Cut Sheet SKM
Cut Sheet SKM
Cut Sheet SKM
1. MODEL: APMRH
INPUT DATA
Return Air Flow Rate 5000 cfm Return Air DBT / WBT / RH 80 °F / 67 °F / 51% Ambient Temperature 115 °F
PERFORMANCE DATA
* Capacity given is gross capacity which does not include the effect of evaporator fan motor heat .
PHYSICAL DATA
CONDENSER
Compressor Model ZP76 + ZP067 Quantity 1+1 Motor Size / Quantity 0.35 kW / 2
Rows / Fins 3 / 16 fpi Coil Face Area 37.3 ft² Fin Material Aluminum fins
EVAPORATOR
Coil Size (H x L) 32 inch x 60 inch Rows / Fins 4 / 14 fpi Fin Material Aluminum fins
External Static Pressure 1.2 in.wg Total Static Pressure 1.66 in.wg Motor Size 2.2 kW
LwA dB(A) 55.6 68.4 69.4 73.8 76.6 76.0 72.0 65.6 81.6
ELECTRICAL DATA
Note :- • Power input mentioned here is at rated condition only, and should not be used for cable/fuse selection.
• MCA/MFA values given in the catalogue electrical data page should be refered for the same .
• For non standard units MCA/MFA values, please consult SKM engineering department.
• Evaporator motor electrical data is based on 4 poles, single speed.
Drawings
Loading Points
Unit A1 A2 A3 A4 Total
lbs 364 364 443 443 1614
Sound Data
SOUND PRESSURE LEVEL in dBA ref 2x10-5 Pa in free field
SPECTRUM PER OCTAVE BAND dB(A)
@ 1 meter 55.2 53.4 45.9 66.5 69.5 68.6 60.7 52.3 73.5
Note: Sound Pressure Level according to ISO 3744, full load operation at 95ºF (35ºC) ambient and 44ºF (6.7ºC) / 54ºF (12.2ºC) evaporator leaving and
entering water temperatures.
Options : -
INPUT DATA
Return Air Flow Rate 5800 cfm Return Air DBT / WBT / RH 80 °F / 67 °F / 52% Ambient Temperature 115 °F
PERFORMANCE DATA
* Capacity given is gross capacity which does not include the effect of evaporator fan motor heat .
PHYSICAL DATA
CONDENSER
Compressor Model ZP090 + ZP083 Quantity 1+1 Motor Size / Quantity 0.95 kW / 2
Rows / Fins 2 / 16 fpi Coil Face Area 52 ft² Fin Material Aluminum fins
EVAPORATOR
Coil Size (H x L) 40 inch x 78 inch Rows / Fins 4 / 14 fpi Fin Material Aluminum fins
External Static Pressure 1.5 in.wg Total Static Pressure 1.76 in.wg Motor Size 2.2 kW
Fan Model SYT 15-15 / 2 (Non Standard motor size, please consult SKM)
Rotational Speed 971 rpm (RPM out of range, please consult SKM)
LwA dB(A) 56.4 71.3 69.0 77.2 78.6 78.2 75.8 68.3 84.1
ELECTRICAL DATA
Note :- • Power input mentioned here is at rated condition only, and should not be used for cable/fuse selection.
• MCA/MFA values given in the catalogue electrical data page should be refered for the same .
• For non standard units MCA/MFA values, please consult SKM engineering department.
• Evaporator motor electrical data is based on 4 poles, single speed.
Drawings
Loading Points
Unit A1 A2 A3 A4 Total
lbs 498 495 656 643 2292
Sound Data
SOUND PRESSURE LEVEL in dBA ref 2x10-5 Pa in free field
SPECTRUM PER OCTAVE BAND dB(A)
@ 1 meter 44.9 50.8 52.3 53.4 56.0 53.6 51.8 43.3 61.3
Note: Sound Pressure Level according to ISO 3744, full load operation at 95ºF (35ºC) ambient and 44ºF (6.7ºC) / 54ºF (12.2ºC) evaporator leaving and
entering water temperatures.
Options : -
INPUT DATA
Return Air Flow Rate 7400 cfm Return Air DBT / WBT / RH 80 °F / 67 °F / 52% Ambient Temperature 115 °F
PERFORMANCE DATA
* Capacity given is gross capacity which does not include the effect of evaporator fan motor heat .
PHYSICAL DATA
CONDENSER
Compressor Model ZP137 + ZP120 Quantity 1+1 Motor Size / Quantity 0.95 kW / 2
Rows / Fins 3 / 16 fpi Coil Face Area 52 ft² Fin Material Aluminum fins
EVAPORATOR
Coil Size (H x L) 40 inch x 78 inch Rows / Fins 4 / 14 fpi Fin Material Aluminum fins
External Static Pressure 1.5 in.wg Total Static Pressure 1.83 in.wg Motor Size 4 kW
Rotational Speed 980 rpm (RPM out of range, please consult SKM)
LwA dB(A) 55.5 70.9 69.2 78.0 79.3 79.3 77.0 69.5 85.0
ELECTRICAL DATA
Note :- • Power input mentioned here is at rated condition only, and should not be used for cable/fuse selection.
• MCA/MFA values given in the catalogue electrical data page should be refered for the same .
• For non standard units MCA/MFA values, please consult SKM engineering department.
• Evaporator motor electrical data is based on 4 poles, single speed.
Drawings
Loading Points
Unit A1 A2 A3 A4 Total
lbs 547 543 665 652 2407
Sound Data
SOUND PRESSURE LEVEL in dBA ref 2x10-5 Pa in free field
SPECTRUM PER OCTAVE BAND dB(A)
@ 1 meter 44.9 50.8 52.3 54.3 57.0 57.3 53.5 45.9 62.8
Note: Sound Pressure Level according to ISO 3744, full load operation at 95ºF (35ºC) ambient and 44ºF (6.7ºC) / 54ºF (12.2ºC) evaporator leaving and
entering water temperatures.
Options : -