default: 2.0 mA
transmit this level of current.
Condition / Internal • Goes to the mA value that represents a value of Not applicable

Configuring Batch
zero 0.0 for the process variable.
• An apparent value of 0.0 for the process
variable could indicate a fault.
Condition / None • The milliamp output never indicates a fault Not applicable
condition.
• The milliamp output always transmits process
variable data.
Last measured value 0 sec • Enter the value, in seconds, that the Not applicable
timeout Series 3000 device will continue to report its last
valid measurement after a fault condition has
been detected. Range is 0.0–60.0 seconds.(2)
(1) The Setting parameter is displayed only if Condition is set to Upscale or Downscale.
(2) This parameter can also be set in the frequency output menu. Only one value is stored. If you change the fault timeout in the mA output
menu, the value displayed in the frequency output menu is changed, and vice versa.

Configuring Outputs
8.4.3 Process variable
For the selected milliamp output, select a process variable. The milliamp output level will vary
according to the value of this process variable, within the limits defined by the calibration span
parameters (see the following section).

CAUTION
Changing the process variable assignment without verifying the milliamp
output range can produce process error.

When the process variable assignment is changed, the milliamp output range
parameters will be changed automatically. The new output range may or may not
be appropriate for the process. To avoid causing process error, always verify the
Configuring Process Monitor

milliamp output range parameters (LRV and URV) after changing the process
variable assignment. See Section 8.4.4.

8.4.4 Calibration span


Calibration span defines the range, scale, and related parameters for the milliamp output. See
Table 8-5.

Configuration and Use Manual 67


Configuring Outputs

Table 8-5 Calibration span variables

Variable Default Description


20 mA Sensor limit for selected (Upper range value, or URV) Enter the value the output will
process variable represent at 20.0 mA. See the section entitled LRV and URV.
4 mA (Lower range value, or LRV) Enter the value the output will represent
at 4.0 mA. See the section entitled LRV and URV.
Low flow cutoff(1) 0.0 for all flow variables • If a flow variable is assigned to the output, the low flow cutoff is the
flow rate below which the output will indicate zero flow.
• If the value entered here is less than the value configured for mass
or volume low flow cutoff, this value will have no effect. See the
section entitled Multiple cutoffs.
Damping 0 sec • Select the amount of added damping for the milliamp output.
seconds(2) • Damping is added to damping that has been configured for flow,
density, or temperature. See the section entitled Multiple damping
parameters.
4.0 mA minimum Not applicable The lowest value that can be represented by the output, as
(read-only) determined by sensor limit.
20.0 mA The highest value that can be represented by the output, as
maximum determined by sensor limit.
Minimum span The smallest allowable difference between the value represented at
4.0 mA and the value represented at 20.0 mA, as determined by
sensor limit.
(1) For most applications, the Low Flow Cutoff default value is used. Contact Micro Motion customer service before changing the Low
Flow Cutoff parameter.
(2) For most applications, the Damping Seconds default value is used. Contact Micro Motion customer service before changing the
Damping Seconds parameter.

LRV and URV


Each process variable that can be assigned to a milliamp output has its own 20 mA and 4 mA value
(URV and LRV). If you assign a different process variable to a milliamp output, the corresponding
LRV and URV are loaded and used. Default LRV and URV settings are listed in Table 8-6.

Table 8-6 Default LRV and URV

Process variable LRV URV


All mass flow variables –200.000 g/s 200.000 g/s
All liquid volume flow variables –0.200 l/s 0.200 l/s
3
All density variables 0.000 g/cm 10.000 g/cm3
All temperature variables –240.000 °C 450.000 °C
Drive gain 0.000% 100.000%
Gas standard volume flow –423.78 SCFM 423.78 SCFM
External temperature –240.000 °C 450.000 °C
External pressure 0.000 bar 100.000 bar
Enhanced density concentration 0% 100%
Enhanced density Baume 0 10
Enhanced density specific gravity 0 10

68 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Outputs

Note: Beginning with rev7.0 of the transmitter software, if the LRV and URV are changed from the
defaults, and the milliamp output source is later changed, the LRV and URV will not be reset to their

Configuring Events
default values. For example, if mass flow is assigned to the milliamp output, and the LRV and URV for
mass flow are changed, then density is assigned to the milliamp output, and finally mass flow is
reassigned to the milliamp output, the LRV and URV for mass flow are reset to the configured values.
In earlier versions of the transmitter software, the LRV and URV were reset to factory default values.

Multiple cutoffs
Cutoffs can be configured for the mA output and also for the mass flow and volume flow process
variables. If mass flow or volume flow has been assigned to an mA output, a non-zero value is
configured for the flow cutoff (see Section 7.3), and the mA output’s Low Flow Cutoff is also
configured, the cutoff occurs at the highest setting, as shown in the following examples.

Example Configuration:
• Primary mA output: Mass flow

Configuring Batch
• Frequency output: Mass flow
• AO cutoff for primary mA output: 10 g/sec
• Mass flow cutoff: 15 g/sec

As a result, if the mass flow rate drops below 15 g/sec, all outputs
representing mass flow will report zero flow.

Example Configuration:
• Primary mA output: Mass flow
• Frequency output: Mass flow
• AO cutoff for primary mA output: 15 g/sec

Configuring Outputs
• Mass flow cutoff: 10 g/sec

As a result:
• If the mass flow rate drops below 15 g/sec but not below 10 g/sec:
- The primary mA output will report zero flow.
- The frequency output will report nonzero flow.
• If the mass flow rate drops below 10 g/sec, both outputs will report
zero flow.

See Section 7.3 for information on the mass flow, volume flow, and density cutoffs.
Configuring Process Monitor

Multiple damping parameters


Damping can be configured for the mA output and also for the mass flow, volume flow, density, and
temperature process variables. If damping has been configured for the process variable assigned to an
mA output (see Section 7.3), and a non-zero value is configured for Damping Seconds for the same
mA output, the effect of damping the process variable is calculated first, and the Damping Seconds
calculation is applied to the result of that calculation. See the following example.

Configuration and Use Manual 69


Configuring Outputs

Example Configuration:
• Flow damping: 1
• Primary mA output: Mass flow
• Frequency output: Mass flow
• Primary milliamp output damping seconds: 2

As a result:
• A change in mass flow will be reflected in the primary mA output
over a time period that is greater than 3 seconds. The exact time
period is calculated by the Series 3000 device according to internal
algorithms which are not configurable.
• The frequency output level changes over a 1-second time period
(the Flow Damping value). It is not affected by the Damping
Seconds parameter.

8.5 Configuring the frequency output


Table 8-7 lists and defines the parameters that can be set for the frequency output.

CAUTION
Using Internal zero or None may hamper identification of fault outputs.

To make sure fault outputs can be identified, select Downscale or Upscale.

Table 8-7 Frequency output variables


Variable Default Description
Flow source Mass flow rate Specifies the process variable that the frequency output will represent.
Select one of the following:
• Frequency input flow rate
• Mass flow rate
• Volume flow rate (liquid)(1)
• Gas standard volume flow rate(1)
• API corr volume flow (available only if petroleum measurement
application is installed)
• Std vol flow (available only if enhanced density application is installed
and configured to indicate standard volume flow)
• Net mass flow (available only if enhanced density application is installed
and configured to indicate net mass flow)
• Net vol flow (available only if enhanced density application is installed
and configured to indicate net volume flow)
The output received at the external device can be totalized or used to
control the process.
Scaling method Frequency = flow Select Frequency = flow, Pulses/unit, or Units/pulse.
(2)
Frequency 1000.000 Hz • Enter the value, in Hz, that will represent the value configured for Flow.
To calculate the Frequency value, see Section 8.5.1.
• The frequency output has a range of 0 to 10,000 Hz.
Flow(2) 16666.6699 g/sec Enter the maximum flow rate that is appropriate to your application. See
Section 8.5.1.
Pulses/unit(3) 0.0600 Enter the number of output pulses that will represent one mass or volume
unit.

70 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Outputs

Table 8-7 Frequency output variables continued

Configuring Events
Variable Default Description
(4)
Units/pulse 16.6700 g Enter the number of mass or volume units that will be represented by one
output pulse.
Maximum pulse 277 ms • The pulse width can be configured for output frequencies below 500 Hz.
width • Enter the desired pulse width in milliseconds: minimum value is 0.5 ms,
maximum value is 277.2352 ms.
• For more information, see Section 8.5.2.
Power Active Select Active or Passive operation for the frequency output.
• Voltage is 24 VDC nominal for active operation, 30 VDC applied
maximum for passive operation.
• Sourcing current is 10 mA at 3 VDC for active operation.
• Sinking current is 500 mA for active or passive operation.
Polarity Active high Specifies how the frequency output will represent an active state.
• Active high – The active state is represented by the frequency output’s
high value.
• Active low – The active state is represented by the frequency output’s low

Configuring Batch
value.
Fault indication Downscale • Downscale: Output goes to 0 Hz.
• Upscale: Output goes to configured Fault frequency value.
• Internal zero:
- Output goes to 0 Hz.
- An apparent no-flow condition could indicate a fault.
• None:
- The frequency output never indicates a fault condition.
- The frequency output always transmits process variable data.
Fault frequency 15000.000 • Enter the value, in Hz, that will be transmitted during fault conditions if
the fault indicator is set to Upscale. Minimum value is 10.000, maximum
value is 15000.000.
Last measured value 0 sec • Enter the value, in seconds, that the Series 3000 device will continue to
timeout report its last valid measurement after a fault condition has been
detected.(5)
(1) Either liquid or gas standard volume flow rate is available, depending on the setting of Volume Flow Type (see Section 7.3.2).

Configuring Outputs
(2) Displayed only if Scaling Method is set to Frequency = Flow.
(3) Displayed only if Scaling Method is set to Pulses/unit.
(4) Displayed only if Scaling Method is set to Units/pulse.
(5) This parameter can also be set in the milliamp output menu. Only one value is stored. If you change the fault timeout in the milliamp
output menu, the value displayed in the frequency output menu is changed, and vice versa.

8.5.1 Frequency = flow


If you specify Frequency = Flow, you must also specify Frequency and Flow. Flow is defined as the
maximum flowrate appropriate to your application. Frequency can then be calculated using the
following formula:
Configuring Process Monitor

Flow
Frequency = ------------  N
T

Configuration and Use Manual 71


Configuring Outputs

where:
• Flow = maximum appropriate flowrate (Flow in configuration)
• T = factor to convert selected flow time base to seconds
• N = number of pulses per flow unit, as configured in the receiving device
The resulting Frequency value must be within the range of the frequency output (0 to 10,000 Hz).
• If the Frequency value is less than 1 Hz, reconfigure the receiving device for a higher
pulses/unit setting.
• If the Frequency value is greater than 10,000 Hz, reconfigure the receiving device for a lower
pulses/unit setting.

Example Maximum appropriate flowrate (Flow) is 2000 lbs/min.


Receiving device is configured for 10 pulses/pound.

Solution:
Flow
Frequency = ------------  N
T

2000
Frequency = -------------  10
60

Frequency = 333.33

Series 3000 device configuration:


• Frequency = 333.33
• Flow = 2000

8.5.2 Maximum pulse width


The frequency output maximum pulse width defines the maximum duration of the “active” portion of
the wave that the Series 3000 device sends to the frequency receiving device. The active portion may
be the high voltage or 0.0 V, depending on the polarity setting, as shown in Figure 8-3.

Figure 8-3 Pulse width


Pulse width
Polarity = Active High

Pulse width

Polarity = Active Low

72 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Outputs

Maximum Pulse Width can be set to 0, or to values between 0.5 and 277.2352 milliseconds. The
user-entered value is adjusted automatically to the nearest valid value. If Maximum Pulse Width is set

Configuring Events
to 0, the output will have a 50% duty cycle, independent of the output frequency. A 50% duty cycle is
illustrated in Figure 8-4.

Figure 8-4 50% duty cycle

If Maximum Pulse Width is set to a non-zero value, the duty cycle is controlled by the crossover
frequency:

Configuring Batch
• At frequencies below the crossover frequency, the duty cycle is determined by the pulse width
and the frequency.
• At frequencies above the crossover frequency, the output changes to a 50% duty cycle.
The crossover frequency is calculated as follows:

1
Crossover frequency = ----------------------------------------------------
2  max pulse width

You can change the setting for Maximum Pulse Width so that the Series 3000 device will output a
pulse width appropriate to your receiving device:
• High-frequency counters such as frequency-to-voltage converters, frequency-to-current
converters, and Micro Motion peripherals usually require approximately a 50% duty cycle.
• Electromechanical counters and PLCs that have low-scan cycle rates generally use an input
with a fixed non-zero state duration and a varying zero state duration. Most low-frequency

Configuring Outputs
counters have a specified requirement for Maximum Pulse Width.
Note: For typical applications, the default pulse width is used.

Example The frequency output is wired to a PLC with a specified pulse width
requirement of 50 ms. The crossover frequency is 10 Hz.

Solution:
• Set Maximum Pulse Width to 50 ms.
• For frequencies less than 10 Hz, the frequency output will have a
50 msec ON state, and the OFF state will be adjusted as required.
For frequencies higher than 10 Hz, the frequency output will be a
square wave with a 50% duty cycle.
Configuring Process Monitor

Note: If you are using the Freq = Flow output scale method, and you set Maximum Pulse Width to a
non-zero value, Micro Motion recommends setting the frequency factor to a value below 200 Hz. See
Section 8.5.1. If you are using the Pulses/unit or Units/pulse output scale method, Maximum Pulse
Width must be set to a value that allows crossover to occur.

Configuration and Use Manual 73


74 Micro Motion® Series 3000 MVD Transmitters and Controllers
Configuring Security & Language
Chapter 9
Configuring the Petroleum Measurement
Application

9.1 About this chapter


This chapter explains how to configure the petroleum measurement application (API feature). The

Configuring System Data


petroleum measurement parameters include all the software parameters listed in Figure 9-1.
Note: The petroleum measurement application is an optional feature of the Series 3000 platform, and
may not be installed on your equipment. To verify that it is installed, use the View menu to list all
installed applications (see Section 17.5).
Failure to perform configuration tasks in the proper sequence could result in an incomplete
configuration. See Section 1.7 for the recommended configuration sequence.

CAUTION
Changing configuration can affect device operation.

Set control devices for manual operation before changing device configuration.

Configuring Inputs
9.2 API menu
Use the API menu, shown in Figure 9-1, to access and configure petroleum measurement parameters.
The API menu is a submenu of the Measurements menu, which is accessed through the Configuration
option of the Management menu. To access the Management menu, see Chapter 4.

Figure 9-1 API menu

Measurements

Discrete events Density functions API


See Chapter 10 See enhanced density manual
Configuring API

• Table type
• User defined TEC(1)
• Temperature units(2)
(1) Displayed only if Table Type is set to 6C, 24C, or 54C. • Density units(2)
(2) Read-only. • Reference temperature(3)
(3) Read-only unless Table Type is set to 53x or 54x.

Configuration and Use Manual 75


Configuring the Petroleum Measurement Application

9.3 About petroleum measurement


The petroleum measurement application enables Correction of Temperature on volume of Liquids, or
CTL. In other words, some applications that measure liquid volume flow or liquid density are
particularly sensitive to temperature factors, and must comply with American Petroleum Institute
(API) standards for measurement.
The petroleum measurement parameters determine the values that will be used in API-related
calculations. The petroleum measurement parameters are available only if the petroleum measurement
application is installed on your Series 3000 device.

9.3.1 Definitions
The following terms and definitions are used in this chapter:
• API – American Petroleum Institute
• CTL – Correction for Temperature on volume of Liquids. The CTL value is used to calculate
the VCF value
• TEC – Thermal Expansion Coefficient
• VCF – Volume Correction Factor. The correction factor to be applied to volume process
variables. VCF can be calculated after CTL is derived

9.3.2 CTL derivation methods


There are two derivation methods for CTL:
• Method 1 is based on observed density and observed temperature.
• Method 2 is based on a user-supplied reference density (or thermal expansion coefficient, in
some cases) and observed temperature.
The choice of reference table determines the derivation method to be used, as discussed in
Section 9.4.1.

9.4 Configuring petroleum measurement parameters


The petroleum measurement parameters are listed and defined in Table 9-1.

Table 9-1 Petroleum measurement parameters


Variable Description
Table type Select the table that matches your requirements. See Section 9.4.1.
User defined TEC(1) Thermal expansion coefficient. Enter value to be used in CTL calculation.
Temperature units(2) Read-only. Displays the unit used for reference temperature in the reference table.
Density units Read-only. Displays the unit used for reference density in the reference table.
Reference Read-only unless Table type is set to 53x or 54x. If configurable:
temperature • Specify the reference temperature to be used in CTL calculation.
• Enter reference temperature in °C.
(1) Displayed only if Table Type is set to 6C, 24C, or 54C.
(2) In most cases, the temperature unit used by the API reference table should also be the temperature unit configured for the device to
use in general processing. To configure the temperature unit, see Section 7.3.

76 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring the Petroleum Measurement Application

Configuring Security & Language


9.4.1 Reference tables
Reference tables are organized by reference temperature, CTL derivation method, liquid type, and
density unit. The table selected here controls all the remaining options.
• Reference temperature:
- If you specify a 5x, 6x, 23x, or 24x table, the default reference temperature is 60 °F, and
cannot be changed.
- If you specify a 53x or 54x table, the default reference temperature is 15 °C. However, you
can change the reference temperature, as recommended in some locations (for example, to
14.0 or 14.5 °C).
• CTL derivation method:
- If you specify an odd-numbered table (5, 23, or 53), CTL will be derived using Method 1
(described in Section 9.3.2).
- If you specify an even-numbered table (6, 24, or 54), CTL will be derived using Method 2

Configuring System Data


(described in Section 9.3.2).
• The letters A, B, C, or D that are used to terminate table names define the type of liquid that the
table is designed for:
- A tables are used with generalized crude and JP4 applications.
- B tables are used with generalized products.
- C tables are used with liquids with a constant base density or known thermal expansion
coefficient.
- D tables are used with lubricating oils.
• Different tables use different density units:
- Degrees API
- Relative density (SG)
- Base density (kg/m3)

Configuring Inputs
Table 9-2 summarizes these options.

Table 9-2 API reference temperature tables


CTL Density unit and range
derivation
Table method Base temperature Degrees API Base density Relative density
5A Method 1 60 °F, non-configurable 0 to 100
5B Method 1 60 °F, non-configurable 0 to 85
5D Method 1 60 °F, non-configurable –10 to +40
23A Method 1 60 °F, non-configurable 0.6110 to 1.0760
23B Method 1 60 °F, non-configurable 0.6535 to 1.0760
23D Method 1 60 °F, non-configurable 0.8520 to 1.1640
53A Method 1 15 °C, configurable 610 to 1075 kg/m3
Configuring API

53B Method 1 15 °C, configurable 653 to 1075 kg/m3


53D Method 1 15 °C, configurable 825 to 1164 kg/m3
Reference temperature Supports
6C Method 2 60 °F, non-configurable 60 °F Degrees API
24C Method 2 60 °F, non-configurable 60 °F Relative density
54C Method 2 15 °C, configurable 15 °C Base density in kg/m3

Configuration and Use Manual 77


Configuring the Petroleum Measurement Application

9.4.2 Temperature data


For the temperature value to be used in CTL calculation, you can use the temperature data from the
sensor, or you can poll an external temperature device:
• To use temperature data from the sensor, no action is required.
• To poll an external temperature device, configure polling for temperature as described in
Section 7.6. When polling is enabled, the Series 3000 device will automatically use the
external temperature value for CTL calculation.

78 Micro Motion® Series 3000 MVD Transmitters and Controllers


Chapter 10

Configuring Events
Configuring Discrete Events

10.1 About this chapter


This chapter explains how to configure discrete events. Discrete events include all the software
parameters listed in Figure 10-1.
Failure to perform configuration tasks in the proper sequence could result in an incomplete
configuration. See Section 1.7 for the recommended configuration sequence.

Configuring Batch
CAUTION
Changing configuration can affect device operation.

Set control devices for manual operation before changing device configuration.

10.2 Discrete events menu


Use the Discrete Events menu, shown in Figure 10-1, to access and configure discrete event
parameters. The Discrete Events menu is a submenu of the Measurements menu, which is accessed
through the Configuration option of the Management menu. To access the Management menu, see
Chapter 4.

Configuring Outputs
10.3 About discrete events
A discrete event occurs if the real-time value of a user-specified process variable varies beyond a
user-specified value.
Discrete events are used to perform specific actions on the Series 3000 platform. For example, the
discrete event can be defined to activate a discrete output if the flow rate is outside a specified range.
Note: In rev7.0 of the Series 3000 firmware, discrete events are available on all Series 3000 devices.
In previous firmware versions, discrete events were available only on the Model 3500 and Model 3700
transmitters; they were not available on the Model 3300 and Model 3350 controllers.
Configuring Process Monitor

Configuration and Use Manual 79


Configuring Discrete Events

Figure 10-1 Discrete events menu

Measurements

Process
Discrete
comparator
events Density functions API
See enhanced density manual See Chapter 9

Discrete event 1 2 3 4 5

Event type
• HI
• LO
• IN HI/LO
• OUT HI/LO

Process variable
HI PV value(1) (1) If Event Type is HI, IN HI/LO, or OUT HI/LO.
LO PV value(2)
(2) If Event Type is LO, IN HI/LO, or OUT HI/LO.

10.4 Discrete event configuration procedure


You can configure 1 to 5 discrete events, as described in the following steps.

Step 1 Discrete event


Select Discrete event 1 – 5.

Step 2 Event type


For the selected discrete event, select one of the event types defined in Table 10-1.

Table 10-1 Event types

Variable Default Description


HI HI Discrete event will occur if the assigned variable is greater than the high value.(1)
LO Discrete event will occur if the assigned variable is less than the low value.(1)
IN HI/LO Discrete event will occur if the assigned variable is greater than the low value and less than
the high value.(1)
OUT HI/LO Discrete event will occur if the assigned variable is less than the low value or greater than the
high value.(1)
(1) A discrete event does not occur if the assigned variable is equal to the high or low value.

Step 3 Process variable


For the selected discrete event, select a process variable.

80 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Discrete Events

Step 4 High and low values

Configuring Events
For the process variable assigned to the selected discrete event, configure a high value, a low value, or
high and low values, as required by the event type. Enter values in the unit that is configured for the
selected process variable. See Table 10-2 for definitions and descriptions.
Values are exclusive. For example, if the event type is HI, and the HI PV value is set to 100 lb/min:
• If the flow rate equals 100 lb/min, the discrete event does not occur.
• If the flow rate exceeds 100 lb/min, the discrete event occurs.

Table 10-2 High and low values of process variables

Variable Description
HI PV value • If event type is HI or OUT HI/LO, enter the value above which the discrete event will occur.
• If event type is IN HI/LO, enter the value below which the discrete event will occur.
• If event type is OUT HI/LO or IN HI/LO, you must also enter a LO PV value.
LO PV value • If event type is LO or OUT HI/LO, enter the value below which the discrete event will occur.

Configuring Batch
• If event type is IN HI/LO, enter the value above which the discrete event will occur.
• If event type is OUT HI/LO or IN HI/LO, you must also enter a HI PV value.

Step 5 Discrete event actions


To assign an action to a discrete event:
• To assign flowmeter zero, see Section 7.3.5.
• To assign a totalizer control action, see Section 7.3.5.
• To assign a batch control function, see Section 11.7.
• To assign a discrete output, see Section 8.3.2.
• To assign a print function, see Chapter 15.
• To assign a meter verification test, see Section 7.3.5.

Configuring Outputs
If the enhanced density application is installed, you may also assign the “next curve” function.
If more than one action is assigned to a single discrete event, all assigned actions are performed when
the discrete event occurs.

Configure discrete event 1 so it will stop all totalizers when the mass
Example
flow rate in forward or backward direction is less than 2 lb/min.

1. Select lb/min as the mass flow unit. See Section 7.3.2.

2. Configure the flow direction parameter for absolute value. See


Section 7.3.2.

3. Configure discrete event 1 so the event type is LO and the process


Configuring Process Monitor

variable is mass flow.

4. Enter a value of 2 for the LO PV value.

5. Exit the Measurements menu.

6. Using the Inputs/Core Processor parameters/Discrete Inputs


menu, assign Start/stop all totals to discrete event 1. See
Section 7.3.5.

Configuration and Use Manual 81


82 Micro Motion® Series 3000 MVD Transmitters and Controllers
Chapter 11

Configuring Events
Configuring the Discrete Batch Application

11.1 About this chapter


This chapter explains how to configure the discrete batch application. The discrete batch application
includes all the software parameters listed in Figure 11-1.
Note: Information on formatting and printing batch tickets is provided in Chapter 15.
Note: Information on operating the discrete batch application is provided in Chapter 18.

Configuring Batch
Note: The discrete batch application is an optional feature of the Series 3000 platform, and may not
be installed on your equipment. To verify that it is installed, use the View menu to list all installed
applications (see Section 17.5).
Note: If the discrete batch application will be used with custody transfer, review the information in
Chapters 14, 15, and 19 before configuring the discrete batch application.
Failure to perform configuration tasks in the proper sequence could result in an incomplete
configuration. See Section 1.7 for the recommended configuration sequence.

CAUTION
Changing configuration can affect device operation, including batching.

Configuring Outputs
Changes made to discrete batch configuration while a batch is running do not take
effect until the batch is ended. Changes made to other configuration parameters
may affect batching. To ensure correct batching, do not make any configuration
changes while a batch is in progress.

11.2 Discrete batch menu


Use the Discrete Batch menu, shown in Figure 11-1, to access and configure batch parameters. The
Discrete Batch menu is accessed through the Configuration option of the Management menu. To
access the Management menu, see Chapter 4.
Configuring Process Monitor

Configuration and Use Manual 83


Configuring the Discrete Batch Application

Figure 11-1 Discrete batch menu

Discrete batch

Flow source Control options Configure presets Discrete inputs

4 5 6
None Enable batch End
Frequency input Time out Preset 1 2 3 Inhibit batch
Mass No. of stages Inhibit totalizer
Volume(1) No. of decimals Reset
Gas standard volume(2) Reset on start Resume
ED std vol Count up Start
ED net mass(3) Enable end warning Stop
ED net vol(4) Enable AOC Increment preset
API temp. corr vol(5) Enable overrun Enable preset Inhibit flow
Lockout target Name
Maximum target(6) Density curve(8)
Ignore source alarms Open primary(9)
Alarm timeout(7) Open secondary(9)
Configure presets by Close primary(9) • None
End warning(10) • Discrete input 1
Target • Discrete input 2
Overrun(11) • Discrete event 1
• Discrete event 2
• Discrete event 3
(1) Displayed only if Volume Flow Type is set to Liquid (see Section 7.3.2). • Discrete event 4
(2) Displayed only if Volume Flow Type is set to Gas Standard (see Section 7.3.2). • Discrete event 5
(3) If enhanced density application is installed and configured, and the derived variable
is mass-based.
(4) If enhanced density application is installed and configured, and the derived variable
is volume-based.
(5) If petroleum measurement application is installed.
(6) If Lockout Target is set to No.
(7) If Ignore Source Alarms is set to Yes.
(8) If enhanced density application is installed and configured.
(9) If No. of Stages is set to 2.
(10) If Enable End Warning is set to Yes.
(11) If Enable Overrun is set to Yes.

11.3 Batching configuration overview


To configure batching, the following general steps are required:
1. From the Discrete Batch menu:
a. Configure flow source.
b. Configure control options.
c. Configure one or more presets (optional).
d. Configure batch control methods, if desired.

84 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring the Discrete Batch Application

2. From the Discrete Outputs menu, configuring the required discrete outputs:

Configuring Events
• For 1-stage operation, you must configure one discrete output. This output must control
either the pump or the primary valve, as appropriate to your application. This discrete
output is required.
• For 2-stage operation, you must configure two or three discrete outputs:
- One to control the primary valve (required)
- One to control the secondary valve (required)
- One to control the pump (optional; only if required by your installation)
You must configure the discrete outputs that are listed as required, whether or not your
installation requires them (for example, you may start and stop the pump manually). You will
not be able to start a batch until the required discrete outputs have been configured. See
Section 8.3 for information on configuring the discrete outputs.
3. If you enabled the Batch AOC control option, you should perform batch AOC (automatic
overshoot compensation) calibration. Batch AOC is used to minimize the amount of overshoot

Configuring Batch
per batch. See Section 18.6 for information on performing batch AOC calibration.
4. You may optionally configure the batch ticket and ticket printing. See Chapter 15 for
information on configuring tickets and ticket printing.

11.4 Flow source


The flow source specifies the flow variable that will be used for batch measurement. Select one of the
flow sources defined in Table 11-1.
Note: If the discrete batch application will be used for custody transfer measurement, ensure that the
transfer variable is configured as the batch flow source. See Chapter 14 for more information.

Table 11-1 Flow sources

Configuring Outputs
Flow Source Default Description
None None • Batch controller is disabled.
• START button will not appear on display.
Frequency input • Frequency input from a Micro Motion IFT9701 or RFT9739 transmitter
• Frequency input from a pulse output device
Mass Mass flow rate from Model 3500 or Model 3700 transmitter
(1)
Volume Liquid volume flow rate from Model 3500 or Model 3700 transmitter
Gas standard Gas standard volume flow rate from Model 3500 or Model 3700 transmitter
volume(2)
ED std vol flow(3) • Standard volume flow rate at reference temperature
• Standard volume flow is available only if the enhanced density application software
is installed and configured to indicate standard volume flow. See the enhanced
density manual.
Configuring Process Monitor

Configuration and Use Manual 85


Configuring the Discrete Batch Application

Table 11-1 Flow sources continued

Flow Source Default Description


(3)
ED net mass flow • Net mass flow rate
• Net mass flow is available only if the enhanced density application software is
installed and configured to indicate net mass flow. See the enhanced density
manual.
ED net vol flow(3) • Net volume flow rate at reference temperature
• Net volume flow is available only if the enhanced density application software is
installed and configured to indicate net volume flow. See the enhanced density
manual.
API temperature- • Volume flow adjusted by the calculated volume correction factor
corrected volume • Available only if the petroleum measurement application is installed. See
flow(4) Chapter 9.
(1) Displayed only if Volume Flow Type is set to Liquid. See Section 7.3.2.
(2) Displayed only if Volume Flow Type is set to Gas Standard. See Section 7.3.2.
(3) Displayed only if the enhanced density application is installed.
(4) Displayed only if the petroleum measurement application is installed.

11.5 Control options


Select one of the control options defined in Table 11-2.
Note: Control options apply to all batch presets.

Table 11-2 Control options

Setting Default Description


Enable batch Yes • Select Yes to enable the discrete batch application.
• Select No to disable the discrete batch application. The operation mode will
default to the process monitor.
• If the custody transfer application is installed, with either World Area set to
NTEP or World Area set to OIML with batching approved (see Chapter 14),
Enable Batch is set to Yes and cannot be changed.
Time out 10.0 sec • The Time Out period specifies how long the batch controller will wait before
posting an alarm if flow stops or the batch totalizer or batch flow is inhibited
while a batch is running.
• Enter a value of 0.0 to 300.0.
• Time Out is disabled if set to 0.0 seconds.
• A discrete output can be configured to activate if the Time Out period expires.
See Section 8.3.2.
No. of stages 1 Enter a value of 1 for 1-stage batch control, or 2 for 2-stage batch control. See
the discussion in Section 11.5.1.
No. of decimals 1 • Enter a value of 0 to 5.
• This value specifies the number of digits to the right of the decimal point on the
operation screen.
Reset on start No • If set to Yes, the batch totalizer resets when the operator starts the batch.
• If set to No, the operator must press RESET before starting a new batch
• Reset and Start can be assigned to discrete inputs or discrete events. See
Section 11.7.
• If the custody transfer application is installed, Reset on Start is set to No and
cannot be changed if either of the following is true: World Area is set to NTEP,
or World Area is set to OIML and the discrete batch application is approved.

86 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring the Discrete Batch Application

Table 11-2 Control options continued

Configuring Events
Setting Default Description
Count up Yes • If set to Yes, the total displayed on screen increases from zero to the target
value.
• If set to No, the total displayed on screen decreases from the target value to
zero
• The setting of the Count Up control option affects only the quantity displayed
on screen. It does not affect configuration of presets.
• If the custody transfer application is installed, with either World Area set to
NTEP or World Area set to OIML with batching approved (see Chapter 14),
Count Up is set to Yes and cannot be changed.
Enable end No • Select Yes to enable the end warning.
warning • When End Warning is enabled and an end warning value has been entered for
the selected preset, a discrete output can be configured to indicate the end
warning.
• End Warning is a status indicator only, and does not affect valve operation.
• End Warning will remain active until batch completion.

Configuring Batch
Enable AOC Yes • Select Yes to enable Automatic Overshoot Compensation (AOC).
• When batch AOC is enabled and batch AOC calibration has been performed,
the batch controller compensates for the time required to close the valve.
• If Enable AOC is set to Yes, batch AOC calibration is required to provide data
for the compensation process. To perform batch AOC calibration, see
Section 18.6.
Enable overrun No • Select Yes to enable overrun indication.
• When Overrun is enabled and an overrun value has been entered for the
selected preset, the batch controller produces an overrun alarm when the
batch total exceeds the target by more than the programmed overrun amount.
• Overrun can be assigned to a discrete output. See Section 8.3.2.
Lockout target No • If set to Yes, the current target cannot be changed from the batch operation
screen.
• If set to No, the batch target can be changed from the batch operation screen
when a batch is not running.
Maximum target 1.0000E9 kg If Lockout Target is set to No, enter the maximum target that the operator will be
allowed to set in the batch operation mode.

Configuring Outputs
Ignore source No A source alarm is any fault-level alarm. If Ignore Source Alarms:
alarms • Is set to Yes, the batch will not stop for the duration of the alarm timeout.
• Is set to No, the batch is stopped as soon as the alarm condition occurs.
If the custody transfer application is installed, with either World Area set to
NTEP or World Area set to OIML with batching approved (see Chapter 14),
Ignore Source Alarms is set to No and cannot be changed.
Alarm timeout 1 minute This parameter is applicable only if Ignore source alarms is set to Yes.
• Enter the number of minutes, from 1 to 20, for which source alarms will be
ignored.
• If the alarm condition is present when the alarm timeout expires, the current
batch is stopped.
Configure presets % of target Select % of Target or Quantity.
by • If set to % of Target, Open Primary, Open Secondary, Close Primary, and End
Warning values are each configured as a percent of target. See Example 2 in
Section 11.6.1.
Configuring Process Monitor

• If set to Quantity, Open Primary and Open Secondary are each configured as
a quantity at which the valve should open; Close Primary and End Warning
values are each configured as a quantity that is subtracted from the target.
See Example 1 in Section 11.6.1.
• To configure Open Primary, Open Secondary, Close Primary, and End
Warning values, see Section 11.6.

Configuration and Use Manual 87


Configuring the Discrete Batch Application

11.5.1 One-stage versus two-stage batching


If No. of Stages is set to 1, a single pump or valve is used to control the batch. (You can assign both a
pump and a valve if desired, although only one is necessary.) When the batch is started, the pump
starts or the valve opens; at the configured target, the pump stops or the valve closes. Open Primary,
Open Secondary, and Close Primary values are not required when configuring the preset (see
Section 11.6).
If No. of Stages is set to 2, two valves are used to control the batch, and the following requirements
apply when configuring the preset:
• Both Open Primary and Open Secondary must be configured.
• Either Open Primary or Open Secondary must be set to 0. Both may be set to 0 if desired.
• Close Primary must be configured.

11.6 Configure presets


You can configure up to six batch presets. Preset 1 cannot be disabled, but you can change its
configuration.
Table 11-3 defines the options for configuring presets. To configure a preset, first select the preset to
be configured, then define its parameters.

Table 11-3 Presets

Setting Default Description


Enable preset • Yes for preset 1 • If set to Yes, the batch preset can be selected in the View menu. See
• No for presets 2–6 Section 17.5.3.
• If set to No, the batch preset is disabled and cannot be selected.
• Preset 1 cannot be disabled.
Name • Preset 1 • Enter the name that will appear on operation screens and in preset selection
• Preset 2 menus.
• Preset 3 • A maximum of 22 characters can be entered. Only 21 characters are
• Preset 4 displayed. You can use the left and right cursor control buttons to scroll
• Preset 5 through and view the entire name.
• Preset 6
Density curves None • If a derived variable is selected as the flow source, you can select a density
curve that will apply to this preset. See the enhanced density manual.
• The batch total will be based on the density curve for that variable.
Open primary(1) 0.00% of target or • Enter the quantity or the percent of the target at which the primary valve will
0.0 kg quantity open. See the examples later in this section.
• Either Open Primary or Open Secondary must be set to 0. If one of these
parameters is set to a non-zero value, the other is set to 0 automatically.
• To enable 2-stage batch control, see Section 11.5.
• Before a batch can be started, the primary valve must be assigned to a
discrete output. See Section 8.3.2.
Open 0.00% of target or • Enter the quantity or the percent of the target at which the secondary valve
secondary(1) 0.0 kg quantity will open. See the examples later in this section.
• Either Open Primary or Open Secondary must be set to 0. If one of these
parameters is set to a non-zero value, the other is set to 0 automatically.
• To enable 2-stage batch control, see Section 11.5.
• Before a batch can be started, the secondary valve must be assigned to a
discrete output. See Section 8.3.2.
Close primary(1) 80.00% of target or • Enter the quantity subtracted from the target, or the percent of the target, at
0.0 kg quantity which the primary valve will close. See the examples later in this section.
• The secondary valve always closes when the target is achieved.
• To enable 2-stage batch control, see Section 11.5.
• Before a batch can be started, the primary valve must be assigned to a
discrete output. See Section 8.3.2.

88 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring the Discrete Batch Application

Table 11-3 Presets continued

Configuring Events
Setting Default Description
(2)
End warning 80.00% of target or • If End Warning is enabled as a control option, enter the quantity subtracted
0.0 kg quantity from the target, or the percent of the target, at which the end warning will
occur. See the examples later in this section.
• End Warning can be assigned to a discrete output. See Section 8.3.2.
• To enable the end warning, see Section 11.5.
Target(3) 0.0 kg Enter the total at which the batch will be completed.
(4)
Overrun 0.0 kg • If Overrun is enabled as a control option, enter the amount over the target
value at which batch overrun will be indicated. For example, if the target is
250 kilograms and overrun should be indicated at 280 kilograms, enter 30.
• Overrun can be assigned to a discrete output. See Section 8.3.2.
• To enable overrun indication, see Section 11.5
(1) This parameter is displayed only if No. of Stages was set to 2.
(2) This parameter is displayed only if Enable End Warning was set to Yes.
(3) A non-zero value must be configured for Target before a batch can be started.

Configuring Batch
(4) This parameter is displayed only if Enable Overrun was set to Yes.

11.6.1 Batch preset examples


The following examples describe the batch processing sequence for two different batch preset
configurations.
Note: For a detailed presentation of batch processing sequences, including how the STOP and
RESUME functions affect processing, see Section 18.4.

Example 1 Configure presets by quantity under the following conditions:


• The target is 200 kilograms
• The primary valve opens at the start of the batch and closes when
180 kilograms have been delivered

Configuring Outputs
• The secondary valve opens when 100 kilograms have been
delivered
• The end warning occurs when 160 kilograms have been delivered

Close Primary = 200 kilograms – 180 kilograms = 20

Open Secondary = 100 kilograms

End Warning = 200 kilograms – 160 kilograms = 40

Configuring Process Monitor

Configuration and Use Manual 89


Configuring the Discrete Batch Application

Example 2 Configure presets by percent of target under the following conditions:


• The target is 200 kilograms
• The primary valve opens at the start of the batch and closes when
180 kilograms have been delivered
• The secondary valve opens when 100 kilograms have been
delivered
• The end warning occurs when 160 kilograms have been delivered
180 kilograms
Close Primary = ------------------------------------- = 0.90
200 kilograms

Since 0.90 equals 90%, enter a Close Primary value of 90.

100 kilograms
Open Secondary = ------------------------------------- = 0.50
200 kilograms

Since 0.50 equals 50%, enter an Open Secondary value of 50.

160 kilograms
End Warning = ------------------------------------- = 0.80
200 kilograms

Since 0.80 equals 80%, enter an End Warning value of 80.

11.7 Batch control methods


Batch control functions can be performed in four ways:
• By using the function buttons on the display (see Section 18.3)
• By assigning a discrete input to a batch control function
• By assigning a discrete event to a batch control function
• By using digital communications (e.g., ProLink II)
Table 11-4 lists the batch control functions, and Table 11-5 describes how the batch responds to
changes in discrete inputs or discrete events. To assign a discrete input or discrete event to perform a
batch control function:
1. Select the batch control function to be performed.
2. Specify the discrete input or discrete event that will perform the batch control function.
Note: For a detailed description of the batch control functions in operation, see Chapter 18.
Note: You can assign one or more actions to a single discrete input or discrete event. All assigned
actions that are compatible with the current batch state will be performed, and all others, except for
print commands, will be discarded. To assign flowmeter zero or a totalizer control function to a
discrete input, discrete event, or batch event, see Section 7.3.5. To assign a print function to a discrete
input or discrete event, see Chapter 15.

90 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring the Discrete Batch Application

Table 11-4 Batch control assignments

Configuring Events
Default
Function assignment Assignment options ON state actions
End None Specify the discrete input or • Ends the batch.
discrete event that will • The batch cannot be resumed.
perform the batch control • The batch totalizer must be reset for the next batch.(1)
function:
Inhibit batch • None • Batch cannot be started.
• Discrete input 1 • Inhibit Batch is used for temporary lockout.
Inhibit • Discrete input 2 • Delivers the batch but does not totalize.
totalizer • Discrete event 1 • While totalizing is inhibited, flow measurement
• Discrete event 2 continues but batch total is not incremented.
• Discrete event 3
Reset(1) • Discrete event 4 • Resets batch total to zero.
• Discrete event 5 • Batch reset cannot be performed while a batch is
running or while a batch is stopped. Before a batch can
be reset, the batch target must be reached or the batch
must be ended.

Configuring Batch
Resume • Resumes a batch that has been stopped.
• Counting resumes from the total at which the batch was
stopped.
Start • Starts the batch by opening the flow control valve(s)
and starting the pump.
Stop • Stops the batch.
• The batch can be resumed.
• If Lockout Target is disabled as a control option, the
operator can change the target before resuming.
• To enable or disable Lockout Target, see Section 11.5.
Increment • Selects next configured and enabled preset (as listed in
preset the preset menus) for use in the next batch.
Inhibit flow • Delivers the batch but does not totalize.
• Used to allow the batch to end while flow is present.
(1) The batch controller can be configured to reset automatically on start. To configure Reset on Start, see Section 11.5.

Configuring Outputs
Table 11-5 Discrete event/discrete input states and batch control functions

Batch control function Discrete event/discrete input Result


End Turns ON Stops current batch; batch cannot be restarted.
Turns OFF No action taken.
Inhibit batch While ON Batch cannot be started. If start is attempted,
“Start Not Okay” alarm is posted.
While OFF Batch can be started.
Turns OFF No action taken.
Any change of state Does not affect batch in progress.
Configuring Process Monitor

Configuration and Use Manual 91


Configuring the Discrete Batch Application

Table 11-5 Discrete event/discrete input states and batch control functions continued

Batch control function Discrete event/discrete input Result


Inhibit totalizer Turns ON Batch totalizer stops incrementing.
• If the Time Out batch control option is set to
0, no time out alarm will be posted.
• If the Time Out batch control option is set to a
non-zero value, a time out alarm will be
posted if the time out period expires before
batch totalizing resumes.
While ON Batch totalizer does not increment.
Turns OFF Resumes incrementing.
While OFF Batch totalizer increments if flow is detected,
whether or not a batch is running.
Reset Turns ON Batch total reset to 0.
Turns OFF No action taken.
Resume Turns ON Resumes current batch.
Turns OFF No action taken.
Start Turns ON Begins new batch.
Turns OFF No action taken.
Stop Turns ON Pauses current batch. Batch can be resumed.
Turns OFF No action taken.
Increment preset Turns ON Sets the batcher to use the next enabled preset
for the next batch.
Works only if a batch is not running.
Turns OFF No action taken.
(1)
Inhibit flow Turns ON Batch totalizer stops incrementing.
While ON Batch totalizer does not increment. The batch
in progress remains active, and will end when
the batch time out is reached or when an END
command is received.
Turns OFF Resumes incrementing.
While OFF Batch totalizer increments.
(1) Does not work during AOC calibration.

11.7.1 Special cases in batch control


There are two common situations in batch control that may require special configuration:
• Cleaning/purging the sensor tubes
In normal processing, the batch totalizer increments whenever flow through the sensor tubes is
detected. If you will want to run fluid through the tubes without incrementing the totalizer,
assign a discrete input to the Inhibit Totalizer function.
• Ending the batch while flow is present
In normal processing, you cannot end a batch while flow is present. If you may need to end a
batch while flow is present, assign a discrete input to the Inhibit Flow function.

92 Micro Motion® Series 3000 MVD Transmitters and Controllers


Chapter 12

Configuring Events
Configuring the Process Monitor

12.1 About this chapter


This chapter explains how to configure the process monitor. Parameters are listed in Figure 12-1.
Failure to perform configuration tasks in the proper sequence could result in an incomplete
configuration. See Section 1.7 for the recommended configuration sequence.

Configuring Batch
CAUTION
Changing configuration can affect device operation.

Set control devices for manual operation before changing device configuration.

12.2 Monitoring menu


Use the Monitoring menu, shown in Figure 12-1, to access and configure process monitor parameters.
The Monitoring menu is accessed through the Configuration option of the Management menu. To
access the Management menu, see Chapter 4.

Figure 12-1 Monitoring menu

Configuring Outputs
Monitoring

Screens Variables Update period

Screen 1, variable 1 ... 4 Variable list


Screen 2, variable 1 ... 4
Screen 3, variable 1 ... 4
Screen 4, variable 1 ... 4
Screen 5, variable 1 ... 4 (1) Displayed only if the custody
Configuring Process Monitor

Number of decimals transfer application is installed and


W&M approval(1)
Label World Area is set to OIML.

Configuration and Use Manual 93


Configuring the Process Monitor

12.3 Process monitor screens


The Process Monitor Screens menu allows you to specify the process variable that will appear on the
display. You can configure five screens, displaying 0 to 4 variables on each screen. Font size is
adjusted according to the number of variables configured for display.
See Table 12-1.
Note: For information about using the process monitor, see Chapter 17.

Table 12-1 Process monitor screen parameters

Variable Default Description


Screen 1, Variable 1 Mass flow rate Select the process variable that will appear on screen 1, line 1.
Screen 1, Variable 2 Mass total Select the process variable that will appear on screen 1, line 2.
Screen 1, Variable 3 None Select the process variable that will appear on screen 1, line 3.
Screen 1, Variable 4 None Select the process variable that will appear on screen 1, line 4.
Screen 2, Variable 1 Volume flow rate Select the process variable that will appear on screen 2, line 1.
Screen 2, Variable 2 Volume total Select the process variable that will appear on screen 2, line 2.
Screen 2, Variable 3 None Select the process variable that will appear on screen 2, line 3.
Screen 2, Variable 4 None Select the process variable that will appear on screen 2, line 4.
Screen 3, Variable 1 Density Select the process variable that will appear on screen 3, line 1.
Screen 3, Variable 2 Temperature Select the process variable that will appear on screen 3, line 2.
Screen 3, Variable 3 None Select the process variable that will appear on screen 3, line 3.
Screen 3, Variable 4 None Select the process variable that will appear on screen 3, line 4.
Screen 4, Variable 1 Density Select the process variable that will appear on screen 4, line 1.
Screen 4, Variable 2 Mass flow rate Select the process variable that will appear on screen 4, line 2.
Screen 4, Variable 3 None Select the process variable that will appear on screen 4, line 3.
Screen 4, Variable 4 None Select the process variable that will appear on screen 4, line 4.
Screen 5, Variable 1 Mass flow rate Select the process variable that will appear on screen 5, line 1.
Screen 5, Variable 2 Volume flow rate Select the process variable that will appear on screen 5, line 2.
Screen 5, Variable 3 Density Select the process variable that will appear on screen 5, line 3.
Screen 5, Variable 4 Temperature Select the process variable that will appear on screen 5, line 4.

12.4 Process monitor variables


The Process Monitor Variables menu allows you to control the following:
• The precision of the process variable values shown on the display. This does not affect the
precision used in internal processing or communicated via digital communications.
• The label to be used for process totalizer and process inventory values on the display.
• The display of the transfer variable (custody transfer applications only).
To change the precision of a process variable:
1. Select it from the list.
2. Specify the number of decimals that will be displayed. The valid range is 0 to 5.

94 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring the Process Monitor

To change the label used for a process totalizer or process inventory value:

Configuring Events
1. Select the process totalizer or process inventory from the list.
2. Enter the label to be used. This label will be used on the display and printed on process
monitor tickets.
Additionally, if the custody transfer application is installed and World Area is set to OIML, this menu
allows you to specify one or more process variables to be marked with asterisks on the transfer ticket
and, optionally, the process monitor. This is typically done to identify the process variable used for
legal compliance (the transfer variable).
To do this:
1. Select the process variable from the list.
2. Set W&M Approval to Approved or Not Approved, as desired.
Note: For more information, see Section 14.5.

Configuring Batch
12.5 Update period
The update period controls how often the display is refreshed with current data. The default value is
200 msec. The range is 100 to 10,000 msec. The Update Period value applies to all process variables
on the display.
Note: Update Period does not affect the values reported by outputs or digital communications.

Configuring Outputs
Configuring Process Monitor

Configuration and Use Manual 95


96 Micro Motion® Series 3000 MVD Transmitters and Controllers
Configuring Digital Communications
Chapter 13
Configuring Digital Communications

13.1 About this chapter


This chapter explains how to configure digital communications. Only communication parameters are
discussed here; for ticket formatting and printing information, see Chapter 15.

Configuring Custody Transfer


Note: To install wiring for digital communications, see Chapter 3.
Failure to perform configuration tasks in the proper sequence could result in an incomplete
configuration. See Section 1.7 for the recommended configuration sequence.

CAUTION
Changing configuration can affect device operation.

Set control devices for manual operation before changing device configuration.

13.2 Digital communication menu


Use the Digital Communication menu, shown in Figures 13-1 through 13-3, to access and configure
digital communications parameters. The RS-485 menu displayed depends on several factors:
• Which protocol is configured

Configuring Tickets
• Whether or not the custody transfer application is installed
• If the custody transfer application is installed, whether World Area is set to OIML or NTEP
The Digital Communication menu is accessed through the Configuration option of the Management
menu. To access the Management menu, see Chapter 4. You will be configuring:
• RS-485 parameters
• Bell 202 parameters
• Device parameters
Note: Before you can use digital communications, the appropriate wiring must be installed. See
Chapter 3.
Note: Although the Digital Communication menu is used to configure ticket formatting and printing,
these topics are not discussed in this chapter. For information on ticket formatting and printing, see
Chapter 15.
Startup

Configuration and Use Manual 97


Configuring Digital Communications

Figure 13-1 Digital communication menu – RS-485 (Protocol = HART, Modbus RTU, or Modbus ASCII)

Digital comm

Configure RS-485

Protocol Configure protocol Discrete inputs(3)


• HART • Baud rate • Transfer reset screen
• Modbus RTU • Parity • Transfer scr to reset
• Modbus ASCII • Data bits
• Printer • Stop bits
• Polling address(1)
• Byte order(2)

(1) If HART protocol is configured for RS-485, Polling Address in RS-485 menu and Polling Address in Bell 202 menu are
duplicates. See Section 13.3.1.
(2) Displayed only if Protocol is set to Modbus RTU or Modbus ASCII.
(3) Displayed only if custody transfer application is installed, World Area is set to OIML, and Protocol is not set to Printer.
For more information, see Section 14.5, Step 6.

Figure 13-2 Digital communication menu – RS-485 (Protocol = Printer)

Digital comm

Configure RS-485

Protocol Configure printer Format W&M ticket(4) Discrete inputs Printer test
• HART • Printer selection
• Modbus RTU • Pre header codes(1) See Chapter 15 See Chapter 15
• Modbus ASCII • Header line 1–2
• Printer • Footer
• Post footer codes(1)
• Baud rate
• Parity
• Data bits
• Stop bits
• Chars per second
• Print buf size
• Lines per page (1) Not displayed if custody transfer application is installed.
• Number of tickets(2)
(2) Displayed only if discrete batch application is installed.
• Auto print(2)
• Disable paper (3) Not displayed if World Area is set to OIML.
check(3) (4) Displayed only if custody transfer application is installed.

98 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Digital Communications

Configuring Digital Communications


Figure 13-3 Digital communication menu – Bell 202 and Device setup

Digital comm

Configure Bell-202 Device setup

Polling address(1) Fault setting


• Upscale
Loop current mode • Downscale
• Enable • Zero
• Disable • NAN
• Zero flow
Burst mode • None

Configuring Custody Transfer


• Enable
• Disable Description
User message
Burst command HART QV
• Primary variable HART device ID
• PV & pct range Transmitter serial no.
• Dyn vars & pct range
• Transmitter vars

Burst variable 1(2)


Burst variable 2(2)
Burst variable 3(2)
Burst variable 4(2)

(1) If HART protocol is configured for RS-485, Polling Address in RS-485 menu and Polling Address in Bell 202 menu are
duplicates. See Section 13.3.1.
(2) Displayed only if Burst Command is set to Transmitter Vars.

13.3 Configuring RS-485 parameters

Configuring Tickets
RS-485 parameters specify how the Series 3000 device will communicate via the RS-485 terminals.
(To set up RS-485 communications, see Section 3.3.)
The RS-485 terminals can be configured for HART, Modbus RTU, Modbus ASCII protocol, or printer
protocol. Different protocol parameters are displayed according to your choice of protocol.

13.3.1 Configuring HART, Modbus RTU, or Modbus ASCII protocol


Parameters used to configure HART, Modbus RTU, and Modbus ASCII protocols are listed and
defined in Table 13-1.
Note: If HART is configured, the Polling Address is used for both HART/RS-485 and HART/Bell 202
communications (see the following section). All other parameters specified here apply only to
HART/RS-485 communications (via the RS-485 terminals). They do not apply to HART/Bell 202
communications (via the primary mA output terminals).
Startup

Configuration and Use Manual 99


Configuring Digital Communications

Table 13-1 HART, Modbus RTU, and Modbus ASCII parameters

Variable Default Description


Baud rate 9600 baud Select the baud rate to be used with the remote device.
Parity Odd Select None, Odd, or Even as required by the remote device.
Data bits 8 bits This parameter is read-only:
• HART and Modbus RTU – 8
• Modbus ASCII – 7
Stop bits 1 bit Enter 1 or 2 stop bits as required by the remote device. If HART is the
configured protocol, Stop bits must be set to 1.
Polling address 0 (HART) Enter the polling address to be assigned to the Series 3000 device.
1 (Modbus) • If Modbus/RS-485 protocol is configured, enter a Modbus polling address.
Valid Modbus polling addresses are in the following ranges: 1–15, 32–47,
64–79, 96–110.
• If HART/RS-485 protocol is configured, enter a HART polling address. See the
discussion in the following section. Valid HART polling addresses are in the
range 0–15. If the HART polling address is set to any value other than 0, the
primary mA output is fixed at 4 mA, and will not report process variable data or
fault conditions.
Byte order 3–4–1–2 (Modbus RTU or Modbus ASCII only) Specifies the floating point byte order for
Modbus communications. Select one of the following:
• 1–2–3–4
• 3–4–1–2
• 2–1–4–3
• 4–3–2–1

Polling address
Two polling addresses are stored on the Series 3000 device: a Modbus polling address and a HART
polling address.
• The Modbus polling address can be configured only in the RS-485 menu, and is used for all
Modbus communications.
• The HART polling address can be configured either in the RS-485 menu (if HART protocol is
specified) or in the Bell 202 menu. Because only one value can be stored, if Polling Address is
set in both menus, the most recent address will be used for HART communication over both
the RS-485 terminals and the primary mA/HART terminals.

Communicating with a remote device


After RS-485 communications have been set up (both wiring and configuration), there are two
communication methods available:
• Service port mode
• RS-485 mode
Note: Service port connections use standard settings and do not require transmitter configuration.
Therefore, they are easy and convenient. However, the standard settings and the address may not be
compatible with your network, and the service port cannot be used when the custody transfer
application is installed and the transmitter is secured.
Immediately after the Series 3000 device is powered up, the RS-485 terminals are available in service
port mode for 10 seconds. To connect during this period, configure your remote device as described in
Table 13-2. If a service port connection is made, the terminals will remain in service port mode.

100 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Digital Communications

Configuring Digital Communications


Table 13-2 Connection parameters for service port mode

Connection parameter Value


Protocol Modbus RTU
Baud rate 38400
Stop bits 1
Parity none
Address/Tag 111
COM port COM port assigned to PC serial port

If no connection is made during the 10-second period, the terminals are automatically reset to RS-485
mode and will remain in that mode. To connect, set the connection parameters to the values

Configuring Custody Transfer


configured in your Series 3000 device.
To switch from service port mode to RS-485 mode or vice versa, you must power down the device,
then power it up and connect in the desired mode.
If the custody transfer application is installed:
• Service port connections are available only if the custody transfer security switch is OFF
(unsecured).
• If the terminals are in service port mode and the custody transfer security switch is then turned
ON (secured), the terminals are reset to RS-485 mode. If there is a current service port
connection, it is broken. To reconnect in service port mode, you must turn off the security
switch and perform a power cycle as described above.

13.3.2 Configuring printer protocol


Printer protocol parameters are used to:

Configuring Tickets
• Configure communications with a printer.
• Test the printer setup.
• Format ticket headers and footers. For more information, see Chapter 15.
• Specify screens to print via a discrete input or discrete event. For more information, see
Chapter 15.

Configuring printer communications


The parameters used to configure printer communications are listed and defined in Table 13-3. These
parameters control printer communications for all tickets. To access these parameters, refer to
Figure 13-1.

Table 13-3 Printer communications parameters

Variable Default Description


Printer selection Generic Specify the type of printer to be used.
Startup

The Terminal option is used to specify a dumb terminal or a terminal emulation


program.
FDW refers to FernDruckWerk, a printer interface device.
Baud rate 9600 baud Select the baud rate to be used to communicate with the printer.
Parity Odd Select None, Odd, or Even as required by the printer.
Data bits 8 bits Select 7 or 8 as required by the printer.

Configuration and Use Manual 101


Configuring Digital Communications

Table 13-3 Printer communications parameters continued


Stop bits 1 bit Enter 1 or 2 stop bits as required by the printer.
Chars per Variable Enter the number of characters per second to be sent to the printer. The range
second is 1–1000.
The default value for the generic printer is very low, resulting in very slow
printing. Micro Motion recommends checking this parameter and setting it
appropriately for the printer being used.
Print buf size Variable Enter the size of the print buffer, in characters. The range is 32–32768.
The default value for the generic printer is very low, resulting in very slow
printing. Micro Motion recommends checking this parameter and setting it
appropriately for the printer being used.
Lines per page 25 This parameter is read-only, and shown only for user reference. If you are
printing more than 25 lines of data, you will need to insert multiple tickets or use
a roll of paper.
Disable paper Yes Valid only for the Epson ticket printer.
check If it is enabled, and an out-of-paper condition is detected:
• If the custody transfer application is installed and World Area is set to OIML, a
print failure message is shown on the Series 3000 display for five seconds.
• In all other cases, an A130 alarm is posted. The alarm is cleared when the
out-of-paper condition is removed.

Printer test
After configuring the printer, select Printer Test to perform a printer test. A standard test page should
be produced at the printer. When the printer test is complete, the display reads “Print Test Complete.”
If printing does not occur:
• Check RS-485 output wiring. See Section 3.3.
• Make sure printer configuration settings are compatible with the selected printer. See the
instructions for the selected printer.

13.4 Configuring Bell 202 parameters


The Bell 202 parameters are used to configure HART communications over the Bell 202 physical
layer. (To set up Bell 202 communications, see Section 3.4.)
When using HART/Bell 202 communications, baud rate, stop bits, parity, and data bits have standard
values and cannot be changed. Parameters that can be set for Bell 202 communications are listed and
defined in Table 13-4.

Table 13-4 Bell 202 parameters

Variable Default Description


(1)
Polling address 0 Enter the HART polling address to be assigned to the Series 3000 device. Valid
HART polling addresses are in the range 0–15.
Loop current Disable • Select Enable to enable Loop Current Mode.
mode(2) • Select Disable to disable Loop Current Mode.
Burst mode(3) Disable • Select Enable to enable burst mode.
• Select Disable to disable burst mode.

102 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Digital Communications

Configuring Digital Communications


Table 13-4 Bell 202 parameters continued

Variable Default Description


Burst command Transmitter vars Specify the type of information that will be broadcast via burst mode. Select
from:
• Primary variable – The Series 3000 device repeats the primary variable
(PV)(4), in measurement units, in each burst (e.g., 14.0 g/s, 13.5 g/s, 12.0 g/s).
• PV & pct range – The device sends the PV’s percent of range and the PV’s
actual mA level in each burst (e.g., 25%, 11.0 mA).
• Dyn vars & Pct range – The device sends PV, SV, TV, and quaternary variable
(QV) values in measurement units and the PV’s actual milliamp reading in
each burst (e.g., 50 lb/min, 23 °C, 50 lb/min, 0.0023 g/cm3, 11.8 mA).
• Transmitter vars – In each burst, the device sends the four process variables
configured for burst variables 1–4.
Burst variable 1(5) Mass flow rate • Specifies the process variable to be broadcast in position 1.
• Select the desired process variable from the list.

Configuring Custody Transfer


Burst variable 2(5) Temperature • Specifies the process variable to be broadcast in position 2.
• Select the desired process variable from the list.
Burst variable 3(5) Density • Specifies the process variable to be broadcast in position 3.
• Select the desired process variable from the list.
Burst variable 4(5) Mass total • Specifies the process variable to be broadcast in position 4.
• Select the desired process variable from the list.
(1) If HART protocol is configured for RS-485, Polling Address in RS-485 menu and Polling Address in Bell 202 menu are duplicates.
See Section 13.3.1.
(2) See Section 13.4.1.
(3) See Section 13.4.2.
(4) The primary variable (PV) is the process variable reported via the primary mA output (MAO1). The secondary variable (SV) is the
process variable reported via the secondary mA output (MAO2). The tertiary variable (TV) is the process variable reported via the
frequency output. The quaternary variable (QV) is accessible via HART, and can be assigned through the Device Setup menu. See
Section 13.5.
(5) This parameter appears only if Transmitter Vars is specified for Burst Command.

Configuring Tickets
13.4.1 Loop current mode
Loop current mode is used to fix or unfix the mA output:
• If Loop Current Mode is disabled, the mA output is fixed at 4 mA, and therefore cannot be
used to report process data.
• If Loop Current Mode is enabled, the mA output will report process data as configured.

13.4.2 Burst mode


Burst mode (or HART burst mode) is a specialized mode of communication during which the
Series 3000 device regularly broadcasts process variable data over the primary mA output, using
HART protocol. The Burst Command parameter allows you to specify the content and format of the
process variable data.
Burst mode is ordinarily disabled, and should be enabled only if another device on the network
requires HART burst mode communication.
Startup

Configuration and Use Manual 103


Configuring Digital Communications

13.4.3 Communicating with a remote device


After Bell 202 communications have been set up (both wiring and configuration), you can connect to
the Series 3000 device using the parameters described in Table 13-5.

Table 13-5 Connection parameters for Bell 202 communications

Connection parameter Value


Protocol HART
Baud rate 1200
Stop bits 1
Parity Odd
Address/Tag As configured in the Series 3000 device
COM port COM port assigned to PC serial port

13.5 Configuring device parameters


The device parameters are used to describe the device and manage digital communication fault
indication. Table 13-6 lists and defines the device parameters.

Table 13-6 Device parameters

Variable Default Description


Fault setting None The method used to indicate a fault alarm via digital communication. This
setting also applies to digital communication from the core processor.
Options are as follows:
• Upscale – Process variables indicate the value is greater than the upper
sensor limit. Totalizers stop.
• Downscale – Process variables indicate the value is less than the lower
sensor limit. Totalizers stop.
• Zero – Flow rates, density, and temperature go to their internal zero
value.
• NAN (Not A Number) – Process variables report IEEE NAN. Totalizers
stop.
• Zero flow – Flow rates go to their internal zero value; other process
variables are not affected. Totalizers do not stop.
• None – Process variables reported as measured. Totalizers do not stop.
For all options, Modbus scaled integers report Max Int + 1.
Description Device-dependent(1) Any user-supplied description. This parameter is not required. The
description may contain up to 16 characters.
User message Device-dependent(2) Any user-supplied message. This parameter is not required. The
description may contain up to 32 characters.
HART QV Volume flow rate The process variable to be assigned to the quaternary variable (QV). See
the definition of Burst Command in Table 13-4.
HART device ID 0 The HART device ID can be set only once, and is usually set at the factory
to the device serial number. If the HART device ID has not been set, its
value is 0.
Transmitter serial 0 The serial number of the Series 3000 device. This parameter is not
number required.
(1) May be set at the service center to the service center name and the year, month, and day the unit was processed.
(2) May be set at the service center to the service center name and the order ID.

104 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Digital Communications
Chapter 14
Configuring Custody Transfer

14.1 About this chapter


This chapter explains how to configure the custody transfer application.
Note: The custody transfer is also known as the weights and measures application. The custody

Configuring Custody Transfer


transfer application is an optional feature of the Series 3000 device, and may not be installed on your
equipment. To verify that it is installed, use the View menu to list all installed applications (see
Section 17.5).
Failure to perform configuration tasks in the proper sequence could result in an incomplete
configuration. See Section 1.7 for the recommended configuration sequence.

CAUTION
Changing configuration can affect device operation.

Set control devices for manual operation before changing device configuration.

14.2 About custody transfer


The custody transfer application is designed to allow compliance with weights and measures

Configuring Tickets
requirements. While the Series 3000 device is “secured,” all device data can be viewed, but critical
device configuration and operation functions (e.g., starting and stopping totalizers) cannot be accessed
manually. Operational functions are performed automatically by the device according to existing
configuration. To perform these functions manually, the device must be “unsecured.”
In addition:
• A hardware switch and a weights and measures seal are used for physical security.
• A security breach alarm is posted if the hardware switch is toggled or the core processor is
replaced.
• For some ticket types, if the ticket is printed while a security breach alarm is active, or while a
batch is in progress, a note is added to the ticket.
For a more detailed description of device behavior when the device is “secured” or “unsecured,” see
Chapter 19.
Startup

Configuration and Use Manual 105


Configuring Custody Transfer

14.3 Configuration options


The custody transfer application is designed to comply with three different sets of requirements, as
defined by two different regulatory agencies. Before configuring the custody transfer application,
review the descriptions below and follow the configuration instructions for the custody transfer
system that applies to you.
• National Type Evaluation Program (NTEP) – Custody transfer (NTEP) may be used on all
Series 3000 devices.
Custody transfer (NTEP) requires the discrete batch application. Only batches, as managed by
the discrete batch application, can be used for custody transfer measurement. Accordingly, the
process variable used for batch measurement (the batch flow source) serves as the transfer
variable (the process variable used for legal compliance), and the transaction is measured and
managed by the discrete batch application. See Table 14-1.
To configure custody transfer (NTEP), follow the instructions in Section 14.4.
Note: In previous versions of the Series 3000 software, this configuration type was called World Wide.
• Organisation Internationale de Métrologie Légale (OIML) – Custody transfer (OIML) and
custody transfer (OIML/batch) can be used only on Model 3500 or Model 3700 transmitters;
they are not supported on Model 3300 or Model 3350 controllers.
- In custody transfer (OIML) installations, the discrete batch application is not approved for
custody transfer use, and the transfer is used to define the custody transfer transaction.
- In custody transfer (OIML/batch) installations, the discrete batch application must be
approved for custody transfer use, and either the transfer or the batch may be used to
define the custody transfer transaction.
The enhanced density and petroleum measurement applications may or may not be approved
for custody transfer use. The options for transfer variable, transaction measurement, and
transaction management are described in Table 14-1.
To configure custody transfer (OIML) or custody transfer (OIML/batch), follow the
instructions in Section 14.5.
Note: If you are using the custody transfer (OIML) configuration (i.e., the discrete batch application
is not approved), you can still install and use the discrete batch application to run batches that are not
custody transfer transactions.
Note: In previous versions of the Series 3000 software, the discrete batch application was not
approved for OIML compliance. The custody transfer (OIML) configuration is equivalent to the
configuration previously known as custody transfer (Europe). The custody transfer (OIML/batch)
configuration is new with transmitter software rev7.0.

106 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Custody Transfer

Configuring Digital Communications


Table 14-1 Transaction measurement and management

Custody Discrete
transfer batch
type application Method Transfer variable Transaction management Legal receipt
NTEP Required Batch • Batch total • Measured by batch total • Batch (NTEP)
• Ended by: ticket
- Batch (NTEP) ticket printing,
manual or automatic
- Batch reset function
(manual)
OIML Not installed, Transfer • Mass total • Measured by transfer total • Transfer (OIML)
or installed • Volume total • Ended manually by: ticket
but not • API corrected - Transfer (OIML) ticket • Transfer log
approved volume total(1) printing
• ED net mass total(1) - Transfer reset function

Configuring Custody Transfer


OIML/batch Installed and Batch • Batch total • Measured by batch total • Batch (OIML)
approved • Ended by: ticket
- Batch (OIML) ticket printing
(manual or automatic)
- Batch reset function
(manual)
Transfer • Mass total • Measured by transfer total • Transfer (OIML)
• Volume total • Ended manually by: ticket
• API corrected - Transfer (OIML) ticket • Transfer log
volume total(1) printing
• ED net mass total(1) - Transfer reset function
(1) If approved.

14.4 Configuring custody transfer (NTEP)


To configure custody transfer (NTEP):
1. Referring to Figure 14-1, set World Area to NTEP.

Configuring Tickets
2. Ensure that the Series 3000 system, including the discrete batch application, is completely
configured and tested. Verify that the discrete batch flow source has been set to the process
variable to be used for custody transfer measurement (the transfer variable). Only the
following process variables are valid:
- Mass flow
- Volume flow (liquid)
- Gas standard volume flow
- Frequency input
3. If you are using a Model 3500 or Model 3700 transmitter, perform a sensor zero. See
Section 16.3.
4. Referring to Section 13.3, use the Digital Communication menu and set Protocol to Printer.
5. Select Configure Printer and configure printer communications (see Section 13.3.2).
6. Configure ticket format and ticket printing as described in Section 15.5.
Startup

7. Set the security switch on your Series 3000 device. The security switch is a hardware switch.
Security does not take effect until the security switch is ON. Detailed instructions for the
different Series 3000 devices are provided in Section 14.6.
8. Contact an authorized agent for installation of the Weights and Measures seal. Detailed
instructions for the different Series 3000 devices are provided in Section 14.7.

Configuration and Use Manual 107


Configuring Custody Transfer

Figure 14-1 Security menu for custody transfer (NTEP)

Security

Weights & Measures

World area
• NTEP
• OIML

Switch status(1)
(1) Read-only.

14.5 Configuring custody transfer (OIML) and custody transfer (OIML/batch)


To configure custody transfer (OIML) or custody transfer (OIML/batch):
1. Referring to Figure 14-2:
a. Set World Area to OIML.
b. Set Discrete Batch (if displayed) as desired:
• Approved: The discrete batch application can be used for transaction measurement
and management.
• Not Approved: The discrete batch application cannot be used for transaction
measurement and management.
c. Set API or Enhanced Density (if displayed) as desired:
• Approved: API or enhanced density process variables can be used as the transfer
variable.
• Not Approved: API or enhanced density process variables cannot be used as the
transfer variable.
2. Ensure that the Series 3000 system, including all special applications (discrete batch,
petroleum measurement, enhanced density), is completely configured and tested. Verify the
following:
• Volume Flow Type is set to Liquid. Gas standard volume flow cannot be used for OIML
custody transfer.
• If you will use the discrete batch application for transaction measurement, verify that the
discrete batch flow source has been set to the process variable to be used for custody
transfer measurement (the transfer variable). Only the following process variables are
valid:
- Mass flow
- Volume flow (liquid)
- API corrected volume flow (if the petroleum measurement application was approved
in the previous step)
- ED net mass flow (if the enhanced density application was approved in the previous
step)
3. Perform a sensor zero. See Section 16.3.

108 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Custody Transfer

Configuring Digital Communications


4. If desired, you can mark the transfer variable with asterisks that will appear on the transfer
(OIML) ticket and in the transfer log, and optionally, the process monitor. To do this, refer to
Figure 12-1 and:
a. Select the transfer variable and set W&M Approval to Approved. Data for this process
variable will be marked with asterisks on the transfer (OIML) ticket and in the transfer log,
and optionally on the process monitor (see Step 5).
b. For all other process variables, set W&M Approval to Not Approved.
Note: The default setting is Not Approved. It is possible to set more than one process variable to
Approved. If you do this, all approved variables will be marked with asterisks.
Note: Approved variables are never marked with asterisks on batch (OIML) tickets.
Note: See Section 19.5.5 for a discussion of the transfer log.
5. If desired, you can specify that all process variables configured as approved in Step 4 will be

Configuring Custody Transfer


marked with asterisks on the process monitor (if the process variables are configured for
display; see Section 12.3). To do this, refer to Figure 14-2 and set Process Monitoring as
desired:
• Approved: Data for all process variables configured as approved in Step 4a will be
marked with asterisks on the process monitor (if the process variables are configured for
display; see Section 12.3).
• Not Approved: No data will be marked with asterisks on the process monitor.
6. Determine how you will end the transaction, and perform required configuration. Typically,
printing a transfer (OIML) ticket or batch (OIML) ticket ends the transaction. However, if
printing is not available, you can end a custody transfer (OIML) transaction by using the
transfer reset function, and you can end a custody transfer (OIML/batch) transaction by
resetting the batch.
• If you will print transfer (OIML) or batch (OIML) tickets:
a. Referring to Figure 13-2, set Protocol to Printer.

Configuring Tickets
b. Select Configure Printer and configure printer communications (see Section 13.3.2).
c. Configure ticket format and ticket printing as described in Section 15.6.
• If you will use the transfer reset function via the RESET-T button, refer to Figure 13-1 and
set Protocol to any value other than Printer. The RESET-T button will now be available
from the Transfer Totalizer screen on the View menu.
• If you will use the transfer reset function via discrete input 1 or discrete input 2:
a. Referring to Figure 13-1, set Protocol to any value other than Printer.
b. Select Discrete Inputs.
c. Select Transfer Reset Screen, then specify the discrete input to be used to complete
the transfer.
d. Select Transfer Scr to Reset and specify the data to be added to the transfer log when
the specified discrete input is activated.
Note: These menu options are similar to the Transfer Print Screen and Transfer Screens To Print
Startup

menu options described in Section 15.6.2, except that if the discrete input is configured here, no
attempt will be made to print a ticket when the discrete input is activated, and the other menu allows
you to print a ticket containing only inventory data. The discrete input and transfer screens specified
here are reflected in the corresponding menu options, and vice versa.

Configuration and Use Manual 109


Configuring Custody Transfer

Note: If a single discrete input is assigned to print both a transfer (OIML) ticket and a standard or
batch ticket, only the transfer (OIML) ticket will be printed. With the exception of ticket printing and
transfer reset, you can assign one or more actions to a single discrete input. All applicable assigned
actions will be performed. Other discrete input actions and assignments are listed and defined in
Table 7-14.
• If you will use the batch reset function, you can press the RESET button from the batch
process screen, or you can assign the batch reset function to a discrete input or discrete
event (see Section 11.7).
7. If desired, you can define an alarm log password that will be required for the user to access the
active alarm log, the alarm history, and the event log. To do this, refer to Figure 14-2 and:
a. Define the four button-presses that will be used for the alarm log password.
b. Enable the alarm log password.
Note: Once enabled, the alarm log password will be required to re-enter this menu and change or
disable the alarm log password.
8. [Measuring Instruments Directive (MID) compliance] Read and document the Field
Verification Zero (FVZ) value. To read FVZ, you must configure the process monitor to
display it. See Section 12.3.
Note: This is required only for systems that include a transmitter. If your custody transfer application
is running on a Model 3300 or Model 3350 controller, you do not have an FVZ value.
9. (Gas applications in Germany) Read and document the checksum values for the transmitter
and core processor firmware in your flowmeter.
Note: The checksum values may also be useful for MID test reports.
10. Set the security switch on your Series 3000 device. The security switch is a hardware switch.
Security does not take effect until the security switch is ON. Detailed instructions for the
different Series 3000 devices are provided in Section 14.6.
11. Contact an authorized agent for installation of the Weights and Measures seal. Detailed
instructions for the different Series 3000 devices are provided in Section 14.7.

110 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Custody Transfer

Configuring Digital Communications


Figure 14-2 Security menu for custody transfer (OIML) and custody transfer (OIML/batch)

Security

Weights & Measures Alarm log

World area Enable alarm log password


• NTEP
• OIML Alarm log password

Process monitoring

Configuring Custody Transfer


Discrete batch(1)
API(2) (1) Displayed only if discrete batch application is installed.
Enhanced density(3) (2) Displayed only if petroleum measurement application is installed.
Transmitter checksum(4) (3) Displayed only if enhanced density application is installed.
Core checksum(4)
Switch status(4) (4) Read-only.

14.6 Setting the security switch


Security for custody transfer will not take effect until the security switch has been set to ON. The
security switch is a hardware switch.
Note: Current status of the security switch can be viewed using the display, but the display cannot be
used to change the security switch setting.
This step provides instructions for:
• Panel-mount devices (Model 3300 or Model 3500)

Configuring Tickets
• Rack-mount devices (Model 3300 or Model 3500)
• Field-mount devices (Model 3350 or Model 3700)
Follow the instructions for your device.

14.6.1 Panel-mount devices


To set the security switch on a Model 3300 or Model 3500 mounted in a panel:
1. Power down the device.
Note: If you set the security switch on a panel-mount device while power is on, communications
alarms may be produced.
2. Loosen the captive screws in the bracket that holds the screw-type wiring connectors or I/O
cables in place on the back panel of the Series 3000 device.
3. Pull the bracket away from the back panel.
Startup

4. The security switch is located on the back panel. To secure the device, set the switch so the
toggle is downward. See Figure 14-3.
5. Plug the bracketed wiring connectors or I/O cables onto the terminal strips in the back panel.
6. Tighten the captive screws to secure the bracket to the back panel.
7. Restore power to the device.

Configuration and Use Manual 111


Configuring Custody Transfer

Figure 14-3 Security switch on panel-mount Model 3300 or Model 3500

Custody transfer tab


Seal wire will be installed by weights and
measures inspector (see Section 14.7)

Security switch
Security is enabled when toggle is downward

14.6.2 Rack-mount devices


To set the security switch on a Model 3300 or Model 3500 mounted in a rack:
1. Loosen the captive screws that secure the front panel of the Series 3000 device to the rack.
2. Slide the platform out of the rack.
3. Remove the protective mask (see Figure 14-4).
4. The security switch is located on the back panel of the platform. To secure the device, set the
switch so the toggle is downward. See Figure 14-4.
5. Reinstall the protective mask.
6. Install a weights and measures seal (see Section 14.7) through the custody transfer tab shown
in Figure 14-4. This installation must be performed by a weights and measures inspector.
7. Align the platform with the guide rails in the rack.
8. Slide the platform into the rack. Make sure the pins on the back panel make contact with the
wiring connectors.
9. (Optional) Replace the top two or bottom two screws in the front panel of the platform with the
supplied lockout screws. See Figure 14-5.
10. Make sure all four front-panel screws are tightly secured to the guide rails in the rack.
11. (Optional) Install a weights and measures seal through the holes in the front panel. See
Figure 14-5.

112 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Custody Transfer

Configuring Digital Communications


Figure 14-4 Security switch on rack-mount Model 3300 or Model 3500

Custody transfer tab


Seal wire will be installed by weights and
Protective mask measures inspector (see Section 14.7)

Security switch

Configuring Custody Transfer


Security is enabled when
toggle is downward

Figure 14-5 Installing lockout screws on rack-mount platform


Optional seal wire will be installed by weights
and measures inspector (see Section 14.7)

Replace top 2 or bottom 2


screws with the supplied
lockout screws

Configuring Tickets
2 x Lockout screw

14.6.3 Field-mount devices

WARNING
Explosion hazard.

In an explosive atmosphere, do not remove the circuit board compartment


cover within 2 minutes after power has been disconnected.
Startup

Figure 14-6 identifies the circuit board compartment.

Configuration and Use Manual 113


Configuring Custody Transfer

CAUTION
Improper handling of device components can damage the Series 3000
device.

If a breaker bar or other tool is used for loosening the cover of the circuit board
compartment:

• Apply steady pressure to avoid chipping the paint. Chipped paint can result in
corrosion of the housing. If the paint is chipped, repaint the housing.
• Do not apply excessive torque. Excessive torque can damage the pipeline or the
platform.

To set the security switch on the Model 3350 or Model 3700:


1. Unscrew the circuit board compartment cover.
2. The security switch is located on the panel inside the circuit board compartment. To secure the
device, set the switch so the toggle is toward the mounting bracket for the Series 3000 device.
See Figure 14-6.
3. Reinstall the cover. Tighten the cover to 12 ft-lb (16 N-m) torque.

Figure 14-6 Security switch on Model 3350 or Model 3700


Circuit board compartment
Do not open within 2 minutes
after power has been
disconnected

Custody transfer hasp and tab (×4)


Seal wire will be installed by weights and
measures inspector (see Section 14.7)

Security switch
Security is enabled
when toggle is toward mounting
bracket

114 Micro Motion® Series 3000 MVD Transmitters and Controllers


Configuring Custody Transfer

Configuring Digital Communications


14.7 Installing the weights and measures seal
The weights and measures seal must be installed and secured by a weights and measures inspector or
authorized third party.
• On a panel-mount Model 3300 or Model 3500, the inspector runs the wire seal through the
custody transfer tab, as shown in Figure 14-3.
• On a rack-mount Model 3300 or Model 3500, two locations are provided for the weights and
measures seal:
- Required: The inspector must run a wire seal through the custody transfer tab, as shown in
Figure 14-4.
- Optional: The inspector may run a wire seal through the holes in the lockout screws on the
front panel of the platform, as shown in Figure 14-5.
• On a field-mount Model 3350 or Model 3700, a hasp on the housing is located beside the

Configuring Custody Transfer


circuit board compartment cover. The cover has four tabs. The inspector runs the wire seal
through the hole in the hasp and the hole in the nearest tab, as shown in Figure 14-6.

Configuring Tickets
Startup

Configuration and Use Manual 115


116 Micro Motion® Series 3000 MVD Transmitters and Controllers
Configuring Digital Communications
Chapter 15
Ticket Formatting and Printing

15.1 About this chapter


This chapter explains how to format and print tickets. To print tickets, digital communication to a
printer must be configured. See Section 13.3.2.

Configuring Custody Transfer


Failure to perform configuration tasks in the proper sequence could result in an incomplete
configuration. See Section 1.7 for the recommended configuration sequence.

CAUTION
Changing configuration can affect device operation.

Set control devices for manual operation before changing device configuration.

15.2 Ticket overview


There are five ticket types. Different ticket types are available, depending on the discrete batch
application and the custody transfer application (see Table 15-1). Contents of each ticket type are
listed in Table 15-2.
You can format each ticket type separately. For some ticket types, you can specify that certain types of
content will be included or excluded, and you can configure the tickets to print automatically, e.g., at

Configuring Tickets
certain points in a discrete batch, or when an event occurs. You can also print tickets manually at
certain times, using either the PRINT button on the display or a discrete input.
Format only the ticket types that you will use. Formatting of each ticket type is described in Sections
15.3 through 15.6.

Startup

Configuration and Use Manual 117


Ticket Formatting and Printing

Table 15-1 Ticket availability

Tickets available
Batch Transfer Batch
Special applications Standard Batch(1) (NTEP)(2) (OIML) (OIML)(3)
None ✓
Discrete batch application ✓ ✓
Custody transfer application (NTEP) ✓ ✓(4)
(Requires discrete batch application)
Custody transfer application (OIML) ✓ ✓(5)(6) ✓(4)
(Discrete batch application not installed, or installed
but not approved)
Custody transfer application (OIML/batch) ✓ ✓(4) ✓(4)
(Requires discrete batch application installed and
approved)
(1) Refers to batch tickets when (a) the custody transfer application is not installed, or (b) the custody transfer application is installed,
World Area is set to OIML, and the discrete batch application is not approved for custody transfer.
(2) Refers to batch tickets when the custody transfer application is installed and World Area is set to NTEP.
(3) Refers to batch tickets when the custody transfer application is installed, World Area is set to OIML, and the discrete batch
application is approved for custody transfer.
(4) Legal receipt.
(5) Not a legal receipt.
(6) Available only if the discrete batch application is installed.

Table 15-2 Ticket contents

Ticket contents
Ticket type Header lines (standard) Ticket contents (conditional)
Standard 1 and 2 • Depends on ticket (e.g., • “*Approved Measurement*” banner
3 and 4(1) process monitor data, alarm
log, etc.)
Batch 1 and 2 • Batch date and time • “Not A Legal Receipt” banner(2)
• Batch data
• Print timestamp
Batch (NTEP) 1 and 2 • Batch date and time • “Duplicate Receipt” banner
3 and 4 • Batch data • “Security Breach” banner
• Batch BOL number • “Not A Legal Receipt” banner
Transfer (OIML) 1 and 2 • Transfer date and time • “Not Complete” banner with current flow rate
3 and 4 • Transfer data data
• Transfer BOL number • “Complete” banner
• “Alarm occurred during the Transfer” banner(3)
Batch (OIML) 1 and 2 • Batch date and time • “Duplicate Receipt” banner
3 and 4 • Batch data • “Security Breach” banner
• Batch BOL number • “Not A Legal Receipt” banner
(1) Audit event log tickets only. Lines 3 and 4 are formatted and printed as configured for transfer tickets.
(2) Appears only when the custody transfer application is installed, World Area is set to OIML, and the discrete batch application is not
approved for custody transfer.
(3) Alarm may or may not have been a security breach.

118 Micro Motion® Series 3000 MVD Transmitters and Controllers


Ticket Formatting and Printing

Configuring Digital Communications


15.3 Standard tickets
This section describes the formatting and printing of standard tickets.

15.3.1 Formatting
To format standard tickets:
1. In the Digital Communication menu, select Configure RS-485 and set Protocol to Printer.
The menu shown in Figure 15-1 is displayed.
2. Select Configure printer.
3. Set parameters as desired. See Table 15-3.
Note: Other parameters in this menu are defined in Table 13-3.
Note: The Header Line 1, Header Line 2, and Footer parameters are shared with all ticket types. Any

Configuring Custody Transfer


formatting defined for standard tickets is applied to all tickets.
Note: Because the audit trail is a custody transfer feature and requires the custody transfer
application, audit event log tickets include the Header Line 3 and Header Line 4 parameters
configured for transfer tickets (see Section 15.6.1 or Section 15.5.1). In all other respects, audit event
log tickets are standard tickets.

Figure 15-1 Ticket configuration menu – Standard tickets

Digital comm

Configure RS-485

Configuring Tickets
Protocol Configure printer Discrete inputs Printer test

• HART • Printer selection • Print screen


• Modbus RTU • Pre header codes(1) • Screens to print
• Modbus ASCII • Header line 1–2 • Print process monitor
• Printer • Footer
• Post footer codes(1)
• Baud rate
• Parity
• Data bits
• Stop bits
• Chars per second
• Print buf size
• Lines per page (1) Not displayed if custody transfer application is installed.
• Number of tickets(2) (2) Displayed only if discrete batch application is installed,
• Auto print(2) and applies only to batch tickets.
• Disable paper check(3)
(3) Not displayed if custody transfer World Area is set to
OIML.
Startup

Configuration and Use Manual 119


Ticket Formatting and Printing

Table 15-3 Ticket parameters for standard tickets

Variable Default Description


Pre header codes None Printer control codes. Enter any control codes required by your
Post footer codes printer, e.g., form feed.(1)
Header line 1 Text Blank (no text) Enter the text for this line of the header or for the footer.
Header line 2 You may enter up to 22 characters. Scroll as required to view all
Footer characters.
Line feeds 1 line Enter 1, 2, or 3. This parameter controls the space between the
current line and the following line.
Font size Normal height Select normal height or double height.(2)
(1) ASCII non-printable control codes are represented by a two-character sequence in hexadecimal format; e.g., the linefeed character
is “0A" (zero, A). Leading or trailing spaces are ignored, but spaces must not be inserted between hex codes.
(2) Not all printers are capable of double height. If double height is configured but the printer cannot print double height, normal height
will be used.

15.3.2 Printing
You can print standard tickets manually, via the display, or via a discrete input. You can also specify
that tickets will be printed automatically if a discrete event occurs. You may use as many of these
methods as desired.

Display
To print standard tickets from the display, use the PRINT button. The PRINT button appears whenever
the print function is available. For example, you can print:
• The current process monitor screen
• All configured process monitor screens
• All configuration data
• The active alarm log, alarm history, or alarm event log
If the Series 3000 device is connected to a standard core processor, you can specify whether or not
process monitor tickets will include the average, maximum, and minimum values for process
variables, when appropriate. To do this, use the Print Process Monitor option described in the
following section.

Discrete input or discrete event


You can configure the Series 3000 device so that a standard ticket is printed whenever a discrete input
is activated or a discrete event occurs. This ticket can include one or several screens; all assigned
screens will be printed. To do this:
1. From the Digital Communication menu (see Figure 15-1), select Configure RS-485, then
select Discrete Inputs.
2. Using the Print screen option, select the discrete input or discrete event to which you will
assign screens.
3. Using the Screens to print option, specify the screens that will be printed when the specified
discrete input is activated or the discrete event occurs. You may specify as many screens as
desired.
4. (Standard core processor only) If you specified a process monitor screen, use the Print
Process Monitor option to control whether or not the ticket will include the average,
maximum, and minimum values for process variables, when appropriate (With Stats or
Without Stats).

120 Micro Motion® Series 3000 MVD Transmitters and Controllers


Ticket Formatting and Printing

Configuring Digital Communications


Note: You can assign one or more actions to a single discrete input or discrete event. Other discrete
input and discrete event actions and assignments are listed and defined in Table 7-14. Note that if you
assign ticket printing to a discrete input or a discrete event, all standard, batch, batch (NTEP), and
batch (OIML) tickets will be printed, but if a transfer (OIML) ticket is assigned with other ticket types,
only the transfer (OIML) ticket will be printed. If required, assign the transfer (OIML) ticket to one
discrete input and assign all other tickets to the second discrete input.

15.4 Batch tickets


This section describes the formatting and printing of batch tickets.

15.4.1 Formatting
To format batch tickets:

Configuring Custody Transfer


1. In the Digital Communication menu, select Configure RS-485 and set Protocol to Printer.
The menu shown in Figure 15-2 is displayed.
2. Select Configure Printer.
3. Set parameters as desired. See Table 15-4.
Note: Other parameters in this menu are defined in Table 13-3.
Note: The Header Line 1, Header Line 2, and Footer parameters are shared with all ticket types. Any
formatting defined for batch tickets is applied to all tickets.

Figure 15-2 Ticket configuration menu – Batch tickets

Digital comm

Configuring Tickets
Configure RS-485

Protocol Configure printer Discrete inputs Printer test


• HART
• Modbus RTU • Printer selection • Print screen
• Modbus ASCII • Pre header codes • Screens to print
• Printer • Header line 1 – 2 • Print process monitor
• Footer
• Post footer codes
• Baud rate
• Parity
• Data bits
• Stop bits
• Chars per second
• Print buf size
• Lines per page
• Number of tickets (1) Not displayed if custody transfer application is installed
and World Area is set to OIML.
Startup

• Auto print
• Disable paper check(1)

Configuration and Use Manual 121


Ticket Formatting and Printing

Table 15-4 Ticket parameters for batch tickets

Variable Default Description


Pre header codes None Printer control codes. Enter any control codes required by your
Post footer codes printer, e.g., form feed.
Header line 1 Text Blank (no text) Enter the text for this line of the header or for the footer.
Header line 2 You may enter up to 22 characters. Scroll as required to view all
Footer characters.
Line feeds 1 line Enter 1, 2, or 3. This parameter controls the space between the
current line and the following line.
Font size Normal height Select normal height or double height.(1)
Number of 1 The number of batch tickets to be printed by the Auto Print
tickets function (if Auto Print is enabled) or by a manual print request.
Auto print No • Select Yes if you want batch tickets to be printed automatically at
the end of each batch. Tickets will be printed only if the target
has been reached and flow is stopped.
• Select No if you do not want tickets to be printed automatically at
the end of each batch.
(1) Not all printers are capable of double height. If double height is configured but the printer cannot print double height, normal height
will be used.

15.4.2 Printing
Batch tickets can be printed in several ways:
• Automatically, when the batch ends or when a discrete event occurs
• Manually, using the display or a discrete input
Note: Information in this section applies only to batch tickets that are not used as custody transfer
tickets. For information on printing batch tickets used as custody transfer tickets, see Section 15.5.2
for batch (NTEP) tickets, or Section 15.6.2 for batch (OIML) tickets.

Auto print
To print batch tickets automatically when the batch target is reached, configure the Auto Print and
Number of Tickets parameters as required (see Table 15-4).

Display
To print batch tickets from the display, use the PRINT button. The PRINT button appears only when
the batch is ended; it does not appear when the batch is stopped.

Discrete input or discrete event


You can configure the Series 3000 device so that a batch ticket is printed whenever a discrete input is
activated or a discrete event occurs. This ticket can include one or several screens in addition to the
batch screen; all assigned screens will be printed. To do this:
1. From the Digital Communication menu (see Figure 15-1), select Configure RS-485, then
select Discrete Inputs.
2. Using the Print Screen option, select the discrete input or discrete event to which you will
assign screens.
3. Using the Screens to Print option, specify the screens that will be printed when the specified
discrete input is activated or the discrete event occurs. You may specify as many screens as
desired.

122 Micro Motion® Series 3000 MVD Transmitters and Controllers


Ticket Formatting and Printing

Configuring Digital Communications


If the print request occurs:
• When flow is not present (the batch is stopped or ended), the batch ticket is printed.
• When flow is present, the request is queued until flow stops, and the batch ticket is printed at
that time.
Note: You can assign one or more actions to a single discrete input or discrete event. Other discrete
input and discrete event actions and assignments are listed and defined in Table 7-14. Note that if you
assign ticket printing to a discrete input or a discrete event, all standard, batch, batch (NTEP), and
batch (OIML) tickets will be printed, but if a transfer (OIML) ticket is assigned with other ticket types,
only the transfer (OIML) ticket will be printed. If required, assign the transfer (OIML) ticket to one
discrete input and assign all other tickets to the second discrete input.

Multiple tickets
If multiple tickets are printed:

Configuring Custody Transfer


• With one print request, all tickets are identical.
• With multiple print requests, each ticket contains the timestamp and batch data that was
current when the ticket was printed.

15.5 Batch (NTEP) tickets


This section describes the formatting and printing of transfer tickets when the custody transfer
application is configured for World Area = NTEP.

15.5.1 Formatting
The batch (NTEP) ticket is basically a batch ticket, with a few additional options. To format batch
(NTEP) tickets:
1. Format a batch ticket as described in Section 15.4.1.

Configuring Tickets
2. In the Digital Communication menu, select Configure RS-485, then select Format W&M
Ticket. The menu shown in Figure 15-3 is displayed.
3. Set parameters as desired. See Table 15-5.
Note: Other parameters in this menu are defined in Table 13-3.
Note: The Pre Header, Post Footer, Header Line 1, Header Line 2, and Footer parameters are shared
with all ticket types. Any formatting defined for batch (NTEP) tickets is applied to all tickets.

Startup

Configuration and Use Manual 123


Ticket Formatting and Printing

Figure 15-3 Ticket configuration menu – Batch (NTEP) tickets

Digital comm

Configure RS-485

Protocol Configure printer Format W&M ticket Discrete inputs Printer test
• HART
• Modbus RTU • Printer selection • Header line 1 – 4 • Print screen
• Modbus ASCII • Pre header codes • Footer • Screens to print
• Printer • Header line 1 – 2 • Batch start no. (BOL) • Print process monitor
• Footer
• Post footer codes
• Baud rate
• Parity
• Data bits
• Stop bits
• Chars per second (1) Does not apply to batch (NTEP) tickets. Only one batch
• Print buf size
• Lines per page
(NTEP) ticket can be printed at a time, whether printed
• Number of tickets(1) automatically or manually.
• Auto print
• Disable paper check

Table 15-5 Ticket parameters – Batch (NTEP) tickets

Variable Default Description


Header line 1 Text Blank (no text) Enter the text for this line of the header or for the footer.
Header line 2 You may enter up to 22 characters. A maximum of 21 characters
Header line 3 are displayed. Scroll as required to view all characters.
Header line 4
Line feeds 1 line Enter 1, 2, or 3. This parameter controls the space between the
Footer
current line and the following line.
Font size Normal height Select normal height or double height.(1)
Batch start no. 0 Starting ticket number for batch bills of lading (BOL).
(BOL)
(1) Not all printers are capable of double height. If double height is configured but the printer cannot print double height, normal height
will be used.

15.5.2 Printing
Batch (NTEP) tickets can be printed in several ways:
• Automatically, when the batch ends or when a discrete event occurs
• Manually, using the display or a discrete input
Only one batch (NTEP) ticket can be printed at a time; the Number of Tickets parameter is not
applied.
The custody transfer transaction ends when the first batch (NTEP) ticket is printed for the current
batch. This is true even when the batch is ended, the target is increased, and the batch is then resumed.
In this case, all tickets will contain identical custody transfer data, even though the batch data may
have changed.

124 Micro Motion® Series 3000 MVD Transmitters and Controllers


Ticket Formatting and Printing

Configuring Digital Communications


Auto print
To print a batch (NTEP) ticket automatically when the batch target is reached, set the Auto Print
parameter for batch tickets to Yes (see Table 15-4).

Display
To print a batch (NTEP) ticket from the display, use the PRINT button on the batch process screen.
The PRINT button appears only when the batch is ended; it does not appear when the batch is stopped.

Discrete input or discrete event


You can configure the Series 3000 device to print a batch (NTEP) ticket when a discrete input is
activated or a discrete event occurs. This ticket can include one or several screens in addition to the
batch (NTEP) ticket; all assigned screens will be printed. To do this:
1. From the Digital Communication menu (see Figure 15-1), select Configure RS-485, then

Configuring Custody Transfer


select Discrete Inputs.
2. Using the Print Screen option, select the discrete input or discrete event to which you will
assign screens.
3. Using the Screens to Print option, specify the screens that will be printed when the specified
discrete input is activated or the discrete event occurs. You may specify as many screens as
desired.
If the print request occurs:
• When flow is not present (the batch is stopped or ended), the batch (NTEP) ticket is printed.
• When flow is present, the request is queued until flow stops, and the batch (NTEP) ticket is
printed at that time.
Note: You can assign one or more actions to a single discrete input or discrete event. Other discrete
input and discrete event actions and assignments are listed and defined in Table 7-14.

Additional tickets

Configuring Tickets
Before the batch reset is performed, additional batch (NTEP) tickets for the current transaction can be
printed manually, by using the PRINT button or by activating a discrete input that has been configured
to print a batch (NTEP) ticket. The batch (NTEP) tickets will contain identical custody transfer data,
and all tickets except the first, will include the “Duplicate receipt” banner.

15.6 Transfer (OIML) tickets


This section describes the formatting and printing of transfer tickets when the custody transfer
application is configured for World Area = OIML and the discrete batch application is not used to
manage the custody transfer transaction.

15.6.1 Formatting
To format transfer (OIML) tickets:
1. In the Digital Communication menu, select Configure RS-485 and set Protocol to Printer.
Startup

The menu shown in Figure 15-4 is displayed.


2. Select Format W&M Ticket.
3. Set parameters as desired. See Table 15-6.

Configuration and Use Manual 125


Ticket Formatting and Printing

Note: The Pre Header, Post Footer, Header Line 1, Header Line 2, and Footer parameters are shared
with all ticket types. Any formatting defined for transfer (OIML) tickets is applied to all tickets.
Note: Other parameters in this menu are defined in Table 13-3.
Note: In previous versions of the custody transfer application, a Transfer Total Format parameter was
displayed. This has been replaced by the W&M Approval option (see Section 14.5, Step 4).

Figure 15-4 Ticket configuration menu – Transfer (OIML) tickets

Digital comm

Configure RS-485

Protocol Configure printer Format W&M ticket Discrete inputs Printer test
• HART
• Modbus RTU • Printer selection Header line 1 – 4 • Transfer print screen(2)
• Modbus ASCII • Pre header codes • Transfer screens to
• Printer • Header line 1 – 2 Transfer ticket print(2)
• Footer • Transfer start (BOL) • Print screen(3)
• Post footer codes • Transfer print • Screens to print(3)
• Baud rate conditions • Print process monitor
• Parity • Transfer form feed
• Data bits • Alarm occurred
• Stop bits • Number of transfer
• Chars per second tickets
• Print buf size
• Lines per page Footer
• Number of tickets(1)
• Auto print(1)

(1) Not applicable to transfer (OIML) tickets.


(2) Used to print transfer (OIML) tickets.
(3) Used to print other ticket types.

Table 15-6 Ticket parameters – Transfer (OIML) tickets

Variable Default Description


Pre header codes None Printer control codes. Enter any control codes required by your
Post footer codes printer, e.g., form feed.
Header line 1 Text Blank (no text) Enter the text for this line of the header or for the footer.
Header line 2 You may enter up to 22 characters. Scroll as required to view
Header line 3 all characters.
Header line 4
Line feeds 1 line Enter 1, 2, or 3. This parameter controls the space between the
Footer
current line and the following line.
Font size Normal height Select normal height or double height.(1)

126 Micro Motion® Series 3000 MVD Transmitters and Controllers


Ticket Formatting and Printing

Configuring Digital Communications


Table 15-6 Ticket parameters – Transfer (OIML) tickets continued

Variable Default Description


Transfer Transfer start 0 Starting ticket number for transfer bills of lading (BOL).
ticket (BOL) Changing the start number resets the transfer log. If the start
number is changed after transfers have been completed, all
data in the transfer log is lost.
Transfer print With flow • No Flow – Tickets cannot be printed if there is any flow
conditions through the sensor. If a ticket is printed under conditions of
no flow, and the ticket includes a transfer total, the transfer is
completed, and the flow rate and the banner “Complete” are
printed on the ticket.
• With Flow – Tickets may be printed while flow is occurring.
- If a ticket is printed while flow is occurring, the flow rate and
the banner “Not complete” are printed on the ticket, and the
transfer continues.

Configuring Custody Transfer


- If a ticket is printed under conditions of no flow and the ticket
includes a transfer total, the transfer is completed, and the
flow rate and the banner “Complete” are printed on the
ticket.
- If a ticket is printed under conditions of no flow and the ticket
does not include a transfer total, the flow rate is printed on
the ticket and the transfer is not completed.
Transfer form feed No • No – A form feed will not be issued automatically after a ticket
has been printed.
• Yes – A form feed will be issued automatically after a ticket
has been printed.
Alarm occurred No • No – Tickets will not include the banner “Alarm occurred
during the transfer” if an alarm occurs during transfer
processing.
• Yes – Tickets will include the banner “Alarm occurred during
the transfer” if an alarm occurs during transfer processing.
Number of 1 The number of transfer (OIML) tickets to be printed when a
transfer tickets print request is received. The range is 1 to 3.(2)
(1) Not all printers are capable of double height. If double height is configured but the printer cannot print double height, normal height

Configuring Tickets
will be used.
(2) Each print request (depending on flow and ticket contents) completes a transaction. If duplicate tickets are required for each
transaction, you must specify the required number here; there is no other way to print duplicate tickets. All tickets for the same
transfer are identical; they do not contain the “Duplicate receipt” banner.

15.6.2 Printing
Transfer (OIML) tickets must be printed manually, using either the PRINT button on the display or a
discrete input configured to print a transfer (OIML) ticket.
The results of the print request depend on the flow at the time of the print request and the Transfer
Print Conditions parameter, and the contents of the ticket, as shown in Table 15-7. Startup

Configuration and Use Manual 127


Ticket Formatting and Printing

Table 15-7 Results of print request for transfer (OIML) tickets

Flow at time of Ticket contains Transfer Print


print request? transfer total? Conditions Result
Flow present N/A With Flow • “Not Complete” banner and flow rate printed on ticket
• Current transfer totals are printed on ticket, but not
marked with asterisks even if the process variables
are approved
• Transfer continues
N/A No Flow • Ticket not printed
• Transfer continues
No flow Yes N/A • “Complete” banner printed on ticket
• Transfer total printed on ticket
• Approved process variables marked with asterisks
• Custody transfer transaction completed automatically
• Transfer data written to transfer log
• Transfer BOL number incremented
• Next custody transfer transaction started
No N/A • “Not Complete” banner and flow rate printed on ticket
• Transfer continues

Display
Note: This function is not available if flow is present and Transfer Print Conditions is set to No Flow.
To print a transfer (OIML) ticket from the display:
1. From the View menu, select Transfer Totalizer.
2. Select the type of ticket you want to print.
3. Press the PRINT button.

Discrete input
You can configure a discrete input to print a transfer (OIML) ticket.
Note: You can assign one or more actions to a single discrete input. Other discrete input actions and
assignments are listed and defined in Table 7-14. Note that if you assign ticket printing to a discrete
input, all standard, batch, and batch (OIML) tickets can be printed from one discrete input, but if a
transfer (OIML) ticket is assigned with other ticket types, only the transfer (OIML) ticket will be
printed. If required, assign the transfer (OIML) ticket to one discrete input and assign all other tickets
to the second discrete input.
To do this:
1. From the Digital Communication menu (see Figure 15-4), select Configure RS-485, then
select Discrete Inputs.
2. Use the Transfer Print Screen option to select the discrete input to which you will assign the
transfer (OIML) ticket.
3. Use the Transfer Screen to Print option to specify the set of data that will be printed when the
specified discrete input is activated.
• If Transfer Totals, Transfer & Inventory, API Transfer & Inventory or ED Transfer &
Inventory is selected, printing this ticket under conditions of no flow will cause the
transfer to be completed and transfer data to be recorded in the transfer log.
• If Inventory is selected, printing this ticket will not cause the transfer to be completed and
no data will be recorded in the transfer log.

128 Micro Motion® Series 3000 MVD Transmitters and Controllers


Ticket Formatting and Printing

Configuring Digital Communications


Note: The Transfer Print Screen and Transfer Screens to Print options are similar to the Transfer
Reset Screen and Transfer Scr To Reset menu options described in Section 14.5, Step 6, except that
this menu includes the Inventory option, and if the discrete input is configured here, a ticket will be
printed when the discrete input is activated. The discrete input and transfer screens specified here are
reflected in the corresponding reset menu options, and vice versa.

Multiple tickets
If multiple tickets are required, set Number of Transfer Tickets to the required number. Because a
transfer (OIML) print request may complete the current transfer and begin a new one, you cannot use
multiple print requests to print duplicate tickets. All tickets for the same OIML transfer are identical;
they do not contain the “Duplicate receipt” banner.

15.7 Batch (OIML) tickets

Configuring Custody Transfer


This section describes the formatting and printing of transfer tickets when the custody transfer
application is configured for World Area = OIML and the discrete batch application is used to manage
the custody transfer transaction.

15.7.1 Formatting
To format batch (OIML) tickets:
1. In the Digital Communication menu, select Configure RS-485 and set Protocol to Printer.
The menu shown in Figure 15-4 is displayed.
2. Select Format W&M Ticket.
3. Set parameters as desired. See Table 15-6.
Note: The Pre Header, Post Footer, Header Line 1, Header Line 2, and Footer parameters are shared
with all ticket types. Any formatting defined for transfer (OIML) or batch (OIML) tickets is applied to
all tickets.

Configuring Tickets
Note: Other parameters in this menu are defined in Table 13-3.
Note: In previous versions of the custody transfer application, a Transfer Total Format parameter was
displayed. This has been replaced by the W&M Approval option in the Configuration > Monitoring
menu (see Section 14.5, Step 4).

Startup

Configuration and Use Manual 129


Ticket Formatting and Printing

Figure 15-5 Ticket configuration menu – Batch (OIML) tickets

Digital comm

Configure RS-485

Protocol Configure printer Format W&M ticket Discrete inputs Printer test
• HART
(2)
• Modbus RTU • Printer selection Header line 1 – 4 • Transfer print screen
• Modbus ASCII • Pre header codes • Transfer screens to
• Printer • Header line 1 – 2 Transfer ticket(2) print(2)
• Footer • Print screen
• Post footer codes Footer • Screens to print
• Baud rate • Print process monitor
• Parity Batch start no. (BOL)
• Data bits
• Stop bits
• Chars per second
• Print buf size
• Lines per page
• Number of tickets(1)

(1) Applies only to batch tickets. Not applicable to batch (OIML) tickets.
(2) Not applicable to batch (OIML) tickets.

Table 15-8 Ticket parameters – Batch (OIML) tickets

Variable Default Description


Pre header codes None Printer control codes. Enter any control codes required by your
Post footer codes printer, e.g., form feed.
Header line 1 Text Blank (no text) Enter the text for this line of the header or for the footer.
Header line 2 You may enter up to 22 characters. Scroll as required to view
Header line 3 all characters.
Header line 4
Line feeds 1 line Enter 1, 2, or 3. This parameter controls the space between the
Footer
current line and the following line.
Font size Normal height Select normal height or double height.(1)
Transfer Not applicable to batch (OIML) tickets.
ticket
Batch start Starting ticket number for batch bills of lading (BOL).
number
(BOL)
(1) Not all printers are capable of double height. If double height is configured but the printer cannot print double height, normal height
will be used.

130 Micro Motion® Series 3000 MVD Transmitters and Controllers


Ticket Formatting and Printing

Configuring Digital Communications


15.7.2 Printing
Batch (OIML) tickets can be printed in several ways:
• Automatically, when the batch ends
• Manually, using the display or a discrete input
Only one batch (OIML) ticket can be printed at a time; the Number of Tickets parameter is not
applied.
The custody transfer transaction ends when the first batch (OIML) ticket is printed for the current
batch. This is true even when the batch is ended, the target is increased, and the batch is then resumed.
In this case, all tickets will contain identical custody transfer data, even though the batch data may
have changed.

Auto print

Configuring Custody Transfer


To print a batch (OIML) ticket automatically when the batch target is reached, set the Auto Print
parameter for batch tickets to Yes (see Table 15-8).

Display
To print a batch (OIML) ticket from the display, use the PRINT button on the batch process screen.
The PRINT button appears only when the batch is ended; it does not appear when the batch is stopped.

Discrete input or discrete event


You can configure the Series 3000 device to print a batch (OIML) ticket when a discrete input is
activated or a discrete event occurs. This ticket can include one or several screens in addition to the
batch (OIML) ticket; all assigned screens will be printed.
Note: You can assign one or more actions to a single discrete input or discrete event. Other discrete
input and discrete event actions and assignments are listed and defined in Table 7-14. Note that if you
assign ticket printing to a discrete input or a discrete event, all standard and batch (OIML) tickets can
be printed from one discrete input or discrete event, but if a transfer (OIML) ticket is assigned with

Configuring Tickets
other ticket types, only the transfer (OIML) ticket will be printed. If required, assign the transfer
(OIML) ticket to one discrete input and assign all other tickets to the second discrete input.
To do this:
1. From the Digital Communication menu (see Figure 15-4), select Configure RS-485, then
select Discrete Inputs.
2. Use the Print Screen option to select the discrete input to which you will assign the batch
(OIML) ticket.
3. Use the Screens to Print option to specify that a batch ticket will be printed. Printing this
ticket will always complete the transfer.

Multiple tickets
If multiple tickets are required, use the PRINT button or the discrete input to print additional tickets
before the batch is reset. One ticket will be printed for each print request. The additional tickets will
contain the “Duplicate receipt” banner.
Startup

Configuration and Use Manual 131


132 Micro Motion® Series 3000 MVD Transmitters and Controllers
Configuring Digital Communications
Chapter 16
Startup Procedures

16.1 About this chapter


This chapter explains the procedures that are required for initial startup of the Series 3000 device.
After initial startup, these procedures may be performed as required for troubleshooting or
maintenance.

Configuring Custody Transfer


The following procedures are discussed:
• Applying power to the flowmeter
• Sensor zero
• Testing the inputs and outputs
• Milliamp output trim
Note: If you are using a Model 3300 or Model 3350 controller, the sensor zero procedure is not
applicable to your device. Perform the other procedures as applicable.

16.2 Applying power


Before you apply power to the Series 3000 device, close and tighten all housing covers.

WARNING

Configuring Tickets
Operating the Series 3000 device without covers in place creates electrical
hazards that can cause death, injury, or property damage.

Make sure safety barrier partition and covers for the field-wiring, circuit board
compartments, electronics module, and housing are all in place before applying
power to the Series 3000 device.

Turn on the electrical power at the power supply. The flowmeter automatically tests its display.
During display testing, the screen darkens for approximately five seconds. After the display test is
completed:
1. The Micro Motion logo is displayed for two to three seconds.
2. An application list is displayed for two to three seconds.
3. The device enters operation mode:
Startup

• If the discrete batch application is not installed, the process monitor screen is displayed, as
shown in Figure 17-1.
• If the discrete batch application is installed, the batch process screen is displayed (see
Figure 18-1).

Configuration and Use Manual 133


Startup Procedures

4. If there are any active alarms, the alarm category will be displayed in the alarm bar. To view,
acknowledge, or respond to the alarms, see Chapter 22.
Note: Series 3000 transmitters are ready to begin measurement approximately one minute after
power-up (time varies with models). However, approximately ten minutes are required for the
electronics to warm up to equilibrium. During this ten-minute period, the transmitter may exhibit
minor instability or inaccuracy.

16.2.1 Communication methods after power-up


After power-up:
• Communication via the display is available as soon as the display is visible.
• If you are using the Communicator, or ProLink II with HART/Bell 202, you can establish
communication with the Series 3000 device immediately after power-up, using the primary
mA output terminals. See Appendix G for more information on using ProLink II and
Appendix H for more information on using the Communicator.
• If you are using ProLink II via the RS-485 physical layer, the RS-485 terminals are available
to establish a connection in service port mode for 10 seconds immediately after power-up. If
no service port connection is made during this period, the terminals are automatically reset to
the configured RS-485/Modbus communication parameters. Be sure to set the ProLink II
connection parameters appropriately.

16.3 Sensor zero


Note: This section is not applicable to Model 3300 or Model 3350 controllers.
Zeroing the flowmeter establishes the flowmeter’s point of reference when there is no flow. The meter
was zeroed at the factory, and should not require a field zero. However, you may wish to perform a
field zero to meet local requirements or to confirm the factory zero.
When you zero the flowmeter, you may need to adjust the zero time parameter. Zero time is the
amount of time the transmitter takes to determine its zero-flow reference point. The default zero time
is 20 seconds.
• A long zero time may produce a more accurate zero reference but is more likely to result in a
zero failure. This is due to the increased possibility of noisy flow, which causes incorrect
calibration.
• A short zero time is less likely to result in a zero failure but may produce a less accurate zero
reference.
For most applications, the default zero time is appropriate.
Note: Do not zero the flowmeter if a fault alarm is active. Correct the problem, then zero the
flowmeter. You may zero the flowmeter if a low-severity alarm is active. See Section 22.6 for
information on viewing transmitter status and alarms.

134 Micro Motion® Series 3000 MVD Transmitters and Controllers


Startup Procedures

Configuring Digital Communications


16.3.1 Zero failure and restoring zero values
If the zero procedure fails, see Section 16.3.4 for troubleshooting information.
Additionally, if you have the enhanced core processor:
• You can restore the factory zero. This procedure returns the zero value to the value obtained at
the factory, if the factory configuration has been saved on the transmitter.
• If you are using ProLink II to zero the flowmeter, you can also restore the prior zero
immediately after zeroing (e.g., an “undo” function), as long as you have not closed the
Calibration window or disconnected from the transmitter. Once you have closed the
Calibration window or disconnected from the transmitter, you can no longer restore the prior
zero.

16.3.2 Preparing for sensor zero calibration

Configuring Custody Transfer


To prepare the flowmeter for sensor zero:
1. Install the sensor according to the appropriate sensor instruction manual.
2. Apply power to the Series 3000 system, then allow it to warm up for at least 30 minutes.
3. Run the process fluid to be measured through the sensor until the sensor temperature
approximates the normal process operating temperature.
4. Close the shutoff valve downstream from the sensor.
5. Fill the sensor completely with process fluid under normal process conditions of temperature,
density, pressure, etc., and ensure zero flow through the sensor.
6. Make sure flow through the sensor is completely stopped.

CAUTION

Configuring Tickets
If fluid is flowing through the sensor, the sensor zero calibration may be
inaccurate, resulting in inaccurate process measurement.

To improve the sensor zero calibration and measurement accuracy, ensure that
process flow through the sensor has completely stopped.

16.3.3 Performing the sensor zero calibration


To perform the sensor zero:
1. From the Calibration menu (see Figure 16-1), select Sensor Zero. The Calibration menu is
accessed through the Maintenance option of the Management menu.
2. Check the setting for Zero Time, and change it if desired.
3. Note the value displayed for Mass Flow Rate. If it is non-zero, recheck sensor preparation
(see Section 16.3.2).
4. Select Calibrate Zero, then press SEL. During sensor zero:
Startup

• A Calibration In Progress alarm is generated.


• The time remaining counts down to zero seconds.
• The Calibrate Zero screen displays an “In Progress” status, and the zero offset in
microseconds.

Configuration and Use Manual 135


Startup Procedures

5. When the calibration is complete:


• In the active alarm log, the alarm changes from “active” to “inactive but unacknowledged.”
• If the calibration succeeded, a “Success” status is displayed.
• If the calibration failed, a “Failed” status is displayed.
6. Press EXIT to return to the Sensor Zero screen.
7. (Optional) To clear the alarm from the active alarm log and the alarm bar at the top of the
display, acknowledge the alarm using the procedures described in Chapter 22.

136 Micro Motion® Series 3000 MVD Transmitters and Controllers


Startup Procedures

Configuring Digital Communications


Figure 16-1 Calibration menu

Calibration

Sensor zero mA output trim Batch AOC(3) Density curve trim(4)


(see Chapter 18) (see the enhanced density
manual)

Zero time Milliamp output 1 2


Mass flow rate(1)
Calibrate zero
Restore factory zero(2)
View current data Trim 4.0 mA

Configuring Custody Transfer


• Enter mA reading
• mA output reads
• Does mA out match?

Trim 20.0 mA
• Enter mA reading
• mA output reads
• Does mA out match?

Density Temperature Meter verification


(see Chapter 21) (see Chapter 21) (see Chapter 21)

Low density Low temperature Uncertainty limit


• Density • Low temp. value Counter
• D1 • Calibrate temp. Start meter verify
• Calibrate density

Configuring Tickets
High temperature
High density • High temp. value
• Density • Calibrate temp.
• D2
• Calibrate density View current data

Flowing density
• Actual density
• Calibrate density

Density D3 (T-Series)
• Density
• D3
• Calibrate density
(1) Read-only; displayed for reference only.
Density D4 (T-Series) (2) Displayed only if you are using the enhanced core processor and the
• Density factory configuration has been saved.
• D4
• Calibrate density (3) Displayed only if the discrete batch application is installed.
(4) Displayed only if the enhanced density application is installed.
View current data
Startup

Configuration and Use Manual 137


Startup Procedures

16.3.4 Diagnosing sensor zero failure


If the Calibrate Zero screen reads “Calibration Failure,” the sensor zero calibration was not
successfully completed. “Calibration Failure” could indicate:
• Flow of fluid during the sensor zero calibration
• Partially empty flow tubes
• An improperly mounted sensor
To clear a sensor zero failure:
• Press EXIT to exit the Calibrate Zero screen, then re-zero after correcting the problem, or
• Abort the sensor zero procedure by cycling power to the platform
• If appropriate, restore the factory zero or prior zero (see Section 16.3.1)

16.4 Testing the inputs and outputs


The Diagnostics menu is used to test the inputs and outputs. Figure 16-2 shows the Diagnostics menu.
The Diagnostics menu is accessed through the Maintenance option of the Management menu.
Using the Diagnostics menu, you can:
• Read the states of discrete inputs
• Read the pressure and temperature values as received from external devices
• Read the value of the frequency input
• Set a specific value for discrete outputs, mA outputs, and the frequency output

Figure 16-2 Diagnostics menu

Diagnostics

Read external inputs Simulate outputs

Discrete input 1 Discrete outputs


Discrete input 2 • Discrete output 1
Frequency input • Discrete output 2
External pressure(1) • Discrete output 3
External temperature(2)
Milliamp outputs
• Milliamp output 1
(1) Displayed only if polling for pressure has been configured. • Milliamp output 2
(2) Displayed only if polling for temperature has been configured.
Frequency output

Note: The Diagnostics menu is not the same as the diagnostic monitor. The diagnostic monitor,
accessed through the View menu, allows you to read the values for tube frequency, left pickoff, right
pickoff, drive gain, and live zero. The diagnostic monitor and its use are described in Chapter 17 and
Chapter 22.

138 Micro Motion® Series 3000 MVD Transmitters and Controllers


Startup Procedures

Configuring Digital Communications


16.4.1 Reading and testing the discrete inputs
Refer to Figure 16-2 to access and read the current states of Discrete Input 1 and 2. States are shown
as:
• Yes (ON)
• No (OFF)
To test the discrete inputs, toggle the remote input device and verify that the appropriate value is
received by the Series 3000 device.

16.4.2 Reading and testing the frequency input


If the Series 3000 device has been wired for a frequency input, refer to Figure 16-2 to access and read
the output level of the frequency input. The frequency is displayed in Hz.

Configuring Custody Transfer


To test the frequency input, check the frequency at the remote input device and verify that the
appropriate value is received by the Series 3000 device.

16.4.3 Reading and testing the pressure and external temperature


If polling for pressure or external temperature has been configured, refer to Figure 16-2 to access and
read the pressure and temperature values being received by the Series 3000.
To test the pressure and temperature input, use a reference device and verify that the appropriate value
is received by the Series 3000 device.

16.4.4 Setting and testing outputs


The software enables you to set the states of discrete outputs or the values of milliamp outputs or the
frequency output.

Configuring Tickets
CAUTION
Performing output tests while control devices are set for automatic control
will result in measurement error.

To avoid measurement error, set control devices for manual operation before
performing output tests.

Discrete outputs
Refer to Figure 16-2 to access and set the current states of discrete outputs.
1. Select the discrete output to be set.
2. The default setting is Unfixed. Reset the output to ON or OFF. The outputs associated with ON
and OFF depends on the output’s polarity, as shown in Table 8-1. (For information on setting
the discrete output polarity, see Section 8.3.1.)
3. Press SAVE to set the state of the selected discrete output.
Startup

4. Check the receiving device to ensure that the correct level is being received.
5. Reset the discrete output to Unfixed, or exit to the Simulate Outputs screen. The discrete
output is released and is again controlled by the application.

Configuration and Use Manual 139


Startup Procedures

Milliamp outputs
Refer to Figure 16-2 to access and set the output levels of milliamp outputs.
1. Select the milliamp output to be set.
2. Use the cursor control buttons to change the output value.
3. Press SAVE to set the output level.
4. Check the receiving device to ensure that the correct output level is being received.
When you exit to the Simulate Outputs screen, the milliamp output is released and is again controlled
by the application.
If the difference between the output level sent by the Series 3000 device and the output level received
by the receiving device is not acceptable for your application, perform a milliamp output trim. See
Section 16.5.

Frequency output
Refer to Figure 16-2 to access and set the output levels of the frequency output.
1. Select the frequency output.
2. Use the cursor control buttons to change the output value.
3. Press SAVE to set the value.
4. Check the receiving device to ensure that the correct output level is being received.
When you exit to the Simulate Outputs screen, the frequency output is released and is again controlled
by the application.

16.5 Milliamp output trim


A milliamp output trim creates a common measurement range between the Series 3000 device and the
device that receives the mA output. For instance, a Series 3000 device might send a 4 mA signal that
the receiving device reports incorrectly as 3.8 mA. If the Series 3000 device output is trimmed
correctly, it will send a signal appropriately compensated to ensure that the receiving device actually
indicates a 4 mA signal.
You must trim the outputs at both the 4 mA and 20 mA points to ensure appropriate compensation
across the entire range of outputs.
To perform a milliamp output trim:
1. Connect a digital multimeter (DMM) or other reference device to the primary or secondary
milliamp wiring terminals. Ensure that the reference device is connected in series. Table 16-1
lists the terminals to which the reference device should be connected.
2. Ensure that the reference device is set to read milliamps.

140 Micro Motion® Series 3000 MVD Transmitters and Controllers


Startup Procedures

Configuring Digital Communications


Table 16-1 Milliamp output wiring terminals

Terminal number
Model 3300 or Model 3500 Model 3300 or
Terminal with screw-type or solder-tail Model 3500 with Model 3350 or
designation Polarity terminals I/O cables Model 3700
4–20 mA primary + c2 1 2
– a2 2 1
4–20 mA secondary + c4 14 4
– a4 15 3
Terminal block location Farthest right block on back panel Attached to DIN rail Gray terminal block

Configuring Custody Transfer


3. From the Maintenance menu, select Calibration (see Figure 16-1).
4. Select mA Output Trim.
5. Select Milliamp Output 1 or Milliamp Output 2.
6. Select the output level to be trimmed:
• To trim at 4 mA, select Trim 4.0 mA
• To trim at 20 mA, select Trim 20.0 mA
7. Press CHG, enter the amount of current indicated by the reference device, then press SAVE.
8. Compare the output level that is indicated by the reference device to the output level that
appears in the display.
• If the output level that appears in the display matches the output level that is indicated by
the reference device, press YES.
• If the output level that appears in the display does not match the output level that is
indicated by the reference device, press NO, then repeat Steps 7 and 8.

Configuring Tickets
Note: Any trimming performed on the output should not exceed  200 microamps. If more trimming is
required, contact Micro Motion customer support.
Note: If you are trimming the primary mA output, and you are performing a trim using a HART
connection to the Series 3000 device, the HART signal will affect the reading. Disconnect the HART
connection before reading the output, then reconnect and resume the trim after taking the reading.

Startup

Configuration and Use Manual 141


142 Micro Motion® Series 3000 MVD Transmitters and Controllers
Chapter 17

Operation Mode
Operation Mode

17.1 About this chapter


This chapter explains how to use the Series 3000 device in operation mode.
There are two different operation modes:
• The process monitor is the default operation mode unless the discrete batch application is

Operation Mode – Batch


present. Process monitor mode is described in Section 17.4.
• Batch mode, which is the default operation mode if the discrete batch application is installed.
Batch mode is described in Chapter 18.
Both modes will operate differently if the custody transfer application is installed and security is
enabled. See Chapter 19.
To determine what applications or special options have been installed, use the applications list in the
View menu (see Section 17.5.9).

17.2 Startup and display test


At startup, the Series 3000 device automatically tests its display. During display testing, the screen

Operation Mode – Custody Transfer


darkens for approximately five seconds. After the display test is completed:
1. The Micro Motion logo is displayed for two to three seconds.
2. An application list is displayed for two to three seconds.
3. The device enters operation mode:
• If the discrete batch application is not installed, the process monitor screen is displayed, as
shown in Figure 17-1.
• If the discrete batch application is installed, the batch process screen is displayed (see
Figure 18-1).
4. If there are any active alarms, the alarm category will be displayed in the alarm bar. To view,
acknowledge, or respond to the alarms, see Section 22.6.

17.3 Initial startup


For Series 3000 transmitters, a sensor zero may be performed at initial startup. Sensor zero establishes
Totalizers and Inventories

flowmeter response to zero flow and sets a baseline for flow measurement.
Once the sensor zero is set, it remains part of the transmitter nonvolatile memory, and will not be
affected by a power failure, brownout, or power cycle.
See Section 16.3 for instructions on performing a sensor zero.

Configuration and Use Manual 143


Operation Mode

CAUTION
Failure to perform a sensor zero calibration at initial startup could cause the
flowmeter to produce inaccurate signals.

To avoid inaccurate measurements, perform a sensor zero before putting the


flowmeter into operation.

17.4 Process monitor operation mode


The process monitor, shown in Figure 17-1, is the default operation mode unless the discrete batch
application is present.
• To scroll through the process monitor, press the left or right cursor control button. The number
beside each arrow on the top line indicates the screen that will be displayed if the left or right
cursor control button is pressed. If no display variables are configured for a particular screen,
that screen is skipped.
• If a total appears on the screen, you can press RESET to reset it to 0. Pressing RESET will
reset only the totals on the screen that is displayed.
• Press PRINT to print a ticket that includes values of process variables on the screen that is
displayed.
You can configure the process variables that will be displayed on each of the five screens of the
process monitor. To configure the process monitor, see Chapter 12.
If the discrete batch application is installed, you can monitor process variables by using the Process
Monitor option from the View menu (see Section 17.5).

Figure 17-1 Series 3000 display in process monitor mode

5 DEVICE 1 2
Mass Flow Rate
Backlit
display
2.33 Cursor control
buttons
g/s
Mass Total
485.88
g
PRINT RESET EXIT VIEW or EXIT
button

Security button
Function buttons

144 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode

17.5 Using the View menu


When you press VIEW at the operation screen, the View menu is displayed (see Figure 17-2).

Operation Mode
This menu varies according to the installed applications. Your menu may be different.
Note: See Chapter 19 for a discussion of the View menu if the custody transfer application is installed
and World Area is set to OIML.
Figure 17-3 shows the functions performed by the function buttons and cursor control buttons in the
View menu.

Figure 17-2 View menu

View menu

Operation Mode – Batch


Active alarm log Process Preset Batch inventory(1) Process totalizers
monitoring selections(1)

Preset 1 Preset inventory 1 Process


Preset 2 Preset inventory 2 • Mass total
Preset 3 Preset inventory 3 • Volume total
Preset 4 Preset inventory 4 • API ref vol total(3)
Preset 5 Preset inventory 5 • ED ref vol total(4)
Preset 6 Preset inventory 6 • ED net mass total(4)
• ED net vol total(4)
• Frequency input total

Operation Mode – Custody Transfer


Inventory
• Mass inventory
• Volume inventory
• API ref vol inventory(3)
Diagnostic monitor Density curves(2) LCD options Applications list • ED ref vol inventory(4)
• ED net mass inventory(4)
• ED net vol inventory(4)
• Freq input inventory

Tube frequency Density curve 1 Contrast


Left pickoff Density curve 2 LCD backlight
Right pickoff Density curve 3
Drive gain Density curve 4
Live zero Density curve 5
Density curve 6

(1) If batch application is installed and configured.


(2) If enhanced density application software is installed and configured, and density curves have not been assigned to batch presets.
(3) If petroleum measurement application is installed and configured.
(4) If enhanced density application software is installed and configured.
Totalizers and Inventories

Configuration and Use Manual 145


Operation Mode

Figure 17-3 Working with the View menu

EXIT
ALARMS Move cursor upward
VIEW MENU
Active Alarm Log
Process Monitoring
Preset Selections SELECT
Batch Inventory
Process Totalizers
Diagnostic Monitor
Density Curves
LCD Options
Applications List

SEL HELP EXIT Move cursor downward

SEL Select highlighted option


CHG Make a change to the HELP Show a help screen EXIT Return to operation screen
highlighted option RESET Reset total
SAVE Save a change
STOP Pause counting of all
totalizers except batch
START Resume counting of all
totalizers except batch
RESET Reset totalizer
PRINT Print a ticket

17.5.1 Active alarm log


The platform performs self-diagnostics during operation. If the platform detects certain events or
conditions, an alarm message appears in the highlight bar at the top of the screen and an item is added
to the active alarm log.
The active alarm log lists:
• All alarms that are active (the condition that caused the alarm is active)
• All alarms that have not been acknowledged (even if the condition causing the alarm is no
longer active)
The alarm will be listed in the active alarm log and displayed in the highlight bar until the alarm has
been acknowledged.
The active alarm log is organized in either of two ways:
• If accessed via the View menu, as shown in Figure 17-2, only alarm categories containing
active or unacknowledged alarms are listed. Alarm categories are listed in order of priority
(Electronics, Sensor, Process, Configuration). To view individual alarms, place the cursor on
an alarm category and press HELP.
• If accessed via the Maintenance menu, individual alarms are listed in numerical order by alarm
number (alarm numbers are documented in Section 22.7).
For information about acknowledging alarms or responding to alarm messages, see Section 22.6.

146 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode

17.5.2 Process monitoring


This selection displays the process monitor, as described in Section 17.4. The display is identical to

Operation Mode
the display shown in Figure 17-1.
If you enter the process monitor from the View menu, then press EXIT, you are returned to the View
menu.

17.5.3 Preset selections


The Preset Selections option allows you to specify which of the existing presets will be used to
control batching. Only presets that have been enabled are listed here.
The discrete batch application can be set up with as many as six different batch presets. Each preset
has its own target. A preset may also have a descriptive name, which will appear on the selection
menu.
For more information on batch presets and how to configure them, see Section 11.6.

Operation Mode – Batch


Note: If a density curve has been assigned to the selected preset, batch totals will be based on the
derived variable that was selected during configuration of the density application. See the enhanced
density manual.

17.5.4 Batch inventory


This option displays the current inventory totals for all enabled presets.
For more information on batch presets and how to configure them, see Section 11.6. For more
information on batch inventories and how to reset them, see Section 18.3.

Operation Mode – Custody Transfer


17.5.5 Process totalizers and inventories
The View menu allows you to view, start, stop, and reset process totalizers, and view process
inventories.
To view or manage process totalizers:
1. From the View menu, select Process Totalizers.
2. Select Process. Current values for the first four totalizers are displayed. Scroll down as
required to view additional totalizers.
3. To start or stop all totalizers, press the left function button (labeled START or STOP).
4. To reset a specific totalizer:
a. Highlight the totalizer to be reset.
b. Press the RESET button.
To view a process inventory:
1. From the View menu, select Process Totalizers.
Totalizers and Inventories

2. Select Inventory.
3. Scroll down the list as required to view the desired value.
Note: Inventories cannot be reset from the View menu. To reset an inventory, you must use the
Maintenance menu. See Section 20.5.

Configuration and Use Manual 147


Operation Mode

17.5.6 Diagnostic monitor


The Diagnostic Monitor shows real-time values for sensor flow tube frequency, left and right pickoffs,
drive gain, and live zero.
Drive gain, pickoff levels, and sensor flow tube frequency values are useful for troubleshooting fault
alarms. For information about troubleshooting fault alarms, see Chapter 22.
Live zero is useful for monitoring the flow rate when it drops below the mass low flow cutoff. To
configure the mass low flow cutoff, see Section 7.3.2.
Note: The diagnostic monitor is not the same as the Diagnostics menu. The Diagnostics menu,
accessed through the Maintenance option of the Management menu, allows you to read the values of
external inputs and simulate output levels for outputs. The Diagnostics menu and its use are described
in Chapter 16.

17.5.7 LCD options


The LCD Options allow you to adjust the contrast, or to enable screen backlighting.
1. Select LCD Options from the View menu.
2. Select Contrast to adjust the screen contrast.
3. Select LCD Backlight to turn screen backlighting on or off.

17.5.8 Density curves


The Density Curves menu item is available only if the enhanced density application is installed and
one or more density curves has been configured. This screen lists all density curves that have been
configured. The active density curve is highlighted.
• If no density curve has been assigned to a batch preset, you can use this menu to change the
active density curve. To do this, highlight the desired curve in the list and press SEL.
• If a density curve has been assigned to a batch preset, that curve is active and you cannot
change the active density curve from this menu.

17.5.9 Applications list


The Applications List shows the software version of the Series 3000 device and the core processor (if
applicable) and all applications that are installed. Refer to this screen for the software revision number
to report problems.

148 Micro Motion® Series 3000 MVD Transmitters and Controllers


Chapter 18

Operation Mode
Operation Mode – Batch

18.1 About this chapter


This chapter explains how to use the discrete batch control application and how to perform batch
AOC (automatic overshoot compensation).
Note: Before you can use the discrete batch application, it must be configured. For information on

Operation Mode – Batch


configuring the discrete batch application, see Chapter 11.
Note: For information on formatting and printing batch tickets, see Chapter 15.

18.2 About discrete batching


Discrete batching is used to start flow, then stop flow automatically when the target amount of process
fluid has flowed through the sensor. During a batch, flow may be stopped and resumed. A batch may
also be ended before the target is reached.
The normal batching sequence is as follows:
1. Select a batch preset (see Section 17.5.3). The batch preset determines the target, how end
warnings and overruns will be handled, and, for 2-stage batching only, the point at which the

Operation Mode – Custody Transfer


primary and secondary valves will be opened and the point at which the primary valve will be
closed.
2. Start the batch. The operator can start the batch manually, using the START button on the batch
process screen, or a discrete input or discrete event can be configured to start the batch (see
Section 11.7). Before a batch can be started, the previous batch must be ended and the totals
must be reset.
Note: Reset may be automatic (Reset on Start is enabled; see Section 11.5) or manual via the RESET
button or an assigned discrete input (see Section 11.7).
3. In normal operation, the flowmeter will stop the batch automatically when the configured
target is reached.
The operator can halt the batch manually, using the STOP or END buttons on the batch process
screen. The STOP and END functions can also be assigned to a discrete input or discrete event
(see Section 11.7).
• If the batch is stopped, the current batch totals are retained, and pressing the RESUME
Totalizers and Inventories

button will restart the batch from the current totals. The RESUME function can also be
assigned to a discrete input or discrete event (see Section 11.7).
• If the batch is ended, it cannot be restarted (with one exception: by increasing the batch
target to a value that is greater than the current batch total).
Table 18-1 describes batch events and how the batch function buttons operate under different batch
conditions.
For examples of batch processing, including the effects of STOP and RESUME, see Section 18.4.
For a discussion of batch control functions, see Section 11.7.

Configuration and Use Manual 149


Operation Mode – Batch

Table 18-1 Batch events

Event Description
Batch in progress • Batch is in progress.
• Batch in progress remains active until the batch completes or is ended. If the batch is
stopped, batch in progress remains active.
Primary valve open/close, • If control options are configured for Reset on Start, pressing START resets the batch
1-stage batch total to zero, starts the pump or opens the valve, and starts the batch.
• If control options are not configured for Reset on Start, pressing START starts the
pump or opens the valve to start the batch.
• The pump stops or the valve closes automatically when the target is reached.
Primary valve open/close, • If control options are configured for Reset on Start and the preset is configured so
2-stage batch Open Primary is 0% of target, or Quantity is set to 0, pressing START resets the
batch total to zero, opens the primary valve, and starts the batch.
• If control options are not configured for Reset on Start and the preset is configured so
Open Primary is 0% of target, or Quantity is set to 0, pressing START opens the
primary valve and starts the batch.
• If the preset is configured so Open Primary is a value other than 0% of target, or a
quantity other than 0, the valve opens when the batch total achieves the Open
Primary value.
• The primary valve closes when the batch total achieves the Close Primary value.
Secondary valve open/close, • If control options are configured for Reset on Start and the preset is configured so
2-stage batch Open Secondary is 0% of target, or Quantity is set to 0, pressing START resets the
batch total, opens the secondary valve, and starts the batch.
• If control options are not configured for Reset on Start and the preset is configured so
Open Secondary is 0% of target, or Quantity is set to 0, pressing START opens the
secondary valve and starts the batch.
• If the preset is configured so Open Secondary is a value other than 0% of target, or a
quantity other than 0, the secondary valve opens when the batch total achieves the
Open Secondary value.
• The secondary valve closes when the target is achieved.
End warning • If End Warning was enabled during configuration, the batch controller produces an
alarm when the batch total achieves the programmed end warning value.
• The end warning remains active until batch completion.
Overrun • If Overrun was enabled during configuration, the batch controller produces an alarm
when the batch total exceeds the target by the programmed amount or percent of
target.
• Overrun remains active until flow stops.
Batch pump • The system pump is operating.
• The pump remains on while the primary or secondary valve is open.

18.3 Batch process screen


Figure 18-1 shows the Series 3000 display in batch operation mode, ready to start a batch.
The display shows that there have been zero kilograms of actual delivery in this batch. When flow
starts, the display is continuously updated to show the actual amount that has been delivered.
The display can be set up to show either the amount that has been delivered (Count Up) or the amount
remaining to be delivered (Count Down). To configure Count Up or Count Down, see Section 11.5.

150 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode – Batch

Figure 18-1 Series 3000 display in batch mode

Operation Mode
DEVICE 1
Preset 1

Backlit
Actual
Cursor control
display
0.0 buttons

Target kg
12.3
START HELP VIEW

Operation Mode – Batch


Editing
Function buttons cursor

Security
button

Note: If the petroleum measurement application or the enhanced density application is installed
and the batch controller is measuring standard volume, net volume, or net mass, actual and
target values indicate net totals rather than gross totals.

Operation Mode – Custody Transfer


18.3.1 Function buttons
In Figure 18-2, the display shows that the batch target is 12.3 kg.
• When you press START, the discrete outputs assigned to the pump and valve are activated, and
flow starts.
• When the target amount has passed through the flowmeter, the discrete outputs assigned to the
pump and valve are deactivated, and flow stops.
The labels on the three function buttons are changed during the batch run to show the actions you can
perform at each point.
To start the batch, press the button on the left, labeled START. Figure 18-2 shows what happens.

Totalizers and Inventories

Configuration and Use Manual 151


Operation Mode – Batch

Figure 18-2 Using batch function buttons

DEVICE 1 DEVICE 1
Preset 1 Preset 1
Actual Actual
0.0 4.4
kg
kg
Target Target
12.3 12.3
START HELP VIEW STOP HELP VIEW

Display shows actual quantity,


Functions of these updated continuously
buttons change

Figure 18-3 indicates the actions that are performed by the function buttons during batch operation.

Figure 18-3 Function buttons in batch mode

DEVICE 1
Preset 1
Actual
0.0
kg
Target
12.3
START HELP VIEW

VIEW Access the View menu


ACK Acknowledge an alarm

HELP Show a help screen


RESUME Resume a batch that has been stopped
PRINT Print a ticket

START Start the batch


STOP • Stop the batch before the target is achieved
• Batch can be resumed
END • End the batch before the target is achieved
• Batch cannot be resumed
RESET Reset the batch total to zero

152 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode – Batch

18.3.2 Cursor control buttons


The Lockout Target parameter can be set to allow the operator to change the target directly from the

Operation Mode
batch operation screen when the batch is not running (Lockout Target set to No). To enable target
adjustment, see Section 11.5.
In Figure 18-4, the line beneath the farthest right digit of the target is the editing cursor. If Lockout
Target is set to No, the cursor appears on the screen whenever the batch is not running. Whenever the
cursor appears on the screen, you can use the cursor control buttons to change the target.
Figure 18-4 shows how the cursor control buttons work when the editing cursor is displayed.

Figure 18-4 Adjusting the batch target

Moves cursor left

Increases value at cursor

Operation Mode – Batch


DEVICE 1
Preset 1
Actual Moves cursor right

0.0
kg
Target
12.3
START HELP VIEW Decreases value at cursor

Cursor

Operation Mode – Custody Transfer


Note: If the petroleum measurement application or the enhanced density application is
installed and the batch controller is measuring standard volume, net volume, or net mass,
the actual and target values indicate net totals rather than gross totals.

18.4 Batch processing sequences


The following sequences (Figures 18-5 and 18-6) show the opening and closing of the primary and
secondary valves, under normal processing and when STOP / RESUME is performed at different
points during the batch.
Note: Because the pump is on whenever a valve is open, it is not shown in these sequences.
For a description of two specific sequences, see the examples following the figures.
Totalizers and Inventories

Configuration and Use Manual 153


Operation Mode – Batch

Figure 18-5 Batch processing sequences: 2-stage batching, Open Primary at 0%

Normal operation

0% m% n% 100%

Valve behavior with STOP/RESUME at x%

x% before secondary open

0% x% m% m+x% n% 100%

x% after secondary open, when


m+x% < n%

0% m% x% m+x% n% 100%

x% after secondary open, when


m+x% > n%

0% m% x% n% m+x% 100%

x% after primary close

0% m% n% x% m+x% 100%

Configured values Legend


• Open Primary: 0% • Primary valve
• Open Secondary: m% • Secondary valve
• Close Primary: n% • Flow

154 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode – Batch

Figure 18-6 Batch processing sequences: 2-stage batching, Open Secondary at 0%

Operation Mode
Normal operation

0% m% n% 100%

Valve behavior with STOP/RESUME at x%

x% before primary open

0% x% m% m+x% n% 100%

Operation Mode – Batch


x% after primary open, when
m+x% < n%

0% m% x% m+x% n% 100%

Operation Mode – Custody Transfer


x% after primary open, when
m+x% > n%

0% m% x% n% m+x% 100%

x% after primary close

0% m% n% x% m+x% 100%

Configured values Legend


Totalizers and Inventories

• Open Primary: m% • Primary valve


• Open Secondary: 0% • Secondary valve
• Close Primary: n% • Flow

Configuration and Use Manual 155


Operation Mode – Batch

Example 1 Batch control configuration:


• No. of Stages = 2
• Configure Presets By = % of Target
Preset configuration:
• Target = 100 liters
• Open Primary = 0%
• m (Open Secondary) = 30%
• n (Close Primary) = 70%
Operator actions:
• None (see the first sequence in Figure 18-5)

As a result:
• At the beginning of the batch run, the primary valve opens and flow
starts.
• When the flowmeter has measured 30 liters, the secondary valve
opens.
• When the flowmeter has measured 70 liters, the primary valve
closes.
• When the flowmeter has measured 100 liters, the secondary valve
closes.

Example 2 Batch control configuration:


• No. of Stages = 2
• Configure Presets By = % of Target
Preset configuration:
• Target = 100 liters
• Open Primary = 0%
• m (Open Secondary) = 30%
• n (Close Primary) = 70%
Operator actions:
• STOP/RESUME occurred after 20 liters had been measured (20%
of target; x = 20%) (see the second sequence in Figure 18-5)

As a result:
• At the beginning of the batch run, the primary valve opens and flow
starts.
• When the flowmeter has measured 50 liters (30 + 20, or m + x), the
secondary valve opens.
• When the flowmeter has measured 70 liters, the primary valve
closes.
• When the flowmeter has measured 100 liters, the secondary valve
closes.

156 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode – Batch

18.5 Special cases in batch processing


This section describes two common situations in batch processing that may require special attention

Operation Mode
from the operator.

18.5.1 Cleaning/purging the tubes


In normal processing, the batch totalizer increments whenever flow is detected. To run fluid through
the tubes without incrementing the batch totalizer:
1. Ensure that the Inhibit Totalizer batch control function has been assigned to a discrete input, as
described in Section 11.7.
2. Activate the discrete input or discrete event.
3. Run fluid through the tubes as desired.
4. When you are ready to resume totalizing, deactivate the discrete input.

Operation Mode – Batch


18.5.2 Ending a batch while flow is present
In general, to end a batch:
• Automatically, the target must be reached and flow must be stopped.
• Manually, the batch must be stopped (paused) and flow must be stopped.
To end a batch while flow is present:
1. Ensure that the Inhibit Flow batch control function has been assigned to a discrete input, as
described in Section 11.7.
2. When the batch total reaches the target, activate the discrete input so that the batch can end
normally.

Operation Mode – Custody Transfer


18.6 Batch AOC calibration
Batch AOC (Automatic Overshoot Compensation) keeps the actual quantity delivered as close as
possible to the batch target, by minimizing the amount of overshoot.
If batch AOC is enabled (see Section 11.5), batch AOC calibration is required to provide data for the
compensation process. Thereafter, batch AOC calibration is recommended:
• Whenever consistent overshooting or undershooting of the target occurs
• If equipment (valve or pump) is changed
Note: If batch AOC is not enabled, you cannot perform batch AOC calibration.
To perform batch AOC calibration:
1. From the Maintenance menu, select Calibration (see Figure 4-2).
2. Select Batch AOC.
Totalizers and Inventories

3. Select Start Calibration.


4. Press EXIT repeatedly to return to the operation screen.
5. Run 2 to 10 batches.

Configuration and Use Manual 157


Operation Mode – Batch

6. When overshoot has been adequately minimized:


a. From the Maintenance menu, select Calibration.
b. Select Batch AOC.
7. Select Save Calibration.
8. Press SEL.

158 Micro Motion® Series 3000 MVD Transmitters and Controllers


Chapter 19

Operation Mode
Operation Mode – Custody Transfer

19.1 About this chapter


This chapter explains how to use and manage the custody transfer application. The following topics
are discussed:
• Identifying a security breach – see Section 19.2

Operation Mode – Batch


• General differences between secured versus unsecured states – see Section 19.3
• Using custody batch (NTEP) – see Section 19.4
• Using custody transfer (OIML) and custody transfer (OIML/batch) – see Section 19.5
• Clearing a security breach – see Section 19.6
• Reconfiguring the Series 3000 device – see Section 19.7
• Audit trail – see Section 19.8
The custody transfer application must be configured for the system that will be used. See Chapter 14
for information on configuring the custody transfer application.

19.2 Identifying a security breach

Operation Mode – Custody Transfer


It is useful to distinguish between data security and legal security. Data security is present if the
custody transfer switch is in the ON position and there is no “Security Breach” banner on the
Series 3000 display. However, legal security requires data security plus an intact weights and
measures seal.
For custody transfer use, legal security is required. Therefore, a security breach is present if either of
the following is true:
• Visual inspection shows that the weights and measures seal is broken or missing.
• The Series 3000 device has detected a security breach and posted the “Security Breach”
banner on the display.
Note: The “Security breach” and “Not a legal receipt” banners will also be printed on batch (NTEP)
tickets or batch (OIML) tickets, but not on transfer (OIML) tickets.
If a security breach is present, security cannot be guaranteed, and Series 3000 data cannot be used to
meet weights and measures requirements. To clear a security breach, see Section 19.6.
Totalizers and Inventories

19.3 Secured versus unsecured


In general, when the Series 3000 device is secured, the operator can run a batch and view process
data, but cannot change device configuration. When the device is unsecured, configuration changes
are permitted but other device behavior changes to indicate the unsecured status.
Table 19-1 provides a detailed list of changes to specific features or functions when the custody
transfer application is installed and the Series 3000 device is either secured or unsecured.

Configuration and Use Manual 159


Operation Mode – Custody Transfer

Table 19-1 Series 3000 behavior and available functions

Custody transfer (OIML) and


Custody transfer (NTEP) custody transfer (OIML/batch)
Function Secured Unsecured Secured Unsecured
Batch processing
Batch reset Y Y Y Y
Batch start, stop, resume Y Y Y Y
Batch BOL number N Y N Y
changed manually
Different batch preset Y Y Y Y
selected
Transfer BOL number changed N/A N/A N Y
manually
Time of day Can be changed by Y Can be changed by Y
one hour in either one hour in either
direction. Cannot be direction. Cannot be
changed in the changed in the
same direction same direction
twice consecutively. twice consecutively.
External pressure and
temperature data
Updated via polling Y Y Y Y
Updated by Modbus or N Y N Y
HART host
Calibration
Zero N Y N Y
Density N Y N Y
Temperature N Y N Y
Meter verification
Original version N Y N Y
Smart Meter Verification
• Outputs set to Continue Y Y Y Y
Measuring
• Outputs set to Fault Y Y Y Y
• Outputs set to Hold Last N Y N Y
Value

160 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode – Custody Transfer

Table 19-1 Series 3000 behavior and available functions continued

Operation Mode
Custody transfer (OIML) and
Custody transfer (NTEP) custody transfer (OIML/batch)
Function Secured Unsecured Secured Unsecured
Outputs
mA output behavior Normal If reporting flow Normal Perform configured
rate, show zero flow fault action
Otherwise, normal
mA output trim N Y N Y
mA output loop test N Y N Y
Frequency output behavior Normal Inactive (produces Normal Perform configured
no pulses) even fault action
under fault
conditions

Operation Mode – Batch


Frequency output loop test N N N Y
Discrete output behavior Normal Normal Normal Perform configured
fault action
Discrete output loop test N Y N Y
Service port connections N Y N Y
If device is secured If device is secured
while service port while service port
connection is active, connection is active,
terminals are reset terminals are reset
to RS-485 mode to RS-485 mode
and connection is and connection is
broken. broken.

Operation Mode – Custody Transfer


Totalizers and Inventories

Configuration and Use Manual 161


Operation Mode – Custody Transfer

Table 19-1 Series 3000 behavior and available functions continued

Custody transfer (OIML) and


Custody transfer (NTEP) custody transfer (OIML/batch)
Function Secured Unsecured Secured Unsecured
Process variables
All flow rates Reported normally Reported as zero Reported normally Reported normally
Density and temperature Reported normally Reported normally Reported normally Reported normally
Process totalizers Increment normally Stopped Replaced by Replaced by
Cannot be stopped If any one is reset: transfer totalizers transfer totalizers
Cannot be reset • All others are Transfer totalizers Transfer totalizers
unless flowrate is reset Increment normally stopped
zero. If any one is automatically
reset: • A test of the
• All others are display is
reset performed
automatically automatically
• A test of the
display is
performed
automatically
Process inventories Increment normally Stopped Increment normally Stopped
Cannot be stopped Cannot be reset Cannot be stopped Cannot be reset
Cannot be reset Cannot be reset
Transfer totalizers N/A N/A Rollover indicator: Rollover indicator
• Cannot be cleared can be cleared
manually
• Cleared
automatically
upon starting new
transfer
Transfer inventories N/A N/A Rollover indicator Rollover indicator
cannot be cleared can be cleared
Simulation mode N Y N Y
Alarm menu Normal Normal Alarm log password Alarm log password
required (if enabled) required (if enabled)

162 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode – Custody Transfer

19.4 Custody transfer (NTEP)


This section provides information on the BOL number, the custody transfer transaction, tickets and

Operation Mode
ticket printing, and general use of the Series 3000 device when World Area is set to NTEP.

19.4.1 BOL number


In custody transfer (NTEP) applications, there is one bill of lading (BOL) number. The BOL number
is used to identify both the custody transfer transaction and the batch. The default BOL start number
is 0, and the BOL number is incremented automatically when the discrete batch is reset. To change or
reset the BOL start number manually, see Section 15.5.1.
Note: The BOL number rolls over to 0 after 99,999,999 batches.
You cannot change the BOL start number while the device is secured. In most cases, the BOL start
number is set during initial configuration and is not changed thereafter. To determine the current BOL
number, check the most recent batch (NTEP) ticket.

Operation Mode – Batch


19.4.2 Executing a custody transfer (NTEP) transaction
Custody transfer (NTEP) is used with the discrete batch application. To execute a custody transfer
(NTEP) transaction:
1. Reset the batch. Because Reset on Start is disabled, you must reset the batch manually. At this
point, the batch BOL number is incremented, the batch total is reset, and the custody transfer
transaction begins.
2. Run the batch. The discrete batch application will automatically stop flow when the target is
reached, but you may increase the target and resume flow if desired.
3. When the desired quantity has been delivered, as measured by the discrete batch application,

Operation Mode – Custody Transfer


stop flow and end the batch.
4. End the transaction by printing a batch (NTEP) ticket. The custody transfer transaction ends
when the first batch (NTEP) ticket is printed. You can print the ticket manually or
automatically, at the end of a batch. You cannot print the ticket while the batch is stopped.
See the following section for information on ticket printing.

19.4.3 Batch (NTEP) tickets and ticket printing


The batch (NTEP) ticket is very similar to the batch ticket but contains some additional data. The
batch (NTEP) ticket serves as the legal receipt. To print a batch (NTEP) ticket, see Section 15.5.2 for
instructions for both automatic and manual printing, and for printing additional tickets.
Note the following:
• A batch (NTEP) ticket cannot be printed until flow stops.
• If a batch (NTEP) ticket is printed, and the batch target is then increased and the batch is
Totalizers and Inventories

resumed, the custody transfer data will not change even though the batch data changes. All
additional batch (NTEP) tickets printed during this batch will contain the original custody
transfer data and the “Duplicate receipt” banner.
• For printer type Epson TMU295, an out-of-paper alarm can be generated, depending on the
setting of the Disable Paper Check parameter (see Table 13-3). No other forms of print failure
are detected.

Configuration and Use Manual 163


Operation Mode – Custody Transfer

19.4.4 General use of Series 3000 device

This section describes the effect of custody transfer (NTEP) on specific Series 3000 device functions.
Information in this section supplements the information in Table 19-1.

19.4.5 Inventories
Process inventory values may become too large to display on screen. If this happens, the decimal
point is shifted to the right, and eventually the screen display may be converted to scientific notation.
Note: Precision may be lost only in the displayed value. No precision is lost in the value stored in the
device.
Note: For definitions of process totalizers, process inventories, transfer totalizers, and transfer
inventories, see Section 20.2.

Audit trail
The audit trail function (see Section 19.8) is active, whether the device is currently secured or
unsecured.

19.5 Custody transfer (OIML) and custody transfer (OIML/batch)


This section provides information on BOL numbers, the custody transfer transaction, tickets and
ticket printing, the transfer log, and general use of the Series 3000 device when World Area is set to
OIML.

19.5.1 BOL numbers


For custody transfer (OIML), the transfer BOL number is used to identify the custody transfer
transaction. The default transfer BOL start number is 0, and the transfer BOL number is incremented
automatically when the custody transfer is completed. The BOL start number is never reset
automatically. To change or reset the transfer BOL start number manually, see Section 15.6.1.
Note: If the transfer BOL start number is changed or reset, the transfer log is reset and all transfer
data is lost. See Section 19.5.5.
For custody transfer (OIML/batch), the batch BOL number is used to identify the custody transfer
transaction. The default batch BOL start number is 0, and the batch BOL number is incremented
automatically when the batch is reset. The batch BOL start number is never reset automatically. To
change or reset the batch BOL start number manually, see Section 15.6.1.
You cannot change either BOL start number while the device is secured. In most cases, the BOL start
numbers are set during initial configuration and are not changed thereafter. To determine the current
BOL number, check the most recent transfer (OIML) or batch (OIML) ticket. For transfer (OIML),
you can also check the transfer log (see Section 19.5.5).

19.5.2 Executing a custody transfer (OIML) transaction


To execute a custody transfer (OIML) transaction:
1. Start flow.
2. Stop flow when the desired quantity has been delivered.

164 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode – Custody Transfer

3. End the transaction, either by printing a transfer (OIML) ticket or by using the transfer reset
function.

Operation Mode
• To end a transaction via ticket printing, print a transfer (OIML) ticket that contains the
transfer total (see Section 19.5.4).
• To end a transaction via the transfer reset function, perform one of the following:
- Press the RESET-T button.
- Activate a discrete input that is configured for transfer completion (see Section 14.5,
Step 6).
Note: During the transfer reset function, the Series 3000 display is temporarily blank.
When the transfer is completed, transfer data is written to the transfer log, the transfer BOL
number is incremented by 1, all totalizers except the batch totalizer are reset automatically, and
the next custody transfer transaction begins immediately.

Operation Mode – Batch


Note: Inventories are not reset automatically when a transfer is completed.
Note the following:
• Tickets are optional. If you do not print a ticket, the transfer log is used for legal compliance,
and the transfer reset function is used to end the transaction and begin a new one.
• If flow is present:
- You cannot end the transaction.
- The transfer reset function is disabled.
- You may or may not be able to print a ticket. If you can, ticket contents will include the
flow rate and a “Not Complete” banner. See Section 19.5.4.
• A custody transfer (OIML) transaction can be executed and completed whether the device is

Operation Mode – Custody Transfer


secured or unsecured.

19.5.3 Executing a custody transfer (OIML/batch) transaction


To execute a custody transfer (OIML/batch) transaction:
1. Reset the batch. Because Reset on Start is disabled, you must reset the batch manually. At this
point, the batch BOL number is incremented, the batch total is reset, and the custody transfer
transaction begins.
2. Run the batch. The discrete batch application will automatically stop flow when the target is
reached, but you may increase the target and resume flow if desired.
3. When the desired quantity has been delivered and flow is stopped, end the batch.
4. End the transaction by printing a batch (OIML) ticket (see Section 19.5.4).
Note the following:
• Ending a batch does not automatically end the transaction. The transaction ends when the first
Totalizers and Inventories

batch (OIML) ticket is printed or when the batch is reset.


• If flow is present, you cannot end the transaction.

Configuration and Use Manual 165


Operation Mode – Custody Transfer

19.5.4 Transfer (OIML) and batch (OIML) tickets and ticket printing
Printing methods, conditions, and ticket contents for transfer (OIML) and batch (OIML) tickets are
described in Table 19-2.

Table 19-2 Transfer (OIML) and batch (OIML) ticket printing methods, conditions, and contents

Transfer (OIML) tickets Batch (OIML) tickets


Printing method • Manual, from PRINT button or discrete input • Manual, from PRINT button or discrete input
• See Section 15.6.2 • Automatic, via Auto Print parameter or
discrete event
• See Section 15.7.2
Approved process Marked with asterisks Not marked with asterisks
variables
Printing when flow is May or may not be permitted, depending on Not permitted
present Transfer Print Conditions parameter (see
Table 15-7)
Security breach No security breach banner Security breach banner printed on ticket
Alarm banner may or may not be included,
depending on Alarms Occurred parameter
(see Table 15-6)
Print failure See the section entitled Print failure See the section entitled Print failure
Print job status See the section entitled Print job status See the section entitled Print job status

Print failure
If a print failure occurs:
• For printer type FDW and transfer (OIML) tickets, the following warning message is
displayed for five seconds after the first failure:
Ticket Print Failure
Printer off-line and/or out of paper
If ticket printing fails a second time, the transfer is automatically completed and the following
warning message is displayed:
Ticket Print Failure
Manually record the transfer data from the Transfer Log
The display then shows the transfer log entry for the just completed transfer.
• For printer type FDW and batch (OIML) tickets, the following warning message is displayed
for five seconds after the first failure:
Ticket Print Failure
Printer off-line and/or out of paper
If the second print attempt succeeds, the ticket will include the “Duplicate receipt” banner,
with other data (e.g., batch totals and timestamp) based on the first print attempt.
If ticket printing fails a second time, the failure message is repeated, the batch total is reset,
and the batch BOL is incremented.
• For printer type Epson TMU295, when the printer is connected through an RS-485 converter,
the out-of-paper condition is handled via the warning message described above. Other types of
print failure cannot be detected.
• For other printer types, two-way communication is not supported. No forms of print failure are
detected.

166 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode – Custody Transfer

Print job status


For some printer types, a discrete output can be configured to indicate that the ticket could not be

Operation Mode
printed (see Section 8.3.2), for one of these two reasons:
• The last ticket print request failed.
• The flow rate is not zero.
If either of these situations occurs, the discrete output is activated.

19.5.5 Transfer log


Note: The transfer log is used only for transfer (OIML) transactions. The transfer log does not
contain entries for batch (NTEP) or batch (OIML) transactions.
Whenever a transfer is completed, transfer data is added to the transfer log. The entry may contain the
transfer totals, or the transfer totals and inventories, and the transfer variable may be marked with

Operation Mode – Batch


asterisks, depending on configuration (see Section 14.5). An example transfer log entry is shown in
Figure 19-1.
If a ticket is printed but the transfer is not completed, no data is added to the transfer log.
You may view data from the transfer log for the 20 most recent transfers. To do this:
1. Select Transfer Log from the View menu.
2. Use the Select BOL to View option to specify the transfer you want to view. Log data for the
selected transfer is displayed automatically.

Figure 19-1 Example transfer log entry

Operation Mode – Custody Transfer


Transfer Log

Transfer Not Printed


M. RESET
5-MAR-2007 19:19:02
Transfer (BOL):
1 Complete
Mass Transfer
* 100.000 kg *
Volume Transfer
10000.000 l

EXIT

Note: If the Transfer Start (BOL) parameter is changed, the transfer log is reset and all transfer data
is lost.
Totalizers and Inventories

Note: It is not possible to print the transfer log or retrieve it via digital communications.

Configuration and Use Manual 167


Operation Mode – Custody Transfer

19.5.6 General use of Series 3000 device


This section describes the effect of custody transfer (OIML) and custody transfer (OIML/batch) on
specific Series 3000 device functions. Information in this section supplements the information in
Table 19-1.

Process monitor
Depending on configuration, the transfer variable may be marked with asterisks on the process
monitor (see Section 14.5, Step 5).

Alarm log password


If the alarm log password has been enabled (see Section 14.5, Step 7), operators will be prompted for
the alarm log password when they attempt to access the active alarm log, the alarm history, or the
event log.

View menu
The View menu changes as follows:
• Transfer Totalizer replaces Process Totalizers.
• Transfer Log is added.
See Figure 19-2.

Figure 19-2 View menu – Custody transfer (OIML) and custody transfer (OIML/batch)

View

Active alarm Preset Transfer Diagnostic LCD


log selections(1) totalizer(2) monitor options

Process Batch Transfer Density Applications


monitoring inventory(1) log curves(3) list

(1) Displayed only if discrete batch application is installed.


(2) Buttons on Transfer Totalizer screen depend on configured Protocol.
(3) Displayed only if enhanced density application is installed.

168 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode – Custody Transfer

If you select Transfer Totalizer:


• You can view current transfer, inventory, or transfer and inventory values for the current

Operation Mode
transfer.
• If Protocol is set to Printer, a PRINT button is displayed when the print function is available
(i.e., if Transfer Print Conditions is set to With Flow, or if Transfer Print Conditions is set to
No Flow and there is no flow through the sensor). You can print current transfer, inventory, or
transfer and inventory values for the current transfer. If you print a ticket that contains a
transfer value, under conditions of zero flow, the current custody transfer transaction is
completed and a new one is started (see Section 19.5.3).
• If Protocol is not set to Printer, the RESET-T button is displayed. This button can be used to
complete the current custody transfer transaction and start a new one (see Section 19.5.3).
To view data for a different transfer:
1. Select Transfer Log from the View menu.

Operation Mode – Batch


2. Use the Select BOL to View option to specify the transfer you want to view. You can view
data for the 20 most recent transfers. Log data for the selected transfer is displayed
automatically.

Totalizers and inventories


Note: For definitions of process totalizers, process inventories, transfer totalizers, and transfer
inventories, see Section 20.2.
Whether the Series 3000 device is secured or unsecured:
• The process totalizers are not available. They are replaced by the transfer totalizers.
• Process inventories cannot be reset.
The maximum value for transfer totalizers and inventories is 999999999. They are not displayed in

Operation Mode – Custody Transfer


scientific notation. If the maximum value is reached, they roll over to 0 and the character R (rollover
indicator) is added to the data line on transfer screens. The R may or may not be displayed on the
process monitor or printed on process monitor tickets, depending on approval of the process monitor:
• If the process monitor is approved (see Section 14.5), the R is displayed on the process
monitor and printed on process monitor tickets.
• If the process monitor is not approved, the R is not displayed on the process monitor and not
printed on process monitor tickets.
The R is cleared automatically from transfer totalizer values when a new custody transfer transaction
is started. The R is not cleared automatically from transfer inventory values. To clear the R from
transfer inventory values:
1. Select Transfer Totalizer from the View menu.
2. Select Inventory.
3. Select the inventory whose display indicator you want to clear.
Totalizers and Inventories

4. Press the CLEAR button (see Figure 4-6).


Note: This action clears only the rollover indicator, and does not affect the transfer inventory value.
To clear the R, the Series 3000 device must be unsecured.

Audit trail
The audit trail function (see Section 19.8) is active, whether the Series 3000 device is currently
secured or unsecured.

Configuration and Use Manual 169


Operation Mode – Custody Transfer

19.6 Clearing a security breach


The method used to clear a security breach depends on the cause of the breach. See Table 19-3.

Table 19-3 Security breach causes and clearing methods

Cause Clearing method


Security switch set to OFF Set security switch to ON.
Core processor replaced, or disconnected and reconnected • Set security switch to OFF and back to ON.
• If A009 and A026 alarms are present on Model 3300
or Model 3500 panel-mount devices, see
Section 22.9.

Note: Clearing the security breach on the Series 3000 device does not establish legal security (see
Section 19.2). To establish legal security, an authorized installation of the weights and measures seal
must be performed (see Section 14.7).

19.7 Reconfiguring the Series 3000 device


If you need to reconfigure the Series 3000 device:
1. Break the weights and measures seal.
2. Set the security switch to OFF (see Section 14.6).
3. Perform required configuration changes.
4. Set the security switch to ON (see Section 14.6).
5. If desired, acknowledge the security breach alarm (see Section 22.6). This step is not required;
the Series 3000 device will operate normally with an unacknowledged alarm.
6. Perform an authorized installation of the weights and measures seal (see Section 14.7).

19.8 Audit trail


The audit trail feature is used to track any changes made to Series 3000 parameters while the device is
unsecured.
The audit trail is organized into events. The Series 3000 device assigns a number to each event, and
stores the events in numerical order. An event includes all parameter changes made between the time
secure mode is exited and the time secure mode is reentered. For example:
• Secure mode is exited, no parameter changes are made, and secure mode is entered – no event
is logged in the audit trail.
• Secure mode is exited, one parameter change is made, and secure mode is entered – one event
is logged in the audit trail.
• Secure mode is exited, several parameter changes are made on one day, and several more are
made on the following day, then secure mode is entered – one event is logged in the audit trail.
The audit trail is accessed from the Maintenance menu. See Figure 19-3.

170 Micro Motion® Series 3000 MVD Transmitters and Controllers


Operation Mode – Custody Transfer

Figure 19-3 Audit trail menu

Operation Mode
Maintenance

Audit trail

Current event number


View event
Date search

Operation Mode – Batch


19.8.1 Using the audit trail
The Current Event Number item on the Audit Trail menu displays the event number of the most
recent event.
The View Event item is used to locate the event to be viewed.
To locate an event for viewing, use one of the following methods:
• Manual
a. Highlight View Event.
b. Press CHG.
c. Use the cursor buttons to move to the event number.
d. Press SAVE.

Operation Mode – Custody Transfer


e. Press EXIT.
• Date search
a. Highlight Date Search.
b. Press SEL.
c. Set Day, Month, and Year to the date on which you want to start your search.
d. Press SAVE.
e. Press EXIT.
To view an event:
1. Use View Event as required to locate the event.
2. Press VIEW.
3. If more than one event is listed, scroll through the list and highlight the event you want to view.
4. Press SEL.
Totalizers and Inventories

5. Scroll through the list of parameter changes, using the cursor buttons or the PGDN and PGUP
buttons.

Configuration and Use Manual 171


172 Micro Motion® Series 3000 MVD Transmitters and Controllers
Chapter 20

Operation Mode
Using Totalizers and Inventories

20.1 About this chapter


This chapter explains how to monitor, start, stop, and reset totalizers and inventories.
Note: Totalizers and inventories operate differently if the custody transfer application is installed. See
Chapter 19 for more information.

Operation Mode – Batch


20.2 Overview
There are several totalizer types:
• Process totalizers track the total quantity of a process variable, and can be viewed, stopped,
started, and reset during normal use (i.e., from the process monitor or the View menu). Process
totalizers include:
- Mass total
- Volume total
- API reference volume total
- ED (enhanced density) reference volume total

Operation Mode – Custody Transfer


- ED net mass total
- ED net volume total
- Frequency input total
• Process inventories track the total quantity of a process variable. They can be viewed from the
process monitor or from the View or the Maintenance menu, but can be reset only from the
Maintenance menu. They are typically used to track the total quantity of a process variable
across multiple resets of the process totalizer. Process inventories include:
- Mass inventory
- Volume inventory
- API reference volume inventory
- ED reference volume inventory
- ED net mass inventory
Totalizers and Inventories

- ED net volume inventory


- Frequency input inventory
• Batch inventories track the total quantity of a process variable across batches. There is one
batch inventory for each batch preset. Batch inventories are available only if the discrete batch
application is installed and configured. The View menu allows you to view batch inventory
values for only the batch presets that are enabled. The Maintenance menu allows you to view
and reset batch inventory values for all six batch presets, whether or not they are defined or
enabled.

Configuration and Use Manual 173


Using Totalizers and Inventories

In addition, if the custody transfer application is installed and World Area is set to OIML, the process
totalizers and inventories are replaced by the following:
• Transfer totalizers – track the total quantity of the transfer variable measured by a single
custody transfer transaction. They are automatically reset when the custody transfer
transaction ends.
• Transfer inventories – track the total quantity of the transfer variable measured across custody
transfer transactions. They cannot be reset.
For more information on transfer totalizers and transfer inventories, see Section 19.5.6.
Note: The transmitter can store totalizer and inventory values up to 2 64. Values larger than this cause
the internal totalizer to go into overflow.

20.3 Totalizer management


The method used to manage totalizers depends on the totalizer type and the function to be performed.
See Table 20-1.
Totalizers appear on the process monitor only if the process monitor has been configured to display
them (see Section 12.3). The user-specified label will be used (see Section 12.4). For information on
using the process monitor to reset totalizers, see Section 17.4.
Refer to Chapter 4 for information on accessing the View menu and the Maintenance menu.

Table 20-1 Totalizer management

Totalizer type Process monitor View menu Maintenance menu


Process totalizer View current value, reset(1) View current value, start, Not accessible
stop, reset(1)
Process inventory View current value View current value View current value, reset(1)
Batch inventory N/A View current value for View current value, reset
enabled batch presets for all six batch presets
(1) Reset is available only if enabled via the display. See Section 5.3.3.

174 Micro Motion® Series 3000 MVD Transmitters and Controllers


Using Totalizers and Inventories

Figure 20-1 View menu – Totalizer management

Operation Mode
View

Process totalizers Batch inventory(3)

Process Inventory • Preset 1


• Preset 2
• Preset 3
• Preset 4

Operation Mode – Batch


• Preset 5
• Mass total • Mass inventory • Preset 6
• Volume total • Volume inventory
• API ref vol total(1) • API ref vol inventory(1)
• ED ref vol total(2) • ED ref vol inventory(2)
• ED net mass total(2) • ED net mass inventory(2)
• ED net vol total(2) • ED net vol inventory(2)
• Frequency input total • Frequency input inventory

(1) Displayed only if the petroleum measurement application is installed.


(2) Displayed only if the enhanced density application is installed.
(3) Displayed only if the discrete batch application is installed. Only enabled presets are listed.

Operation Mode – Custody Transfer


Figure 20-2 Maintenance menu – Totalizer management

Maintenance

Batch inventory(1) Process inventory

• Preset 1 • Mass inventory


• Preset 2 • Volume inventory
• Preset 3 • API ref vol inventory(2)
• Preset 4 • ED ref vol inventory(3)
• Preset 5 • ED net mass inventory(3)
• Preset 6 • ED net vol inventory(3)
Totalizers and Inventories

• Freq input inventory

(1) Displayed only if the discrete batch application is installed.


(2) Displayed only if the petroleum measurement application is installed.
(3) Displayed only if the enhanced density application is installed.

Configuration and Use Manual 175


Using Totalizers and Inventories

20.4 Process totalizers


Use the View menu to:
• View the current value of a process totalizer
• Start or stop all process totalizers and inventories simultaneously
• Reset a process totalizer
From the View menu:
1. Select Process Totalizers.
2. Select Process. All process totalizers are displayed. Scroll down the list as required.
3. To start all totalizers and inventories, press START.
4. To stop all totalizers and inventories, press STOP.
5. To reset a totalizer, highlight the desired totalizer and press RESET.
Note: The RESET button is available only if resetting totalizers via the display has been enabled. See
Section 5.3.3.
Note: If write-protection has been enabled (see Section 5.3.2), process totalizers cannot be reset
unless the flow rate is zero.

20.5 Process inventories


Use the Maintenance menu to:
• View the current value of a process inventory
• Reset a process inventory
From the Maintenance menu:
1. Select Process Inventory. All process inventories are displayed. Scroll down the list as
required.
2. To reset a process inventory, highlight the desired process inventory and press RESET.
Note: The RESET button is available only if resetting totalizers via the display has been enabled. See
Section 5.3.3.
You can also use the View menu to view the current value of a process inventory. From the View
menu:
1. Select Process Totalizers.
2. Select Inventory.
3. Select the desired process inventory. Its current value is displayed on screen.

20.6 Batch inventories


Use the Maintenance menu to:
• View the current value of a batch inventory
• Reset a batch inventory
From the Maintenance menu:
1. Select Batch Inventory. Values for all batch presets are displayed. Scroll down the list as
required.
2. To reset a batch inventory, highlight the desired batch preset and press RESET.

176 Micro Motion® Series 3000 MVD Transmitters and Controllers


Using Totalizers and Inventories

You can also use the View menu to view the current value of a batch inventory. From the View menu:
1. Select Batch Inventory. Values are listed only for presets that have been enabled.

Operation Mode
2. Scroll down the list as required.

Operation Mode – Batch


Operation Mode – Custody Transfer
Totalizers and Inventories

Configuration and Use Manual 177


178 Micro Motion® Series 3000 MVD Transmitters and Controllers
Measurement Performance
Chapter 21
Measurement Performance

21.1 Overview
This chapter describes the following procedures:
• Meter verification – see Section 21.3

Diagnostics and Troubleshooting


• Meter validation and adjusting meter factors – see Section 21.4
• Density calibration – see Section 21.5
• Temperature calibration – see Section 21.6
This chapter provides basic information and procedural flowcharts for each step. For more details
about how to perform each procedure, see the flowcharts for your Series 3000 device and
communication tool, provided in the appendices to this manual.
Notes: All ProLink II or Communicator procedures provided in this section assume that your
computer is already connected to the Series 3000 device and you have established communication,
and that you are complying with all applicable safety requirements.

21.2 Meter verification, meter validation, and calibration

Specifications – Model 3300/3500


There are three procedures:
• Meter verification – establishing confidence in the sensor’s performance by analyzing
secondary variables that are highly correlated with flow and density calibration factors
• Meter validation – confirming performance by comparing the sensor’s measurements to a
primary standard
• Calibration – establishing the relationship between a process variable (flow, density, or
temperature) and the signal produced by the sensor
These three procedures are discussed and compared in Sections 21.2.1 through 21.2.4. Before
performing any of these procedures, review these sections to ensure that you will be performing the
appropriate procedure for your purposes.

Specifications – Model 3350/3700

Configuration and Use Manual 179


Measurement Performance

21.2.1 Meter verification


Meter verification applies only to the Model 3500 and Model 3700 transmitters. To use meter
verification, the transmitter must be connected to an enhanced core processor and the meter
verification option must have been ordered.
Meter verification evaluates the structural integrity of the sensor tubes by comparing current tube
stiffness to the stiffness measured at the factory. Stiffness is defined as the load per unit deflection, or
force divided by displacement. Because a change in structural integrity changes the sensor’s response
to mass and density, this value can be used as an indicator of measurement performance. Changes in
tube stiffness are typically caused by erosion, corrosion, or tube damage.
Note: Micro Motion recommends that you perform meter verification on a regular basis.
There are two versions of the meter verification application: the original version and Micro Motion
Smart Meter Verification. Table 21-1 lists requirements for the original version and Smart Meter
Verification. Table 21-2 provides a comparison of the two versions.
Note: If you are running an older version of ProLink II or the Communicator device description, you
will not be able to access the additional features in Smart Meter Verification. If you are running an
updated version of ProLink II or the Communicator with the original version of meter verification, the
meter verification procedures will be slightly different from the procedures shown here.

Table 21-1 Version requirements for meter verification application

Meter verification application


Requirement type Original version Smart Meter Verification
Transmitter v7.0 v8.0 and later
Enhanced core processor(1) v3.0 v3.6 and later
ProLink II requirements v2.5 v2.9
HART DD requirements 375 Field Communicator device rev 7, 375 Field Communicator device rev 8,
DD rev 1 DD rev 1
(1) The standard core processor does not support meter verification.

Table 21-2 Comparison of meter verification features and functions: original version vs. Smart Meter
Verification

Meter verification application


Feature or function Original version Smart Meter Verification
Process interruption No need to halt flow No need to halt flow
Measurement interruption Three minutes. Outputs go to: User option:
• Last Measured Value • Continue Measurement. Measurement is
• Configured Fault Value not interrupted. Test requires
approximately 90 seconds.
• Last Measured Value. Outputs fixed and
measurement interrupted for
approximately 140 seconds.
• Configured Fault Value. Outputs fixed
and measurement interrupted for
approximately 140 seconds.
Result storage Test results stored only for tests run with Twenty most recent results stored on the
ProLink II, and stored on the PC transmitter, independent of tool used to
perform the procedure. For tests run with
ProLink II, additional result data stored on
PC.

180 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance

Measurement Performance
Table 21-2 Comparison of meter verification features and functions: original version vs. Smart Meter
Verification continued

Meter verification application


Feature or function Original version Smart Meter Verification
Result data on display Pass/Fail/Abort for current test For all results stored on transmitter:
• Pass/Fail/Abort
• Abort code (if relevant)
• Stiffness of the right and left pickoffs
Result data with Communicator Pass/Caution/Abort for current test For all results stored on transmitter:
• Pass/Caution/Abort
• Abort code (if relevant)
• Stiffness of the right and left pickoffs
• Comparison table for stored results

Diagnostics and Troubleshooting


• Comparison plot for stored results
Result data with ProLink II For all results stored on PC: For all results stored on transmitter:
• Pass/Fail/Abort • Pass/Fail/Abort
• Abort code (if relevant) • Abort code (if relevant)
• Stiffness of the right and left pickoffs • Stiffness of the right and left pickoffs
• Test execution metadata • Test execution metadata
• Comparison graphs • Comparison graphs
• Test reports • Test reports
• Data export and manipulation • Data export and manipulation
capabilities capabilities
Startup methods Manual Manual
Scheduler
Event
Discrete input

21.2.2 Meter validation and meter factors

Specifications – Model 3300/3500


Meter validation can be used with all Series 3000 systems (both transmitters and controllers). There
are no special requirements.
Meter validation compares a measurement value reported by the Series 3000 device with an external
measurement standard. Meter validation requires one data point.
Note: For meter validation to be useful, the external measurement standard must be more accurate
than the sensor. See the sensor’s product data sheet for its accuracy specification.
If the Series 3000 device’s mass flow, volume flow, or density measurement is significantly different
from the external measurement standard, you may want to adjust the corresponding meter factor. A
meter factor is the value by which the Series 3000 device multiplies the process variable value. The
default meter factors are 1.0, resulting in no difference between the data retrieved from the sensor and
the data reported externally.
Meter factors are typically used for proving the flowmeter against a weights and measures standard.
Specifications – Model 3350/3700

You may need to calculate and adjust meter factors periodically to comply with regulations.

21.2.3 Calibration
Calibration applies only to the Model 3500 and Model 3700 transmitters. There are no special
requirements.

Configuration and Use Manual 181


Measurement Performance

The flowmeter measures process variables based on fixed points of reference. Calibration adjusts
those points of reference. Three types of calibration can be performed:
• Zero (see Section 16.3)
• Density calibration
• Temperature calibration
Density and temperature calibration require two data points (low and high) and an external
measurement for each. Calibration produces a change in the offset and/or the slope of the line that
represents the relationship between process density and the reported density value, or the relationship
between process temperature and the reported temperature value.
Note: For density or temperature calibration to be useful, the external measurements must be
accurate.
Transmitters are calibrated at the factory, and normally do not need to be calibrated in the field.
Calibrate the flowmeter only if you must do so to meet regulatory requirements. Contact Micro
Motion before calibrating your flowmeter.
Micro Motion recommends using meter validation and meter factors, rather than calibration, to prove
the meter against a regulatory standard or to correct measurement error.

21.2.4 Comparison and recommendations


When choosing among meter verification, meter validation, and calibration, consider the following
factors:
• Process and measurement interruption
- Smart Meter Verification provides an option that allows process measurement to continue
during the test.
- The original version of meter verification requires approximately three minutes to
perform. During these three minutes, flow can continue (provided sufficient stability is
maintained); however, measurement is halted.
- Meter validation for density does not interrupt the process or process measurement.
However, meter validation for mass flow or volume flow requires process down-time for
the length of the test.
- Calibration requires process down-time. In addition, density and temperature calibration
require replacing the process fluid with low-density and high density fluids, or with
low-temperature and high-temperature fluids.
• External measurement requirements
- Neither version of meter verification requires external measurements.
- Zero calibration does not require external measurements.
- Density calibration, temperature calibration, and meter validation require external
measurements. For good results, the external measurement must be highly accurate.

182 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance

Measurement Performance
• Measurement adjustment
- Meter verification is an indicator of sensor condition, but does not change flowmeter
internal measurement in any way.
- Meter validation does not change flowmeter internal measurement in any way. If you
decide to adjust a meter factor as a result of a meter validation procedure, only the reported
measurement is changed – the base measurement is not changed. You can always reverse
the change by returning the meter factor to its previous value.
- Calibration changes the transmitter’s interpretation of process data, and accordingly
changes the base measurement. If you perform a zero calibration, you can restore the
factory zero at a later time. You cannot return to the previous zero (if different from the
factory zero), density calibration values, or temperature calibration values unless you have
manually recorded them.

Diagnostics and Troubleshooting


Micro Motion recommends obtaining the meter verification option and performing meter verification
on a regular basis.

21.3 Performing meter verification


Note: To use meter verification, the transmitter must be paired with an enhanced core processor, and
the meter verification option must be purchased for the transmitter.

21.3.1 Preparing for the meter verification test

Process fluid and process conditions


The meter verification test can be performed on any process fluid. It is not necessary to match factory
conditions.

Specifications – Model 3300/3500


During the test, process conditions must be stable. To maximize stability:
• Maintain a constant temperature and pressure.
• Avoid changes to fluid composition (e.g., two-phase flow, settling, etc.).
• Maintain a constant flow. For higher test certainty, reduce or stop flow.
If stability varies outside test limits, the meter verification procedure will be aborted. Verify the
stability of the process and retry the test.

Transmitter configuration
Meter verification is not affected by any parameters configured for flow, density, or temperature. It is
not necessary to change the transmitter configuration.

Control loops and process measurement


Specifications – Model 3350/3700

If the transmitter outputs will be set to Last Measured Value or Fault during the test, the outputs will
be fixed for two minutes (Smart Meter Verification) or three minutes (original version). Disable all
control loops for the duration of the test, and ensure that any data reported during this period is
handled appropriately.

Configuration and Use Manual 183


Measurement Performance

Specification uncertainty limit


The specification uncertainty limit defines the acceptable degree of variation from factory results,
expressed as a percentage. Variation inside the limit is reported as Pass. Variation outside the limit is
reported as Fail or Caution.
• In Smart Meter Verification, the specification uncertainty limit is set at the factory and cannot
be configured.
• In the original version of meter verification, the specification uncertainty limit is configurable.
However, Micro Motion suggests using the default value. Contact Micro Motion Customer
Service before changing the specification uncertainty limit.

21.3.2 Running the meter verification test, original version


To run a meter verification test:
• With ProLink II, see Figure 21-1
• With the display, see Figure 21-2
Note: If you start a meter verification test from ProLink II, the transmitter display shows the following
message:
SENSOR
VERFY/x%

184 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance

Measurement Performance
Figure 21-1 Meter verification test, original version – ProLink II

Tools >
Meter Verification >
Structural Integrity Method

Verify configuration View previous test data


parameters

Next

Back(1) Graph of results

Enter optional test data


Next

Diagnostics and Troubleshooting


Next
View report (option to print
or save)
Initialize and start meter
verification
Finish(2)

Start

Fault Hold last


configuration value

Progress bar shows


Abort
test in progress

Specifications – Model 3300/3500


Abort Fail Pass Back
Yes
Next

(1) If the graph was viewed at the beginning of the procedure,


Rerun No clicking Back here will return to the beginning of the
test?
procedure (along the dotted line).
(2) The results of the meter verification test are not saved until
Finish is clicked.

Specifications – Model 3350/3700

Configuration and Use Manual 185


Measurement Performance

Figure 21-2 Meter verification test, original version – Display

Maintenance Menu >


Meter Verification >

Set Uncertainty Limit(1)


(1) Enter the uncertainty limit as a decimal value,
e.g., 0.0400 (4%).
Start Meter Verify

Select

Set output behavior

Proceed?

Yes

Progress . . . . . . . . . x%

PASS FAIL ABORT

21.3.3 Running Smart Meter Verification


To run a Smart Meter Verification test:
• With ProLink II, see Figure 21-3.
• With the display, see Figure 21-4.
• With the Communicator, see Figure 21-5.
Note: If the custody transfer application is installed and the transmitter is secured, you can run a
Smart Meter Verification test with outputs set to Continue Measuring or Fault. Last Measured Value is
not available. See Section 19.3 for detailed information.
Note: If you start a Smart Meter Verification test from ProLink II or the Communicator, and the
outputs are set to Last Measured Value or Fault, the transmitter display shows the following message:
SENSOR
VERFY/x%

186 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance

Measurement Performance
Figure 21-3 Smart Meter Verification test – ProLink II

Tools >
Meter Verification >
Run Meter Verification

Verify configuration
View Previous Results
parameters

Next

Enter descriptive data


(optional)

Diagnostics and Troubleshooting


Next

Configuration Changed
No Yes
or Zero Changed?

View details (optional)

Select output behavior

Start Meter Verification

Specifications – Model 3300/3500


---------------------

Fail Test result Pass

Rerun
Yes No
test? Abort Next Back

Test result chart

Next
Specifications – Model 3350/3700

Report

Finish

Configuration and Use Manual 187


Measurement Performance

Figure 21-4 Smart Meter Verification test – Display

Maintenance Menu >


Meter Verification >

Start Meter Verify

Select

Set output behavior

Output
Continue Measuiring Hold last value
setting

Fault

Proceed?

Yes

Progress . . . . . . . . . x%

PASS FAIL ABORT

188 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance

Measurement Performance
Figure 21-5 Smart Meter Verification test – Communicator

Online > Online >


1 Overview > 3 Service Tools >
3 Shortcuts > 4 Maintenance >
6 Meter Verification 1 Routine Maintenance >
3 Meter Verification

6 3

1 Run Meter Verification


2 View Test Results
3 Schedule Meter Verification

Diagnostics and Troubleshooting


Select Output Behavior

1 Continue Measuring
2 Outputs Held at Last Value
3 Outputs Held at Fault

Meter verification in progress:


x% complete

Abort
Result screen

Abort OK

Specifications – Model 3300/3500


Specifications – Model 3350/3700

Configuration and Use Manual 189


Measurement Performance

21.3.4 Reading and interpreting meter verification test results

Pass/Fail/Abort
When the test is completed, the result will be reported as Pass, Fail, or Abort:
• Pass – The test result is within the specification uncertainty limit. In other words, the stiffness
of the left and right pickoffs match the factory values plus or minus the specification
uncertainty limit. If transmitter zero and configuration match factory values, the sensor will
meet factory specifications for flow and density measurement. It is expected that meters will
pass meter verification every time the test is run.
• Fail/Caution – The test result is not within the specification uncertainty limit. Micro Motion
recommends that you immediately repeat the meter verification test. If you were using Smart
Meter Verification, with outputs set to Continue Measurement, change the setting to Last
Measured Value or Fault.
- If the meter passes the second test, the first Fail/Caution result can be ignored.
- If the meter fails the second test, the flow tubes may be damaged. Use your process
knowledge to determine the possibilities for damage and the appropriate actions for each.
These actions might include removing the meter from service and physically inspecting
the tubes. At minimum, you should perform a flow validation and a density calibration.
• Abort – A problem occurred with the meter verification test (e.g., process instability). Abort
codes are listed and defined in Table 21-3, and suggested actions are provided for each code.

Table 21-3 Meter verification abort codes

Abort code Description Suggested action


1 User-initiated abort None required. Wait for 15 seconds before
starting another test.
3 Frequency drift Ensure that temperature, flow, and density are
stable, and rerun the test.
5 High drive gain Ensure that flow is stable, minimize entrained
gas, and rerun the test.
8 Unstable flow Review the suggestions for stable flow in
Section 21.3.1 and rerun the test.
13 No factory reference data for meter verification Contact Micro Motion customer service and
test performed on air provide the abort code.
14 No factory reference data for meter verification Contact Micro Motion customer service and
test performed on water provide the abort code.
15 No configuration data for meter verification Contact Micro Motion customer service and
provide the abort code.
Other General abort. Repeat the test. If the test aborts again, contact
Micro Motion customer service and provide the
abort code.

190 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance

Measurement Performance
Detailed test data with ProLink II
For each test, the following data is stored on the transmitter:
• Powered-on hours at the time of the test (Smart Meter Verification)
• Test result
• Stiffness of the left and right pickoffs, shown as percentage variation from the factory value. If
the test aborted, 0 is stored for these values.
• Abort code, if applicable
ProLink II stores additional descriptive information for each test in a database on the local PC,
including:
• Timestamp from the PC clock
• Current flowmeter identification data

Diagnostics and Troubleshooting


• Current flow and density configuration parameters
• Current zero values
• Current process values for mass flow rate, volume flow rate, density, temperature, and external
pressure
• (Optional) User-entered customer and test descriptions
If you are using Smart Meter Verification and you run a meter verification test from ProLink II,
ProLink II first checks for new test results on the transmitter and synchronizes the local database if
required. During this step, ProLink II displays the following message:

Synchronizing x out of y
Please wait

Note: If you request an action while synchronization is in process, ProLink II displays a message

Specifications – Model 3300/3500


asking whether or not you want to complete synchronization. If you choose No, the ProLink II
database may not include the latest test results from the transmitter.
Test results are available at the end of each test, in the following forms:
• A test result chart (see Figure 21-6).
• A test report that includes the descriptive information for the current test, the test result chart,
and background information about meter verification. You can export this report to an HTML
file or print it to the default printer.
Note: To view the chart and the report for previous tests without running a test, click View Previous
Test Results and Print Report from the first meter verification panel. See Figure 21-3. Test reports are
available only for tests initiated from ProLink II.
Specifications – Model 3350/3700

Configuration and Use Manual 191


Measurement Performance

Figure 21-6 Test result chart

Initiated from ProLink II


Initiated from the display or other tool

The test result chart shows the results for all tests in the ProLink II database, plotted against the
specification uncertainty limit. The inlet stiffness and the outlet stiffness are plotted separately. This
helps to distinguish between local and uniform changes to the sensor tubes.
This chart supports trend analysis, which can be helpful in detecting meter problems before they
become severe.

192 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance

Measurement Performance
Note the following:
• The test result chart may not show all test results, and test counters may not be continuous.
ProLink II stores information about all tests initiated from ProLink II and all tests available on
the transmitter when the test database is synchronized. However, the transmitter stores only the
twenty most recent test results. To ensure a complete result set, always use ProLink II to
initiate the tests, or synchronize the ProLink II database before overwriting occurs.
• The chart uses different symbols to differentiate between tests initiated from ProLink II and
tests initiated using a different tool. A test report is available only for tests that were initiated
from ProLink II.
• You can double-click the chart to manipulate the presentation in a variety of ways (change
titles, change fonts, colors, borders and gridlines, etc.), and to export the data to additional
formats (including “to printer”).

Diagnostics and Troubleshooting


• You can export this chart to a CSV file for use in external applications.

Detailed test data with the display


Note: Requires Smart Meter Verification. No detailed test data is available with the original version
of the meter verification application.
For each Smart Meter Verification test, the following data is stored on the transmitter:
• Powered-on hours at the time of the test
• Test result
• Stiffness of the left and right pickoffs, shown as percentage variation from the factory value. If
the test aborted, 0 is stored for these values.
• Abort code, if applicable
To view this data, see Figure 21-7.

Specifications – Model 3300/3500


Figure 21-7 Meter verification test data – Display

Maintenance Menu >


Meter Verification >

Read Results

Select

Select Test Number


Specifications – Model 3350/3700

Pass Test result Abort

Fail

Test Result Test Result Test Result


Running Seconds Running Seconds Running Seconds
Outlet Stiffness Outlet Stiffness Test Result
Inlet Stiffness Inlet Stiffness Abort Code

Configuration and Use Manual 193


Measurement Performance

Detailed test data with the Communicator


Note: Requires Smart Meter Verification. No detailed test data is available with the original version
of the meter verification application.
For each Smart Meter Verification test, the following data is stored on the transmitter:
• Powered-on hours at the time of the test
• Test result
• Stiffness of the left and right pickoffs, shown as percentage variation from the factory value. If
the test aborted, 0 is stored for these values.
• Abort code, if applicable
The Communicator also provides a trend function that allows you to compare the results of the 20
tests, viewed as either a table or a graph.
To view this data, see Figure 21-8.

Figure 21-8 Meter verification test data – Communicator

Online > Online >


1 Overview > 3 Service Tools >
3 Shortcuts > 4 Maintenance >
6 Meter Verification 1 Routine Maintenance >
3 Meter Verification

6 3

1 Run Meter Verification


2 View Test Results
3 Schedule Meter Verification

1 Run Counter
2 Running Hours
3 Test Result
4 Abort Code
5 LPO Stiffness
5 RPO Stiffness
7 Show Results Table
8 Show Results Plot

Test Result #x

Run Counter
Running Hours
Test Result
Abort Code
LPO Stiffness
RPO Stiffness

Abort OK

To previous test

194 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance

Measurement Performance
21.3.5 Setting up automatic or remote execution of the meter verification test
Note: Requires Smart Meter Verification. Scheduling is not available with the original version of the
meter verification application.
There are three ways to execute a Smart Meter Verification test automatically:
• Define it as an event action
• Set up a one-time automatic execution
• Set up a recurring execution
In addition, if your transmitter has a discrete input, you can configure the discrete input to initiate a
Smart Meter Verification test remotely.
In all cases, the test will be performed with outputs set to Continue Measuring.
You can use these methods in any combination. For example, you can specify that a Smart Meter

Diagnostics and Troubleshooting


Verification test will be executed three hours from now, every 24 hours starting now, every time a
specific discrete event occurs, and every time the discrete input is activated.
• To define meter verification as an event action, see Figure 10.4.
• To define meter verification as a discrete input action, see Section 7.3.5.
• To set up a one-time automatic execution, set up a recurring execution, view the number of
hours until the next scheduled test, or delete a schedule:
- With ProLink II, click Tools > Meter Verification > Schedule Meter Verification.
- With the display, see Figure 21-9.
- With the Communicator, see Figure 21-10
Note the following:
• If you are setting up a one-time automatic execution, specify the start time as a number of

Specifications – Model 3300/3500


hours from the present time. For example, if the present time is 2:00 and you specify 3.5 hours,
the test will be initiated at 5:30.
• If you are setting up a recurring execution, specify the number of hours to elapse between
executions. The first test will be initiated when the specified number of hours has elapsed, and
testing will be repeated at the same interval until the schedule is deleted. For example, if the
present time is 2:00 and you specify 2 hours, the first test will be initiated at 4:00, the next at
6:00, and so on.
• To turn off automatic execution from the display, set the appropriate value (Next Run or
Recurring Time) to 0 hours.

Specifications – Model 3350/3700

Configuration and Use Manual 195


Measurement Performance

Figure 21-9 Smart Meter Verification scheduler – Display

Maintenance Menu >


Meter Verification >

Schedule Meter Verify

Select

Time Remaining

Next Run

Recurring Time

Figure 21-10 Smart Meter Verification scheduler – Communicator

Online > Online >


1 Overview > 3 Service Tools >
3 Shortcuts > 4 Maintenance >
6 Meter Verification 1 Routine Maintenance >
3 Meter Verification

6 3

1 Run Meter Verification


2 View Test Results
3 Schedule Meter Verification

1 Next Run
2 Set Hrs Until Next Run
3 Set Recurring Hours
4 Turn Off Schedule

21.4 Performing meter validation


To perform meter validation, measure a sample of the process fluid and compare the measurement
with the flowmeter’s reported value.
Use the following formula to calculate a meter factor:

ExternalStandard
NewMeterFactor = ConfiguredMeterFactor  -----------------------------------------------------------------------------------
ActualTransmitterMeasurement

Valid values for meter factors range from 0.8 to 1.2. If the calculated meter factor exceeds these
limits, contact Micro Motion customer service.
To enter the new meter factor, use the Inputs menu (see Figure 7-1).

196 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance

Measurement Performance
Example The flowmeter is installed and proved for the first time. The flowmeter
mass measurement is 250.27 lb; the reference device measurement is
250 lb. A mass flow meter factor is determined as follows:
250
MassFlowMeterFactor = 1  ------------------ = 0.9989
250.27

The first mass flow meter factor is 0.9989.

One year later, the flowmeter is proved again. The flowmeter mass
measurement is 250.07 lb; the reference device measurement is
250.25 lb. A new mass flow meter factor is determined as follows:
250.25
MassFlowMeterFactor = 0.9989  ------------------ = 0.9996
250.07

Diagnostics and Troubleshooting


The new mass flow meter factor is 0.9996.

21.5 Performing density calibration


Density calibration includes the following calibration points:
• All sensors:
- D1 calibration (low-density)
- D2 calibration (high-density)
• T-Series sensors only:
- D3 calibration (optional)
- D4 calibration (optional)
For T-Series sensors, the optional D3 and D4 calibrations could improve the accuracy of the density

Specifications – Model 3300/3500


measurement. If you choose to perform the D3 and D4 calibration:
• Do not perform the D1 or D2 calibration.
• Perform D3 calibration if you have one calibrated fluid.
• Perform both D3 and D4 calibrations if you have two calibrated fluids (other than air and
water).
The calibrations that you choose must be performed without interruption, in the order listed here.
Note: Before performing the calibration, record your current calibration parameters. If you are using
ProLink II, you can do this by saving the current configuration to a file on the PC. If the calibration
fails, restore the known values.

21.5.1 Preparing for density calibration


Specifications – Model 3350/3700

Before beginning density calibration, review the requirements in this section.

Sensor requirements
During density calibration, the sensor must be completely filled with the calibration fluid, and flow
through the sensor must be at the lowest rate allowed by your application. This is usually
accomplished by closing the shutoff valve downstream from the sensor, then filling the sensor with
the appropriate fluid.

Configuration and Use Manual 197


Measurement Performance

Density calibration fluids


D1 and D2 density calibration require a D1 (low-density) fluid and a D2 (high-density) fluid. You
may use air and water. If you are calibrating a T-Series sensor, the D1 fluid must be air and the D2
fluid must be water.

CAUTION
For T-Series sensors, the D1 calibration must be performed on air and the D2
calibration must be performed on water.

For D3 density calibration, the D3 fluid must meet the following requirements:
• Minimum density of 0.6 g/cm3
• Minimum difference of 0.1 g/cm3 between the density of the D3 fluid and the density of water.
The density of the D3 fluid may be either greater or less than the density of water
For D4 density calibration, the D4 fluid must meet the following requirements:
• Minimum density of 0.6 g/cm3
• Minimum difference of 0.1 g/cm3 between the density of the D4 fluid and the density of the
D3 fluid. The density of the D4 fluid must be greater than the density of the D3 fluid
• Minimum difference of 0.1 g/cm3 between the density of the D4 fluid and the density of water.
The density of the D4 fluid may be either greater or less than the density of water
During the calibration, you must enter the density of the calibration fluid. For convenience, Tables
21-4 and 21-5 provide the density of air and water at different environmental conditions.

Table 21-4 Density of air

Pressure Temperature in °C and °F


in millibar
(inches of 10 °C 15 °C 20 °C 25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
mercury) 50 °F 59 °F 68 °F 77 °F 86 °F 95 °F 104 °F 113 °F 122 °F
850 (25.14) .0010 .0010 .0010 .0010 .0010 .0010 .0009 .0009 .0009
900 (26.62) .0011 .0011 .0011 .0010 .0010 .0010 .0010 .0010 .0009
950 (28.10) .0012 .0011 .0011 .0011 .0011 .0011 .0010 .0010 .0010
1000 (29.57) .0012 .0012 .0012 .0012 .0011 .0011 .0011 .0011 .0011
1050 (31.06) .0013 .0013 .0012 .0012 .0012 .0012 .0012 .0011 .0011

198 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance

Measurement Performance
Table 21-5 Density of water

Temperature Temperature
°C °F Density in g/cm3 °C °F Density in g/cm3
0 32 0.99987 21 69.8 0.99802
1 33.8 0.99993 22 71.6 0.99780
2 35.6 0.99997 23 73.4 0.99756
3 37.4 0.99999 24 75.2 0.99732
4 39.2 1.00000 25 77 0.99707
5 41 0.99999 26 78.8 0.99681
6 42.8 0.99997 27 80.6 0.99654
7 44.6 0.99993 28 82.4 0.99626
8 46.4 0.99988 29 84.2 0.99597
9 48.2 0.99981 30 86 0.99567
10 50 0.99973

Diagnostics and Troubleshooting


11 51.8 0.99963 31 87.8 0.99537
12 53.6 0.99952 32 89.6 0.99505
13 55.4 0.99940 33 91.4 0.99473
14 57.2 0.99927 34 93.2 0.99440
15 59 0.99913 35 95 0.99406
16 60.8 0.99897 36 96.8 0.99371
17 62.6 0.99880 37 98.6 0.99336
18 64.4 0.99862 38 100.4 0.99229
19 66.2 0.99843
20 68 0.99823

21.5.2 Density calibration procedures


To perform the low-density calibration:
1. Fill the sensor with a low-density fluid, such as air.

Specifications – Model 3300/3500


2. If possible, shut off the flow. Otherwise, pump the fluid through the sensor at the lowest flow
rate allowed by the process.
3. Use any established method to derive an accurate density, in g/cm3, for the fluid at line
conditions. If air is the low-density calibration fluid, a value from Table 21-4 can be used for
the density.
4. Press the Security button on the display.
5. From the Maintenance menu, select Calibration.
6. Select Density.
7. Select Low Density.
a. Set the D1 value to the line-condition density in grams per cubic centimeter.
b. Select Calibrate Density, then press SEL. A “Calibration In Progress” alarm is generated.
8. When the calibration is complete:
Specifications – Model 3350/3700

• In the active alarm log, the alarm changes from “active” to “inactive but unacknowledged.”
• If the calibration succeeded, a “Success” status is displayed.
• If the calibration failed, a “Failed” status is displayed.
9. Press EXIT to return to the Density menu.
10. (Optional) To clear the alarm from the active alarm log and the alarm bar at the top of the
display, acknowledge the alarm using the procedures described in Chapter 22.
To perform the high-density calibration:
1. Fill the sensor with a high-density fluid, such as water.

Configuration and Use Manual 199


Measurement Performance

2. If possible, shut off the flow. Otherwise, pump the fluid through the sensor at the lowest flow
rate allowed by the process.
3. To ensure stable density, make sure the fluid in the flow tubes remains completely free of gas
bubbles during the calibration.
4. Use any established method to derive an accurate density, in g/cm3, for the fluid at line
conditions. If water is the high-density calibration fluid, a value from Table 21-5 can be used
for the density.
5. From the Density menu, select High Density.
a. Set the D2 value to the line-condition density in grams per cubic centimeter.
b. Select Calibrate Density, then press SEL. A “Calibration In Progress” alarm is generated.
6. When the calibration is complete:
• In the active alarm log, the alarm changes from “active” to “inactive but unacknowledged.”
• If the calibration succeeded, a “Success” status is displayed.
• If the calibration failed, a “Failed” status is displayed.
7. Press EXIT to return to the Density menu.
8. (Optional) To clear the alarm from the active alarm log and the alarm bar at the top of the
display, acknowledge the alarm using the procedures described in Chapter 22.
To perform the D3 calibration (T-Series sensors only):
1. Fill the sensor completely with a fluid of known density.
2. If possible, shut off the flow. Otherwise, pump the fluid through the sensor at the lowest flow
rate allowed by the process.
3. To ensure stable density, make sure the fluid in the flow tubes remains completely free of gas
bubbles during the calibration.
4. Use any established method to derive an accurate density, in g/cm3, for the fluid at line
conditions.
5. From the Density menu, select Density D3.
a. Set the D3 value to the line-condition density in grams per cubic centimeter.
b. Select Calibrate Density, then press SEL. A “Calibration In Progress” alarm is generated.
6. When the calibration is complete:
• In the active alarm log, the alarm changes from “active” to “inactive but unacknowledged.”
• If the calibration succeeded, a “Success” status is displayed.
• If the calibration failed, a “Failed” status is displayed.
7. Press EXIT to return to the Density menu.
8. (Optional) To clear the alarm from the active alarm log and the alarm bar at the top of the
display, acknowledge the alarm using the procedures described in Chapter 22.
To perform the D4 calibration (T-Series sensors only):
1. Fill the sensor completely with a fluid of known density.
2. If possible, shut off the flow. Otherwise, pump the fluid through the sensor at the lowest flow
rate allowed by the process.
3. To ensure stable density, make sure the fluid in the flow tubes remains completely free of gas
bubbles during the calibration.

200 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance

Measurement Performance
4. Use any established method to derive an accurate density, in g/cm3, for the fluid at line
conditions.
5. From the Density menu, select Density D4.
a. Set the D4 value to the line-condition density in grams per cubic centimeter.
b. Select Calibrate Density, then press SEL. A “Calibration In Progress” alarm is generated.
6. When the calibration is complete:
• In the active alarm log, the alarm changes from “active” to “inactive but unacknowledged.”
• If the calibration succeeded, a “Success” status is displayed.
• If the calibration failed, a “Failed” status is displayed.
7. Press EXIT to return to the Density menu.
8. (Optional) To clear the alarm from the active alarm log and the alarm bar at the top of the

Diagnostics and Troubleshooting


display, acknowledge the alarm using the procedures described in Chapter 22.

21.6 Performing temperature calibration


Temperature calibration is a two-part procedure: temperature offset calibration and temperature slope
calibration. The entire procedure must be completed without interruption.
Temperature calibration requires reading and entering temperature values in degrees Celsius.
Although it is not required, it may be useful to configure the temperature unit for degrees Celsius. See
Section 7.3.2 for information on configuring the temperature unit.
To perform the temperature offset calibration:
1. Fill the sensor with process fluid at the lowest temperature measured during the application.
2. Wait approximately 30 minutes for the flow tube temperature to stabilize.

Specifications – Model 3300/3500


3. Use a highly accurate thermometer, temperature sensor, RTD, or other device to measure the
temperature of the process fluid.
4. From the Maintenance menu, select Calibration.
5. Select Temperature.
6. Select Low Temperature.
7. At the Low Temperature menu:
a. Set the Low Temperature Value to the temperature that was measured in Step 3, in
degrees Celsius, then press SAVE.
b. Select Calibrate Temp, then press SEL.
8. During calibration, an alarm message is generated.
9. When the calibration is complete:
• In the active alarm log, the alarm changes from “active” to “inactive but unacknowledged.”
Specifications – Model 3350/3700

• If the calibration succeeded, a “Success” status is displayed.


• If the calibration failed, a “Failed” status is displayed.
10. Press EXIT to return to the Temperature menu.
11. (Optional) To clear the alarm from the active alarm log and the alarm bar at the top of the
display, acknowledge the alarm using the procedures described in Chapter 22.
To perform the temperature slope calibration:
1. Fill the sensor with process fluid at the highest temperature measured during the application.

Configuration and Use Manual 201


Measurement Performance

2. Wait approximately 30 minutes for the flow tube temperature to stabilize.


3. Use the same reference device as the one that was used during the temperature offset
calibration to measure the temperature of the process fluid.
4. From the Temperature menu, select High Temperature.
5. At the High Temperature menu:
a. Set the High Temperature Value to the temperature that was measured in Step 3, in
degrees Celsius, then press SAVE.
b. Select Calibrate Temp, then press SEL.
6. During calibration, an alarm message is generated.
7. When the calibration is complete:
• In the active alarm log, the alarm changes from “active” to “inactive but unacknowledged.”
• If the calibration succeeded, a “Success” status is displayed.
• If the calibration failed, a “Failed” status is displayed.
8. Press EXIT to return to the Temperature menu.
9. (Optional) To clear the alarm from the active alarm log and the alarm bar at the top of the
display, acknowledge the alarm using the procedures described in Chapter 22.

202 Micro Motion® Series 3000 MVD Transmitters and Controllers


Measurement Performance
Chapter 22
Diagnostics and Troubleshooting

22.1 About this chapter


This chapter explains how to use the diagnostic software to troubleshoot alarm conditions. Diagnostic
software includes:

Diagnostics and Troubleshooting


• Meter fingerprinting
• Sensor simulation mode
• The active alarm log
• Alarm messages
• The diagnostic monitor
This chapter also provides additional information on troubleshooting.

22.2 Checking process variables


Micro Motion suggests that you make a record of basic process variables under normal operating
conditions. This will help you recognize when the process variables are unusually high or low. The
meter fingerprinting feature (see Section 22.3) may be used to record the current levels of twelve

Specifications – Model 3300/3500


process variables, and to view the recorded levels of these process variables at three other points of
transmitter operation.
For troubleshooting, check the process variables under both normal flow and tubes-full no-flow
conditions. Except for flow rate, you should see little or no change between flow and no-flow
conditions. if you see a significant difference, record the values and contact Micro Motion customer
service for assistance.
Unusual values for process variables may indicate a variety of different problems. Table 22-1 lists
several possible problems and remedies.

Table 22-1 Process variables problems and possible remedies

Symptom Cause Possible remedy


Steady non-zero flow rate under Misaligned piping (especially in new Correct the piping.
no-flow conditions installations)
Specifications – Model 3350/3700

Open or leaking valve. Check or correct the valve mechanism.


Bad sensor zero Rezero the flowmeter. See
Section 16.3.
Inappropriate measurement unit Check configuration. See
Section 22.13.
Cutoff set too low Check configuration. See Section 7.3.2.
Bad flow calibration factor Verify characterization. See
Section 22.16.

Configuration and Use Manual 203


Diagnostics and Troubleshooting

Table 22-1 Process variables problems and possible remedies continued

Symptom Cause Possible remedy


Erratic non-zero flow rate under RF interference Check environment for RF interference.
no-flow conditions See Section 22.11.5.
Wiring problem Verify all sensor-to-transmitter wiring
and ensure the wires are making good
contact.
Incorrectly grounded 9-wire cable Verify 9-wire cable installation.
(remote core processor with remote
transmitter installations)
Vibration in pipeline at rate close to Check environment and remove source
sensor tube frequency of vibration.
Improper sensor grounding (T-Series Verify that the sensor is grounded to
sensors only) earth ground.
Leaking valve or seal Check pipeline.
Inappropriate measurement unit Check configuration. See
Section 22.13.
Inappropriate damping value Check configuration. See Section 7.3.2.
Slug flow See Slug flow alarms in Section 22.7.3.
Plugged flow tube Check drive gain and tube frequency.
Purge the flow tubes or replace the
sensor.
Moisture in sensor junction box Open junction box and allow it to dry.
Do not use contact cleaner. When
closing, ensure integrity of gaskets and
O-rings, and grease all O-rings.
Mounting stress on sensor Check sensor mounting. Ensure:
• Sensor is not being used to support
pipe.
• Sensor is not being used to correct
pipe misalignment.
• Sensor is not too heavy for pipe.
Sensor cross-talk Check environment for sensor with
similar (± 0.5 Hz) tube frequency.
Incorrect sensor orientation Sensor orientation must be appropriate
to process fluid. See the installation
manual for your sensor.
Erratic non-zero flow rate when flow Output wiring problem Verify wiring between Series 3000
is steady device and receiving device. See the
transmitter installation instructions.
Problem with receiving device Test with another receiving device.
Inappropriate measurement unit Check configuration. See
Section 22.13.
Inappropriate damping value Check configuration. See Section 7.3.2.
Excessive or erratic drive gain See Section 22.18.3 and
Section 22.18.4.
Slug flow See Slug flow alarms in Section 22.7.3.
Plugged flow tube Check drive gain and tube frequency.
Purge the flow tubes or replace the
sensor.
Wiring problem Verify all sensor-to-transmitter wiring
and ensure the wires are making good
contact.

204 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Table 22-1 Process variables problems and possible remedies continued

Symptom Cause Possible remedy


Inaccurate flow rate or batch total Bad flow calibration factor Verify characterization. See
Section 7.3.3.
Inappropriate measurement unit Check configuration. See
Section 22.13.
Bad sensor zero Rezero the meter. See Section 16.3.
Bad density calibration factors Verify characterization. See
Section 7.3.3.
Bad flowmeter grounding See Section 22.11.3.
Slug flow See Slug flow alarms in Section 22.7.3.
Problem with receiving device See Section 22.11.6.

Diagnostics and Troubleshooting


Wiring problem Verify all sensor-to-transmitter wiring
and ensure the wires are making good
contact.
Inaccurate density reading Problem with process fluid Use standard procedures to check
quality of process fluid.
Bad density calibration factors Verify characterization. See
Section 7.3.3.
Wiring problem Verify all sensor-to-transmitter wiring
and ensure the wires are making good
contact.
Bad flowmeter grounding See Section 22.11.3.
Slug flow See Slug flow alarms in Section 22.7.3.
Sensor cross-talk Check environment for sensor with
similar (±0.5 Hz) tube frequency.

Specifications – Model 3300/3500


Plugged flow tube Check drive gain and tube frequency.
Purge the flow tubes or replace the
sensor.
Temperature reading significantly RTD failure Check for alarm conditions and follow
different from process temperature troubleshooting procedure for indicated
alarm.
Verify polling configuration and disable
polling for temperature if appropriate.
See Section 7.6.
Problem with sensor wiring Check wiring to sensor. See
Section 22.11.2.
Incorrect calibration factor Verify that the temperature calibration
factor is set correctly. See
Section 22.17.
Temperature reading slightly different Temperature calibration required Perform temperature calibration. See
from process temperature Section 21.6.
Specifications – Model 3350/3700

Loose connections in sensor wiring Check wiring to sensor. See


Section 22.11.2.
Corrosion in flow tube Purge the flow tubes.
Unusually high density reading Plugged, partially filled, or coated flow Check drive gain and tube frequency.
tube See Section 22.18.
Purge the flow tubes.
Incorrect K2 value Verify characterization. See
Section 22.16.

Configuration and Use Manual 205


Diagnostics and Troubleshooting

Table 22-1 Process variables problems and possible remedies continued

Symptom Cause Possible remedy


Unusually low density reading Slug flow See Section 22.7.3.
Incorrect K2 value Verify characterization. See
Section 22.16.
Sensor erosion Contact Micro Motion.
Unusually high tube frequency Sensor erosion Contact Micro Motion.
Reversed drive coil leads (remote core Verify drive coil leads
processor with remote transmitter
installations)
Unusually low tube frequency Plugged, partially filled, or coated flow Check drive gain and tube frequency.
tube See Section 22.18.
Purge the flow tubes.
Unusually low pickoff voltages Several possible causes See Section 22.18.5.
Unusually high drive gain Several possible causes See Section 22.18.3.

22.3 Meter fingerprinting


Note: Meter fingerprinting is available only on systems with the standard core processor.
The meter fingerprinting feature provides snapshots, or “fingerprints,” of twelve process variables, at
four different points of transmitter operation. See Table 22-2.

Table 22-2 Meter fingerprinting data

Fingerprint time Description Process variables recorded


Current Present-time values • Mass flow rate • Tube frequency
• Volume flow rate • Drive gain
Factory Values at time transmitter left factory
• Density • Left pickoff
Installation Values at time of first sensor zero • Temperature • Right pickoff
• Case temperature • Core processor temperature
Last zero Values at time of most recent sensor • Mech zero • Core processor input voltage
zero

For each process variable, the following values are recorded:


• For Mech Zero:
- 5-minute running average
- 5-minute running standard deviation
• For all other process variables:
- Instantaneous value
- 5-minute running average
- 5-minute running standard deviation
- Recorded minimum
- Recorded maximum
To access meter fingerprint data, use the Maintenance menu as shown in Figure 22-1. The transmitter
will report the data in either SI units or English units, as configured from the Units menu item. The
display is updated continuously.

206 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
When the cursor is positioned on Current, you can use the RESET button to set a new start time for
the recorded minimum and maximum values.
When the cursor is positioned on Factory, you can use the SAVE button to overwrite the data in the
factory fingerprint with the current fingerprint data.
Note: Due to the continuous updating, the meter fingerprinting feature can have a negative effect on
other sensor-transmitter communications. Do not open the meter fingerprinting window unless you
plan to use it, and be sure to close it when you no longer need it.

Figure 22-1 Meter fingerprinting menu

Maintenance

Diagnostics and Troubleshooting


Meter Fingerprinting

Units Current Factory Installation Last zero

SI
English
• Mass flow rate
• Volume flow rate
• Density
• Temperature

Specifications – Model 3300/3500


• Case temperature
• Live zero
• Tube frequency
• Drive gain
• Left pickoff
• Right pickoff
• Board temperature
• Input voltage

22.4 Sensor simulation mode


Note: Sensor simulation mode is available only on systems with the enhanced core processor.
Sensor simulation allows you to simulate process data for mass flow, temperature, and density. Sensor
simulation mode has several uses:
• It can help determine if a problem is located in the transmitter or elsewhere in the system. For
Specifications – Model 3350/3700

example, signal oscillation or noise is a common occurrence. The source could be the PLC, the
meter, improper grounding, or a number of other factors. By using sensor simulation to output
a flat signal, you can determine the point at which the noise is introduced.
• It can be used to analyze system response or to tune the loop.

Configuration and Use Manual 207


Diagnostics and Troubleshooting

If sensor simulation mode is active, the specified simulated values are substituted for process data
from the sensor. Therefore, sensor simulation will affect, for example:
• All mass flow, temperature, or density values shown on the display or reported via outputs or
digital communications
• The mass total and mass inventory values
• All volume calculations and data, including reported values, volume totals, and volume
inventories
Accordingly, do not enable simulation when your process cannot tolerate these effects, and be sure to
disable simulation when you have finished testing.
Note: Unlike actual mass flow and density values, the simulated values are not
temperature-compensated.
Note: Simulation does not change any diagnostic values.
Sensor simulation mode is available via ProLink II (see Figure G-3) or the Communicator (see
Figure H-7). To set up sensor simulation, follow the steps below:
1. Enable simulation mode.
2. For mass flow:
a. Specify the type of simulation you want: fixed value, triangular wave, or sine wave.
b. Enter the required values.
• If you specified fixed value simulation, enter a fixed value.
• If you specified triangular wave or sine wave simulation, enter a minimum amplitude,
maximum amplitude, and period.
3. Repeat Step 2 for temperature and density.
To use sensor simulation mode for problem location, enable simulation mode and check the signal at
various points between the transmitter and the receiving device.

22.5 Updates, upgrades, and master resets


Micro Motion recommends that you document or save device configuration information before
updating or upgrading the software in your Series 3000 device or before performing a master reset.
You can document the configuration manually. Alternatively, if you have ProLink II, you can save the
configuration data to a file on the PC.

22.6 Alarm types and handling


The Series 3000 device performs self-diagnostics during operation. If the device detects certain events
or conditions, an alarm message appears in the highlight bar at the top of the screen, and an alarm is
written to the active alarm log.

22.6.1 Alarm severity


Alarms are classified into three levels of severity. The severity level controls device behavior when the
alarm condition occurs. See Table 22-3.

208 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Table 22-3 Alarm severity levels and fault reporting

Series 3000 device action if condition occurs


“Alarm active” Alarm shown “Alarm active” record Fault indication
Severity level status bit set? on display? written to history? activated? (1)
Fault Yes Yes Yes Yes
Informational Yes Yes Yes No
Ignore Yes No No No
(1) For some alarms, fault indication (setting outputs to configured fault levels) will not occur until the fault timeout expired. For other
alarms, fault indication begins as soon as the fault condition is recognized. Tables 22-4 through 22-6 include information on which
alarms are affected by the fault timeout. To configure fault timeout, see Chapter 8.

Diagnostics and Troubleshooting


Some alarms can be reclassified. For example:
• The default severity level for Alarm A020 (calibration factors unentered) is Fault, but you can
reconfigure it to either Informational or Ignore.
• The default severity level for Alarm A102 (drive over-range) is Informational, but you can
reconfigure it to either Ignore or Fault.
For information on which alarms can be reclassified, see Section 22.7. For information on how to
reclassify alarms, see Section 6.3.1.

22.6.2 Fault timeout


By default, the Series 3000 device immediately sets outputs to their configured fault levels when a
fault is encountered. For specific faults, you can delay this action by changing the fault timeout to a
non-zero value (see Chapter 8). If fault timeout is configured:

Specifications – Model 3300/3500


• During the fault timeout period, the device continues to report its last valid measurement.
• The fault timeout applies only to the mA output, frequency output, and discrete output. Fault
indication via digital communications is unaffected.
The fault timeout is not applicable to all faults. See Section 22.7 for information about which faults
are affected.

22.6.3 Alarm categories


Alarms are organized into four alarm categories, in the following order of priority:
• Electronics
• Sensor (Model 3500 and Model 3700 transmitters only)
• Process
Specifications – Model 3350/3700

• Configuration

22.6.4 Alarm occurrences and logs


Information about alarm occurrences is maintained and displayed in three different ways:
• Active alarm log (see Figure 22-2) – Lists:
- All alarms that are active (the condition that caused the alarm is active)
- All alarms that have not been acknowledged (even if the condition causing the alarm is no
longer active)

Configuration and Use Manual 209


Diagnostics and Troubleshooting

The active alarm log provides help for each alarm listed (see Section 22.6.5), and also allows
you to acknowledge alarms. It is cleared and regenerated with every Series 3000 power cycle.
When the active alarm log is viewed through the View menu, only categories containing active
alarms are listed; individual alarms are not listed. When the active alarm log is viewed through
the Maintenance menu, individual alarms are listed.
• Alarm history (see Figure 22-3) – Lists all alarms that have occurred, with a count of the
number of times a particular alarm has occurred, and the timestamp of the last time the alarm
was posted and cleared. It is not cleared when a Series 3000 power cycle occurs. You cannot
acknowledge alarms or access the help system from alarm history. Alarm history is accessible
from the Maintenance menu.
• Alarm event log (see Figure 22-4) – Lists the 50 most recent alarm post or alarm clear events.
It is not cleared when a Series 3000 power cycle occurs. You cannot acknowledge alarms or
access the help system from the alarm event log. The alarm event log is accessible from the
Maintenance menu.

Figure 22-2 Example alarm log

Active Alarm Log

Sensor Failure
23-JUN-03 10:02
Density Out-of-Range
23-JUN-03 10:02
Xmtr Initializing
23-JUN-03 10:02
Power Reset
23-JUN-03 10:02

ACK HELP EXIT

Figure 22-3 Example alarm history

Alarm History

Power Reset
Cnt 25
Post 23-JUN-03 14:56
Clr 23-JUN-03 14:56

Freq. Output Fixed


Cnt 1
Post 13-JUN-03 9:39
Clr 13-JUN-03 9:39

EXIT

210 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Figure 22-4 Example alarm event log

Alarm Event Log

Meter Verify Hold LMV


Clr: 15-JAN-07 16:53

Sensor Failure
Clr: 15-JAN-07 16:51

Sensor Failure
Post: 15-JAN-07 16:50

EXIT

Diagnostics and Troubleshooting


Active alarm log
To access the active alarm log from the View menu:
1. At the operation screen, press EXIT or VIEW.
2. Highlight Active Alarm Log.
3. To acknowledge all alarms, press the ACKALL button.
4. To acknowledge all alarms in an alarm category:
a. Select Active Alarm Log.
b. Use the cursor keys to highlight the alarm category.
c. Press the ACK button.

Specifications – Model 3300/3500


Note: You cannot view and acknowledge individual alarms from the View menu.
To access the active alarm log from the Maintenance menu:
1. At the operation screen, press the Security button.
2. Select Maintenance.
3. Highlight Active Alarm Log.
4. To acknowledge all alarms, press the ACKALL button.
5. To acknowledge a single alarm:
a. Select Active Alarm Log.
b. Use the cursor keys to highlight the alarm.
c. Press the ACK button.
Specifications – Model 3350/3700

22.6.5 Help system


Help is provided for each alarm. The help system can be accessed from several locations:
• From the list of alarm categories in the active alarm log. If multiple alarms are posted in the
active alarm log, press PGDN to view help for all alarms in the selected category.
• From the list of individual alarms in the active alarm log
• Wherever the HELP button appears
To view help from a list, highlight a list entry and press the HELP button.

Configuration and Use Manual 211


Diagnostics and Troubleshooting

The help system will display up to five screens of information. On these screens:
• The alarm number is displayed.
• An explanation of the alarm is provided.
• Instructions for correcting the alarm condition may be provided.
• If the help occupies more than one screen, use the PGDN (page down) or PGUP (page up)
buttons to view all the help text.

Figure 22-5 Example alarm help

ALARMS
Alarm number Density Out-of-Range
[A8]The density
reading is outside
the sensor limits. If
the Sensor Failure
(A3) alarm is also
present, solve the
Sensor Failure first.
Verify all density
PGDN EXIT

22.7 Alarm listings by category


This section lists all alarms in the four alarm categories (Electronics, Sensor, Process, and
Configuration), and provides information on alarm severity level, user configuration, fault timeout
behavior, and suggested user actions.

22.7.1 Electronics alarms


Table 22-4 lists all alarms in the Electronics category, with descriptions, suggested user actions, and
related information.

Table 22-4 Electronics alarms

Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
A001 CP EEPROM Uncorrectable Fault No No Cycle power to the
Failure checksum flowmeter.
mismatch.
The flowmeter might need
service. Contact Micro
Motion customer service.
A002 CP RAM Failure A RAM location Fault No No Cycle power to the
in the core flowmeter.
processor cannot
be written to. The flowmeter might need
service. Contact Micro
Motion customer service.

212 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Table 22-4 Electronics alarms continued

Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
A009 Xmtr Initializing Device is Fault Yes No No action required unless
performing alarm does not clear. If alarm
self-calibration does not clear:
after power-up. • Check wiring to sensor.
• Check power supply wiring.
• Make sure that the sensor
is completely full or
completely empty.
• Verify sensor configuration.
See Section 7.3.3.

Diagnostics and Troubleshooting


• If A026 alarm is present,
check core processor
address. See Section 19.6.
A014 Transmitter Error Transmitter Fault No No Cycle power to the
failure for any of flowmeter.
several reasons.
Perform sensor coil and
resistance tests. See
Section 22.20.
The flowmeter might need
service. Contact Micro
Motion customer service.
A018 EEPROM (3000) Uncorrectable Fault No No Cycle power to the
checksum flowmeter.
mismatch.
The flowmeter might need
service. Contact Micro
Motion customer service.

Specifications – Model 3300/3500


A019 RAM Failure A RAM location Fault No No Cycle power to the
in the transmitter flowmeter.
cannot be written
The flowmeter might need
to.
service. Contact Micro
Motion customer service.
A022(1) CP Config Failure Uncorrectable Fault No No Cycle power to the
checksum flowmeter.
mismatch.
The flowmeter might need
service. Contact Micro
Motion customer service.
A023(1) CP Totals Failure Uncorrectable Fault No No Cycle power to the
checksum flowmeter.
mismatch.
The flowmeter might need
service. Contact Micro
Motion customer service.
Specifications – Model 3350/3700

A024(1) CP Program Uncorrectable Fault No No Cycle power to the


Failure checksum flowmeter.
mismatch.
The flowmeter might need
service. Contact Micro
Motion customer service.
A025(1) CP Boot Program Uncorrectable Fault No No Cycle power to the
Fault checksum flowmeter.
mismatch.
The flowmeter might need
service. Contact Micro
Motion customer service.

Configuration and Use Manual 213


Diagnostics and Troubleshooting

Table 22-4 Electronics alarms continued

Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
A026 Xmtr Comm Communication Fault No No If the custody transfer
Problem errors between application is installed, the
transmitter and core processor may have
core processor. been disconnected or
replaced. See Section 22.9.
Check wiring between
transmitter and core
processor (remote core
processor with remote
transmitter installations).
Check for noise in wiring or
transmitter environment.
Check the core processor
LED. See Section 22.19.1.
Check that the core
processor is receiving power.
See Section 22.11.1.
Perform the core processor
resistance test. See
Section 22.19.2.
A028 Xmtr Write Error Attempt to write Fault No No Cycle power to the
to the core flowmeter.
processor has
The flowmeter might need
failed.
service. Contact Micro
Motion customer service.
A031(2) Low Power The core Fault No No Check the power supply and
processor is not all power wiring.
receiving enough
power.
A103(1) Data Loss Core processor Info Yes No Cycle power to the
Possible unable to store flowmeter.
totalizer values
View the entire current
on last power
configuration to determine
down.
what data were lost.
Configure any settings with
missing or incorrect data.
The flowmeter might need
service. Contact Micro
Motion customer service.
A107 Power Reset Transmitter has Info Yes No No action required.
been restarted.
A112(3) Upgrade Transmitter Info Yes No Upgrade software. Contact
Software software is Micro Motion customer
downlevel from service. Note that the device
core processor is still functional.
software.
A129 PPI Display Error (Custody transfer Info Yes No Cycle power to the
only) Readback flowmeter. If the problem
function from persists, contact Micro
transmitter Motion customer service.
display indicates
error or failure.

214 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Table 22-4 Electronics alarms continued

Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
A130 Printer Out of (Custody transfer Ignore Yes No Add paper to the printer.
Paper only) The ticket
printer is out of
paper.
A134 PPI Memory Memory or Info Yes No Cycle power to the
Error checksum error flowmeter. If the problem
in transmitter persists, contact Micro
display. Motion customer service.
A135 PPI Comm Error Internal Info Yes No Cycle power to the

Diagnostics and Troubleshooting


communication flowmeter. If the problem
error with persists, contact Micro
transmitter Motion customer service.
display.
(1) Applies only to systems with the standard core processor.
(2) Applies only to systems with the enhanced core processor.
(3) Applies only to systems with transmitter software earlier than rev7.0.

22.7.2 Sensor alarms


Table 22-5 lists all alarms in the Sensor category, with descriptions, suggested user actions, and
related information.

Table 22-5 Sensor alarms

Specifications – Model 3300/3500


Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
A003 Sensor Failure No tube vibration Fault Yes Yes Check the test points. See
detected at the Section 22.18.
sensor.
Check the sensor coils. See
Section 22.20.
Check wiring to sensor. See
Section 22.11.2.
Check for slug flow. See
Section 22.7.3.
Check sensor tubes.
Specifications – Model 3350/3700

Configuration and Use Manual 215


Diagnostics and Troubleshooting

Table 22-5 Sensor alarms continued

Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
A004 Temp. The measured Fault No Yes Check wiring to sensor. See
Out-of-Range temperature is Section 22.11.2.
outside the
Verify sensor configuration.
sensor limits.
See Section 7.3.3.
Check the test points. See
Section 22.18.
Check the sensor coils and
RTD. See Section 22.20.
Verify that process
temperature is within range
of sensor and transmitter.
Contact Micro Motion
customer service.
A016 Sensor RTD Error Sensor RTD has Fault Yes Yes Check wiring to sensor. See
failed. Section 22.11.2.
Make sure the appropriate
sensor type is configured.
See Section 7.3.3.
Check the test points. See
Section 22.18.
Check the sensor coils. See
Section 22.20.
Contact Micro Motion
customer service.
A017 Meter RTD Error Meter RTD has Fault Yes Yes Check wiring to sensor. See
failed. Section 22.11.2.
Make sure the appropriate
sensor type is configured.
See Section 7.3.3.
Contact Micro Motion
customer service.

22.7.3 Process alarms


Table 22-6 lists all alarms in the Process category, with descriptions, suggested user actions, and
related information. More information on specific process alarms is provided later in this section.

216 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Table 22-6 Process alarms

Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
A005 Mass Flow Mass flow value Fault Yes Yes Check the test points. See
Overrange is outside sensor Section 22.18.
limits.
Check the sensor coils. See
Section 22.20.
Verify process.
Make sure that the
appropriate measurement
unit is configured. See

Diagnostics and Troubleshooting


Section 22.13.
Verify 4 mA and 20 mA
values. See Section 22.14.
Verify calibration factors in
transmitter configuration.
See Section 22.17.
Re-zero the transmitter.
A008 Density Density value is Fault Yes Yes Check the test points. See
Out-of-Range outside sensor Section 22.18.
limits.
If accompanied by an A003
alarm, check the sensor
coils. See Section 22.20.
Verify process. Check for air
in the flow tubes, tubes not
filled, foreign material in

Specifications – Model 3300/3500


tubes, or coating in tubes.
Verify calibration factors in
transmitter configuration.
See Section 22.17.
Perform density calibration.
See Section 21.5.
A010 Calibration Calibration Fault No No Ensure that there is no flow
Failure procedure failed through the sensor. Check
for any of a for pipe stress at sensor.
variety of Then retry. See Calibration
reasons. alarms.
Cycle power to the
flowmeter, then retry. See
Calibration alarms.
A011 Cal Fail - Too Low Calibration Fault Yes No Ensure that there is no flow
procedure failed through the sensor. Check
Specifications – Model 3350/3700

due to reverse for pipe stress at sensor.


flow through the Then retry. See Calibration
sensor. alarms.
Cycle power to the
flowmeter, then retry. See
Calibration alarms.

Configuration and Use Manual 217


Diagnostics and Troubleshooting

Table 22-6 Process alarms continued

Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
A012 Cal Fail - Too Calibration Fault Yes No Ensure that there is no flow
High procedure failed through the sensor. Check
due to flow for pipe stress at sensor.
through the Then retry. See Calibration
sensor. alarms.
Cycle power to the
flowmeter, then retry. See
Calibration alarms.
A013 Cal Fail - Too Calibration Fault Yes No Ensure that there is no flow
Noisy procedure failed through the sensor. Check
due to flow for electromechanical noise.
through the Sources of noise include:
sensor. • Mechanical pumps
• Pipe stress at sensor
• Electrical interference
• Vibration effects from
nearby machinery
Then retry. See Calibration
alarms.
Cycle power to the
flowmeter, then retry. See
Calibration alarms.
A033(1) Tube Not Full No signal from Fault Yes Yes Verify process. Check for air
LPO or RPO, in the flow tubes, tubes not
suggesting that filled, foreign material in
sensor tubes are tubes, or coating in tubes.
not vibrating.
A100 mA 1 Saturated Process variable Info Yes(2) No See Output saturation
assigned to alarms.
primary mA
output is outside
configured limits.
A102 Drive Overrange No tube vibration Info Yes No Ensure that sensor tubes are
or erratic tube unobstructed. Purge tubes if
vibration. necessary.
Ensure sensor is full of
process fluid.
Ensure sensor is free to
vibrate.
Verify sensor configuration.
See Section 7.3.3.
Ensure that flow rate is within
sensor limits.
A105 Slug Flow Slug flow Info Yes No See Slug flow alarms.
detected in
process.
A110 Freq. Out Process variable Info Yes(2) No See Output saturation
Saturated assigned to alarms.
frequency output
is outside
configured scale
limits.

218 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Table 22-6 Process alarms continued

Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
(2)
A113 mA 2 Saturated Process variable Info Yes No See Output saturation
assigned to alarms.
secondary mA
output is outside
configured limits.
A115 External Input HART polling Info Yes No Ensure that external device
Error connection to is available:
external device • Verify device operation.
has failed. • Verify wiring.

Diagnostics and Troubleshooting


Verify polling configuration.
See Section 7.6.
A116 API: Temp Process Info Yes No Verify process.
Overrange temperature
Verify API reference table
outside
and temperature
API-defined
configuration. See
extrapolation
Section 9.4.
limits.
A117 API: Dens Process density Info Yes No Verify process.
Overrange outside
Verify API reference table
API-defined
and density configuration.
extrapolation
See Section 9.4.
limits.
A121 ED: Extrap. Fail Enhanced Info Yes No Verify process temperature.
density
Verify process density.
calculations are
outside the Verify enhanced density

Specifications – Model 3300/3500


configured data configuration. See the
range. enhanced density manual.
A124 Freq. Input Frequency input Info Yes No Reconfigure frequency
Saturated from external scaling on input device.
device is too
Reconfigure frequency
high.
scaling on Series 3000
platform. See Section 7.4.
A125 Batcher Timeout No flow detected Info Yes No See Batch alarms.
during configured
timeout period.
A126 Batcher Overrun The batcher has Info Yes No See Output saturation
overrun the alarms.
configured target.
(1) Applies only to systems with the enhanced core processor.
(2) Can be set to either Info or Ignore, but cannot be set to Fault.
Specifications – Model 3350/3700

Slug flow alarms


Slugs – for example, gas in a liquid process or liquid in a gas process – occasionally appear in some
applications. The presence of slugs can significantly affect the process density reading. Slug-flow
limits and duration can help the transmitter suppress extreme changes in reading.
Note: Default slug-flow limits are 0.0 and 5.0 g/cm3. Raising the low slug-flow limit or lowering the
high slug-flow limit will increase the possibility of slug flow conditions.

Configuration and Use Manual 219


Diagnostics and Troubleshooting

If slug limits have been configured, and slug flow occurs:


• A slug flow alarm is generated.
• All outputs that are configured to represent flow rate hold their last “pre-slug” value for the
configured slug-flow duration.
If the slug flow condition clears before the slug-flow duration expires:
• Outputs that represent flow rate revert to reporting actual flow.
• The slug flow alarm is deactivated, but remains in the active alarm log until it is
acknowledged.
If the slug flow condition does not clear before the slug-flow duration expires, outputs that represent
flow rate report a flow rate of zero.
If slug time is configured for 0.0 seconds, outputs that represent flow rate will report zero flow as
soon as slug flow is detected.
If slug flow occurs:
• Check process for cavitation, flashing, or leaks.
• Change the sensor orientation.
• Monitor density.
• If desired, enter new slug flow limits (see Section 7.3.2).
• If desired, increase slug duration (see Section 7.3.2).

Output saturation alarms


If an output variable exceeds the upper range limit or goes below the lower range limit, the
Series 3000 device produces an output saturation alarm. The alarm can mean:
• The output variable is outside appropriate limits for the process.
• The unit of flow needs to be changed.
• Sensor flow tubes are not filled with process fluid.
• Sensor flow tubes are plugged.
If an output saturation alarm occurs:
• Bring flow rate within sensor limit.
• Check the measurement unit. You may be able to use a smaller or larger unit.
• Check the sensor:
- Ensure that flow tubes are full.
- Purge flow tubes.
• For the mA outputs, change the 20 mA and 4 mA values (see Section 8.4.4).
• For the frequency output, change frequency and flow values, pulses/unit, or units/pulse (see
Section 8.5).

Batch alarms
If the batch controller is operating, the Series 3000 device produces batch alarms. Table 22-7
summarizes batch alarms and lists corrective actions.

220 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Table 22-7 Using batch alarms

Alarm message Cause Action


Time Out No flow was detected for the number of • Check valves, piping, and pumps for proper operation
seconds configured for time out • Check flow source configuration.
• Increase number of seconds for time out. See
Section 11.5.
• After cause has been diagnosed, press END to end
batch or RESUME to resume batch.
• If you are using a Model 3300 or Model 3350, verify
that the controller is receiving frequency input from the
remote transmitter.
Overrun • Batch total has exceeded target • End batch if required.
• Batch has not ended • Check wiring for discrete output indicating overrun.
• Flow is still being measured • Check device connected to discrete output indicating

Diagnostics and Troubleshooting


overrun.
• Enable batch AOC. See Section 11.5.
• Increase quantity configured for overrun.
• Verify that low-flow cutoff is correctly configured for
process conditions.
• Re-zero flowmeter.
• After cause has been diagnosed, press RESET or
START to start new batch.
Start Without Reset Operator attempted to start batch • Press RESET, then press START or
without pressing RESET • Set Reset on start option to Yes. See Section 11.5.
Start Not OK Enable batch control option is set to Set Enable batch control option to Yes. See Section 11.5.
No
Batch flow source is not configured Configure batch flow source. See Section 11.4.
Control functions have not been Assign control functions such as primary valve,
assigned to discrete outputs secondary valve, or pump to discrete outputs. See
Section 8.3.2).

Specifications – Model 3300/3500


An alarm is active Clear all alarm messages. See Section 22.6.
Discrete input is configured to inhibit Shut off discrete input.
batch
Target value is zero Change target value. See Section 11.6.
If enhanced density is enabled and an Configure batch preset for a valid enhanced density
enhanced density variable has been curve. See Section 11.6.
configured as the batch flow source, a
valid enhanced density curve has not
been assigned to the current preset
Output is fixed, calibration is in Correct the condition and retry.
progress, or slug flow has occurred

Calibration alarms
If a calibration procedure fails:
Specifications – Model 3350/3700

1. Ensure that there is no flow through the sensor.


2. Eliminate mechanical noise, if possible.
3. Ensure the interior of the sensor junction box (if present in your installation) is dry.
4. Retry the calibration procedure.

Configuration and Use Manual 221


Diagnostics and Troubleshooting

22.7.4 Configuration alarms


Table 22-8 lists all alarms in the Configuration category, with descriptions, suggested user actions,
and related information.

Table 22-8 Using configuration alarms

Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
A006 Characterize Master reset has Fault Yes No Enter required values. See
Meter been performed. Section 7.3.3.
Required
calibration values
are missing.
A020 Cal. Factors Master reset has Fault Yes No Enter required values. See
Missing been performed. Section 7.3.3.
Required
calibration values
are missing.
A021 Sensor Type K1 value missing Fault No No Verify characterization
Incorrect or incorrect, or parameters. See
RTD data from Section 7.3.3.
sensor is
incorrect.
A027 Security Breach (Custody transfer Fault No No Weights and Measures
only) Device has security seal has been
been tampered broken. Alarm can be
with. cleared by user, but
authorized procedure is
required to reestablish
security. Ensure that the
security switch is set to the
ON position. Contact Micro
Motion.
A032(1)(2) Meter Verify Fault Meter verification Fault No No Allow the procedure to
in progress, with complete. If desired, abort
outputs set to the procedure and restart
fault. with outputs set to last
measured value.
A032(3) Outputs Fixed Meter verification Varies(4) Allow the procedure to
in progress, with complete.
outputs set to If desired, abort the
Fault or Last procedure and restart with
Measured Value. outputs set to Continue
Measurement.
A034(3) Meter Verify The test ran to Info Yes No Rerun the test. If the test fails
Failed completion but again, see Section 21.3.4.
the results were
not within limits.
A035(3) Meter Verify The test did not Info Yes No If desired, read the abort
Aborted run to code, see Section 21.3.4,
completion. and perform the appropriate
action.

222 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Table 22-8 Using configuration alarms continued

Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
(5)
A101 mA 1 Fixed Primary mA Info Yes No Change Loop Current Mode
output is parameter. See
transmitting fixed Section 22.11.7.
output level.
Exit from mA output trim.
See Section 16.5.
Exit from mA output
simulation. See
Section 16.4.4.
Check to see if the output

Diagnostics and Troubleshooting


has been fixed via digital
communication.
A104 Cal in Progress Transmitter Info Yes(5) No No action required.
currently
performing flow
or density
calibration.
A106 Burst Enabled Transmitter Info Yes(5) No No action required.
configured for
burst mode.
A111 Freq. Output Frequency output Info Yes(5) No Exit from frequency output
Fixed is transmitting simulation. See
fixed output level. Section 16.4.2.
A114 mA 2 Fixed Secondary mA Info Yes(5) No Exit from mA output trim.
output is See Section 16.5.
transmitting fixed

Specifications – Model 3300/3500


output level. Exit from mA output
simulation. See
Section 16.4.4.
Check to see if the output
has been fixed via digital
communication.
A118 DO 1 Fixed Discrete output 1 Info Yes(5) No Unfix discrete output 1. See
transmitting fixed Section 16.4.1.
output.
A119 DO 2 Fixed Discrete output 2 Info Yes(5) No Unfix discrete output 2. See
transmitting fixed Section 16.4.1.
output.
A120 ED: Curve Fit Fail Configured Info No No Verify enhanced density
values for density configuration. See the
curves do not enhanced density manual.
meet accuracy
Specifications – Model 3350/3700

requirements.
A122 DO 3 Fixed Discrete output 3 Info Yes(5) No Unfix discrete output 3.
transmitting fixed SeeSection 16.4.1.
output.
A127 Batcher Needs Tried to start a Info Yes No See Section 22.7.3.
Reset batch without
resetting
previous batch.
A128 Batcher Cannot Transmitter Info Yes No See Section 22.7.3.
Start cannot start a
batch.

Configuration and Use Manual 223


Diagnostics and Troubleshooting

Table 22-8 Using configuration alarms continued

Alarm severity
Affected
Alarm Maintenance User by fault
number menu listing Description Default config? timeout User actions
(1)(2)
A131 Meter Verify Hold Meter verification Info Yes No Allow the procedure to
LMV in progress, with complete. If desired, abort
outputs set to last the procedure and restart
measured value. with outputs set to fault.
A131(3) Meter Verify Meter verification Info Yes No Allow the procedure to
Progress in progress, with complete.
outputs set to
continue
reporting process
data.
A132(1) Simulation Mode Simulation mode Info Yes(5) No Disable simulation mode.
is active. See Section 22.4.
(1) Applies only to systems with the enhanced core processor.
(2) Applies only to systems with the original version of the meter verification application.
(3) Applies only to systems with Smart Meter Verification.
(4) If outputs are set to Last Measured Value, severity is Info. If outputs are set to Fault, severity is Fault.
(5) Can be set to either Info or Ignore, but cannot be set to Fault.

22.8 Restoring a working configuration


At times it may be easier to start from a known working configuration than to troubleshoot the
existing configuration. To do this, you can:
• Restore a configuration file saved via ProLink II, if one is available. See Figure G-1.
• Restore the factory configuration, as stored in the Series 3000 device (no external
configuration file is required). To do this:
- Using ProLink II, see Figure G-2. ProLink II v2.6 or higher is required.
- Using the Communicator, see Figure H-3.
Both of these actions will overwrite the existing configuration. Ensure that the existing configuration
is appropriately documented or saved.

22.9 A009/A026 alarms on Model 3300 or Model 3500 panel-mount


On Model 3300 or Model 3500 panel-mount devices rev6.1 or lower, when the custody transfer
application is installed, A009 and A026 alarms may be generated if the position of the security switch
is changed while the device is powered.
Note: These alarms occur because to change the position of the security switch, you must remove the
connector wiring bracket, which means that power to the core processor will be interrupted.
To clear these alarms, you must change the core processor address manually to the default value of 1
while the transmitter is unsecured. Then, when the transmitter is secured, the core processor address
will automatically be changed to the unique address used for secure processing.
To change the core processor address manually:
1. Disconnect the RS-485 wires from the RS-485 terminals on the Series 3000 device (see
Figure 2-3).
2. Connect ProLink II to the RS-485 wires, or to the RS-485 terminals on the core processor,
using Modbus RTU (8-bit) protocol and any values for baud rate, parity, and stop bit.

224 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
3. Poll to make a connection to the core processor.
4. When the core processor is found, click ProLink > Configuration > Device and set the
Modbus address to 1.
5. Click Apply.
6. Disconnect ProLink II.
7. Reconnect the RS-485 wiring between the Series 3000 device and the core processor.
To avoid this problem, always power down the transmitter before removing the connector wiring
bracket.
Note: Do not confuse the Modbus address of the core processor with the Modbus address of the
transmitter. The Modbus address of the core processor is accessible only when you connect directly to
the core processor.

Diagnostics and Troubleshooting


22.10 I/O problems
If you are experiencing problems with I/O, use Table 22-9 to identify an appropriate remedy.

Table 22-9 I/O problems and remedies

Symptom Possible cause Possible remedy


No mA output and Power supply problem Check power supply and power-supply wiring.
no frequency output or loop See Section 22.11.
test failed
Fault condition present if fault Check the fault indicator settings to verify
indicators are set to downscale or whether or not the transmitter is in a fault
internal zero condition. See Section 8.4.2 to check the mA
fault indicator or Section 8.5 to check the
frequency fault indicator.

Specifications – Model 3300/3500


If a fault condition is present, see Section 22.7.
mA output < 4 mA Process condition below value Verify process.
configured for 4 mA Verify or change the 4 mA value. See
Section 8.4.4.
Fault condition if fault indicator is set to Check the fault indicator settings to verify
internal zero whether or not the transmitter is in a fault
condition. See Section 8.4.2.
If a fault condition is present, check the active
alarm log. See Section 22.6.
Open in wiring Verify all connections.
Bad mA receiving device Check the mA receiving device or try another
mA receiving device. See Section 22.11.6.
Bad output circuit Measure DC voltage across output to verify that
output is active.
Test output. See Section 16.4.4.
Specifications – Model 3350/3700

Configuration and Use Manual 225


Diagnostics and Troubleshooting

Table 22-9 I/O problems and remedies continued

Symptom Possible cause Possible remedy


No frequency output Process condition below cutoff Verify or change the cutoff. See Section 8.4.4.
Fault condition if fault indicator is set to Check the fault indicator settings to verify
downscale or internal zero whether or not the transmitter is in a fault
condition. See Section 8.5.
If a fault condition is present, check the active
alarm log. See Section 22.6.
Slug flow See Slug flow alarms in Section 22.7.3.
Flow in reverse direction from Verify process.
configured flow direction parameter Check flow direction parameter. See
Section 7.3.2.
Verify sensor orientation. Ensure that flow
direction arrow on sensor case matches process
flow.
Bad frequency receiving device Check the frequency receiving device or try
another frequency receiving device. See
Section 22.11.6.
Output level not compatible with Verify that the output level and the required
receiving device receiving input level are compatible.
Bad output circuit Test output. See Section 16.4.4.
Incorrect pulse width configuration Verify pulse width setting. See Section 8.5.2.
Internal totalizer stopped and not Restart internal totalizer.
restarted
Output is configured for passive power Ensure output power is set to active. See
Section 8.5.
Constant mA output Non-zero HART address (multi-drop Set HART address to zero. See Section 22.11.7.
communications) (primary mA output
only)
Output is fixed in a test mode Exit output from test mode. See Section 16.4.4.
Burst mode enabled (primary mA Disable burst mode. See Section 13.4.
output only)
Zero calibration failure See Section 22.17.
mA output consistently out of Fault condition if fault indicator is set to Check the fault indicator settings to verify
range upscale or downscale whether or not the transmitter is in a fault
condition. See Section 8.4.2.
If a fault condition is present, check the active
alarm log. See Section 22.6.
20 mA and 4 mA values not set Check the 20 mA and 4 mA values. See
correctly Section 22.14.
Consistently incorrect mA Output not trimmed correctly Trim the output. See Section 16.5.
measurement
Incorrect flow measurement unit Verify flow measurement unit configuration. See
configured Section 22.13.
Incorrect process variable configured Verify process variable assigned to mA output.
See Section 8.4.3.
20 mA and 4 mA values not set Check the 20 mA and 4 mA values. See
correctly Section 22.14.
mA reading correct at low mA loop resistance may be too high Verify mA output load resistance is below
currents but wrong at higher maximum supported load.
currents

226 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Table 22-9 I/O problems and remedies continued

Symptom Possible cause Possible remedy


Consistently incorrect Output not scaled correctly Check frequency output scale and method. See
frequency measurement Section 22.15. Verify that voltage and resistance
match the frequency output load resistance
value chart.
Incorrect flow measurement unit Verify flow measurement unit configuration. See
configured Section 22.13.
Erratic frequency RF (radio frequency) interference from See Section 22.11.5.
measurement when flow is environment
stable
Cannot connect to RS-485 Terminals not in service port mode Terminals are accessible in service port mode
terminals in service port ONLY for a 10-second interval after power-up.
mode Cycle power and connect during this interval.

Diagnostics and Troubleshooting


Leads reversed Switch leads and try again.
Transmitter installed on multidrop All Series 3000 devices on network default to
network address=111 during 10-second service port
interval. Disconnect or power down other
devices, or use RS-485 communications.
Device is secured (custody transfer Change Series 3000 device to unsecured, or
only) use RS-485 communications.
Cannot connect to RS-485 Terminals not in RS-485 mode For the first 10 seconds after power-up, the
terminals in RS-485 mode terminals are in service port mode. If a service
port connection is made during this period, they
remain in service port mode. Wait until
10-second interval has expired, cycle power to
the device to reset the terminals if required, or
connect in service port mode.
Incorrect RS-485 configuration After 10-second interval on power-up, the

Specifications – Model 3300/3500


transmitter switches to RS-485 mode. Default
settings are:
• Address=1
• Baud rate=9600
• Parity=odd
Use the display to check or change the RS-485
settings (see Section 13.3), then set parameters
appropriately in the remote device.
Leads reversed Switch leads and try again.

22.11 Diagnosing wiring problems


Use the procedures in this section to check the transmitter installation for wiring problems.

22.11.1 Checking the power supply wiring


Specifications – Model 3350/3700

To check the power supply wiring:


1. Verify that the correct external fuse is used. An incorrect fuse can limit current to the
transmitter and keep it from initializing.
2. Power down the transmitter. If the transmitter is in a hazardous area, wait five minutes.
3. Ensure that the power supply wires are connected to the correct terminals. See the installation
instructions.
4. Verify that the power supply wires are making good contact, and are not clamped to the wire
insulation.

Configuration and Use Manual 227


Diagnostics and Troubleshooting

5. Use a voltmeter to test the voltage at the transmitter’s power-supply terminals. Verify that it is
within the specified limits (see Appendix A or Appendix B).

22.11.2 Checking the sensor-to-transmitter wiring


To check the sensor-to-transmitter wiring, verify that:
• The transmitter is connected to the sensor according to the wiring information provided in the
installation instructions.
• The wires are making good contact with the terminals.
If the wires are incorrectly connected:
1. Power down the transmitter.
2. If the transmitter is in a hazardous area, wait five minutes.
3. Correct the wiring.
4. Restore power to the transmitter.

22.11.3 Checking grounding


The Series 3000 device must be grounded. If you are using a T-Series sensor, it must be grounded. If
the core processor is installed separately, it must be grounded separately. See the installation
instructions.

22.11.4 Checking the HART communication loop


To check the HART communication loop (primary mA output only):
1. Verify that the loop wires are connected correctly for HART/analog wiring.
2. Remove analog loop wiring.
3. Install a 250  resistor across the primary mA output terminals.
4. Check for voltage drop across the resistor (4–20 mA = 1–5 VDC). If voltage drop < 1 VDC,
add resistance to achieve voltage drop > 1 VDC.
5. Connect the Communicator directly across the resistor and attempt to communicate (poll).

22.11.5 Checking for RF interference


If you are experiencing RF (radio frequency) interference on your frequency output or discrete output,
use one of the following solutions:
• Eliminate the RF source. Possible causes include a source of radio communications, or a large
transformer, pump, motor, or anything else that can generate a strong electrical or
electromagnetic field, in the vicinity of the transmitter.
• Move the transmitter.
• Use shielded cable for the frequency output.
- Terminate output cable shielding at the input device. If this is not possible, terminate the
output shielding at the cable gland or conduit fitting.
- Do not terminate shield inside the wiring compartment.
- 360° termination of shielding is not necessary.

228 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
22.11.6 Checking the output wiring and receiving device
If you receive an inaccurate frequency or mA reading, there may be a problem with the output wiring
or the receiving device.
• Check the output level at the transmitter.
• Check the wiring between the transmitter and the receiving device.
• Try a different receiving device.

22.11.7 Checking the Loop Current Mode parameter


Depending on the setting of the Loop Current Mode parameter, the primary mA output may be fixed
at 4 mA. In this situation:
• The primary mA output will not report process variable data.

Diagnostics and Troubleshooting


• The primary mA output will not indicate fault conditions.
See Section 13.4.1.

22.12 Checking the sensor tubes


Corrosion, erosion, or damage to the sensor tubes can affect process measurement. To check for these
conditions, perform the meter verification procedure, if available (see Chapter 21). If the meter
verification procedure is not available, perform a visual inspection, or perform a density calibration
and check for a shift in the K1 and K2 values. Contact Micro Motion customer service.

22.13 Checking the flow measurement unit


Using an incorrect flow measurement unit can cause the transmitter to produce unexpected output

Specifications – Model 3300/3500


levels, with unpredictable effects on the process. Make sure that the configured flow measurement
unit is correct. Check the abbreviations; for example, g/min represents grams per minute, not gallons
per minute. See Section 7.3.2.

22.14 Checking the calibration span


A saturated mA output or incorrect mA measurement could indicate that an incorrect 4 mA or 20 mA
value has been configured for the mA output. Verify that these values are correct and change them if
necessary. See Section 8.4.4.

22.15 Checking the frequency output scale and method


A saturated frequency output or an incorrect frequency measurement could indicate a faulty frequency
output scale and/or method. Verify that the frequency output scale and method are correct and change
Specifications – Model 3350/3700

them if necessary. See Section 8.5.

22.16 Checking the characterization


A transmitter that is incorrectly characterized for its sensor might produce inaccurate output values. If
the flowmeter appears to be operating correctly but sends inaccurate output values, an incorrect
characterization could be the cause. See Section 7.3.3.

Configuration and Use Manual 229


Diagnostics and Troubleshooting

22.17 Checking the calibration


Improper calibration can cause the transmitter to send unexpected output values. If the transmitter
appears to be operating correctly but sends inaccurate output values, an improper calibration may be
the cause.
Micro Motion calibrates every transmitter at the factory. Therefore, you should suspect improper
calibration only if the transmitter has been calibrated after it was shipped from the factory.
The calibration procedures in this manual are designed for calibration to a regulatory standard. To
calibrate for true accuracy, always use a measurement source that is more accurate than the flowmeter.
If there is significant discrepancy (>20%) between process data and the transmitter’s reported values,
do not attempt to recalibrate. Contact Micro Motion customer service for assistance.
Note: Micro Motion recommends using meter factors, rather than calibration, to prove the meter
against a regulatory standard or to correct measurement error. Contact Micro Motion before
calibrating your flowmeter. For information on meter performance verification, see Chapter 21.

22.18 Checking the test points


Some status alarms that indicate a sensor failure or overrange condition can be caused by problems
other than a failed sensor. You can diagnose sensor failure or overrange status alarms by checking the
flowmeter test points. These values describe the current operation of the sensor.

22.18.1 Obtaining the test points


To obtain current values for test points, use the Diagnostic Monitor, which is accessed from the View
menu. The Diagnostic Monitor displays:
• Tube frequency
• Left pickoff
• Right pickoff
• Drive gain
• Live zero
Note: The Diagnostic Monitor is not the same as the Diagnostics menu. The Diagnostics menu,
accessed through the Maintenance option of the Management menu, allows you to read the values of
external inputs and set output levels for outputs. The Diagnostics menu and its use are described in
Chapter 16.

22.18.2 Evaluating the test points


Use the following guidelines to evaluate the test points:
• If the drive gain is unstable, refer to Section 22.18.3.
• If the value for the left or right pickoff does not equal the appropriate value from Table 22-10,
based on the sensor flow tube frequency, refer to Section 22.18.5.
• If the values for the left and right pickoffs equal the appropriate values from Table 22-10,
based on the sensor flow tube frequency, record your troubleshooting data and contact Micro
Motion customer service for assistance.

230 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Table 22-10 Sensor pickoff values

Sensor model(1) Pickoff value


ELITE Model CMF sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency
Model D, DL, and DT sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency
Model F025, F050, F100 sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency
Model F200 sensors (compact case) 2.0 mV peak-to-peak per Hz based on sensor flow tube frequency
Model F200 sensors (standard case) 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency
Model H025, H050, H100 sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency
Model H200 sensors 2.0 mV peak-to-peak per Hz based on sensor flow tube frequency
Model R025, R050, or R100 sensors 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency
Model R200 sensors 2.0 mV peak-to-peak per Hz based on sensor flow tube frequency

Diagnostics and Troubleshooting


Micro Motion T-Series sensors 0.5 mV peak-to-peak per Hz based on sensor flow tube frequency
CMF400 I.S. sensors 2.7 mV peak-to-peak per Hz based on sensor flow tube frequency
CMF400 sensors with booster amplifiers 3.4 mV peak-to-peak per Hz based on sensor flow tube frequency
(1) If your sensor is not listed, contact Micro Motion.

22.18.3 Excessive drive gain


Excessive drive gain can be caused by several problems. See Table 22-11.

Table 22-11 Excessive drive gain causes and remedies

Cause Possible remedy


Excessive slug flow Eliminate slugs.

Specifications – Model 3300/3500


Change the sensor orientation.
Plugged flow tube Purge the flow tubes.
Cavitation or flashing Increase inlet or back pressure at the sensor.
If a pump is located upstream from the sensor, increase the distance
between the pump and sensor.
Overpressurized tubes Contact Micro Motion.
Drive board or module failure, cracked flow tube, Contact Micro Motion.
or sensor imbalance
Mechanical binding at sensor Ensure sensor is free to vibrate.
Open drive or left pickoff sensor coil Contact Micro Motion.
Incorrect sensor characterization Verify sensor configuration. See Section 22.16.
Specifications – Model 3350/3700

22.18.4 Erratic drive gain


Erratic drive gain can be caused by several problems. See Table 22-12.

Configuration and Use Manual 231


Diagnostics and Troubleshooting

Table 22-12 Erratic drive gain causes and remedies

Cause Possible remedy


Wrong K1 characterization constant for sensor Re-enter the K1 characterization constant. See
Section 7.3.3.
Polarity of pick-off reversed or polarity of drive reversed Contact Micro Motion.
Slug flow Verify flow tubes are completely full of process fluid.
Foreign material caught in flow tubes Purge flow tubes.

22.18.5 Low pickoff voltage


Low pickoff voltage can be caused by several problems. See Table 22-13.

Table 22-13 Low pickoff voltage causes and remedies

Cause Possible remedy


Faulty wiring runs between the sensor and core processor Verify wiring. See Section 22.11.2.
Process flow rate beyond the limits of the sensor Verify that the process flow rate is not out of range of the
sensor.
Slug flow Verify flow tubes are completely full of process fluid.
No tube vibration in sensor Check for plugging.
Verify power to transmitter.
Ensure sensor is free to vibrate (no mechanical binding).
Verify wiring. See Section 22.11.2.
Test coils at sensor. See Section 22.20.
Moisture in the sensor electronics Eliminate the moisture in the sensor electronics.
The sensor is damaged Contact Micro Motion.

22.19 Checking the core processor


Two core processor procedures are available:
• You can check the core processor LED. The core processor has an LED that indicates different
flowmeter conditions. See Table 22-14.
• If an A026 alarm is present, you can perform the core processor resistance test to check for a
damaged core processor.

22.19.1 Checking the core processor LED


To check the core processor LED:
1. Maintain power to the transmitter.
2. Remove the core processor lid. The core processor is instrinsically safe and can be opened in
all environments. Do not disconnect the 4-wire cable between the core processor and the
transmitter.
3. Check the core processor LED against the conditions described in Table 22-14 (standard core
processor) or Table 22-15 (enhanced core processor).
4. To return to normal operation, replace the lid.
Note: When reassembling the meter components, be sure to grease all O-rings.

232 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Table 22-14 Standard core processor LED behavior, flowmeter conditions, and remedies

LED behavior Condition Possible remedy


1 flash per second Normal operation No action required.
(ON 25%, OFF 75%)
1 flash per second Slug flow See Section 22.7.3.
(ON 75%, OFF 25%)
Solid ON Zero or calibration in If calibration is in progress, no action required. If no calibration is in
progress progress, contact Micro Motion.
Core processor Check power supply to transmitter.
receiving between 11.5
and 5 volts
3 rapid flashes, Sensor not recognized Check wiring between transmitter and sensor. See Section 22.11.2.
followed by pause

Diagnostics and Troubleshooting


Improper configuration Check sensor characterization parameters. See Section 22.16.
Broken pin between Contact Micro Motion.
sensor and core
processor
4 flashes per second Fault condition Check alarm status. See Section 22.6.
OFF Core processor • Verify power supply wiring to core processor. See Section 22.11.2.
receiving less than 5 • If transmitter display is lit, transmitter is receiving power. Check
volts voltage across terminals 1 (VDC+) and 2 (VDC–) in core processor.
Normal reading is approximately 14 VDC. If reading is normal,
internal core processor failure is possible. Contact Micro Motion. If
reading is 0, internal transmitter failure is possible. Remove the wires
from core processor terminals 1 and 2, and check the voltage across
the wires. If the voltage reading is now ~14 VDC, the transmitter is
normal. If the voltage reading is not ~14 VDC, contact Micro Motion.
If reading is less than 1 VDC, verify power supply wiring to core
processor. Wires may be switched. See Section 22.11.2.
• If transmitter display is not lit, transmitter is not receiving power.

Specifications – Model 3300/3500


Check power supply. If power supply is operational, internal
transmitter or display failure is possible. Contact Micro Motion.
Core processor Contact Micro Motion.
internal failure

Table 22-15 Enhanced core processor LED behavior, flowmeter conditions, and remedies

LED behavior Condition Possible remedy


Solid green Normal operation No action required.
Flashing yellow Zero in progress If calibration is in progress, no action required. If no calibration is in
progress, contact Micro Motion.
Solid yellow Low severity alarm Check alarm status.
Solid red High severity alarm Check alarm status.
Specifications – Model 3350/3700

Flashing red (80% on, Tubes not full If alarm A105 (slug flow) is active, see Slug flow alarms in
20% off) Section 22.7.3.
If alarm A033 (tubes not full) is active, verify process. Check for air in
the flow tubes, tubes not filled, foreign material in tubes, or coating in
tubes.
Flashing red (50% on, Electronics failed Contact Micro Motion.
50% off)

Configuration and Use Manual 233


Diagnostics and Troubleshooting

Table 22-15 Enhanced core processor LED behavior, flowmeter conditions, and remedies continued

LED behavior Condition Possible remedy


Flashing red (50% on, Sensor failed Contact Micro Motion.
50% off, skips every
4th)
OFF Core processor • Verify power supply wiring to core processor.
receiving less than 5 • If transmitter display is lit, transmitter is receiving power. Check
volts voltage across terminals 1 (VDC+) and 2 (VDC–) in core processor.
If reading is less than 1 VDC, verify power supply wiring to core
processor. Wires may be switched. See Section 22.11. Otherwise,
contact Micro Motion.
• If transmitter display is not lit, transmitter is not receiving power.
Check power supply. See Section 22.11. If power supply is
operational, internal transmitter, display, or LED failure is possible.
Contact Micro Motion.
Core processor Contact Micro Motion.
internal failure

22.19.2 Core processor resistance test (standard core processor only)


Note: Perform this test only if an A026 alarm is present.
To perform the core processor resistance test:
1. Power down the transmitter.
2. Remove the core processor lid.
3. Disconnect the 4-wire cable between the core processor and the transmitter.
4. Measure the resistance between core processor terminals 3 and 4 (RS-485/A and RS-485/B).
See Figure 22-6. Resistance should be 40 k to 50 k.
5. Measure the resistance between core processor terminals 2 and 3 (VDC– and RS-485/A).
Resistance should be 20 k to 25 k .
6. Measure the resistance between core processor terminals 2 and 4 (VDC– and RS-485/B).
Resistance should be 20 k to 25 k.
7. If any resistance measurements are lower than specified, the core processor may not be able to
communicate with a transmitter or a remote host. Contact Micro Motion customer service.
8. To return to normal operation:
a. Reconnect the 4-wire cable between the core processor and the transmitter.
b. Replace the core processor lid.
Note: When reassembling the meter components, be sure to grease all O-rings.

234 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
Figure 22-6 Core processor resistance test

40 k – 50 k

20 k – 25 k

20 k – 25 k

Diagnostics and Troubleshooting


22.20 Checking sensor coils and RTD
Problems with sensor coils can cause several alarms, including sensor failure and a variety of
out-of-range conditions. Testing the sensor coils involves testing the terminal pairs and testing for
shorts to case.

22.20.1 Remote core processor with remote transmitter installation


If you have a remote core processor with remote transmitter installation:
1. Power down the transmitter.
2. If the transmitter is in a hazardous area, wait five minutes.

Specifications – Model 3300/3500


3. At the core processor:
a. Remove the end-cap.
b. Unplug the terminal blocks from the terminal board.
c. Using a digital multimeter (DMM), check the pickoff coils listed in Table 22-16 by
placing the DMM leads on the unplugged terminal blocks for each terminal pair. Record
the values.

Table 22-16 Coils and test terminal pairs

Coil Test terminal pair


Drive coil Brown to red
Left pickoff coil (LPO) Green to white
Specifications – Model 3350/3700

Right pickoff coil (RPO) Blue to gray


Resistance temperature detector (RTD) Yellow to violet
Lead length compensator (LLC) (all sensors except CMF400 I.S. and T-Series) Yellow to orange
Composite RTD (T-Series sensors only)
Fixed resistor (CMF400 I.S. sensors only)

4. There should be no open circuits, i.e., no infinite resistance readings. The LPO and RPO
readings should be the same or very close (±5 ). If there are any unusual readings, repeat the
coil resistance tests at the sensor junction box to eliminate the possibility of faulty cable. The
readings for each coil pair should match at both ends.

Configuration and Use Manual 235


Diagnostics and Troubleshooting

5. Leave the core processor terminal blocks disconnected. At the sensor, remove the lid of the
junction box and test each sensor terminal for a short to case by placing one DMM lead on the
terminal and the other lead on the sensor case. With the DMM set to its highest range, there
should be infinite resistance on each lead. If there is any resistance at all, there is a short to
case.
6. Test terminal pairs as follows:
a. Brown against all other terminals except Red
b. Red against all other terminals except Brown
c. Green against all other terminals except White
d. White against all other terminals except Green
e. Blue against all other terminals except Gray
f. Gray against all other terminals except Blue
g. Orange against all other terminals except Yellow and Violet
h. Yellow against all other terminals except Orange and Violet
i. Violet against all other terminals except Yellow and Orange
Note: D600 sensors and CMF400 sensors with booster amplifiers have different terminal pairs.
Contact Micro Motion customer service for assistance.
There should be infinite resistance for each pair. If there is any resistance at all, there is a short
between terminals. See Table 22-17 for possible causes and solutions.
7. If the problem is not resolved, contact Micro Motion customer service for assistance.
8. To return to normal operation:
a. Plug the terminal blocks into the terminal board.
b. Replace the end-cap on the core processor housing.
c. Replace the lid on the sensor junction box.
Note: When reassembling the meter components, be sure to grease all O-rings.

Table 22-17 Sensor and cable short to case possible causes and remedies

Possible cause Solution


Moisture inside the sensor junction box Make sure that the junction box is dry and no corrosion is present.
Liquid or moisture inside the sensor case Contact Micro Motion.
Internally shorted feedthrough (sealed passage Contact Micro Motion.
for wiring from sensor to sensor junction box)
Faulty cable Replace cable.
Improper wire termination Verify wire terminations inside sensor junction box. See Micro
Motion’s 9-Wire Flowmeter Cable Preparation and Installation Guide
or the sensor manual.

22.20.2 4-wire remote installation


If you have a 4-wire remote installation:
1. Power down the transmitter.
2. If the transmitter is in a hazardous area, wait five minutes.
3. Remove the core processor lid.

236 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
4. Disconnect the wires from the core processor terminals.
5. If you have a standard core processor – Loosen the captive screw (2.5 mm) in the center of the
core processor. Carefully remove the core processor from the sensor by grasping it and lifting
it straight up. Do not twist or rotate the core processor.
6. If you have an enhanced core processor – Loosen the two captive screws (2.5 mm) that hold
the core processor in the housing. Gently lift the core processor out of the housing, then
disconnect the sensor cable from the feedthrough pins by removing the snap clip and pulling
the plug straight out.

CAUTION
If the core processor (feedthrough) pins are bent, broken, or damaged in any
way, the core processor will not operate.

Diagnostics and Troubleshooting


To avoid damage to the core processor pins:

• Do not twist or rotate the core processor when lifting it.


• When replacing the core processor on the pins, be sure to align the guide pins
and mount the core processor carefully.

7. Using a digital multimeter (DMM), check the pickoff coil resistances by placing the DMM
leads on the pin pairs. Refer to Figure 22-7 (standard core processor) or Figure 22-8 (enhanced
core processor) to identify the pins and pin pairs. Record the values.

Figure 22-7 Sensor pins – Standard core processor

Right pickoff –

Specifications – Model 3300/3500


LLC / Composite RTD /
Fixed resistor(1) Right pickoff +

Left pickoff –

RTD –

Left pickoff +

RTD +
Drive –
Drive + Specifications – Model 3350/3700

(1) Functions as fixed resistor for the following sensors: F300, H300, F025A, F050A, F100A, CMF400 I.S., CMFS. Functions
as composite RTD for T-Series sensors. For all other sensors, functions as lead length compensator (LLC).

Configuration and Use Manual 237


Diagnostics and Troubleshooting

Figure 22-8 Sensor pins – Enhanced core processor


Drive – Drive +

RTD –
LLC / Composite RTD /
Fixed resistor(1)

RTD +

Left pickoff – Right pickoff +

Left pickoff +
Right pickoff –

(1) Functions as fixed resistor for the following sensors: F300, H300, F025A, F050A, F100A, CMF400 I.S., CMFS. Functions
as composite RTD for T-Series sensors. For all other sensors, functions as lead length compensator (LLC).

8. There should be no open circuits, i.e., no infinite resistance readings. The LPO and RPO
readings should be the same or very close (±5 ).
9. Using the DMM, check between each pin and the sensor case. With the DMM set to its highest
range, there should be infinite resistance on each lead. If there is any resistance at all, there is a
short to case. See Table 22-17 for possible causes and solutions.
10. Test terminal pairs as follows:
a. Drive + against all other terminals except Drive –
b. Drive – against all other terminals except Drive +
c. Left pickoff + against all other terminals except Left pickoff –
d. Left pickoff – against all other terminals except Left pickoff +
e. Right pickoff + against all other terminals except Right pickoff –
f. Right pickoff – against all other terminals except Right pickoff +
g. RTD + against all other terminals except LLC + and RTD/LLC
h. LLC + against all other terminals except RTD + and RTD/LLC
i. RTD/LLC against all other terminals except LLC + and RTD +
Note: D600 sensors and CMF400 sensors with booster amplifiers have different terminal pairs.
Contact Micro Motion customer service for assistance.
There should be infinite resistance for each pair. If there is any resistance at all, there is a short
between terminals. See Table 22-17 for possible causes and solutions.
11. If the problem is not resolved, contact Micro Motion customer service for assistance.
To return to normal operation:

238 Micro Motion® Series 3000 MVD Transmitters and Controllers


Diagnostics and Troubleshooting

Measurement Performance
1. If you have a standard core processor:
a. Align the three guide pins on the bottom of the core processor with the corresponding
holes in the base of the core processor housing.
b. Carefully mount the core processor on the pins, taking care not to bend any pins.
2. If you have an enhanced core processor:
a. Plug the sensor cable onto the feedthrough pins.
b. Reinsert the snap clip to secure the sensor cable to the feedthrough.
c. Replace the core processor in the housing.
3. Tighten the captive screw(s) to 6 to 8 in-lbs (0,7 to 0,9 N-m) of torque.
4. Reconnect the wires to the core processor terminals.
5. Replace the core processor lid.

Diagnostics and Troubleshooting


Note: When reassembling the meter components, be sure to grease all O-rings.

Specifications – Model 3300/3500


Specifications – Model 3350/3700

Configuration and Use Manual 239


240 Micro Motion® Series 3000 MVD Transmitters and Controllers
Measurement Performance
Appendix A
Specifications – Model 3300 and Model 3500

A.1 Housing and mounting


There are two housing and mounting options available for the Model 3300 or Model 3500.

Diagnostics and Troubleshooting


A.1.1 Panel-mount
• With bezel mounting kit
• Front panel with bezel is rated IP65 (NEMA 4X)

A.1.2 Rack-mount
• 19-inch (486,2 mm) rack-mount meets DIN standard 41494 and IEC 297-3
• Front panel is rated IP40

A.2 Interface/display

Screen

Specifications – Model 3300/3500


• Backlit LCD, 128 x 128 pixel, bit map
• Adjustable contrast
• Non-glare chemical-resistant acrylic lens

Keypad membrane switch


• Large pushbuttons with tactile feedback
• Software-defined function keys
• Chemical-resistant polyester

A.3 Weight
Maximum 3.5 lb (1,6 kg), excluding prepared cables
Specifications – Model 3350/3700

A.4 Dimensions
Panel-mount: See Figures A-1 and A-2.
Rack-mount: See Figure A-3.
Core processor: See Figure A-4.

Configuration and Use Manual 241


Specifications – Model 3300 and Model 3500

Figure A-1 Panel-mount dimensions for Model 3300 or Model 3500 with screw-type connectors
inches
Dimensions in
(mm)

6 1/2
(165)

Panel 8 1/2
(216)
7 3/4
(197)

Frame
Bezel

4 1/2
6 (114)
(152)
6 11/16
(170)

6
(152) Approvals tag
Intrinsic safety barrier
(Model 3500 only)
1/2
(12)

242 Micro Motion® Series 3000 MVD Transmitters and Controllers


Specifications – Model 3300 and Model 3500

Measurement Performance
Figure A-2 Panel-mount dimensions for Model 3300 or Model 3500 with I/O cables
inches
Dimensions in
(mm)

6 1/2
(165)

Diagnostics and Troubleshooting


8 3/4
Panel (222)

Frame

Bezel

5 5/16
6 (135)
(152)
6 11/16
(170)

Specifications – Model 3300/3500


Approvals tag Minimum 4 1/4˝
6 (108 mm) bend radius
(152)

1/2
(12)

Specifications – Model 3350/3700

Configuration and Use Manual 243


Specifications – Model 3300 and Model 3500

Figure A-3 Rack-mount dimensions for Model 3300 or Model 3500


1 U = 1 HE = 1.750 inches (44,45 mm)
inches 1 HP = 1 TE = 0.200 inch (5,08 mm)
Dimensions in
(mm) 25 HP (25 TE)
4 x M2.5x11

3U
(3 HE)
5 1/16
(128,5)
4 13/16
(122,5)

5 9/16
(142,2)
28 HP (28 TE)
19-inch (486,2 mm) rack conforms to DIN 41494, Part 5, and IEC 297-3.
Not included with Model 3300 or Model 3500.

Optional screw terminal


Rear rail for mounting connectors
that conform to DIN 41612 and IEC 603-2.
Not included with Model 3300 or Model 3500.

Intrinsic safety shield


(Model 3500 only)

Approvals tag
6 11/16
1 (169,9)
(25,4)
7 11/32
(186,7)
7 29/32
(200,6)
8 33/64
(216,2)

244 Micro Motion® Series 3000 MVD Transmitters and Controllers


Specifications – Model 3300 and Model 3500

Measurement Performance
Figure A-4 Core processor dimensions

Ø4 3/8
inches (111)
Dimensions in
(mm)

5 11/16
(144)
2X 3
(76)

Diagnostics and Troubleshooting


2 1/4
(57)

2 5/8
(67)

6 3/16
(158) 4X Ø3/8
(10)
2 13/16
(71)

Specifications – Model 3300/3500


To centerline of 2” pipe

2 13/16
(71) 5 3/4
(146)
4 1/2 Pole Mount
(114)

4 9/16 1/2˝–14 NPT


2 1/2 OR
(116) (64)
Wall Mount M20 X 1.5
Note: These dimensions apply only to the 2 3/8
core processor component in remote core (61)
processor with remote transmitter 1 11/16
installations. (43)
Specifications – Model 3350/3700

3 5/16
(84)

3/4˝–14 NPT

Configuration and Use Manual 245


Specifications – Model 3300 and Model 3500

A.5 Electrical connections


Electrical connections depend on the mounting option.

A.5.1 Panel-mount

Input and output connections


• Available as screw terminals (standard) or remote DIN-rail-mount screw terminals (optional)
with I/O cable
• Remote terminals attach to any of four rail types. I/O cable is available in lengths of 2, 5, and
10 feet (0,6, 1,5, and 3 meters)
• Terminals accept 24 to 16 AWG (0,25 to 1,5 mm2) wires

Power connection
Screw terminals accept 18 to 14 AWG (0,75 to 2,5 mm2) wires

A.5.2 Rack-mount

Input and output connections


• Type D connectors per DIN standard 41612 (IEC 603-2)
• Available as solder tails (standard) or screw terminals (optional)
• Screw terminals accept 24 to 16 AWG (0,25 to 1,5 mm2) wires

Power connection
• Screw terminals are fixed to rack chassis
• Ground makes first and breaks last
• Terminals accept 18 to 14 AWG (0,75 to 2,5 mm2) wires

A.6 Inputs and outputs

A.6.1 Intrinsically safe input signals


One 4-wire Coriolis sensor signal input with ground (standard)

A.6.2 Non-intrinsically safe input signals

Frequency/pulse input
One 2-wire frequency/pulse input
• Frequency range: 0–20,000 Hz
• Minimum pulse width: 25 sec
• Power: Sourcing or sinking
• Voltage: 0–0.8 VDC low state, 3–30 VDC high state
• Current: Nominal 5 mA pull-up

246 Micro Motion® Series 3000 MVD Transmitters and Controllers


Specifications – Model 3300 and Model 3500

Measurement Performance
Discrete inputs
Two discrete, momentary inputs
• Pulse width: 0.15 sec minimum
• Voltage: 0–0.8 VDC low state, 3–30 VDC high state, dry contacts

A.6.3 Non-intrinsically safe output signals

Milliamp outputs
Two active 4–20 mA outputs
• Isolated to ±50 VDC from all other outputs and earth ground
• Maximum load limit: 1000 

Diagnostics and Troubleshooting


• Output is linear with process from 3.8 to 20.5 mA, per NAMUR NE43 (June 1994)

Discrete outputs
Three discrete outputs
• Configurable for the application
• Polarity: Active high or active low, software selectable
• Power: Internal pull-up to 24 V
• Voltage: 24 VDC nominal
• Current: Sourcing at 5.6 mA when Vout = 3 VCD, sinking up to 500 mA at 30 VDC maximum

Frequency/pulse output

Specifications – Model 3300/3500


One 2-wire frequency/pulse output
• Output is linear with flow rate to 12,500 Hz
• Configurable unit of measure
• Scalable to 10000 Hz
• Pulse width: 50% duty cycle above 500 Hz, configurable for frequencies below 500 Hz
• Power: Active or passive, software selectable
• Polarity: Active high or active low, software selectable
• Voltage: 24 VDC nominal, active; 30 VDC applied maximum, passive
• Current: Sourcing, 10 mA at 3 VDC, active; sinking, 500 mA, active or passive

Fault output
When a fault is detected, outputs go to configured states. User can select high, low, last measured
Specifications – Model 3350/3700

value, or internal zero. Milliamp outputs conform to NAMUR NE43 (June 1994).
• High output limits can be configured from 21 to 24 mA for milliamp; 15,000 Hz for frequency
• Low output limits can be configured from 1 to 3.6 mA for milliamp; 0 Hz for frequency
• Last measured value is the last output for the process variable
• Internal zero drives the milliamp and frequency outputs for process variables to zero values

Configuration and Use Manual 247


Specifications – Model 3300 and Model 3500

A.6.4 Digital communications


• One RS-485 port (standard)
- Supports Modbus RTU, Modbus ASCII, HART/RS-485, or printer
- User-configurable
• HART superimposed on primary mA output
- Standard HART/Bell 202 communication parameters, not configurable
• External adapters (not included) required for conversion to RS-232

A.7 Power supply options

A.7.1 Model 3300 controller

85 to 265 VAC
• 50/60 Hz, 15 VA
• 0.25 A max at 85 VAC; 0.12 A max at 265 VAC
• IEC 127-3/4 fuse, 0.63 A time-delay
• Complies with “low-voltage directive” 2006/95/EC per IEC 61010-1
• Installation (Overvoltage) Category II, Pollution Degree 2

18 to 30 VDC
• 7 watts typical, 14 watts maximum
• IEC 127-3/4 fuse, 1.6 A time-delay

A.7.2 Model 3500 transmitter

85 to 265 VAC
• 50/60 Hz, 30 VA
• 0.33 A max at 85 VAC; 0.15 A max at 265 VAC
• IEC 127-3/4 fuse, 0.63 A time-delay
• Complies with “low-voltage directive” 2006/95/EC per IEC 61010-1
• Installation (Overvoltage) Category II, Pollution Degree 2

18 to 30 VDC
• 18 watts typical, 25 watts maximum
• IEC 127-3/4 fuse; 1.6 A time-delay

248 Micro Motion® Series 3000 MVD Transmitters and Controllers


Specifications – Model 3300 and Model 3500

Measurement Performance
A.8 Environmental limits
• Ambient temperature:
- Operating: –4 to +140 °F (–20 to +60 °C)
- Storage: –40 to +158 °F (–40 to +70 °C)
Some darkening of display may occur above 131 °F (55 °C). Display responsiveness decreases
below –4 °F (–20 °C).
• Humidity: 5 to 95% relative humidity, non-condensing at 140 °F (60 °C)
• Vibration: Meets IEC 68.2.6, endurance sweep, 5 to 2000 Hz, 50 sweep cycles at 1.0 g

A.9 Environmental effects

Diagnostics and Troubleshooting


EMI effects
• Meets EMC directive 89/336/EEC per EN 61326 Industrial
• Conforms to NAMUR NE21 (June 1997)

Ambient temperature effect


• On analog outputs: ± 0.005% of span per °C

A.10 Hazardous area classifications

A.10.1 ATEX

Specifications – Model 3300/3500


Model 3500 transmitter
Safe area only [EEx ib] IIB/IIC. The sensor outputs are intrinsically safe and can be connected to a
sensor in the Zone 1 area.

A.10.2 UL and CSA

Model 3300 controller


Class I, Div. 2, Groups A, B, C, D when installed in a suitable enclosure.

Model 3500 transmitter


Class I, Div. 2, Groups A, B, C, D when installed in a suitable enclosure. Provides nonincendive
sensor outputs for use in Class I, Div. 2, Groups A, B, C, D, or intrinsically safe sensor outputs for use
in Class I, Div. 1, Groups C and D; Class II, Div. 1, Groups E, F, and G.
Specifications – Model 3350/3700

A.11 Performance specifications


For performance specifications, refer to the sensor specifications.

A.12 Cleaning instructions


To clean the Model 3300 or Model 3500, use a clean dry cloth or dry air.

Configuration and Use Manual 249


250 Micro Motion® Series 3000 MVD Transmitters and Controllers
Measurement Performance
Appendix B
Specifications – Model 3350 and Model 3700

B.1 Compartmentalized housing


• Compartment with threaded cover contains electronics
• Terminal compartment contains:

Diagnostics and Troubleshooting


- Non-intrinsically safe compartment with input and output terminals
- Intrinsically safe compartment with interface/display, sensor wiring terminals
(Model 3700 only), and optional input and output terminals
• Mounting bracket and interface/display rotate to allow mounting in four different orientations
• Rated NEMA 4X (IP67)

B.2 Interface/display

Screen
• Backlit LCD, 128 × 128 pixel, bit map
• Adjustable contrast

Specifications – Model 3300/3500


• Non-glare tempered glass lens
• Suitable for hazardous area installation

Keypad membrane switch


• Large pushbuttons with tactile feedback
• Software-defined function keys
• Chemical-resistant polyester

B.3 Weight
19 lb (8,6 kg)
Specifications – Model 3350/3700

B.4 Dimensions
See Figures B-1 through B-4.

Configuration and Use Manual 251


Specifications – Model 3350 and Model 3700

Figure B-1 Model 3350 or Model 3700 dimensions – Face view

inches
Dimensions in 12
(mm)
(305)
11
(279)

4 x 5/16-inch
(9 mm)
diameter

9 3/16
(234)
2 13/16
(71)

4
(102)

Mounting bracket can be


rotated 90° as needed

Display cover can be 3 5/8


rotated 90° or 180° as (92)
needed (see Section 2.8) 6
(152)

Figure B-2 Model 3350 or Model 3700 dimensions – Top view

inches
Dimensions in
(mm)

5 1/16-inch (129 mm)


clearance for removal
of circuit boards

Approvals tag
11 5/16
(288)

6 1/8
(158)

8 11/16
(221)
15 1/2
(394)

252 Micro Motion® Series 3000 MVD Transmitters and Controllers


Specifications – Model 3350 and Model 3700

Measurement Performance
Figure B-3 Model 3350 or Model 3700 dimensions – Conduit openings view
2 x 2 13/16
inches (71)
Dimensions in 1 7/8
(mm)
(48)
2 x 15/16
(24)

Case ground

5 x 3/4–14 NPT
or
5 x M20 x 1.5 – 6H

Diagnostics and Troubleshooting


10 3/8
(265)
7 1/2
(191)

5 3/4
(147)

Mounting surface

Specifications – Model 3300/3500


Specifications – Model 3350/3700

Configuration and Use Manual 253


Specifications – Model 3350 and Model 3700

Figure B-4 Core processor dimensions

Ø4 3/8
inches (111)
Dimensions in
(mm)

5 11/16
(144)
2X 3
(76)

2 1/4
(57)

2 5/8
(67)

6 3/16
(158) 4X Ø3/8
(10)
2 13/16
(71)

To centerline of 2” pipe

2 13/16
(71) 5 3/4
(146)
4 1/2 Pole Mount
(114)

4 9/16 1/2˝–14 NPT


2 1/2 OR
(116) (64)
Wall Mount M20 X 1.5
Note: These dimensions apply only to the 2 3/8
core processor component in remote core (61)
processor with remote transmitter 1 11/16
installations. (43)

3 5/16
(84)

3/4˝–14 NPT

254 Micro Motion® Series 3000 MVD Transmitters and Controllers


Specifications – Model 3350 and Model 3700

Measurement Performance
B.5 Electrical connections
Two color-coded wiring compartments:
• Compartment with intrinsically safe terminal block has two 3/4-inch NPT or M20 × 1.5
conduit openings
• Compartment with non-intrinsically safe terminal block has three 3/4-inch NPT or M20 × 1.5
conduit openings
Input and output screw terminals accept 22 to 16 AWG (0,35 to 1,5 mm2) wires
Power screw terminals accept 18 to 12 AWG (0,75 to 4.0 mm2) wires

B.6 Inputs and outputs

Diagnostics and Troubleshooting


B.6.1 Intrinsically safe input signals
One 4-wire Coriolis sensor signal input with ground (standard)

B.6.2 Non-intrinsically safe input signals

Frequency/pulse input
One 2-wire frequency/pulse input
• Frequency range: 0–20,000 Hz
• Minimum pulse width: 25 sec
• Power: Sourcing or sinking
• Voltage: 0–0.8 VDC low state, 3–30 VDC high state

Specifications – Model 3300/3500


• Current: Nominal 5 mA pull-up

Discrete inputs
Two discrete, momentary inputs
• Pulse width: 0.15 sec minimum
• Voltage: 0–0.8 VDC low state, 3–30 VDC high state, dry contacts

B.6.3 Non-intrinsically safe output signals

Milliamp outputs
Two active 4–20 mA outputs
Specifications – Model 3350/3700

• Isolated to ±50 VDC from all other outputs and earth ground
• Maximum load limit: 1000 
• Output is linear with process from 3.8 to 20.5 mA, per NAMUR NE43 (June 1994)

Configuration and Use Manual 255


Specifications – Model 3350 and Model 3700

Discrete outputs
Three discrete outputs
• Configurable for the application
• Polarity: Active high or active low, software selectable
• Power: Internal pull-up to 24 V
• Voltage: 24 VDC nominal
• Current: Sourcing at 5.6 mA when Vout = 3 VCD; sinking up to 500 mA at 30 VDC maximum

Frequency/pulse output
One 2-wire frequency/pulse output
• Output is linear with flow rate to 12,500 Hz
• Configurable unit of measure
• Scalable to 10000 Hz
• Pulse width: 50% duty cycle above 500 Hz, configurable for frequencies below 500 Hz
• Power: Active or passive, software selectable
• Polarity: Active high or active low, software selectable
• Voltage: 24 VDC nominal, active; 30 VDC applied maximum, passive
• Current: Sourcing, 10 mA at 3 VDC, active; sinking, 500 mA, active or passive

Fault output
When a fault is detected, outputs go to configured states. User can select high, low, last measured
value, or internal zero. Milliamp outputs conform to NAMUR NE43 (June 1994).
• High output limits can be configured from 21 to 24 mA for milliamp; 15,000 Hz for frequency
• Low output limits can be configured from 1 to 3.6 mA for milliamp; 0 Hz for frequency
• Last measured value is the last output for the process variable
• Internal zero drives the milliamp and frequency outputs for process variables to zero values

B.6.4 Digital communications


• One RS-485 port (standard)
- Supports Modbus RTU, Modbus ASCII, HART/RS-485, or printer
- User-configurable
• HART superimposed on primary mA output
- Standard HART/Bell 202 communication parameters, not configurable
• External adapters (not included) required for conversion to RS-232

256 Micro Motion® Series 3000 MVD Transmitters and Controllers


Specifications – Model 3350 and Model 3700

Measurement Performance
B.7 Power supply options

85 to 265 VAC
• 50/60 Hz, 30 VA
• 0.33 A max at 85 VAC; 0.15 A max at 265 VAC
• IEC 127-3/4 fuse, 0.63 A time-delay
• Complies with “low-voltage directive” 2006/95/EC per IEC 61010-1
• Installation (Overvoltage) Category II, Pollution Degree 2

18 to 30 VDC
• 18 watts typical, 25 watts maximum

Diagnostics and Troubleshooting


• IEC 127-3/4 fuse; 1.6 A time-delay

B.8 Environmental limits


• Ambient temperature:
- Operating: –4 to +140 °F (–20 to +60 °C)
- Storage: –40 to +158 °F (–40 to +70 °C)
Some darkening of display may occur above 131 °F (55 °C). Display responsiveness decreases
below –4 °F (–20 °C).
• Humidity: 5 to 95% relative humidity, non-condensing at 140 °F (60 °C)
• Vibration: Meets IEC 68.2.6, endurance sweep, 5 to 2000 Hz, 50 sweep cycles at 1.0 g

Specifications – Model 3300/3500


B.9 Environmental effects

EMI effects
• Meets EMC directive 89/336/EEC per EN 61326 Industrial
• Conforms to NAMUR NE21 (June 1997)

Ambient temperature effect


• On analog outputs ± 0.005% of span per °C

B.10 Hazardous area classifications


Specifications – Model 3350/3700

B.10.1 ATEX
Zone 1, complying with ATEX Directive (94/9/EC) for group II category 2G and marked as
EEx de [ib] IIB/IIC T4.

B.10.2 UL and CSA


Class I, Div. 2, Groups A, B, C, and D. Provides nonincendive sensor outputs for use in Class I, Div.
2, Groups A, B, C, D, or intrinsically safe sensor outputs for use in Class I, Div. 1, Groups C and D;
Class II, Div. 1, Groups E, F, and G.

Configuration and Use Manual 257


Specifications – Model 3350 and Model 3700

B.11 Performance specifications


For performance specifications, refer to the sensor specifications.

B.12 Cleaning instructions


To clean the Model 3350 or Model 3700, use a clean damp cloth.

WARNING
Using a dry cloth to clean the display cover of the Model 3350 or Model 3700
can cause static discharge, which could result in an explosion in an
explosive atmosphere.

To prevent an explosion, use a clean damp cloth to clean the display cover of the
Model 3350 or Model 3700 in an explosive atmosphere.

258 Micro Motion® Series 3000 MVD Transmitters and Controllers


Specifications – Model 3100
Appendix C
Specifications – Model 3100

C.1 Overview
The Model 3100 accessory features relay packs for interfacing with high-energy solenoids, pump
starters, or other devices.

C.2 Relay packs

Relay Installation
The Model 3100 contains three relays with the following characteristics:
• Solid state, SPST
• Rated at 24–250 VAC, 40 mA–5 A; or 0–70 VDC, 5 A
• Energized by discrete outputs

C.3 Hazardous area classifications

C.3.1 ATEX
Zone 2, complying with ATEX Directive (94/9/EC) for Group II, Category 3G, according to
CENELEC standard prEN 50021:1998 and marked as:
• EEx n V II T4
• KEMA 97 ATEX 4940 X

Defaults
• Ambient temperature –20 to +60 °C (–4 to +140 °F)

C.3.2 UL and CSA


Class I, Division 2, Groups A, B, C, and D

Series 3000 Menus

Configuration and Use Manual 259


260 Micro Motion® Series 3000 MVD Transmitters and Controllers
Specifications – Model 3100
Appendix D
Installing Relays

D.1 About this appendix


This appendix explains how to install relay modules for the Series 3000 device. Relays are used to
connect the device’s discrete outputs to control devices.

D.2 Relay types

Relay Installation
Two types of relay can be used with the Series 3000:
• The Model 3100 relay module supplied by Micro Motion. The Model 3100 contains three
solid-state relays.
• User-supplied relay or relay module compatible with the Series 3000 discrete outputs (see
Section D.5.1).

D.2.1 Power
The Model 3100 relay module is powered by the Series 3000 discrete outputs.
User-supplied relays can be powered by the Series 3000 discrete outputs if both of the following are
true:
• They are solid-state relays, and
• The relay input requirements are met by the discrete output characteristics (see Section D.5.1).

Defaults
If either of these conditions is not true, user-supplied relays must be powered externally.

D.3 Hazardous area installations


If you are installing the relay or relay module in a hazardous area, review the information in this
section.

D.3.1 Model 3100 relays

ATEX
Model 3100 relay modules are suitable for installation in Zone 2, complying with ATEX Directive
Series 3000 Menus

(94/9/EC) for Group II, Category 3G, according to CENELEC standard prEN 50021:1998 and
marked as:
• EEx nV II T4
• KEMA 97 ATEX 4940 X
• Ambient temperature –20 to +60 °C (–4 to +140 °F)

Configuration and Use Manual 261


Installing Relays

To comply with hazardous area requirements:


• Model 3100 relay modules must be mounted into a suitable and classified enclosure that
provides ingress protection of at least IP4X according to EN 60529, taking into account the
environmental conditions into which the equipment will be installed.
• The external metal parts of the relay module (heat sinks) must be connected to the
potential-equalizing system within the hazardous area.

UL and CSA
Model 3100 relay modules are suitable for installation in Class I, Division 2, Groups A, B, C, and D.
Note: For CSA compliance, the relay module must be installed in a suitable enclosure where the final
combination is subject to acceptance by the Canadian Standards Association (CSA).

D.3.2 User-supplied relays


User-supplied relays to be used for Zone 2 applications must be certified as Category 3 equipment.

D.4 Replacing relays


You may not replace a defective relay separately. If an individual relay is defective, you must replace
the entire relay module.
This requirement applies to both the Model 3100 and to user-supplied relays, and to both hazardous
and non-hazardous areas.

D.5 Using relays with the Series 3000 device


A relay is used to connect the Series 3000 device’s discrete outputs to control devices.

D.5.1 Series 3000 discrete outputs


The Series 3000 has three discrete outputs, which can be configured for specific application
requirements. The outputs have the following characteristics:
• Polarity:
- Active high or active low
- Software selectable
• Current:
- Sourcing at 5.6 mA, Vout = 3 VDC minimum
- Sinking up to 500 mA at 30 VDC supply maximum
Figure D-1 shows a diagram of a typical discrete output circuit.

262 Micro Motion® Series 3000 MVD Transmitters and Controllers


Installing Relays

Specifications – Model 3100


Figure D-1 Discrete output circuit
+24 V (Nom)

3.2 k

Out+

Out–

Relay Installation
D.6 Installing the Model 3100 relay module
Follow these steps to install a Model 3100 relay module.

Step 1 Mount relay module


Mount the supplied relay module to a DIN rail. The relay module accommodates various standard rail
types. See Figure D-2.

Defaults
Series 3000 Menus

Configuration and Use Manual 263


Installing Relays

Figure D-2 Relay module dimensions

inches 3 3/64
Dimensions in (77)
(mm)

2
(50)
2 1/32 2 7/32
(52) (56) 2 21/64
(59)

TS 32

TS 15

TS 35 x 7.5 TS 35 x 15

8
(203)

264 Micro Motion® Series 3000 MVD Transmitters and Controllers


Installing Relays

Specifications – Model 3100


Step 2 Connect discrete output terminals to relays
Follow the steps below to connect the transmitter/controller’s discrete output wiring terminals to one,
two, or three relays.

WARNING
Shock Hazard.

Improper installation of wiring, or installation with power supply on, can cause
electric shock or property damage.

For personal and system safety:

• Shut off power before installing wiring.


• Make sure the installation meets or exceeds local code requirements.
• Install relays and wiring in accordance with the illustrations in these instructions.

Relay Installation
• Install relays and wiring where ambient temperature remains between –4 and
+140 °F (–20 and +60 °C).

1. Use the following wire sizes:


• Model 3300 or Model 3500: 24 to 16 AWG (0,25 to 1,5 mm2)
• Model 3350 or Model 3700: 22 to 16 AWG (0,35 to 1,5 mm2)
2. Connect the wires between the transmitter/controller terminals and the relay terminals as
shown in Table D-1 and in the following diagrams:
• Model 3300 or Model 3500 with screw-type or solder-tail connectors: see Figure D-3
• Model 3300 or Model 3500 with I/O cables: see Figure D-4
• Model 3350 or Model 3700: see Figure D-5

Table D-1 Transmitter/controller terminals and Model 3100 terminals

Defaults
Transmitter/controller terminals
Model 3300 or Model 3500 Model 3350 or Model 3700
Screw-type or
I/O cables or I/O solder-tail Terminal Model 3100
terminal block terminals Gray terminal block function terminals
19 a 14 20 Return a 14
18 c 14 18 DO1 c 14
20 c 16 17 DO2 c 16
22 c 18 16 DO3 c 18
Series 3000 Menus

Configuration and Use Manual 265


Installing Relays

Figure D-3 Model 3300 or Model 3500 to Model 3100 – Screw-type or solder-tail connector

Wire size is 24 to 16 AWG (0,25 to 1,5 mm2)

MODEL 3300/3500
TERMINAL
CONNECTION

Relay 3 Relay 2 Relay 1

Model 3300 or Model 3500 input/output wiring terminals


See Figure 2-2

Figure D-4 Model 3300 or Model 3500 to Model 3100 – I/O cables

Wire size is 24 to 16 AWG (0,25 to 1,5 mm2)

MODEL 3300/3500
TERMINAL
CONNECTION

Relay 3 Relay 2 Relay 1

Model 3300 or Model 3500 input/output wiring


terminals
See Figure 2-2

266 Micro Motion® Series 3000 MVD Transmitters and Controllers


Installing Relays

Specifications – Model 3100


Figure D-5 Model 3350 or Model 3700 to Model 3100

Model 3350 or Model 3700 input/output


wiring terminals
Gray terminal block
See Figure 2-2

Relay Installation
MODEL 3300/3500
TERMINAL

Relay 3 Relay 2 Relay 1 CONNECTION

Wire size is 22 to 16 AWG (0,35 to 1,5 mm2)

Step 3 Connect relay wiring to control devices


Follow the steps below to connect one, two, or three relays to a control device.
1. Wire size must be between 22 and 16 AWG (0,35 to 1,5 mm2).
2. Connect the wires between the relay module and the control device as shown in the diagrams:

Defaults
• If the relay loads have an AC power supply, see Figure D-6. AC output terminals do not
have polarity.
• If the relay loads have a DC power supply, see Figure D-7. DC output terminals have
polarity.

Series 3000 Menus

Configuration and Use Manual 267


Installing Relays

Figure D-6 Model 3100 relay module to control devices – AC power

24 to 280 VAC One relay, two relays, or all three


(no polarity) relays may be connected
MODEL 3300/3500

CONNECTION
TERMINAL

Primary control valve


Relay 1 or other control device

Secondary control valve


or other control device
Relay 2

Pump or other
control device

Relay 3

Figure D-7 Model 3100 relay module to control devices – DC power

One relay, two relays, or all three


12 to 30 VDC relays may be connected
MODEL 3300/3500

CONNECTION
TERMINAL

Primary control valve or


Relay 1 other control device

Secondary control valve


or other control device
Relay 2

Pump or other
control device

Relay 3

268 Micro Motion® Series 3000 MVD Transmitters and Controllers


Installing Relays

Specifications – Model 3100


D.7 Installing user-supplied relays
Follow these steps to install user-supplied relays.

Step 1 Connect discrete output terminals to relays


Follow the steps below to connect the transmitter/controller’s discrete output wiring terminals to one,
two, or three relays.

WARNING
Shock Hazard.

Improper installation of wiring, or installation with power supply on, can cause
electric shock or property damage.

For personal and system safety:

Relay Installation
• Shut off power before installing wiring.
• Make sure the installation meets or exceeds local code requirements.
• Install relays and wiring in accordance with the illustrations in these instructions.
• Install relays and wiring where ambient temperature remains between –4 and
+140 °F (–20 and +60 °C).

1. Use the following wire sizes:


• Model 3300 or Model 3500: 24 to 16 AWG (0,25 to 1,5 mm2)
• Model 3350 or Model 3700: 22 to 16 AWG (0,35 to 1,5 mm2)
2. Connect the wires between the transmitter/controller and the relay as shown in Table D-2 and
in the following diagrams:
• Model 3300 or Model 3500 with screw-type or solder-tail connectors: see Figure D-8
• Model 3300 or Model 3500 with I/O cables: see Figure D-9

Defaults
• Model 3350 or Model 3700: see Figure D-10

Table D-2 Transmitter/controller terminals for user-supplied relays

Transmitter/controller terminals
Model 3300 or Model 3500 Model 3350 or Model 3700
Screw-type or
I/O cables or I/O solder-tail
terminal block terminals Gray terminal block Terminal function
19 a 14 20 Return
18 c 14 18 DO1
Series 3000 Menus

20 c 16 17 DO2
22 c 18 16 DO3

Configuration and Use Manual 269


Installing Relays

Figure D-8 Model 3300 or Model 3500 to user-supplied relay – Screw-type or solder-tail connector

Model 3300 or Model 3500


input/output wiring terminals
See Figure 2-2 External • 12 to 30 VDC
power • Maximum coil load:
supply 500 mA/relay

500 mA
maximum

Wire size is 24 to 16 AWG 500 mA


(0,25 to 1,5 mm2) User-supplied relays
maximum

500 mA
maximum

Figure D-9 Model 3300 or Model 3500 to user-supplied relay – I/O cable

External • 12 to 30 VDC
Model 3300 or • Maximum coil load:
power
Model 3500 input/output 500 mA/relay
supply
wiring terminals
See Figure 2-2
Wire size is 24 to 16 AWG
(0,25 to 1,5 mm2)
500 mA
maximum

500 mA
maximum User-supplied relays

500 mA
maximum

270 Micro Motion® Series 3000 MVD Transmitters and Controllers


Installing Relays

Specifications – Model 3100


Figure D-10 Model 3350 or Model 3700 to user-supplied relay

Model 3350 or Model 3700 input/output wiring terminals


Gray terminal block
See Figure 2-2

500 mA maximum
User-supplied relays

500 mA maximum

500 mA maximum
External • 12 to 30 VDC
+ power supply • Maximum coil load:
500 mA/relay

Relay Installation
Wire size is 22 to 16 AWG (0,35 to 1,5 mm2)

Step 2 Connect relay wiring to control devices


The method used to connect the relay to the control device depends on the function the relay will
perform. For an illustration of typical wiring for a 2-stage batch application, see Figure D-11.

Figure D-11 User-supplied relay to control device: 2-stage batch application

Primary control valve


or other control device

Defaults
Secondary control valve
or other control device
User-supplied relays

Pump or other
control device Series 3000 Menus

Configuration and Use Manual 271


272 Micro Motion® Series 3000 MVD Transmitters and Controllers
Specifications – Model 3100
Appendix E
Default Values and Ranges

E.1 Overview
This appendix provides information on the default values for most Series 3000 parameters. Where
appropriate, valid ranges are also defined.
These default values represent the platform configuration after a master reset. Depending on how the
platform was ordered, certain values may have been configured at the factory.

Relay Installation
E.2 Most frequently used defaults and ranges
The table below contains the default values and ranges for the most frequently used Series 3000
settings.

Table E-1 Series 3000 default values and ranges

Type Setting Default Range Comments


Flow Flow direction Forward only
Flow damping 0.8 sec 0.0 – 51.2 sec User-entered value is
corrected to nearest lower
value in list of preset values.
For gas applications, Micro
Motion recommends a value
of 2.56 seconds or higher.
Flow calibration factor 1.00005.13 For T-Series sensors, this

Defaults
value represents the FCF and
FT factors concatenated. See
Section 7.3.3.
Mass flow units g/s
Mass flow cutoff 0.0000 g/s Recommended setting:
• Standard use – 0.2% of the
sensor’s rated maximum
flowrate
• Empty-full-empty batching –
2.5% of the sensor’s
maximum flowrate
Volume flow type Liquid
Volume flow units L/s
Series 3000 Menus

Volume flow cutoff 0.0000 l/s 0.0 – x l/s x is obtained by multiplying


the flow calibration factor by
0.2, using units of l/s
Meter factors Mass factor 1.00000
Density factor 1.00000
Volume factor 1.00000

Configuration and Use Manual 273


Default Values and Ranges

Table E-1 Series 3000 default values and ranges continued

Type Setting Default Range Comments


Density Density damping 1.6 sec 0.0 – 51.2 sec User-entered value is
corrected to nearest value in
list of preset values
Density units g/cm3
Density cutoff 0.2 g/cm3 0.0 – 0.5 g/cm3
D1 0.00000
D2 1.00000
K1 1000.00
K2 50,000.00
FD 0.00000
Temp Coefficient 4.44
Slug flow low limit 0.0 g/cm3 0.0 – 10.0 g/cm3
Slug flow high limit 5.0 g/cm3 0.0 – 10.0 g/cm3
Slug duration 0.0 sec 0.0 – 60.0 sec
Temperature Temperature damping 4.8 sec 0.0 – 38.4 sec User-entered value is
corrected to nearest lower
value in list of preset values
Temperature units degC
Temperature calibration factor 1.00000T0.0000
Frequency input Flow rate units kg/min
Scaling method Frequency = Flow
Frequency 1000.0000
Flow 999.9999 kg/min
K factor 1.0000
Discrete inputs Polarity Active low
Discrete events Type HI
Process variable Mass flow rate
HI PV value 0.0000
Discrete Polarity Active low
outputs
Assignment None
Fault indication None
Milliamp output Fault indication: Condition Downscale
1
Fault indication: Setting 2.0000 mA 1.0 – 3.6 mA
Fault indication: Last 0 sec 0.0 – 60.0 sec
measured value timeout
Variable assignment Mass flow
Calibration span: 20.0 mA 200.0000 g/s
Calibration span: 4.0 mA –200.0000 g/s
Calibration span: Low flow 0.0000 g/s
cutoff
Damping seconds 0.0000

274 Micro Motion® Series 3000 MVD Transmitters and Controllers


Default Values and Ranges

Specifications – Model 3100


Table E-1 Series 3000 default values and ranges continued

Type Setting Default Range Comments


Milliamp output Fault indication: Condition Downscale
2
Fault indication: Setting 2.0000 mA 1.0 – 3.6 mA
Fault indication: Last 0 sec 0.0 – 60.0 sec
measured value timeout
Variable assignment Density
Calibration span: 20.0 mA 10.0000 g/cm3
Calibration span: 4.0 mA 0.0000 g/cm3
Damping seconds 0.0000
LRV Mass flow –200.000 g/s
Volume flow –0.200 l/s
Density 0.000 g/cm3

Relay Installation
Temperature –240.000 °C
Drive gain 0.000%
Gas standard volume flow –423.78 SCFM
External temperature –240.000 °C
External pressure 0.000 psi
URV Mass flow 200.000 g/s
Volume flow 0.200 l/s
Density 10.000 g/cm3
Temperature 450.000 °C
Drive gain 100.000%
Gas standard volume flow 423.78 SCFM
External temperature 450.000 °C
External pressure 100.000 psi

Defaults
Frequency Flow source Mass flow
output
Scaling method Frequency = flow
Frequency 1,000.00 Hz 0.00091 –
10,000.00 Hz
Flow 16,666.66999 g/s
Max pulse width 277.2352 ms 0 – 277.2352 ms
Power Active
Polarity Active high
Fault indication Downscale
Last measured value timeout 0.0 sec 0.0 – 60.0 sec
RS-485 Baud rate 9600
parameters –
Series 3000 Menus

Parity Odd
HART protocol
Data bits 8
Stop bits 1
Polling address 0

Configuration and Use Manual 275


Default Values and Ranges

Table E-1 Series 3000 default values and ranges continued

Type Setting Default Range Comments


RS-485 Baud rate 9600 Modbus RTU is the default
parameters – RS-485 protocol
Parity Odd
Modbus RTU
protocol Data bits 8
Stop bits 1
Polling address 1
Byte order 3–4–1–2
RS-485 Baud rate 9600
parameters –
Modbus ASCII Parity Odd
protocol Data bits 7
Stop bits 1
Polling address 1
Byte order 3–4–1–2
RS-485 Baud rate 9600
parameters –
Parity Odd
printer protocol
Data bits 7
Stop bits 1
Bell 202 HART polling address 0
parameters
Burst mode Disabled
Burst command PV & Pct Range
Device Fault setting None
parameters
HART QV Volume flow

276 Micro Motion® Series 3000 MVD Transmitters and Controllers


Specifications – Model 3100
Appendix F
Series 3000 Menu Flowcharts

F.1 Overview
This appendix provides flowcharts for the Series 3000 display menus.

F.2 Process monitor


Access to the process monitor depends on whether or not the discrete batch application is installed:

Relay Installation
• As shown in Figure F-1, when the discrete batch is not installed, the process monitor is the
default display. The five process monitor screens are accessed via the Left and Right cursor
control buttons. If no display variables are configured for a particular screen, that screen is
skipped.
• As shown in Figure F-2, when the discrete batch application is installed, the default display is
the batch operation screen, and the process monitor is accessed through the View menu.

Figure F-1 Process monitor: Discrete batch application not installed

< > < > < > < > < >
Screen 1 Screen 2 Screen 3 Screen 4 Screen 5

Var Var Var Var Var


Var Var Var Var Var
Var Var Var Var Var

Defaults
Var Var Var Var Var

Series 3000 Menus

Configuration and Use Manual 277


Series 3000 Menu Flowcharts

Figure F-2 Process monitor: Discrete batch application installed

Well Performance Meas

Start Well Test

>
View Well Tests
Recalculate Well Test < >

>
VIEW

View Menu

Process Monitoring

< > < > < > < > < >
Screen 1 Screen 2 Screen 3 Screen 4 Screen 5

Var Var Var Var Var


Var Var Var Var Var
Var Var Var Var Var
Var Var Var Var Var

F.3 Menu access


As shown in Figure F-3:
• To access the View menu system, press the VIEW function button.
• To access the Management menu system, press the Security button.

Figure F-3 Menu access

Process monitor(1) Batch operation screen(2)

< >
Preset Name
Screen x
>

>

< > Total < >


Var
Var
>

>

Target
Var
Var
VIEW VIEW

to View menu to Management menu

(1) Displayed if the discrete batch application is not installed. See Figure F-1 for details.
(2) Displayed if the discrete batch application is installed. See Figure F-2 for details.

278 Micro Motion® Series 3000 MVD Transmitters and Controllers


Series 3000 Menu Flowcharts

Specifications – Model 3100


F.4 View menu
The appearance of the View menu depends on the special applications that are installed:
• Figure F-4 shows the View menu when neither the custody transfer application or the discrete
batch application is installed. The petroleum measurement and enhanced density applications
are optional.
• Figure F-5 shows the View menu when the custody transfer application is installed and
configured for OIML compliance. The discrete batch, petroleum measurement, and enhanced
density applications are optional.
• Figure F-6 shows the View menu when the discrete batch application is installed, or the
discrete batch and custody transfer applications are installed and custody transfer is configured
for NTEP compliance. The petroleum measurement and enhanced density applications are
optional.

Figure F-4 View menu: Special applications – None, API only, or ED only

Relay Installation
View Menu

Active Alarm Log Process Monitoring Process Totalizers

Screen
Screen
1
Screen
2
Screen
3
Screen
4 5 Process Inventory

Var Var Var Var Var


· Mass Total · Mass Inventory
Var
· Volume Total · Volume Inventory
Var Var Var Var Var
· API Corr Volume Total(1) · API Cor Vol Inventory(1)
· ED Std Volume Total(2) · ED Std Volume Inventory(2)
< > · ED Net Mass Total(2) · ED Net Mass Inventory(2)
· Freq Input Total · Freq Input Inventory

Diagnostic Monitor Density Curves(2) LCD Options Applications List

Defaults
· Tube Frequency · Curve 1 name(3) · Contrast · I/O
· Left Pickoff · Curve 2 name(3) · LCD Backlight · Core processor version
· Right Pickoff · …. · API(1)
· Drive Gain · Enhanced Density(2)
· Live Zero
· Temperature

(1) Displayed only if the petroleum measurement application is installed.


(2) Displayed only if the enhanced density application is installed.
(3) Only configured curves are listed.
Series 3000 Menus

Configuration and Use Manual 279


Series 3000 Menu Flowcharts

Figure F-5 View menu: Special applications – Custody transfer (OIML)


(Discrete batching, API, and ED optional)

View Menu

Active Alarm Log Process Monitoring Preset Selections (1) Batch Inventory (1)

Screen
Screen
1
Screen
2
Screen
3
Screen
4 5 Preset 1 name (2) Preset 1 name (2)
Preset 2 name (2) Preset 2 name (2)
Var Var Var Var Var …. ….
Var
Var Var Var Var Var

< >

Transfer Totalizer Transfer Log

Transfer Inventory Transfer & Inventory · Current BOL


· Select BOL to view
· Current BOL · Current BOL · Current BOL
· Mass Transfer · Mass Inventory · Mass Transfer
· Volume Transfer · Volume Inventory · Mass Inventory
· Volume Transfer
· Volume Inventory

API Transfer & Inventory (3) ED Transfer & Inventory (4)

· Current BOL · Current BOL


· API Corr Vol Transfer · ED Net Mass Transfer
· API Cor Vol Inventory · ED Net Mass Inventory
· Volume Transfer
· Volume Inventory
· ED Concentration

Diagnostic Monitor Density Curves (5) LCD Options Applications List

· Tube Frequency · Curve 1 name (6) · Contrast · I/O


· Left Pickoff · Curve 2 name (6) · LCD Backlight · Core processor version
· Right Pickoff · …. · API(7)
· Drive Gain · Enhanced Density (5)
· Live Zero · Weights & Measures (8)
· Temperature

(1) Displayed only if the discrete batch application is installed.


(2) Only configured presets are listed.
(3) Displayed only if the petroleum measurement application is installed and approved for custody transfer.
(4) Displayed only if the enhanced density application is installed and approved for custody transfer.
(5) Displayed only if the enhanced density application is installed.
(6) Only configured curves are listed.
(7) Displayed only if the petroleum measurement application is installed.
(8) If World Area is set to OIML, the custody transfer application version is displayed.

280 Micro Motion® Series 3000 MVD Transmitters and Controllers


Series 3000 Menu Flowcharts

Specifications – Model 3100


Figure F-6 View menu: Special applications – Discrete batch (no custody transfer) or discrete batch with
custody transfer (NTEP) (API and ED optional)

View Menu

Active Alarm Log Process Monitoring Preset Selections Batch Inventory

Screen
Screen
1
Screen
2
Screen
3
Screen
4 5 Preset 1 name(1) Preset 1 name(1)
Preset 2 name(1) Preset 2 name(1)
Var Var Var Var Var …. ….
Var
Var Var Var Var Var

< >

Process Totalizers Density Curves(3)

Relay Installation
Process Inventory · Curve 1 name(4)
· Curve 2 name(4)
· ….
· Mass Total · Mass Inventory
· Volume Total · Volume Inventory
· API Corr Volume Total(2) · API Cor Volume Inventory(2)
· ED Std Volume Total(3) · ED Std Volume Inventory(3)
· ED Net Mass Total(3) · ED Net Mass Inventory(3)
· Freq Input Total · Freq Input Inventory

Diagnostic Monitor LCD Options Applications List

· Tube Frequency · Contrast · I/O


· Left Pickoff · LCD Backlight · Core processor version
· Right Pickoff · API(2)
· Drive Gain · Enhanced Density(3)
· Live Zero · Discrete Batch

Defaults
· Temperature

(1) Only configured presets are listed.


(2) Displayed only if the petroleum measurement application is installed.
(3) Displayed only if the enhanced density application is installed.
(4) Only configured curves are listed.

F.5 Management menus


The Management menu system is illustrated in Figures F-7 through F-13:
• Figure F-7 shows the top level of the Management menu, plus the Security and Language
menus.
• Figures F-8 through F-12 show the Configuration menu. Note that the Digital Communication
Series 3000 Menus

menu structure changes according to the setting of the Protocol parameter.


• Figure F-13 shows the Maintenance menu.

Configuration and Use Manual 281


Series 3000 Menu Flowcharts

Figure F-7 Management menu – top level, Security menu, and Language menu

Management Menu

Configuration Maintenance Security Language

See following pages See following pages Security Language


· Enable/disable
· Write Protect(1)
· Totalizer Reset(1)

Passwords
(1) Displayed only if the custody transfer application is · Maintenance
not installed. · Configuration
(2) Displayed only if the custody transfer application is
Weights & Measures(2)
installed. · World Area
(3) Displayed only if the custody transfer application is · Process Monitoring(3)
configured for OIML. · Discrete Batch(3)(4)
(4) Displayed only if the discrete batching application · API(3)(5)
· Enhanced Density(3)(6)
is installed. · Transmitter Checksum(3)
(5) Displayed only if the petroleum measurement · Core Checksum(3)
application is installed. · Switch Status
(6) Displayed only if the enhanced density application
Alarm Log(3)
is installed. · Enable Alarm Password
· Alarm Log Password

282 Micro Motion® Series 3000 MVD Transmitters and Controllers


Series 3000 Menu Flowcharts

Specifications – Model 3100


Figure F-8 Configuration menu

Management Menu

Configuration

continued

System Inputs

 Tag Core Processor Frequency Input Discrete Inputs External Inputs


 Time  Flow Rate Units  Discrete Input 1–2  Polling Variable 1–2
 Date  Scaling Method  Polarity  Polling Control
 Alarm Severity  Frequency(6)  Polled Variable
 Electronics Alarms  Flow(6)  Pressure Compensation(7)
 Process Alarms  Pulses/Unit(6)  Pressure Units(7)
 Sensor Alarms  Units/Pulse(6)  Flow Factor(7)
 Configuration Alarms  K-factor  Density Factor(7)
 Cal Pressure(7)
 Ext Temp Compensation(8)

Relay Installation
Enable Config Process Var Discrete Inputs
 Flow Variables  Start Zero
 Flow Damping  Reset Mass Total
 Flow Direction  Reset Volume Total
 Mass Units  Reset API Cor Vol Tot(4)
 Mass Low Flow Cutoff  Reset ED Std Vol Tot(5)
 Volume Flow Type  Reset ED Net Mass Tot(5)
 Volume Units(1)  Reset All Totals
 Vol Low Flow Cutoff(1)  Start/Stop All Totals
 Std Gas Volume Units(2)
 Std Gas Volume Cutoff(2)
 Std Gas Density(2)
 Special Mass Units Sensor Cal Data Sensor Information
 Special Volume Units(1)  T-Series Setup(3)  Sensor Model No.
 Special Gas Std Units(2)  Sensor Serial No.
Yes No
 Density  Sensor Material
 Density Units  Sensor Flange
 FCF  Flow Cal  Sensor Liner
 Density Damping
 FTG  D1–2
 Density Cutoff
 FFQ  K1–2
 Slug Low Limit
 D1–4  FD
 Slug High Limit
 K1–4  Dens Temp Coeff
 Slug Duration

Defaults
 FD  Temp Cal Factor
 Temperature
 DT  Temperature Slope
 Temperature Units
 DTG  Temperature Offset
 Temperature Damping
 DFQ1–DFQ2  Mass Factor
 Temperature Slope  Density Factor
 Temperature Offset  Volume Factor
 Mass Factor
 Density Factor
 Volume Factor

(1) Liquid volume; displayed only if Volume Flow Type = Liquid.


(2) Gas standard volume; displayed only if Volume Flow Type = Gas Standard.
(3) T-Series option displayed only if transmitter is not connected to sensor. The parameter list displayed depends on the
sensor type.
(4) Displayed only if the petroleum measurement application is installed.
(5) Displayed only if the enhanced density application is installed.
(6) Options displayed depend on Scaling Method.
Series 3000 Menus

(7) Displayed only if Polled Variable = Pressure.


(8) Displayed only if Polled Variable = Temperature.

Configuration and Use Manual 283


Series 3000 Menu Flowcharts

Figure F-9 Configuration menu continued

Management Menu

Configuration

continued
(1)
Discrete Batch Measurements

Flow Source Discrete Events API(3) Density Functions(4)


· Frequency Input · Discrete Event 1–5 · Table Type · Derived Variable
· Mass · Event Type · Temperature Units · DI Next Curve
· Volume · Process Variable · Density Units · Configure Curve
· HI PV Value(2) · Reference Temperature · Extrapolation Alarms
Control Options · LO PV Value(2) · Curve Fit Results
· Enable Batch
· Time Out
· No. of Stages
· No. of Decimals
· Reset on Start
· Count Up
· Enable End Warning
· Enable AOC
· Enable Overrun
· Lockout Target
· Maximum Target
· Ignore Source
· Alarms
· Configure Presets by

Configure Presets
(1) Displayed only if the discrete batching application is installed.
· Preset 1–6 (2) Either or both are displayed, depending on Event Type.
· Enable Preset (3) Displayed only if the petroleum measurement application is installed.
· Name (4) Displayed only if the enhanced density application is installed.
· End Warning
· Target
· Overrun

Discrete Inputs
· End
· Inhibit Batch
· Inhibit Totalizer
· Reset
· Resume
· Start
· Stop
· Increment Preset
· Inhibit Flow

284 Micro Motion® Series 3000 MVD Transmitters and Controllers


Series 3000 Menu Flowcharts

Specifications – Model 3100


Figure F-10 Configuration menu continued

Management Menu

Configuration

continued

Outputs Monitoring

Screens 1–5
Discrete Outputs Milliamp Outputs Frequency Output · Variables 1–4
· Discrete Output 1–3 · Milliamp Output 1–2 · Flow Source
· Polarity · Fault Indication · Scaling Method Variables
· Assignment · Condition · Frequency(3) · Number of Decimals
· Fault Indication · Setting · Flow(3) · W&M Approval(4)
· Flow Switch Source(1) · Last Meas Val Timeout(2) · Pulses/Unit(3) · Label
· Flow Switch Setpoint(1) · Variable Assignment · Units/Pulse(3)
· Calibration Span · Max Pulse Width Update Period
· 20 mA · Power
· 4 mA · Polarity

Relay Installation
· Low Flow Cutoff · Fault Indication
· Damping Seconds · Last Meas Val Timeout(2)
· 4 mA Minimum
· 20 mA Maximum
· Minimum Span

(1) Displayed only if Assignment = Flow Switch.


(2) One setting applies to both milliamp and frequency outputs.
(3) Options displayed depend on Scaling Method.
(4) Displayed only if the custody transfer application is installed and configured for OIML.

Figure F-11 Configuration menu continued

Management Menu

Configuration

Defaults
Digital Communication

continued
Protocol=HART, Modbus RTU,
Modbus ASCII

Configure Bell-202 Device Setup Configure RS-485


· Polling Address · Fault Setting · Protocol
· Loop Current Mode · Description · HART
· Burst Mode · User Message · Modbus RTU
· Burst Command · HART QV · Modbus ASCII
· Burst Variable 1–4 · HART Device ID · Printer
· Transmitter Serial No · Configure Protocol
· Baud Rate
· Parity
· Data Bits
Series 3000 Menus

· Stop Bits
· Polling Address
· Byte Order

Configuration and Use Manual 285


Series 3000 Menu Flowcharts

Figure F-12 Configuration menu continued

Management Menu

Configuration

Digital Communication

Protocol=Printer Protocol=Printer
Protocol=Printer Protocol=Printer
Protocol=Printer Discrete Batching Discrete Batching
Discrete Batching Custody Transfer (OIML)
Custody Transfer (NTEP) Custody Transfer (OIML/batch)

Configure RS-485 Configure RS-485 Configure RS-485 Configure RS-485 Configure RS-485
· Protocol (Printer) · Protocol (Printer) · Protocol (Printer) · Protocol (Printer) · Protocol (Printer)
· Configure Printer · Configure Printer · Configure Printer · Configure Printer · Configure Printer
· Printer Selection · Printer Selection · Printer Selection · Printer Selection · Printer Selection
· Pre Header Codes · Pre Header Codes · Header Line 1–2 · Header Line 1–2 · Header Line 1–2
· Header Line 1–2 · Header Line 1–2 · Footer · Footer · Footer
· Footer · Footer · Baud Rate · Baud Rate · Baud Rate
· Post Footer Codes · Post Footer Codes · Parity · Parity · Parity
· Baud Rate · Baud Rate · Data Bits · Data Bits · Data Bits
· Parity · Parity · Stop Bits · Stop Bits · Stop Bits
· Data Bits · Data Bits · Chars Per Second · Chars Per Second · Chars Per Second
· Stop Bits · Stop Bits · Print Buf Size · Print Buf Size · Print Buf Size
· Chars Per Second · Chars Per Second · Lines Per Page · Lines Per Page · Lines Per Page
· Print Buf Size · Print Buf Size · Number Of Tickets · Format W&M Ticket · Number Of Tickets
· Lines Per Page · Lines Per Page · Auto Print · Header Line 1–4 · Auto Print
· Disable Paper Check · Disable Paper Check · Disable Paper Check · Transfer Ticket · Format W&M Ticket
· Discrete Inputs · Discrete Inputs · Format W&M Ticket · Transfer Start (BOL) · Header Line 1–4
· Print Screen · Print Screen · Header Line 1–4 · Transfer Print Cond. · Transfer Ticket
· None · None · Footer · Transfer Form Feed · Transfer Start (BOL)
· Discrete Input 1–2 · Discrete Input 1–2 · Batch Start No. (BOL) · Alarm Occurred · Transfer Print Cond.
· Discrete Event 1–5 · Discrete Event 1–5 · Discrete Inputs · Num. Transfer Tickets · Transfer Form Feed
· Screens to Print · Batch Timeout · Print Screen · Footer · Alarm Occurred
· Process Monitor · Batch End Warn · None · Discrete Inputs · Num. Transfer Tickets
· Monitor Screen 1–5 · Batch Overrun · Discrete Input 1–2 · Transfer Print Screen · Footer
· Batch Ticket · Batch in Progress · Discrete Event 1–5 · None · Batch Start No. (BOL)
· All Config Data · Batch Pump · Batch Timeout · Discrete Input 1 · Discrete Inputs
· Active Alarm Log · Batch Primary Valve · Batch End Warn · Discrete Input 2 · Transfer Print Screen
· Alarm History · Screens to Print · Batch Overrun · Transfer Screen To Print · None
· Alarm Event Log · Process Monitor · Batch in Progress · Transfer Totals · Discrete Input 1
· Audit Event Log · Monitor Screen 1–5 · Batch Pump · Inventory · Discrete Input 2
· Print Process Monitor · Batch Ticket · Batch Primary Valve · Transfer & Inventory · Transfer Screen To Print
· Printer Test · All Config Data · Screens to Print · API Transfer & Inv(1) · Transfer Totals
· Active Alarm Log · Process Monitor · ED Transfer & Inv(2) · Inventory
· Alarm History · Monitor Screen 1–5 · Print Screen · Transfer & Inventory
· Alarm Event Log · Batch Ticket · None · API Transfer & Inv(1)
· Audit Event Log · All Config Data · Discrete Input 1–2 · ED Transfer & Inv(2)
· Print Process Monitor · Active Alarm Log · Discrete Event 1–5 · Print Screen
· Printer Test · Alarm History · Screens to Print · None
· Alarm Event Log · Process Monitor · Discrete Input 1–2
· Audit Event Log · Monitor Screen 1–5 · Discrete Event 1–5
· Print Process Monitor · Batch Ticket · Batch Timeout
· Printer Test · All Config Data · Batch End Warn
· Active Alarm Log · Batch Overrun
· Alarm History · Batch in Progress
· Alarm Event Log · Batch Pump
· Audit Event Log · Batch Primary Valve
· Print Process Monitor · Screens to Print
· Printer Test · Process Monitor
· Monitor Screen 1–5
· Batch Ticket
(1) Displayed only if the petroleum measurement application is · All Config Data
installed and approved for custody transfer. · Active Alarm Log
(2) Displayed only if the enhanced density application is installed and · Alarm History
· Alarm Event Log
approved for custody transfer. · Audit Event Log
· Print Process Monitor
· Printer Test

286 Micro Motion® Series 3000 MVD Transmitters and Controllers


Series 3000 Menu Flowcharts

Specifications – Model 3100


Figure F-13 Maintenance menu

Management Menu

Maintenance

Active Alarm Log Process Inventory Calibration Diagnostics Meter Verification(7)

Alarm History Mass Inventory Sensor Zero Read External Inputs Uncertainty Limit
Volume Inventory · Zero Time · Discrete Input 1–2 Counter
API Cor Vol Inventory(3) · Mass Flow Rate · Frequency Input Start Meter Verify
Alarm Event Log ED Std Vol Inventory(4) · Calibrate Zero · External Pressure(5) · Fault
ED Net Mass Inventory(4) · Restore Factory Zero · External Temperature(6) · Hold Last Value
Freq Input Inventory · View Current Data Simulate Outputs
Density · Discrete Output 1–3
· Low Density · Milliamp Output 1–2
· Density · Frequency Output
· D1

Relay Installation
· Calibrate Density
· High Density
· Density
· D2
Batch Inventory(1) Audit Trail(2) · Calibrate Density
· Flowing Density
· View Current Data
Preset 1–6 Current Event Number
mA Output Trim
View Event
· Milliamp Output 1–2
Date Search
· Trim 4.0 mA
· Trim 20.0 mA
Batch AOC(1)
Temperature
· Low Temperature
· High Temperature
· View Current Data
Density Curve Trim(4)
· Curve x
· ED Trim Offset
· ED Trim Slope

(1) Displayed only if the discrete batching application is installed.


(2) Displayed only if the custody transfer application is installed.

Defaults
(3) Displayed only if the petroleum measurement application is installed.
(4) Displayed only if the enhanced density application is installed.
(5) Displayed only if polling for pressure is configured.
(6) Displayed only if polling for temperature is configured.
(7) Displayed only if the meter verification option is available.

Series 3000 Menus

Configuration and Use Manual 287


288 Micro Motion® Series 3000 MVD Transmitters and Controllers
Appendix G
ProLink II and Pocket ProLink

ProLink II
G.1 Overview
ProLink II is a Windows-based configuration and management tool for Micro Motion transmitters. It
provides access to most Series 3000 functions and data. Pocket ProLink is a version of ProLink II that
runs on a Pocket PC.

375 Field Communicator


Note: Not all Series 3000 features and functions are available via ProLink II. For complete access,
use the Series 3000 display menus.
This appendix provides basic information for connecting and using ProLink II with your Series 3000
device. The following topics and procedures are discussed:
• Requirements – see Section G.2
• Configuration upload/download – see Section G.3
• Connecting to a Series 3000 device – see Section G.4
• ProLink II menus for Series 3000 devices – see Section G.4
For more information on installing or using ProLink II, see the ProLink II manual. For more
information on installing or using Pocket ProLink, see the Pocket ProLink manual. Instructions in this
appendix will refer only to ProLink II.

G.2 Requirements

Sample Tickets
To use ProLink II with a Series 3000 device, the following are required:
• ProLink II v2.5 or later for most basic functions
• ProLink II v2.9 or later for the most recent Series 3000 enhancements
• One of the following ProLink II installation kits:
- RS-232 to Bell 202 (HART) converter with tester and cables
- RS-232 to RS-485 (Modbus or HART) converter with tester and cables
- USB to Bell 202 (HART) converter with tester and cables
- USB to RS-485 (Modbus or HART) converter with tester and cables
Note: Windows drivers are required for correct operation of the USB converters. The drivers are
provided with the USB installation kits. Install the driver before connecting the converter or adapter.
If you do not, Windows will not recognize the device when it is plugged in.
Safety Labels

Note: If you are using the enhanced core processor and you connect directly to the core processor’s
RS-485 terminals, instead of to the transmitter, ProLink II v2.4 or later is required. This connection
type is sometimes used for troubleshooting.

Configuration and Use Manual 289


ProLink II and Pocket ProLink

G.3 ProLink II configuration upload/download


ProLink II provides a configuration upload/download function which allows you to save configuration
sets to your PC. This allows:
• Easy backup and restore of device configuration
• Easy replication of configuration sets
Micro Motion recommends that all Series 3000 configurations be downloaded to a PC as soon as the
configuration is complete.
To access the configuration upload/download function:
1. Connect ProLink II to your Series 3000 device as described in this chapter.
2. Open the File menu.
• To save a configuration file to a PC, use the Load from Xmtr to File option.
• To restore or load a configuration file to a Series 3000 device, use the Send to Xmtr from
File option.

G.4 Connecting from a PC to a Series 3000 device


For a Series 3000 device, ProLink II supports the following connection types:
• HART/Bell 202
• HART/RS-485
• Modbus/RS-485
• Service port (specialized Modbus/RS-485)
Notes: Due to the design of HART protocol, connections made using HART protocol are slower than
connections that use Modbus protocol. If you use HART protocol, you cannot open more than one
ProLink II window at a time.
The RS-485 terminals are available in service port mode only for the first 10 seconds after power-up.
If a service port connection is made during that period, the terminals remain in service port mode
until power is cycled. If no connection is made during that period, they revert to standard
Modbus/RS-485 mode using the RS-485 parameters configured in the Series 3000 device.
To connect to the Series 3000 device:
1. Determine the connection type you will use.
2. Identify the terminals for that connection type:
• All Bell 202 connections use the primary mA output terminals.
• All RS-485 connections use the RS-485 terminals.
See Figure 2-2 for the location of the terminal blocks on the different Series 3000 devices. See
Figure 2-3 to identify the terminals.
3. Connect the appropriate signal converter to your PC’s serial or USB port, using adapters as
required.
4. Connect the two leads of the signal converter leads to the appropriate terminals, or to any point
on the network.

290 Micro Motion® Series 3000 MVD Transmitters and Controllers


ProLink II and Pocket ProLink

5. Add resistance as required.


• For HART/Bell 202 connections, the signal converter must be connected across a
resistance of 250–600  . See the ProLink II manual for more information.

ProLink II
• For RS-485 connections, additional resistance may or may not be required. See the
ProLink II manual for more information.
6. Start ProLink II and click Connection > Connect to Device. In the Connect dialog box:
a. Select the protocol for your connection type. The ProLink II dialog box is updated to
reflect your choice.
b. Set other required parameters.
c. Click Connect.
7. If you are using an RS-485 connection, the RS-485 terminals may not be in the desired mode.
To change mode:

375 Field Communicator


a. Power-cycle the device.
b. To connect in service port mode, click Connect within the 10-second interval after
power-up.
c. To connect in RS-485 mode, wait more than 10 seconds, then click Connect.

G.5 ProLink II menu flowcharts


This section contains flowcharts for the ProLink II main menu and the configuration menu. These
flowcharts are based on:
• ProLink II v2.6
• Series 3000 device software rev7.0

Sample Tickets
Safety Labels

Configuration and Use Manual 291


ProLink II and Pocket ProLink

Figure G-1 ProLink II main menu

File View Connection ProLink Tools Plug-ins

Load from Xmtr to File Connect to Device Gas Unit Configurator Data Logging(1)
Save to Xmtr from File Disconnect
Meter Verification Enable/Disable
License Custody Transfer
Options
• ProLink II Language
• Error Log On
Preferences
• Use External Temperature
• Enable Inventory Totals Reset
Configuration
• Enable External Pressure Compensation
Output Levels
• Copper RTD
Process Variables
Status
Installed options
Alarm Log
Diagnostic Information
Calibration
Test
ED Totalizer Control
Totalizer Control
Core Processor Diagnostics
Finger Print
API Process Variables
ED Process Variables
PPI Variables
Batcher Control

(1) For information about using Data Logger, refer to the ProLink II manual.

292 Micro Motion® Series 3000 MVD Transmitters and Controllers


ProLink II and Pocket ProLink

Figure G-2 ProLink II configuration menu

ProLink >

ProLink II
Configuration

Additional configuration options

Flow Density Temperature Pressure

• Flow direction • Density units • Temp units • Flow factor


• Flow damp • Density damping • Temp cal factor • Dens factor
• Flow cal • Slug high limit • Temp damping • Cal pressure
• Mass flow cutoff • Slug low limit • External temperature • Pressure units
• Mass flow units • Slug duration • External pressure
• Vol flow cutoff(1) • Low density cutoff
• Vol flow units(1) • K1
• Vol flow type • K2
• Std gas vol flow cutoff(2)(3) • FD

375 Field Communicator


• Std gas flow units(2) • D1
• Std gas density(2) • D2
• Temp coeff (DT)
Gas wizard(2)

• Mass factor
• Dens factor
T Series Device Display
• Vol factor
• FTG • Tag Screen 1
• Flow switch variable
• FFQ • Date • Var 1...4
• Flow switch setpoint
• DTG • Descriptor
• DFQ1 • Message Screen 2
• DFQ2 • Sensor type • Var 1...4
• K3 • Transmitter serial number
• D3 • Floating pt ordering Screen 3
• D4 • Add comm resp delay • Var 1...4
• K4
Restore factory configuration Screen 4
• Var 1...4
Digital comm settings
• Fault setting Screen 5
• HART address • Var 1...4

Sample Tickets
• Loop current mode
• HART device ID Display precision
• Modbus address • Var
• Enable write protection • Number of decimals
• Custody transfer approved
Update rate
• Response time Display language

Burst setup
• Enable burst
• Burst cmd
• Burst var 1...4

(1) Displayed only if Volume Flow Type = Liquid Volume.


(2) Displayed only if Volume Flow Type = Gas Standard Volume.
(3) Displayed only on systems with the enhanced core processor.
Safety Labels

Configuration and Use Manual 293


ProLink II and Pocket ProLink

Figure G-3 ProLink II configuration menu continued

ProLink >
Configuration

Additional configuration options

Analog output Frequency Sensor simulation(1)

Primary/secondary output • Tertiary variable • Enable/disable


• PV/SV is • Scaling method
• Lower range value • Freq factor Mass flow
• Upper range value • Rate factor • Wave form
• AO cutoff • Pulses per unit • Fixed value
• AO added damp • Units per pulse • Period
• LSL • Freq pulse width • Minimum
• USL • Last measured value timeout • Maximum
• Min span • Freq output power
• AO fault action • Freq fault action Density
• AO fault level • Freq fault level • Wave form
• Freq output polarity • Fixed value
• Last measured value timeout • Period
• Minimum
• Maximum

Temperature
Frequency input Discrete output Discrete input • Wave form
• Fixed value
• Scaling method Discrete output 1/2/3 Assignment • Period
• Freq factor • DO1/2/3 assignment • Minimum
• Rate factor • DO1/2/3 polarity Polarity • Maximum
• Pulses per unit • DO1/2/3 fault action • DI1 polarity
• Units per pulse • DI2 polarity

• K-factor
• Units

(1) Displayed only on systems with the enhanced core processor.

294 Micro Motion® Series 3000 MVD Transmitters and Controllers


ProLink II and Pocket ProLink

Figure G-4 ProLink II configuration menu continued

ProLink >

ProLink II
Configuration

Additional configuration options

System Special units RS-485 Discrete events

Real-time clock • Base mass unit • Protocol • Event name


• Base mass time • Baud rate • Event type
Security • Mass flow conv fact • Parity • Process variable
• Enable security • Mass flow text • Stop bits • Low setpoint (A)
• Maintenance password • Mass total text • High setpoint (B)
• Configuration password • Choose typical
• Enable alarm security(1) • Base vol unit(3) HART settings
• Alarm password(1) • Base vol time(3)
• Totalizer reset options(1) • Vol flow conv fact(3)

375 Field Communicator


• Vol flow text(3)
Weights and measures • Vol total text(3)
• Approval
• Software rev • Base gas vol unit(4)
• Enable OIML CT approval for API(2) • Base gas vol time(4)
• Enable OIML CT approval for ED(2) • Gas vol flow conv fact(4)
• Enable OIML CT approval for process • Gas vol flow text(4)
monitor(2) • Gas vol total text(4)
• Enable OIML CT approval for discrete
batcher(2)

Polled variables Sensor Variable mapping Alarm

Polled variable 1/2 • Sensor s/n • PV is • Alarm


• Polling control • Sensor model • SV is • Severity
• External tag • Sensor matl • TV is
• Variable type • Liner matl • QV is
• Current value • Flange

Sample Tickets
(1) Available only if the custody transfer application is installed.
(2) Available only if Approval is set to OIML.
(3) Displayed only if Vol Flow Type is set to Liquid.
(4) Displayed only if Vol Flow Type is set to Gas Standard.

Safety Labels

Configuration and Use Manual 295


ProLink II and Pocket ProLink

Figure G-5 ProLink II configuration menu continued

ProLink >
Configuration

API setup(1) Discrete batch(2) Printer

• Table type Flow source Printer


• Units • Type
Control options • Data bits
(3) · Enable batch • Chars/sec
ED setup · Count up • Buffer size
· Enable AOC • Disable paper out detection
Global config · Lockout target
· Active curve · Auto print at batch end Ticket
· Derived variable · Reset on start • Batch start number (BOL)
· Reset all curve info · Enable end warning • No. of batch tickets
· Lock/unlock ED curves · Enable overrun • Transfer start (BOL)
· Ignore source alarms • Transfer type
Curve specific config · No-flow timeout • No. of transfer tickets
· Curve configured · Number of stages • Transfer type
· Curve name · Number of decimals • Use form feed
· Reference temperature · Maximum target • Print with non-zero flow
· Water reference temperature · Alarm timeout • Alarm occurrence on transfer
· Water reference density · Configure presets by ticket
· Trim slope
· Trim offset Configure presets Header and footer
· Preset number • Pre header
Extrapolation · Preset name • Line #1 … #4
· Alarm limit · Enable preset • Line feeds #1 … #4
· Enable density low · Open primary • Font size #1 … #4
· Enable density high · Open secondary • Footer line
· Enable temperature low · Close primary • Post footer
· Enable temperature high · End warning • Footer line feeds
· Density curve • Footer font size
Concentration · Overrun
· Units · Preset target Print request configuration
· Special unit string • Process monitor with statistics
• Process monitor
• Monitor screen 1 … 5
ED curve(3) • Batch ticket
• All configuration data
Process fluid density at specified temperature • Alarm history
and concentration • Active alarm log
· Curve being configured • Audit trail event log
· Curve fit max order • Printer test
· Temperature isotherms • Alarm event log
· Concentration points
· Curve data points

Curve fit results


· Accuracy

Process fluid density at reference temperature


and specified concentration
· Reference temperature
· Concentration points
· Curve data points

(1) Displayed only if the petroleum measurement application is installed.


(2) Displayed only if the discrete batch application is installed.
(3) Displayed only if the enhanced density application is installed.

296 Micro Motion® Series 3000 MVD Transmitters and Controllers


Appendix H
375 Field Communicator

ProLink II
H.1 Overview
This appendix provides basic information for connecting and using the 375 Field Communicator with
your Series 3000 device. The following topics and procedures are discussed:
• Requirements – see Section H.2

375 Field Communicator


• Connecting to a Series 3000 device – see Section H.3
• Communicator menus – see Section H.4

H.2 DD requirements
To use the 375 Field Communicator with a Series 3000 device, the following device description (DD)
must be loaded to your Communicator: Micro Motion 3000 Mass flo v7 DD v2
This DD does not provide complete access to the Series 3000 features, functions, and data. For
complete access, use the Series 3000 display menus.

H.3 Connecting from the 375 Field Communicator to a Series 3000 device
To connect to the Series 3000 device:
1. Identify the primary mA output terminals on your Series 3000 platform.

Sample Tickets
See Figure 2-2 for the location of the terminal blocks on the different Series 3000 devices. See
Figure 2-3 to identify the terminals.
2. Attach the leads from the Communicator to the primary mA output terminals.
3. Add resistance as required.
4. Follow standard Communicator procedures to connect to the Series 3000 device.

H.4 Communicator menu flowcharts


This section contains flowcharts for most Communicator menus. These flowcharts are based on:
• Micro Motion 3000 Mass flo v7 DD v2
• Series 3000 device software rev7.0
The flowcharts start from the Communicator Online menu.
Safety Labels

Configuration and Use Manual 297


375 Field Communicator

Figure H-1 Communicator Process Vars menu

On-Line Menu >


1 Process variables

Additional options
1 2

View fld dev vars View output vars

1 View basic vars 1 View PV-Analog 1


2 View external vars 2 View SV-Analog 2
3 View FI vars 3 View TV-Freq/DO
4 View API vars 4 View QV(1)
5 View ED vars 5 View discrete event
6 View batcher vars

1 Discrete event 1
1 Current ED curve 2 Discrete event 2
1 Mass flo 2 ED std vol flo 5 3 Discrete event 3
2 Mass totl 3 ED std vol totl 4 Discrete event 4
3 Mass inventory 4 ED std vol inv 5 Discrete event 5
4 Temp 5 ED net mass flo
1 5 Dens 6 ED net mass totl
6 Vol flo 7 ED net mass inv Value
5
7 Vol totl 8 ED net vol flo Type
8 Vol inventory 9 ED net vol totl Setpoint A
ED net vol inv Setpoint B
ED dens at ref Status
1 Pressure ED dens (SGU)
2
2 Temp ED dens (Baume)

1 FI flow rate
1 name unit
3 2 FI total
3 FI inv 2 Batch total
3 Batch target
4 Preset 1 inv
1 TC Dens 6 5 Preset 2 inv
2 TC vol 6 Preset 3 inv
3 TC vol totl 7 Preset 4 inv
4 4 TC vol inv 8 Preset 5 inv
5 TC avg temp 9 Preset 6 inv
6 TC avg dens
7 CTL

298 Micro Motion® Series 3000 MVD Transmitters and Controllers


375 Field Communicator

Figure H-2 Communicator Process Vars menu continued

On-Line Menu >

ProLink II
1 Process variables

3 4 5 6

View status Totlizer contrl Batcher cntrl Custody trf tot reset
opt
1 Mass totl 1 None unit
2 Vol totl 2 Batch total
3 Start totalizer 3 Batch target
4 Stop totalizer 4 Batcher cntrl
5 Reset all totals
6 Reset mass total
7 Reset volume total 1 Start batch
2 Stop batch
3 End batch

375 Field Communicator


4 Inhibit batch
4 5 Resume batch
6 Reset batch
7 Inhibit totalizer
8 Print batch ticket

Sample Tickets
Safety Labels

Configuration and Use Manual 299


375 Field Communicator

Figure H-3 Communicator Diag/Service menu

On-Line Menu >


2 Diag/Service

1 2 3 4

Test/Status Calibration Perform diagnostic action Loop test

1 View status 1 Auto zero 1 Reset alarm log 1 Fix analog out 1
2 Self test 2 Density cal 2 Acknowledge all alarms 2 Fix analog out 2
3 Meter verification 3 Reset Power On time 3 Fix frequency out
4 Restore factory configuration 4 Fix discrete out 1
5 Reset all ED curve information 5 Fix discrete out 2
6 Enable write protect 6 Fix discrete out 3
7 Disable write protect
8 Restore factory zero
9 Exit

5 6 7 8

Trim outputs Read outputs Read inputs Test points

1 Trim Analog out 1 1 Pres freq 1 Read discrete in 1 Status words


2 Trim analog out 2 2 Read DO 1 2 Read DI 2 2 LPO
3 Scaled AO1 trim 3 Read DO 2 3 FI freq 3 RPO
4 Scaled AO2 trim 4 Read DO 3 4 Tube
5 Drive
6 Board temperature
7 Meter temp. T-Series
8 Live zero flow
9 Input voltage
Actual target amplitude
Average sensor temp
Min sensor temp
Max sensor temp
Max electronics temp
Min electronics temp
Average electronics temp
Wire RTD
Meter RTD
Line RTD
Power cycle count
Power on time
Drive current

300 Micro Motion® Series 3000 MVD Transmitters and Controllers


375 Field Communicator

Figure H-4 Communicator Basic Setup menu

On-Line Menu >

ProLink II
3 Basic Setup

1 2 4 6
Tag PV unit 3 SV unit 5 Freq scaling

1 FO scale method
· Freq = flow
Anlog 1 range values Anlog 2 range values · Pulses/Unit
· Units/Pulse
1 PV URV 1 PV URV
2 PV LRV 2 PV LRV 2 FO scaling(1)
· TV freq factor
· TV rate factor
· TV pulses/unit

375 Field Communicator


· TV units/pulse

(1) Options displayed depend on FO Scale Method.

Sample Tickets
Safety Labels

Configuration and Use Manual 301


375 Field Communicator

Figure H-5 Communicator Detailed Setup menu

On-Line Menu >


4 Detailed Setup

Additional options
1 2

Charize sensor Config fld dev vars

1 Sensor selection 1 Flow


2 Flow 2 Density
3 Density 3 Temperature
4 Temp cal factor 4 Pressure
5 Pressure compensation 5 API
6 Meter factors 6 Batcher
7 Polling setup
8 External temp
1 Mass flow unit
2 Mass flow cutoff
1 T-Series 3 Spcl mass units
1
2 Other 1 Mass factor 4 Vol flow unit 1 Current preset
1 5 Vol flow cutoff
6 2 Vol factor 2 Batch flow source
3 Dens factor 6 Spcl vol units 3 Batch timeout
1 FlowCal(1) 7 Flo direction 4 Reset on start
8 Flo damp 5 Counting up
2 1 FCF(2) 1 Poll control 6 Ignore alarms
2 FTG(2) 2 External device tag 1 6 7 Alarm timeout
3 FFQ(2) 7 3 Polled var 1 8 Preset 1 setup
4 External device tag 2 9 Preset 2 setup
5 Polled var 2 1 Density unit Preset 3 setup
1 D1 2 Density damp Preset 4 setup
2 K1 3 Density cutoff Preset 5 setup
2 4 Slug low limit
3 D2 1 Enable ext temp Preset 6 setup
8 5 Slug high limit
4 K2 2 Static temperature
5 Temp coeff(1) 6 Slug duration
5 DTG(2) 1 Enabled
6 FD(1) 2 Target
3 6 DFQ1(2) 3
1 Temp unit 3 Source units
7 DFQ2(2) 2 Temp damp 4 ED curve
8 DT(2)
9 FD(2)
· D3(2) 4 1 Pressure unit
· K3(2)
· D4(2)
· K4(2) 1 API setup
2 Enable API
5 3 API 2440 CTL table (read-only)
1 Enable pressure 4 API thermal exp (read-only)
2 Flow factor 5 API ref temp (read-only)
5 3 Dens factor
4 Flowcal pressure
5 Static pressure

(1) All sensors except T-Series.


(2) T-Series sensors only.

302 Micro Motion® Series 3000 MVD Transmitters and Controllers


375 Field Communicator

Figure H-6 Communicator Detailed Setup menu continued

ProLink II
On-Line Menu >
4 Detailed Setup

Additional options
3 4

Config outputs Config inputs

1 AO setup 1 Discrete actions


2 FO output 2 DI setup
3 DO setup 3 FI setup
4 HART output
5 RS485 setup
6 Fault timeout 1 Assign discretes
2 Read action assign (read-only)
1 3 Action assignments (read-only)
4 PrintScreen assign

375 Field Communicator


1 PV is 1 Var assignment
2 Range values 2 Poll addr 1 Start sensor zero
3 PV AO cutoff 3 Num preambles 2 Reset mass total
4 PV AO added damp 4 Burst mode 3 Reset volume total
5 AO1 fault setup 4 5 Burst option 4 Reset API ref vol
1
6 SV is 6 Burst var 1 5 Reset all totals
7 Range values 7 Burst var 2 6 Reset ED ref vol
8 SV AO2 cutoff 8 Burst var 3 7 Reset ED net mass
9 SV AO added damp 9 Burst var 4 8 Reset ED net vol
AO2 fault setup 9 Start/stop all totals
1 End batch
1 PV is
2 SV is Inhibit batch
1 TV is 1 Inhibit batch tot
2 FO scale method(1) 3 TV is
4 QV is Reset batch
3 TV freq factor Resume batch
2 4 TV rate factor Start batch
5 Max pulse width 1 RS485 protocol Stop batch
6 FO fault indicator 2 RS485 baudrate Increment preset
7 FO fault value 3 RS485 parity Increment ED curve
5 4 RS485 stop bits Print screen

Sample Tickets
1 DO1 is 5 Modbus address
2 DO1 polarity 6 Comm fault indicator
7 Printer setup Process monitor
3 DO1 fault indicator Batch ticket
4 DO2 is All config data
3 5 DO2 polarity 4 Alarm history
6 DO2 fault indicator Active alarm log
7 DO3 is Audit trail
8 DO3 polarity
9 DO3 fault indicator
1 DI1 polarity
2
2 DI2 polarity

1 FI scale method(1)
2 Freq factor
3 3 Rate factor
4 FI unit
5 K factor

(1) Options displayed depend on FO or FI Scale Method.


Safety Labels

Configuration and Use Manual 303


375 Field Communicator

Figure H-7 Communicator Detailed Setup menu continued

On-Line Menu >


4 Detailed Setup

5 6 7

Device information Config discrete event Config alarms

1 Tag 1 Discrete event 1 1 Write severity


2 Descriptor 2 Discrete event 2 2 Read severity (read-only)
3 Message 3 Discrete event 3 3 Review severity
4 Date 4 Discrete event 4 4 Acknowledge the selected alarm
5 Device id 5 Discrete event 5 5 Alarm history
6 Final assembly num 6 Refresh alarm history
7 Sensor s/n
8 Sensor model 1 Discrete event var
9 Output option board 2 Discrete event type
Construction materials 3 Setpoint A
Revision #s 4 Setpoint B
Real-time clock

8 9

Display setup Setup simulation mode Modbus data

1 Enable/disable 1 Simulation mode enable/disable 1 Read Modbus data value


2 Display variables 2 Simulate mass flow 2 Write Modbus data value
3 Display precision 3 Simulate temperature
4 Simulate density
5 Mass flow simulation mode (read-only)
6 Mass flow fixed value (read-only)
1 Update period
1 7 Mass flow minimum amplitude (read-only)
2 Display language
8 Mass flow maximum amplitude (read-only)
9 Mass flow period of waveform (read-only)
1 Screen 1, Line 1 Temperature simulation mode (read-only)
2 Screen 1, Line 2 Temperature fixed value (read-only)
2 … Temperature minimum amplitude (read-only)
Screen 5, Line 4 Temperature maximum amplitude (read-only)
Temperature period of waveform (read-only)
Density simulation mode (read-only)
Density fixed value (read-only)
1 Var code varx
Density minimum amplitude (read-only)
3 2 Precision varx
Density maximum amplitude (read-only)

Density period of waveform (read-only)

304 Micro Motion® Series 3000 MVD Transmitters and Controllers


Appendix I
Sample Tickets

ProLink II
I.1 Overview
This appendix provides sample tickets for the following ticket types:
• Standard tickets
- Process monitor tickets – see Figure I-1

375 Field Communicator


- Alarm tickets – see Figure I-2
- Configuration ticket and audit event log ticket – see Figure I-3
• Batch tickets – see Figure I-4
• Batch (NTEP) tickets
- Original tickets – see Figure I-5
- Duplicate tickets – see Figure I-6
• Transfer (OIML) tickets
- No alarm banner – see Figure I-7
- Alarm banner – see Figure I-8
- Process variable approved – see Figure I-9
• Batch (OIML) tickets
- Original tickets – see Figure I-10

Sample Tickets
- Duplicate tickets – see Figure I-11

Safety Labels

Configuration and Use Manual 305


Sample Tickets

I.2 Standard tickets

Figure I-1 Typical process monitor tickets

No custody transfer Custody transfer installed


With Stats Without Stats

HEADER 1 Not A Legal Receipt

HEADER 2 HEADER 1
M. RESET HEADER 2
29-SEP-2003 10:58:27 M. RESET
Mass Flow Rate 29-SEP-2003 10:58:27
g/s Mass Flow Rate
Current_Value:0.000000 g/s
Average:-0.043297 Current_Value:0.000000
Maximum:56:830570 Mass Total
Minimum:-0.145275 g
Mass Total Current_Value:628050.562500
g Volume Flow Rate
Current_Value:628050.562500 l/s
Volume Flow Rate Current_Value:0.000000
l/s Volume Total
Current_Value:0.000000 l
Average:-0.000035 Current_Value:744.410522
Maximum:0.046584 Density
Minimum:-0.000107 g/cm3
Volume Total Current_Value:1.219813
l FOOTER
Current_Value:744.410522 Not A Legal Receipt
Density
g/cm3
Current_Value:1.219813
Average:1.219888839
Maximum:1.262375
Minimum:1.216220
FOOTER

306 Micro Motion® Series 3000 MVD Transmitters and Controllers


Sample Tickets

Figure I-2 Typical alarm tickets


Active alarm log Alarm history

ProLink II
HEADER 1 HEADER 1
HEADER 2 HEADER 2
M. RESET M. RESET
29-SEP-2003 13:27:33 29-SEP-2003 13:27:33
Active Alarm Log Historical Alarm Log
Temp. Out-of-Range Drive Overrange
INFO 17-JAN-07 14:14:53 Cnt 13
Sensor RTD Error Post 29-SEP-3 13:27
INFO 17-JAN-07 14:14:53 Clr 29-SEP-3 13:27

375 Field Communicator


Meter RTD Error Security Breach
INFO 17-JAN-07 14:14:53 Cnt 11
API: Temp Overrange Post 29-SEP-3 11:02
FAULT 17-JAN-07 14:14:53 Clr 29-SEP-3 11:03
FOOTER Xmtr Initializing
Cnt 10
Post 29-SEP-3 13:27
Clr 29-SEP-3 13:27
FOOTER

Alarm event log

HEADER 1
HEADER 2

Sample Tickets
M. RESET
28-MAR-2007 16:36:45
Alarm Event Log
Drive Overrang
Post: 28-MAR-07 16:36
Power Reset
Clr: 28-MAR-07 16:36
Power Reset
Post: 28-MAR-07 16:36
Security Breach
Post: 28-MAR-07 16:36
FOOTER
Safety Labels

Configuration and Use Manual 307


Sample Tickets

Figure I-3 Configuration ticket and audit event log ticket

HEADER 1 HEADER 1
HEADER 2 HEADER 2
M.RESET HEADER 3
29-SEP-2003 1:05:03 HEADER 4
::Frequency Output:: M. RESET
0 29-SEP-2003 1:05:03
FO Active Audit Trail
1 001 4-JAN-2003 15:58:58
FO Polarity MA01 Source
1 0
FO Flow Source 001 4-JAN-2003 15:58:58
0 MA02 Source
FO Fault Frequency 0
15000.000000 001 4-JAN-2003 15:59:01
FO Frequency Factor FO Flow Source
1000.000000 5
. . . 001 4-JAN-2003 15:59:01:
FOOTER Flow Direction
2
FOOTER

For the tickets shown in Figure I-3, codes are used for all items which are selected from a selection
list. For example, FO Flow Source code 0 represents mass flow rate, and FO Flow Source code 5
represents volume flow rate.
Selection lists and codes are documented in the following manuals:
• Using Modbus Protocol with Micro Motion Transmitters, November 2004, P/N 3600219,
Rev. C (manual plus map)
• Modbus Mapping Assignments for Micro Motion Transmitters, October 2004, P/N 20001741,
Rev. B (map only)
In the audit event log ticket:
• The first date and time represent the time at which the ticket print job was initiated.
• All other dates and times represent the time at which the configuration parameter was
changed.

308 Micro Motion® Series 3000 MVD Transmitters and Controllers


Sample Tickets

I.3 Batch tickets

Figure I-4 Typical batch tickets

ProLink II
Custody transfer application not installed Custody transfer application installed,
discrete batch application not approved

Not A Legal Receipt


HEADER 1 HEADER 1
HEADER 2 HEADER 2
M. RESET
29-SEP-2003 11:05:01 M. RESET
Preset 1 15-MAR-2005 11:05:01
Units: g Preset 1
Units: g

375 Field Communicator


Actual: 1324.5 g Actual: 1324.5 g
Target: 1300.9 g
FOOTER Target: 1300.9 g
FOOTER
Not A Legal Receipt

I.4 Batch (NTEP) tickets

Figure I-5 Original tickets


Data secured Data unsecured

Sample Tickets
HEADER 1 HEADER 1
HEADER 2 HEADER 2
HEADER 3 HEADER 3
HEADER 4 HEADER 4
M. RESET M. RESET
15-MAR-2005 10:57:23 15-MAR-2005 10:57:23

Total: 1162.0591 g Total: 1324.5 g


Batch Count: (8) Batch Count: (9)
FOOTER
SECURITY BREACH
Not A Legal Receipt
Safety Labels

FOOTER

Configuration and Use Manual 309


Sample Tickets

Figure I-6 Duplicate tickets


Data secured Data unsecured

HEADER 1 HEADER 1
HEADER 2 HEADER 2
HEADER 3 HEADER 3
HEADER 4 HEADER 4
M. RESET M. RESET
15-MAR-2005 10:57:23 15-MAR-2005 10:57:23

Total: 1162.0591 g Total: 1324.5 g


Batch Count: (8) Batch Count: (9)
DUPLICATE_RECEIPT DUPLICATE_RECEIPT
FOOTER
SECURITY BREACH
Not A Legal Receipt
FOOTER

I.5 Transfer (OIML) tickets


For the tickets shown in Figure I-7, there is no way to distinguish between the following:
• No alarm occurred.
• An alarm occurred (possibly a security breach), but the Alarm Occurred parameter was
disabled.
For the tickets shown in Figure I-8, the alarm may or may not be a security breach. The security
breach banner will appear on the Series 3000 display, if appropriate.

310 Micro Motion® Series 3000 MVD Transmitters and Controllers


Sample Tickets

Figure I-7 No alarm banner


Transfer complete Transfer incomplete

ProLink II
HEADER 1 HEADER 1
HEADER 2 HEADER 2
HEADER 3 HEADER 3
HEADER 4 HEADER 4
M. RESET M. RESET
15-MAR-2005 10:57:23 15-MAR-2005 10:57:23
Transfer (BOL): Transfer (BOL):
31 Complete 500 Not Complete
Mass Transfer Mass Flow Rate

375 Field Communicator


* 0.906 kg* 0.0513 g/s
Volume Transfer Volume Flow Rate
* 0.3 US gal* 0.0001 l/s
FOOTER Mass Transfer
53434.1016 g
Volume Transfer
60.3386 l
FOOTER

Sample Tickets
Safety Labels

Configuration and Use Manual 311


Sample Tickets

Figure I-8 Alarm banner


Transfer complete Transfer incomplete

HEADER 1 HEADER 1
HEADER 2 HEADER 2
HEADER 3 HEADER 3
HEADER 4 HEADER 4
M. RESET M. RESET
15-MAR-2005 10:57:23 15-MAR-2005 10:57:23
Transfer (BOL): Transfer (BOL):
36 Complete 501 Not Complete
Mass Transfer Mass Flow Rate
* 0.000 kg* 0.0513 g/s
Mass Inventory Volume Flow Rate
297.18 kg 0.0001 l/s
Volume Transfer Mass Transfer
* 0.0 US gal* 53434.1016 g
Volume Inventory Volume Transfer
137.3086 US gal 70.3386 l
Alarm occurred during the Alarm occurred during the
Transfer. Transfer.
FOOTER FOOTER

312 Micro Motion® Series 3000 MVD Transmitters and Controllers


Sample Tickets

Figure I-9 Process variable approved


Approved variable: Mass total Approved variable: Volume total
Transfer complete Transfer incomplete

ProLink II
HEADER 1 HEADER 1
HEADER 2 HEADER 2
HEADER 3
HEADER 3 HEADER 4
HEADER 4 M. RESET
M. RESET 28-MAR-2007 16:41:43
28-MAR-2007 16:42:01 Transfer (BOL):
Transfer (BOL): 2 Not Complete
2 Complete

375 Field Communicator


Mass Flow Rate
Mass Flow Rate 0.1007 kg/s
0.0000 kg/s Volume Flow Rate
Volume Flow Rate 0.1020 l/s
0.0000 l/s Mass Transfer
Mass Transfer 5.1050 kg
* 5.1050 kg* Volume Transfer
Volume Transfer 5.1718 l
5.1718 l
FOOTER
FOOTER

I.6 Batch (OIML) tickets

Sample Tickets
Figure I-10 Original tickets
Data secured Data unsecured

HEADER 1 HEADER 1
HEADER 2 HEADER 2
HEADER 3 HEADER 3
HEADER 4 HEADER 4
M. RESET M. RESET
15-MAR-2005 10:57:23 15-MAR-2005 10:57:23

Total: 1162.0591 g Total: 1324.5 g


Safety Labels

Batch Count: (8) Batch Count: (9)


FOOTER
SECURITY BREACH
Not A Legal Receipt
FOOTER

Configuration and Use Manual 313


Sample Tickets

Figure I-11 Duplicate tickets

Data secured Data unsecured

HEADER 1 HEADER 1
HEADER 2 HEADER 2
HEADER 3 HEADER 3
HEADER 4 HEADER 4
M. RESET M. RESET
15-MAR-2005 10:57:23 15-MAR-2005 10:57:23

Total: 1162.0591 g Total: 1324.5 g


Batch Count: (8) Batch Count: (9)
DUPLICATE_RECEIPT DUPLICATE_RECEIPT
FOOTER
SECURITY BREACH
Not A Legal Receipt
FOOTER

314 Micro Motion® Series 3000 MVD Transmitters and Controllers


Appendix J
Label Maintenance and Replacement

ProLink II
J.1 Maintaining and replacing labels
Micro Motion product safety labels have been designed in accordance with the voluntary standard
ANSI Z535.4. If the labels illustrated below are illegible, damaged, or missing, promptly have new
ones installed.

375 Field Communicator


Contact Micro Motion for replacement labels. Contact information is provided on the title page of this
manual.

J.2 Labels on the device


The Series 3000 platform may include the safety labels illustrated below.

Figure J-1 Safety labels

Label number 3300215

Sample Tickets
Label number 3100436

Safety Labels

Label number 3300709

Configuration and Use Manual 315


316 Micro Motion® Series 3000 MVD Transmitters and Controllers
Appendix K

Return Policy
Return Policy

K.1 General guidelines


Micro Motion procedures must be followed when returning equipment. These procedures ensure legal
compliance with government transportation agencies and help provide a safe working environment for
Micro Motion employees. Failure to follow Micro Motion procedures will result in your equipment
being refused delivery.
Information on return procedures and forms is available on our web support system at

NE 53 History
www.micromotion.com, or by phoning Micro Motion customer service.

K.2 New and unused equipment


Only equipment that has not been removed from the original shipping package will be considered new
and unused. New and unused equipment requires a completed Return Materials Authorization form.

K.3 Used equipment


All equipment that is not classified as new and unused is considered used. This equipment must be
completely decontaminated and cleaned before being returned.
Used equipment must be accompanied by a completed Return Materials Authorization form and a
Decontamination Statement for all process fluids that have been in contact with the equipment. If a
Decontamination Statement cannot be completed (e.g., for food-grade process fluids), you must
include a statement certifying decontamination and documenting all foreign substances that have

Index
come in contact with the equipment.

Configuration and Use Manual 317


318 Micro Motion® Series 3000 MVD Transmitters and Controllers
Appendix L

Return Policy
NE 53 History

L.1 Overview
This appendix documents the change history of the Series 3000 MVD device software.

L.2 Software change history


Table L-1 describes the change history of the software. Operating instructions are English versions.

NE 53 History
Table L-1 Series 3000 device software change history

Software Operating
Date version Changes to software instructions
10/2003 6.00 Initial release 20001266A
7/2005 6.10 Software expansion 20001266B
Independent reset of inventory totals
Added display of enhanced density curve fit result
Added support for Katakana language on the display
Added configurable pre-header and post-footer control codes for
printing
Software adjustment
Improved accuracy when batching on frequency input

Index
Allow batch to be ended when flow is present
Clarified the behavior of certain Modbus calibration coils
HART Tri-Loop and other communication improvements
HART support of concentration units
Clarified state of discrete outputs during device startup following a
power on condition.
Feature addition
Added support for FDW printer protocol
Added compliance with OIML custody transfer requirements

Configuration and Use Manual 319


NE 53 History

Table L-1 Series 3000 device software change history continued

Software Operating
Date version Changes to software instructions
3/2007 7.00 Software expansion 20001266C
Added flow switch to selection list for discrete output assignment
Added ability to configure discrete output fault indication
Added several HART and Modbus commands
Added ability to restore the factory configuration
Added ability to restore the factory zero value
Added alarm event log
Added ability to write protect configuration data
Added new items to selection list for mA output source assignment
Range values for mA output stored separately for each process
variable
Expanded custody transfer application for independent
implementation of NTEP and OIML compliance
Expanded custody transfer (OIML) features to include configurable
approval of discrete batcher, enhanced density, API, and process
monitor applications; added ability to mark OIML-approved process
variables with asterisks, added display of firmware checksum of core
processor and transmitter, added display of W&M version number,
expanded discrete output source selection to include PPI Display
Error, added configurable password protection of alarms menu
Added ability to configure the display update rate
Printer output expanded to include alarm event history
Expanded HART command 33 to include frequency input raw
frequency
Added ability to use discrete input to inhibit flow measurement by
discrete batcher
Added active enhanced density curve to selection list for process
monitor display variables
Added discrete events for Model 3300 controller
Added core processor ETO number to applications list on display
Added ability to configure Loop Current Mode
Added ability to configure text strings used to identify totals and
inventories
Added 304 Stainless Steel to selection of sensor material

320 Micro Motion® Series 3000 MVD Transmitters and Controllers


NE 53 History

Table L-1 Series 3000 device software change history continued

Software Operating

Return Policy
Date version Changes to software instructions
Software adjustment
Clarified range checking when writing D1 and D2 values for T-Series
sensors
Clarified posting of Start Not Okay alarm
Allow discrete batch to be started when milliamp output is fixed
Allow batch target to be changed from batcher process screen when
no decimal point is displayed (precision set to zero)
Removed printing of character when power is cycled
Allow batch preset selection to be changed when device is secured for
custody transfer.
Clarified use of HART command 180 for Model 3300 controller for
writing output fault parameters

NE 53 History
Clarified default derived variable when standard curves feature is
enabled
Expanded range of frequency input total and frequency input
inventory
Feature addition
Added configurable alarm severity
Added gas standard volume functionality
Added support for meter verification option
11/2009 8.00 Software expansion 20001266CA
Added Field Verification Zero process variable
Updated meter verification to add support for “continue measurement”
option, scheduling, and execution from a discrete input or discrete
event
Added user-configurable hysteresis to flow switch
Added ability to configure pre header and post footer printer codes

Index
when the custody transfer application is enabled but the transmitter is
not secured
Software adjustment
Support for HART command 139 modified to include unit checking
Response to a Modbus write command to coil 34 modified so that an
A028 alarm is no longer generated
Feature addition
Added support for Marine Bunker Transfer Package (refer to the
manual entitled Series 3000 Transmitters: Marine Bunker Transfer
Package Supplement, available on the Micro Motion web site at
www.micromotion.com)

Configuration and Use Manual 321


322 Micro Motion® Series 3000 MVD Transmitters and Controllers
Index

Return Policy
Numerics Application 2
20 mA value Applications list 148
configuration 67 ATEX 259, 261
troubleshooting 229 Model 3350 or Model 3700 257
375 Field Communicator 297 Model 3500 249
connecting to Series 3000 device 297 Audit trail 170
menu flowcharts 297 Auto print
requirements 297 batch (NTEP) tickets 125
4 mA value batch (OIML) tickets 131
configuration 67 batch tickets 122
troubleshooting 229

NE 53 History
4-wire cable 10 B
9-wire cable 10 Batch
See Discrete batch application
A Batch (NTEP) tickets
Active alarm log 209 See Tickets, batch (NTEP)
from View menu 146 Batch (OIML) tickets
Active high 66 See Tickets, batch (OIML)
Active low 66 Batch alarms 220
Alarm event log 210 Batch AOC 85, 157
Alarm history 210 Batch inventories
Alarm log password 110, 168 See Inventories
Alarm severity 38, 208 Batch tickets
Alarms See Tickets, batch
active alarm log 146, 209 Bell 202
alarm categories 209 communications 19
alarm event log 210 parameters 102

Index
alarm handling 208 signal converter 16
alarm history 210 wiring diagrams 20
alarm severity 208 wiring terminals 19
alarm types 208 BOL number
batch alarms 220 batch 163, 164
calibration alarms 221 transfer 164
configuration alarms 222 Burst mode 103
electronics alarms 212 Buttons
help 211 cursor control buttons 30
listed by category 212 in discrete batch operation mode 153
output saturation alarms 220 function buttons 28
process alarms 216 in discrete batch operation mode 151
sensor alarms 215 Security button 27
slug flow alarms 219
Ambient temperature effect C
Model 3300 or Model 3500 249 Cable glands 11
Model 3350 or Model 3700 257 Cable types 10
API Calibration 179, 181
See Petroleum measurement application alarms 221

Configuration and Use Manual 323


Index

batch AOC 85, 157 control options 86


density 197 flow source 85
sensor zero 134 presets 88
temperature 201 discrete events 79
troubleshooting 230 action 81
Calibration factors 53 event type 80
Calibration span 67 high and low values 81
Characterization 53 process variable 80
density calibration factors 54 setpoints 81
flow calibration parameters 55 discrete inputs
troubleshooting 229 assignment 56
Checksum, core processor 110 polarity 58
Checksum, transmitter 110 discrete outputs 63
Cleaning instructions assignment 64
Model 3300 or Model 3500 249 fault indication 65
Model 3350 or Model 3700 258 polarity 63
Coil, testing resistance 235 external inputs 59
Communication loop, troubleshooting 228 flow damping 42
Communication parameters flow direction 42
HART over Bell 202 104 frequency input 57
RS-485 mode 100 flow rate units 57
service port mode 100 K-factor 57
Communication tools scaling method 57
375 Field Communicator 3 frequency output 70
local display 3 flow source 70
Pocket ProLink 3 maximum pulse width 71
ProLink II 3 polarity 71
Configuration power 71
alarm severity 38 scaling method 70
Bell 202 parameters 102 HART over RS-485 99
burst mode 103 input parameters 39
core processor parameters 41 language 35
custody transfer application 105 low flow cutoff
cutoff mass flow 42
density 51 volume flow (gas standard) 43
mass flow 42 volume flow (liquid) 43
milliamp output 68 mass flow process variable 42
volume flow (gas standard) 43 mass flow units 42
volume flow (liquid) 43 measurement units
damping density 51
density 51 mass flow 42
flow 42 temperature 52
temperature 52 volume flow (gas standard) 43
date 38 volume flow (liquid) 43
default values and ranges 273 milliamp outputs 66
density damping 51 Modbus 99
density process variable 51 outputs 61
density units 51 passwords 34
device parameters 104 petroleum measurement application 75
digital communications 97 polling 59
discrete batch application 83 printer 101
batch control methods 90 process inventory reset methods 35

324 Micro Motion® Series 3000 MVD Transmitters and Controllers


Index

process monitor Core processor parameters


display variables 94 configuration 41

Return Policy
precision of displayed variables 94 discrete inputs 56
process totalizer and process inventory process variables 42
labels 94 sensor calibration data 53
process totalizer reset methods 35 sensor information 56
process variables 42 Core processor resistance test 234
quaternary variable 104 Crossover frequency 72
restoring a working configuration 224 CSA 259, 262
RS-485 parameters 99 Model 3300 or Model 3500 249
RS-485 protocol 99 Model 3350 or Model 3700 257
security 34 CTL 76
sensor calibration data 53 Cursor control buttons 30
sensor information 56 in discrete batch operation mode 153
slug duration 51 Custody transfer application 105
slug high limit 51 audit trail 170
slug low limit 51 configuration 105

NE 53 History
standard gas density 43 device behavior 159
system parameters 37 NTEP 106
tag 38 BOL number 163
temperature damping 52 configuration 107
temperature process variable 52 executing a transaction 163
temperature units 52 process inventory values 164
ticket formatting and printing 117 ticket printing 163
batch (NTEP) tickets 123 transfer variable 107
batch (OIML) tickets 129 OIML 106
batch tickets 121 alarm log password 110
standard tickets 119 application approval 108
transfer (OIML) tickets 125 BOL number 164
time 38 configuration 108
volume flow process variable 42 executing a transaction 164
volume flow type 43 process monitor approval 109

Index
volume flow units (gas standard) 43 process variable approval 94, 109
volume flow units (liquid) 43 ticket printing 166
when custody transfer application is enabled 170 transfer log 167
write-protecting 34 transfer variable 108
Configuration files (ProLink II) 290 transfer variable approval 109
Connecting with ProLink II or Pocket ProLink View menu 168
software 277 OIML/batch 106
Control device, connecting to relay 267, 271 alarm log password 110
Control options 86 application approval 108
Controller 2 BOL number 164
Core processor 2 configuration 108
dimensions 245, 254 executing a transaction 165
enhanced 2 process monitor approval 109
remote 10 process variable approval 94, 109
standard 2 ticket printing 166
troubleshooting 232 transfer variable 108
Core processor checksum 110 transfer variable approval 109
Core processor inputs View menu 168
enabling and disabling 42 operation mode 159
reconfiguring Series 3000 device 170

Configuration and Use Manual 325


Index

security switch 111 Model 3350 or Model 3700 251


Model 3300 or Model 3500 panel- relay module 264
mount 111 Discrete batch application 83
Model 3300 or Model 3500 rack-mount 112 batch AOC 85, 157
Model 3350 or Model 3700 field-mount 113 batch control functions 91
weights and measures seal 115 batch events 150
Customer service, contacting 5 cleaning or purging the tubes 157
Cutoff configuration 83
definition 53 control options 86
density 51 ending with flow 157
interaction between milliamp output cutoff and flow source 85
low flow cutoff 69 function buttons 151
mass flow 42 operation mode 149
milliamp outputs 67 preset selections 147
volume flow (gas standard) 43 presets 88
volume flow (liquid) 43 printing batch tickets 122
processing sequences 153
D stages 88
Damping tickets 85
damping values 52 Discrete events
definition 52 configuration 79
density 51 action 81
flow 42 event type 80
interaction between milliamp output damping and high and low values 81
other damping parameters 69 setpoints 81
milliamp outputs 67 in batch control 90
temperature 52 printing
Data security 159 batch (NTEP) tickets 125
Default values 273 batch (OIML) tickets 131
Density batch tickets 122
calibration 197 standard tickets 120
calibration factors 54 process variable 80
cutoff 51 Discrete inputs
damping 51 configuration
process variable configuration 51 assignment 56
slug flow alarms 219 polarity 58
slug flow configuration parameters 51 in batch control 90
units 51 printing
Density curves batch (NTEP) tickets 125
from View menu 148 batch (OIML) tickets 131
See also Enhanced density application batch tickets 122
Device parameters 104 standard tickets 120
Diagnostic monitor 148 transfer (OIML) tickets 128
Digital communications 15 testing 139
configuration 97 Discrete outputs 262, 265
fault indication 104 configuration 63
installation 15 assignment 64
protocols 15 fault indication 65
wiring 13 polarity 63
Dimensions discrete batch requirements 65
core processor 245, 254 testing 139
Model 3300 or Model 3500 241 troubleshooting 228

326 Micro Motion® Series 3000 MVD Transmitters and Controllers


Index

voltage levels 63 Field-mount


Display See Model 3350 or Model 3700

Return Policy
process monitor configuration 94 Flow calibration parameters 55
scientific notation 30 Flow direction 42
startup 25 Flow source
update period 95 discrete batch 85
using 25 frequency output 70
Documentation resources 4 Flow switch 65
Drive gain setpoint 65
erratic 231 Flow switch, hysteresis 65
excessive 231 Frequency input
Duty cycle 72 cable length 8
configuration 57
E flow rate units 57
Electrical connections K-factor 57
Model 3300 or Model 3500 246 scaling method 57
Model 3350 or Model 3700 255 testing 139

NE 53 History
EMI effects Frequency output
Model 3300 or Model 3500 249 configuration 70
Model 3350 or Model 3700 257 fault indication 71
End batch 91 flow source 70
Enhanced core processor 2 maximum pulse width 71
Enhanced density application 1 polarity 71
Environmental effects power 71
Model 3300 or Model 3500 249 scaling method 70
Model 3350 or Model 3700 257 testing 140
Environmental limits troubleshooting 225, 228, 229
Model 3300 or Model 3500 249 Function buttons 28
Model 3350 or Model 3700 257 in discrete batch operation mode 151
Erratic drive gain 231 FVZ
Events See Field Verification Zero
See Discrete events

Index
Excessive drive gain 231 G
External inputs Gas standard volume flow 43, 48
configuration 59 Grounding
testing 139 I/O wiring 13
External temperature compensation 59 troubleshooting 228
configuration 59 GSV
petroleum measurement application 78 See Gas standard volume flow
wiring diagram 22
with HART Tri-Loop, wiring diagram 23 H
HART
F loop current mode 103
Factory zero 135 polling address 100
Fault indication RS-485 configuration 99
digital communications 104 See also Bell 202
discrete outputs 65 HART burst mode
frequency output 71 See Burst mode 103
milliamp outputs 66 HART Communicator
Fault timeout 209 See 375 Field Communicator
Field Verification Zero 110 HART interface 289

Configuration and Use Manual 327


Index

HART Tri-Loop wiring diagram 23 displaying large values 164


with pressure compensation or external with custody transfer (OIML) or custody
temperature compensation 23 transfer (OIML/batch) 169
Hazardous area classifications See also Totalizers
Model 3100 259 transfer inventories 169, 174
Model 3300 or Model 3500 249 viewing 174
Model 3350 or Model 3700 257
user-supplied relays 262 K
Help system 211 K-factor 57
Housing
Model 3300 or Model 3500 241 L
Model 3350 or Model 3700 251 Labels
Hysteresis, flow switch 65 maintaining and replacing safety labels 315
safety labels on Series 3000 device 315
I terminal labels on Series 3000 device 11
I/O wiring 11 used for process totalizers and process
grounding 13 inventories 95
relays 13 Language used in Series 3000 device 35
terminal blocks and terminal locations 11 LCD options 148
Increment preset 91 Legal security 159
Ingress protection on Model 3300 8 Liquid volume flow 43
Inhibit batch 91 Loop current mode 103, 229
Inhibit flow 91 Low flow cutoff
Inhibit totalizer 91 mass flow 42
Input parameters 39 volume flow (gas standard) 43
Inputs volume flow (liquid) 43
Model 3300 or Model 3500 246 Low pickoff voltage 232
Model 3350 or Model 3700 255
Installation M
digital communications 15 mA outputs
digital communications wiring 13 See Milliamp outputs
display cover orientation (Model 3350 or Model Maintenance
3700) 9 cleaning instructions
environmental requirements 8 Model 3300 or Model 3500 249
frequency input cable length 8 Model 3350 or Model 3700 258
grounding I/O wiring 13 density calibration 179
I/O wiring 11 meter factors 179
Model 3100 263 meter validation 179
relay 13, 263 meter verification 179
remote core processor 10 safety labels 315
sensor wiring 10 temperature calibration 179
supplemental information 7 zero calibration 179
user-supplied relay 269 Management menu 26
Interface/display Security button 27
Model 3300 or Model 3500 241 Marine Bunker Transfer Package 1
Model 3350 or Model 3700 251 Mass flow
Inventories 173 damping 42
batch inventories 147, 174 low flow cutoff 42
managing 174 process variable configuration 42
process inventories special units 49
configuring labels 94 units 42
configuring reset methods 35 Maximum pulse width 71, 72

328 Micro Motion® Series 3000 MVD Transmitters and Controllers


Index

Measurement units Quick Reference Guide 7


density 51 rack-mount

Return Policy
mass flow 42 replacement for RFT9739 rack-mount 7
special units 49 Model 3350
temperature 52 display cover orientation 9
verifying correct configuration 229 frequency input cable length 8
volume flow (gas standard) 43 installation 7
volume flow (liquid) 43 K-factor 57
Measuring Instruments Directive 110 Quick Reference Guide 7
Menu system Model 3500
flowcharts 277 installation 7
Management menu 26 Quick Reference Guide 7
Management menu flowcharts 281 rack-mount
process monitor flowcharts 277 replacement for RFT9739 rack-mount 7
shortcuts 28 sensor wiring 10
using 25 Model 3700
View menu 26 display cover orientation 9

NE 53 History
View menu flowcharts 279 installation 7
Meter factors 55, 181, 196 Quick Reference Guide 7
Meter fingerprinting 206 sensor wiring 10
Meter validation 179, 181, 196 Mounting relays 263
Meter verification 179, 180, 183 MVD 2
execution 184
preparing for test 183 N
results 190 Net Oil Computer 1
See also Smart Meter Verification New equipment returns 317
Meter verification, specification uncertainty NTEP
limit 184 See Custody transfer application
Micro Motion customer service 5
MID O
See Measuring Instruments Directive OIML
Milliamp outputs See Custody transfer application

Index
configuration 66 OIML/batch
calibration span 67 See Custody transfer application
cutoff 67 Operation mode
damping 67 custody transfer application 159
fault indication 66 discrete batch application 149
process variable 67 process monitor mode 144
range 67 View menu 145
scale 67 Optional applications 1
testing 140 applications list 148
trimming 140 Output, troubleshooting
troubleshooting 225 frequency output 225
calibration span 229 milliamp outputs 225
Modbus Outputs
configuration 99 configuration 61
polling address 100 Model 3300 or Model 3500 246
Model 3300 Model 3350 or Model 3700 255
frequency input cable length 8 output saturation alarms 220
ingress protection 8
installation 7
K-factor 57

Configuration and Use Manual 329


Index

P Prior zero 135


Panel-mount Process inventories
See Model 3300 or Model 3500 panel-mount See Inventories
Passwords Process monitor
configuration 34 approval for custody transfer 109
alarm log password 110 configuration
configuration password 34 displayed variables 94
maintenance password 34 precision of displayed variables 94
types 34 process totalizer and process inventory
Petroleum measurement application 75 labels 94
definitions 76 from View menu 147
external temperature compensation 78 process variable approval 94, 168
parameters 76 Process monitor mode 144
reference tables 77 Process totalizers
Pickoff voltage 232 See Totalizers
Platform 2 Process variable
Pocket ProLink 277, 289 approval for custody transfer 109
Polarity assigned to frequency output 70
discrete inputs 58 assigned to milliamp outputs 67
discrete outputs 63 configuration 42
frequency output 71 in discrete events 80
Polling 59 troubleshooting 203
Polling address ProLink II 277, 289
HART over Bell 202 102 configuration upload and download 290
HART over RS-485 100 connecting to Series 3000 device 290
Modbus 100 menu flowcharts 291
Power supply requirements 289
for relay 261 saving configuration files 290
specifications Protocol
Model 3300 or Model 3500 248 on RS-485 terminals 99
Model 3350 or Model 3700 257 printer 101
Power supply, troubleshooting 227 supported 15
Power-up 133 Pulse width
Preset selections 147 definition 72
Presets 88 See also Maximum pulse width
Pressure compensation 59
configuration 59 Q
wiring diagram 22 QRG
with HART Tri-Loop, wiring diagram 23 See Quick Reference Guide
Printer Quaternary variable 104
configuration 101 Quick Reference Guide 7
test 102 QV
Printing See Quaternary variable 104
auto print
batch (NTEP) tickets 125 R
batch (OIML) tickets 131 Rack-mount
batch tickets 122 See Model 3300 or Model 3500
batch (NTEP) tickets 124 Range
batch (OIML) tickets 131 milliamp outputs 67
batch tickets 85, 122 Receiving device, troubleshooting 229
standard tickets 120 Relay 13, 261
transfer (OIML) tickets 127 connecting to control device 267, 271

330 Micro Motion® Series 3000 MVD Transmitters and Controllers


Index

installation 263 cable types 10


mounting 263 Sensor zero 134

Return Policy
power 261 Series 3000 2
replacing 262 software change history 319
types 261 Service port mode 100
user-supplied 262, 269 Setpoint
Relay packs 259 discrete events 81
Remote core processor 10 flow switch 65
Replacing relays 262 Short to case test 235
Reset batch 91 Signal converter
Resistance Bell 202 16
testing coil 235 RS-485 15, 289
testing core processor 234 Simulation mode
Restore factory configuration 224 See Sensor simulation mode
Resume batch 91 Slug flow
Return policy 317 alarms 219
RF (radio frequency) interference 228 configuration parameters 51

NE 53 History
RFT9739 rack-mount transmitter, replacing 7 Smart Meter Verification
RS-485 16 execution 186
parameters 99 preparing for test 183
signal converter 15 results 190
wiring diagrams 17 scheduling 195
wiring terminals 16 Special units 49
Specification uncertainty limit 184
S Specifications
Safety labels 315 Model 3100 259
Safety messages 1 Model 3300 241
Saving ProLink II configuration files 290 Model 3350 251
Scale, milliamp outputs 67 Model 3500 241
Scaling method Model 3700 251
frequency input 57 Standard core processor 2
frequency output 70 Standard density 48

Index
Scientific notation 30 Standard gas density 43
Security Standard tickets
configuration 34 See Tickets, standard
with custody transfer application 159 Start batch 91
Security breach Startup
clearing 170 device behavior 143
identifying 159 initial 133, 143
Security button 27, 159 Startup procedures
Security switch 111 milliamp output trim 140
Model 3300 or Model 3500 panel-mount 111 sensor zero 134
Model 3300 or Model 3500 rack-mount 112 testing inputs and outputs 138
Model 3350 or Model 3700 field-mount 113 Stop batch 91
Sensor 2 System parameters
characterization 53 configuration 37
pickoff values 231
testing coil resistance 235 T
Sensor simulation mode 207 TEC 76
Sensor tubes 229 Temperature
Sensor wiring 10 calibration 201
cable glands 11 damping 52

Configuration and Use Manual 331


Index

process variable configuration 52 Totalizers


units 52 managing
Temperature compensation from Maintenance menu 174
See External temperature compensation from View menu 147, 174
Terminal blocks 11 process totalizers 176
Terminal labels 11 configuring labels 94
Terminology 2 configuring reset methods 35
controller 2 from View menu 147
core processor 2 with custody transfer (OIML) or custody
enhanced core processor 2 transfer (OIML/batch) 169
MVD 2 See also Inventories
platform 2 transfer totalizers 169, 174
sensor 2 types 173
Series 3000 2 viewing 174
standard core processor 2 Transfer (OIML) tickets
transmitter 2 See Tickets, transfer (OIML)
Test points 230 Transfer log
Testing See Custody transfer application, OIML, transfer
core processor resistance 234 log
discrete inputs 139 Transfer variable
discrete outputs 139 See Custody transfer application
external temperature value 139 Transmitter 2
frequency input 139 default values 273
frequency output 140 ranges 273
inputs 138 Transmitter checksum 110
meter verification 184 Trimming the milliamp outputs 140
milliamp outputs 140 Troubleshooting 203
outputs 138 alarms 208
pressure value 139 calibration 230
printer 102 calibration span 229
sensor coil resistance 235 characterization 229
short to case 235 communication loop 228
Smart Meter Verification 186 core processor 232
Tickets core processor resistance test 234
batch (NTEP) tickets customer service telephone number 5
formatting 123 discrete outputs 228
printing 124 erratic drive gain 231
batch (OIML) tickets excessive drive gain 231
formatting 129 frequency output 225, 228, 229
printing 131, 166 grounding 228
batch tickets 85 loop current mode 229
formatting 121 low pickoff voltage 232
printing 122 mA output fixed 229
sample tickets 305 measurement range 229
standard tickets measurement unit configuration 229
formatting 119 meter fingerprinting 206
printing 120 milliamp outputs 225
transfer (OIML) tickets 127 power supply wiring 227
formatting 125 process variables 203
printing 127, 166 receiving device 229
types 117 RF (radio frequency) interference 228
sensor coil resistance 235

332 Micro Motion® Series 3000 MVD Transmitters and Controllers


Index

sensor pickoff values 231 Weights and measures


sensor simulation mode 207 seal 115

Return Policy
sensor tubes 229 See Custody transfer application
sensor-to-transmitter wiring 228 Wiring
short to case 235 digital communications 13
test points 230 I/O 11
wiring problems 227 sensor 10
Wiring diagrams
U Bell 202 20
UL 259, 262 external temperature compensation 22
Model 3300 or Model 3500 249 external temperature compensation with HART
Model 3350 or Model 3700 257 Tri-Loop 23
Update period 95 HART multidrop 22
Used equipment returns 317 HART Tri-Loop 23
User-supplied relays 262, 269 HART/analog single-loop 21
pressure compensation 22
V pressure compensation with HART Tri-Loop 23

NE 53 History
VCF 76 RS-485 17
View menu 26 Wiring problems 227
active alarm log 146 Write-protection
applications list 148 device configuration 34
batch inventories 147 with custody transfer application 159
density curves 148
diagnostic monitor 148 Z
in process monitor mode 145 Zero 134
LCD options 148 factory zero 135
managing totalizers 147 prior zero 135
managing totalizers and inventories 174
preset selections 147
process monitoring 147
process totalizers 147
with custody transfer (OIML) or custody transfer

Index
(OIML) batch 168
Volume flow
damping 42
gas standard 43, 48
low flow cutoff 43
special units 49
standard gas density 43
units 43
liquid 43
low flow cutoff 43
special units 49
units 43
process variable configuration 42
type 43

W
Weight
Model 3300 or Model 3500 241
Model 3350 or Model 3700 251

Configuration and Use Manual 333


334 Micro Motion® Series 3000 MVD Transmitters and Controllers
*20001266*
20001266
Rev. CD
2020

Micro Motion Inc. USA Micro Motion Europe


7070 Winchester Circle Emerson Automation Solutions
Boulder, Colorado USA 80301 Neonstraat 1
T +1 303-527-5200 6718 WX Ede
T +1 800-522-6277 The Netherlands
F +1 303-530-8459 T +31 (0) 318 495 555
www.emerson.com T +31 (0) 70 413 6666
F +31 (0) 318 495 556
www.emerson.com/nl-nl

Micro Motion Asia Micro Motion United Kingdom


Emerson Automation Solutions Emerson Automation Solutions
1 Pandan Crescent Emerson Process Management Limited
Singapore 128461 Horsfield Way
Republic of Singapore Bredbury Industrial Estate
T +65 6363-7766 Stockport SK6 2SU U.K.
F +65 6770-8003 T +44 0870 240 1978
F +44 0800 966 181

©2020 Micro Motion, Inc. All rights reserved.

The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE,
ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of their respective owners.

You might also like