This manual provides the installation, operation and troubleshooting of this unit, please read this manual LOGIN
Target Group
For qualified persons and end users. Qualified persons and end users must have the following skills:
Cellcronic Server
Knowledge about this unit operation Solar Panel
Training in deal with the security issues associated with installations and electrical safety
Before using the unit, read all instructions and cautionary marking on the unit. Any damage caused by
inappropriate operation is not warranted by Cellcronic.
Generator
All the electrical installation must comply with the local electrical safety standards.
Battery
Do not disassemble the unit. Take it to a qualified service center when service or repair is required,
incorrect re-assembly may result in a risk of electric shock or fire. Do not open inverter cover or change ULTRA series is a multifunctional, high frequency pure sine wave on grid solar inverter, features:
any components without cellcronic's authorization, otherwise the warranty commitment for the inverter
will be invalid. Applicable for pure off grid/ backup power / self-consumption / on grid situation
To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning, Integrated with 2 MPPT solar charge controllers, MPPT ranges 120V~385V
turning off the unit will not reduce this risk. Rated power 5KW, power factor 1
CAUTION-To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries and Be able to run with or without battery in ongrid and offgrid mode
lithium batteries, other types of batteries may burst, causing personal injury and damage. With separated generator input interface, able to control generator remotely
NEVER charge a frozen battery. Solar and utility grid can power loads at the same time
For optimum operation of this unit, please follow required spec to select appropriate cable size and breaker. With integrated advanced parallel function, up to 10pcs max paralleling
Please strictly follow installation procedure when you want to disconnect AC or DC terminals, please refer Support CAN/RS485 for Li-ion battery BMS communication
to INSTALLATION section of this manual for the details.
WIFI/ GPRS remote monitoring , setting and firmware update, support website, free IOS/Android APP
GROUNDING INSTRUCTIONS -This unit should be connected to a permanent grounded wiring system,
be sure to comply with local requirements and regulation to install this inverter.
NEVER cause AC output and DC input short circuited. Do not connect to the mains when
DC input short circuits.
01 02
1.2 Interface of the inverter 1.3 Packing List
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged.
You should have received the following items in the package:
LCD display
b) The storage temperature should be within -25~60 and humidity within 0~85%.
d) Do not directly exposed the inverter and its packaging to sunshine, raindrops and keep away
from corrosion.
MPPT485 WIFI
Li-ion
CAN/RS485 Dry Port GEN
NTC
No2 COM2 Nc2 No1 COM1 Nc1
ON ON
03 04
2. Installation 2. AC connection: Please install a separate AC breaker between inverter and AC input power source,
inverter and AC output load. This will ensure the inverter can be securely disconnected during maintenance
and fully protected from over current of AC input. The recommended spec of AC breaker is 32A.
2.1 Preparation Recommended AC input/ AC output /GEN cable size for each inverter.
L QF 1
ULTRA 5000W 1x12AWG 4 1.2 Nm
GEN N G
BAT PV Generater 4. Before connecting all wiring, please take off bottom cover by removing 3 screws as shown below.
600V, 4*12AWG
MAX:140A
QF 3 QF 1 In≥63A
QF 2 In≥63A
QF 3 In≥140A
QF 2 is Double interlock switch or Dual Power Switch In≥63A
1. Battery connection: For safety operation and regulation compliance, it's requested to install a separate
DC over-current protector or disconnect device between battery and inverter. The recommend battery
capacity is 150AH-200AH, the recommended spec of DC breaker is 150A/60V. Recommended battery cable
and terminal size:
Ring Terminal
Maximum Battery Torque value
Model Amperage capacity Wire Size Dimensions
Cable
mm2 D (mm) L (mm)
ULTRA 1*2AWG 38 6.4 39.2
5000W 110A 200AH 2~ 3 Nm
2*6AWG 28 6.4 33.2
05 06
2.2 Mounting the Unit 2.3 Battery Connection
Notice: Consider the following points before selecting where to install:
Mount on a solid surface
2.3.1 Battery Power Cable Connection
Do not mount the inverter on flammable construction materials. Note: for lead acid battery, the recommended charge current is 0.2C( C to battery capacity)
For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 1. Please follow below steps to implement battery connection:
50 cm above and below the unit.
2. Assemble battery ring terminal based on recommended battery cable and terminal size.
The ambient temperature should be between 0°C and 55°C to ensure optimal operation. 3. Connect all battery packs as units requires. It's suggested to connect at least 200Ah capacity battery
for ULTRA5000WPV.
The recommended installation position is to be adhered to the wall vertically.
4. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts
Steps to mounting the unit are tightened with torque of 2 ~3Nm. Make sure polarity of the battery is correctly connected and ring
Step1. Use the wall-mounting bracket as the template to mark the position of the 4 holes, then drill 8 mm terminals are tightly screwed to the battery terminals.
holes and make sure the depth of the holes is deeper than 50mm.
Step2. Install the expansion tubes into the holes and tight them, then use the expansion screws (packaged 2.3.2 Lithium Battery Connection
together with the expansion tubes) to install and fix the wall-mounting bracket on the wall.
If choosing lithium battery for ULTRA5000W PV, please make sure the battery BMS is compatible with
Step3. Install the inverter on the wall-mounting bracket and lock the inverter using the security screws. Cellcornicinverter. Please check thecompatible list in thecellcronicwebsite.
2. Connect the CAN or RS485 communication cable between inverter and battery. If you do not get
the communication cable from inverter manufacturer or battery manufacturer, please make the cable
519 mm
Inverter
200mm 200mm
MPPT485
Battery Pack
NTC
Parallel
500mm
07 08
2.4 AC Input/Output Connection 2.5 PV Connection
Please follow below steps to implement PV module connection:
CAUTION!! 1. Remove insulation sleeve 10 mm for positive and negative conductors.
- There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and
2. Check correct polarity of connection cable from PV modules and PV input connectors.
output connectors.
3. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative
- Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may
pole (-) of connection cable to negative pole (-) of PV input connector.
cause utility short-circuited when these inverters are worked in parallel operation.
4. Make sure the wires are securely connected.
5. Finally, after connecting all wiring, please put bottom cover back by screwing two screws as shown below.
Please follow below steps to implement AC input/output connection:
2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws.
Be sure to connect PE protective conductor first.
4. Insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
Be sure to connect PE protective conductor first. PVA+ PVA- PVB+ PVB- L N PE L N PE L N
AC INPUT AC OUTPUT GEN
BAT+ BAT-
5. Make sure the wires are securely connected.
10
Ground (yellow-green)
3
L→LINE (brown or black)
10
N→Neutral (blue)
3
2.6 Generator Connection
L→LINE (brown or black) N→Neutral (blue)
3. Insert L and N wires according to polarities indicated on terminal block and tighten the terminal screws
09 10
All cellcronic units can work with generator.
2.7 Dry Contact Signal control
Users can connect the generator output to off grid inverters. GEN input terminal.
The Dry port(NO2,COM2,NC2) could be used to deliver signal to external device when battery voltage
The generator will be automatically started when battery voltage is lower than the cut-off value or there is charge reaches warning level. The GEN port(NO1,COM1,NC1) could be used to wake-up the Generator and
request from BMS. When voltage is higher than AC charge setting value, it will stop the generator then the generator can charge the battery.
Battery will get charged when the generator is turned on, and the generator is bypassed to AC output to Dry port GEN Dry port GEN
take all loads . NO2 COM2 NC2 NO1 COM1 NC1 NO2 COM2 NC2 NO1 COM1 NC1
NO2 & COM2 NC2 & COM2 NO1 & COM1 NC1 & COM1
Power Off Inverter is off and no output is powered. Open Close Open Close
MPPT485 WIFI
N
Li-ion
CAN/RS485 Dry Port GEN
L Battery voltage < Low DC
NTC
No2 COM2 Nc2 No1 COM1 Nc1
Close Open Close Open
warning voltage
Parallel BAT+ BAT- PVA PVB AC INPUT AC OUTPUT GEN
OFF OFF
Without Grid
ON ON
In≥63A Battery voltage > Setting value or
EPS Output Power Open Close Open Close
battery charging reaches floating stage
Power On Battery voltage < Low DC
PE
Close Open Open Close
N warning voltage
In≥140A With Grid
Battery voltage > Setting value or
N Open Close Open Close
L L HOUSE Essential LOAD battery charging reaches floating stage
N L
PE 2.8 Parallel function
N
BATTERY L ULTRA series inverter support upto10 units to composed single phase parallel system or three phase
In≥63A parallel system, for parallel system setup
Grid Step1. Cable connection: the system connection is as below:
Inverter 1
L AC Grid Bus-Bar(L,N)
The system will use AC first if there is both utility input and generator input.
PV AC Input N
PE
CAN 1 L AC
CAN 2 AC Output N
Parallel line 1 PE
BAT
DC
EPS Bus-Bar(L,N)
Inverter 2 AC Input
Parallel line 3 L AC Grid Bus-Bar(L,N)
PV N
AC Input PE Grid
PE
CAN 1 L AC
CAN 2 N
AC Output
Parallel line 2 PE
BAT
DC
Inverter 3
L AC
PV AC Input N
PE AC Output
CAN 1 L AC EPS Bus-Bar(L,N)
CAN 2 AC Output N
PE PE EPS LOAD
BAT
DC
11 12
Inverter 1 Phase L1 Step3. Setup the monitor for the system, add all datalogs in one station. Users can login to the visit interface of
L AC
Grid or Generater monitor system, Configuration->station->Plant Management->add datalog to add the datalogs.
PV AC Input N
PE
Phase L1
CAN 1 L AC Monitor Data Overview Maintain Aspergo User Center
DC Datalogs Plant name Installer End User Country Timezone Daylight saving time Create date Action
L AC Phase L2
CAN 1
CAN 2 AC Output
N EPS Step4. Enable share battery for the system if the system share one battery bank, otherwise disable the
Parallel line 2 PE
BAT shared battery function
DC
Step5. Set the system as a parallel group in the monitor system
Inverter 3 Phase L3
L AC Stations Overview Search by inverter SN
Grid or Generater Station Name
PV AC Input
N
PE Device Overview
AC Phase L3 Serial number Status Solar Power Charge Power Discharge Pow Load Solar Yielding Battery Dischar Feed Energy Consumption E Plant name Parallel Action
CAN 1 L
1 0272011008 Normal 228 W 42 W 0W 182 W 215.3 kWh 39.6 kWh 0 kWh 551.2 kWh Dragonview A-1 Parallel
CAN 2 N EPS
AC Output
PE 2 0272011011 35 W 32 W 0W 0W 158.7 kWh 21.1 kWh 0 kWh 160.5 kWh Dragonview A-2 Parallel
BAT
3 0272011012 1 kW 129 W 0W 1 kW 170.3 kWh 49.9 kWh 0 kWh 434.5 kWh Dragonview A-3 Parallel
DC
4 0272011017 79 W 48 W 0W 106 W 99 kWh 85.6 kWh 0 kWh 257.1 kWh Dragonview A-4 Parallel
MPPT485 WIFI
Parallel line(n to 1)
Parallel BAT+ BAT- PVA PVB AC INPUT AC OUTPUT GEN
The max parallel quantity is 10, so 2<n<10 OFF OFF
ON ON
15 16
3.2 Working Modes related setting description
Situation Setting 1 Setting 2 Setting 3 Working modes and Description
Bypass Mode
In the AC first time NA
AC will take the load and Solar is used to charge battery
17 18
1.ULTRA can work as traditional off grid inverteror as ahybrid inverter. When disable PV&AC 3.1 AC First: During this setting time, system will use AC to take load, use solar power to charge the battery
Take load Jointly, it will work as a traditional off grid inverter, otherwise it will work as a hybrid first. If there is extra solar power, extra solar power will take the load. When out of the setting time, system
Hybrid Setting
will use solar and battery to take load first until the battery voltage/SOC is lower than On Grid EOD settings,
PV&AC Take Load Jointly Enable Disable Discharge Current Limit 300 Set then it will use AC to take the load.
Export to Grid Enable Disable Export Power Percent(%) 0 Set Discharge Setting
Discharge Control According to SC Set
Application Setting Discharge Cut-off Voltage 45 Set Discharge Cut-off SOC 15 Set
AC First
AC first Start Time 1 00 : 00 Set AC first Start Time 2 14 : 30 Set AC first Start Time 3 16 : 30 Set
3.2 Export to Grid/Export Power percent: Users can also enable export function, it is allowed and set export
AC first End Time 1 12 : 00 Set AC first End Time 2 15 : 00 Set AC first End Time 3 16 : 40 Set
power percent
AC Charge
Discharge Setting AC Charge Start Battery Voltage(V) 46.4 Set AC Charge End Battery Voltage(V) 48 Set
Discharge Control According to SC Set AC Charge Start Battery SOC(%) 20 Set AC Charge End Battery SOC(%) 100 Set
Battery Warning Recovery Voltage 46 Set Battery Warning Recovery SOC 60 Set 3.3 AC Charge function Disable: The system will not use AC to charge the battery(except Li ion BMS set
force charge flag )
Discharge Cut-off Voltage 45 Set Discharge Cut-off SOC 15 Set
According to Time: During the setting time, system will use AC to charge the battery until battery full and
On Grid EOD Voltage(V) 56 Set On Grid EOD SOC(%) 30 Set battery will not discharge during the setting time.
According to Battery Voltage: During the setting time, system will use AC to charge the battery if battery
3. Working as a hybrid inverter voltage is lower than AC Charge Start Battery Voltage and will stop when Voltage is higher than AC Charge
Related settings End Battery Voltage. And battery will not discharge during the setting time.
According to Battery SOC: During the setting time, system will use AC to charge the battery if battery SOC
Application Setting
is lower than AC Charge Start Battery SOC and will stop when Voltage is higher than AC Charge End Battery
EPS Voltage Set(V) 230 Set EPS Frequency Set(Hz) 50 Set
SOC. And battery will not discharge during the setting time.
AC Input Range 0: APL(Utility Range90 Set
AC First
AC first Start Time 1 00 : 00 Set AC first Start Time 2 14 : 30 Set AC first Start Time 3 16 : 30 Set
AC first End Time 1 12 : 00 Set AC first End Time 2 15 : 00 Set AC first End Time 3 16 : 40 Set
19 20
4. LCD display and settings No. Description Remarks
4.1 LED Display This area will display the currently time/date by default(year/
month/day/ hour/minute” switching automatically). When press
Generally Information Up or Down buttons, this area will display the firmware version
1
Display Area information, serial number etc. Display the setting selection
LED Indicator Messages
information when entering settings
UPS/EPS output When UPS function is enabled, this area will display UPS voltage,
5
information and data frequency, power etc. in turns of periods of 1s
4.2 LCD Display When firmware updating in process, it will display relevant
Programming & the percentage
6 information When in grid off, this area will display the
of AC output power
Percentage of the maximum AC output power
7 Loads consumption Display the power consumption by the loads in on grid model
21 22
4.3 Inverter Status Display 4.4 LCD Settings
Setting Year/Month/day
Default: S
S: two independent
Strings input
2 PV input mode
P:Same string input
for 2 MPPTs
23 24
Run with No Battery:
Step1:Choose battery type first, when no flashing,
select Enter to choose Run with No battery
Setting range:
For Lead Acid: ConChr: 50.0-59.0Vdc
Step1:Choose battery type first, when Lead-Acid CV voltage setting Default: 56.4V
7
flashing, select Enter to choose Lead-acid battery (Only in Lead-acid
battery type)
3 Battery Step2:Then choose battery capacity
Setting Range:
Totoal charge current setting VOLT/SOC
Ic: Maximum Setting range :10A~140A
TEOd:
charge current Default: 110A 10
Discharge control
6 (utility charge type: VOLT/SOC
current + solar
charge current)
25 26
AC charge setting
(The setting process AC Charge function:
Setting range:
must enable the AC Disable(Default)
VOLT: 40.0-OnGrid EOD Volt
charging function, Enable
Default: 42V
confirm the full (Touch “Enter” button to
CutOFF: battery SOC value, set ac charge parameter )
Cut off Voltage and set the
11 or SOC, depend
SOC: 0-OnGrid EOD SOC confirmation time
on TEOd period 1, 2, 3 to
Default: 15%
truly complete the
AC charging
function setting)
14
start
16 Hybrid enable/
AcIn: AC voltage
13 disable
range setting AC Output voltage range :
170Vac~280Vac
Hybrid Enable
27 28
Setting Range:
Setting Range: Green Function Disable
Feed-In Disable (default) (default)
Feed-In
Enable/disable Green Function
Only valid when 20 enable/disable
Hybrid is enabled Feed-In Enable Green Function Enable
16
Parallel type setting
Maximum Feed-In Setting Range: NoPL
Setting Range:0-100%
percent Only valid (not Parallel)/1PH (Single
0% (default)
when Feed-In is phase)/3PH (Three phase)
enabled Power NoPL (default)
percent can be set
21 Parallel setting
larger than 100%
in case of there is
other generating
device in the
system
Setting Range:0-7369W
7369W (default)
Error Record
18 Max Generator ->Record Index
Input Power Power ->>Record Msg:
(Year: Month:Day;
Hour: Min:Sec; Error code)
22 Error/Alarm
Setting Range: Record
PV Off Grid Enable (default)
Alarm Record
->Record Index
19 PV Off Grid
->>Record Msg:
enable/disable
PV Off Grid Disable (Year:Month:Day; Hour:Min:Sec; Alarm code)
29 30
5. Monitor System for Off grid 6. Specifications
Users can use wifi dongle / WLAN dongle / 4G dongle (Avaiblable from 2021 March for some countries) to
monitor theenergystorage system, The monitor website is: www.cellcronic.com Table 1 Line Mode Specifications
The APP is also available in the google play and apple APP store(Scan two code bar to download the APP).
INVERTER MODEL ULTRA 5000W - 48V
Please download the introduction of guidance by website: https//www.cellcornic.com
Document Reference: Input Voltage Waveform Sinusoidal (utility or generator)
0W Notice
Table 2 Inverter Mode Specifications
0W PV Power
Battery Power
0W Rated Output Power 5KVA/5KW
Low DC Warning Voltage 20% ≤ load < 50% Warning Voltage @load < 20% -1.2V Charging Curve
load ≥ 50% Cut-off Voltage @load < 20% -3.6V MPPT Solar Charging Mode
33 34
7. Trouble Shooting & Error List
The failures mainly divided into 5 categories, for each category, the behavior is different:
E000 Internal communication fault1 Restart inverter, if the error still exist, contact us (DSP&M3) Check if you have choose the right battery brand and
Communication failure
W000 communication cable is right, if the warning still exist,
E002 Bat On Mos Fail Restart inverter, if the error still exist, contact us (DSP&M3) with battery
contact us
E003 CT Fail Restart inverter, if the error still exist, contact us (DSP&M3)
Check battery temperature sensor is right connected
W001 Battery temperature high
CAN communication error Check CAN cable connection is connected to the right and the battery temperature is not too high
E008
in Parallel System COM port
W002 Battery temperature low Check battery temperature sensor is right connected
Check parallel setting for master/Slave part, and the battery temperature is not too low
E009 No master in parallel system
there should be one master in the system
Inverter get battery fault info from battery BMS,
W004 Battery failure restart battery, if the warning still exist,
Check parallel setting for master/Slave part,
E010 Multi master in parallel system contact us or battery manufacture
there should be one master in the system
W008 Software mismatch Please contact cellcronicfor firmwareupdate
Check if AC Connection is same for all inverters in
E011 AC inconsistent in parallel system
parallel system W009 Fan Stuck Check if the fan is OK
Check if the load is short circuit, try to turn off the load W012 Bat On Mos Restart inverter, if the error still exist, contact us
E012 Off grid output short circuit
and restart inverter
W013 Over temperature The temperature is a little bit high inside inverter
E013 UPS reserve current Restart inverter, if the error still exist, contact us
W018 AC Frequency out of range Check AC frequency is in range
Phase Error in three phase Check if the AC connection is right for three phase system,
E015 W025 Battery voltage high Check if battery voltage is in normal range
parallel system there should one at least one inverter in each phase
Check if battery voltage is in normal range, need to
E016 Relay fault Restart inverter, if the error still exist, contact us W026 Battery voltage low
charge the battery if battery voltage is low
E017 Internal communication fault2 Restart inverter, if the error still exist, contact us (DSP&M8)
Check if there is output from the battery and battery
W027 Battery open
E018 Internal communication fault3 Restart inverter, if the error still exist, contact us (DSP&M3) connection with inverter is OK
E019 Bus voltage high Check if PV input voltage is higher than 480V W028 EPS Over load Check if EPS load is too high
E020 EPS connection fault Check if EPS and AC connection is in wrong terminal W029 EPS voltage high Restart inverter, if the error still exist, contact us
Check PV input connection and if PV input voltage is W031 EPS DCV high Restart inverter, if the error still exist, contact us
E021 PV voltage high
higher than 480V
E022 Over current internal Restart inverter, if the error still exist, contact us
E026 Internal Fault Restart inverter, if the error still exist, contact us (Bus sample)
E031 Internal communication fault4 Restart inverter, if the error still exist, contact us (DSP&M8)