Air System Sizing Summary for 2ND-AHU-01

Project Name: 479-16 Quran Memorization center AWQAF-20230129 02/15/2023


Prepared by: APG 08:57AM

Air System Information


Air System Name 2ND-AHU-01 Number of zones 3
Equipment Class CW AHU Floor Area 578.0 m²
Air System Type VAV Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 63.7 kW Load occurs at Jun 1600
Sensible coil load 56.5 kW OA DB / WB 45.1 / 29.9 °C
Coil L/s at Jun 1600 3180 L/s Entering DB / WB 24.3 / 15.6 °C
Max block L/s at Jul 1600 3533 L/s Leaving DB / WB 9.6 / 8.8 °C
Sum of peak zone L/s 3535 L/s Coil ADP 7.9 °C
Sensible heat ratio 0.887 Bypass Factor 0.100
m²/kW 9.1 Resulting RH 46 %
W/m² 110.2 Design supply temp. 12.0 °C
Water flow @ 5.6 °K rise 2.74 L/s Zone T-stat Check 3 of 3 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s at Jul 1600 3533 L/s Fan motor BHP n/a
Standard L/s 3528 L/s Fan motor kW 8.11 kW
Actual max L/(s-m²) 6.11 L/(s-m²)

Outdoor Ventilation Air Data


Design airflow L/s 610 L/s L/s/person 7.06 L/s/person
L/(s-m²) 1.06 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 2


Zone Sizing Summary for 2ND-AHU-01
Project Name: 479-16 Quran Memorization center AWQAF-20230129 02/15/2023
Prepared by: APG 08:57AM

Air System Information


Air System Name 2ND-AHU-01 Number of zones 3
Equipment Class CW AHU Floor Area 578.0 m²
Air System Type VAV Location Doha, Qatar

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
2-LOUNGE & SEATING AREA 31.2 2871 570 Jul 1600 7.3 418.0 6.87
2-CORRIDOR-2 01 4.3 400 40 Jun 1900 1.8 114.0 3.51
2-TOILET 4 3.0 194 2 Jul 1600 0.5 46.0 4.21

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
2-LOUNGE & SEATING AREA 12.8 0.27 0.0 0.00 0
2-CORRIDOR-2 01 2.1 0.05 0.0 0.00 0
2-TOILET 4 0.5 0.01 0.0 0.00 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
2-LOUNGE & SEATING AREA
2-LOUNGE & SEATING AREA 1 31.2 Jul 1600 2871 7.3 418.0 6.87
2-CORRIDOR-2 01
2-CORRIDOR-2 01 1 4.3 Jun 1900 400 1.8 114.0 3.51
2-TOILET 4
2-TOILET-4 1 3.0 Jul 1600 194 0.5 46.0 4.21

Hourly Analysis Program v4.90 Page 2 of 2