Schneider Electric - TeSys-D - LC1D50AM7

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Product datasheet

Specifications

TeSys D contactor - 3P(3 NO) -


AC-3 - <= 440 V 50 A - 220 V AC
50/60 Hz coil
LC1D50AM7

Main
Range TeSys
TeSys Deca

Range of product TeSys Deca

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
product or component type Contactor

Device short name LC1D

contactor application Resistive load


Motor control

Utilisation category AC-4


AC-1
AC-3
AC-3e

poles description 3P

[Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz


Power circuit: <= 300 V DC

[Ie] rated operational current 50 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
50 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

[Uc] control circuit voltage 220 V AC 50/60 Hz

Complementary
Motor power kW 15 kW at 220...230 V AC 50/60 Hz (AC-3)
22 kW at 380...400 V AC 50/60 Hz (AC-3)
30 kW at 500 V AC 50/60 Hz (AC-3)
33 kW at 660...690 V AC 50/60 Hz (AC-3)
25 kW at 415 V AC 50/60 Hz (AC-3)
30 kW at 440 V AC 50/60 Hz (AC-3)
11 kW at 400 V AC 50/60 Hz (AC-4)
15 kW at 220...230 V AC 50/60 Hz (AC-3e)
22 kW at 380...400 V AC 50/60 Hz (AC-3e)
30 kW at 500 V AC 50/60 Hz (AC-3e)
33 kW at 660...690 V AC 50/60 Hz (AC-3e)
25 kW at 415 V AC 50/60 Hz (AC-3e)
30 kW at 440 V AC 50/60 Hz (AC-3e)

Motor power hp 3 hp at 115 V AC 50/60 Hz for 1 phase motors


7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
15 hp at 200/208 V AC 50/60 Hz for 3 phases motors
15 hp at 230/240 V AC 50/60 Hz for 3 phases motors
40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
40 hp at 575/600 V AC 50/60 Hz for 3 phases motors

Compatibility code LC1D

Pole contact composition 3 NO

Protective cover With

[Ith] conventional free air thermal 10 A (at 60 °C) for signalling circuit
current 80 A (at 60 °C) for power circuit

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Jul 15, 2024 1


Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
900 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity 900 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand 400 A 40 °C - 10 s for power circuit


current 810 A 40 °C - 1 s for power circuit
84 A 40 °C - 10 min for power circuit
208 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit

Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1


100 A gG at <= 690 V coordination type 1 for power circuit
100 A gG at <= 690 V coordination type 2 for power circuit

Average impedance 1.5 mOhm - Ith 80 A 50 Hz for power circuit

Power dissipation per pole 3.7 W AC-3


9.6 W AC-1
3.7 W AC-3e

[Ui] rated insulation voltage Power circuit: 600 V CSA certified


Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage category III

Pollution degree 3

[Uimp] rated impulse withstand 6 kV conforming to IEC 60947


voltage
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO
13849-1

Mechanical durability 6 Mcycles

Electrical durability 1.45 Mcycles 50 A AC-3 at Ue <= 440 V


1.1 Mcycles 80 A AC-1 at Ue <= 440 V
1.45 Mcycles 50 A AC-3e at Ue <= 440 V

Control circuit type AC at 50/60 Hz standard

Coil technology Without built-in suppressor module

Control circuit voltage limits 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz


0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz

Inrush power in VA 140 VA 60 Hz cos phi 0.75 (at 20 °C)


160 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA 13 VA 60 Hz cos phi 0.3 (at 20 °C)


15 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation 4…5 W at 50/60 Hz

Operating time 4...19 ms opening


12...26 ms closing

Maximum operating rate 3600 cyc/h 60 °C

2 Jul 15, 2024


Connections - terminals Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with
cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without
cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without
cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable
end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without
cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without
cable end
Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible
without cable end
Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible
without cable end
Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible
with cable end
Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible
with cable end
Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: solid
without cable end
Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: solid
without cable end

Tightening torque Control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver flat Ø
6 mm
Control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver
Philips No 2
Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25…35 mm²
hexagonal screw head 4 mm
Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm²
hexagonal screw head 4 mm
Control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver
pozidriv No 2
Power circuit: 2.5 N.m - on EverLink BTR screw connectors - with screwdriver
pozidriv No 2

Auxiliary contact composition 1 NO + 1 NC

Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1


type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency 25...400 Hz

Minimum switching voltage 17 V for signalling circuit

Minimum switching current 5 mA for signalling circuit

Insulation resistance > 10 MOhm for signalling circuit

Non-overlap time 1.5 ms on de-energisation between NC and NO contact


1.5 ms on energisation between NC and NO contact

mounting support Plate


Rail

Environment
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1

Product certifications RINA


DNV
CSA
GOST
BV
GL
UL
CCC
LROS (Lloyds register of shipping)

IP degree of protection IP20 front face conforming to IEC 60529

Jul 15, 2024 3


Protective treatment TH conforming to IEC 60068-2-30

Climatic withstand conforming to IACS E10 exposure to damp heat


conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Permissible ambient air -40…60 °C


temperature around the device 60…70 °C with derating

Operating altitude 0...3000 m

Fire resistance 850 °C conforming to IEC 60695-2-1

Flame retardance V1 conforming to UL 94

Mechanical robustness Vibrations contactor open (2 Gn, 5...300 Hz)


Vibrations contactor closed (4 Gn, 5...300 Hz)
Shocks contactor closed (15 Gn for 11 ms)
Shocks contactor open (10 Gn for 11 ms)

Height 122 mm

Width 55 mm

Depth 120 mm

net weight 0.855 kg

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 6.2 cm

Package 1 Width 13.5 cm

Package 1 Length 15.2 cm

Package 1 Weight 916.0 g

Unit Type of Package 2 S02

Number of Units in Package 2 10

Package 2 Height 15.0 cm

Package 2 Width 30.0 cm

Package 2 Length 40.0 cm

Package 2 Weight 9.93 kg

Unit Type of Package 3 P06

Number of Units in Package 3 160

Package 3 Height 77.0 cm

Package 3 Width 80.0 cm

Package 3 Length 60.0 cm

Package 3 Weight 165.698 kg

Contractual warranty
Warranty 18 months

4 Jul 15, 2024


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Reach Free Of Svhc

 Toxic Heavy Metal Free

 Mercury Free

 Rohs Exemption Information Yes

 Pvc Free

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant

EU RoHS Declaration

China Rohs Regulation China RoHS declaration


Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

Jul 15, 2024 5


Product datasheet LC1D50AM7

Dimensions Drawings

Dimensions

(1) Minimum electrical clearance

LC1 D40A…D65A

a 55

with LA4 D●2 –

with LA4 DB3 or LAD 4BB3 136


b1
with LA4 DF, DT 157

with LA4 DM, DW, DL 166

without cover or add-on blocks 118


c
with cover, without add-on blocks 120

with LAD N (1 contact) –


c1
with LAD N or C (2 or 4 contacts) 150

c2 with LA6 DK10, LAD 6DK 163

with LAD T, R, S 171


c3
with LAD T, R, S and sealing cover 175

6 Jul 15, 2024


Product datasheet LC1D50AM7

Connections and Schema

Wiring

Jul 15, 2024 7

You might also like