Data sheet 3RB2036-1UB0

Overload relay 12.5...50 A For motor protection Size S2, Class 10


Contactor mounting Main circuit: Screw terminal Auxiliary circuit:
Screw terminal Manual-Automatic-Reset !!! Phased-out product !!!
Successor is SIRIUS 3RB3 Preferred successor type is >>3RB3036-
1UB0<<

Product brand name SIRIUS


Product designation solid-state overload relay

General technical data


Size of contactor can be combined company-specific S2
Power loss [W] for rated value of the current
● at AC in hot operating state 0.05 W
● at AC in hot operating state per pole 0.02 W
Insulation voltage
● with degree of pollution 3 at AC rated value 690 V
Surge voltage resistance rated value 6 kV
Protection class IP
● on the front IP00
Shock resistance 15g / 11 ms
Type of protection PTB 06 ATEX 3001 Ex II (2) GD
Reference code acc. to DIN EN 81346-2 F

Ambient conditions
Installation altitude at height above sea level
● maximum 2 000 m

3RB2036-1UB0 Subject to change without notice


Page 1/5 06/09/2020 © Copyright Siemens
Ambient temperature
● during operation -25 ... +60 °C
● during storage -40 ... +80 °C
● during transport -40 ... +80 °C
Relative humidity during operation 100 %

Main circuit
Number of poles for main current circuit 3
Adjustable pick-up value current of the current- 12.5 ... 50 A
dependent overload release
Operating voltage
● at AC-3 rated value maximum 690 V

Auxiliary circuit
Number of NC contacts for auxiliary contacts 1
Number of NO contacts for auxiliary contacts 1
Number of CO contacts
● for auxiliary contacts 0
Operating current of auxiliary contacts at AC-15
● at 24 V 4A
● at 110 V 4A
● at 120 V 4A
● at 125 V 4A
● at 230 V 3A
Operating current of auxiliary contacts at DC-13
● at 24 V 2A
● at 60 V 0.55 A
● at 110 V 0.3 A
● at 125 V 0.3 A
● at 220 V 0.11 A

Protective and monitoring functions


Trip class CLASS 10E

Short-circuit protection
Design of the fuse link
● for short-circuit protection of the auxiliary switch fuse gL/gG: 6 A
required

Installation/ mounting/ dimensions


Mounting position any
Mounting type Contactor mounting
Height 92 mm
Width 55 mm
Depth 109 mm
Required spacing

3RB2036-1UB0 Subject to change without notice


Page 2/5 06/09/2020 © Copyright Siemens
● with side-by-side mounting
— forwards 0 mm
— Backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 0 mm
● for grounded parts
— forwards 0 mm
— Backwards 0 mm
— upwards 0 mm
— at the side 6 mm
— downwards 0 mm
● for live parts
— forwards 0 mm
— Backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 6 mm

Connections/ Terminals
Product function
● removable terminal for auxiliary and control Yes
circuit
Type of electrical connection
● for main current circuit screw-type terminals
● for auxiliary and control current circuit screw-type terminals
Type of connectable conductor cross-sections
● for main contacts
— solid 2x (1 ... 16 mm²)
— stranded 2x (max. 25 mm²), 1 ... 35 mm²
— finely stranded with core end processing 2x (1 ... 16 mm²), 1 ... 25 mm²
● at AWG conductors for main contacts 2 x (max. 4), 1 x (18 ... 2)
Type of connectable conductor cross-sections
● for auxiliary contacts
— solid 0.5 ... 4 mm², 2x (0.5 ... 2.5 mm²)
— finely stranded with core end processing 0.5 ... 2.5 mm², 2x (0.5 ... 1.5 mm²)
● at AWG conductors for auxiliary contacts 2x (20 ... 14)

Electromagnetic compatibility
Conducted interference
● due to burst acc. to IEC 61000-4-4 2 kV (power ports), 1 kV (signal ports) corresponds to degree of
severity 3

3RB2036-1UB0 Subject to change without notice


Page 3/5 06/09/2020 © Copyright Siemens
● due to conductor-earth surge acc. to IEC 2 kV (line to earth) corresponds to degree of severity 3
61000-4-5
● due to conductor-conductor surge acc. to IEC 1 kV (line to line) corresponds to degree of severity 3
61000-4-5
Field-bound parasitic coupling acc. to IEC 61000-4-3 10 V/m
Electrostatic discharge acc. to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge

Certificates/ approvals
General Product Approval EMC For use in haz-
ardous loca-
tions

Declaration of Conformity Test Certificates Marine / Shipping


Miscellaneous Type Test Certific- Special Test Certi-
ates/Test Report ficate

Marine / Shipping other


Miscellaneous Confirmation

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RB2036-1UB0
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RB2036-1UB0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RB2036-1UB0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RB2036-1UB0&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RB2036-1UB0/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RB2036-1UB0&objecttype=14&gridview=view1

3RB2036-1UB0 Subject to change without notice


Page 4/5 06/09/2020 © Copyright Siemens
18 9 56

57
92
76

5 21
54 104

last modified: 06/08/2020

3RB2036-1UB0 Subject to change without notice


Page 5/5 06/09/2020 © Copyright Siemens

You might also like