Contents
1 Overview
1.1 Product Overview
1.2 Applicable Personnel

2 Safety Precautions
2.1 Safety Overview
2.2 Symbol Conventions
2.3 Label Description

3 Product Introduction
3.1 Appearance
3.2 Size Dimensions
3.3 Nameplate
3.4 Working Principle
3.5 Inverter Storage
3.6 Grid Types

4 Unpacking

5 Installation
5.1 Basic Installation Requirem-
ents
5.2 Installation Environment
Requirements
5.3 Moving Requirements
5.4 Wall Mounted Bracket Installa-
tion
5.5 Installing PV Inverter
6 Electrical Connections 11 Decommissioning
6.1 AC side Connection
6.2 DC side Connection
6.3 Communication Connection
6.4 Protective Ground Connection
6 . 5 Lightning Protection Grounding

7.1 Debug Inverter 12 Quality Assurance


7 Debugging 7.2 Operating Mode
7.3 OLED Display and Touch Buttons

13 Contact Us
8 Monitoring Method
8.1 Remote Data Monitoring
8.2 Local Data Monitoring

9 System Maintenance 9.1 Routine Maintenance


9.2 Trouble Shooting

10 Product Specification
1 Overview
1.1Product Overview •Please follow this installation manual as installation condition environ-
This manual is aimed at providing sufficient information and installing instruction for ment,space and so on.
consumers buying Shenzhen Growatt New Energy Technology Co. Ltd (short as Growatt) •Please install the inverter in a dry and ventilated environment,otherwi-
MAC Series solar inverters. Please read this manual carefully before using the MAC series WARNING se may affect the performance of the inverter.
inverters and store the manual in a reachable place for an authorized technician. No •Please follow the installation procedures in this manual.
further notice if there is any change in this manual.

1.2 Applicable Personnel Electrical Connections:

Only qualified electrical technicians are allowed to install MAX series inverter. With •Before electrical connection, please ensure the inverter DC switch is
reading through this manual and following all the precautions, qualified electrical at ” OFF” also disconnect AC switch, otherwise the high voltage
technician can properly install MAC serial inverter, finish trouble shooting and from inverter may cause life risk.
communication settings. •Only trained authorized electrical technician can do the electric
If there is any problem during the installation, the installer can either log on connection also please follow the connection procedures in this
www.ginverter.com and leave a message or call consumer service hotline +86 755 DANGER manual along with local country's regulations.
27471942. •High voltage may cause electric shocks and serious injury please do
not touch the inverter.
•Please do not store inverter in area with flammable and explosive
material.

2 Safety Precautions •Each inverter must install one AC breaker; AC breaker is forbidden
to share with other inverters.
2.1 Safety Overview •It is forbidden to add load between inverter and breaker.
1> Before installation please make sure reading through this manual, any damage caused •If the cable is thick, after tightening the cable do not shake it and
by improper installation, Growatt reserve the right to disclaim any warranty. ensure the cable is well-connected and then start the inverter. Loose
2>All the operations and connections must be done by trained qualified electrical WARNING
connection may cause overheat.
technician.
•Before connecting between PV panels and inverter please ensure the
3> During installation except for terminals, do not touch any inside part of the inverter.
positive and negative poles are correct connected.
4>All the electrical connections must meet local country's safety regulations.
5> If you need maintenance for this inverter, please contact our local authorized installi-
ng and maintenance technician.
6>You must get the local power supplier's permit before connecting this inverter to the Maintenance and replacement:
grid. •Must be installed by trained and authorized electrical technician and
7>When installing PV modules during the day, use opaque materials to cover the PV
accurately follow this manual.
modules. Otherwise, the voltage at the component terminals is high in the sun, which
may cause personal danger. •Please disconnect the DC and AC switch for at least five minutes, all
the operations should be carried after power disconnection.
DANGER
•If there is PV isolation low alarm, the inverter case may be unground-
Handle Process:
ed, please do not touch the inverter case.
•High voltage of inverter may result in electric shock.
•The inverter is heavy,please treat with care while handling,in case of
crushing injury. •For better cooling purpose, please regularly clean the fans.
WARNING
•Do not use air pump to clean the fans, cause it may damage the fans.
Installation: WARNING

•Before installation,please read through this manual,any damage


cause by improper installation,Growatt reserve the right to disclaim
NOTICE any warranty.

•Ensure that the MAC is not connected to a power supply and is not
power on before installation.
DANGER

1 2
Other: 2.3 Lable Description

•After you receiving the inverter please check the packing materials Symbol Name Meaning
for damage,if there is any damage please contact your supplier.
Inverter operating with high voltage,any
High Voltage
•The Max. PV input voltage should not exceed 1100V. operation regarding inverter need to be done by
Electric Shock
•For the disposed inverter,the consumer should dispose it according to trained and authorized electrical technician.
local disposal rules for electrical equipment waste.
WARNING
Do not touch a running inverter cause it
Burn Warning
generates high temperature on the case.

2.2 Symbol Conventions


Protective
Symbol Description Connect inverter to grounding bar.
Grounding

Indicates an imminently hazardous situation which,if not avoid-


ed,will result in serious injury or death. Residual voltage exists after the inverter is
DANGER Delay discharge powered off,it takes 5 minutes for the inverter
to discharge to the safe voltage.
Indicates potentially hazardous situation which,if not avoided,
will result in serious injury or death.
WARNING Read the
Reminds operator to read installation manual
installation
before operating or installing inverter.
Indicates potentially hazardous situation which,if not avoided, manual
will result in minor or moderate injury.
CAUTION
DC Means this terminal is for DC side.
Indicates certain hazardous situation which,if not avoided,will
rusult in property damage.
NOTICE
AC Means this terminal is for AC side.
Reminds operator to read installation manual before operating or
installing inverter.
CE Mark The inverter complies with the requirements of
the applicable CE guidelines

3 4
3 Product Introduction
3.1 Appearance Identification Description Explanation
Front view:

Touch button to switch OLED display


Touch mark
and set parameters by touch

Indicates the current operating status


of the inverter:
Inverter status 1. Red: Fault
identification 2. Green: normal operation
3. Red light flashes: warning
4. Green light flashes: update program

3.2 Size Description

Figure 3.1 Size(unit:mm)


Weight
Model
(unit: kg)
Width High Deep
Mark Description Mark Description
MAC series PV inverter 680 508 281 52
A DC switch G 485 Waterproof connector
MAC series PV Inverter with packaging 730 650 350 60
B Fan H AC Waterproof connector

C PV input terminal I LED Indicator light

D Breathable valve J OLED Screen

E Safety ground terminal K Touch button

F USB interface

5 6
3.3 Nameplate 3.5 Inverter Storage
1>Do not unpack the Inverter and store it in a ventilation dry place.
PV Grid Inverter 2>Keep the storage temperature at -25℃ ~ +60℃ and humidity at 0-95%.
Model name MAC 60KTL3-X LV 3>A maximum of four inverters with package can be stacked.
Max. PV voltage 1100 d.c.V 4>If the inverter has been long-term stored, inspections and tests should be conducted
PV voltage range 200-1000 d.c.V by qualified personnel before it is put into use.
PV Isc 55 d.c.A 3
Max. input current 50 d.c.A 3
Max. output power 60000 W
Max. apparent power 66600 VA
3.6 Grid Type
Nominal output voltage 3W/N/PE
230/400 a.c.V In the MAC series, the MAC 30-60KTL3-X LV model grid connection method is shown in
Max output current 96.6 a.c.A Figure 3.3, and the MAC 50-70KTL3-X MV model grid connection method is shown in
Nominal output
50/60 Hz Figure 3.4,and the MAC 15-36KTL3-XL model grid connection method is shown in
Frequency
Figure 3.5.
Power factor range 0.8leading~0.8lagging
Safety level Class I
Ingress Protection IP65
Operation Ambient
Temperature -25°C - +60°C
480V 480V
400V 400V
230V

Made in China 230V 230V

Note: The MAC series inverter nameplate is similar to the nameplate shown above, but 480V

the product model and specific parameters are different. See Chapter 10 Product 400V
Specifications for specific parameters. Figure 3.4
Figure 3.3

3.4 Working Principle


Mac inverter's working principle is like following:
1>The PV panels gather solar to generate DC power to inverter.
2>With input current detection circuit, it can monitor all the PV panels' working status 220V
220V
and use MPPT to track the maximum power point.
3>With inverter circuit change DC power to AC power, and feed power back to grid per
grid reuqirement.
4>With output isolation relay can isolate AC output and grid, if anything goes wrong on
either inverter side or grid side, isolation relay can disconnect inverter immediately.
220V
On-grid connection system diagram:

Figure 3.5

A B C D E F
Figure 3.2

Mark Description Mark Description Mark Description

A Photovoltaic module C PV inverter E Meter

B DC circuit breaker D AC circuit breaker F Grid

7 8
4 Unpacking Installation5
Checking before installation
To prevent device damage and personal injury, keep balance when
1>Before unpacking the inverter, check the outer packing materials for damage.

moving the inverter because it is heavy.


2>After unpacking the inverter, check that the contents are intact and complete. If any
Do not place the inverter with its wiring and signal terminals at the
damage is found or any component is missing, contact your supplier.

bottom contacting with floor or any other object because the terminals
The MAC series inverter accessories are as follows: are not designed to support the weight of inverter.
WARNING When placing inverter on the floor, put foam or paper under the inverter

to protect its cover.

A B C D E F G H 5.1Basic Installation Requirements


A.Ensure that the installation wall is solid enough to bear the inverter.(Inverter weigh
please refer to installation manual Figure 5.1 )
B.There must be enough installation space to fit the size of inverter.
I J K L M N O C.Do not install inverter on flammable or heat-intolerant buildings.
D.This inverter is IP 65 protection, you can install it indoor or outdoor.
Figure 4.1
E. Install the inverter in the eye for easy viewing of the OLED display and maintenance
work.
No. Description Qty. No. Description Qty. F.To avoid inverter performance de-rate due to the over heat, please do not expose the
inverter under direct sunlight.
A PV inverter 1 8/8 a G.The installation humidity should be from 0-95%.
H.The surrounding temperature of inverter should be from -25℃ ~ +60℃.
B AC Protective cover 1 PV+/PV- metal 9/9 b I.Inverter should be installed in a vertically or rear tilted surface, please refer to
L terminal following drawings.
c
C Wall mount 1 10/10

d
D User manual 1 12/12

E Data collector / manual (optional) 1/1 M PV Removal tool 1

F Self-tapping screw 5 N RNBS14-6 1

Figure 5.1
G Plastic expansion tube 5 O SC50-10 5

When the equipment is placed horizontally, the height from the ground
H Safety screw 1 * Warranty card 1 must be more than 1 meter.
NOTICE

I 485 terminal (3PIN) 1 * Copy of the business 1


license J.To ensure the inverter can work smoothly and easy for personnel to operate, please
notice there is sufficient space for inverter, refer to following drawing:
J 485 terminal (6PIN) 1 * Certificate 1/1 ≥500mm

Min 50cm

Min 50cm

Min 50cm
8/8a Note: Min 50cm Min 100cm Min 100cm Min 50cm

1.a:MAC 30KTL3-X;b:MAC 40KTL3-


PV+/PV- terminal
≥500mm

9/9b X;c:MAC 50KTL3-X;d:others;

Min 50cm

Min 50cm

Min 50cm
≥500mm

K 2.The MAC series comes standard with


10/10
c 50-10 copper crimp terminals. If you
Min 50cm Min 100cm Min 50cm
have copper and aluminum terminals,
please contact the supplier.
12/12d

Min 50cm

Min 50cm
≥500mm

Figure 5.2

9 10
K. Do not install inverter close to strong electromagnetic signal. 5.3 Moving Requirements
L. Install the inverter out of children's reach.
●The inverter is heavy, please move it with care and keep balance to avoid
personnel injury.
5.2 Installation Environment Requirements ●Do not place the inverter with its wiring and signal terminals at the
A.Although the inverter's protection level is IP 65, to extent inverter lifespan you still WARNING bottom contacting with floor or any other object because the terminals
need to avoid rain and snow, please refer to following drawings. are not designed to support the weight of inverter.

1>2-3 people put their hands into the package, lift the inverter out of the package, and
move to the designated installation location.
2>When you are moving the inverter, please keep the balance.

Notice: There is front and bottom mark on the package.

5.4 Wall Mount Bracket Installation


Before install the inverter you need install the wall mount bracket so that the inverter can
be firmly installed on the wall.
Figure 5.3 Wall mount plane drawing:

B.To reduce the de-rate performance of the inverter and extend inverter's life span, we
strongly recommend you install an awning, for the distance between an awning and
inverter, please refer to following drawing.

Figure 5.6
Figure 5.4

To avoid electric shock or other damage, be sure to check the wall for
D.Do not install inverter into an enclosed space like following drawing:
power lines or other piping before opening the wall.
DANGER

Steps:
1>Use the wall mount plate as a template drill holes on the wall and put in expansion
bolts.
2>Follow the following drawing put the bolt to install the wall mount plate on the wall.

Figure 5.5
11 12
Electrical Connections 6
6.1 AC Side Connection
●Before electrical connection, please ensure the inverter DC switch
is at ”OFF” also disconnect AC switch, otherwise the high voltage
from inverter may cause life risk.
● Only trained authorized electrical technician can do the electric
connection also please follow the connection procedures in this
manual along with local country's regulations.
DANGER ● High voltage may cause electric shocks and serious injury please
do not touch the inverter.
● Please do not store inverter in area with flammable and explosive
Figure 5.7 material.

●Each inverter must install one AC breaker, AC breaker is forbidden to share


with other inverters.
5.5 Install PV Inverter ●It is forbidden to add load between inverter and breaker.
●If the cable is thick, after tightening the cable do not shake it and ensure
1>Before installing the inverter on the wall mount, please make sure that the wall mount
is firmly fixed to the wall: WARNING the cable is well-connected and then start the inverter. Loose connection
may cause overheat.
2>Hang the inverter on the wall mount and fix it with bolts. Keep the inverter balanced
when hanging.
3>Check the inverter if it is firm enough and lock all the screws. Preparation before connection:
1. Disconnect inverter DC switch and AC breaker or switch
2. When the AC wire is tightened, the torque of the PE grounding is 35kgf.cm, and the
other torque is 50kgf.cm.
3. Measure the grid voltage and frequency. For detailed parameters, please refer to
Chapter 10 Product Specifications.

AC circuit breaker specifications:

PV inverter model Circuit breaker specifications

MAC 30KTL3-X LV 64A/400Vac

MAC 40KTL3-X LV 80A/400Vac

MAC 50-60KTL3-X LV 100A/400Vac

MAC 50KTL3-X MV 80A/ 480Vac


Figure 5.8
MAC 60-70KTL3-X MV 100A/480Vac

MAC 15-20KTL3-XL 63A/220Vac

MAC 22-25KTL3-XL 80A /220Vac

MAC 30-36KTL3-XL 100A /220Vac

13 14
Cable specifications refer to the following table:

Cross-sectional Recommended
area(mm2) value(mm2 )
PV Inverter
Aluminum Aluminum
Copper wire Copper wire
wire wire

MAC 30KTL3-X LV 10-35 25-50 16 25

MAC 40KTL3-X LV 25-35 35-50 30 35 Figure 6.2

D.Lock the protective casing on the inverter frame and block the waterproof joint with
MAC 50-60KTL3-X LV 25-35 35-50 35 50
fireproof mud to prevent water ingress

MAC 50KTL3-X MV 25-35 35-50 30 35

MAC 60-70KTL3-X MV 25-35 35-50 35 50

MAC 15KTL3-XL 10-35 35-50 16 25

MAC 20-25KTL3-XL 25-35 35-50 30 35

MAC 30-36KTL3-XL 25-35 35-50 35 50 Figure 6.3


Notice:Waterproof joints must be blocked with fireproof mud to prevent water
ingress.
Notice: The cable must be unbroken.50

AC terminal wiring steps: 6.2 DC Side Connection


A. The following figure shows the AC terminal on the inverter. L1, L2, and L3 are three
●Before electrical connection, please ensure the inverter DC switch is at
fire channels, and N is a nature channel.
”OFF” also disconnect AC switch, otherwise the high voltage from inverter
Note: The screws are matched with M8 screws.
may cause life risk.
B. Determine the stripping length according to the specifications of the crimping
terminal (recommended 16-18mm), crimp the wire and terminal with the crimping ●Only trained authorized electrical technician can do the electric connection
pliers, then pass the cable through the protective casing, lock it on the corresponding also please follow the connection procedures in this manual along with local
AC terminal, and tighten the terminals Screw. country's regulations.
DANGER ●High voltage may cause electric shocks and serious injury please do not
touch the inverter.
●Please do not store inverter in area with flammable and explosive material.

Notice: The sunlight will generate voltage on the solar panels, after serial connection,
the high voltage may injure personnel, so before connect DC input cable you need cover
solar panels with light-tight materials and make sure the inverter DC switch is at ”OFF”
status, otherwise high voltage may injure personnel.

●Each string's maximum open circuit voltage cannot exceed 1100Vdc, otherwise it
Figure 6.1 PC could lead to fire or damage the inverter.
● If the inverter was damaged by higher maximum open circuit voltage (higher than
1100Vdc) product warranty will be forfeited and Growatt will not take any
C. Connect the MP cable of the AC terminal with the matching M4 screw. After the WARNING
responsibility.。
RS485 is connected, lock the protective casing on the inverter frame.

15 16
A.Each string solar panels should be same brand and same model. E.Panel component configuration recommendation table:
B.The total panels power should not exceed 1.25 times of inverter input power.
C.According to the specification of the crimping terminal, determine the stripping
length (recommended 8-10, mm), crimp the wire and terminal with the crimping MPPT PVA PVB PVC
pliers, and connect them to the corresponding connector housings separately, and
hear the click sound to ensure the connection is good. The picture shows the
12 Strings ●●●● ●●●● ●●●●
connection of the DC terminal.
Notice: Connectors need to be fit with male and female terminals, before connecting
panels with inverter please make sure the positive pole and negative pole, namely the 11 Strings ●●●● ●●●● ●●●○
solar panels'positve pole connect to”+” negative pole connect to”-”.
10 Strings ●●●● ●●●○ ●●●○

9 Strings ●●●○ ●●●○ ●●●○

8 Strings ●●●○ ●●●○ ●●○○

Figure 6.4 Notice:When there is a hanging string in each MPPT, it is necessary to add a dust plug
D.The positive and negative terminals of the panel are connected to the corresponding for waterproof treatment.
terminals of the inverter. For the maximum input current value of each MPPT of
different types of inverters, please refer to the following table: F.Cable specification requirements:

PV inverter Maximum input current per MPPT Cross-sectional Recommende Line outer diameter
PV inverter model
area(mm 2 ) d value(mm²) range(mm²)
MAC 30KTL3-X LV 12.5A*3/12.5A*3/12.5A*2

MAC 40KTL3-X LV 12.5A*3/12.5A*3/12.5A*3 MAC series PV


4-6 4 4.5-7.8
inverter
MAC 50KTL3-X LV 12.5A*4/12.5A*3/12.5A*3
Notice:
MAC 60KTL3-X LV 12.5A*4/12.5A*4/12.5A*4 1.Under any circumstance, the total current of all strings cannot exceed the inverter's
maximum current.
2. Do not touch any working solar panels.
MAC 50KTL3-X MV 12.5A*4/12.5A*3/12.5A*3 3. Make sure the cable is unbroken.

MAC 50-70KTL3-X MV 12.5A*4/12.5A*4/12.5A*4

MAC 15-36KTL3-XL 12.5A*4/12.5A*4/12.5A*4

17 18
6.3 Communication Connection Multiple inverters ShineMaster cable router

6.3.1 RS 485 32 2 1
The MAC series comes standard with two RS485 interfaces, and you can monitor one or
more inverters via RS485. Another RS485 port is used to connect the smart meter (single TR+
machine anti-backflow function). When connecting the RS485 communication line to a TR-
GND
single unit, please follow the instructions below.
1>Loosen the AC protective cover and remove the protective cover;
RS 485 twisted pair cable
2>Pass the RS 485 communication cable through the waterproof rubber plug and
connect to the RS485 interface;
3)>The inverter is connected hand-in-hand through the RS 485 communication line. The
RS485A1 and RS485B1 (4/5/6 port or 7/8/9 port) at the end of the 485 cable are
connected to the ShineMaster for remote server monitoring
4>Lock the protective casing on the inverter frame to prevent water ingress.

4 5 6 7 8 9

Figure 6.6

6.3.2 USB
Figure 6.5 ●The USB port is mainly used to connect to the monitoring module or firmware update:
●External optional data collector(Shine GPRS-X ,Shine WiFi-X,Shine4G-X),Can
No. Definition Description be connected to the USB interface for monitoring.
●Quickly update software with U disk.
1 RS485B2 ●Steps for installing the monitoring module: Make sure △ is on the front side, then insert
RS485A2 / B2: Anti-backflow the display and tighten the screws.
2 GND communication port, connected to smart Install Disassembly
meter
The Inverter Side
3 RS485A2 The Inverter Side

4/7 RS485B1
RS485A1 / B1: The customer uses the
5/8 GND communication port to connect to the
The Inverter Side
third-party monitoring equipment
The Inverter Side
6/9 RS485A1

When multiple machines are connected in parallel, two customers use RS485 wiring
ports (4/5/6 and 7/8/9 ports) at the same time, and use multiple twisted pairs with
shielding layers to connect multiple inverters by hand. Parallel connection through the
RS485 communication line, an inverter (defined as the first) is connected to the
monitoring equipment to achieve multi-machine monitoring, the number of parallel Figure 6.7
machines can reach 32 units. When multiple machines are connected in parallel or the
transmission distance is long, it is recommended to switch the DIP switch 2 of the last
inverter from the left side to the right side to introduce a matching resistor. Refer to the
following figure for wiring:

19 20
6.4 Protective Ground Connection 3>The lightning down conductor and the equipment ground wire eventually sink at a
total ground point, but the two cannot share the wire. That is, the equipment
In this solar system all the unloaded metal components and cases should be connected to grounding wire should be pulled separately, and the wire diameter requirement is
the ground. >6mm2 when the safety interval distance S is satisfied; (Note4)
Single inverter need grounding over a PE point, multiple inverters need connect all the 4>Refer to GB/T 21714.3-2015 for the relevant design of the above lightning protection
inverter PE cable and solar panels shelves to the same grounding point to achieve lightning receptor system.
equipotential.
Note1:Refer to IEC 61643-32 <Low Voltage Surge Protector (SPD) Part 32: Surge
Protectors Connected to the DC Side of Photovoltaic Devices—Selection and Use
Guide>, Appendix C.
Note2:Refer to GB/T 21714.3-2015 <Lightning Protection Part 3 _ Physical Damage and
Life Danger of Buildings>, 6.3.1.
Note3:Refer to 6.2.2 and 6.2.3 of IEC 61643-32.
Note4:Refer to Chapter 7 and Appendix C of IEC 61643-32.

Figure 6.8 The lightning protection measures for photovoltaic systems shall be
Note: Pay attention to the rain at the grounding wire terminal joint. Do not expose it carried out in accordance with the corresponding national standards and
directly to the air. The recommended torque value for tightening the screw is 25kgf.cm. IEC standards. Otherwise, photovoltaic devices such as components,
inverters and power distribution facilities may be damaged by lightning.
WARNING In this case, the company does not carry out warranty and assumes any
responsibility.
6.5 Lightning Protection Grounding
Lightning
protection device

Distribution
Photovoltaic panel Inverter Cabinet
Lightning down the line

Safety
interval S 4 1 2 3 Power grid

SPD

Grounding bar

Lightning down the line Equipment ground wire

Total grounding point

Figure 6.9
1>It is generally recommended to install lightning protection devices (generally referred
to as lightning rods or lightning protection belts and down conductors at the top of
the building) to prevent lightning from hitting the PV array. (Note1)
2>Lightning protection devices and down-conductors and related equipment in
photovoltaic systems (including photovoltaic panels, inverters, cables, power
distribution equipment) shall maintain a safe separation distance S; Suggested value
of S: According to the general 5 storey height (about 15m) building roof, S takes 2.5m
enough, this distance can be simplified according to the inverse relationship of the
floor height. (Note2)

21 22
7 Debugging
7.1 Debug Inverter
1>Close the DC switch on the inverter. As long as the input DC voltage is greater than
250V, the inverter display will display the following message: If there is no mains
connection error, the inverter LED will turn red. If other information is displayed,
please refer to Chapter 9. If the debugging process encounters an unsolvable
problem, please contact customer service and perform the next step.
2>Close the circuit breaker or switch between the inverter and the grid. The inverter
starts the self-test countdown. After the self-test is normal, it will be connected to the
grid.
3>In normal operation, the leaves of the inverter indication window will turn green.
4>Complete debugging.

If the inverter is stored over one month, its default time and date may Figure 7.1
looks wrong, the time and date should be reset before connection to the
grid.
7.1.1.3 Server WEB Page Set Communication Address
Refer to Section 8.1.2 to log in to the server. After obtaining the inverter data through
the collector, modify the device communication address. This operation is performed by a
7.1.1 Set the PV inverter Communication Address professional.
1>Click "Settings" in "device list" to enter the advanced settings page;
After the inverter is turned on normally, the inverter communication address can be set 2>Read the "30" register to get the current device address, the password is max + today
through RS485, USB to WIFI module or server webpage. When the inverter is connected date (such as August 7th: max20190807);
by RS485 and multi-machine parallel communication, the inverter should be set to 3>When setting a new communication address, write the value of the "30" register as
different communication address; when the single machine communicates, the factory the address to be set (1~254), and then click "Save";
default communication address can be used directly. Note: The inverter communication 4>After setting the communication address, you can read the value of the "30" register
address can be set from 1 to 254. to confirm whether the setting is successful.

7.1.1.1 ShineBus Sets the Communication Address


The communication address of the inverter can be modified by the PC software ShineBus,
which is performed by a professional.

7.1.1.2 Mobile APP Set Communication Address


Refer to Section 8.2 Local Data Monitoring, download the mobile app and log in to the
monitoring interface to modify the communication address. This operation is performed
by a professional.
1>Select "Parameter Settings".
2>Enter the control password. (First time you need to set the control password, click
"Reset Password", jump to the page, enter the OSS account and password, the
distributor and installer can apply for the OSS account to Growatt, click "Login", set
Control password, the relevant settings can be used after the setting is successful.)
3>Select the setting item "Communication Address".
4>Click "Read" in the upper right corner to get the original communication address of
the machine.
5>Set the inverter communication address.
6>Read the inverter communication address and confirm that the setting is successful. Figure 7.2

23 24
7.2 Operating Mode
At this mode, inverter will check the system parameter. If the system is normal and PV
voltage is more than 250VDC, inverter will try to connect to the grid.

7.2.1 Waiting Mode


In this mode, the inverter works normally, the leaf of the indication window turns
green, and the LED display shows the active power and apparent power.
When the DC voltage is more than 250V DC, inverter will send the AC current
converted from PV module DC to the grid.
When the DC voltage is lower than 250VDC, inverter will enter into “waiting” and try
to connect to the grid, at this status, inverter consume very small power to check the
internal system status.
Note: only when the PV modules supply enough power(voltage> 200VDC) then the
inverter will start automatically.

7.2.2 Failure Mode


The intelligent control system of the inverter constantly monitors and adjusts the state
of the system. When the inverter detects any fault, the leaf of the indication window is
steady red or flashing red, and the LED display shows the fault message.
Note: please refer to section 9.2 to check the fault message and take corrective
measures.
Figure 7.3

7.1.2 Set Inverter Time and Date 7.2.3 Shutdown Mode


Refer to Section 8.2.1 to log in to the mobile APP. After the mobile phone communicates When the sunlight is weak or no light, inverter will stop working automatically. When it is
normally with the inverter through the APP, click “Parameter Configuration” and select off, inverter will not consume gird power or PV module.At the same time, the OLED lamp
“System Time (45~50)” to set the inverter time and date. and LED display of the inverter will be extinguished.
Note: When PV string DC voltage is too low(≤150VDC),inverter will be off.

7.3 OLED Display and Touch Buttons


The OLED display can display the operating status of the inverter and various parameter
information. The touch panel can be used to switch the display interface of the inverter
and set the inverter parameters.

Touch mode Definition

single Switch or current number plus 1

Two consecutive times Go to Settings & OK

Three consecutive times Return to the previous display interface

Figure 7.4 Long press 5S Current data is zeroed

25 26
7.3.1 Boot Display All settings interface is as follows:
When the inverter is turned on, the OLED display interface is as follows:
Growatt Set
PV inverter Parameter

General General
CUTDOWN
More info Advanced Advanced
30S

Set Password Set Language


Connect OK 111 English
Parameter

WideVolt Set Set Comaddr


Power PV2
1 2 3 1
XXXXw XXXvXXXXw

Etoday PV1 Set Date


Enable|Nline
XXXkWh XXXvXXXXw 2018-12-14

Etotal Grid Exporlimit Set Time


XXXXw XXXvXXXHz OFF ON 12:30:30

Figure 7.5
Reset factory
7.3.2 OLED Display Wake Up YES NO
After the inverter works normally for 5 minutes, the OLED display will be automatically Figure 7.6
turned off. At this time, the OLED has no display, the leaf of the indication window is
green, and the display data needs to be viewed or set. The OLED can be redisplayed by
touch operation.
7.3.3.1 Select Protection Voltage Level
7.3.3 Function Setting The inverter is factory set to CQC standard regulations, customers can choose different
voltage protection levels according to the actual situation; single touch switching
The inverter can support multiple touch mode modes: single touch, two voltage level, continuous touch twice to confirm the setting.
consecutive touches, three consecutive touches, and long press 5S. Different
types of taps have different functions. Advanced setup password: 111
WideVolt Set
WideVolt Set
1 2 3 Set OK
Touch mode definition
Figure 7.7
single Move, turn page or current number plus 1 1 standard
2 wide voltage level 2
Two consecutive times Enter setup mode, confirm settings 3 wide voltage level 3

Three consecutive times Return to the previous display interface

Long press 5S Current data is zeroed

27 28
Tips and Disclaimers
Set Set Date Set Time
The grid voltage and frequency of the inverter are set according to NB/T 32004-2013 or
the latest domestic standard. Parameter 2018-12-14 12:30:30
If the grid voltage is close to or higher than the domestic regulations, the inverter cannot
be connected to the grid and the local power operator can obtain the voltage level.
According to the voltage of the grid connection point, the user can select other voltage
levels. General Set Date Set Time
Advanced 2018-12-14 12:30:30
Excessive voltage of the power grid may affect the normal use and
service life of the household appliances on the grid side, or cause loss
of power generation. Due to the related effects and consequences
caused by the integration of the output voltage automatic control Set Language Set Date Set Time
function, we do not recognize any responsibility English 2018-12-14 12:30:30

7.3.3.2 Language Setting


Set Comaddr Set OK Set OK
The default language is Chinese, press the touch twice to enter the setting mode, switch
1
the language with a single touch, and touch the setting twice to confirm the setting.
Figure 7.10
Set Language English
English Chinese Set OK

Figure 7.8

7.3.3.3 Set the COM Address


The default COM address is 1, continuous touch twice to enter the setting mode, single
touch, number +1, continuous touch twice to confirm the setting, long press 5S digital to
zero.

Set Comaddr Set Comaddr


1 2 Set OK

Figure 7.9

7.3.3.4 Set Date and Time

After the storage time exceeds one month, the time and date set by the
inverter may be incorrect. The inverter needs to be set before it is
connected to the grid.

Touch twice to enter the parameter setting submenu, select the general setting, press
twice to enter the general setting submenu, single touch to switch the display interface,
touch the date and time interface twice to enter the setting state, single touch, number +
1, press twice to confirm the setting, long press 5S digital to zero.

29 30
8. Monitoring Method ShinePhone Main interface:
8.1 Remote Data Monitoring
1>The center of the main interface shows the current power station name. You can
MAC series inverter remote data monitoring methods include mobile APP and server
switch between different power stations in the account by clicking the invertedtriangle
WEB, RS485, GPRS, 4G can meet the above two monitoring methods.
symbol.
2>Add a collector, view the collector, and add a power station by clicking the + sign I
the upper right corner of the main interface.
8.1.1 Mobile APP (ShinePhone) remote monitoring 3>The top of the main interface shows the total power, power generation and revenue of
1.You can download and install the app by scanning the QR code below or by searching the current power plant's inverter.
for "ShinePhone" in the Google/Apple store. 4>“My device "shows the inverter of the current power station, click on the inverter name
to enter the details interface, or you can top and edit it by left sliding. Editing includes
modifying the alias and deleting the device.

Figure 8.1
Note:
1. Make sure you are installing the latest version of the software.
2. For details, please refer to the contents on http://server-cn.growatt.com.
3. There are two ways to register your mobile phone APP:
Method 1: Go to the mobile APP login page and click “One button to build a station”.
Scan the barcode to obtain the serial number of the collector, and complete the
registration by filling in the mobile phone number, password, agent number and other
information with one-click registration.
Method 2: Go to the mobile APP login page and click on “Register”.
Registration is required to fill in the information, with an * is required. After completing
the registration, you can log in to the main interface of ShinePhone. The registration
page and main interface are as shown below:

Add collector interface Collector list interface Add power station interface

Figure 8.3

Collector:
1>Add a collector to add multiple collectors under the specified power station name.
Way: click “+”on the top right corner to add datalogger( WiFi/GPRS etc) as 7.1.1
02(Note:
If add wifi datalogger will need to configure it manually, scan the wifi datalogger for 2
seconds until a window pops up, then choose configure datalogger, APP will get the WIFI
name , only need to input password and click set, around 30 seconds, the configuration
will be done successfully.
2>User can add datalogger at the datalogger list page to add a datalogger, edit, delete,
configure etc.
3>User can add more plants with the add Plant function.

Figure 8.2

31 32
2>Control: user set inverter on/off, set active power, set reactive power, set PF, set inverter
time, set grid voltage high, set grid voltage low. The operation password is:
inverter+date.
For example, if the date of the day is April 18, 2019, the password is inverter20190418.
3>Parameter interface: view the basic information such as the serial number, model,
voltage, current and power of the inverter.

Figure 8.4

Inverter Details Page:


1>Click on the inverter name to enter the details main interface, which contains
information about inverter power and power generation. Enter the control, log, edit,
and parameter interface by clicking the icon below the interface.
Figure 8.6

4>Data interface: View PV power, PV voltage, PV current, R phase power, S phase power,
T phase power and output power of the inverter, and view detailed monitoring data by
sliding up.
5>Log interface: View the fault information of the inverter.

Figure 8.5

Figure 8.7

33 34
8.1.2 Server WEB webpage remote monitoring(ShineGPRS-X) 2. Add Collector
On the Plant page, click on “device list”, “datalog”, “add data logger”, enter the SN
1. Register account number and verification code and save. datalogger will show after 5mins, also the device
Open browser, input server.growatt.com, click “New User” at login page, input the will come online.(The inverter is monitored by the collector, so the collector can be
necessary information then go back to login page, input the registered username and added)
password, click login.

Figure 8.9

Figure 8.8

35 36
3. View Plant and Inverter Information
A.Click on “Dashboard” to view related information such as “Day of Power Generation”, C.View detailed data
“Cumulative Power Generation”, “Today's revenue” and “Total revenue”. Click "Plant", "device list", "MAX/MID", and the inverter list of the power station is
displayed. Double-click on the inverter name in the list to display the detailed data of the
inverter. The data can be viewed by date or exported.

Figure 8.10

B.Click “plant”and “Plant data” to view the inverter power, voltage, current and other Figure 8.12
graphs.
The inverter can be set by clicking the "Settings" operation key. The operation is
performed by a professional, and the password is datalog+ current date.
For example, if the date of the day is July 21, 2019, the password is datalog20190721.

Figure 8.11
Figure 8.13

37 38
8.2 Local Data Monitoring
MAC series inverter local data monitoring can be realized by mobile phone APP, USB
connected U disk.

8.2.1 Mobile phone app (Shinephone) Local Monitoring


8.2.1.1 Log on to app for local monitoring
1>Method 1
When you open the app login front page ,click the local debugging tool, and you can get
the wifi name of the collector by scanning the QR code or barcode( The default
password for WIFI is 12345678. If you have already connected, you can click "Skip" to
connect directly to the WIFI.)

Figure 8.15

8.2.1.2 Local Monitoring and Debugging Use


When viewing local monitoring, you must keep the phone's wifi connected to the
collector's wifi to view local monitoring (to enter the local monitoring page, first click
auto refresh to get the latest data information. Electricity generation: the option to view
the latest generation, daily generation, monthly and annual generation of detailed
information; power: you can see the current power and rated power value; failure: can
read the equipment detailed fault information;
Note:Please ask the professional to operate above.
Figure 8.14
1.device control
Note:In addition to resetting the password to connect to the network, other WiFi
2>Method 2 modules that must connect to the collector can view information.
Open app enter user name and password click login, enter me (personal center). Click A.Reset password
the enter tool, find the local debugger to enter, and you can get the wifi name of the Need network connection login oss account to set up or modify the local debug
password;
collector by scanning the QR code or barcode(The default password for WIFI is
B.Setting configuration
12345678. If you have already connected, you can click "Skip" to connect directly to the
The configuration data of inverter, voltage, power and so on can be modified according
WIFI.) to the usage.

39 40
D.Intelligent detection
Detailed and accurate view of the device's detailed data and status .

Figure 8.16

C.Parameter configuration Figure 8.18


The parameter data of the equipment can be modified according to the usage .

E.Intelligent I-V curve scanning


Can remotely scan each mppt.

Figure 8.17

Figure 8.19

41 42
F.Fault recording detection H. One-click diagnosis
Remote, fast and accurate fault location. One-button detection of power plant environment, including I-V curve diagnosis, grid
waveform THDV and cable impedance detection.

2
1

Figure 8.20

G.Real-time recording detection


Inverter voltage and current quality can be observed in real time .

Figure 8.22
Figure 8.21

44
43
I.High level setting 2.Fault Recording
According to register address set parameters (professional operation). Create a BCONFIG.txt file under the root directory of the USB flash drive, write
"down_fault", insert the USB flash drive to read the fault recording information, and
J.Device Information store a total of 100 fault recording information in the root directory. The latest number is
Check PV voltage/current, string voltage/current, AC voltage/current/power/frequency, 0.
PID voltage/current, internal parameters, and detailed device detailed data information
about the device.

Figure 8.25

3.Curve Analysis
Create the bconfig.txt file under the root of the U disk, write the following content, the
insert U disk to record I-V curve, then generates a form under the files in the root
directory.

Figure 8.23

8.2.2 U Disk Monitoring


The local monitoring of U disk can realize the functions of software burning, fault
recording, curve analysis and real-time recording. Details are as follows:
1.Firmware Programming
Create the bconfig.txt file under the root of the U disk, write to the following content,
then insert the U disk to programming. Note the M3 program needs to be programming
at last time.

Figure 8.26

4.Real Time Recording


Create the bconfig.txt file under the root of the U disk, write the following content,
then insert
U disk to read real time recording information,then generates a form under the files in
the root directory,the form record's waveform is consistent with the ID of the command
setting.

Figure 8.24

45 46
System Maintenance 9
9.1 Routine Maintenance
9.1.1 Cleaning Inverter

● Before any operation, please disconnect the DC switch and AC


switch, and wait for at least 5 minutes until internal capacitance
DANGER discharge completely.

1>Check the ambient temperature and dust of the inverter, clean the inverter when
necessary.
2>Observe whether the air outlets is normal, when necessary, clean the air outlets or
clean the fan step by step, steps refer to 9.1.2
Figure 8.27

9.1.2 Fan Maintenance

●It must be carried out by qualified, trained personnel and comply with
all prevailing local code and regulations.
● Please disconnect the DC switch and AC switch before any operation,
and wait for at least 5 minutes until the internal bus capacitance
DANGER
discharge completely.

●Do not use the air pump cleaning fan, which may cause fan damage.
WARNING

When the Growatt Max series inverter work in high temperature environment, good
ventilation and heat dissipation can effectively reduce the chance of load derating .
Inverter equipped with internal cooling fans, when the internal temperature is too high,
the fans work in to reduce the internal temperature. When the inverter is derating
because of the internal temperature is too high, the following are the possible reasons or
solutions;
●Fan is blocked or the heat sink gathers too much dust, it needs to clean the fan, fan
cover or heat sink.
●Fan is damaged, it need to replace the fan.
●Poor ventilation of the installation location, it needs to select the appropriate
installation location according to the basic installation requirements.

Fan cleaning and replacement procedure.


1>Please ensure that the DC side and AC side of the inverter have been disconnected
before cleaning or replacement of the fan.
●Turn off DC switch.
●Disconnect DC terminals from inverter(Users need tools to disconnect the DC
connection terminals)
●Turn off AC switch;
2>Remove the screws on the fan guards with a cross screwdriver. it is shown as below

47 48
9.2.1 Warning
Warnings identify the current status of the inverter(Max), warnings do not related to a
fault and it does not affect the normal running of the inverter. When a warning with a
number after it appears in the display, it indicates a warning code and is usually cleared
through an orderly shutdown/re-set or a self-corrective action performed by the inverter.
See the warning code in the following table;

Warning
Description Suggestion
Message

Warning 1.After shutdown,Check the panel is normal.


String fault
200 2.If error message still exists, contact manufacturer.

Figure 9.1 Warning DC SPD function 1.After shutdown,Check the DC SPD.


202 abnormal 2.If error message still exists,contact manufacturer.
3>Disconnect the wire connector of the fans with a flat head screw driver and remove the
fans from the fan guards, it is shown as below. Warning 1.Check the PV1 or PV2 wiring is short-circuited.
PV Circuit short
203 2.If error message still exists,contact manufacturer.

Warning AC SPD function 1.After shutdown,Check the AC SPD.


206 abnormal 2.If error message still exists,contact manufacturer.

1.unplug the U disk


Warning U disk over-current
2.Re-access U disk after shutdown
207 protection
3.If the error message still exists, contact manufacturer.

1.After shutdown,Check the fan connection.


Warning Fan function
2.Replace the fan.
400 abnormal
3. If the error message still exists, contact manufacturer.

Figure 9.2
Warning 1.Check if the meter is on
4>Clean fan, fan guards and heat sink or replace fan.
Meter abnormal
401 2.Check the machine and the meter connection is normal
●Clean the fan and fan guards with air pump, brush or a damp cloth.
●Remove each fan separately for cleaning if necessary.
●Remove the fan that need to replace with a cross screwdriver, replace a new fan. Optimizer and
1. Check if the optimizer is on.
●Tidy up the wire. Warning inverter
2. Check whether the connection between the optimizer
402 communication is
and the inverter is normal
5>Install the fan, fan guard fixed and the inverter again. abnormal

Warning 1.Restart inverter.


EEPROM abnormal
404 2.If error message still exists,contact manufacturer.

9.2 Trouble Shooting DSP and COM


Warning 1.Check the firmware version.
firmware version
405 2.If error message still exists,contact manufacturer.
●Work on the Growatt Max must be carried out by qualified personnel. unmatch
●Normally grounded conductors may be ungrounded and energized
when a PV isolation low is indicated . Warning 1.Restart inverter
NTCBroken
DANGER ●Risk of electric shock 408 2.If error message still exists, contact manufacturer.

If the above suggestions do not work, please contact Growatt.

49 50
9.2.2 Error
Errors codes identify a possible equipment failure, fault or incorrect inverter setting or Output DC 1.Restart inverter.
Error 402
configuration, any or all attempts to correct or clear a fault must be performed by current too high 2.If error message still exists,contact manufacturer.
qualified personnel.
Typically, the error code can be cleared once the cause or fault is removed. 1.After shutdown,Check the output current is not
Some of error code as table shows below, may indicate a fatal error and require you to Output current balanced.
Error 403
contact the supplier or Growatt for help. unbalance 2.If the error message still exists, contact
manufacturer

Error Code Description Suggestion 1.Restart inverter.


Error 404 bus sample fault
2.If error message still exists,contact manufacturer.
1.After shutdown,Check the panel terminal.
2.Restart inverter. 1.Restart inverter.
Error 200 AFCI Fault Error 405 Relay fault
3.If error message still exists,contact 2.If error message still exists,contact manufacturer
manufacturer.
1.After shutdown,Check the temperature, normal
1.Restart inverter. NTC Temperature restart the inverter
Leakage current Error 408
Error 201 2.If error message still exists,contact too high 2.If the error message still exists, contact
too high manufacturer
manufacturer.

The DC input Bus voltage 1.Restart inverter.


1.Immediately disconnect the DC switch and Error 409
voltage is abnormal 2.If error message still exists,contact manufacturer.
check the voltage
Error 202 exceeding the
2:.If the fault code still exists after the normal
maximum 1.After shutdown,Check communication board
voltage is restored, contact manufacturer
tolerable value. Communication wiring
Error 411
fault 2. If the error message still exists, contact
1.After shutdown,Check if panel enclosure manufacturer
ground properly.
Error 203 PV Isolation Low
2.If error message still exists,contact 1.Restart inverter.
Error 413 IGBT drive fault
manufacturer 2.If error message still exists,contact manufacturer

1.Check grid voltage. Internal power


1.Restart inverter.
Error 300 AC V Outrange 2.If the error message still exists despite the grid Error 415 test fail(PV
2.If error message still exists,contact manufacturer
voltage being within the tolerable range, contact Power low)

1.After shutdown,Check AC wiring. Over current


1.Restart inverter.
Error 302 No AC Connection 2.If error message still exists,contact Error 416 protected by
2.If error message still exists,contact manufacturer.
manufacturer software

1.Check PE,to ensure that the PE line contact 1.After shutdown,Check the leakage current
good. GFCI Module module
Error 303 PE abnormal Error 420
2.If error message still exisits,contact damage 2 .If the error message still exists, contact
Manufacturer manufacturer

1.Restart inverter. sampling is 1.Restart inverter.


Error 304 AC F Outrange 2.If error message still exists,contact Error 422
inconsistent 2.If error message still exists,contact manufacturer
manufacturer.

51 52
Technical Data10
1.Restart inverter
Error 425 AFCI self-test fault 2.If error message still exists, contact
MAC MAC MAC MAC
manufacturer. Model 30KTL3-X LV 40KTL3-X LV 50KTL3-X LV 60KTL3-X LV

1.Restart inverter
PV Curr Sample
Error 426 2.If error message still exists, contact Input data
Fault
manufacturer.
Max.recommended PV 39000W 52000W 65000W 78000W
1.Restart inverter PV power(for module STC)
AC Curr Sample
Error 427 2.If error message still exists, contact
Fault 1100V
manufacturer. Max. DC voltage

Start voltage 250V

Nominal voltage 600V

MPP voltage range 200V-1000V

600V-850V
Full load MPP voltage

Max. input current per 37.5A/37.5A 37.5A/37.5A 50A/37.5A/ 50A/50A/


per MPP trackers /25A /37.5A 37.5A 50A

Max. short-circuit current 45A/45A/ 45A/45A/ 55A/55A/ 55A/55A/


per MPP trackers 45A 45A 55A 55A

No. of MPP trackers 3

No. of PV strings per 3/3/2 3/3/3 4/3/3 4/4/4


MPP trackers

Output Data(AC)

AC nominal power 30000W 40000W 50000W 60000W

Max. AC apparent power 33300VA 44400VA 55500VA 66600VA

Nominal AC voltage/range 230V/400V/340-440VAC

50/60 Hz
AC grid frequency/range 45~55Hz/55-65 Hz

43.5A(cos 58.0A(cos 72.5A(cos 87.0A(cos


φ=1) φ=1) φ=1) φ=1)
Max. output current
48.3A(cos 64.4A(cos 80.5A(cos 96.6A(cos
φ=0.9) φ=0.9) φ=0.9) φ=0.9)

53 54
Power factor(@nominal power) >0.99(0.8LG ...0.8LD) Operating temperature range –25°C ... +60°C (derating over 45°C)

THDi <3% Noise emission (typical) ≤60dB(A)

AC grid connection type 3W/N/PE Relative humidity 0~100%

Efficiency
Highest Altitude 4000m
Max. efficiency 98.80%
Self-Consumption night < 1W
MPPT efficiency 99.90%
Topology Transformerless
Protection devices
Cooling concept Fan cool
DC reverse polarity protection YES
Environmental Protection Rating Ip65
DC switch YES
Warranty: 5 years/10years(Option)
DC Surge protection YES(Class II)
Certificates and approvals
Insulation resistance monitoring YES
EN 61000-3, EN 61000-6, EN/IEC 62109-1, EN/IEC
RCD check (GFCI) YES Safety /EMC
62109-2,

AC short-circuit protection YES

AC surge protection YES(Class II)

Interfaces

Display OLED+LED/WIFI+APP

USB YES

Rs485 YES

WIFI Option

GPRS Option

4G Option

General Data

Dimensions (W / H / D) 680*508*281 mm

Weight 52kg

55 56
MAC MAC MAC MAC Power factor(@nominal power) >0.99(0.8LG ...0.8LD)
Model 50KTL3-X MV 60KTL3-X MV 66KTL3-X MV 70KTL3-X MV
THDi <3%

Input data AC grid connection type 3W/N/PE

Max.recommended PV 65000W 78000W 85800W 91000W Efficiency


PV power(for module STC)
Max. efficiency 98.80%
Max. DC voltage 1100V

MPPT efficiency 99.90%


Start voltage 250V
Protection devices
Nominal voltage 700V
DC reverse polarity protection YES

MPP voltage range 200V-1000V


DC switch YES
650V-850V
Full load MPP voltage DC Surge protection YES(Class II)

Max. input current per 50A/37.5A/ 50A/50A/ 50A/50A/ 50A/50A/ Insulation resistance monitoring YES
per MPP trackers 37.5A 50A 50A 50A
RCD check (GFCI) YES
Max. short-circuit current 55A/55A/ 55A/55A/ 55A/55A/ 55A/55A/
per MPP trackers 55A 55A 55A 55A
AC short-circuit protection YES

No. of MPP trackers 3


AC surge protection YES(Class II)

No. of PV strings per 4/3/3 4/4/4 4/4/4 4/4/4 Interfaces


MPP trackers
Display OLED+LED/WIFI+APP
Output Data(AC)
USB YES
AC nominal power 50000W 60000W 66000W 70000W
Rs485 YES
Max. AC apparent power 55500VA 66600VA 73300VA 77700VA
WIFI Option

Nominal AC voltage/range 277V/480V/425-540VAC


GPRS Option

50/60 Hz 4G Option
AC grid frequency/range 45~55Hz/55-65 Hz
General Data
60.2A(cos 72.2A(cos 79.4A(cos 84.2A(cos
φ=1) φ=1) φ=1) φ=1) Dimensions (W / H / D) 680*508*281 mm
Max. output current
66.9A(cos 80.2A(cos 88.2A(cos 93.6A(cos
φ=0.9) φ=0.9) φ=0.9) φ=0.9)
Weight 52kg

57 58
For Brazilian only
Operating temperature range –25°C ... +60°C (derating over 45°C)
MAC MAC MAC
Noise emission (typical) ≤60dB(A) Model 15KTL3-XL 20KTL3-XL 22KTL3-XL

Relative humidity 0~100%


Input data
Highest Altitude 4000m
Max.recommended PV 19500W 26000W 28600W
Self-Consumption night < 1W PV power(for module STC)

Max. DC voltage 1100V


Topology Transformerless

Start voltage 250V


Cooling concept Fan cool

Nominal voltage 360V


Environmental Protection Rating Ip65

MPP voltage range 200V-1000V


Warranty: 5 years/10years(Option)

No. of MPP trackers 3


Certificates and approvals

No. of PV strings per 4/4/4


EN 61000-3, EN 61000-6, EN/IEC 62109-1, EN/IEC MPP trackers
Safety /EMC
62109-2,

Max. short-circuit current 50A/50A/50A


per MPP trackers

Max. input current per 55A/55A/55A


per MPP trackers
Output Data(AC)

AC nominal power 15000W 20000W 22000W

16600kVA@ 22200kVA@ 24400kVA@


Max. AC apparent power 220VAC 220VAC 220VAC

Nominal AC voltage/range 127V/220V,101.6-139.7V

AC grid frequency/range 50/60 Hz,45~55Hz/55-65 Hz

Nominal output current 39.4A 52.5A 57.7A

Max. output current 46.3A 58.3A 64.0A

59 60
Power factor(@nominal power) >0.99(0.8LG ...0.8LD) Operating temperature range –25°C ... +60°C (derating over 45°C)

THDi <3% Noise emission (typical) ≤60dB(A)

AC grid connection type 3W/N/PE Relative humidity 0~100%

Efficiency
Highest Altitude 4000m
Max. efficiency 98.80%
Self-Consumption night < 1W
Euro efficiency 98.2% 98.2% 98.2%
Topology Transformerless
Protection devices
Cooling concept Fan cool
DC reverse polarity protection YES

Environmental Protection Rating Ip65


DC switch YES
Warranty: 5 years/10years(Option)
DC Surge protection YES(Class II)
Certificates and approvals
Insulation resistance monitoring YES

EN 61000-3, EN 61000-6, EN/IEC 62109-1, EN/IEC


RCD check (GFCI) YES Safety /EMC
62109-2,

AC short-circuit protection YES

AC surge protection YES(Class II)

Interfaces

Display OLED+LED/WIFI+APP

USB YES

Rs485 YES

WIFI Option

GPRS Option

4G Option

General Data

Dimensions (W / H / D) 680*508*281 mm

Weight 52kg

61 62
MAC MAC MAC Power factor(@nominal power) >0.99(0.8LG ...0.8LD)
Model 25KTL3-XL 30KTL3-XL 36KTL3-XL
THDi <3%

Input data AC grid connection type 3W/N/PE

Max.recommended PV 32500W 39000W 46800W Efficiency


PV power(for module STC)
Max. efficiency 98.80%
Max. DC voltage 1100V

Euro efficiency 98.2% 98.3% 98.5%


Start voltage 250V
Protection devices
Nominal voltage 360V
DC reverse polarity protection YES

MPP voltage range 200V-1000V


DC switch YES

No. of MPP trackers 3


DC Surge protection YES(Class II)
No. of PV strings per 4/4/4
MPP trackers Insulation resistance monitoring YES

RCD check (GFCI) YES


Max. short-circuit current 50A/50A/50A
per MPP trackers
AC short-circuit protection YES
Max. input current per 55A/55A/55A
per MPP trackers AC surge protection YES(Class II)

Output Data(AC)
Interfaces
AC nominal power 25000W 30000W 36000W Display OLED+LED/WIFI+APP

USB YES

36000kAV@
27800kVA@ 33300kVA@ Rs485 YES
220VAC
Max. AC apparent power 220VAC 220VAC
39200kVA@
240VAC WIFI Option

GPRS Option
Nominal AC voltage/range 127V/220V,101.6-139.7V
4G Option
AC grid frequency/range 50/60 Hz,45~55Hz/55-65 Hz
General Data
Nominal output current 65.6A 78.8A 94.5A
Dimensions (W / H / D) 680*508*281 mm

Max. output current 73.0A 87.4A 94.5A


Weight 52kg

63 64
Decommissioning 11
If the inverter does not operate in the future, it needs to be properly disposing. The steps
Operating temperature range –25°C ... +60°C (derating over 45°C) are as follows:
1>Disconnect the external AC short circuit and prevent reconnection due to
Noise emission (typical) ≤60dB(A) misoperation.
2>Turn the DC switch to "OFF" position.
Relative humidity 0~100% 3>Wait at least 5 minutes until the internal capacitor discharge is completed.
4>Disconnect the AC connector.
5>Disconnect DC connector.
Highest Altitude 4000m
6>Remove the inverter from the wall.
7>Disposing of the inverter.
Self-Consumption night < 1W

Topology Transformerless

Cooling concept Fan cool

Environmental Protection Rating Ip65


12 Quality assurance
Warranty: Please refer to related file.
5 years/10years(Option)

Certificates and approvals

EN 61000-3, EN 61000-6, EN/IEC 62109-1, EN/IEC


Safety /EMC
62109-2,

13 Contact
If you have technical problems concerning our products, contact your installer or
Growatt, please provide information below for better support.
1>Inverter type
2>Serial number of inverter
3>Error code of inverter
4>LED status of inverter
5>DC input voltage of inverter (Modules information)
6>Inverter communication method